Xylem IMS SOLOQ User Manual

QUICK START GUIDE
IMS-SOLOQ-1
Aquavar SOLO – Quick Installation Guide
1. Mount Aquavar SOLO Drive (in a vertical position);
• Must have 6” minimum clearance on all sides for proper cooling.
2. Wire Input Power to SOLO Drive (Single Phase, 230V)
• Review Circuit Breaker Sizing - see IMS-SOLOQ-2 or IM229
3. Wire Motor Drop Cable to SOLO Drive (75˚C Copper Wire min.)
• 3AS Models - Use with Three Phase, 230V, ¾ to 5 HP Motors
• 1AS15 Model - Compatible w/Single Phase, 230V Motors
3-Wire - .5 - 2 HP CP / Pentek XE; .5 – 1.5 HP FE & Grundfos
2-Wire - .5 – 1.5 CentriPro, Pentek XE, Franklin Elec. & Grundfos 2-Wire
– units with R05K or newer software only.
• Review Wire Sizing (Table 4 of IM229)
4. Mount Transducer and Confirm Transducer Cable Wiring
• Transducer cable maximum length = 200 feet
• Connect Pressure Transducer to piping manifold and to ground
5. User Interface Board Adjustments
• Select proper “Current Limit Setting” (equal to motor SFA)
• 1AS15 Only - Set “Pump Stop Sensitivity” - High is Default
_ _
• 3AS
• Dry Well Sensitivity - Set on “High” position;
• Low Pressure Cut-Off and Pressure Drop setting adjusted to application /
• Optional use of Secondary Switch Connection, refer to IM229
6. Adjust Tank Pressure
• Set approximately 20 PSI below pressure set point
• Adjust as needed to optimize - see IMS-SOLOQ-2 or IM229
7. Turn Drive Power On - Adjust Pressure - Purge Air
• Purge air from system and check for leaks
• Factory default is 50 psi - push and hold Increase Pressure button if
8. Check Motor Rotation and Confirm Performance
Refer to Aquavar SOLO Installation Manual, IM229, for complete details. Check Motor Insulation Resistance on retrot jobs before replacing drive.
Only - Select maximum frequency setting (60 Hz or 80 Hz);
60 Hz = matching Liquid End HP and Motor HP
80 Hz = “over-speed” application; motor HP > Liquid End HP
If nuisance tripping occurs, switch to “Low” position
system requirements.
higher pressure is desired and also adjust tank pre-charge.
Aquavar SOLO User Interface Board
1AS Controllers 3AS Controllers
Drive
Settings /
Protection
Pressure
Adjustment
Current Limit Dial
(Motor Overload Protection)
TRANSDUCER JUMPER
Pressure
Transducer
Connection
Switch Input (Over
Pressure Protection,
Level Control)
Service Factor Amps – All Motors
230 Volt 200 Volt
HP 1Ø 2-Wire 1Ø 3-Wire
CentriPro1 Franklin Grundfos CentriPro1 Franklin Grundfos CentriPro Franklin Grundfos CentriPro Franklin
½ 4.7/4.7 6 6 6.3/6.1 6 6 N/A N/A N/A N/A N/A
¾ 6.4/6.2 8 8.4 8.3/7.8 8 8.4 3.9 3.8 N/A 4.5 4.4
1 9.1/8.1 9.8 9.8 9.7/9.4 9.8 9.8 4.7 4.7 N/A 5.5 5.4
1½ 11.0/10.4 13.12 13.12 11.1/10.9 11.5 11.6 6.1 5.9 7.3 7.2 6.8
2 N/A N/A N/A 12.2 13.22 13.22 7.6 8.1 8.7 8.8 9.3
3 N/A N/A N/A N/A N/A N/A 10.1 10.9 12.2 12 12.5
5 N/A N/A N/A N/A N/A N/A 17.5 17.8 19.82 20.22 20.5
1. CentriPro 2-Wire motors have Generation 1 and Generation 2 amp ratings, see motor nameplate or motor data sticker that was supplied with motor.
2. Amps are higher than controller overload range - use of these motors will current limit and provide reduced performance.
2
Pressure Ranges for All Available Transducers
Transducer
(Min. PSI) (Max. PSI) (Min. PSI) (Max. PSI) (Min. PSI) (Max. PSI)
100 PSI 200 PSI 300 PSI 60 255 60 255 30 150
(1) Standard on 1AS15, 3AS20 and 3AS30 (2) Standard on 3AS50
1AS15 / 3AS20 3AS30 3AS50
(1)
20 85 20 85 10 50
(2)
40 170 40 170 20 100
Xylem Inc.
www.xyleminc.com
© 2012 Xylem Inc. IMS-SOLOQ-1 January 2012
Loading...
+ 4 hidden pages