Xylem MM 301C User Manual

INSTRUCTION MANUAL
MM-301C
MAINTENANCE
SCHEDULE:
Daily
Blow down when boiler is in operation if boiler operating pressure is above 15 psi.
Weekly
Blow down when boiler is in operation if boiler operating
pressure is below 15 psi.
Annually
Disassemble and inspect/clean strainer screen.
Replace if screen is torn or not able to be cleaned.
Remove and inspect/clean cartridge.
Replace if poppet does not move freely
cannot be removed.
Remove head and inspect internal parts.
Clean out all mud, silt, sediment and debris from chamber, float mechanism and other waterside
components.
Inspect equalizing piping.
Clean or replace as
required.
Check for leaks at gasket surface and solder joints.
or debris
NOTE
Use clean water to rinse components and surfaces. DO
NOT use sharp objects to scrape off any accumulations
of sediment or debris.
Replace entire unit including equalizing piping every 10 years. More frequent cleaning or replacement may be required if used in locations where water treatment is required or in applications with high make-up water requirements.
WARNING
!
• Before using this product read and understand instructions.
CAUTION
WARNING
• Save these instructions for future reference.
• All work must be performed by qualified personnel trained in the proper application, instal­lation, and maintenance of plumbing, steam, and electrical equipment and/or systems in
accordance with all applicable codes and ordinances.
• To prevent serious burns, the boiler must be cooled to 80˚F (27˚C) and the pressure must be 0 psi (0 bar) before servicing.
California Proposition 65 warning! This product contains chemicals known to the
state of California to cause cancer and birth defects or other reproductive harm. Previous controls should never be installed on a new system. Always install new
controls on a new boiler or system.
Failure to follow this warning could cause property damage, personal inj ury or death.
CAUTION:
A more frequent replacement interval may be necessary based on the condition of the unit at time of inspection. McDonnell Miller s warranty is one (1) year from date of installation or two (2) years from the date of manufacture.
!
&
'
Xylem Inc.
8200 N. Austin Avenue Morton Grove, Illinois 60053 Phone: (847) 966-3700 Fax: (847) 965-8379 www.xyleminc.com/brands/mcdonnellmiller
McDonnell & Miller is a trademark of Xylem Inc. or one of its subsidiaries.
© 2013 Xylem Inc. MM-301C July 2013 Part No. 246770