Xylem MM 619F User Manual

Series FS6 Flow Switch
INSTRUCTION MANUAL
MM-619F
SPECIFICATIONS
Maximum Liquid Pressure: 100 psi (7 kg/cm2)
Ambient Temperature Range (T
): 32 - 225˚F (0 - 107˚C)
L
): 32 - 120˚F (0 - 49˚C)
S
Electrical Enclosure Rating: Nema Type 1 (IP 21) (All models except “W”)
Nema Type 4X (IP 56) (“W” models)
Maximum Velocity: 10ft/sec (3M/sec)
Pipe Connection Thread Size:
3
/4” or 1” NPT (All models except “J”)
3
/4” or 1” BSPT (“J” models)
ELECTRICAL RATINGS
Motor Switch Rating (Amperes)
Voltage Full Load Locked Rotor Pilot Duty
120 VAC 7.4 44.4 240 VAC 3.7 22.2
125 VA at
120 or 240 VAC
50 or 60 cycles
2
FLOW RATES
FS6 VELOCITIES IN FPS
40
30
20
10
VELOCITY IN FEET PER SECOND
GPM CAPA
CITY
10 20 30 40 50 60 70
FS6-
3
/
4
"
PIPE
FS6-1"
PIPE
Flow rates required to activate the flow switch are shown in chart below.These values were
calculated using clean water in a horizontal pipe.
Flow Rates
Pipe
Mode of Operation
Size NPT Flow No Flow in. (mm) Settings gpm (lpm) gpm (lpm)
3
4
or Minimum .12 (.45) .06 (.23)
1 (25)
Values are ± 10%
90
80
70
60
50
40
30
20
DIFFERENTIAL PRESSURE
10
Factory or
(20)
Maximum 2.5 (9.46) 1.5 (5.68)
FS6 SERIES PRESSURE DROP
Max. Flow
Rate gpm (lpm)
w/o Paddle
Damage
70 (265)
Settings will vary when used to sense flow of other fluids.
NOTE: THIS PRODUCT IS NOT INTENDED
FOR USE IN POTABLE WATER
APPLICATIONS.
NOTE: DO NOT USE LIQUID FLOW
SWITCHES ON SYSTEMS WITH FLOW VELOCITY GREATER THAN 10 FEET (3M) PER SECOND.
INSTALLATION –
STEP 1 - Determine the Location of the Flow Switch
• The flow switch should be located in a horizontal section of pipe where there is a straight horizontal
run of at least 5 pipe diameters on each side of the flow switch.
• The flow switch must be installed in the upright position as shown with arrow mark on side of casting in the same direction as fluid will flow.
• Some system conditions that require more than 5 pipe diameters are high viscosity fluid and high fluid velocity.
10 20
30 40 50 60 70
GPM CAPA
CITY
3/4" or 1" PIPE
5 x D
MINIMUM
D
5 x D
MINIMUM
D= PIPE DIAMETER
3
STEP 2 - Connecting the Flow Switch to Pipe
a. Apply pipe sealing compound or
PTFE
tape to the
pipe threads.
NOTE: Do not apply sealant to first threads as this switch is grounded (earthed) via the pipe mounting.
b. Insert pipe threads into flow switch and turn 2
or 3 times until tight.
• Place one pipe wrench on hex fitting of flow switch and one wrench on connecting piping. Tighten to following torque values.
- 47 ft•lb (64 N•m) for 3/4” pipe
- 63 ft•lb (85 N•m) for 1” pipe
PTFE
• Repeat to connect pipe to opposite side of flow switch.
4
STEP 3 - Electrical Installation
• To prevent electrical shock, turn off the electrical power before making electrical connections.
• To prevent an electrical fire or equipment damage, electrical wiring insulation must have a rating of 167˚F (75˚C) if the liquid’s temperature exceeds 180˚F (82˚C).
• To prevent electrocution, when the electrical power is connected to the flow switch, do not touch the terminals.
• Make sure flow switch electrical cover is secured before turning on electric power.
Failure to follow this warning could cause property damage, personal injury or death.
WARNING
!
a. Cover Removal and Installation Procedure
For FS6 models with NEMA 1 Enclosure
• Using a flathead screwdriver, loosen but do not remove the two cover screws and remove the cover (A).
• Place the cover on the flow switch sliding the slots behind the two loose cover screws. Push the cover down into the flow switch and using a flat blade screwdriver, tighten the cover screws to a torque of 10 lb•in (1.13 N•m).
For FS6-W models with NEMA 4X Enclosure
• Using flathead screwdriver, unscrew the six cover screws and remove cover.
• Place the electrical connection cover on the flow switch and insert the six cover screws. Tighten the screws to a torque of 10 lb•in (1.13 N•m).
A
b. Electrical Conduit Connection
• Connect electric conduit to flow switch electrical enclosure.
• Follow accepted electrical practices when installing fittings and making connections.
• Refer to and follow local codes and standards when selecting the types of electrical fittings and conduit to connect to flow switch.
5
c. Determine which switch action is required for the
flow switch.
• “Flow” means that the switch will close circuit C.-N.O. and open circuit C.-N.C. when flow rate is increased above setpoint of flow switch.
• “No Flow” means that the switch will open circuit C.-N.O. and close circuit C.-N.C. when flow rate is decreased below setpoint of flow switch.
C. N.O
FLOW
.
N.C.
C. N.O
.
NO FLOW
N.C.
d. Based upon the mode of operation (“Flow” or “No-
Flow”) required, complete the appropriate steps to connect wires to flow switch. Use a Phillip’s head screwdriver to loosen and tighten switch terminal screws when attaching wires.
For “Flow” Mode of Operation (Fig. 1)
If the flow switch will be used to actuate a signal, alarm or other device when flow occurs, connect the wire from that device to the “N.O.” contact. Connect the “Hot” power supply wire to “C” terminal.
For “No Flow” Mode of Operation (Fig. 2)
If the flow switch will be used to actuate a signal, alarm or other device when no flow occurs, connect the wire from that device to the “N.C.” contact. Connect the “Hot” power supply wire to “C” terminal.
Common
(
Common
1
(
Normally
(
Flow Closes Circuit
open
Flow Opens Circuit
2
3
Nor
mally
(
(
closed
(
FS4-3
31
2
Fig. 1
HOT
LINE
LOAD
FS4-3
31
2
Fig. 2
LINE
HOT
LOAD
6
STEP 4 - Testing
a. Place cover on flow switch and turn on power. Initiate
fluid flow through the system. Observe the device being activated by the flow switch to determine if device is operating as required.
b. Turn off fluid flow to determine if device is operating
as required.
c. Repeat initiating and turning off fluid flow several times to
test flow switch and device for proper operation.
- If operating as required, put system into service.
- If not operating as required, flow switch may need to be adjusted.
ON
OFF
STEP 5 - Adjustment
Adjustment is necessary only if required flow/no flow setpoints are above factory set minimum.
a. Turn off power.
b. Locate adjustment lever on bottom of unit.
Note that lever will be perpendicular to flow switch body.
c. Loosen adjustment lever screw but DO NOT
REMOVE.
d. Turn adjustment lever counter-clockwise to
increase setpoint. Maximum setting is with adjustment lever parallel with flow switch body.
e. Tighten adjustment lever screw.
f. Turn on power.
g. Test the operation of the flow switch after
each adjustment.
ADJUSTMENT DATA
(All flow rates given in GPM - gallons per minute)
FLOW
Flow
0.12
No Flow
0.06
MINIMUM
ADJUSTMENT
Adjustment Lever Screw
Flow
No Flow
MAXIMUM
ADJUSTMENT
The Flow Rates Shown Are Averages, May Vary –10%
2.5
1.5
7
MAINTENANCE
TROUBLESHOO
TING
SCHEDULE:
nspect and clean annually. Turbulent or high
• I flow velocity conditions may require more frequent inspection and/or replacement.
• Replace flow switch every 5 years or 100,000 cycles, whichever occurs first.
Problem:
1. Flow Switch Does Not Operate Solution: a. Make sure power has been turned on to device
and flow switch.
b. Verify that flow rate is high enough for flow sw
to activate. Measure flow rate and match with velocities shown in flow rate chart.
c. Flow switch may be located to sense flow in
polluted (scale, rust, sludge, etc.) water. Relocate switch to a pipe that senses flow of non-polluted water.
2. Flow Switch Operates Erratically Solution: a. Adjustment screw may have been turned below
r
iginal factory setpoint. Verify that flow rate is high
o
ough for flow switch to activate. Measure flow
en rate and match with velocities shown in flow rate chart.
b. Flow switch may be located to sense flow in
polluted (scale, rust, sludge, etc.) water. Relocate switch to a pipe that senses flow of non-polluted water.
itch
3. Flow Switch Does Not Deactivate Solution:
Me
asure flow rate and match with velocities shown
a.
in
flow rate chart. Flow switch must prove flow
before it can indicate no flow.
b. Flow switch may be located to sense flow in
polluted (scale, rust, sludge, etc.) water. Relocate switch to a pipe that senses flow of non-polluted water.
Xylem Inc.
8200 N. Morton Grove, Illinois 60053 Phone: (847) 966-3700 Fax: (847) 965-8379 www.mcdonnellmiller.com
McDonnell & Miller is a trademark of
© 2014 Xylem Inc. MM-619F March 2014 Part No. 210413
Austin Avenue
Xylem Inc. or one of its subsidiaries.
Loading...