SUPPLEMENT TO THE INSTALLATION AND OPERATION MANUAL (IM167)
TABLE OF CONTENTS
SAFETY
Use of Warnings and Notes ...................................................................................................................................................3
Input Disconnect Features and Functions ...........................................................................................................................4
Drive Module Fan Replacement ........................................................................................................................................ 14
Enclosure Fan Replacement – NEMA 12 Enclosures ....................................................................................................... 15
Enclosure Air Filter Replacement – NEMA 12 Enclosures............................................................................................... 16
Ratings (Supplement to Aquavar CPC-01/U1 User’s Manual) ........................................................................................ 25
Input Power Connections (Supplement to Aquavar CPC-01/U1 User’s Manual) ........................................................ 26
Motor Connections .............................................................................................................................................................. 32
Dimensions and Weights (Supplement to Aquavar CPC-01/U1 User’s Manual) ......................................................... 33
Applicable Standards and Markings ................................................................................................................................. 40
INDEX .................................................................................................................................................................................. 42
2
SAFETY
WARNING! The AQUAVAR CPC adjustable speed AC drive with Input Disconnect should ONLY be
installed by a qualied electrician.
WARNING! Even when the motor is stopped, dangerous voltage is present at the Power Circuit terminals
U1, V1, W1 and U2, V2, W2 and, depending on the frame size, UDC+ and UDC-, or BRK+ and BRK-.
WARNING! Dangerous voltage is present when input power is connected. After disconnecting the
supply, wait at least 5 minutes (to let the intermediate circuit capacitors discharge) before removing the
cover.
WARNING! Even when power is removed from the input terminals of the AQUAVAR CPC, there may be
dangerous voltage (from external sources) on the terminals of the relay outputs.
WARNING! When the control terminals of two or more drive units are connected in parallel, the auxiliary
voltage for these control connections must be taken from a single source which can either be one of the
units or an external supply.
WARNING! The AQUAVAR CPC will start up automatically after an input voltage interruption if the
external run command is on.
WARNING! When the AQUAVAR CPC with Input Disconnect is connected to the line power, the Motor
Terminals T1, T2 and T3 are live even if the motor is not running. Do not make any connections when the
AQUAVAR CPC with Input Disconnect is connected to the line. Disconnect and lock out power to the
drive before servicing the drive. Failure to disconnect power may cause serious injury or death.
NOTE! For more technical information, contact the factory or your local AQUAVAR representative.
WARNING! Do not attempt to install or remove EM1, EM3, F1 or F2 screws while power is applied to
the drive’s input terminals.
WARNING! Do not control the motor with disconnecting device (disconnecting means); instead, use
the control panel start and stop keys, or commands via the I/O board of the drive. The maximum allowed
number of charging cycles of the DC capacitors (i.e. power-ups by applying power) is ve in ten minutes.
WARNING! The opening of a branch-circuit protective device may be an indication that a fault has been
interrupted. To reduce the risk of re or electric shock, current-carrying parts and other components of
the controller should be examined and replaced if damaged or equivalent.
USE OF WARNINGS AND NOTES
There are two types of safety instructions throughout this manual:
• Notes draw attention to a particular condition or fact, or give information on a subject.
• Warnings caution you about conditions which can result in serious injury or death and/or damage to the
equipment. They also tell you how to avoid the danger. The warning symbols are used as follows:
DANGEROUS VOLTAGE WARNING warns of high voltage which can cause physical injury and/or
damage to the equipment.
GENERAL WARNING warns about conditions, other than those caused by electricity, which can result
in physical injury and/or damage to the equipment.
3
INSTALLATION
Study these installation instructions carefully before proceeding. Failure to observe the warnings and instructions may cause a malfunction or personal hazard.
WARNING! Before you begin read “Safety” on page 3.
WARNING! When the Aquavar CPC with Input Disconnect is connected to the line
power, the Motor Terminals T1, T2, and T3 are live even if the motor is not running. Do
not make any connections when the Aquavar CPC with Input Disconnect is connected
to the line. Disconnect and lock out power to the drive before servicing the drive. Failure to disconnect power may cause serious injury or death.
Application
This manual contains supplemental information that is unique to Aquavar CPC input dis-
connect congurations (“FD” sufx). Refer to the base manual, Aquavar CPC User’s Manual
(IM167), for all other information.
Input Disconnect Features and Functions
The Aquavar CPC with Input Disconnect is an Aquavar CPC AC adjustable frequency drive
packaged with an input disconnect switch, and with a door mounted, external operating
handle. The operating handle can be padlocked in the OFF position (padlock not supplied).
Enclosure options are NEMA 1, NEMA 12 and NEMA 3R (UL Type 1, UL Type 12 and UL Type
3R).
The following is a typical power diagram:
Disconnect Switch
or Circuit Breaker
3 Phase
Input Power
or
1 Phase
Input Power
3
Drive with Input Disconnect
Aquavar
CPC
Drive
3Ø
3
Motor
4
INSTALLATION
The following gures show the front view of the Aquavar CPC Input Disconnect standard
congurations and identify the major components.
R1 … R4 R5, R6 R7, R8
NEMA 1 & 12 NEMA 1 & 12 NEMA 1 & 12
Enclosures Enclosures Enclosures
Aquavar CPC Drive
Control Panel
BP0096
BP0094
Operating Handle
for Disconnect Switch
BP0093
5
INSTALLATION
Installation Flow Chart
The installation of Input Disconnect congurations for Aquavar CPC drives follows the outline
below. The steps must be carried out in the order shown. At the right of each step are references to the detailed information needed for the correct installation of the unit.
NOTE! References in the middle column below are to the Aquavar CPC User’s Manual
(IM167). References in the third column below are to this manual.
Refer to the
Task Aquavar CPC User’s Manual
Additional Reference
in this Manual
“Installation” Section
PREPARE for “Preparing for Installation” • R7/R8: “Lifting the Drive”
installation on page 7.
• “Drive Identication” on page 8.
• “Suitable Mounting Location”
on page 9.
PREPARE the “Prepare the Mounting Location” • R7/R8: “Prepare the MountingMounting Location – R7 and R8” on
Location page 9.
• “Dimensions and Weights
(Supplement to Aquavar CPC
User’s Manual)” on page 27.
REMOVE the “Remove Front Cover” R7/R8: “Remove Side Panel- R7 and front cover R8 NEMA 1 and 12 Enclosures” on
page 9.
MOUNT the drive “Mount the Drive” R7/R8: “Mount the Drive” on page 10.
INSTALL wiring “Wiring Overview” and “Installing the Wiring (Supplement “Install the Wiring” to Aquavar CPC User’s Manual)”
starting on page 10.
CHECK installation “Check Installation” —
REINSTALL the “Reinstall Cover” —
cover
APPLY power “Apply Power” —
START-UP “Start-Up” —
6
INSTALLATION
Preparing for Installation (Supplement to Aquavar CPC User’s Manual)
Lifting the Drive
R7…R8 Frames
WARNING! Handle and ship oor mounted enclosures only in
the upright position. These units are not designed to be laid on their backs.
1. Use a pallet truck to move the package/enclosure to the installation site.
2. Remove the cabinet side panels from NEMA 1 and 12 enclosures for
access to the cabinet/pallet mounting bolts. (Six (6) torx screws hold
each cabinet side panel in place. Leave the side panels off until later.)
PC00005
3. Remove the 4 bolts that secure the cabinet to the shipping pallet.
WARNING! Use the lifting lugs/bars at the top of the unit
to lift R7/R8 drives.
4. Use a hoist to lift the drive. (Do not place drive in nal position until
mounting site is prepared.
2
R70010
30º
PC00003
7
INSTALLATION
Preparing for Installation (Supplement to Aquavar CPC User’s Manual)
Drive Identication
To identify the type of device you are installing, refer to the type code number on the device
identication label.
• Wall mounting base drives – label attached on the side surface of the heat sink.
• Packaged drive with screw cover – label attached to outside surface on the left ide of the
enclosure.
• Enclosure with hinged cover/door – label on inside surface of the cover/door.
Type Code Number
Use the following to interpret the type code found on the identication label.
CPC 4 370 1 FD
AQUAVAR® (Series)
Voltage
2 – 208-240 Volt
4 – 480 Volt
5 – 575 Volt
Amps
370 Amps
*See Technical Section
NEMA Enclosure Rating
1 – NEMA 1
2 – NEMA 12
Disconnect with Drive Fuses
NOTE: Standard equipment on 200 HP and above models, R7-R8 Frames.
Options
* Consult factory for other options, if available. Not all combinations may be available.
Ratings and Frame Size
Charts in the “Ratings” sections of the Aquavar CPC User’s Manual and this manual list
technical specications, and identify the drive’s frame size.
NOTE! Some instructions in this document vary, depending on the drive’s frame size. To
read the Ratings table, you need the “Output current rating” entry from the type code (see
above).
8
INSTALLATION
Suitable Mounting Location
For selecting a suitable mounting location for FD congurations, refer to:
• Preparing for installation in the Aquavar CPC User’s Manual, and
• The Technical Data section of this manual for information on dimensions and weights.
Installing the Drive (Supplement to Aquavar CPC User’s Manual - IM167)
WARNING! Metal shavings or debris in the enclosure can damage electrical
equipment and create a hazardous condition. Where parts, such as conduit plates
require cutting or drilling, rst remove the part. If that is not practical, cover nearby
electrical components to protect them from all shavings or debris.
Prepare the Mounting Location – R7 and R8
The Aquavar CPC should only be mounted where all of
the requirements dened in “Preparing for Installation”
are met.
PC00023
Frame sizes R7 and R8 have mounting holes inside
the enclosure base. See “NEMA 1 and 12, R7…R8
Mounting Dimensions” on page 28.
Where it is not possible to use either mounting hole
at the back of the base, use an L-bracket at the top of
the enclosure to secure the cabinet to a wall or to the
back of another enclosure. Bolt the L-bracket to the
enclosure using the lifting lug bolt hole on the top of
the enclosure.
Remove Side Panels – R7 and R8 NEMA 1 and 12 Enclosures
Cabinet Door
Fastening points when installed
back against a wall (top view)
Fastening points when installed
back against back
Fastening the cabinet at the top
using L-brackets (side view)
L-bracket
M12 bolt (1/2 to 9/16 in)
Cabinet top
2
1. To open the cabinet door, loosen the quarter-turn screws
that hold the cabinet door closed.
2. Installation access is easier if these panels are kept off
throughout the installation.
R70020
9
INSTALLATION
Mount the Drive
R7…R8
1. Use a hoist to move the cabinet into position.
NOTE! If the cabinet location does not provide access to the cabinet
sides, be sure to re-mount side panels before positioning cabinet.
2. Install and tighten mounting bolts.
Installing the Wiring (Supplement to Aquavar CPC User’s Manual)
WARNING!
• Metal shavings or debris in the enclosure can damage electrical equipment and create a
hazardous condition. Where parts, such as conduit plates require cutting or drilling, rst
remove the part. If that is not practical, cover nearby electrical components to protect
them from all shavings or debris.
• Do not connect or disconnect input or output power wiring, or control wires, when power
is applied.
30º
PC00003
• Never connect line voltage to drive output Terminals T1, T2 and T3.
• Do not make any voltage tolerance tests (Hi Pot or Megger) on any part of the unit.
Disconnect motor wires before taking any measurements in the motor or motor wires.
• Make sure that power factor correction capacitors are not connected between the drive
and the motor.
Wiring Requirements
Refer to the “Wiring Requirements” Section in the Aquavar CPC User’s Manual. The
requirements apply to all Aquavar CPC drives. In particular:
• Use separate, metal conduit runs for the following different classes of wiring:
– Input power wiring
– Motor wiring
– Control/communications wiring
• Properly and individually ground the drive, the motor and cable shields.
• Ground the pressure transducer or piping back to the Aquavar chassis or common
grounding point.
10
INSTALLATION
Wiring Overview
Power Connection – Standard Input Disconnect (R1…R6, Wall Mounted)
The following gures show the Standard Input Disconnect (wall mounted) wiring connection
points. Refer to the Aquavar CPC User’s Manual for control connections to the drive.
R1…R4
NEMA 1 & 12
Enclosures
BP0058
Ground
Motor
Terminals
Gnd
Input Power
Terminals
Disconnect Switch
or Circuit Breaker
Input Power
Terminals
I/O Conduit
(Bottom)
Aquavar
CPC
Lug(s)
R5, R6
NEMA 1 & 12
Enclosures
I/O Conduit
(Top)
Motor
Terminals
BP0057
11
INSTALLATION
Power Connection – Standard Input Disconnect (R7…R8, Floor Mounted)
The R7 and R8 Aquavar CPC Standard Input Disconnect units are congured for wiring access
from the top and include a removable conduit mounting plate. The following gure shows the
Standard Input Disconnect (oor mounted) wiring connection points. Refer to the Aquavar
CPC User’s Manual for control connections to the drive.
Motor
Terminals
Input Power
Terminals
Disconnect Switch
or Circuit Breaker
R7
NEMA 1 & 12
Ground Lug
Bar
CPC
Terminals
Input Power
Terminals
Disconnect Switch
or Circuit Breaker
Motor
CPC
R8
NEMA 1 & 12
Ground Lug
Bar
12
BP0054BP0055
INSTALLATION
Install the Line Input Wiring
Line Input Connections – Standard Input Disconnect Congurations
Connect input power to the terminals of the disconnect switch or circuit breaker. Connect the
equipment grounding conductor to the ground lug. The gure below shows the connection
points for Standard Input Disconnect congurations.
R1…R4
NEMA 1 & 12
Enclosures
BP0058
Input
Power
Dashed line is ground run.
R5, R6
NEMA 1 & 12
Enclosures
BP0057
Input
Power
R7, R8
NEMA 1 & 12
Enclosures
BP0054
R7 shown.
R8 similar to R7.
WARNING! Check the motor and motor wiring insulation before connecting the
Aquavar CPC to line power. Follow the procedure in the Aquavar CPC User’s Manual.
Before proceeding with the insulation resistance measurements, check that the Aquavar
CPC is disconnected from incoming line power. Failure to disconnect line power could
result in death or serious injury.
NOTE! For the remainder of the installation and start-up (motor and control wiring) refer to
the Aquavar CPC User’s Manual.
13
MAINTENANCE
Maintenance Intervals
If installed in an appropriate environment, the drive requires very little maintenance. This table
lists the routine maintenance intervals recommended by CentriPro.
Maintenance Conguration Interval Instruction
Check/replace R5/R6 R5/R6 NEMA 12 Check every 3 “Frame Sizes R5/R6 – Enclosure
enclosure inlet air lter enclosures months. Replace Inlet Air Filter” on page 16.as needed.
Check/replace R7/R8 R7/R8 NEMA 12 Check every 3 “Frame Sizes R7/R8 – NEMA 12
enclosure inlet air lter enclosures months. Replace Enclosure Inlet Air Filter” onas needed. page 16.
Check/replace R7/R8 R7/R8 NEMA 12 Check every 6 “Frame Sizes R7/R8 – NEMA 12
enclosure exhaust air enclosures months. Replace Enclosure Exhaust Filters” on
lter as needed. page 18.
Check and clean All Depends on the See “Maintenance” in Aquavar
heatsink dustiness of the CPC User’s Manual.
environment
(every 6…12
months)
Replace drive All Every 6 years See “Maintenance” in Aquavar
module fan CPC User’s Manual.
Replace enclosure NEMA 12 Every 3 years See “Frame Sizes R7/R8 – NEMA
fan(s) 12 Enclosures” on page 15. For
other frame sizes, see
“Maintenance” in Aquavar CPC
User’s Manual.
Change capacitor Frame sizes R5 and Every 10 years See “Maintenance” in Aquavar
R6 CPC User’s Manual.
Replace battery in the All Every 10 years See “Maintenance” in Aquavar
Assistant control panel CPC User’s Manual.
Drive Module Fan Replacement
The drive module fan cools the heatsink. Fan failure can be predicted by the increasing
noise from fan bearings and the gradual rise in the heatsink temperature in spite of
heatsink cleaning. If the drive is operated in a critical part of a process, fan replacement is
recommended once these symptoms start appearing. Replacement fans are available from
the factory. Do not use other than CentriPro specied spare parts.
To monitor the running time of the cooling fan, see “Group 29: Maintenance Trig” in the
Aquavar CPC Users’s Manual.
Frame Sizes R7 and R8
Refer to the installation instructions supplied with the fan kit.
14
MAINTENANCE
Enclosure Fan Replacement – NEMA 12 Enclosures
NEMA 12 enclosures include an additional fan (or fans) to move air through the enclosure.
Frame Sizes R7/R8 – NEMA 12 Enclosures
The enclosure fan is located in the exhaust box on top of the NEMA 12
enclosure.
1. Remove the left and right lter frames of the exhaust fan box by lifting
them upwards.
2. Disconnect the fan’s electrical connector from the cabinet roof (top
right Inside the cabinet).
3. Undo the four fastening screws at the corners of the fan frame. The
screws are through bolts with nuts on the inside of the cabinet.
(Do not drop the hardware into the drive).
PC00014
PC00017
PC00021
PC00018
PC00018
4. Remove the fan and fan frame as one unit.
5. Disconnect the fan wiring and capacitor from the fan frame.
Then remove the four screws attaching the fan to the fan frame.
Remove the old fan.
6. Install the new fan and capacitor with the
replacement part for CentriPro in the reverse
order of the above. Ensure the fan is centered
on the velocity stack and rotates freely.
Velocity
Stack
Capacitor
PC00014
PC00014
PC00020
15
MAINTENANCE
Enclosure Air Filter Replacement – NEMA 12 Enclosures
Frame Sizes R5/R6 – Enclosure Inlet Air Filter
This procedure applies to disconnect congurations in R5 and R6 frame sizes with NEMA 12
enclosures. This lter is located at the bottom of the enclosure. Use the following procedure to
check and replace lters.
1. On the enclosure, remove the screw holding the lter bracket in place.
2. Slide the lter bracket forward until the hooks on the bracket clear the slots on the
enclosure base. This step allows the lter and bracket to drop free from the enclosure.
Back of Enclosure
Enclosure
Slot
Hook
Mounting
Screw
Filter Bracket
3. Lift the lter out of the lter bracket and replace as appropriate.
4. With the lter in the lter bracket, align the hooks on the bracket with the slots in the
enclosure base, and press the hooks up into the slots.
5. Slide the lter bracket back, making sure that the hooks catch on the enclosure.
6. Replace the mounting screw. Tighten until the gasket on the bracket is about 50%
compressed.
Frame Sizes R7/R8 – Nema 12 Enclosure Inlet Air Filter
The inlet air lter for the R7/R8 NEMA 12 enclosure is
located in the enclosure front door.
1. While holding the top of the lter frame, pull up on
the bottom of the frame. The lter frame will slide up
approximately ¾ inch and can then safely removed
by tilting away from the cabinet and lifting up.
16
PC00010PC00015
MAINTENANCE
2. Lay the lter frame on a at work surface. Remove
the 3 retaining brackets by squeezing the tabbed
corners in towards the middle of each bracket
until the bracket clears the lter frame. Save these
brackets for replacement. Remove and inspect the
lter.
3. Install the replacement lter. Be sure to tuck the lter
into the grove around the entire lter frame. This is very
important for proper installation.
4. Reinstall the 3 lter restraining brackets. These will
prevent the lter from being pulled out of the lter
frame.
PC00009PC00007
PC00013
• Install the center bracket rst.
• Install the 2nd bracket overlapping the center
bracket by ½ to the left.
PC00007PC00009
• Install the 3rd bracket overlapping the center bracket by ½ to the right.
1st lter retaining bracket
1st and 2nd lter retaining brackets
All 3 lter retaining brackets
5. Install the lter frame back to the cabinet door. Carefully
align the mounting hooks to the slots in the cabinet
door. The hooks should be pointing down. Press in at the
center of the lter frame with your knee and gently press
down with your hands at the top of the frame. The lter
frame will slide down approximately ¾ inch and should
be sealed securely to the door around the entire lter
frame.
PC00008PC00006
17
MAINTENANCE
Frame Sizes R7/R8 – NEMA 12 Enclosure Exhaust Filters
The exhaust lters in the R7/R8 NEMA 12 enclosure are located in the exhaust box at the top
of the enclosure.
There are 2 lter frames attached to the exhaust box.
1. Remove each lter frame:
• Lift up on the lter frame until it slides approximately ¾ inch.
• Pull away from the exhaust box to remove.
2. For each lter frame, remove the wire retainers
that hold the lters in place:
• Lay the lter frames on a at work surface.
• The wire retainers have a square “U” shape.
Remove by squeezing the open end of the“U”
towards the middle of the “square” until the
retainer top (open end of “U”) clears the lter
frame.
PC00001PC00019
• Save the retainers for reinstallation.
3. Remove and inspect the lter.
4. Install clean lters.
NOTE! When installing DUSTLOK® lter media, the white side must face
to outside of the cabinet, and the orange side faces in. Be sure to tuck
the lter edges into the groove around the entire lter frame. This detail
is very important for proper operation.
PC00021
5. Reinstall the lter restrainers.
• Insert the base of a retainer (bottom of “U”
shape) into a lter frame channel.
• Squeeze the open end of the “U” until it
clears the lter frame.
• Seat the open end of the “U” in the lter
frame channel.
• Release the retainer to its relaxed, square
shape.
6. Install each lter frame to the bonnet on top of the
cabinet.
• Carefully align the frame’s mounting hooks with the
slots in the bonnet. (The hooks should be pointing
down.)
• Press down at the top of the lter frame. (The lter
frame slides down approximately ¾ inch).
• Check all around the lter frame for a secure seal to
the exhaust box.
18
PC00022
PC00001PC00019
PC00011PC00012
TECHNICAL DATA
The following tables provide current, horsepower, frame size and recommended cable sizes for the Aquavar CPC.
NOTE: THIS MANUAL SUPERCEDES PAGES 131-135 OF IM167R08.
CABLE SIZING/ RATINGS
208…240 Volt Drives
GWT AQUAVAR CPC
NEMA 1
Voltage Phase
Base
Model
CPC201718.52R11414
CPC20241123R21410
CPC2031115.55R2148
CPC20461237.5R3126
CPC2059129.510R3104
1
CPC2088144.015R482
CPC2114157.020R461/0
CPC2143171.525R643/0
CPC2178189.030R634/0
CPC22211110.540R62
CPC22481124.050R61
CPC2012111.83R11414
230
CPC2017116.75R11414
CPC2024124.27.5R21210
CPC2031130.810R2108
CPC2046146.215R386
CPC2059159.420R364
3
CPC2075174.825R443
CPC2088188.030R432
CPC21141114.040R421/0
CPC21431143.050R61/03/0
CPC21781178.060R62/04/0
CPC22211221.075R64/0
CPC22481248.0100R6
NOTE 1: Recommended AWG Size based on NEC table 310.16 , 40º C ambient, 90º C, UL type copper wire. For other wire
sizes or types, consult local, state or NEC codes.
NOTE 2: Frame sizes R7 and R8, the Aquavar CPC will have multiple conductor terminals for each phase. Consult technical
section ( CABLE TERMINALS)
Cont.
Output
Amps
Normal Duty
Horsepower
Frame
Size²
Output
Cable
Min. AWG¹
250MCM
or 2 X 1
Input
Cable
Min. AWG¹
300 MCM
or 2 x 1/0
350MCM
or 2 x 2/0
300 MCM
or 2 x 1/0
350MCM
or 2 x 2/0
Vendor
Part Number
ACS550-U1-017A-
2+N2000+P918+X1555
ACS550-U1-024A-
2+N2000+X1555
ACS550-U1-031A-
2+N2000+X1555
ACS550-U1-046A-
2+N2000+X1555
ACS550-U1-059A-
2+N2000+X1555
ACS550-U1-088A-
2+N2000+X1555
ACS550-U1-114A-
2+N2000+X1555
ACS550-U1-143A-
2+N2000+X1555
ACS550-U1-178A-
2+N2000+X1555
ACS550-U1-221A-
2+N2000+X1555
ACS550-U1-248A-
2+N2000+X1555
ACS550-U1-012A-
2+N2000+P918+X1555
ACS550-U1-017A-
2+N2000+P918+X1555
ACS550-U1-024A-
2+N2000+X1555
ACS550-U1-031A-
2+N2000+X1555
ACS550-U1-046A-
2+N2000+X1555
ACS550-U1-059A-
2+N2000+X1555
ACS550-U1-075A-
2+N2000+X1555
ACS550-U1-088A-
2+N2000+X1555
ACS550-U1-114A-
2+N2000+X1555
ACS550-U1-143A-
2+N2000+X1555
ACS550-U1-178A-
2+N2000+X1555
ACS550-U1-221A-
2+N2000+X1555
ACS550-U1-248A-
2+N2000+X1555
19
TECHNICAL DATA
The following table provides Aquavar CPC rating information, and recommended wire sizing for the input and output cables.
NOTE: THIS MANUAL SUPERCEDES PAGES 131-135 OF IM167R08.
CABLE SIZING/ RATINGS
380…480 Volt Drives
GWT AQUAVAR CPC
Volt-
age
Phase
NEMA 1
Base
Model
CPC40061
CPC40081
CPC40121
CPC40151
CPC40231
CPC40311
CPC40381
CPC40441
CPC40591
CPC40721
CPC40771
4603
CPC40961
CPC41241
CPC41571
CPC41801
CPC42451
CPC43161
CPC43681
CPC44141
CPC44861
CPC45261
CPC46021
CPC46451
NOTE 1: Recommended AWG Size based on NEC table 310.16 , 40º C ambient, 90º C, UL type copper wire. For other wire
sizes or types, consult local, state or NEC codes.
NOTE 2: Frame sizes R7 and R8, the Aquavar CPC will have multiple conductor terminals for each phase. Consult technical
section ( CABLE TERMINALS) for max. wire diameter and torque values. For submersible motors consult motor manufacturer
on recommended wire type and size based on lead length and amperage.
20
Cont.
Output
Amps
Normal
Duty
Horsepower
Frame
Size²
Output Cable
Min. AWG¹
Input Cable
Min. AWG¹
6.93R11414
8.85R11414
11.97.5R11414
15.410R21214
2315R21210
3120R3108
3825R388
4430R486
5940R464
7250R443
7760R543
9675R531
124100R611/0
157125R62/03/0
180150R63/04/0
245200R7
316250R7
368300R8
414350R8
486400R8
526450R8
602500R8
645550R8
300MCM or
2 X 1/0
500MCM or
2 X 3/0
600MCM or 2 X
4/0 or 3 X 1/0
2 X 250MCM
or 3 X 2/0
2 X 300MCM
or 3 X 3/0
2 X 350MCM
or 3 X 4/0
2 X 500MCM or
3 X 250MCM
2 X 500MCM or
3 X 250MCM
350MCM or
2 X 300MCM
2 X 350MCM
2 X 500MCM
2 X 500MCM or
3 X 250MCM
2 X 500MCM or
3 X 250MCM
2 X 2/0
2 X 3/0
2 X 4/0
Vendor
Part Number
ACS550-U1-06A9-
4+N2000+P918+X1555
ACS550-U1-08A8-
4+N2000+X1555
ACS550-U1-012A-
4+N2000+P918+X1555
ACS550-U1-015A-
4+N2000+X1555
ACS550-U1-023A-
4+N2000+X1555
ACS550-U1-031A-
4+N2000+X1555
ACS550-U1-038A-
4+N2000+X1555
ACS550-U1-045A-
4+N2000+X1555
ACS550-U1-059A-
4+N2000+X1555
ACS550-U1-072A-
4+N2000+X1555
ACS550-U1-078A-
4+N2000+X1555
ACS550-U1-097A-
4+N2000+X1555
ACS550-U1-125A-
4+N2000+X1555
ACS550-U1-157A-
4+N2000+X1555
ACS550-U1-180A-
4+N2000+X1555
ACS550-U1-246A-
4+N2000+X1555
ACS550-PC-316A-
4+N2000+X1555
ACS550-PC-368A-
4+N2000+X1555
ACS550-PC-414A-
4+N2000+X1555
ACS550-PC-486A-
4+N2000+X1555
ACS550-U2-526A-
4+N2000+X1555
ACS550-U2-602A-
4+N2000+X1555
ACS550-U2-645A-
4+N2000+X1555
TECHNICAL DATA
The following tables provide current, horsepower, frame size and recommended cable sizes for the Aquavar CPC.
NOTE: THIS MANUAL SUPERCEDES PAGES 131-135 OF IM167R08.
CABLE SIZING/ RATINGS
600 Volt Drives
GWT AQUAVAR CPC
NEMA 1
Voltage Phase
Base
Model
CPC500312.72R21414
CPC500413.93R21414
CPC500616.15R21414
CPC5009197.5R21414
CPC501111110R21414
CPC501711715R21414
CPC502212220R31210
CPC502712725R31010
4603
CPC503213230R4108
CPC504114140R486
CPC505215250R466
CPC506216260R464
CPC507717775R643
CPC5099199100R631
CPC51251125125R622/0
CPC51441144150R613/0
NOTE 1: Recommended AWG Size based on NEC table 310.16 , 40º C ambient, 90º C, UL type copper wire. For other wire
sizes or types, consult local or Provincial codes.
NOTE 2: Terminal block for input voltage and output motor voltage have diameter limits. Consult technical section ( CABLE
TERMINALS) for max. wire diameter and torque values.
Cont.
Output
Amps
Normal Duty
Horsepower
Frame
Size²
Output
Cable
Min. AWG¹
Input
Cable
Min. AWG¹
Vendor
Part Number
ACS550-U1-02A7-
6+N2000+X1555
ACS550-U1-03A9-
6+N2000+X1555
ACS550-U1-06A1-
6+N2000+X1555
ACS550-U1-09A0-6
+N2000+X1555
ACS550-U1-011A-
6+N2000+X1555
ACS550-U1-017A-
6+N2000+X1555
ACS550-U1-022A-
6+N2000+X1555
ACS550-U1-027A-
6+N2000+X1555
ACS550-U1-032A-
6+N2000+X1555
ACS550-U1-041A-
6+N2000+X1555
ACS550-U1-052A-
6+N2000+X1555
ACS550-U1-062A-
6+N2000+X1555
ACS550-U1-077A-
6+N2000+X1555
ACS550-U1-099A-
6+N2000+X1555
ACS550-U1-125A-
6+N2000+X1555
ACS550-U1-144A-
6+N2000+X1555
For submersible motor applications refer to motor manufacturers recommendations based on lead length and voltage drop.
21
TECHNICAL DATA
The following table provides Aquavar CPC rating information, and recommended fuse sizing for the input short
circuit protection. Branch circuit protection must be provided by the end user, contractor or distributor. Sized
according to local or applicable NEC codes.
FUSE SIZING/ RATINGS
208…240 Volt Drives
GWT AQUAVAR CPC
NEMA 1
Voltage Phase
Base
Model
CPC201718.52R121.325
CPC20241123R230.030
CPC2031115.55R238.840
CPC20461237.5R357.560
CPC2059129.510R373.880
1
CPC2088144.015R4110.0110
CPC2114157.020R4142.5150
CPC2143171.525R6178.8200
CPC2178189.030R6222.5225
CPC22211110.540R6276.3300
CPC22481124.050R6310.0350
CPC2012111.83R113.615
230
CPC2017116.75R119.225
CPC2024124.27.5R227.830
CPC2031130.810R235.440
CPC2046146.215R353.160
CPC2059159.420R368.380
3
CPC2075174.825R486.0100
CPC2088188.030R4101.2110
CPC21141114.040R4131.1150
CPC21431143.050R6164.5200
CPC21781178.060R6204.7250
CPC22211221.075R6254.2300
CPC22481248.0100R6285.2350
NOTE 3: UL Class T fuses are recommended for short circuit protection. Very fast acting Bussmann* T-tron type JJN and JJS
are shown in the Aquavar CPC tables. Other manufacturers are acceptable if they meet fuse requirements.
Cont.
Output
Amps
Normal Duty
Horsepower
Frame
Size
Input
Current
Amps
Fuse Type³
JJN
Vendor
Part Number
ACS550-U1-017A-
2+N2000+P918+X1555
ACS550-U1-024A-
2+N2000+X1555
ACS550-U1-031A-
2+N2000+X1555
ACS550-U1-046A-
2+N2000+X1555
ACS550-U1-059A-
2+N2000+X1555
ACS550-U1-088A-
2+N2000+X1555
ACS550-U1-114A-
2+N2000+X1555
ACS550-U1-143A-
2+N2000+X1555
ACS550-U1-178A-
2+N2000+X1555
ACS550-U1-221A-
2+N2000+X1555
ACS550-U1-248A-
2+N2000+X1555
ACS550-U1-012A-
2+N2000+P918+X1555
ACS550-U1-017A-
2+N2000+P918+X1555
ACS550-U1-024A-
2+N2000+X1555
ACS550-U1-031A-
2+N2000+X1555
ACS550-U1-046A-
2+N2000+X1555
ACS550-U1-059A-
2+N2000+X1555
ACS550-U1-075A-
2+N2000+X1555
ACS550-U1-088A-
2+N2000+X1555
ACS550-U1-114A-
2+N2000+X1555
ACS550-U1-143A-
2+N2000+X1555
ACS550-U1-178A-
2+N2000+X1555
ACS550-U1-221A-
2+N2000+X1555
ACS550-U1-248A-
2+N2000+X1555
22
TECHNICAL DATA
The following table provides Aquavar CPC rating information, and recommended fuse sizing for the input short
circuit protection. Branch circuit protection must be provided by the end user, contractor or distributor. Sized
according to local or applicable NEC codes. NOTE: THIS MANUAL SUPERCEDES PAGES 131-135 OF IM167R08.
FUSE SIZING/ RATINGS
380…480 Volt Drives
GWT AQUAVAR CPC
NEMA 1
Voltage Phase
Base
Model
CPC400616.93R17.910
CPC400818.85R110.115
CPC4012111.97.5R113.715
CPC4015115.410R217.720
CPC402312315R226.530
CPC403113120R335.740
CPC403813825R343.750
CPC404414430R450.660
CPC405915940R467.980
CPC407217250R482.890
CPC407717760R588.6100
4603
CPC409619675R5110.4125
CPC41241124100R6142.6175
CPC41571157125R6180.6200
CPC41801180150R6207.0250
CPC42451245200R7281.8300
CPC43161316250R7363.4400
CPC43681368300R8423.2450
CPC44141414350R8476.1500
CPC44861486400R8558.9600
CPC45261526450R8604.9600
CPC46021602500R8692.3800
CPC46451645550R8741.8800
NOTE 3: UL Class T fuses are recommended for short circuit protection. Very fast acting Bussmann* T-tron type and JJS are
shown in the Aquavar CPC tables. Other manufacturers are acceptable if they meet fuse requirements.
Cont.
Output
Amps
Normal Duty
Horsepower
Frame
Size
Input
Current
Amps
Fuse Type³
JJS
Vendor
Part Number
ACS550-U1-06A9-
4+N2000+P918+X1555
ACS550-U1-08A8-
4+N2000+X1555
ACS550-U1-012A-
4+N2000+P918+X1555
ACS550-U1-015A-
4+N2000+X1555
ACS550-U1-023A-
4+N2000+X1555
ACS550-U1-031A-
4+N2000+X1555
ACS550-U1-038A-
4+N2000+X1555
ACS550-U1-045A-
4+N2000+X1555
ACS550-U1-059A-
4+N2000+X1555
ACS550-U1-072A-
4+N2000+X1555
ACS550-U1-078A-
4+N2000+X1555
ACS550-U1-097A-
4+N2000+X1555
ACS550-U1-125A-
4+N2000+X1555
ACS550-U1-157A-
4+N2000+X1555
ACS550-U1-180A-
4+N2000+X1555
ACS550-U1-246A-
4+N2000+X1555
ACS550-PC-316A-
4+N2000+X1555
ACS550-PC-368A-
4+N2000+X1555
ACS550-PC-414A-
4+N2000+X1555
ACS550-PC-486A-
4+N2000+X1555
ACS550-U2-526A-
4+N2000+X1555
ACS550-U2-602A-
4+N2000+X1555
ACS550-U2-645A-
4+N2000+X1555
23
TECHNICAL DATA
The following table provides Aquavar CPC rating information, and recommended fuse sizing for the input short
circuit protection. Branch circuit protection must be provided by the end user, contractor or distributor. Sized
according to local or applicable NEC codes. NOTE: THIS MANUAL SUPERCEDES PAGES 131-135 OF IM167R08.
FUSE SIZING/ RATINGS
600 Volt Drives
GWT AQUAVAR CPC
NEMA 1
Voltage Phase
Base
Model
CPC500312.72R22.710
CPC500413.93R23.910
CPC500616.15R26.110
CPC5009197.5R2915
CPC501111110R21115
CPC501711715R21725
CPC502212220R32225
CPC502712725R32740
5753
CPC503213230R43240
CPC504114140R44150
CPC505215250R45260
CPC506216260R46280
CPC507717775R677100
CPC5099199100R699150
CPC51251125125R6125175
CPC51441144150R6144200
NOTE 3: UL Class T fuses are recommended for short circuit protection. Very fast acting Bussmann* T-tron type JJS are
shown in the Aquavar CPC tables. Other manufacturers are acceptable if they meet fuse requirements.
Cont.
Output
Amps
Normal Duty
Horsepower
Frame
Size
Input
Current
Amps
Fuse Type³
JJS
Vendor
Part Number
ACS550-U1-02A7-
6+N2000+X1555
ACS550-U1-03A9-
6+N2000+X1555
ACS550-U1-06A1-
6+N2000+X1555
ACS550-U1-09A0-6
+N2000+X1555
ACS550-U1-011A-
6+N2000+X1555
ACS550-U1-017A-
6+N2000+X1555
ACS550-U1-022A-
6+N2000+X1555
ACS550-U1-027A-
6+N2000+X1555
ACS550-U1-032A-
6+N2000+X1555
ACS550-U1-041A-
6+N2000+X1555
ACS550-U1-052A-
6+N2000+X1555
ACS550-U1-062A-
6+N2000+X1555
ACS550-U1-077A-
6+N2000+X1555
ACS550-U1-099A-
6+N2000+X1555
ACS550-U1-125A-
6+N2000+X1555
ACS550-U1-144A-
6+N2000+X1555
24
TECHNICAL DATA
Ratings (Supplement to Aquavar CPC User’s Manual - IM167)
NOTE! The ratings listed below are exceptions to the ratings listed in the Aquavar CPC
User’s Manual.
Ratings, 380…480 Volt Drives
Type Code
Valid up to 40°C (104 °F)
Normal UseHeavy-Duty Use
AQUAVAR CPC-FD -
see below
CPC4245xFD245200192150R7
CPC4316xFD316250240200R8
CPC4368xFD368300302250R8
CPC4414xFD414350368300R8
CPC4486xFD486400414350R8
CPC45261FD526450477400R8
CPC46021FD602500515450R8
CPC46451FD645550590500R8
I
2N
A
P
HP
N
I
2hd
A
P
hd
HP
Frame
Size
Vendor
Part Number
ACS550-PD-246A-
4+N2000+X1555
ACS550-PD-316A-
4+N2000+X1555
ACS550-PD-368A-
4+N2000+X1555
ACS550-PD-414A-
4+N2000+X1555
ACS550-PD-486A-
4+N2000+X1555
ACS550-PD-526A-
4+N2000+X1555
ACS550-PD-602A-
4+N2000+X1555
ACS550-U2-645A-
4+N2000+X1555
NOTE: I2N = Motor current draw normal
PN = Normal rated power
I
Phd = Heavy-duty NEMA power rating
= Heavy-duty current rating
2hd
25
TECHNICAL DATA
Input Power Connections (Supplement to Aquavar CPC User’s Manual)
Fuses
NOTE! Although fuses listed are similar in functional characteristics to fuses listed in
the Aquavar CPC User’s Manual, physical characteristics may differ. Fuses from other
manufacturers can be used if they meet the functional characteristics of those in these
tables.
Drive input fuses are provided to disconnect the drive from power in the event that a
component fails in the drive’s power circuitry.
208…240 Volt Fuses
208 … 240 Volt
Base
Drive Input Fuse Ratings
Drive
HPIdentication
Frame
Size
1CPC2004xFDR115KTK-R-15
2CPC2007xFDR115KTK-R-15
3CPC2012xFDR115KTK-R-15
5CPC2017xFDR130KTK-R-30
7.5CPC2024xFDR230KTK-R-30
10CPC2031xFDR250JJS-50
15CPC2046xFDR380JJS-80
20CPC2059xFDR380JJS-80
25CPC2075xFDR4100JJS-100
30CPC2088xFDR4125170M1368
40CPC2114xFDR4160170M1369
50CPC2143xFDR6200170M1370
60CPC2178xFDR6250170M1371
75CPC2221xFDR6315170M1372
100CPC2248xFDR6315170M1372
Amps
(600V)
Bussmann
Type
Vendor
Part Number
ACS550-PD-04A6-
2+N2000+P918+X1555
ACS550-PD-07A5-2
+N2000+X1555
ACS550-PD-012A-2
+N2000+X1555
ACS550-PD-017A-2
+N2000+X1555
ACS550-PD-024A-2
+N2000+X1555
ACS550-PD-031A-2
+N2000+X1555
ACS550-PD-046A-2
+N2000+X1555
ACS550-PD-059A-2
+N2000+X1555
ACS550-PD-075A-2
+N2000+X1555
ACS550-PD-088A-
2+N2000+X1555
ACS550-PD-114A-
2+N2000+X1555
ACS550-PD-143A-
2+N2000+X1555
ACS550-PD-178A-
2+N2000+X1555
ACS550-PD-222A-
2+N2000+X1555
ACS550-PD-248A-
2+N2000+X1555
NOTE: “x” represents both NEMA 1 and NEMA 12 enclosures.
26
TECHNICAL DATA
380…480 Volt Fuses
380 … 480 Volt
Base
Drive Input Fuse Ratings
Drive
HPIdentication
Frame
Size
3CPC4006xFDR115KTK-R-15
5CPC4008xFDR115KTK-R-15
7.5CPC4012xFDR115KTK-R-15
10CPC4015xFDR230KTK-R-30
15CPC4023xFDR230KTK-R-30
20CPC4031xFDR350JJS-50
25CPC4038xFDR350JJS-50
30CPC4044xFDR3100JJS-100
40CPC4059xFDR4100JJS-100
50CPC4072xFDR4100JJS-100
60CPC4077xFDR5125170M1368
75CPC4096xFDR5125170M1368
100CPC4124xFDR6160170M1369
125CPC4157xFDR6200170M1370
150CPC4180xFDR6250170M1371
200CPC4245xFDR7400JJS-400
250CPC4316xFDR8400JJS-400
300CPC4368xFDR8400JJS-400
350CPC4414xFDR8600JJS-600
400CPC4486xFDR8600JJS-600
450CPC4526xFDR8800JJS-800
500CPC4602xFDR8800JJS-800
550CPC4645xFDR8800JJS-800
Amps
(600V)
Bussmann
Type
Vendor
Part Number
ACS550-PD-06A9-4
+N2000+X1555
ACS550-PD-08A8-
4+N2000+X1555
ACS550-PD-012A-4
+N2000+X1555
ACS550-PD-015A-4
+N2000+X1555
ACS550-PD-023A-4
+N2000+X1555
ACS550-PD-031A-4
+N2000+X1555
ACS550-PD-038A-4
+N2000+X1555
ACS550-PD-045A-
4+N2000+X1555
ACS550-PD-059A-4
+N2000+X1555
ACS550-PD-072A-4
+N2000+X1555
ACS550-PD-078A-4
+N2000+X1555
ACS550-PD-097A-4
+N2000+X1555
ACS550-U1-125A-
4+B055+N2000+X1555
ACS550-PD-157A-
4+N2000+X1555
ACS550-PD-180A-
4+N2000+X1555
ACS550-PD-246A-
4+N2000+X1555
ACS550-PD-316A-
4+N2000+X1555
ACS550-PD-368A-
4+N2000+X1555
ACS550-PD-414A-
4+N2000+X1555
ACS550-PD-486A-
4+N2000+X1555
ACS550-U2-526A-
4+N2000+X1555
ACS550-U2-602A-
4+N2000+X1555
ACS550-U2-645A-
4+N2000+X1555
NOTE: “x” represents both NEMA 1 and NEMA 12 enclosures.
27
TECHNICAL DATA
500…600 Volt Fuses
500 … 600 Volt
Base
Drive Input Fuse Ratings
Drive
HPIdentication
Frame
Size
Amps
(600V)
Bussmann
Type
2CPC5002xFDR215KTK-R-15
3CPC5004xFDR215KTK-R-15
5CPC5006xFDR215KTK-R-15
7.5CPC5009xFDR215KTK-R-15
10CPC5011xFDR230KTK-R-30
15CPC5017xFDR230KTK-R-30
20CPC5022xFDR350JJS-50
25CPC5027xFDR350JJS-50
30CPC5032xFDR4100JJS-100
40CPC5041xFDR4100JJS-100
50CPC5052xFDR4100JJS-100
60CPC5062xFDR4100JJS-100
75CPC5077xFDR6125170M1368
100CPC5099xFDR6125170M1368
125CPC5125xFDR6160170M1369
150CPC5144xFDR6200170M1370
Vendor
Part Number
ACS550-PD-02A1-
6+N2000+X1555
ACS550-PD-04A1-
6+N2000+X1555
ACS550-PD-06A1-
6+N2000+X1555
ACS550-PD-09A1-
6+N2000+X1555
ACS550-PD-11A1-
6+N2000+X1555
ACS550-PD-17A1-
6+N2000+X1555
ACS550-PD-22A1-
6+N2000+X1555
ACS550-PD-27A1-
6+N2000+X1555
ACS550-PD-32A1-
6+N2000+X1555
ACS550-PD-41A1-
6+N2000+X1555
ACS550-PD-52A1-
6+N2000+X1555
ACS550-PD-62A1-
6+N2000+X1555
ACS550-PD-77A1-
6+N2000+X1555
ACS550-PD-99A1-
6+N2000+X1555
ACS550-PD-125A1-
6+N2000+X1555
ACS550-PD-144A1-
6+N2000+X1555
NOTE: “x” represents both NEMA 1 and NEMA 12 enclosures.
Input Power Cables / Wiring – R7/R8
NEC
Based on:
• NEC Table 310-16 for copper wires • 40 °C (104 °F) ambient temperature
• 90 °C (194 °F) wire insulation • Copper cables with concentric copper shield
• Not more than three current-carrying conductors in raceway or cable, or earth (directly buried).
Max Load Current (A) Cu Wire Size (AWG/kcmil) Max Load Current (A) Cu Wire Size (AWG/kcmil)
345 400 MCM or 2 x 2/0 474 2 x 250
391 500 MCM or 2 x 3/0 534 2 x 300
410 2 x 3/0 615 2 x 350
465 2 x 4/0 711 2 x 500
28
TECHNICAL DATA
Drive’s Power Connection Terminals (Supplement to Aquavar CPC User’s Manual)
The following tables show maximum wire size and required tightening torque for incomming
power and motor terminals, and grounding terminal lug information.
208…240 Volt, Terminals
208 … 240 Volt
Frame
HPType Code
1CPC2004xFDR1
2CPC2007xFDR1
3CPC2012xFDR1
5CPC2017xFDR1
7.5CPC2024xFDR2
10CPC2031xFDR2
15CPC2046xFDR3
20CPC2059xFDR3
25CPC2075xFDR4
30CPC2088xFDR4
40CPC2114xFDR4
50CPC2143xFDR6
60CPC2178xFDR6
75CPC2221xFDR6
100CPC2248xFDR6
Size
Circuit
Breaker
#10
35 in-lbs
#6
45 in-lbs
#3
50 in-lbs
#1
50 in-lbs
350 MCM
274 in-lbs
2 x 250
MCM
274 in-lbs
Power Wiring Data
Disconnect
Switch
#10
7 in-lbs
#8
7 in-lbs
#4
18 in-lbs
#1
55 in-lbs
#1/0 70 in-lbs
300 MCM
275 in-lbs
2 x 250 MCM
275 in-lbs
Motor
Terminals
#10
12 in-lbs
12 in-lbs
24 in-lbs
48 in-lbs
#1/0
48 in-lbs
350 MCM
360 in-lbs
#6
#3
#1
Ground
Lugs
NEMA
1 & 12
#10
35 in-lbs
#3
50 in-lbs
#2
50 in-lbs
3 x #3/0
250 in-lbs
Vendor
Part Number
ACS550-PD-04A6-
2+N2000+P918+X1555
ACS550-PD-07A5-2
+N2000+X1555
ACS550-PD-012A-2
+N2000+X1555
ACS550-PD-017A-2
+N2000+X1555
ACS550-PD-024A-2
+N2000+X1555
ACS550-PD-031A-2
+N2000+X1555
ACS550-PD-046A-2
+N2000+X1555
ACS550-PD-059A-2
+N2000+X1555
ACS550-PD-075A-2
+N2000+X1555
ACS550-PD-088A-
2+N2000+X1555
ACS550-PD-114A-
2+N2000+X1555
ACS550-PD-143A-
2+N2000+X1555
ACS550-PD-178A-
2+N2000+X1555
ACS550-PD-222A-
2+N2000+X1555
ACS550-PD-248A-
2+N2000+X1555
NOTE: “x” represents both NEMA 1 and NEMA 12.
29
TECHNICAL DATA
380…480 Volt, Terminals
380 … 480 Volt
Power Wiring Data
Frame
HPType Code
3CPC4006xFDR1
5CPC4008xFDR1
7.5CPC4012xFDR1
10CPC4015xFDR2
15CPC4023xFDR2
20CPC4031xFDR3
25CPC4038xFDR3
30CPC4044xFDR4
40CPC4059xFDR4
50CPC4072xFDR4
60CPC4077xFDR4
75CPC4096xFDR5
100CPC4124xFDR6
125CPC4157xFDR6
150CPC4180xFDR6
200CPC4245xFDR7
250CPC4316xFDR8
300CPC4368xFDR8
350CPC4414xFDR8
400CPC4486xFDR8
450CPC4526xFDR8
500CPC4602xFDR8
550CPC4645xFDR8
NOTE: “x” represents both NEMA 1 and NEMA 12.
30
Size
Circuit
Breaker
#10
35 in-lbs
#6
45 in-lbs
#3
50 in-lbs
#1
50 in-lbs
350 MCM
274 in-lbs
2 x 250 MCM
274 in-lbs
2 x 500
MCM
274 in-lbs
3 x 400
MCM
375 in-lbs
Disconnect
Switch
18 in-lbs
55 in-lbs
62 in-lbs
70 in-lbs
300 MCM
275 in-lbs
2 x 250 MCM
274 in-lbs
2 x 500 MCM
274 in-lbs
3 x 400 MCM
375 in-lbs
#10
7 in-lbs
#8
7 in-lbs
#4
#1
#1
#1/0
Motor
Terminals
#10
12 in-lbs
#6
12 in-lbs
#3
24 in-lbs
#1
48 in-lbs
#1/0
48 in-lbs
#2/0
132 in-lbs
350 MCM
360 in-lbs
2 x 250 MCM
2 x 500
MCM
500 in-lbs
2 x 600
MCM
500 in-lbs
3 x 400 MCM
Ground
Lugs
NEMA
1 & 12
#10
35 in-lbs
#6
35 in-lbs
#3
50 in-lbs
#1
50 in-lbs
3 x #3/0
250 in-lbs
5 Bus Bar
Holes
(13/32”
Bolts)
Vendor
Part Number
ACS550-PD-06A9-4
+N2000+X1555
ACS550-PD-08A8-
4+N2000+X1555
ACS550-PD-012A-4
+N2000+X1555
ACS550-PD-015A-4
+N2000+X1555
ACS550-PD-023A-4
+N2000+X1555
ACS550-PD-031A-4
+N2000+X1555
ACS550-PD-038A-4
+N2000+X1555
ACS550-PD-045A-
4+N2000+X1555
ACS550-PD-059A-4
+N2000+X1555
ACS550-PD-072A-4
+N2000+X1555
ACS550-PD-078A-4
+N2000+X1555
ACS550-PD-097A-4
+N2000+X1555
ACS550-U1-125A-
4+B055+N2000+X1555
ACS550-PD-157A-
4+N2000+X1555
ACS550-PD-180A-
4+N2000+X1555
ACS550-PD-246A-
4+N2000+X1555
ACS550-PD-316A-
4+N2000+X1555
ACS550-PD-368A-
4+N2000+X1555
ACS550-PD-414A-
4+N2000+X1555
ACS550-PD-486A-
4+N2000+X1555
ACS550-U2-526A-
4+N2000+X1555
ACS550-U2-602A-
4+N2000+X1555
ACS550-U2-645A-
4+N2000+X1555
TECHNICAL DATA
500…600 Volt, Terminals
500 … 600 Volt
Frame
HPType Code
2CPC5002xFDR2
3CPC5004xFDR2
5CPC5006xFDR2
7.5CPC5009xFDR2
10CPC5011xFDR2
15CPC5017xFDR2
20CPC5022xFDR3
25CPC5027xFDR3
30CPC5032xFDR4
40CPC5041xFDR4
50CPC5052xFDR4
60CPC5062xFDR4
75CPC5077xFDR6
100CPC5099xFDR6
125CPC5125xFDR6
150CPC5144xFDR6
Size
Circuit
Breaker
#6
62 in-lbs
#3
62 in-lbs
#1
62 in-lbs
350 MCM
274 in-lbs
Power Wiring Data
Disconnect
Switch
#8
7 in-lbs
#4
18 in-lbs
#1
55 in-lbs
#1
62 in-lbs
#1/0
70 in-lbs
300 MCM
275 in-lbs
Motor
Terminals
12 in-lbs
24 in-lbs
48 in-lbs
350 MCM
360 in-lbs
#6
#3
#1
Ground
Lugs
NEMA
1 & 12
#6
35 in-lbs
#3
50 in-lbs
#2
50 in-lbs
3 x #3/0
250 in-lbs
Vendor
Part Number
ACS550-PD-02A1-
6+N2000+X1555
ACS550-PD-04A1-
6+N2000+X1555
ACS550-PD-06A1-
6+N2000+X1555
ACS550-PD-09A1-
6+N2000+X1555
ACS550-PD-11A1-
6+N2000+X1555
ACS550-PD-17A1-
6+N2000+X1555
ACS550-PD-22A1-
6+N2000+X1555
ACS550-PD-27A1-
6+N2000+X1555
ACS550-PD-32A1-
6+N2000+X1555
ACS550-PD-41A1-
6+N2000+X1555
ACS550-PD-52A1-
6+N2000+X1555
ACS550-PD-62A1-
6+N2000+X1555
ACS550-PD-77A1-
6+N2000+X1555
ACS550-PD-99A1-
6+N2000+X1555
ACS550-PD-125A1-
6+N2000+X1555
ACS550-PD-144A1-
6+N2000+X1555
NOTE: “x” represents both NEMA 1 and NEMA 12.
31
TECHNICAL DATA
Cable Terminals (Frames R1-R6)
U1, V1, W1
U2, V2, W2
Frame
Size
1
R1
1
R2
1
R3
1
R4
1
R5
Minimum
Wire Size
2
mm
0.75181081.411081.41
0.75181081.411081.41
2.5142532.51.81661.81.3
610501/05.6425321.5
610702/01511702/01511
BRK±, UDC± Terminals
Maximum
Wire Size
AWGmm
2
Tightening
Torque
AWGN•mlb•ftmm
R6953/0240350 MCM4030953/086
1 Aluminum cable cannot be used with frame sizes R1…R6 because of its lower capacity.
Note: See the recommended cable sizes for different load currents in section Cable Sizing/Ratings.
Motor Connections
Motor Connection Specications – R7/R8
Earthing PE Terminal
Maximum
Wire Size
2
AWGN•mlb•ft
Tightening
Torque
Motor Connection Specications
Maximum Motor
Cable Length
R7…R8 300 m 980 ft Does not apply
Frame
Maximum Motor Cable Length*
Size
fsw = 1 or 4 kHz fsw = 8 kHz or 12 kHz
WARNING! Using a motor cable longer than specied in the chart above may cause permanent
damage to the drive.
Cooling – R7/R8
Cooling Specications
Method Internal fan, ow direction from bottom to top.
• R7/R8: Free space in front of enclosure: 152 mm (6 in).
Requirement
• R7/R8: Free space at sides of enclosure: None required for cooling.
• R7/R8: Also see “Additional Free Space Recommendations” on page 33.
Air Flow, 380…480 Volt Drives – R7/R8
The following table lists heat loss and air ow data for 380…480 Volt drives.
Drive Heat Loss Air Flow
CPC-xx- Frame Size W BTU/Hr m3/h ft3/min
-245A-4 R7 3850 13000 300 540
-316A-4 R8 5300 18000 700 1220
-368A-4 R8 6850 23000 700 1220
-414A-4 R8 7000 24000 700 1220
-486A-4 R8 7600 26000 700 1220
-526A-4 R8 7800 27000 700 1220
-602A-4 R8 8100 28000 700 1220
-645A-4 R8 9100 31000 700 1220
• R7/R8: Free space above enclosure: None required for cooling.
32
TECHNICAL DATA
Dimensions and Weights (Supplement to Aquavar CPC User’s Manual)
Mounting Dimensions
NEMA 1 & 12, R1…R6 Mounting Dimensions
See Detail A
See Detail B
a
c
R1…R4
W1
W2
R5/R6
W1
H
H
DS0301
bd
Detail BDetail A
W2
BP0057
NEMA 1 and NEMA 12 – Mounting Dimensions for each Frame Size
M6 1/4 M6 1/4 M6 1/4 M6 1/4 M8 5/16 M8 5/16
* Measurements are center to center.
NOTE: -088A-2, -114A-2 and -097A-4 NEMA 1 & 12 units are R4 frame base drives in R5 enclosures.
R5 enclosure information applies.
33
TECHNICAL DATA
NEMA 1 & 12, R7…R8 Mounting Dimensions
NEMA 1 and NEMA 12 – Dimensions for each Frame Size
R7 & R8
Ref.
Top View
mm in
W 806 31.7
D 659 25.9
a 675 26.6
b 474.5 18.7
c 61 2.4
d 65.5 2.6
Mounting Hardware
11 mm 13/32
* Measurements are center to center.
b
a
d
D
c
W
Weights
The following table lists typical maximum weights for each frame size. Variations within each
frame size (due to components associated with voltage/current ratings and options) are minor.
Weight
En-
closure
R1 R2 R3 R4 R5 R6 R7 R8
kg lb. kg lb. kg lb. kg lb. kg lb. kg lb. kg lb. kg lb.
NOTE: -088A-2, -114A-2 and -097A-4 NEMA 1 & 12 units are R4 frame base drives in R5 enclosures.
R5 enclosure information applies.
Ref.
R1 R2 R3 R4
mm in mm in mm in mm in
36
TECHNICAL DATA
NEMA 1, R5/R6 Outside Dimensions
H
D
W
BP0063
Input Disconnect, NEMA 1, R5/R6
W 713 28.1 713 28.1
H212 47.7 1212 47.7
D484 19.1 484 19.1
NOTE: -088A-2, -114A-2 and -097A-4 NEMA 1 & 12 units are R4 frame base drives in R5 enclosures.
R5 enclosure information applies.
Dimensions
Ref.
R5 R6
mm in mm in
37
TECHNICAL DATA
NEMA 12, R5/R6 Outside Dimensions
W
H
BP0062
D
Input Disconnect, NEMA 12, R5/R6
W 734 28.9 734 28.9
H1371 54.0 1371 54.0
D484 19.1 484 19.1
NOTE: -088A-2, -114A-2 and -097A-4 NEMA 1 & 12 units are R4 frame base drives in R5 enclosures.
R5 enclosure information applies.
Dimensions
Ref.
R5 R6
mm in mm in
38
TECHNICAL DATA
NEMA 1 & 12, R7…R8 Outside Dimensions
W
H
BP0017
D
Outside Dimensions by Frame Size
R7 R8
Enclosure Ref.
mm in mm in
W 806 31.7 806 31.7
NEMA 1H 2125 83.7 2125 83.7
D 659 25.9 659 25.9
W 806 31.7 806 31.7
NEMA 12 H 2377 93.6 2377 93.6
D 659 25.9 659 25.9
Additional Free Space Recommendations
In addition to the free space requirements for cooling (“Cooling - R7/R8”), allow:
• 800 mm (31.5 in) in front of R7/R8 enclosures – room for the cabinet door to swing open.
• 305 mm (12 in) above R7/R8, IP54 / UL Type 12 enclosures – room for fan replacement.
39
CU
CU
U
C
TECHNICAL DATA
Applicable Standards
Drive compliance with the following standards is identied by the standards “marks” on the type code label.
Mark Applicable Standards
UL 508C and UL Standard for Safety, Power Conversion Equipment, second
U
L
®
C22.2 No. 14 edition and CSA Standard for Industrial Control Equipment
UL 508A UL Standard for Safety, Industrial Control Panels
C22.2 No. 14 CSA Standard for Industrial Control Equipment
Compliance is valid with the following provisions:
• The motor and control cables are chosen as specied in this manual.
• The installation rules of this manual are followed.
The AQUAVAR is suitable for use on a circuit capable of delivering not more than 100,000 RMS symmetrical
amperes, 600 V maximum.
For open type enclosures, that is units without the conduit box and/or cover for enclosures, that is units without
the conduit box and/or cover for IP21/UL type 1 units or without the conduit place and/or top cover for IP54
units, the unit must be mounted inside an enclosure per National Electrical Code and local electrical codes.
LISTED
L
®
U
L
®
S
UL/CSA Markings
U
LISTED
A UL mark is attached to ACS550 drives to verify that the drive follows the provisions of UL 508C.
L
®
S
A CSA mark is attached to ACS550-U1 type drives to verify that the drive follows the provisions of C22.2
NO. 14.
®
The ACS550 is suitable for use in a circuit capable of delivering not more than 100 kA RMS symmetrical
amperes, 600 V maximum. The ampere rating is based on tests done according to UL 508.
Branch circuit protection must be provided in accordance with local codes.
The ACS550 has an electronic motor protection feature that compiles with the requirements of UL 508C
and, for ACS550-U1, C22.2 No. 14. When this feature is selected and properly adjusted, additional
overload protection is not required unless more than one motor is connected to the drive or unless
additional protection is required by applicable safety regulations. See parameters 3005 (MOT THERM
PROT) and 3006 (MOT THERM RATE).
The drives are to be used in a controlled environment.
Note: For open type enclosures, i.e. drives without the conduit box and/or cover for IP21 / UL type 1
drives, or without the conduit plate and/or hood for IP54 / UL type 12 drives, the drive must be mounted
inside an enclosure in accordance with National Electric Code and local electrical codes.
Brake choppers, when applied with appropriately sized brake resistors, will allow the drive to dissipate
regenerative energy (normally associated with quickly decelerating a motor). Frame sizes R1 and
R2 have a built-in brake chopper as standard equipment. For frame sizes R3…R6, contact your ABB
representative for appropriate parts.
WARNING! Do not attempt to install or remove EM1, EM3, F1 or F2 screws while power is
applied to the drive’s input terminals.
WARNING! Do not control the motor with the disconnecting device (disconnecting means);
instead, use the control panel start and stop keys and , or commands via the I/O
board of the drive. The maximum allowed number of charging cycles of the DC capacitors
(i.e. power-ups by applying power) is ve in ten minutes.
40
TECHNICAL DATA
CE Marking
A CE mark is attached to the drive to verify that the drive follows the provisions of the European Low
Voltage and EMC Directives.
Note: The 600 V ACS550-U1 drives are not CE approved.
Compliance with the EMC Directive
The Directive denes the requirements for immunity and emissions of electrical equipment used
within the European Union. The EMC product standard (IEC/EN 61800-3 [2004]) covers requirements
stated for drives.
Compliance with IEC/EN 61800-3 (2004)
C-Tick Marking
The drive carries C-Tick marking.
✔
C-Tick marking is required in Australia and New Zealand. A C-Tick mark is attached to the drive to
verify compliance with the relevant standard (IEC 61800-3 (2004) — Adjustable speed electrical power
drive systems — Part 3: EMC product standard including specic test methods), mandated by the Trans-
Tasman Electromagnetic Compatibility Scheme.
The Trans-Tasman Electromagnetic Compatibility Scheme (EMCS) was introduced by the Australian
Communication Authority (ACA) and the Radio Spectrum Management Group (RSM) of the New
Zealand Ministry of Economic Development (NZMED) in November 2001. The aim of the scheme is
to protect the radio frequency spectrum by introducing technical limits for emission from electrical/
electronic products.
Compliance with IEC/EN 61800-3 (2004)
41
INDEX
Refer to the Aquavar CPC User’s Manual (IM167) index for topics not listed here.
line input installation ........................13
overview ...................................11
requirements ...............................10
43
CENTRIPRO LIMITED WARRANTY
This warranty applies to all Aquavar CPC controllers manufactured by Xylem, Inc.
Any part or parts found to be defective within the warranty period shall be replaced at no charge to the dealer during the warranty period. The warranty period shall exist
for a period of twenty-four (24) months from date of installation or thirty (30) months from date of manufacture, whichever period is shorter.
A dealer who believes that a warranty claim exists must contact the authorized CentriPro distributor from whom the controller was purchased and furnish complete details
regarding the claim. The distributor is authorized to adjust any warranty claims utilizing the CentriPro Customer Service Department.
The warranty excludes:
(a) Labor, transportation and related costs incurred by the dealer;
(b) Reinstallation costs of repaired equipment;
(c) Reinstallation costs of replacement equipment;
(d) Consequential damages of any kind; and,
(e) Reimbursement for loss caused by interruption of service.
For purposes of this warranty, the following terms have these definitions:
(1) “Distributor” means any individual, partnership, corporation, association, or other legal relationship that stands between CentriPro and the dealer in purchases,
consignments or contracts for sale of the subject controllers.
(2) “Dealer” means any individual, partnership, corporation, association, or other legal relationship which engages in the business of selling or leasing controllers to
customers.
(3) “Customer” means any entity who buys or leases the subject controllers from a dealer. The “customer” may mean an individual, partnership, corporation, limited
liability company, association or other legal entity which may engage in any type of business.
THIS WARRANTY EXTENDS TO THE DEALER ONLY.
Xylem, Inc.
2881 East Bayard Street Ext., Suite A
Seneca Falls, NY 13148
Phone: (800) 453-6777
Fax: (888) 322-5877
www.centripro.com
CentriPro and Aquavar are trademarks of Xylem Inc. or one of its subsidiaries.
Goulds is a registered trademark of Goulds Pumps, Inc. and is used under license.
DUSTLOK® is a registered trademark of Fiberbond Corp.
Bussmann is a registered trademark of Cooper Industries Inc.