Xylem IM201 User Manual

ITT
Goulds Pumps
CentriBoost™
Fixed Speed Pumping Package
Installation, Operation and Maintenance Instructions
Commercial Water
Goulds Pumps is a brand of ITT Residential and Commercial Water.
Engineered for life
Single or dual pump pressure booster for boosting system pressure by as much as
55 PSI. The pump is automatically controlled to run on demand to save energy.
SECTION 1 - Safety Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
- General Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
- Purpose of Manual. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
- Storage and Handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
- Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
SECTION 2 - Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
SECTION 3 - Putting the Unit into Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
- Adjustments and Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
SECTION 4 Final Check Lists
- Start Up Check List - Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
- Start Up Check List - Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
SECTION 5 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-7
APPENDIX 1 Programmable Pump Sequence Control Module for Duplex Units . . . . . . . . . . . . . . . . . . . . . . . . . . 8
FIELD PIPING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
LIMITED WARRANTY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
NOTE: The information contained in this manual is intended to assist operating personnel by providing information on the
characteristics of the purchased equipment.
It does not relieve the user of the responsibility to adhere to local codes and ordinances and the use of accepted prac-
tices in the installation, operation and maintenance of this equipment.
Further information pertaining to the installation, operation and maintenance of your CentriBoost Pumping System can
be found in the Installation, Operation and Maintenance manuals for the associated equipment provided:
A. Goulds Pumps Model NPE
B. Tank (Model Specific)
Owner’s Information
Owner’s Information
Pump Model Number:
Pump Serial Number:
Control Model Number:
Dealer:
Dealer Phone No.
Date of Purchase: Installation:
Current Readings at Startup:
Amps:
Volts:
2
SECTION 1
dANGER
WARNING
CAUTION
WARNING
WARNING
WARNING
SAFETY INSTRUCTIONS
TO AVOID SERIOUS OR FATAL PERSONAL INJURY OR MAJOR PROPERTY DAMAGE, READ AND FOLLOW ALL SAFETY INSTRUCTIONS IN MANUAL AND ON PUMP.
THIS MANUAL IS INTENDED TO ASSIST IN THE INSTALLATION AND OPERATION OF THIS UNIT AND MUST BE KEPT WITH THE PUMP.
This is a SAFETY ALERT SYMBOL. When you see this symbol on the pump or in the manual, look for one of the fol­lowing signal words and be alert to the potential for personal injury or property damage.
Warns of hazards that WILL cause serious personal injury, death or major property damage.
Warns of hazards that CAN cause serious personal injury, death or major property damage.
Warns of hazards that CAN cause per­sonal injury or property damage.
NOTICE: INDICATES SPECIAL INSTRUCTIONS
WHICH ARE VERY IMPORTANT AND MUST BE FOLLOWED.
THOROUGHLY REVIEW ALL INSTRUCTIONS AND WARNINGS PRIOR TO PERFORMING ANY WORK ON THIS PUMP.
MAINTAIN ALL SAFETY DECALS.
GENERAl dESCRIpTION
The CentriBoost pumping package is a fixed constant speed, and will increase the domestic water pressure at the fixtures from 20 to 55 PSI above that of the city water pressure.
Depending upon the pumping capacity required, a Sim­plex (one pump) type or a Duplex (two pump) type is used. In both types, a pressure switch starts and stops the pump(s).
TICES. FAILURE TO FOLLOW THESE INSTRUC-
TIONS COULD RESULT IN SERIOUS PERSONAL INJURY, DEATH, AND/OR PROPERTY DAMAGE.
PREVENT ELECTRICAL SHOCKS. DISCONNECT THE POWER SUPPLY
BEFORE BEGINNING INSTALLATION. FAILURE TO
FOLLOW THESE INSTRUCTIONS COULD RESULT IN SERIOUS PERSONAL INJURY, DEATH AND/OR PROPERTY DAMAGE.
Always use accurate test meters when checking electrical components. Always work with another person in case of emergency.
STORAGE
For long periods of storage, the unit should be covered to prevent corrosion and contamination from dirt. It should be STORED in a clean, dry location between 0 and 170° F. The relative humidity should not exceed 85%. The unit should be checked periodically to ensure that no condensation has formed. After storage, again check that it is dry before applying power.
HANdlING
Care should be taken to prevent damage due to dropping or jolting when moving the CentriBoost. Transportation damage should be brought to the carrier's attention im­mediately upon receipt.
TEmpERATURE ANd VENTIlATION
All electrical equipment is susceptible to failure if oper­ated in ambient temperatures outside of its rating. The OPERATING temperature range for this unit is 32 to 105° F. The relative humidity should not exceed 95% non-condensing. The unit should not be operated outside these extremes.
ElECTRICAl CONNECTIONS - A.C. pOWER ANd SIGNAlS INpUT VOlTAGE
The input voltage tolerance is +10/-10% of nameplate voltage.
pURpOSE OF mANUAl
This manual is furnished to acquaint you with some of the practical ways to install, operate and maintain this unit. Read it completely before doing any work on your unit and keep it handy for future reference.
Equipment cannot operate well without proper care. To keep this unit at top efficiency, follow the recommended installation and servicing procedure outlined in this manual.
AddITIONAl SAFETY REQUIREmENTS
ELECTRICAL SHOCK HAZARD.
INSPECT ALL ELECTRICAL CONNEC­TIONS PRIOR TO POWERING THE UNIT. WIRING CONNECTIONS MUST BE MADE BY A QUALIFIED ELECTRICIAN IN ACCORDANCE WITH ALL APPLI­CABLE CODES, ORDINANCES AND GOOD PRAC-
GROUNd CONNECTIONS
A grounding terminal is provided for a dedicated ground wire connection. All provisions of the National Electrical Code and local codes must be followed.
CONDUIT GROUNDS ARE NOT AD-
EQUATE. A SEPARATE GROUND WIRE MUST BE ATTACHED TO THE GROUND LUG PRO­VIDED IN THE ENCLOSURE TO AVOID POTENTIAL SAFETY HAZARDS. FAILURE TO FOLLOW THESE
INSTRUCTIONS COULD RESULT IN SERIOUS PERSONAL INJURY, DEATH AND/OR PROPERTY DAMAGE.
pOWER WIRING
Power wire types and sizes must be selected based upon conformance with the National Electrical Code and all local codes and restrictions. In addition, only copper
3
(Cu) wire rated for at least 75° C may be used for the
dANGER
WARNING
WARNING
WARNING
CAUTION
power connections. Refer to the input current as listed on the motor nameplate when sizing wire.
cut out. If the system does not include the other devices, consult the responsible engineer or architect before mak­ing pumps operational.
FIEld CONNECTION dIAGRAmS
Refer to the NPE pump Installation, Operation and Main­tenance manual for specific details unique to the pump.
The following field connection diagrams should be re­viewed prior to unit installation and operation.
Drawing # Description Page
1MBD02 Piping: Simplex 8
1MBD03 Piping: Duplex 9
1SWD01 or Wiring, Simplex 1SWD02 (shipped with unit)
1SWD03 Wiring, Duplex (shipped with unit)
1380 (shipped with unit)
_ _
Unit specific Drawing
SECTION 2
INSTAllATION INSTRUCTIONS
Locate the pumping unit for ease of inspection, mainte­nance, and service.
Place the unit preferably on a concrete floor or base. Level the steel base, on which the pumps are mounted, in both directions by placing steel shims between the base and the anchor bolts.
HEAVY LOAD, MAY DROP IF NOT
LIFTED PROPERLY. DO NOT LIFT THE ENTIRE UNIT BY THE MOTOR EYEBOLTS. LIFT THE UNIT WITH SLINGS PLACED UNDER THE UNIT BASE RAILS. FAILURE TO FOLLOW
THESE INSTRUCTIONS COULD RESULT IN SERI­OUS PERSONAL INJURY, DEATH AND/OR PROP­ERTY DAMAGE.
A well-leveled and secured unit will result in quiet opera­tion as well as longevity of service.
See drawing 1MBD02 (Simplex) or 1MBD03 (Duplex) in Section 6 for general piping requirements.
Eccentric increasers can be used in the suction line when increasing the pipe size. The straight side of eccentric reducers should be installed with the flat side on top to eliminate air pockets. Support the suction and discharge lines independently by the use of pipe hangers or an­chors. Do not attempt to spring the suction and dis­charge lines into position. It is recommended that a three (3) valve by-pass between the suction and discharge be installed at this time. See drawing 1MBD02 or 1MBD03 for location of valves.
IMPORTANT: Do not install and operate Goulds pumps in closed systems unless the system is constructed with properly sized safety devices and control devices. Such devices include the use of properly sized and located pressure relief valves, compression tanks, pressure controls, temperature controls and flow controls as ap­propriate. The CentriBoost includes a high temperatures
4
THE HEATING OF WATER AND
OTHER FLUIDS CAUSES VOLUMET­RIC EXPANSION. THE ASSOCIATED FORCES MAY CAUSE FAILURE OF SYSTEM COMPONENTS AND RELEASE OF HIGH TEMPERATURE FLUIDS. THIS WILL BE PREVENTED BY INSTALLING PROPERLY SIZED AND LOCATED PRESSURE RELIEF VALVES AND COMPRESSION TANKS. FAILURE TO FOL-
LOW THESE INSTRUCTIONS COULD RESULT IN SERIOUS PERSONAL INJURY, DEATH AND/OR PROPERTY DAMAGE.
IMPORTANT: Unless the piping to which the vibra-
tion eliminators are connected to are properly anchored to the floor, the benefits may not be fully realized. See drawing 1MBD02 (Simplex) or 1MBD03 (Duplex).
ELECTRICAL SHOCK HAZARD.
INSPECT ALL ELECTRICAL CONNEC­TIONS PRIOR TO POWERING THE UNIT. WIRING CONNECTIONS MUST BE MADE BY A QUALIFIED ELECTRICIAN IN ACCORDANCE WITH ALL APPLI­CABLE CODES, ORDINANCES, AND GOOD PRAC­TICES. FAILURE TO FOLLOW THESE INSTRUC-
TIONS COULD RESULT IN SERIOUS PERSONAL INJURY, DEATH, AND/OR PROPERTY DAMAGE.
The power supply required for the unit is either 230/1/60 or 208, 230, 460/3/60 with a dedicated ground wire. Single phase motors have internal overload protection and three phase motors have external overload protec­tion in the control panel.
On single phase units the disconnecting means and short circuit protection are to be supplied and mounted by others. Three phase units have disconnecting means and fuses for short circuit protection in the control panel.
For units installed with an optional tank, the tank must be installed to the top connection of the discharge cross for simplex units and the discharge manifold for duplex units (see 1MBD02 or 1MBD03). Precharge the tank per the tank specific IOM.
For units installed with an optional low suction pressure switch, the switch, which typically ships loose, must be piped to the inlet ¼" tap on the check valve for simplex units or on of the ¼" tap on the suction manifold for du­plex units (see 1MBD02 or 1MBD03). See section 3.10 for instructions on setting the switch.
CONDUIT GROUNDS ARE NOT AD-
EQUATE. A SEPARATE GROUND WIRE MUST BE ATTACHED TO THE GROUND LUG PRO­VIDED IN THE ENCLOSURE TO AVOID POTENTIAL SAFETY HAZARDS. FAILURE TO FOLLOW THESE
INSTRUCTIONS COULD RESULT IN SERIOUS PERSONAL INJURY, DEATH AND/OR PROPERTY DAMAGE.
SEAL DAMAGE MAY OCCUR. DO
NOT RUN PUMPS DRY. FILL AND VENT THE PUMP VOLUTE PRIOR TO OPERATION.
FAILURE TO FOLLOW THESE INSTRUCTIONS COULD RESULT IN PROPERTY DAMAGE AND/OR MODERATE PERSONAL INJURY.
Loading...
+ 8 hidden pages