10. PLANT MANAGER LIST .....................................11
11. LOG BOOK ...........................................................11
2
1. GENERAL
1.1 Foreword
The staff employed on installation, operation,
inspection and maintenance must be able
to prove that they know about the relevant
accident prevention regulations and that they
are suitably qualified for this work. If staff do not have
the relevant knowledge, they should be provided with
suitable instruction.
The operating safety of the pumps or units (i.e. pump
plus motor) supplied is only guaranteed if these are used
in accordance with the provisions in “Installation and
Operation”.
The operator is responsible for following the instructions
and complying with the safety requirements given in
these Operating Instructions.
Smooth operation of the pump or pump unit can only be
achieved if installation and maintenance are carried out
carefully in accordance with the rules generally applied in
the fields of engineering and electrical engineering.
If not all the information can be found in these Operating
Instructions, please contact us.
The manufacturer takes no responsibility for the pump or
pump unit if the Operating Instructions are not followed.
These Operating Instructions should be kept in a safe
place for future use.
If this pump or pump unit is handed on to any third
party, it is essential that these Operating Instructions and
the operating conditions and working limits given in the
Confirmation of Order are also passed on in full.
These Operating Instructions do not take into account
all design details and variants nor all the possible chance
occurrences and events which might happen during
installation, operation and maintenance.
Alterations or changes to the machine are only permitted
by agreement with the manufacturer. Original spare parts
and accessories authorized by the manufacturer should be
used for greater safety. We bear no responsibility for the
consequences of using other parts.
We retain all copyright in these Operating Instructions;
they are intended only for personal use by the owner of
the pump or the pump unit. The Operating Instructions
contain technical instructions and drawings which may
not, as a whole or in part, be reproduced, distributed or
used in any unauthorized way for competitive purposes
or passed on to others.
1.2 Guarantee
The guarantee is given in accordance with our
Conditions of Delivery and/or the confirmation of order.
Repair work during the guarantee period may only be
carried out by our authorized distributor. Otherwise the
guarantee ceases to apply.
The guarantee shall not cover natural wear and tear and
all parts subject to wear, such as impellers, shaft sealings,
shafts, shaft sleeves, bearings, wear rings etc., or damage
caused by transport or improper handling.
In order for the guarantee to apply, it is essential that
the pump or pump unit is used in accordance with
the operating conditions given on the type plate,
confirmation of order and in the Data Sheet. This applies
particularly for the endurance of the materials and
smooth running of the pump and shaft sealing.
If one or more aspects of the actual operating conditions
are different, we should be asked to confirm in writing
that the pump is suitable.
1.3 Safety Regulations
These Operating Instructions contain important
instructions which must be followed when the pump
is assembled and commissioned and during operating
and maintenance. For this reason, these Operating
Instructions must be read by the skilled staff responsible
and/or by the operator of the plant before it is installed
and commissioned, and they must be left permanently
ready to hand at the place where the pump or pump unit
is in use. The operator must ensure that the contents
of the Operating Instructions are fully understood by
the staff. The operator must confirm this by signing the
“Plant Manager List” (see Point 10). These Operating
Instructions do not refer to the General Regulations on
Accident Prevention or local safety and/or operating
regulations. The operator is responsible for complying
with these (if necessary by calling in additional
installation staff).
The safety instructions contained in these Operating
Instructions have the following special safety markings.
Warning against personal accidents which
could occur if the safety instructions given in
this part of the Operating Instructions are not
followed.
WARNING
Hazardous
voltage
ATTENTION: WARNING AGAINST POSSIBLE
DAMAGE TO PROPERTY OR THE
ENVIRONMENT.
It is absolutely essential that safety information affixed
directly to the pump ot pump unit is followed and
maintained so that it is always easily legible.
1.4 Safety Instructions
Dangers of not following safety instructions
Failure to follow the safety instructions can result in the
following, for example:
• People being at risk because of electrical, mechanical
and chemical factors.
• Important functions of the pump or pump unit failing.
• Dangers to the environment.
Safety instruction for the operator
• Depending on the operating conditions, wear and
tear, corrosion or age will limit the working life of
the pump/pump unit, and its specified characteristics.
The operator must ensure that regular inspection
and maintenance are carried out so that all parts
are replaced in good time which would otherwise
endanger the safe operation of the system. If abnormal
operation or any damage are observed, the pump must
cease operation immediately.
• If the breakdown or failure of any system or unit could
lead to people being hurt or property being damaged,
such system or unit must be provided with alarm
devices and/or spare modules, and they should be
tested regularly to ensure that they function properly.
Warning against dangerous electrical
voltage.
3
• If there is any risk of injury from hot or cold machine
parts, these parts must be protected against contact by
the user, or suitable warning signs must be affixed.
• Contact protection on moving parts (e.g. Coupling
guards) must not be removed from systems that are in
operation.
• If dangerous media (e.g. explosive, toxic, hot) leak out
(e.g. from shaft seals), these must be directed away so
that there is no danger to people or the environment.
The provisions of the law must be observed.
• Measures should be taken to exclude any danger from
electricity (e.g. by complying with the local regulations
on electrical equipment). If work is carried out on
live electrical components, they should be unplugged
from the mains or the main switch turned off and fuse
unscrewed. A motor protection switch is to be provided.
• Basically, all work on the pump or pump unit should
only be carried out when the pump is stationary and
not under pressure. All parts must be allowed to return
to ambient temperature. Make sure that no one can
start the motor during such work. It is essential that
the procedure for stopping the system described in the
Operating Instructions is observed. Pumps or pump
systems that carry media that are dangerous to health
must be decontaminated before being taken apart. See
Safety Data Sheets for the various liquids handled. After
the work has been completed, all safety and protective
devices must be replaced or restarted.
Speed, Pressure, Temperature
Suitable safety measures must be taken at the plant to
ensure that the speed, pressure and temperature of the
pump and the shaft sealing do not exceed the limit values
given in the Data Sheet. The given suction pressures must
also be sufficiently high. In addition, the pump must be
protected against pressure surges such as can be caused by
switching off the plant quickly (e.g. by non-return valve on
the pressure side, flywheel, air vessel).
Permitted Forces on Flanges
Basically, the suction and pressure lines should be such that
the forces on the pump are kept to a minimum. If this is
not feasible, contact your distributor for limits.
NPSH
When entering the impeller, the liquid being handled must
have a minimum pressure NPSH to prevent cavitation or
breaking off of flow. This requirement is met if the unit
NPSH value (NPSHA) is well above the pump NPSH value
(NPSHR) under all operating conditions.
Attention must be paid to the NPSH value in particular
when liquids close to boiling point are being handled. If
the value falls below the pump NPSHR value, this can lead
to damage resulting from cavitation or serious damage
from overheating.
The NPSHR for each pump type is given in the sheets of
characteristic curves. We can supply leaflets for calculation
of NPSH values on request.
Sealing, Flushing, Cooling
Suitable facilities for the regulation and monitoring of
sealing, flushing or cooling are to be provided. When
handling dangerous liquids or if temperatures are high,
care should be taken to ensure that the pump ceases
operating if the sealing, flushing or cooling system fails.
Sealing, flushing and cooling systems must always be
operational before the pump is started up. They should
not be taken out of operation until the pump has stopped,
provided that he nature of the operation allows this at all.
Minimum Flows
If the pump is started against a closed pressure line
valve, it should be noted that the power taken up by the
pump is transmitted to the liquid handled in the form
of heat. This can cause the liquid to heat up excessively
within a relatively short time, which will then cause
damage to the pump’s internal fittings. After the pump
has reached operating speed, the discharge valve should
therefore be opened as quickly as possible. If operating
conditions mean that Q = 0 is unavoidable, or if hot
water is circulating, a free flow non-return valve, or, on
smaller systems, a by-pass pipe, should be provided. Your
distributor can help in determining the minimum flow or
designing the by-pass line.
Protection against Running Dry
The pumps must not run dry under any circumstances,
since overheating can damage pump components (e.g.
mechanical seals).
Back Flow
In systems where pumps are operating in closed circuits
under pressure (gas cushions, steam pressure), the pressure
of the gas cushion must not be reduced via the pump,
since the back flow speed may be much higher than the
operating speed, which would destroy the unit.
2. DESCRIPTION
2.1 Model
Design MPVN
Design Features:
• Vertical conguration with separate thrust bearing,
grease lubrication with grease nipples.
• Motors according NEMA-Standard MG 1-4.07.
• Flexible coupling between pump and motor.
• Medium lubricated sleeve bearing in suction casing.
Shaft vertical.
Other installation positions only by agreement.
2.2 Shaft Sealing
Basic design with mechanical seal. Seal code SA with
unbalanced seal; seal code SB with balanced seal.
ATTENTION: YOU WILL FIND MORE INFORMATION ABOUT MECHANICAL SEALS, AND THE
RISKS OF ACCIDENTS THAT THESE
MAY INVOLVE, UNDER POINT 4.6
“OPERATION AND MONITORING”
AND IN POINT 5 “MAINTENANCE
AND REPAIRS’.
2.3 Bearings and Lubrication
Drive Side: re-lubricatable roller bearings (thrust
bearing).
Pump Side: medium-lubricated sleeve bearing in the
suction casing.
4
Lubrication of Roller Bearings
Standard: grease lubrication with grease nipples.
Grease lubricants to be of Lithium Base Grade 2.
The bearings are already filled with grease and are thus
pulleys, sling ropes, etc.) must be sufficiently strong.
• The pump/pump unit may only be lifted by solid
points such as the casing, flanges or frame. The
illustration above shows the correct method of carrying
by crane.
Do not stand underneath suspended loads; take
note of the general regulations on prevention of
accidents.
The pump/pump unit must be secured against tipping
over and slipping until it has been fixed in its final
location.
3.2 Storage
Pump or pump units that are stored for a long time
before use must be protected against moisture,
vibrations and dirt (e.g. by wrapping in oil paper or
plastic sheeting). Pumps must basically be stored in a
place where they are protected from the weather, e.g.
under cover. During this time, all suction and discharge
branches and all other intakes and outlets must be closed
with dummy flanges or plugs.
Preservation
On storing the pump longer than 3 months (depends on
order): Special preservation has been used for shipment
prep. The product used for that must be removed from
the unit before the first normal operation.
4. INSTALLATION, OPERATION
4.1 Assembly and Connection of Pump
MPVN type pumps must be bolted to a xed subframe
(e.g. concrete foundation, steel plate, steel beam, etc.).
The subframe must withstand all loads that arise during
operation. The size of the subframe and the location and
size of the recesses for the foundation anchors are given
in the dimension drawing, which is binding.
ATTENTION: SUFFICIENT SPACE MUST BE
PROVIDED FOR MAINTENANCE
AND REPAIR WORK, ESPECIALLY
FOR REPLACING THE DRIVE
MOTOR OR THE COMPLETE
PUMP UNIT. THE MOTOR FAN
MUST BE ABLE TO TAKE IN
ENOUGH COOL AIR, AND THE
INTAKE GRILLE MUST THEREFORE
BE AT LEAST 10 CM AWAY FROM
ANY WALL, ETC.
To prevent vibrations being transmitted to adjoining
components, the foundation should be laid on a suitable
insulating base (panels providing insulation against
structure-borne sound or vibration panels).
ATTENTION: THE SIZE OF THESE INSULATING
PANELS WILL VARY, DEPENDING
ON CIRCUMSTANCES, AND
SHOULD THEREFORE BE DETERMINED BY AN EXPERIENCED SPECIALIST.
Concrete foundations must be completely set and the
surfaces must be smooth before the pump unit is mounted.
Put pump unit onto the foundation and, if necessary, level
vertically with the help of thin sheet-metal panels (with spirit
level). Tighten foundation anchor evenly and firmly.
The alignment must be carried out with the utmost
care and attention, so that the unit will operate
without failure. If you do not pay attention to this
hint you will lose your warranty!
4.2 Installation and Alignment of Coupling
Make sure that nobody can start the motor
when work is being carried out on the
coupling. In accordance with the Accident
Prevention Regulations, the pump unit may
only be operated when the coupling guard is mounted.
• Before starting installation, carefully clean shaft ends
and coupling components.
• Pull coupling hub onto motor shaft end. The coupling
may be heated beforehand in an oil bath to approx.
100°C. The motor hub will need to be mounted flush
to the motor shaft.
• The motor coupling hub will have an interference t
and the pump coupling hub will have a clearance fit.
The clearance allows the pump hub to be adjusted on
the pump shaft. Keep pump hub loose for adjusting the
elastomer element.
• Place half of the coupling elastomer element around
the hubs and secure with self-locking capscrews.
5
• The elastomer element will space the pump hub. Now
secure the pump hub to the shaft.
• Mount other half of the elastomer element. Tighten all
capscrews to recommended torques.
• Mount coupling guard.
Capscrew Torques
Recommended Capscrew Torques Coupling Torque – Dry
Size In. lbs. Ft. lbs.
2
3
4 204 17
5
10
20
30 360 30
40
Capscrews can be further used
50
60
70 900 75
80
100 3240 270
120
140 7080 590
IMPORTANT
Capscrews have self-locking
patches which should not
be reused more than twice.
with applications of a thread-
locking adhesive.
Do Not Lubricate Capscrew
Threads.
Equipment Alignment
(coupling alignment is directly related to equipment and coupling life.)
Although Omega couplings can withstand gross
misalignment, care should be taken for best possible
alignment to assure optimum performance. The
caliper/straightedge alignment procedure is described
below. If greater alignment accuracy is desired, a dial
indicator method is recommended. There are occasions
when equipment manufacturers require more specific
alignment tolerances, in which case, the manufacturer’s
recommendations should be followed.
• To correct for angular misalignment, use calipers to
check the gap between hubs. Adjust or shim equipment
until the gap is the same at all points around the hubs.
• To correct parallel offset, place a straightedge across
the hub flanges in two places at 90° to each other.
Adjust or shim equipment until the straightedge lays
flat on both sides.
• Tighten down connected equipment and recheck
alignment.
• Install elastomer element, tightening all capscrews to
the values shown in table.
• If practical, recheck and tighten capscrews after several
hours of operation.
PARALLEL OFFSET
ADJUST FOR ANGULAR MISALIGNMENTADJUST FOR PARALLEL OFFSET
4.3 Connecting the Pipes to the Pump
Suction and Discharge Pipe
• The pipes must be of a size and design that liquid can
flow freely into the pump and that the pump functions
without problems. Particular attention is to be paid to
ensuring that suction pipes are airtight and that the
NPSH values are observed. Lay the suction pipe in the
horizontal section towards the pump so that it is slightly
inclined upwards so that no air pockets occur. In most
cases, it is recommended that a non-return valve is
installed in the discharge pipe shortly after the pump.
• When laying the pipes, make sure that the pump is
accessible for maintenance and installation.
• Please note 1.4: “Permitted Forces on Flanges”.
• Before connecting up to pump: remove protective
coverings from suction and discharge branches.
• To protect the shaft sealing (especially mechanical seals)
against foreign bodies, it is recommended that a sieve,
800 micron, is installed in the suction/intake pipe
when the motor is being started up.
• Before starting up, the pipe system, ttings and
equipment must be cleaned to remove weld spatter,
scale etc. Any pollutants are to be completely removed
from pump units that are directly or indirectly
connected to drinking water systems before being
installed and taken into use.
• If the pipe system is tested with the pump installed, do
not exceed the maximum permitted casing pressure of
the pump and/or shaft sealing (see Data Sheet).
• When emptying the pipe after the pressure test, make
sure that the pump is treated properly (danger of rust
and problems when starting up).
• In the case of pumps with stufng boxes, replace
packing after pressure test (packing may be overcompressed and thus no longer suitable for use).
Auxiliary Pipes
Any sealing, flushing or cooling pipe connections that are
necessary must be installed. Please consult the Data Sheet
to see which pipes, pressures and quantities are necessary.
The relevant detail drawing of the shaft sealing contains
a diagrammatic proposal for the pipework and fittings.
This proposal does not take into account the safety
requirements for each specific pump unit.
ATTENTION: POINT 1.4, “SEALING, COOLING”
MUST BE OBSERVED AS REGARDS
REGULATION AND MONITORING.
It is recommended that a pipeline is installed to take off
any leakage from the shaft seal. For connection, see the
Dimension Sheet.
4.4 Electrical Connection
WARNING
Hazardous
voltage
Electrical connection work may
only be carried out by an authorized
professional. The rules and regulations
valid for electrical technology, especially
those concerned with safety measures,
must be observed. The regulations of the
power supply companies operating in
that area must also be observed.
Before starting work, check that the information on the
motor rating plate is the same as the local mains network.
The power supply cable of the coupled drive motor must
be connected up in accordance with the wiring diagram
produced by the motor manufacturer. A protective motor
switch is to be provided.
ATTENTION: THE DIRECTION OF ROTATION
SHOULD ONLY BE CHECKED
WHEN THE PUMP IS FULL. DRY
RUNNING WILL CAUSE DAMAGE
TO THE PUMP.
6
4.5 Starting Up
The plant may only be started up by people who
are familiar with the local safety regulations and
with these Operating Instructions (especially
with the safety regulations and safety instruction
given here).
In order to be able to observe and monitor the shaft sealing,
no protective covering is provided in this area. If the pump
is running, particular care should therefore be taken (watch
out for long hair, loose pieces of clothing etc.).
Hints for the Use as Boiler Feed Pump
Limits for cast iron when used in boiler feed or condensate
applications: pH-value 9,0 (optimum 9,3), short term:
pH-value 8,5.
The above stated values must be guaranteed at the suction
side of the pump in any case.
The water treatment must be in accordance with the
specifications for water treatment of boiler feed water in
steam plants up to 64 bar.
Air traps in the system must be avoided in any case.
Starting up for the First Time
• With MPV type pumps, no further lubrication is needed
before initial start-up.
• Pump and suction pipe must be completely exhausted
from air and filled with handling liquid before each
start up of the pump unit. When filling the pump open
screwed plug “PM2”. Close it when water is flowing out.
• Open slide valve in suction/intake pipe.
• Turn pump unit once again by hand and check that it
moves smoothly and evenly.
• Check that coupling guard is installed and that all safety
devices are operational.
• Switch on any sealing, ushing or cooling devices that are
provided. See Data Sheet for hydraulic requirements.
• Set discharge side slide valve to approx. 25% of rated
flow quantity. With pumps with a discharge branch rated
width less than 200 GPM, the slide valve can remain
closed when starting up (see also Point 1.4 “Minimum
Quantities”.
• Check direction of rotation by switching on and off
briefly. It must be the same as the directional arrow on
the bearing frame.
• Start drive device.
• As soon as it reaches normal operating speed, open
discharge valve immediately and adjust the required
operating point (see Data Sheet).
• Mechanical seals don’t need to be maintained and are
almost free of leakage.
Putting into Operation Again
(after longer standstill; 1 month)
Each time you put the pump into operation again you
have to do the same things you do when starting the pump
for the first time. The control of the rotation direction
of the unit can be dropped. You are only allowed to put
the pump into operation again automatically when the
pump remained filled with liquid during standstill and the
required test drives have been made, see point 4.7.
4.6 Operation and Monitoring
Be particularly careful not to touch hot machine
parts and when working in the unprotected
shaft seal area. Remember that automatically
controlled systems may switch themselves on
suddenly at any time. Suitable warning signs should be
affixed.
ATTENTION: REGULAR MONITORING AND
MAINTENANCE WILL EXTEND THE
LIFE OF YOUR PUMP OR PUMP
SYSTEM.
• You must observe the area of application given on the
Data Sheet.
• Do not exceed the output given on the motor rating
plate.
• Avoid dry running, running against closed discharge
valves or operation while the liquid handled is in the
vapor phase.
• Avoid sudden changes in temperature (temperature
shocks).
• The pump and motor should run evenly and without
vibrations; check at least once a week.
• Check the regulating and monitoring facilities of any
sealing, flushing or cooling systems once a week to
ensure that they function properly. Outgoing cooling
water should be body temperature.
• Pumps which are exposed to corrosive chemicals or to
wear through abrasion must be inspected periodically for
corrosion or wear and tear. The first inspection should
be carried out after six months. All further inspection
intervals should be determined on the basis of the state
of the pump.
Permitted Number of Starts
Do not exceed the pump’s permitted number of starts
– see diagram. With electric motors, the permitted number
of starts is given in the motor operating instructions. If two
different figures are given, the lower figure is valid.
4.7 Shutting Down
• Close slide valve in discharge pipe. This is not necessary
if there is a spring-loaded non-return valve.
• Switch off motor (make sure it runs down quietly.
• Close slide valve on suction side.
• Close auxiliary systems. Do not shut down cooling
system until pump has cooled down.
• If there is any risk of freezing, empty pump, cooling
system and pipes completely.
• If the pump also remains under operating conditions
(pressure and temperature) when stationary: leave all
sealing, flushing and cooling systems switched on.
• If the pump remains under operating conditions when
stationary, test drives have to be made in regular intervals
with a duration of at least 5 minutes. The intervals
7
between the test drives depend on the unit, but they
should be made at least once a week.
4.8 Dismantling
The operator’s or manufacturer’s fitters
should be informed as to the nature of the
liquid handled. In the case of pumps handling
dangerous liquids, the liquid handled should be
disposed of by environmentally acceptable means before
the pump is dismantled.
• Before starting to disassemble the pump unit make sure
that it cannot be switched on again.
• The pump casing must be depressurized and empty.
• All valves in the suction, intake and discharge pipes
must be closed.
• All components must have cooled down to ambient
temperature.
• To avoid corrosion it is recommended to ush the
pump and fill it with a water-repellant preservative,
e.g. KLÜBERTOP K01.601 or equal.
• To spread the preservative turn the pump several times
with the hand. Then drain the pump and lock the
nozzles.
5. MAINTENANCE, SERVICING
Work should only be carried out on the pump
or pump unit when it is not in operation. You
must observe Point 1.4 “Safety Instructions”.
ATTENTION: MAINTENANCE AND SERVICING
WORK MUST ONLY BE CARRIED
OUT BY TRAINED, EXPERIENCED
STAFF WHO ARE FAMILIAR WITH
THE CONTENTS OF THESE
OPERATING INSTRUCTIONS, OR BY
THE DISTRIBUTOR’S OWN SERVICE
STAFF. THE WORK CARRIED OUT
MUST BE DULY ENTERED IN THE
“LOG BOOK” (SEE POINT 11) AND
CONFIRMED BY BEING SIGNED.
Mechanical Seals
Before opening the pump, it is essential that
you note Point 1.4 “Safety Instructions”, Point
4.8 “Dismantling” and Point 8 “Repairs”.
Mechanical seals do not need to be maintained and
are completely free of leakage. Pumps with mechanical
seals must only be operated when completely filled and
without air locks (or air pockets). The seal casing where
the mechanical seal is located must always be filled with
the sealing liquid. If the liquid being handled drips out at
the mechanical seal, it is damaged and must be replaced.
When installing the mechanical seal, make sure that
the seal cavity is absolutely clean, particular care has to
be paid to the surface of the seal rings. To facilitate the
slip-on of the rotating components of the seal onto the
shaft, lubricate all moving components and sliding areas
by means of water, soapy water or soft soap. Use mineral
oils only in case all elastomers are oil resistant. Do not
lubricate the surface of the seal rings. Do not force
elastomeric elements over sharp edges, if necessary use
assembling aiding sleeves.
Lubrication of Bearing
• Intervals of re-lubrication/grease quantities (see point
2.3 “bearing and lubrication”).
8
• If the pump is left non-operational for any length of
time, the grease in the bearings should be changed
after 2 years.
Coupling
When inspecting the element, look for fatigue cracks
(over ½") originating near the stress relief grooves
(approximately ¼" – ½" above the metal shoe),
discoloration (a darker faded orange color signals
possible material degradation) or surface cracking if used
in adverse conditions such as cooling towers or severe
environments (pH < 4 or pH > 10).
In critical applications, the probability of unexpected
downtime can be greatly diminished by scheduling
flexible element replacement at regular intervals. The
frequency of replacement will depend upon the severity
of the application and environmental conditions. A
properly sized element which is stored and operated
under normal conditions (i.e. under 85% humidity and
85°F) should obtain a minimum of 6 to 8 years of service
life after the date of manufacture. A production date
sticker is applied to all elements for ease of inspection
(I.E. 3Q93 indicates Third Quarter 1993 production).
After the coupling has been in operation for some time,
a “torsional set” may develop in the flex element (up to
1
⁄4" on a size E40, even more on larger sizes). This does
not affect the performance of the coupling, as it is simply
the material creeping under the applied stress. A very
large torsional set may suggest a sizing problem and will
warrant a close review of the application and coupling
selection parameters. For ease of assembly/disassembly,
elements should be re-installed in the same “position of
rotation” in which they were removed.
INSPECT
HERE
Cleaning the Pump
Dirt on the outside of the pump has an adverse effect
on transmission of heat. The pump should therefore be
cleaned with water at regular intervals (depending on the
degree of dirt).
ATTENTION: THE PUMP SHOULD NOT BE
CLEANED WITH PRESSURIZED
WATER – WATER WILL GET INTO
THE BEARINGS AND INTO THE
MOTOR.
6. LONGER PERIODS OF NON-OPERATION
6.1 Drained Pumps
• Turn by hand at least 1 x week (do not switch on because
of dry running).
• If necessary, unblock by tapping gently on the coupling in
axial direction.
• Change the grease in the bearings after 2 years.
• Replace bearings after 5 years.
6.2 Filled Pumps
• Switch stand-by pumps on and immediately off again
once a week.
• If the stand-by pump is at operating pressure and
temperature:
• Change the grease in the bearings after 2 years.
• Replace bearings after 5 years.
7. FAULTS – CAUSES AND SOLUTIONS
The following notes on causes of faults and how to
repair them are intended as an aid to recognizing the
problem. The distributor’s Customer Service Department
is available to help repair faults that the operator cannot
or does not want to repair. If the operator repairs or
changes the pump, the design data on the Data Sheet and
Points 1.2 – 1.4 of these Operating Instructions should be
particularly taken into account. If necessary, the written
agreement of the distributor must be obtained.
Code no. 7, 10, 14, 22, 23, 24, 25, 29, 30, 33
TEMPERATURE IN THE PUMP TOO HIGH
Code no. 7, 10, 30
TEMPERATURE IN THE SHAFT SEALING TOO
HIGH
Code no. 18, 19, 21
TEMPERATURE AT THE BEARING TOO HIGH
Code no. 2, 14, 23, 24, 25, 26, 29, 31, 32
PUMP LEAKING
Code no. 25, 28
LEAKAGE RATE AT SHAFT SEALING TOO HIGH
Code no. 19, 21, 22, 25
MEANING OF CODE NUMBER FOR CAUSE AND
METHOD OF REPAIR
1. Back-pressure too high
• open discharge valve further
• reduce resistance in discharge pipe (e.g. clean lter if
necessary)
• Use larger impeller (note available motor power)
2. Back-pressure too low, discharge too low
• throttle discharge valve
3. Speed too high
• reduce speed
• compare speed of motor with specied pump speed
(rating plate)
• when adjusting speed (frequency transformer) check
reference value setting
4. Speed too low
• increase speed (check available motor power)
•compare speed of motor with specied pump speed
(rating plate)
• when adjusting speed (frequency transformer) check
reference value settings
5. Impeller diameter too large
• use smaller impeller
6. Impeller diameter too small
• use larger impeller (check available motor power)
7. Pump and/or pipes not completely filled with liquid
• ll
• vent
8. Pump or suction/intake pipe blocked
• clean
9. Air pocket in pipeline
• vent
• improve course of pipe
10. NPSH of system too small
• increase liquid level
• increase admission pressure
• reduce resistance in the intake/suction pipe (change
course and rated width, open shutoff valves, clean
filters)
11. Air being sucked in
• increase liquid level
• check suction pipe is vacuum-tight
• provide straightening vanes in suction pipe ttings with
water seal
12. Air being sucked in through shaft sealing
• clean sealing pipe
• increase sealing pressure
• replace shaft sealing
13. Direction of rotation is wrong
• swap over two phases of power supply (to be done by
a specialist electrician)
14. Inner components suffering from wear
• replace worn parts
15. Density and/or viscosity of liquid handled is too high
• seek assistance
16. Shaft sealing worn
• check sealing, ushing and cooling pipes (pressure)
• avoid dry running
17. Lines and roughness on shaft or shaft sleeve
• replace parts
18. Deposits on mechanical seal
• clean
• replace mechanical seal if necessary
• if necessary provide additional rinsing or quench
19. Impeller out of balance
• remove blocks/deposits
• replace if broken or unevenly worn
• check shafts to ensure that they are running true
20. Coupling not aligned
• align pump unit better
21. Coupling distance too small
• change
22. Forces in pipeline too high (pump unit under strain)
• change (support pipes, use copensators, etc.)
• is foundation plate/frame properly cast in place?
23. Too much, too little or the wrong type of lubricant
• change
24. Electricity supply not right
• check voltage of all phases (2-phase running)
• check cable connections
• check fuses
25. Sealing insufficient
• tighten screws
• replace sealing
26. Bearing damaged
• replace
• check lubricant and bearing cavity for pollutants (clean
grease cavity if needed)
27. Discharge too small
• increase min. amount carried (open slide valves, bypass)
28. Discharge too high
• reduce amount carried (throttle slide valve)
9
29. Relief fittings insufficient
• clean balance in impeller
• replace worn parts (impeller, split rings)
• adjust in line with the system pressure/intake
pressure given on ordering
30. System-related vibrations (resonance)
• seek assistance
31. Flow indicator wrong
• check owmeter
• get rid of blockages
• put owmeter in suitable place (no ow distortion
or burbling)
8. REPAIRS
Repairs to the pump or pump system may only
be carried out by authorized skilled personnel
or by the distributor’s specialist staff.
Trained Customer Service engineers are available to
assist with installation and repair work on request. When
removing the pump, you must comply with Point 1.4
“Safety Instructions”, Point 3.1 “Transport, Handling”
and Point 4.8 “Dismantling”.
9. SPARE PARTS, SPARE PUMPS
9.1 Spare Parts
Spare parts should be selected to last for two-years
continuous operation. If no other guidelines are
applicable, we recommend that you stock the number of
parts listed below.
ATTENTION: TO ENSURE OPTIMUM AVAILABILITY, WE RECOMMEND
THAT SUITABLE QUANTITIES OF
SPARE PARTS ARE HELD IN STOCK,
ESPECIALLY IF THESE ARE MADE
FROM SPECIAL MATERIALS AND IN
THE CASE OF MECHANICAL SEALS,
BECAUSE OF THE LONGER
DELIVERY TIMES.
Ordering Spare Parts
When ordering spare parts, please supply the following
information:
Pump Type:
Pump Order No.
Part Designation in sectional drawing
All the information is given in the Data Sheet and the
relevant sectional drawing.
9.2 Stand-By Pumps
It is essential that a sufficient number of standby pumps are kept ready for use in plants where
failure of a pump could endanger human life or
cause damage to property or high costs. Regular
checks should be carried out to ensure that such pumps are
always ready for use (see Point 6.2).
Number of Pumps (including stand-by pumps)
2 3 4 5 6/7 8/9 10+
Spare Part Number of Spare Parts
Impeller i i i 2i 2i 3i 30%
Diffuser i/2 i/2 i/2 i i 3i/2 15%
Shaft with key and shaft screws/nuts 1 1 2 2 2 3 30%
Bearing (roller bearing) 1 1 2 2 2 3 30%
Shaft sleeve 2 2 2 3 3 4 50%
Joints for Pump Casing – sets 4 6 8 8 9 12 150%
Other joints†– sets 4 6 8 8 9 10 100%
Mechanical seal 2 3 4 5 6 7 90%
i = no. of stages
10
10. PLANT MANAGER LIST
Each plant manager should sign below to confirm that he has received, read and understood these Operating
Instructions. He undertakes to follow the instructions conscientiously. If these instructions are not followed, the
manufacturer’s guarantee and liability shall cease to apply.
Name: Date: Signature:
11. LOG BOOK
Each plant operator shall duly enter all maintenance and service work that has been carried out, and shall see that the
person responsible confirms such work by signing below.
Plant Operator Person Responsible
Maintenance Work Date
Signature Confirmed By
11
Loading...
+ 25 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.