Xylem MM 284D User Manual

INSTRUCTION MANUAL
MM-284D
Operation
The Ser
ies PSE-800 probe type LWCO’s provide protection against low water conditions for residential and commercial steam boiler applications. The control uses patented technology to monitor changes in water conductivity. When defined parameters are exceeded, the new PSE-800 makes a decision to shut the burner off based on the volatility/variability
SPECIFICA
A
utomatic reset after power outage
All models include a provision for adding an alarm or automatic water feeder.
30 second Delay on Make (DOM)
10 second Delay on Break (DOB)
Contr T
T
Humidity: 85% (non-condensing)
ol Unit
emperature Ratings:
emperature:
Storage: -40˚F to 135˚F (-40˚C to 57˚C)
Ambient: 32 F to 120 F (0 C to 4 C)
TIONS
oo
o
o
9
of the resistance readings. This new patented technology provides the best protection possible without turning off the boiler unless a low water condition exists. As an added measure of safety, the control will turn off the boiler if it recognizes an out-of-water condition when the sensitivity threshold is exceeded.
Green
(Power On)
Red
(Low Water)
obe Specifications
Pr
Maxim Pr
HZ: 50/60
Contr
1.7VA @ 24VAC
3.6VA @ 120VAC
Electrical Enclosure Rating: NEMA 1 General Purpose
um Steam Pressure: 15 psi (1.0 kg/cm
obe Sensitivity: 7,000 ohm
Model
PSE-802-24 PSE-802-U-24 PSE-802-RX2-24 PSE-801-120 PSE-801-U-120
ol Power Consumption:
24 VAC N/A 50VA
120 VAC 7.5 FLA 43.2 LRA 125VA
2
)
Pilot Rating
2
INST
T
ALLATION
OOLS NEEDED:
One (1) flathead screwdriver, and one (1) pipe wrench. For Remote Installations a level and power drill will be required.
STEP 1 - Locating and Installing the Pr
a. Based on the f
For all Applications:
1. Refer to boiler manufacturers instructions to determine suitable tapping for the probe.
2. Make sure probe is installed above minimum safe water line as determined by the boiler manufacturer.
3. Make sure that ends and sides of the probe are at least 1/4” (6.4mm) from all internal metal surfaces.
4. sure the probe is positioned to shut off
Make the boiler before the water level falls below the lowest visible part of the gauge
b. Sparingly, apply pipe sealant to the ext
threads (D) of the (A).
ollowing criteria locate a suitable position for the probe:
glass.
ernal
probe
obe
4
A
1/4"
3
(6mm)
1
1/4"
(6mm)
Minimum Safe
Water Level
(May vary
by boiler
manufacturer)
A
D
Control
Steam
Boiler
Probe
IMPORTANT: Do not use tape. Only use
04&%
pipe sealant.
c. Using a wrench, tighten the probe (A) into the
tapped connection (E) that w
as determined in Step 1 of these instructions. Tighten to 47 ft•lb (64 N•m). NOTE: Be sure to align the probe so that the mounting scre
STEP 2 - Installing Contr
ws (F) are in a horizontal position.
ol Box
a. Using a flathead screwdriver, loosen the two (2) screws
that secure the cover (G) to the control about 1-1/2 turns and remove cover.
F
E
A
G
3
Loading...
+ 5 hidden pages