Xylem IM192R00 User Manual

ITT
Commercial Water Systems
CentriPro
TM
CentriPro
FloStandard SIMPLEX PUMP CONTROL PANEL
Installation and Operation Manual
CentriPro is a brand of ITT Residential and Commercial Water.
www.centripro.com
Engineered for life
ITT
OWNER’S INFORMATION
Pump Model No:
__________________________
Commercial Water Systems
Pump Serial No:
CENTRIPRO
________________________________
Control Model No:
Dealer Phone No:
Date of Purchase:
_________________________
__________________________
__________________________
Control Panel Serial No:
Dealer:
Installation Date:
________________________________________
_________________________
_______________________________
CURRENT READINGS AT SETUP
L1 L2 L3
Amps: Amps:
Volts: Volts:
MOTOR INFORMATION
______________________________________
HP:
____________________________________
Volts:
_________________________________________
RPM:
Service Factor:
_________________________________
Frequency:
Enclosure:
________________________________
Phase:
2
________________________________________
_____________________________________
ITT
CENTRIPRO
Commercial Water Systems
TABLE OF CONTENTS
Safety Instructions ............................................................................................................................. 4
Pre-Installation Checks ...................................................................................................................... 4
Pump Control Panels and Wiring ....................................................................................................... 5
Wiring and Grounding ...................................................................................................................... 5
Selecting Control Panels ....................................................................................................................5
Warning Pump Control Panels and Switches .....................................................................................5
Panel Operation ................................................................................................................................5
Check Rotation ..................................................................................................................................5
Combination Starter and Overload Relay ..........................................................................................7
Controller Functions ..........................................................................................................................8
Specifications
General Specifications ............................................................................................................... 8
Electrical ................................................................................................................................... 8
Interpreting Model Numbers ............................................................................................................. 9
Suggested Fuse, Wire, and Conduit Sizes ................................................................................ 11
Schematics ...................................................................................................................................... 12
Recommended Spare Parts For Five Years Of Operation ..................................................................22
Limited Warranty .............................................................................................................................24
3
ITT
CENTRIPRO
daNgER
WARNING
CAUTION
WARNING
WARNING
WARNING
daNgER
daNgER
WARNING
Commercial Water Systems
saFETY INsTRUCTIONs
TO AVOID SERIOUS OR FATAL PERSONAL INJURY OR MAJOR PROPERTY DAMAGE, READ AND FOLLOW ALL SAFETY INSTRUCTIONS IN MANUAL AND ON PUMP.
THIS MANUAL IS INTENDED TO ASSIST IN THE INSTALLATION AND OPERATION OF THIS UNIT AND MUST BE KEPT WITH THE PUMP.
This is a SAFETY ALERT SYMBOL. When you see this
symbol on the pump or in the manual, look for one of the following signal words and be alert to the potential for personal injury or property damage.
Warns of hazards that WILL cause serious personal injury, death or major property damage.
Warns of hazards that CAN cause serious personal injury, death or major property damage.
Warns of hazards that CAN cause personal injury or property damage.
NOTICE: INDICATES SPECIAL INSTRUCTIONS WHICH ARE VERY IMPORTANT AND MUST BE FOLLOWED.
THOROUGHLY REVIEW ALL INSTRUCTIONS AND WARNINGS PRIOR TO PERFORMING ANY WORK ON THIS PUMP.
MAINTAIN ALL SAFETY DECALS.
All electrical work must be per-
formed by a qualified technician. Always follow the National Electrical Code (NEC), or the Canadian Electrical Code, as well as all local, state and provincial codes. Code questions should be directed to your local electrical inspec­tor. Failure to follow electrical codes and OSHA safety standards may result in personal injury or equipment damage. Failure to follow manufactur­er’s installation instructions may result in electrical shock, fire hazard, personal injury or death, dam­aged equipment, provide unsatisfactory perfor­mance, and may void manufacturer’s warranty.
See specific pump and motor name-
plates for all agency Listings.
Check motor nameplate and Flo-
Standard nameplate for all electri­cal ratings.
The FloStandard fixed-speed pump
panel may have safety devices that will stop the motor in the event of electrical, mechanical load or external faults. This does not remove power to the panel.
The FloStandard may have an auto
reset feature in the event of faults, which can result in the pump motor restarting unexpectedly. You must remove all main power to the pump and motor before attempting a repair.
PRE-INsTallaTION ChECks
Open all cartons and inspect for
shipping damage. Report any dam­age to you supplier or shipping carrier immedi­ately.
Verify that all equipment is the correct voltage and phase. Warranty does not cover damage caused by connecting pumps and controls to an incorrect power source (voltage/phase supply).
Record the model numbers and serial numbers from the pumps and control panel on the front of this instruction manual for future reference. Give it to the owner or place it in the plastic protective pocket inside the panel cabinet when finished with the installation.
4
ITT
CENTRIPRO
WARNING
WARNING
WARNING
WARNING
WARNING
Commercial Water Systems
PUmP CONTROl PaNEls aNd WIRINg
NOTE: CONSULT MOTOR AND PUMP MANUALS FOR SPECIFIC
WIRING INSTRUCTIONS.
WIRINg aNd gROUNdINg
IMPORTANT NOTICE: Read Safety Instructions before proceed-
ing with any wiring.
Use only stranded copper wire to pump/mo­tor and ground. The ground wire must be at least as large as the power supply wires. Wires should be color coded for ease of maintenance and troubleshooting.
Install wire and ground according to the National Electrical Code (NEC), or the Canadian Electrical Code, as well as all local, state, and provincial codes.
Disconnect and lockout electrical power be­fore performing any service or installation.
All splices must be waterproof. If using splice kits follow manufacturer’s instructions.
Seal all panel connections tightly from gases or moisture present which may damage elec­trical components.
FAILURE TO PERMANENTLY
GROUND PUMP, MOTOR, AND CONTROLS BEFORE CONNECTING TO POWER CAN CAUSE SHOCK, BURNS, OR DEATH.
sElECTINg CONTROl PaNEls
MATCH EQUIPMENT TO
POWER SUPPLY: It is important
always to match the pump motor voltage, phase, and HP ratings to your control panel and power supply. Record the motor nameplate HP, voltage and phase in the Owner Information table on the cover page. Make sure that the power supply, mo­tor nameplate, and panel nameplate data match. Incorrect voltage or phase can cause fire, motor and control damage and voids the warranty.
WaRNINg PUmP CONTROl PaNEls aNd sWITChEs
It is important to use the wiring
diagrams furnished in the manual and to wire all connections as indicated. Please refer to Figure 1 on page 4 and pages 9-12.
Motor Lead Connections: Locate the terminal block labeled T1, T2, T3 and ground screw. Connect wires to terminal block and route wires through one of the knock out ports on the bottom of the panel. There is room allowed to wire with service loops to avoid wire strain.
Input Power Cable Installation: The main power cable is connected to the terminal block labeled L3, L2, and L1. Room is allowed in the panel to wire with service loops to avoid wire strain.
PaNEl OPERaTION
Operation is with a Hand/Off/Auto (HOA) three­position switch on the panel cover. The pump may be started and stopped at the panel cover by set­ting the switch to the Hand (manual start) or Off positions. When the three-position switch is in the Auto position, start and stopping is controlled only by the wired remote contact or control device.
ChECk ROTaTION
Always verify correct rotation. Correct rotation is usually indicated on the pump casing. Motor direction is reversible. Consult pump and motor manuals for specific instructions.
A full three-phase supply consisting of three indi­vidual transformers or one three-phase transform­er is recommended. “Open” delta or wye connec­tions using only two transformers can be used, but are more likely to cause poor performance, overload tripping or early motor failure due to current unbalance.
Check the current in each of the three motor leads and calculate the current unbalance as explained below.
• If the current unbalance is 2% or less, leave the leads as connected.
5
ITT
CENTRIPRO
Commercial Water Systems
• If the current unbalance is more than 2%, current readings should be checked on each leg using each of the three possible hook-ups. Roll the motor leads across the starter in the same direction to prevent motor reversal.
To calculate percent of current unbalance (see, Example below):
1. Add the three-line amp values together.
2. Divide the sum by three, yielding average
current
3. Pick the amp value, which is furthest from
the average current (either high or low).
4. Determine the difference between this amp
value (furthest from average) and the aver­age.
5. Divide the difference by the average. Multi-
ply the result by 100 to determine percent of unbalance.
Current unbalance should not exceed 5% at ser­vice factor load or 10% at rated input load. If the unbalance cannot be corrected by rolling leads, the source of the unbalance must be located and cor­rected. If, on the three possible hookups, the leg farthest from the average stays on the same power lead, most of the unbalance is coming from the power source.
Contact your local power company to resolve imbalance.
Main Power Supply
L1 L2 L3
Disconnect
Starter
T1 T2 T3
Motor
‡ Class J Fuses are not included. Supplied by other vendors.
Figure 1 – Panel Connection Points
Hookup 1 Hookup 2 Hookup 3
Starter Terminals L1 L2 L3 L1 L2 L3 L1 L2 L3
Motor Leads T3 T1 T2 T2 T3 T1 T1 T2 T3
Example:
T3 = 51 amps T2 = 50 amps T1 = 50 amps T1 = 46 amps T3 = 48 amps T2 = 49 amps T2 = 53 amps T1 = 52 amps T3 = 51 amps Total = 150 amps Total = 150 amps Total = 150 amps ÷ 3 = 50 amps ÷ 3 = 50 amps ÷ 3 = 50 amps – 46 = 4 amps – 48 = 2 amps – 49 = 1 amps 4 ÷ 50 = .08 or 8% 2 ÷ 50 = .04 or 4% 1 ÷ 50 = .02 or 2%
6
ITT
CENTRIPRO
Commercial Water Systems
COmbINaTION sTaRTER aNd OvERlOad RElaY
FloStandard is furnished with a combination starter and overload relay to protect the mo­tor from overload during start-up or operation. Panels designed for use on three phase power also incorporate circuitry that will protect motors from phase loss or phase imbalance, in addition to over­load during start-up or operation.
Figure 2 – Starter/Overload Relay
The following are field adjustments and indications are available and can be referenced from Figure 2 above:
Setting Based on Motor Service Factor: For continuous-rated motors having a service factor (SF) of 1.0, set the current adjustment dial to 90% of the motor’s full-load current (MFLC). For continuous-rated motors having a service factor of 1.15 to 1.25, set the FLA dial indicator current to the MFLC.
Visible Trip Indication: A viewing window on the front of the solid-state overload relay pro­vides visible trip indication. A yellow marker appears when the device is tripped.
When the overload relay detects motor current in excess of 125% of the current adjustment dial set­ting, the overload contacts open and the optional auxiliary contacts change state (N.O. contacts close and N.C. contacts open). The time required for the overload relay to trip depends upon:
• Current value.
• Time elapsed since last trip.
The phase loss/phase imbalance circuitry can detect a phase loss and initiate a trip within three seconds. Phase loss detection extends to a phase loss in either the primary or the secondary of a wye-delta or delta-wye transformer. The circuitry also detects a phase imbalance and initiates a trip when any phase current drops 25% below or rises 25% above the average of the three phase cur­rents.
Reset Bar: The overload relay is reset by depress­ing the reset bar on the front of the device. Since the overload relay trip function is of the “trip­free” design, it cannot be overridden by holding down the reset bar.
Overload Relay Power On Light: A red LED indicates that the power necessary to operate the overload relay protective circuitry is present. This power is derived from the current flowing in the motor leads. When sufficient power is extracted to enable normal operation, the LED blinks. It blinks faster as the current being monitored increases.
Functional Test: To test for proper operation of the overload contacts, de-energize the starter and disconnect the control circuit power. With a small, flat-blade screwdriver, slide the TEST switch located on the bottom of the overload relay to the right. This operates the trip mechanism, opening the N.C. overload contacts at terminals 95 and 96. Verify proper operation of the overload contacts, and then reset the device by depressing the red RESET bar. Reconnect the control circuit power and reenergize the starter as required.
Inspecting and Replacing Contacts: Discoloration and slight pitting do not harm contacts. Do not file contacts; this wastes contact material. Replace con­tacts only when worn thin. To inspect or replace contacts, disconnect all power. Do not remove any wiring. Loosen the four captive screws holding the contact actuator to the contact block. Lift the contact actuator to expose the contacts. Manually operate the contactor or starter with a screwdriver by pushing down the contact carrier. There is a step on the outside of the contact carrier suitable for this use. Replacement starter contacts may be obtained from a local electrical supply house.
7
ITT
CENTRIPRO
Commercial Water Systems
Loss of Phase/Phase Imbalance: The overload relay has phase loss and phase imbalance monitor­ing circuitry. Loss of phase or a phase imbalance of 25% or more of the average of the three phases will result in a trip. Disconnect the unit from the main power supply, find and correct cause for phase loss of phase imbalance. Possible causes would be blown fuse(s) or loose wiring connec­tions. Reset the overload relay with the reset bar on the front of the combination starter. Restart the pump.
CONTROllER FUNCTIONs
FloStandard is designed to accept a variety of inputs to function as a pump controller. Pressure Switches, Level Sensors, Flow Switches, etc. can be used as a dry contact signal to automatically start and stop the pump. Caution should be used to prevent pump cycling when utilizing remote controllers.
sPECIFICaTIONs
GENERAL SPECIFICATIONS:
Enclosure Type Outdoor Use
Operating Temperature 4º F to 122º F
Storage Temperature 20º F to 149º F
Humidity 0-95% non-condensing
ELECTRICAL:
Voltage Input Voltage
Input Line Frequency 50/60 Hz +/- 2 Hz
Line Voltage / 115 Volts Control Voltage AC with control power transformer option
Overload Capacity current for 60 seconds
NEMA 3R Suitable for
+/- 10% Rated Panel
125% of rated RMS
Overload Class 10 or 20
Adjustable setting for Time Overload 125% of rated motor current
Agency Listing UL508A or equivalent
8
Loading...
+ 16 hidden pages