KEYENCE LK-CC100, LK-DN100 User Manual

96M11549
CC-Link Communication Unit for the LK-G5000 Series
Read this manual before use. Keep this manual in a safe place for future reference.
User's Manual
LK-CC100
LK-DN100
NOTE

Introduction

This manual describes the basic operations and hardware functions of the LK-CC100 and LK-DN100. Before using the LK-CC100 and LK-DN100, read this manual carefully to ensure complete understanding so that you can take full advantage of these product's performance and functions. Keep this manual in a safe place for future reference. Please deliver this manual to the end users of this product.
Symbols
The following symbols alert you to important messages concerning the prevention of human injury and product damage.
DANGER
Failure to follow the instructions may lead to death or severe injury.
WARNING
Failure to follow the instructions may lead to injury (such as electric shock or burn).
CAUTION
Failure to follow the instructions may lead to property damage or product breakdown.
Provides additional information on proper operation.
Reference
Provides reference information or useful information about operation.
2

Safety Precautions

General cautions

• At startup and during operation, be sure to monitor the functions and performance of the LK-CC100 and LK-DN100.
• It is recommended that you take substantial safety measures to avoid any damage in case of product failure.
• Do not modify the LK-CC100 or LK-DN100 or use it in any way other than as described in the specifications. The warranty will be voided in such cases.
• When the LK-CC100 or LK-DN100 is used in combination with other devices, functions and performance may be degraded depending on the operating conditions and surrounding environment.
• Do not use the LK-CC100 or LK-DN100 for the purpose of protecting the human body.
• Do not allow the temperature to change sharply around the LK-CC100 or LK-DN100, including the accessories. Otherwise, condensation may lead to a malfunction.

WARNING

Ensuring safe operation
• Use the proper power supply voltage as specified. Failure to do so may cause a fire, electric shock, or malfunction.
• Do not attempt to disassemble or modify the unit. Doing so may cause a fire, electric shock or unit malfunction.
Handling abnormal conditions
Turn off the power immediately in the following cases. Using the LK-CC100 or LK-DN100 in an abnormal condition could cause product breakdown. Contact your nearest KEYENCE office for repair.
• If liquid or foreign matter enters the unit.
• If the unit is dropped or the housing is damaged.
• If smoke or an abnormal odor is emitted from the controller.
96M11549
3

CAUTION

Ensuring safe operation
Do not block the vent holes on the unit. The rise in the internal temperature may cause product failure.
Installation environment
To use the LK-CC100 or LK-DN100 properly and safely, avoid installing it in the following locations. Doing so may lead to product breakdown.
• Location that is humid, dusty or poorly ventilated
• Location where the temperature becomes high, such as a place exposed to direct sunlight
• Location where there are flammable or corrosive gases
• Location where the product may be directly subjected to vibration or impact
• Location where water, oil or chemicals may splash onto the product
• Location where static electricity is readily generated
Influence of ambient temperature
Changes in the ambient temperature may cause the measurement to fluctuate. Be sure to keep the temperature constant at all times. When the ambient temperature changes by 10 °C, it takes about 60 minutes until the temperature inside the unit is uniformly distributed.

Other considerations

Handling
Do not wipe the unit with a wet cloth, benzene, or thinner. This may cause discoloration or deformation of the housing. If the unit becomes dirty, wipe it off with a cloth moistened with a mild detergent and then wipe with a soft dry cloth.

Precautions on CE Marking

The LK-CC100 and LK-DN100 conform to the CE marking directives under the conditions that the following requirements are satisfied. Make sure these conditions are met if using this device within the EU nations. The applicable standards (EMC Directive) are listed below: EMI : EN61326-1, Class A EMS : EN61326-1 Limit the length of all input/output cables that are connected to the terminal panel of the controller to 30 m or less.
4

Contents

Introduction............................................... 2
Safety Precautions ................................... 3
General cautions ................................ 3
WARNING .......................................... 3
CAUTION ...........................................4
Other considerations ..........................4
Precautions on CE Marking ................ 4
Contents ................................................... 5
Chapter 1 Before Use
System Configuration ...........................1-2
Checking the Package Contents ..........1-3
LK-CC100
(CC-Link communication unit)..... 1-3
LK-DN100
(DeviceNet communication unit). 1-3
Part Names and Functions ...................1-4
CC-Link communication unit
LK-CC100 ................................... 1-4
DeviceNet communication unit
LK-DN100 ................................... 1-6
Mounting/Connecting the Units ............1-7
Connecting the communication unit
.. 1-7
Changing the CC-Link Communication Unit
Settings ...........................................2-7
Field network connection
specifications .............................. 2-7
Control using CC-Link .................... 2-8
Creating the Ladder Program .............2-19
Timing Diagrams ................................2-21
Chapter 3 Connecting to DeviceNet
Typical DeviceNet System
Configuration ..................................3-2
Typical system configuration using
DeviceNet ................................... 3-2
Special notes for using a DeviceNet
system......................................... 3-3
Connecting to the Field Network ..........3-4
Preparing the communication cable 3-4
Connecting the wiring cable ........... 3-5
Wiring to the DeviceNet controller
(LK-DN100)................................. 3-6
Changing the DeviceNet Communication
Unit Settings ...................................3-7
Field network connection
specifications .............................. 3-7
Control using DeviceNet ................. 3-9
Creating the Ladder Program .............3-18
Timing Diagrams ................................3-20
Chapter 2 Connecting to CC-Link
Typical CC-Link System Configuration .2-2
Typical system configuration using
CC-Link ....................................... 2-2
Special notes for using a CC-Link
system......................................... 2-3
Connecting to the Field Network ..........2-4
Preparing the communication cable
Connecting the wiring cable ........... 2-5
Wiring to the CC-Link controller
(LK-CC100)................................. 2-6
.. 2-4
Chapter 4 Specifications
Specifications .......................................4-2
CC-Link unit LK-CC100 .................. 4-2
LK-DN100 DeviceNet unit .............. 4-3
Dimensions ...........................................4-4
LK-CC100....................................... 4-4
LK-DN100....................................... 4-5
Appendices
Error Codes ......................................... A-2
Revision History ................................... A-6
5
6
Before Use1
System Configuration..........................................................1-2
Checking the Package Contents ........................................ 1-3
Part Names and Functions .................................................1-4
Mounting/Connecting the Units .........................................1-7
1
1-1
1 Before Use

System Configuration

The LK-CC100 and LK-DN100 can be used along with commercially-available devices for various purposes.
1
Enables control and measured value reading through RS-232C communication or the parallel I/O board of the PC.
Indicator, buzzer
Issues an alarm depending on the comparator result output.
LK-G5000 Series
LK Navigator2
*2
Programmable logic controller (PLC)
Enables synchronization control of the measurement and program number switching as well as reading of control output and measured values.
Recorder
Records the measurement result.
Photoelectric sensors, proximity sensors
Use to send timing input signals when the measurement object is detected.
Dedicated touch panel
LK-HD1001
Setup support software (LK-H2)
USB/RS-232C/ Ethernet
Head expansion unit
LK-HA100
OUT1
HIGOLO
LK-HD500
OUT2
TIM
HIGOLO TIM
HEAD1 HEAD2
LASER ON
LASER ON
S TABILITY S TABILITY
BRIGHT D
P R O
BRIGHT
G R
A
ARK
M
D ARK
SET
ZE
RO
ENT
Controller
LK-G5001V/LK-G5001PV
*1
Expansion unit
LK-CC100 LK-DN100
Head (12 heads max.)
*1: The single unit type controller (LK-G5001V/LK-G5001PV) can be separated into the display panel
and controller unit. They can also be purchased separately. The single unit type controller is labeled as LK-HD500 on the display panel side and as LK-G5001 or LK-G5001P on the terminal panel side.
*2: Refer to the LK-Navigator 2 User's Manual (the PDF file is on the CD-ROM) for further details on the
setup support software (LK-H2) LK-Navigator 2.
1-2

Checking the Package Contents

MS
NS
10
(
FG
)
LK-D
N100
1
B R
A
TE
V
+
CAN H
SHIELD
CAN L
V
-
STATION No.

LK-CC100 (CC-Link communication unit)

1 Before Use
CC-Link communication unit LK-CC100: 1
User's Manual: 1 Resistors
• 110 1/2W: 2
• 130 1/2W: 2
100
LK-CC
L RUN
SD
RD
L ERR
10
STATION No.
1
TE
A
B R
MODE
)
FG
(
SLD
DG
DB
DA

LK-DN100 (DeviceNet communication unit)

DeviceNet communication unit LK-DN100: 1
User's Manual: 1 Metal-film resistor
121 1% 1/4W: 2
Screwdriver: 1
Screwdriver: 1
1
The package contents have been carefully inspected; however, if any component is defective or damaged, contact your nearest KEYENCE office (address listed at the end of this manual).
1-3
1 Before Use

Part Names and Functions

This section describes the name and functions of each component.
1

CC-Link communication unit LK-CC100

L RUN (Operating status) indicator
Lit: Data communication between the master and local stations (when lit green).
Unlit: Data communications timed out (indicator will light up again when data is received normally).
SD (Send data) indicator
Lit: Sending data.
RD (Receive data) indicator
Lit: Receiving data.
L ERR (error) indicator
Lit: A communications error exists (when lit red).
LK-CC100
L RUN
L ERR
3
2
4
1
0
9
7
8
3
2
4
1
0
9
7
8
3
2
4
1
0
9
7
8
5
4
6
3
7
2
1
0
F
B
E
C
D
SD
RD
5
10
6
5
1
6
STATION No.
5
B RATE
6
8
9
MODE
A
(FG)
SLD
DG
DB
A
D
Flashing at regular intervals: Station number or communication speed change detected while power was on.
Flashing irregularly: Terminator (terminating resistor) is set incorrectly, or noise is affecting the unit or CC-Link dedicated cable.
Unlit: Communications are normal.
STATION No. setting switch
Sets the station number (setting range: 1 to 64). x10 indicates the tens place, x1 indicates the ones place.
B RATE setting switch
Sets the baud rate. The baud rate settings can be set as follows. 0: 156 kbps, 1: 625 kbps, 2: 2.5 Mbps, 3: 5 Mbps, 4: 10 Mbps
MODE setting switch
Sets the communication mode. The communication mode settings can be set as follows.
햲 햳 햴 햵
햷 햸
Switch setting Multiple Station Ver si on Remark
0 1 1 - Not supported (Disables control input, tolerance comparison
and readout of measurement values for any OUT).
1 1 2 1.1 Disables control input, tolerance comparison and readout of
measurement values for OUT03 and higher.
2 1 3 1.1 Disables control input, tolerance comparison and readout of
measurement values for OUT05 and higher.
1-4
1 Before Use
Switch setting Multiple Station Ve rsi on Remark
3 1 4 1.1 Disables control input, tolerance comparison and readout of
measurement values for OUT07 and higher.
4 2 1 2.0 Disables control input or tolerance comparison for any OUT,
and disables readout of measurement values for OUT3 and higher.
5 2 2 2.0 Disables control input or tolerance comparison for OUT05
and on, and disables readout of measurement values for OUT07 and higher.
6 2 3 2.0 Disables control input or tolerance comparison for OUT09
and on, and disables readout of measurement values for OUT11 and higher.
7 2 4 2.0 Unused.
8 4 1 2.0 Disables control input or tolerance comparison for OUT03
and on, and disables readout of measurement values for OUT07 and higher.
9 4 2 2.0 Disables control input and tolerance comparison for OUT11
and higher.
A 4 3 2.0 Unused.
B 4 4 - Cannot be used due to stress placed on network.
C 8 1 2.0 Disables control input and tolerance comparison for OUT07
and higher.
D 8 2 2.0 Unused.
E 8 3 - Cannot be used due to stress placed on network.
F 8 4 - Cannot be used due to stress placed on network.
1
Connector
Termina l bl ock
Ter minal name Function
FG Functional ground terminal.
Ground to a ground resistance of 100 ohms or less.
SLD Shield.
Connect shield wire from the dedicated CC-Link cable supporting Ver. 1.10 (OP-79426, OP-79427, etc.).
DG Communication ground
DB Communication signal Low
DA Communication signal High
1-5
1 Before Use

DeviceNet communication unit LK-DN100

MS (Status) indicator
Displays the status of the LK-DN100.
Lit green: Normal operation.
1
LK-DN100
MS
NS
Lit red: An unrecoverable alarm exists (caused when
3
2
wrong switches are selected at start up).
Flashing red: A recoverable alarm exists (can be caused by turning the rotary switch after start up). Reset
4
1
5
0
10
6
9
7
8
3
2
4
1
5
0
1
6
9
7
Node Address
8
5
4
6
3
7
2
8
1
Data
9
0
A
F
B
Rate
E
C
D
error by returning the switch where it was at start up.
+
Unlit: The power is OFF.
NS (Network status) indicator
Displays the status of the network communication.
Lit green: Slave unit is online and connected to the
V
CAN H
SHIELD
CAN L
V
-
(FG)
master unit.
Flashing green: Slave unit is online but not connected to the master unit.
Lit red: Indicates the bus is off, a duplicate node address exists, or the wrong switches were selected at start up.
Flashing red: 1 or more connections have timed out.
Alternately flashing red and green: A network access error exists.
Unlit: The power is OFF.
Node Address (node address setting) switch
Sets the node address (setting range: 0 to 63, default setting: 63). x10 indicates the tens place, x1 indicates the ones place.
햵 햶 햷
Data Rate (baud rate) setting switch
Sets the baud rate. The baud rate settings can be set as follows. 0: 125 kbps, 1: 250 kbps, 2 (default): 500 kbps
Connector
Terminal block
Terminal name Wire color Function
V+ Red Communication power supply (24 VDC input)
CAN_H White Communication signal High
Shield Exposed Shield
CAN_L Blue Communication signal Low
V- Black Communication power supply (0 VDC input)
F.G. terminal
1-6

Mounting/Connecting the Units

Connecting the communication unit

1 Before Use
Connect the LK-CC100 CC-Link communication unit or the LK-DN100 DeviceNet communication unit to the controller.
CAUTION
Turn off the power of the LK-G5000 Series before connecting the communication unit. Otherwise, you may suffer a shock or damage the unit.
Connect the communication unit by aligning its connector to the connector on
1
the left side of the LK-G5000.
You need to remove the sticker attached to the left side of the LK-G5000 beforehand.
Connector
LK-CC100
L RUN
SD
RD
L ERR
10
STATION No.
1
ATE B R
MODE
) FG
(
SLD
DG
LK-CC100
DB
DA
or
LK-DN100
Secure the communication unit by tightening the two connecting screws.
2
LK-DN100
MS
NS
10
STATION No.
1
B RATE
+ V
CAN H
SHIELD
CAN L
­V
) FG (
Screw position
LK-G5000
) V (
) A (
0V
)
1
V (
LASER ON
) A (
0V
21 22
2
23
1
1
24
2
25
ETHERNET
3
26
LK-DN100
4
27
5
MS
28
6
29
7
30
8
31
HEAD
NS
2
9
32
10
33
11
34
12
35
13
36
14
LK-CC100
RUN L
SD
RD
L ERR
10
STATION No.
1
ATE B R
MODE
) FG
(
SLD
DG
DB
DA
LK-CC100
or
LK-DN100
37
15
38
USB
16
39
17
40 18 19 20
10
STATION No.
1
HEAD
1
RS-232C
TE A B R
COM INZERO 1TIMING 1GOLASER 1DC 24V
+ V
DISPLAY
CAN H
SHIELD
CAN L
­V
) FG (
LK-G5000
) V ( ) A (
0V
)
1
V (
LASER ON
) A (
0V
21 22
2
23
1
1
24
2
25
ETHERNET
3
26
4
27
5
28
6
29
7
30
8
31
HEAD
2
9
32
10
33
11
34
12
35
13
36
14
37
15
38
USB
16
39
17
40 18 19 20
HEAD
1
RS-232C
COM INZERO 1TIMING 1GOLASER 1DC 24V
AY
DISPL
1
Screw position
Tightening torque
Limit the tightening torque to 0.7 Nm or less.
1-7
1
1 Before Use
1-8
Connecting to CC-Link2
Typical CC-Link System Configuration............................. 2-2
Connecting to the Field Network....................................... 2-4
Changing the CC-Link Communication Unit Settings..... 2-7
Creating the Ladder Program ...........................................2-19
Timing Diagrams .............................................................. 2-21
2
2-1
2 Connecting to CC-Link
Host device: PLC, etc. (CC-Link master unit)
LK-G5001
+
LK-CC100
LK-G5001
+
LK-CC100
LK-G5001
+
LK-CC100
Terminator connection for KV-CL20, etc.
RS-232C/USB/Ethernet
1
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
2
21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40
LASER ON
ETHERNET
USB
DISPL
AY
R
S-232C
H
EA
D
1
(
V
)
(
A
)
0V
(
V
)
(
A
)
0V
COM INZERO 1TIMING 1GOLASER 1DC 24V
1
H
EA
D
LK-G5000
2
L
R
UN
SD
RD
L ERR
10
LK-CC100
1
B R
A
TE
SLD
DG
DB
DA
MODE
STATION No.
(
FG
)
1
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
2
21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40
LASER ON
ETHERNET
USB
DISPLA
Y
R
S
-232C
H
EA
D
1
(
V
)
(
A
)
0V
(
V
)
(
A
)
0V
COM INZERO 1TIMING 1GOLASER 1DC 24V
1
H
EA
D
LK-G5000
2
L
R
UN
SD
RD
L ERR
10
LK-CC100
1
B R
A
TE
SLD
DG
DB
DA
MODE
STATION No.
(
FG
)
1
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
2
21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40
LASER ON
ETHERNET
USB
DISPLA
Y
R
S-232C
H
EA
D
1
(
V
)
(
A
)
0V
(
V
)
(
A
)
0V
COM INZERO 1TIMING 1GOLASER 1DC 24V
1
H
EA
D
LK-
G5000
2
L
R
UN
SD
RD
L ERR
10
LK-CC100
1
B R
A
TE
SLD
DG
DB
D
A
MODE
STATION No.
(
FG
)
LK-H02*/H05* series head
LK-H02*/H05* series head
Terminator
Max. connections: 64 units
LK-H02*/H05* series head
PC for setup

Typical CC-Link System Configuration

Typical system configuration using CC-Link

2
2-2
2 Connecting to CC-Link

Special notes for using a CC-Link system

Take note of the following when using the LK-CC100 in a CC-Link network.
• The LK-CC100 is a network controller for CC-Link Ver. 2.00 or Ver. 1.10. If using the LK­CC100 on a CC-Link Ver. 2.00 network, it must be connected to a master device compatible with CC-Link Ver. 2.00. The LK-CC100 operates as a Ver. 1.10 unit when the extended cyclic setting is set to single. It operates as a Ver. 2.00 unit at double or faster.
• CC-Link supports up to 64 connected devices. The actual number of devices that can be connected is limited by the number of stations each unit occupies. Refer to the manual for the master device used on the CC-Link to determine the number of stations occupied and the maximum number of devices that can be connected.
• The maximum total length of the entire CC-Link network is 1.2 km (at 156 kbps). Refer to the following table for the relation between communication speed and maximum cable length.
2
Communication speed Cable length between
stations
156 kbit/s 20 cm min. 1,200 m
625 kbit/s 900 m
2.5 M bit/s 400 m
5 M bit/s 160 m
10 M bit/s 100 m
• Connect the LK-CC100 using the dedicated CC-Link cable (Ver. 1.10 or higher).
• Always connect a terminator (110 ohms 1/2W) between DA - DB on the units at both ends of the CC-Link.
• The setup support software LK-Navigator 2 (LK-H2) cannot be used to display received light waveforms through the CC-Link.
Maximum total cable length
Precautions on CC-Link settings
• The parameters for the LK-CC100 should be set to match the CC-Link master unit. Set using the STATION No. setting switch, B RATE setting switch, and MODE setting switch.
• Refer to the manual for the CC-Link master unit for details on how to set it.
NOTE
The number of stations occupied must be set according to the data read/write size.
2-3
2 Connecting to CC-Link
Approx. 8 mm
Twist conductor strands together

Connecting to the Field Network

To connect to the master device or network controller on the field network using a multidrop connection, or to connect other slave devices, connect a communication cable that supports each field network to the field network connector.
2

Preparing the communication cable

Use a communication cable dedicated for CC-Link (Ver. 1.10 or higher).
Remove the sheath (outer insulation) from the cable.
1
Approx. 50 mm
Sheath (outer insulation)
Carefully remove about 50 mm from the end of the dedicated cable so as not to damage the braided shield wires.
Prepare the shield.
2
Aluminum polyester laminated tape
Carefully unravel the braided shield wires. Inside the shield is a single exposed drain wire (twisted or loose). Twist this with the unraveled shield wire and cover it with an insulation tube.
Strip the insulation from the signal lines.
3
Shield (braided shield wire)
Twisted shield wireInsulation tube
Being careful not to damage the signal lines, remove the aluminum polyester laminated tape and filling, and strip about 8 mm from each signal line. Twist the exposed conductor strands to keep them together.
2-4
2 Connecting to CC-Link

Connecting the wiring cable

Connect the prepared wiring cable to the field network connector (terminal block).
Reference
The field network connector is designed for multidrop connection of slave devices.
Insert each signal line into the holes in the connector.
1
Insert into corresponding connector
NOTE
Before inserting the communication cable, loosen the connector clamp screws.
Secure each signal line by tightening the clamp screws on the side of the
2
connector.
2
Secure by tightening clamp screw
Wiring varies depending on the network controller. Insert the applicable signal lines into the connector.
2-5
2 Connecting to CC-Link
SLD
DG
DB
DA
(FG)
NOTE

Wiring to the CC-Link controller (LK-CC100)

The LK-CC100 field network connector (terminal block) is to be wired as explained below.
Terminal name Funct ion
FG Functional ground terminal.
SLD Shield.
2
DG Communication ground
DB Communication signal Low
DA Communication signal High
• To connect the CC-Link controller to the CC-Link, use the CC-Link dedicated cable (Ver. 1.10 or higher).
• At each CC-Link station connection, connect the cable shield to FG.
Ground to a ground resistance of 100 ohms or less.
Connect shield wire from the dedicated CC-Link cable supporting Ver. 1.10 (OP-79426, OP-79427, etc.).
Typical connection
Refer to the manual for the CC-Link master unit for wiring details.
Master station
Terminator Terminator
LK-CC100 Other unit Other unit
Connecting terminators
A terminator must be connected to both ends of the trunk line. The terminators must be connected to reduce signal reflection and stabilize communication. Terminator resistance: 110 ohms, 1/2W
• The terminators must be connected, otherwise, the CC-Link will not communicate properly.
• If using the CC-Link dedicated high-performance cable, use a 130 ohm, 1/2W resistor.
2-6
Other unit LK-CC100
DB
Terminator
DA
(FG)
SLD
DG
DB
DA
2 Connecting to CC-Link

Changing the CC-Link Communication Unit Settings

This section explains the principle and operation of the CC-Link communication unit (LK­CC100).
NOTE
This manual describes only those functions and settings of the CC-Link master device necessary for communicating with the LK-CC100. Refer to the manual supplied with the master device for details on functions and settings between the CC-Link master device and a PLC.

Field network connection specifications

Master settings
To connect the LK-CC100 to the CC-Link master, it is necessary to configure the slave attribute and memory allocation settings.
Slave attributes
Register the LK-CC100 to the CC-Link master unit as a remote device station. You can also set this by importing a CSP file into the software for the master unit (ladder programming software, CC-Link setting software).
Memory allocation settings
In order to exchange data between the LK-CC100 and CC-Link master unit, the memory allocation must be set using the software for the master unit (ladder programming software, CC-Link setting software).
Reference
• The RX, RY, RWw, and RWr communicated over the CC-Link is stored in the master unit's buffer memory.
• When multiple slaves are being used, the memory is allocated automatically for each slave according to the specified starting address. You can view the memory allocation information for each slave in the CC-Link setting software.
• CSP files can be downloaded from the KEYENCE website. http://www.keyence.co.jp/
2
2-7
2 Connecting to CC-Link

Control using CC-Link

This section explains how to use a PLC to control the LK-CC100 configured for a CC-Link network.
NOTE
This section describes only those functions and settings of the CC-Link master station necessary for communicating with the LK-CC100. Refer to the manual supplied with the CC-Link master station and
2
PLC for details on functions and settings of each device.
Operation and memory configuration with CC-Link
On a CC-Link network, the LK-CC100 operates as a slave station (remote device station) to the CC-Link master station connected via the network cable.
• The buffer memory inside the LK-CC100 is linked to remote I/O and remote registers on the CC-Link master station according to the memory configuration illustrated below.
• Control the system by setting and programming (2-14) according to this memory configuration.
Memory configuration
Buffer memory inside the LK-CC100 is linked as shown here.
Read buffer
Write buffer
2-8
Buffer memory
Read control buffer
Read data buffer
Write control buffer
Write data buffer
CC-Link master station
RY (remote outputs)
RWw (remote registers)
RX (remote inputs)
RWr (remote registers)
Loading...
+ 50 hidden pages