Schneider Electric ION8650 Datasheet

ADVANCED UTILITY METERING FUNCTIONS AND CHARACTERISTICS
ION8650 series Technical Datasheet (US)
Providing high accuracy and a wide range of features for transmission and distribution metering, the PowerLogic ION8650 advanced revenue and power quality meter has the flexibility to change along with your needs. The meter provides the tools necessary to:
Manage energy procurement and supply contracts
Perform network capacity planning and stability analysis
Monitor power quality compliance, supply agreements, and regulatory requirements
Applications
Transmission and distribution metering
Revenue metering
Extensive power quality monitoring and analysis
Power quality compliance monitoring
Digital fault recording
Instrument transformer correction
PB107500
Version: 1.0 - 22/03/2021
Version: 1.0 - 22/03/2021
PLSED310027EN_US
PLSED310027EN_US
ION8650
1
ADVANCED UTILITY METERING FUNCTIONS AND CHARACTERISTICS
The solution for
Markets that can benefit from a solution that includes PowerLogic ION8650 series meters:
Transmission networks
Distribution network
Benefits
Reduce operations costs
Improve power quality
Improve continuity of service
Competitive advantages
Be integrated into existing wholesale settlement system
Be able to use Power Monitoring Expert software for data
analysis or share operation data with SCADA systems through multiple communication channels and protocols
Transformer/line loss compensation
Instrument transformer correction
Power management solutions
Schneider Electric provides innovative power management solutions to increase your energy efficiency and cost savings, maximise electrical network reliability and availability, and optimise electrical asset performance.
Conformity of standards
IEC 62053-22/23
IEC 61000-4-30
EN 50160
IEC 61000-4-7
IEC 61000-4-15
IEEE 1159
IEEE 519
IEC 61000-4-2
IEC 61000-4-3
IEC 61000-4-4
IEC 61000-4-5
IEC 61000-4-6
IEC 61000-4-12
CISPR 22
IEC 62052-11
IEC 60950
ANSI C12.20
2
Version: 1.0 - 22/03/2021
PLSED310027EN_US
ADVANCED UTILITY METERING FUNCTIONS AND CHARACTERISTICS
Main characteristics
Used to monitor electric energy provider networks, service entrances and
PB107500
substations, PowerLogic ION8650 meters are ideal for independent power producers and cogeneration applications that need to accurately measure energy bi-directionally in both generation and stand-by modes. These meters give utilities the tools to manage complex energy supply contracts that include commitments to power quality. Integrate them with our EcoStruxure™ Power Monitoring operations software or other energy management and SCADA systems through multiple communication channels and protocols, including Itron MV-90, Modbus, DNP, DLMS, IEC 61850 Ed. 3.
Applications
Revenue metering.
PowerLogic ION8650 socket meter
Cogeneration and IPP monitoring.
Compliance monitoring.
Power quality analysis.
Demand and power factor control.
Load curtailment.
Equipment monitoring and control.
Energy pulsing and totalisation.
Instrument transformer correction.
Outage Notification
Feature selection
Commercial reference number
S8650A
S8650B
S8650C
ION8650 meters
ION8650A
ION8650B
ION8650C
Main characteristics
ANSI Class 0.1 and IEC 62053-22/23 Class 0.2 S metering
For interconnection points on medium, high, and ultra-high voltage
networks; twice as accurate as current IEC and meets ANSI Class standards over all conditions and including single wide range current measurement.
Power quality compliance monitoring
Monitor compliance with international quality-of-supply standards (IEC
61000-4-30 Ed. 3 Class A/S, EN 50160 Ed. 4, IEC 61000-4-7, IEC 61000-4­15, IEEE 1159, IEEE 519). Also detects disturbance direction.
Digital fault recording
Simultaneous capture of voltage and current channels for sub-cycle
disturbance.
Complete communications
Multi-port, multi-protocol ports including serial, infrared, modem and
ethernet. Simultaneously supports multiple industry standard protocols including: Itron MV-90, Modbus, Modbus Master, DLMS, DNP 3.0 and IEC 61850 Ed. 2.
Multiple tariffs and time-of-use
Apply tariffs, seasonal rate schedules to measure energy and demand
values for time periods with specific billing requirements.
Multiple setpoints for alarm and functions
Use up to 65 setpoints for single/multi-condition alarms and I/O functions
with response times down to 1/2 cycle.
Multiple setpoints for alarm and functions
Use up to 65 setpoints.
Instrument transformer correction
Save money and improve accuracy by correcting for less accurate
transformers.
Alarm notification via email
High-priority alarms, data logs sent directly to the user’s PC. Instant
notification of power quality events by email.
Cyber security enhancements
Assign communication admin rights to selected user; prevention measures
ensure no loss of security logs; support syslog for external security.
Version: 1.0 - 22/03/2021
Version: 1.0 - 22/03/2021
PLSED310027EN_US
PLSED310027EN_US
3
ADVANCED UTILITY METERING FUNCTIONS AND CHARACTERISTICS
PE86302-95
PowerLogic ION8650 switchboard meter.
1 Terminals 2 Optical port 3 Main display status bar 4 Watt LED 5 Navigation, ALT/Enter buttons 6 VAR LED 7 Nameplate label 8 Demand reset switch
PE86002
Disturbance waveform capture and power quality report
Selection guide
ION8650 AION8650 BION8650
General
Use on LV, MV and HV systems
Current accuracy
Voltage accuracy
Power accuracy
Samples/cycle
b b b
0.1 % 0.1 % 0.1 %
0.1 % 0.1 % 0.1 %
0.1 % 0.1 % 0.1 %
1024 1024 1024
Instantaneous values
Current, voltage, frequency
Active, reactive, apparent power Total & per phase
Power factor Total & per phase
Current measurement range
b b b b b b b b b
0 A - 20 A 0 A - 20 A 0 A - 20 A
Energy values
Active, reactive, apparent energy
Settable accumulation modes
b b b b b b
Demand values
Current
Active, reactive, apparent power
Predicted active, reactive, apparent power
Synchronisation of the measurement window
Demand modes: Block (sliding), thermal (exponential)
Present & max value s
Present & max values
b b b b b b b b b b b b b b b
Power quality measurements
Harmonic distortion Current & voltage
Individual harmonics Via front panel
Waveform / transient capture
Harmonics: magnitude, phase, and interharmonics
Detection of voltage sags and swells
IEC 61000-4-30 class A / S
IEC 61000-4-15 (Flicker)
High speed data recording (down to 10 ms)
EN 50160 compliance reporting
Programmable (logic and math functions)
b b b
63 63 31
b / b - / b - / -
50 40 -
b b b
A S
b b b b b b b b b
Data recording
Onboard Memory (in Mbytes)
Revenue logs
Event logs
Historical logs
Harmonics logs
Sag/swell logs
Transient logs
Time stamping to 1 ms
GPS synchronisation (IRIG-B standard)
128 64 32
b b b b b b b b b b b b b b b b
- -
b b b b b b
Display and I/O
Front panel display
Wiring self-test (requires PowerLogic ION Setup)
Pulse output (front panel LED) Digital or analogue inputsg (max)
Digital or analogue outputsg (max, including pulse output)
b b b b b b
2 2 2
11 11 11
16 16 16
Communication
Infrared port
RS-485 / RS-232 port
RS-485 port
Ethernet port (Modbus/TCP/IP protocol) with gateway
Internal modem with gateway (ModemGate)
HTML web page server
IRIG-B port (unmodulated IRIG B00x time format)
Modbus TCP Master / Slave (Ethernet port)
Modbus RTU Master / Slave (Serial ports)
DNP 3.0 through serial, modem, and I/R ports
Cell modem option (LTE)
DLMS COSEM through serial, Ethernet and optical ports for all variants
g
With optional I/O Expander.
gg
For 9S, and 36S only. For 35S system up to 480 V L-L.
ggg
C model limited to IR + 2 other ports at one time. Ports can be enabled/disabled by user.
1 1 1
1 1 1
1 1 1
1 1 1
1 1 1
b b b
1 1 1
b / b
b / b
b / b b / b
b b b b b b
b b b
C
-
-
-
-
ggg
ggg
ggg
ggg
- / b
- / b
4
Version: 1.0 - 22/03/2021
PLSED310027EN_US