INSTRUCTION MANUAL
IM138
HMC
Close-Coupled Centrifugal Pump
INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS
Table of Contents
Table of Contents
SUBJECT PAGE
Important Information ................................................................................................................................................3
Installation ..................................................................................................................................................................3
Operation ....................................................................................................................................................................3
Maintenance................................................................................................................................................................3
Red Jacket Water Products Limited Warranty ..............................................................................................................4
2
IMPORTANT
IMPORTANT
A. Inspect unit for shipping damage. Report damage to car-
rier immediately.
B. Electrical supply must be a separate branch circuit with
fuses or circuit breakers, wire sizes, per national and local
electrical codes.
C. ALWAYS disconnect electrical power when handling
pump or controls. Install all-leg disconnect switch near
pump.
D. Motors must be wired for proper voltage. (CHECK
NAMEPLATE). Wire size must limit voltage drop to 10%
of nameplate voltage at motor terminals, or motor life
and pump performance will be lowered.
E. Single-Phase: Thermal protection for single-phase units is
sometimes built-in (CHECK NAMEPLATE). If no builtin protection is provided, use a contactor with proper
overload. Fusing is permissible is properly fused.
F. Three-Phase: Provide three-leg protection with a proper
size magnetic starter.
lowed. Motor branch circuit must be protected by a suitable
manual or magnetic starter. Proper fusing and time delay for
starting must be selected to codes. Low voltage protection is
recommended.
Single phase motors are dual voltage, 115/230 V, 60 Hz,
A.C. All pumps are tested at the factory. At installation,
correct rotation (3-phase), phase, frequency and voltage
of power supply must be checked. Power lines must be of
proper size to carry the amperage.
Single Phase 3 HP motors are dual voltage 115/230 V,
60 Hz, A.C. Single phase 5 HP motors are 230 V, 60 Hz,
A.C. All other motors are three phase dual voltage
230/460 V, 60 Hz, A.C. The high voltages are
recommended wherever available.
Three phase rotation must be checked at installation.
Close, then break contacts quickly, observing rotation of
exposed portion of rotating parts. Rotation must agree with
arrow on pump casing. Standard rotation is counter-clockwise viewed from suction end. Motor wiring can be changed
in the field by following wiring diagram inside terminal box
cover or on motor nameplate.
G. Maximum liquid temperatures: HSC & 3673 plastic
fitted, 180°F (82°C) maximum. 3642-3656-3673, AI, BF,
AB, 212° F (100°C) with optional high-temperature seal.
H. Regular inspection and maintenance will increase service
life. Base schedule on operating time.
INSTALLATION
INSTALLATION
Location – Locate the pump as near the liquid source as
practical (below the level of liquid storage if automatic
operation is contemplated). Protect unit from cold weather
or water damage due to flooding. Low static lift and short,
direct suction and discharge pipes are desirable. At suction
lift higher than 15 ft. consult the pump performance curve
for NPSHR (Net Positive Suction Head - Required). Suction
pipe must be at least equal in size to suction connection of
pump, and slope upward to the pump to avoid air pockets.
If pipe larger than pump suction is used, an eccentric pipe
reducer must be used at the pump. Gate valve in suction is
necessary only on positive suction head installation and must
not be used to throttle the pump.
Allow adequate room for servicing and ventilation.
Foundation – Bolt unit to foundation for easy dismantling.
Foundation surface must be flat so there is no distortion and/
or strain developed when tightening bolts. The pumps are
quiet and smooth running, but rubber mounting is desirable
on foundations susceptible to sound effect.
Alignment – No filed alignment is necessary as pumps are
close-coupled.
Wiring – National Electric Code and local codes must be fol-
OPERATION
OPERATION
Fill suction pipe and casing with liquid to be pumped to
insure mechanical seal will not run dry. Four plugs are
provided in the casing. In any position one will be on top for
priming and/or venting and another at bottom for draining.
With pump primed and motor properly wired, the unit may
be started. Be sure pump is not started against a closed valve
in the discharge line.
Maximum temperature (212° F) limitation is imposed by the
mechanical seal material. Optional high temperature seals
are available.
MAINTENANCE
MAINTENANCE
1. Lubrication
Pumps should require no maintenance.
Motors use double-shielded ball bearings, prelubricated
for the life of the bearings. No further lubrication is
required.
2. Replacing Mechanical Seal
A) Dismantling:
1. Turn off power.
2. Drain system.
3. Remove bolts holding motor adapter to
foundation.
4. Remove casing bolts.
5. Remove motor and rotating element from
casing, leaving casing and piping undisturbed.
6. Insert a screwdriver in impeller waterway
passage. Remove impeller nut with a socket
wrench (5⁄8” across flats).
7. Remove impeller from shaft as follows:
3
a) Franklin motors:
Remove motor shaft end cap. Insert a
screwdriver in slot of motor shaft. While
holding shaft from rotation, unscrew impeller
from shaft by turning counter-clockwise
when facing it. To loosen three phase and
metal impellers, use a torch to apply heat
to exposed shaft thread and impeller hub, as
locking compound was used to secure
impeller in place.
b) A.O. Smith motors:
Remove motor end cover. Insert 7⁄16” open end
wrench under switch mechanism onto flats
on motor shaft. While holding shaft from
rotating, unscrew impeller from shaft.
Heat may be required as indicated in 7a.
8. Pry off rotating member of mechanical seal
from shaft by using two (2) screwdrivers
(Fig. 1).
Figure 1
with LOCQUIC®, Primer “T” - Loctite® product
Item No. 74756. (Purchase at Automotive
Parts or Hardware). Let parts dry and then
apply Loctite® #271 on same parts.
6. Hold shaft from rotating as described in
paragraph 7 of Dismantling. Thread impeller
on shaft until it is tight against shaft
shoulder.
7. Apply locking compound and replace
impeller nut. Hold impeller from rotating as
indicated in paragraph 6 of dismantling.
8. Remove burrs caused by screwdriver on
periphery of impeller in waterway passages.
9. Replace motor and rotating element in
casing. Be sure to install new gasket.
10. Tighten casing bolts alternately and evenly.
11. Replace hold-down bolts.
12. Check for free rotation after assembly is
complete.
13. Replace hold-down bolts.
14. Close all drain openings. Use pipe joint
compound on male threads.
15. Reprime before starting. Do not start unit
until pump is completely filled with water.
9. Remove bolts holding adapter to motor.
10. Place adapter on a flat surface. Push out
stationary parts of mechanical seal (seat and
rubber mounting cup).
B) Reassembly:
1. Clean gasket and flange faxes, male and
female locks, seal seat counterbore and shaft,
and in particular the shaft shoulder fitting
against impeller.
2. Lube counterbore of adapter and rubber
bushing of stationary seal with water or light
oil. Press stationary seat in counterbore
squarely and evenly. Caution: Do not mar the
lapped face of seat.
3. Remount adapter on motor. Make sure motor
shaft does not dislocate stationary seat of
the seal.
4. Apply a thin coat of light oil or water to
motor shaft and the rubber seal member of
seal. Slide rotating member of mechanical
seal on motor shaft. Be sure rotating seal face
stays in holding collar during installation.
Take extra care not to damage the seal
lapped faces.
5. Spray both shaft and metal impeller threads
4
This warranty applies to all water systems pumps manufactured by Red Jacket Water Products.
Any part or parts found to be defective within the warranty period shall be replaced at no charge to the dealer during the warranty period. The war-
ranty period shall exist for a period of twelve (12) months from date of installation or eighteen (18) months from date of manufacture, whichever
period is shorter.
A dealer who believes that a warranty claim exists must contact the authorized Red Jacket Water Products distributor from whom the pump was
purchased and furnish complete details regarding the claim. The distributor is authorized to adjust any warranty claims utilizing the Red Jacket Water
Products Customer Service Department.
The warranty excludes:
(a) Labor, transportation and related costs incurred by the dealer;
(b) Reinstallation costs of repaired equipment;
(c) Reinstallation costs of replacement equipment;
(d) Consequential damages of any kind; and,
(e) Reimbursement for loss caused by interruption of service.
For purposes of this warranty, the following terms have these definitions:
(1) “Distributor” means any individual, partnership, corporation, association, or other legal relationship that stands between Red Jacket Water Products
and the dealer in purchases, consignments or contracts for sale of the subject pumps.
(2) “Dealer” means any individual, partnership, corporation, association, or other legal relationship which engages in the business of selling or leasing
pumps to customers.
(3) “Customer” means any entity who buys or leases the subject pumps from a dealer. The “customer” may mean an individual, partnership, corpora-
tion, limited liability company, association or other legal entity which may engage in any type of business.
THIS WARRANTY EXTENDS TO THE DEALER ONLY.
RED JACKET WATER PRODUCTS LIMITED WARRANTY
Xylem, Inc.
2881 East Bayard Street Ext., Suite A
Seneca Falls, NY 13148
Phone: (866) 325-4210
Fax: (888) 322-5877
www.xyleminc.com/brands/redjacketwaterproducts
Red Jacket Water Products is a trademark of Xylem Inc. or one of its subsidiaries.
© 2012 Xylem Inc. IM138 Revision Number 1 July 2012
5