Carrier 48HDT User Manual

4 (1)

Carrier Corporation • Syracuse, N Y 13221

Connbination Heating/Cooling Units

 

 

INDEX

 

 

 

 

Page

SAFETY CONSIDERATIONS....................................

1

INSTALLATION .......................................................

1-16

Step 1 — Provide Unit Support ..............................

1

ROOF CURB

 

SLAB MOUNT

 

Step 2 — Field Fabricate Ductwork........................

1

Step 3 — Rig and Place Unit....................................

I

POSITIONING

 

Step 4

— Install Flue Hood .....................................

3

Step 5

— Trap Condensate Drain ...........................

3

Step 6

— Install Gas Piping.....................................

3

Step 7

— Make Electrical Connections..................

3

FIELD POWER SUPPLY

FIELD CONTROL WIRING

HEAT ANTICIPATOR SETTINGS

Step 8 — Make Outdoor Air Inlet Adjust­

ments and InstallOutdoor Air Hood.....................

10

OPTIONAL OUTDOOR AIR DAMPER

OPTIONAL ECONOMIZER

Step 9 — Adjust EvaporatorFanSpeed...........

16

START-UP..............................................................

16,17

SERVICE.................................................................

18-22

SAFETY CONSIDERATIONS

Installation and servicing of air conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and quali­ fied service personnel should install, repair or service air conditioning equipment.

Untrained personnel can perform basic mainte­ nance functions of cleaning coils and filters and replacing filters. All other operations should be per­ formed by trained service personnel. When workiog on air conditioning equipment, observe precautions in the literature, tags and labels attached to the unit and other safety precautions that may apply.

Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for unbrazing operations. Have fire extinguishers available for all brazing operations.

soçipiiçtl j^$ pî|îiï^ m

above fjS

oiîit

VâiYov^îaitôihe^&Èotsoected

fiotti

Û,S

SfÊSS»!!

at

^ 45 m fern, A mk

ssaiïtîiihjî do$ü3Etg thè .gas. i?aìYe<$ìii,

"WARiilNiJc Before g«:Tf<*rî3aîït^ service

EEteîïtî£eitî3ïiee «peîatîoîîs oa

 

power switch to ’tiottEted:ricaî

cooïd

catîse

 

INSTALLATION

NOTE: 004,005,006 size units in California require the installation of an accessory NOx baffle. Refer to Accessory NOx Baffle Installation Instructions for details.

Step 1 — Provide Unit Support

ROOF CURB (Downshot Units Only) — Assemble and install accessory roof curb in accordance with instructions shipped with curb. Curb details and information required to field fabricate a roof curb are shown in Fig. 1. Install insulation, cant strips, roofing and flashing as shown. Ductwork must he

attached to curb.

Oie^sfcehsig of the

roof cîïïhis CFîîîcaJ ii>r wter i'aiegjtiij'. ïastaif ^pasîietîsîg ïoàtertaî. with the ccxif corb as

io L

Curb should be level. Unit leveling tolerance is 1/16 in. per linear foot in any direction. This is necessary for unit drain to function properly. Refer to Accessory Roof Curb Installation Instructions for additional information as required.

SLAB MOUNT (Horizontal Units Only) — Provide a level concrete slab that extends a minimum of 6 in. beyond unit cabinet. The slab should be 8 in. thick with 4 in. above grade. Install a gravel apron in front of condenser air inlet to prevent grass and foliage from obstructing airflow. Trap condensate drai.n. Allow for trap when pouring slab.

Step 2 — Field Fabricate Ductwork — On downshot units secure all ducts to roof curb and

building structure.

Insulate and weatherproof all external duct­

work, joints and roof openings with flashing and mastic in accordance with applicable codes.

Ducts passing through an unconditioned space must be insulated and covered with a vapor barrier.

A minimum clearance is not required around ductwork. Cabinet return air static shall not exceed -.35in.wg with economizer or -.45in.wg without economizer.

Step 3 — Rig and Place Unit — Inspect unit for transportation damage. File any claim with trans­ portation agency. Keep upright and do not drop.

Carrier Corporation 1984

Form 48H.L-7SI

Fig. 1 — Roof Curb Details

Spreader bars are not required if top crating is left on unit. Rollers may be used to move unit across a roof. Level by using unit frame as a reference, leveling tolerance is ± l/16in. per linear foot in any direction. See Fig. 2 for additional information. Weight is shown in Table 1.

Lifting holes are provided in base rails as shown in Fig. 2. Refer to rigging instructions on unit.

POSITIONING — Maintain clearance around and above unit to provide minimum distance from com­ bustible materials, proper airflow and service access. See Fig. 3 and 4.

Do not install unit in an indoor location. Do not locate unit air inlets near exhaust vents or other sources of contaminated air.

Although unit is weatherproof, guard against water from higher level runoff and overhangs.

Locate mechanical draft system flue assembly at least 48 in. from any opening through which com­ bustion products could enter the building, and at least 48 in. from an adjacent building. When unit is located adjacent to public walkways, flue assembly must be at least 7 ft above grade.

After unit is in position, remove polyethylene shipping wrapper and rigging skids.

Step 4 — Install Flue Hood — Flue hood and screen are shipped screwed to the basepan in furnace compartment. Remove from shipping location and using screws provided, install flue hood and screen in location shown in Fig. 3 or 4. On 48LDT004-006 units, a flue restrictor plate MUST be assembled to the flue discharge. The plate is shipped with the flue hood package. Install as shown in Fig. 5.

Step 5 — Trap Condensate Drain — See Fig. 3 or 4 for drain location. A 7/8-in. preformed drain hose is shipped clamped to the indoor basepan. At instal­ lation, re-route the hose so it passes through the hole in the indoor basepan and unit base rail.

When installed properly, the hose protrudes through the base rail one inch. Replace clamp over the hose where hose passes through the basepan to ensure that hose remains level. Use a trap at least 4 in. deep and provide protection for trap against freeze-up.

Step 6 — Install Gas Piping — Unit is equipped for use with type of gas shown on nameplate. Refer to local building codes, or, in the absence of local codes, to ANSI Z223.1-1980 entitled National Fuel Gas Code.

Natural gas pressure at unit gas connection must not be less than 5 in. wg or greater than 13.5 in. wg

 

while unit is operating.

 

Size gas supply piping for O.Sin.wg maximum

 

pressure drop. Do not use supply pipe smaller than

 

unit gas connection. See Fig. 6 for typical pipe guide

 

and location of external manual main shutoff valve.

#

For LP gas units, pressure at unit gas connection

must not be less than 12in. wg or greater than

13.5 in. wg.

 

A 1/8-in. NPT plugged tapping, accessible for test

 

gage connection, must be installed immediately up­

 

stream of the gas supply connection to the furnace.

Step 7 — Make Electrical Connections

FIELD POWER SUPPLY

004,005,006,007 — All units except 208/230-volt units are factory wired for the voltage shown on the nameplate. If the 208/230-v unit is to be connected to a 208 power supply, the transformer must be re­ wired by connecting the blue wire to C-13 and the red wire to C-DUl.

48HDD,LDD/ HD,LD008 — 230and 460-volt units are factory wired for the voltage shown on nameplate. If unit will be connected to a 208 power supply, the transformer must be rewired by connect­ ing the black wire to the 200-volt lead and insulating the 230-volt lead.

48HHD,LHD/HH,LH008 — 230and 460-volt units are factory wired for the voltage shown on nameplate. If 208/ 230-voIt unit will be connected to a 208 power supply, the transformer must be rewired by connecting the blue wire to C-13 and red wire to C-DUL

All Units — Refer to unit label diagram for addi­ tional information. Pigtails are provided for field service. Use factory-supplied splices or ULapproved copper/aluminum connector.

When installing units, provide a disconnect per NEC.

All field wiring must comply with National Elec­ trical Code and local requirements.

Install conduit connectors in side panel openings indicated in Fig. 3 or 4. Route power lines through connector to terminal connections as shown in Fig. 7.

Voltage to compressor terminals during opera­ tion must be within voltage range indicated on unit nameplate (also see Table 2). On 3-phase units, voltages between phases must be balanced within 2% and the current within 10%. Use the formula shown in Table 2, Note 2 to determine the % voltage imbalance. Contact local power company for cor­ rection of improper voltage or phase imbalance. Operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electrical components. Such operation, would invalidate any applicable warranty.

FIELD CONTROL WIRING ^ Install a Carrierapproved accessory thermostat assembly according to installation instructions included with the acces­ sory. Locate thermostat assembly on a solid wall in the conditioned space to sense average temperature.

Carrier 48HDT User Manual

 

 

 

 

=-=^--A ;y.

 

 

 

 

 

'iigSBEf^^ L

. . ' ^

I

 

: _ __

. . ^

s

1

 

' ‘x-b*’

 

 

 

I

 

 

.%'^CTO^^jNf<»i'pT79W’^ifl^W99«<%CMSiW».wW.w3^‘fW«<v?0%''Xww^

■•s .• s

Fig. 2 — Rigging Details

L

Table 1 — Physical Data

UNIT SIZE 48 SERIES

 

004

 

005

 

 

006

 

006

007

 

008

 

 

 

008

 

OPER WT (lb)

 

 

LDT

 

HDT ] LDT

 

HDT

 

LDT

HH

 

LH

HD

 

HH

HD.HH

 

 

LD.LH

 

 

HDD.HLD

LDD.LHD

Unit

 

 

 

630

 

650 630

660

 

640

660

 

640

720

 

720

890

 

886

 

 

 

945

941

with Economizer

 

655

 

675 1 655

 

685

 

665

 

745

 

_

950 (HD)

 

 

946 (LD)

 

1005(HDD)

996 (LDD)

Roof Curb

 

 

130

 

130

 

 

130

 

130

 

125 (HD)

 

 

125 (LD)

 

 

125 (HDD)

125 (LDD)

COMPRESSOR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Qty Type

 

 

1 M4023E

 

1 P53260

1 P6026B

1 P60-6-

1 P77

1 Hermetic

 

 

 

2 P46

Oil (oz)

 

 

42

 

66

 

 

66

 

74

74

 

124

 

 

 

124

 

REFRIG (R-22)

 

 

61

 

 

 

 

 

 

 

Capillary Contre

 

 

 

 

9 9

 

 

 

 

 

Charge (lb)

 

 

48

 

 

72

 

 

7 2 I 9 3

 

 

 

 

 

 

6 2 per system

COND COIL

 

 

2

 

2

 

 

 

 

Copper Tube, Aluminum Plate Fins

 

 

 

 

 

 

 

 

 

 

 

Rows

 

 

 

 

 

 

 

 

 

2

 

:

 

 

 

 

 

 

 

 

2

 

 

Fins/in

 

 

170

 

170

 

 

140

 

14 0

140

 

 

 

 

139

 

 

Total Face Area (sq ft)

 

6 3

 

6 3

 

 

9 73

 

9 73

108

 

 

 

 

15 6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COND FAN

 

 

2200

 

3100

 

 

3800

 

Propeller Type

4000

 

 

 

 

 

 

 

 

 

Nom Cfm

 

 

 

 

 

 

3800

 

 

 

 

4500

 

 

Qty Diam (in )

 

 

1 22

 

1 22

 

1

22

1

22

1

22

 

 

 

 

 

 

22

 

 

Motor Hp

 

 

%

 

’/2

 

 

’/2

 

’/2

'/2

 

 

 

 

 

’/2

 

 

Motor Rpm

 

 

850

 

1075

 

 

1075

 

1075

1075

 

 

 

 

1075

 

 

EVAP COIL

 

 

2

 

2

 

 

 

 

Copper Tube, Aluminum Plate Fins

 

 

 

 

 

 

 

 

 

 

 

Rows

 

 

 

 

 

 

 

 

 

3

 

A

 

 

 

 

 

 

3

 

 

Fins/in

 

 

140

 

140

 

 

140

 

140

140

 

 

 

 

13 9

 

 

Total Face Area (sq ft)

 

5 33

 

5 33

 

 

5 33

 

5 33

6 3

 

 

 

 

 

 

8 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EVAP FAN

 

 

 

 

 

 

HDT

 

LDT

HH

 

LH

 

 

 

 

 

 

 

 

 

 

 

 

Qty Size (in )

 

 

1 10x10

 

1 10x10

1 11x10

 

1 11x10

1 11x10

 

1 11x10

1 11x10

 

1

 

12x12

 

Type

 

 

 

DD

 

DD

 

DD

 

DD

BD

 

DD

BD

 

 

 

 

 

BD

 

 

Nom Cfm

 

 

1200

 

1500

 

2000

 

2000

2000

 

2000

2200

 

 

 

 

3000

 

 

Motor Hp Std

 

 

'/3

 

3/4

 

1

 

3/4

’/2

 

3/4

3/4

 

 

 

 

1 0

 

 

 

 

 

Opt

3/4

 

 

 

1

3/4

 

1

1

 

 

 

 

 

1 5

 

 

Nom Motor Rpm

 

 

 

 

 

1725

 

_

1725

 

 

 

 

 

 

 

 

Std/Opt Low

 

 

800/ 890

 

890

 

1000

 

890/1000

__

 

890/1000

 

 

 

 

 

 

 

_

 

 

 

 

High

 

850/1050

 

1000

 

1130

 

1050/1130

 

1050/1130

 

 

 

 

 

 

 

 

 

 

 

Rpm Range Std

 

 

 

 

 

630960

 

-

796-

130

 

 

838-1032 (@2 turns open)

 

 

 

 

Opt

 

 

 

796-1130

 

930-1260

 

 

 

352-11 27 (@ 1 turn open)

 

Motor Pulley

 

Std

 

 

 

 

 

 

 

1 9-2 9

 

 

2 4-3 4

 

 

 

 

2 4-3 4

 

Pitch Diam

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Opt

 

 

 

 

 

 

 

2 4-3 4

 

 

2 8-3 8

 

 

 

 

2 4-3 4

 

(in )

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fan

Pulley

 

Std

 

 

 

 

 

 

 

5 2

 

 

5 2

 

 

 

 

50

 

 

Pitch

Diam

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Opt

 

 

 

 

 

 

 

5 2

 

 

5 2

 

 

 

 

5 0

 

 

(in )

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Belt. Qty Type. Length (in

 

 

 

 

 

 

 

 

 

 

 

1 A 43

 

 

 

 

 

 

 

 

 

Speed Change per Full

Std

 

 

 

 

 

 

 

66

 

 

66

 

 

 

 

65

 

 

Turn of Moveable

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pulley Flange (Rpm)

Opt

 

 

 

 

 

 

 

66

 

 

66

 

 

 

 

69

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Moveable Pulley

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Max Full Turns

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

from Closed Position

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory Setting

 

Std

 

 

 

 

 

 

 

2

 

 

 

2

 

 

 

 

 

 

4

 

 

Full Turns Open

 

Opt

 

 

 

 

 

 

 

2

 

 

 

2

 

 

 

4Y2

 

 

Factory Speed

Setting

Std

 

 

 

 

 

 

 

830

 

 

995

 

 

 

 

907

 

 

(Rpm)

 

Opt

 

 

 

 

 

 

 

995

 

 

1130

 

 

 

 

885

 

 

FURNACE SECTION

 

 

LDT

 

HDT

LDT

HDT

 

LDT

HH

 

LH

HD

 

HH

HD.HH

 

 

LD.LH

 

 

HHD.HDD

LDD.LHD

Temp Rise (F)

 

 

30-60

35-65

30-60

35-65

30-60

35-65

30-60

35-65

35-65

35-65

 

 

15-45

 

 

35-65

15-45

Heating Input (Btuh)

 

80,000

120,000

80,000

1 20,000

80,000

120,000

80,000

120,000

120,000

203,000

 

114,000

 

 

203,000

114,000

Output Cap (Btuh)

 

61,600

92,400

61,600

92,400

61,600

92,400

61,600

92,400

92,400

160,370

 

91,200

 

 

160,370

91,200

Burner Orifice Diam

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(in . drill size)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Natural Gas

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

132 29

 

113 33

 

 

132 29

113 33

Pilot Orifice Diam

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(in drill size)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Natural Gas

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

036 64

 

033 66

 

 

036 64

033 66

Thermostat Heat Anticipator

 

 

 

 

 

1 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 2

 

 

Setting

460v

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208/230V

 

 

 

 

 

1 0

 

 

 

 

 

 

 

 

 

 

1 0

 

 

HIGH-PRESS SWITCH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cutout (psig)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

426

±

7

 

Reset (psig)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

320 ± 20

 

LOW-PRESS SWITCH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Suction Line)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cutout (psig)

 

 

 

 

 

 

 

27 ± 4

 

 

 

 

 

 

 

 

 

 

27

±

4

 

Reset (psig)

 

 

 

 

 

 

 

67 ± 7

 

 

 

 

 

 

 

 

 

 

67 ± 7

 

 

AIR INLET SCREENS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Qty. Size (in )

 

 

 

 

 

 

 

 

1 32X19XV2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RETURN AIR FILTERS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Qty Size (in )

 

 

 

 

 

 

 

 

1 16X25X1

 

 

 

 

 

 

 

2

 

16X20X1

 

 

 

 

 

 

 

 

 

1...20x25x1

 

 

 

 

 

 

 

 

 

2 20X20X1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DD — Direct Drive

#

----------- . •*.*

Fig. 3 — Downshot Base Unit Dimensions

Fig. 4 — Horizontal Base Unit Dimensions

*NPT plug is field supplied NOTE Follow all local codes

Fig. 6 — Gas Piping Guide

Fig. 5 — Flue Hood Details;

48LDT004-006 Units

BLK-

-YEL

-i?

 

 

 

 

 

 

 

 

 

EQUIP

 

 

 

 

 

 

 

GND

 

 

 

 

 

 

I-------

UM

 

 

 

 

 

 

I

 

 

 

 

 

 

FIELD POWER SUPPLY

 

 

 

 

230-1-60

'“DTSCONNECTI

 

 

 

 

 

u_PifLNJc_l

 

 

 

 

 

004,005,006,007 UNITS

 

 

 

 

 

 

BLK

 

 

 

 

BLK •

 

 

■ YEL •

I

 

 

 

■ YEL ■

 

 

 

 

 

 

 

 

 

 

I

 

 

 

 

 

 

 

I

 

 

 

 

 

 

 

 

 

EQUIP

 

 

 

EQUIP

 

 

 

GND

 

 

 

GND

BLU-

 

I—dn

 

-BLU-

I

--Q®]

 

 

I

 

 

 

I

 

44

 

 

 

I

 

H--------

 

 

-I+ H--------

TO

FIELD POWER SUPPLY

TO INDOOR

FIELD POWER SUPPLY

 

 

 

 

 

 

COMP

roTsCONNECT"!

 

FAN CONTACTOR

TI^SCONNE'CT”!

I

208/230-3-60 (SEE NOTE)

PER NEC

 

 

I

PER NEC

 

 

 

 

004,005,006,007 UNITS

 

 

 

008 UNITS

 

 

 

Factory

Wiring

 

 

 

 

 

. Field Wiring

 

 

 

 

 

NOTE If

connected to 208-v

power supply, rewire unit transformer

 

 

 

no 1 by

 

 

 

 

 

 

1Connecting blue wire from transformer no 1 to C-13

2Connecting red wire from transformer no 1 to C-DUl

Fig. 7 — Power Wiring Connections

8

Loading...
+ 18 hidden pages