A. Using a 1/2" wrench, unscrew the four (4) hex-head
bolts (B) that secure the strainer.
B. Clean any debris (scale, rust, etc.) from strainer.
Replace if debris cannot be removed.
C. Re-install strainer.
Series 51-S/53
Removal of strainer for inspection and cleaning
Boiler is getting too much water.
a) Cause: The valve is not shutting off.
Test: Perform broken union test.
Solution:
• Series 51 Feeders Only: Remove and inspect
cartridge. Clean or replace as necessary.
• Series 51-S and 53 Feeders Only: There may be
debris lodged in the valve preventing it from closing
completely. Remove and clean valve assembly.
Replace if necessary.
b) Cause: By-pass valve is leaking.
Test: Perform broken union test.
Solution: Repair or replace valve.
c) Cause: Float chamber clogged with sediment.
Test: Open blow-down valve. If there is little or no
water flow, the chamber may be clogged with sediment.
Solution: Remove head assembly from float chamber
and clean sediment from chamber, float and bellows
mechanism. Replace head mechanism if necessary.
d) Cause: Float has filled with water.
Solution: Replace float.
e) Cause: Equalizing piping is plugged.
Solution: Clean or replace piping.
f) Cause: City water supply is above 150 psi (51, 53
Feeders) or 100 psi (51-S Feeder).
Solution: Install pressure reducing valve to reduce
water pressure.
Boiler is not getting enough water.
a) Cause: There is something preventing the valve from
fully opening.
Test: Perform broken union test.
Solution:
• Series 51 Feeders Only: Remove and inspect
cartridge. Clean or replace as necessary.
• Series 51-S and 53 Feeders Only: There may be
debris lodged in the valve preventing it from closing
completely. Remove and clean valve assembly.
Replace if necessary.
b) Cause: Strainer clogged with sediment.
Test: Perform broken union test.
Solution: Remove and inspect strainer. Clean or
replace as necessary.
c) Cause: Float chamber clogged with sediment.
Test: Open blow-down valve. If there is little or no
water flow, the chamber may be clogged with sediment.
Solution: Remove head assembly from float chamber
and clean sediment from chamber, float and bellows
mechanism. Replace head mechanism if necessary.
d) Cause: Feed line between valve and boiler is partially
plugged.
Test: Perform broken union test. With union broken,
there should be water flowing through the piping from
the boiler.
Solution: Clean or replace piping.
e) Cause: Feed line between valve and city water supply
is plugged.
Solution: Clean or replace piping.
f) Cause: Water supply pressure less than boiler
pressure.
Solution: Reduce boiler pressure or convert to pumped
return.