DefinitionThe Model 506.62/.72 Hydraulic Power Supply (HPS) uses a variable-
volume (pressure compensated) main pump, with a pressurized
(supercharged) hydraulic fluid inlet, to provide pressure to systems
with various flow requirements. The HPS is designed to be used with
servo-controlled, electro-hydraulic systems.
1.1Functional Description
Front panel controls
and indicators
Pressure output
Front panel controls on the HPS include local operating controls for the
main pump and supercharge pump. Front panel indicators show running
time, power on, low fluid level, fluid over-temperature, and dirty filter
conditions.
Pressure output is controlled by an adjustment on the main pump and is
monitored by the output pressure gage. An adjustable back-up relief
valve limits output pressure by porting fluid back to the reservoir when
the output pressure rises above the relief valve setting. High/low
pressure operation is controlled by the high/low solenoid valves.
These valves control the main pressure control (pressure compensator)
vent ports and the backup relief valve vent port.
019-341M
Introduction 1-1
Pressure accumulationThe pump-outlet pressure accumulator smooths the HPS output and
provides additional hydraulic pressure for high instantaneous flow
demands. It is precharged with dry nitrogen to a pressure proportional
to HPS output pressure. The optional slow turn-on accumulator slows
the rate at which the backup relief valve shifts from low to high
pressure.
Temperature controlA temperature gage indicates hydraulic fluid temperature. An
oil-to-water heat exchanger controls the fluid temperature. When the
temperature exceeds a preset limit, a temperature sensitive switch
turns off the HPS and lights the front panel Fluid Over-Temperature
indicator.
Fluid level indicationA transparent gage indicates the level of hydraulic fluid in the HPS
reservoir. A low-level switch automatically turns off the HPS and
lights the front panel Low Fluid Level indicator if hydraulic fluid
drops below a preset level.
Programmable logic
controller
The PLC (programmable logic controller) located in the starter
assembly performs logic functions. The I/O (input/output) section of the
PLC provides an interface for various signals received from or sent to
external devices.
The required water pressure between the input and the output of the
heat exchanger is 30 to 45 psi (0.2 to 0.3 MPa). The maximum allowable
pressure is 120 psi (0.8 MPa). The flow rate (±20%) at a given
temperature is shown in the table below.
Main pump motor power rating (2 each)150 hp (112 kW)200 hp (150 kW)
Supercharge pump motor power rating15 hp (11 kW)20 hp (15 kW)
3-phase current 460V/60 Hz:
†
Inrush385 A515 A
Conti nuous200 A250 A
Starter type (main pump motor)Wye-deltaWye-delta
24 V external hydraulic control amps, 60 Hz9 A9 A
Maximum cooling water heat load:
BTU per hour380,000509,000
Kilocalories per hour96,000128,600
Atmospheric heat load
BTU per hour27,60037,000
Kilocalories per hour7,00011,100
Water inlet/outlet size1.25 in. (38.8 mm) I.D.1.25 in. (38.8 mm) I.D.
Maximum ambient operating temperature104°F (40°C)104°F (40°C)
Minimum ambient operating temperature40°F (4.4°C)40°F (4.4°C)
Height with casters68 in. (1727 mm)78 in. (1981 mm)
Length90 in. (2286 mm)90 in. (2286 mm)
Width45 in. (1143 mm)45 in. (1143 mm)
Weight with oil6000 lb (2722 kg)6,500 lb (2948 kg)
*The number of connections are shown in parentheses.
†
Currents listed are typical values. Maximum values may be as much as 10 to 15% higher.
Specifications are subject to change without notice. Contact MTS for verification of any critical specifications.
Introduction 1-3
Section 2
Operation
2.1Controls and Indicators
The controls and indicators provided with the Model 506.62/.72
Hydraulic Power Supply (HPS) are described in Table 2-1. The
locations of these components are identified in the following figure.
Power
1
Spch Pump
Auto
Run
Start
Emergency Stop
11
2
HPS
Control
Source
RemoteLocal
Main Pump
High
Low
Stop
Start
3
4
Conditions Fluid Low Level
Fluid Over-Temp
65
Dirty Filter
7
Reset
10
9
Hours of Operation
8
Figure 2-1. Controls and Indicators
12
13
VW-G041C
Operation 2-1
Table 2-1. Controls and Indicators
ItemControl/IndicatorDescription
1Power indicator*The Power indicator lights to indicate that electrical power is
applied to the HPS.
2Spch Pump
Auto/Run/Start switch
To operate the supercharge pump when the main pump is not
operating, turn this spring-loaded switch to Start. After the
switch is released, it returns to the Run position — indicating
that the supercharge pump is circulating hydraulic fluid through
the heat exchanger and fine filter. If the switch is in the Auto
position, the HPS can be controlled by either the High/Low/Start switch or the optional remote control panel.
3Source Remote/Local
switch
If this two-position switch is in the Local position, you can
operate the HPS with the front panel controls. If it is in the
Remote position, use a remote control device to operate the HPS.
4Main Pump
High/Low/Start switch
To apply low pressure in local control, turn this spring-loaded
switch to Start. After the switch is released, it returns to the
Low position — indicating low pressure operation. Turn the
switch to High to select high pressure.
5Low Fluid Level
indicator*
6Fluid Over-Temperature
indicator*
When this indicator lights, the hydraulic fluid level has
dropped below a preset value.
When this indicator lights, hydraulic fluid temperature has
exceeded a preset value.
7Dirty Filter indicator*When this indicator lights, the low-pressure filter needs
replacement. See Subsection 3.1.1.
8Hours of Operation
meter
This front panel meter indicates the total operating hours of the
pump.
9Stop switchWhen Stop is pressed (in either local and remote control), the
HPS output first ramps to low pressure and then goes to zero
pressure. The supercharge pump continues to run for
approximately 10 seconds.
10Reset switchThis switch resets the interlock circuit if the condition causing
the interlock has been corrected.
11Emergency Stop switchThis switch operates in both local and remote control and is used
during emergency situations only. When pressed, it immediately
shuts down the HPS (the supercharge pump may continue to run
briefly to supply the main pump until they fully stop).
12Fluid level gageThis gage indicates the level of hydraulic fluid in the reservoir.
13Temperature gageThis gage indicates the temperature of the hydraulic fluid in the
HPS reservoir.
*Indicators are "push-to-test" type indicators. This means that if you push the indicator, it will light. If it does not light, the
bulb is burned out.
2-2 Operation
2.2Operation Procedures
WARNING
!
This section provides the local and remote operating procedures for the
506.62/.72 Hydraulic Power Supply.
Warning
Do not start the HPS if the servovalve command is not equal to
feedback (that is, zero balanced).
Failure to do this can result in sudden actuator movement which may
cause injury to persons and/or damage to equipment.
Ensure that the system is at zero balance before starting the HPS.
Before you beginMake sure that the external hydraulic system is ready for operation.
NOTEThe Dirty Filter indicator may light during a cold-
start. It should turn off when the HPS reaches its
normal operating temperature. If the indicator fails to
turn off, correct the condition (Subsection 3.1.1.2) and
press Reset.
Local operation1.Turn the Source Remote/Local switch to Local.
2.Apply electrical power to the HPS (the Power indicator will
light).
3.Press Reset.
1
4.Momentarily turn the High/Low/Start switch to Start. When you
release the switch, it returns to Low.
5.Check the HPS and external hydraulic system for leaks and
unusual sounds.
6.Turn the High/Low/Start switch to High to apply high pressure.
7.Press Stop on the HPS front panel to stop the HPS and remove
output pressure.
1
Reset must be pressed whenever electrical power to the HPS has been interrupted.
Operation 2-3
Remote Operation
1.Turn the Source Remote/Local switch to Remote. Make sure that
the remote control cable is connected to the cable connector (the
figure on the left shows the location of this connector) and to the
remote control device.
2.Apply electrical power.
1
Remote control
connector
3.Press Reset.
4.Use the remote control device to start the HPS at low pressure.
5.Check for leaks and unusual sounds.
6.Select high pressure at the remote control device.
7.Use the Off switch on the remote control device to stop the HPS
and remove output pressure.
2.3Supercharge Pump Operation
When the temperature of the hydraulic fluid in the HPS reservoir
When to use the
supercharge pump
Cooling procedure1.Ensure the water supply to the heat exchanger is turned on.
exceeds 140˚F (60˚C), the fluid over-temperature switch automatically
shuts down the HPS. The HPS main pumps cannot be restarted in local
or remote until the hydraulic fluid cools. The following procedure uses
the supercharge pump to hasten the cooling of the hydraulic fluid.
2.Turn the Spch Pump switch to the Start position and then release
the switch and allow it to return to the Run position. The
supercharge pump operates independently of the main pumps and
circulates hydraulic fluid through the heat exchanger to cool the
fluid.
3.When the temperature gage reads approximately 130˚F (54˚C),
turn the Spch Pump switch to the Auto position (the supercharge
pump will stop).
4.To restart the HPS, first press the Reset control on the local or
remote control panel to clear the hydraulic interlock circuit, and
then start the HPS in low pressure.
1
Reset must be pressed whenever electrical power to the HPS has been interrupted.
2-4 Operation
Section 3
9
Service
IntroductionThis section contains service information for the Model 506.62/.72
Hydraulic Power Supply (HPS). It provides:
•maintenance procedures
•service adjustments
•electrical information
3.1Maintenance Procedures
Maintenance overviewThe following subsections provide the routine maintenance procedures
for the HPS. Figure 3-1 shows the location of the components accessed
for the maintenance procedures. Table 3-1 lists the maintenance
schedule.
Pressure
Accumulator
High Pressure
Filter
Low Pressure
Filter
Slow Turn-on
Accumulator
Heat Exchanger
Manifold Drain
(under manifold)
Filter
Drain
Supercharge Pump
Figure 3-1. Location of Maintenance Components (HPS Side View)
VW-G06
Service 3-1
Table 3-1. Maintenance Schedule
WARNING
!
6
ProcedureIntervalSubsection
Check output pressure on gage*daily
Replace high-pressure filterwhen the indicator points to CHANGE3.1.1
Replace low-pressure filterwhen Dirty Filter indicator lights3.1.1
Check hydraulic fluid level on gagedaily3.1.2
Check hydraulic fluid in reservoir150 operating hours3.1.2
Analyze hydraulic fluid500 operating hours3.1.2
Check accumulator prechargeat established interval3.1.3
Check hydraulic hosesmonthly
*
See Subsection 3.2.1 to adjust the output pressure.
3.1.1Filters
Fluid filtration is provided by a 10-micron high-pressure filter and a
3-micron low-pressure filter. See Figure 3-1 for the location of the
filters and their drains.
High-pressure release occurs if the system is pressurized.
High-pressure release may cause personal injury or damage equipment.
Ensure that the output pressure gage reads zero before replacing the
filters.
3.1.1.1 High-Pressure Filter Replacement
CHANGE
Replace the high-pressure filter elements whenever the DIRT ALARM
indicator mounted on the base of each high-pressure filter housing
points to CHANGE (red or yellow zone) or whenever the hydraulic
OK
DIRT ALARM
VW-GO4
fluid is replaced.
1.Press Stop on the HPS. The output pressure gage must read zero.
3-2 Service
Loading...
+ 30 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.