Schneider Electric Industrial Actuators Catalog

Rev: 11/2012
Industrial Electric Actuators
Featured Actuators
Featured
Industrial Actuators
Industrial Actuators
24V and 120V, On/Off and Modulating
Series 92/93
Up to 30,000 lb. in.
Pneumatic Double Acting
and Spring Return
Series 70
600 to 18,000 lb. in.
21,000 to 70,000 lb. in.
On/Off and Modulating
Industrial Actuators
11/2012
IA-2
Industrial Actuators
Series 70
Industrial Electric Actuators
The Bray Series 70 Electric Actuator provides a rugged, compact industrial actuator solution to a wide range of quarter turn applications including butterfly valves, ball valves, and dampers. Available in torque outputs from 600 to 18,000 lb. in. (68 to 2033 Nm), these actuators mount directly to Bray and other industry standard butterfly valves without the need for brackets and linkages. The manual declutchable override handwheel is standard on all Bray Series 70 actuators, providing end
user convenience in installation, commissioning
and service.
Industrial Electric Actuators
Series 70 - Features and Benefits
On/Off and modulating models are available in 24, 110 and 220 VAC. The standard enclosure is NEMA 4x and IP65 rated with an industrial polyester finish, making the Series 70 the ideal choice for cooling tower valves and other outdoor applications. The advanced Servo Pro modulating control card assures compatibility with virtually any analog control signal used in today’s building automation and temperature control systems.
FEATURES BENEFITS
Compact design and direct mounting
UL, CSA and CE approved (most models)
High visibility beacon position indicator
Industrial Actuators
Internal isolation relays
Manual declutchable override handwheel
Fits in tight spaces, installs easily
Assures universal application acceptability
Assists in field operation
Allows parallel wiring of multiple actuators from a single control output
Allows manual positioning without disconnecting power
IA-3
Advanced Servo Pro modulating option
Optional battery backup on 24 VAC models
Provides on-board diagnostics and user adjustable options including control signal type, speed controls and other features.
Assures return to a predetermined position upon loss of power supply
11/2012
MODEL SELECTION
Industrial Electric Actuators
Series 70 - Non-Spring Return
Industrial Actuators
Model Number
70-24-0061
70-24-0061H
70-24-0061SV
70-24-0061SVH
70-0061
70-0061H
70-0061SV
70-0061SVH
70-0121
70-0121H
70-0121SV
70-0121SVH
70-24-0201
70-24-0201H
70-24-0201SV
70-24-0201SVH
70-0201
70-0201H
70-0201SV
70-0201SVH
Feature
in/lbs.
Torque Output
600 600 600 600 600 600 600 600
1200 1200 1200 1200 2000 2000 2000 2000 2000 2000 2000 2000
24 VAC
120 VAC
On/Off
Modulating
Heater
• •
• •
• •
• • • •
• •
• •
• • • •
• •
• •
• •
• •
• • • •
• •
Aux. Switches
Model Number
70-0301
70-0301H
70-0301SV
70-0301SVH
70-24-0501
70-24-0501H
70-24-0501SV
70-24-0501SVH
70-0501
70-0501H
70-0501SV
70-0501SVH
70-0651
70-0651H
70-0651SV
70-0651SVH
70-1300
70-1300H
70-1300SV
70-1300SVH
70-1800
70-1800H
70-1800SV
70-1800SVH
Feature
in/lbs.
Torque Output
3000 3000 3000 3000 5000 5000 5000 5000 5000 5000 5000 5000 6500 6500 6500
6500 13,000 13,000 13,000 13,000 18,000 18,000 18,000 18,000
24 VAC
120 VAC
On/Off
Modulating
Heater
• •
• •
• •
• •
• •
• •
• •
• •
• •
• •
• •
• •
• •
• •
• •
• •
Aux. Switches
Application Note:
Use Series 70 actuators only to control equipment under normal operating conditions. Where failure or malfunction of the electric actuator could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices, such as supervisory or alarm systems or safety or limit controls, intended to warn of or protect against failure or malfunction of the electric actuator.
11/2012
Industrial Actuators
IA-4
Industrial Actuators
Industrial Electric Actuators
Specifications - Series 70
SPECIFICATIONS
Industrial electric actuators shall include manual declutchable override handwheel and high visibility position indication. Motors shall be continuous duty. Enclosure shall be NEMA 4X, IP 65 rated. Actuator shall conform to ISO 5211 standards for direct mounting onto quarter turn valves. On/Off actuators shall be equipped with internal isolation relays to allow parallel wiring of multiple units. Modulating actuators shall be equipped with a microprocessor-based servo control with on-board diagnostics. Actuator shall be UL, CSA and CE approved. Actuators shall be Bray Series 70 or approved equal.
Model
70-24-0061 24 VAC 600 45 sec. 1.8 70-24-0201 24 VAC 2000 60 sec. 2.0 70-24-0501 24 VAC 5000 60 sec. 3.0 70-0061 120 VAC 600 30 sec. 1 1.4 70-0121 120 VAC 1200 30 sec. 0.78 2.1 70-0201 120 VAC 2000 30 sec. 1 2.1 70-0301 120 VAC 3000 30 sec. 1.2 3.0 70-0501 120 VAC 5000 30 sec. 1.6 3.0 70-0651 120 VAC 6500 30 sec. 2.3 3.1 70-1300 120 VAC 13000 110 sec. 2.3 3.1 70-1800 120 VAC 18000 110 sec. 2.5 3.1
Motor Duty Cycle Continuous Duty
Aux Switches 10A (1/3 HP) @ 120 VAC (Two SPDT) 10A (1/2 HP) @ 220 VAC
Heater (Optional) 24V Models 5 Watt, PTC style, self regulating
Voltage
120 V Models 5 Watt, PTC style, self regulating
Torque Stroke
(lb. in.) Time Full Load Locked Rotor
Current Draw (Amps)
-
-
-
Servo Control Input 0 to 10 VDC, 2 to 10 VDC, 0 to 5 VDC, 4 to 20 mA (Modulating Models) Input Impedance Voltage: 1000K Ohms; Current: 250 Ohms
Housing Die Cast Aluminum, Polyester Finish
Industrial Actuators
Conduit Entries (2) 70-0061, 1/2" NPT
Terminal Strip On/off Models, 12 to 22 AWG
Ambient Temperature -20 to 150F (-29 to 65C)
Agency Listings (120V) UL, CE, CSA
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult the nearest Bray office. Bray controls shall not be liable for damages resulting from misapplication or misuse of its products.
IA-5
NEMA 4X, IP 65
All Other Models, 3/4" NPT
Modulating Models, 14 to 24 AWG
11/2012
Industrial Electric Actuators
Industrial Actuators
Wiring - Series 70
WIRING
Note: Use this Series 70 Electric Actuator only to control equipment under normal operating conditions. Where failure or malfunction of the electric actuator could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices such as supervisory or alarm systems or safety or limit controls intended to warn of, or protect against, failure or malfunction of the electric actuator.
Note: Do not install or use the Series 70 Electric Actuator in or near environments where corrosive substances or vapors could be present. Exposure of the electric actuator to corrosive environments may damage the internal components of the device, and will void the warranty.
SINGLE PHASE POWER SUPPLY
120 VAC ON/OFF WIRING
FIELD WIRING
CLOSE N.O.
(VOLTAGE FREE)
OPEN N.O.
(VOLTAGE FREE)
N
L
FOR HEATER OPTION ONLY
CLOSE
OPEN
ACTUATOR
OPEN
CLOSE
O C
MOTOR
N
GROUND
AUX SWITCH CLOSE
(VOLTAGE FREE)
AUX SWITCH OPEN
(VOLTAGE FREE)
SINGLE PHASE
POWER SUPPLY
INCOMING COMMAND SIGNAL
+ 5 VDC AT 50 mA (RESISTIVE CONTROL)
NEUTRAL
LIVE
GROUND
POSITION
FEEDBACK
DEVICE
LOAD DEVICE
NOT TO EXCEED
500 OHM
FIELD WIRING ACTUATOR
BLUE
RED
YELLOW OR
BLACK
A
B
C
D
1
2
3
4
5
6
7
8
9
CLOSE N.O.
(VOLTAGE FREE)
OPEN N.O.
(VOLTAGE FREE)
24 VAC
SINGLE PHASE
POWER SUPPLY
GROUND
120 VAC MODULATING WIRING
N.O.
N.O.
-
+
-
+
NOTE: 24 VAC SERVO HAS 2 TERMINALS ONLY
A
B
C
D
E
F
CALIBRATE
OUTGOING FEEDBACK SIGNAL
24 VAC ON/OFF WIRING
N
INPUT (-)
INPUT (+)
+5 VDC
OUTPUT (-)
OUTPUT (+ )
HIGH VOLTAGE
MOTOR CLOSE
MOTOR OPEN
NEUTRAL
NEUTRAL
LINE
POWER
OPEN
OFF
CLOSE
OPEN
SPEED
FUSE
7 8910
SPEED
PRO
FACTORY
DEAD BAND
CLOSE
SERVO
®
HEATER
FOR HEATER OPTION ONLY
-
DC
MOTOR
+
1 234 5 6
STATUS
ON
COM
FB POT
+5
CONTROL BO X
COM
OPEN
CLOSE
COMMON
HANDWHEEL
TORQUE LIMIT
COM
OPEN
CLOSE
COMMON
CLOSE LIMIT
OPEN LIMIT
L
WHITE
BLACK
A
B
C
D
1
2
3
4
5
6
Industrial Actuators
11/2012
IA-6
Industrial Actuators
Industrial Electric Actuators
Wiring - Series 70
WIRING
AUX SWITCH CLOSE
(VOLTAGE FREE)
AUX SWITCH OPEN
(VOLTAGE FREE)
24 VAC
POWER
{
SUPPLY
POSITIVE INCOMING COMMAND SIGNAL
24 VAC 3WIRE MODULATING
N.O.
N.O.
NEUTRAL
LIVE
GROUND
+
+ 5 VDC AT 50 mA
(RESISTIVE CONTROL)
POSITION
FEEDBACK
DEVICE
LOAD DEVICE
NOT TO EXCEED
500 OHM
-
OUTGOING FEEDBACK SIGNAL
+
Notes:
1. Command signal and feedback wires MUST be shielded and grounded for proper servo operation.
A
B
C
D
E
F
CLOSE
SERVO
®
DEAD BAND
HEATER
1 234 5 6
STATUS
ON
COM
FB POT
+5
CONTROL BOX
COM
OPEN
CLOSE
COMMON
HANDWHEEL
TORQUE LIMIT
COM
OPEN
CLOSE
COMMON
CLOSE LIMIT
OPEN LIMIT
CALIBRATE
INPUT (-)
INPUT (+)
+5 VDC
OUTPUT (-)
OUTPUT (+)
MOTOR CLOSE
MOTOR OPEN
NEUTRAL
LINE
POWER
OPEN
SPEED
FUSE
7 8910
SPEED
PRO
2. The command signal input (-) terminal is internally connected to the servo neutral terminal. DO NOT connect the live to the neutral terminal on the servo.
The 24 V Servo Pros (Revision J) can be wired 3 or 4 wire configured
Industrial Actuators
INCOMING COMMAND SIGNAL
AUX SWITCH CLOSE
(VOLTAGE FREE)
AUX SWITCH OPEN
(VOLTAGE FREE)
24 VAC POWER SUPPLY
+ 5 VDC AT 50 mA (RESISTIVE CONTROL)
NOT TO EXCEED
24 VAC 4WIRE MODULATING
NEUTRAL
LIVE
{
GROUND
POSITION
FEEDBACK
DEVICE
LOAD DEVICE
500 OHM
{
N.O.
N.O.
-
+
-
OUTGOING FEEDBACK SIGNAL
+
A
B
C
D
E
F
CLOSE
SERVO
DEAD BAND
®
HEATER
1 234 5 6
STATUS
ON
COM
FB POT
+5
CONTROL BOX
COM
OPEN
CLOSE
COMMON
HANDWHEEL
TORQUE LIMIT
COM
OPEN
CLOSE
COMMON
CLOSE LIMIT
OPEN LIMIT
CALIBRATE
INPUT (-)
INPUT (+)
+5 VDC
OUTPUT (-)
OUTPUT (+)
MOTOR CLOSE
MOTOR OPEN
NEUTRAL
LINE
POWER
OPEN
SPEED
FUSE
7 8910
SPEED
PRO
IA-7
11/2012
DIMENSIONS
SERIES 70 ACTUATOR DIMENSIONS
ACTUATOR
MODEL
NUMBER
S70-0061
S70-0121
S70-0201
S70-0301
S70-0501
S70-0651
S70-1300
S70-1800
Dimensions are in Inches [Millimeters in brackets]
A B C D E F G H J
7.5
5.6
3.0
5.1
[191]
[142]
[76]
[130]
10.1
7.8
3.7
6.5
[257]
[198]
[94]
[165]
12.1
9.5
5.6
7.2
[307]
[241]
[142]
[183]
12.1
9.5
6.0
12.5
[307]
[241]
[152]
[317]
70-0061 to 70-0651
Allow 5.0 [127] For Cover Removal
Industrial Electric Actuators
Dimensions - Series 70
Please reference illustration below
K
(UNC)
x B.C.
[51]
[66]
[79]
[211]
5/16-18 x ø2.76
F07
5/16-18 x ø2.76
F07
1/2-13
x ø4.92
F12
1/2-13
x ø4.92
F12
1.9
[48]
2.5
[64]
2.9
[74]
8.1
[206]
1.94
[49.3]
2.69
[68.3]
3.19
[81]
9.2
[234]
.19
[4.8]
.56
[14.2]
.56
[14.2]
.56
[14.2]
1/2‡2.0
3/4‡2.6
3/4‡3.1
3/4‡8.3
M
(UNC)
x B.C.
1/2-13
x ø4.92
F12
3/4-10
x ø6.50
F16
3/4-10
x ø6.50
F16
Industrial Actuators
N P Q S T U
.75
.51
[19]
[13]
1.18
.87
[30]
[22]
See Detail A1
See Detail A2
øR
1.75
3.5
[44]
[89]
2.20
[56]8[203]
12
[305]
12
[305]
_ _ _
_ _ _
_ _ _
6.1
12.7
[155]
[323]8[203]
F
Wt.
lbs
[kgs]
12
[6]
28
[13]
48
[22]
118
[54]
1.60 [41]
D
1.25 [32]
J
Typically .78
[20]
Holes For #10-24 UNC or M5 4 Places
70-1300 to 70-1800
Holes For #10-24 UNC [M5]
Allow 5.0 for
Cover Removal
1.25 [32]
D
3.00 [76]
B
H NPT Conduit Entry 2 Places
B
.60 For Override
[15] Engagement
E
øA
M
Typically 4 Places
øA
P
K
Detail A1 - Output Bore
(Series 70-030,
050, 065 Only)
.47
G
[12]
øN x Q Deep
ø1.97 x 2.6 Deep
[50 x 66]
Typically 4 Places
øR
F
S
T
U
J
Typically .78
[20]
Max Stem
H NPT Conduit Entry 2 Places
3.00 [76]
5.4
Entry
E
K
Typically 4 Places
Detail A2 - Output Bore
G
C
øR
2.38 [60]
.47 [12]
1.97 [50]
3.05
[77.9]
S70-130/180S70-131/181
[15.8]
M
Typically 4 Places
.62
2.50
[62.7]
Industrial Actuators
IA-8
11/2012
Loading...
+ 18 hidden pages