Atec ODEN-AT User Manual

4 (1)

ODEN AT

Primary Current Injection Test System

ODEN AT

Primary Current Injection Test System

Most Advanced Primary Current Injection

Test System to simplify all types of switchgear and CT commissioning, ground grid, circuit breaker testing and more

Modular design to permit optimal user configuration of output current vs. unit size

Compact transport cart facilitates portability into switchgear rooms with limited space

Unique I/30 function allows the current to be pre-set using low current to prevent test sample heating, thus eliminating corruption of test result

Description

This powerful test system is designed for primary injection testing of protective relay equipment and circuit breakers. It is also used to test the turns ratio of current transformers and for other applications that require high variable currents.

The system consists of a control unit together with one, two or three current units. There are three versions of the current unit: S, X and H. The S and X current units are identical except that the X unit has an additional 30/60 V output. The H unit is rated for even higher current. This makes it possible to configure an ODEN AT system in a suitable way. All parts are portable, and ODEN AT can be quickly assembled and connected.

The control unit has many advanced features – a powerful measurement section for example, that can display turns ratio as well as time, voltage and current. A second measurement channel can be used to measure an additional current or voltage. Current transformer turns ratio, impedance, resistance, power, power factor (cos φ) and phase angle are calculated and shown in the display. Current and voltage can be presented as percentages

of nominal value. The fast-acting hold function freezes shortduration readings on the digital display when the voltage or contact signal arrives at the stop input, the object under test interrupts the current or injection is stopped

Application

Primary current injection testing and breaker testing

These tests require high currents and the ability to measure very short duration, current flow. ODEN AT has been designed especially to meet these needs. No extra contacts are needed to measure the operating time of a low-voltage breaker. Testing stops at the instant when the main breaker contacts open to interrupt the current. Output current initiation is synchronized with the currents zero-crossover point to ensure good repeatability and minimized DC offset.

Testing current transformers

For turns ratio testing, the primary current and either the secondary current or the turns ratio are displayed simultaneously. Since the turns ratio is displayed directly as the nominal value (1000/5 for example), no further calculation is needed. Burden of secondary circuits can be measured and presented in VA.

Polarity testing

The currents phase displacement is shown, and the polarities of the outputs are clearly marked.

Heat runs

ODEN AT is ideal for performing heat runs. Current can be applied continuously or through programmable intervals. The times can be shown in minutes and hours which facilitates longterm testing capability.

Automatic reclosers and sectionalizers

ODEN AT can also be set to test circuit breakers with reclosing relays. Operating limits, partial times, total times and the number of operations before lockout can be measured. User-selectable reclosing sequences can be programmed for testing sectionalizers.

Testing integrity of ground grids and safety-ground devices

One way to test ground grids is by injecting current between a reference ground and the ground to be tested and measuring the voltage drop and the percentage of current flowing through the ground grid. The type X current unit included with ODEN AT is designed for this type of application. Personal safety grounds

must be tested at rated current, a task for which ODEN AT is well suited.

Atec ODEN-AT User Manual

Features and Benefits

1.Display. The display presents time, output current, voltage, current shown on ammeter 2 and phase angle. You can scroll through entities Z, P, Q, R, X, S, power factor (cos φ) and I max.

2.Miniature circuit breaker used for current output. Interrupts output current. Can also be actuated manually for safe disconnection of load.

3.Current reduction button. Used during setting to reduce the output current to 1/30. Useful in order to avoid for example unintentional tripping and overheating.

4.Fine adjustment knob. Knob for fine adjustment of current and +/- buttons for coarse adjustment.

5.Indicator lamps. Indicate whether ammeter 2 or the voltmeter is enabled.

6.Input for voltmeter. Used to measure voltage and for microhmmeter measurement.

7.Input for ammeter 2. Used to measure current in an external circuit (in a current transformer´s secondary winding for example).

8.Hold function. This function freezes readings on the display.

9.Selection/setting (CHANGE) knob. Selects the desired menu option (shown in the display window). Also used to change numerical values.

10.Setting buttons. Personnel unfamiliar with ODEN AT can use the pre-defined settings very effectively, while experienced users can make their own basic settings.

Ammeter. Used to set the main current-output ammeter. You can select the desired range or select autoranging.

V/A Meter. Toggles between the voltmeter and ammeter 2. Also used to select the desired range or select autoranging.

System. Used for general settings.

Memory. Used to save or recall settings to or from the ten ODEN AT memories. One of these memories contains the default (pre-defined) settings that are invoked when ODEN AT is powered up.

ODEN AT

Primary Current Injection Test System

• Application. Used to invoke the desired measurement mode: automatic recloser, sectionalizer or microhmmeter.

ODEN AT can also be set to generate pulse trains with user-se- lectable pulse and pause times.

11.Injection. Starts current injection and timing.

12.Momentary Injection. When this button is used, injection continues only as long as it is pressed. Useful in order to avoid for example overheating.

13.RS232 for computer. ODEN AT is equipped with a serial port for communication with PC (for transfer of test data for example).

14.Manual shut-off. Injection and timing are stopped when this button is pressed.

15.Automatic injection stop. Generation stops after a user-spec- ified interval or when condition at the input is met. The diodes show the selected OFF condition.

16.Stop-condition indicator. Indicates that a stop condition is met, voltage or contact triggered.

17.Status indicator. Indicates if a contact connected to the input is closed or if voltage is present.

18.Stop input. Used to freeze a reading or stop injection. Activated when current is interrupted by the object being tested, when an external contact is actuated or when a voltage is applied or removed.

1

 

2

 

3

 

4

 

5

6

 

7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8

 

9

 

10

11

12

 

13

 

14

 

15

 

16

 

17

18

Specifications ODEN AT

Specifications are valid at nominal input voltage and an ambient temperature of +25°C, (77°F). Specifications are subject to change without notice.

System designation

An ODEN AT-system consists of a control unit and one, two or three current units. There are three different versions of the current units: S-unit (standard), X-unit (extra 30/60 V outlet) and H-unit (high current). The system designation indicates the number and version of current units included.

Example: ODEN AT/2X

2 = Number of current units

X = Version of current unit (S, X or H)

Environment

Application field

The instrument is intended for use

 

in high-voltage substations and

 

industrial environments.

Temperature

 

Operating

0°C to +50°C (+32°F to +122°F)

Storage & transport

-25°C to +55°C (-13°F to +127°F)

Humidity

5% – 95% RH, non-condensing

CE-marking

 

LVD

2006/95/EC

EMC

2004/108/EC

General

 

Mains voltage

240 / 400 V AC, 50 / 60 Hz

 

480 V AC / 60 Hz

Mains inlet

IEC 60309-2, 63 A

Input current

Output current x open circuit voltage

 

/ input voltage

Protection

The output transformer has a built-in

 

thermal cut-out, and the primary

 

side is protected by a miniature

 

circuit breaker.

Dimensions

 

Control unit AT

570 x 310 x 230 mm

 

(22.4” x 12.2” x 9”)

Current unit S, X H

570 x 310 x 155 mm

 

(22.4” x 12.2” x 6”)

Complete with cart

690 x 350 x 860 mm

 

(27.2” x 13.8” x 33.9”)

Weight

 

Control unit AT

25 kg (55 lbs)

Current unit S

42 kg (92.6 lbs)

Current unit X

45 kg (99.3 lbs)

Current unit H

49 kg (108 lbs)

Cart

11 kg (24.3 lbs)

Display

LCD

Available languages

English, German, French, Spanish,

 

Swedish.

ODEN AT

Primary Current Injection Test System

Measurement section

Ammeters

Measurement method

AC, true RMS

Inaccuracy

1% of range ±1 digit

Ammeter 1

 

 

Ranges

0

– 4800 A / 0 –15 kA

 

0

– 9600 A / 0 – 30 kA

 

0

– 960 A / 0 – 3 kA

Ammeter 2

 

 

Ranges

0

– 2.000 A / 0 – 20.00 A

Maximum current

20 A (The input is not protected by

 

a fuse)

Voltmeter

 

 

Measurement method

AC, true RMS

Ranges

0

– 0.2 V, 0 – 2 V, 0 – 20 V,

 

0

– 200 V, AUTO

Inaccuracy

1% of range ±1 digit

Input resistance (Rin)

240 kΩ (range 0 – 200 V)

 

24 kΩ (other ranges)

Dielectric withstand

2.5 kV

Timer

 

 

Presentation

In seconds, mains frequency cycles

 

or hours and minutes

Ranges

0.000 – 999.9 s

 

0

– 9999 cycles

 

0.001 s – 99 h 59 min

Inaccuracy

±(1 digit + 0.01% of value)

 

For the stop condition in INT-mode

 

1 ms shall be added to the specified

 

measurement error.

Stop input

 

 

Max. input voltage

250 V AC / 275 V DC

Phase angle

 

 

Range

0

– 359º

Resolution

Inaccuracy

±2º (for voltage and current readings

 

that are higher than 10% of the

 

selected range)

Z, P, R, X, S, Q and power factor (cos φ)

For these measurements the result is calculated using U, I and sometimes φ.

Imax

Stores highest current value that exists ≥100 ms

INT-level

Threshold indicating that current is interrupted. Can be set to 0.7% or 2.1% of Ammeter 1 range.

Loading...
+ 4 hidden pages