Quick Setup Guide
tN2 Wiring Center 316
1. Location
316
Zoning
316_Q
02/14
Replaces: 01/14
316
2. Install Junction Box
OR
A Watts Water Technologies Company
1
© 2014 316_Q - 02/14
3. Line Voltage Wiring
Zone 1
Zone 2
Zone 3
Zone 4
(red)
(black)
(black)
(black)
(black)
316
Zone Power (L)
Zone 1
Zone 2
Zone 3
Zone 4
Strip wires
1/2 inch (13 mm).
Installed wires are
not removable.
12-18 AWG
LNG
115 V (ac)
4. Install Enclosure
A Watts Water Technologies Company
2
© 2014 316_Q - 02/14
5. Low Voltage Wiring
tekmarNet®4 Thermostats
tekmarNet
®
4 Expansion to
House Control, Wiring Centers,
Timers, or User Switch
tN4
Expansion
CtN4
OR
Boiler T-T
T
T
OR
Powered Boiler Demand
(ie. Input into tekmar
Outdoor Reset Control)
Expansion
tN4CX
End Switch
X
Expansion
tN4CX
End Switch
X
tN4CXXCR
C
WtN4 R C
Zone 2
W tN4C tN4C
Zone 1
Zone 1 Expansion
Zone 2
Zone 3
Zone 4
End Switch
X X
Input Power
RR
tN4 Wiring Center 316
C
Four Zone Pumps
Power
End Switch
WtN4 R C
Zone 3
Input Power: 24 V (ac) ±10% 60 Hz
Class 2
Control Load: 11 VA
End Switch: 24 V (ac) 2 A
Pump Relays: 115 V (ac) 5 A
Zone Power: 115 V (ac) 12 A
Zone 4
Made in Canada
tektra 1031-01
Use at least 167°F (75°C) conductors
WtN4 R
H8002A
Boiler
Demand
C
R
6. Install The Cover
C
R
N
24 V (ac) Transformer 009
L
tekmar Control Systems Ltd., A Watts Water Technologies Company.
Vernon, B.C. Canada V1B 3K4, 250-545-7749, Fax. 250-545-0650 Web Site: www.tekmarControls.com
Product design, software and literature are Copyright ©2014 by
tekmar Control Systems Ltd.,
A Watts Water Technologies Company
Head Offi ce: 5100 Silver Star Road,
3
All specifications are subject to change without notice.
Printed in Canada. 316_Q - 02/14.