Toshiba RAS-M10SKCV, RAS-M22NKCV1, RAS-M22SKCV, RAS-4M26SACV, RAS-M13SKCV SERVICE MANUAL

...
4 (2)

FILE NO.A07-007

Revised 1: Jul., 2008

SERVICE MANUAL

AIR-CONDITIONER

SPLIT TYPE

RAS-M10SKCV, RAS-M13SKCV, RAS-M16SKCV, RAS-M22SKCV, RAS-M22NKCV1 / RAS-4M26SACV

R410A

PRINTED IN JAPAN, Jul., 2008 ToMo

CONTENTS

1.

SAFETY PRECAUTIONS ..........................................................................

3

2.

SPECIFICATIONS......................................................................................

5

3.

REFRIGERANT R410A ...........................................................................

13

4.

CONSTRUCTION VIEWS ........................................................................

21

5.

WIRING DIAGRAM ..................................................................................

25

6.

SPECIFICATIONS OF ELECTRICAL PARTS .........................................

29

7.

REFRIGERANT CYCLE DIAGRAM ........................................................

30

8.

CONTROL BLOCK DIAGRAM ................................................................

32

9.

OPERATION DESCRIPTION ...................................................................

34

10.

INSTALLATION PROCEDURE ................................................................

60

11.

HOW TO DIAGNOSE THE PROBLEM .....................................................

84

12.

HOW TO REPLACE THE MAIN PARTS .................................................

112

13.

EXPLODED VIEWS AND PARTS LIST .................................................

134

1. SAFETY PRECAUTIONS

Power supply cord of outdoor unit shall be more than 2.5 mm² (H07RN-F or 60245IEC66) polychloroprene sheathed flexible cord.

Read this “SAFETY PRECAUTIONS” carefully before servicing.

The precautions described below include the important items regarding safety. Observe them without fail.

After the servicing work, perform a trial operation to check for any problem.

Turn off the main power supply switch (or breaker) before the unit maintenance.

CAUTION

New Refrigerant Air Conditioner Installation

THIS AIR CONDITIONER ADOPTS THE NEW HFC REFRIGERANT (R410A) WHICH DOES NOT DESTROY OZONE LAYER.

R410A refrigerant is apt to be affected by impurities such as water, oxidizing membrane, and oils because the working pressure of R410A refrigerant is approx. 1.6 times higher than that of refrigerant R22. Accompanied with the adoption of the new refrigerant, the refrigeration machine oil has also been changed.

Therefore, during installation work, be sure that water, dust, former refrigerant, or refrigeration machine oil does not enter into the new type refrigerant R410A air conditioner circuit.

To prevent mixing of refrigerant or refrigerating machine oil, the sizes of connecting sections of charging port on main unit and installation tools are different from those used for the conventional refrigerant units.

Accordingly, special tools are required for the new refrigerant (R410A) units.

For connecting pipes, use new and clean piping materials with high pressure fittings made for R410A only, so that water and/or dust does not enter. Moreover, do not use the existing piping because there are some problems with pressure fittings and possible impurities in existing piping.

CAUTION

TO DISCONNECT THE APPLIANCE FROM THE MAIN POWER SUPPLY

This appliance must be connected to the main power supply by a circuit breaker or a switch with a contact separation of at least 3 mm.

DANGER

ASK AN AUTHORIZED DEALER OR QUALIFIED INSTALLATION PROFESSIONAL TO INSTALL/MAINTAIN THE AIR CONDITIONER.

INAPPROPRIATE SERVICING MAY RESULT IN WATER LEAKAGE, ELECTRIC SHOCK OR FIRE.

TURN OFF MAIN POWER SUPPLY BEFORE ATTEMPTING ANY ELECTRICAL WORK.

MAKE SURE ALL POWER SWITCHES ARE OFF. FAILURE TO DO SO MAY CAUSE ELECTRIC SHOCK.

DANGER: HIGH VOLTAGE

The high voltage circuit is incorporated.

Be careful to do the check service, as the electric shock may be caused in case of touching parts on the P.C. board by hand.

CORRECTLY CONNECT THE CONNECTING CABLE. IF THE CONNECTING CABLE IS INCORRECTLY CONNECTED, ELECTRIC PARTS MAY BE DAMAGED.

CHECK THAT THE EARTH WIRE IS NOT BROKEN OR DISCONNECTED BEFORE SERVICE AND INSTALLATION. FAILURE TO DO SO MAY CAUSE ELECTRIC SHOCK.

DO NOT INSTALL NEAR CONCENTRATIONS OF COMBUSTIBLE GAS OR GAS VAPORS. FAILURE TO FOLLOW THIS INSTRUCTION CAN RESULT IN FIRE OR EXPLOSION.

3 –

TO PREVENT THE INDOOR UNIT FROM OVERHEATING AND CAUSING A FIRE HAZARD, PLACE THE UNIT WELL AWAY (MORE THAN 2 M) FROM HEAT SOURCES SUCH AS RADIATORS, HEAT RESISTORS, FURNACE, STOVES, ETC.

WHEN MOVING THE AIR-CONDITIONER FOR INSTALLATION IN ANOTHER PLACE, BE VERY CAREFUL NOT TO ALLOW THE SPECIFIED REFRIGERANT (R410A) TO BECOME MIXED WITH ANY OTHER GASEOUS BODY INTO THE REFRIGERATION CIRCUIT.

IF AIR OR ANY OTHER GAS IS MIXED IN THE REFRIGERANT, THE GAS PRESSURE IN THE REFRIGERATION CIRCUIT WILL BECOME ABNORMALLY HIGH AND IT MAY RESULT IN THE PIPE BURSTING AND POSSIBLE PERSONNEL INJURIES.

IN THE EVENT THAT THE REFRIGERANT GAS LEAKS OUT OF THE PIPE DURING THE SERVICE WORK AND THE INSTALLATION WORK, IMMEDIATELY LET FRESH AIR INTO THE ROOM.

IF THE REFRIGERANT GAS IS HEATED, SUCH AS BY FIRE, GENERATION OF POISONOUS GAS MAY RESULT.

WARNING

Never modify this unit by removing any of the safety guards or bypass any of the safety interlock switches.

Do not install in a place which cannot bear the weight of the unit. Personal injury and property damage can result if the unit falls.

After the installation work, confirm that refrigerant gas does not leak.

If refrigerant gas leaks into the room and flows near a fire source such as a cooking range, noxious gas may generate.

The electrical work must be performed by a qualified electrician in accordance with the Installation Manual. Make sure the air conditioner uses an exclusive circuit.

An insufficient circuit capacity or inappropriate installation may cause fire.

When wiring, use the specified cables and connect the terminals securely to prevent external forces applied to the cable from affecting the terminals.

Be sure to provide grounding.

Do not connect ground wires to gas pipes, water pipes, lightning rods or ground wires for telephone cables. Inappropriate grounding may cause electric shock.

Conform to the regulations of the local electric company when wiring the power supply.

CAUTION

Exposure of unit to water or other moisture before installation may result in an electrical short. Do not store in a wet basement or expose to rain or water.

Do not install in a place that can increase the vibration of the unit.

Do not install in a place that can amplify the noise level of the unit or where noise or discharged air might disturb neighbors.

To avoid personal injury, be careful when handling parts with sharp edges.

Perform the specified installation work to guard against an earthquake.

If the air conditioner is not installed appropriately, accidents may occur due to the falling unit.

For Reference:

If a heating operation would be continuously performed for a long time under the condition that the outdoor temperature is 0°C or lower, drainage of defrosted water may be difficult due to freezing of the bottom plate, resulting in a problem of the cabinet or fan.

It is recommended to procure an antifreeze heater locally for a safe installation of the air conditioner.

For details, contact the dealer.

– 4 –

2. SPECIFICATIONS

The indoor and outdoor units that can be used in combination are shown in the tables below.

Table of models that can be connected

Type

Outdoor unit

 

Indoor unit

RAS-

 

 

 

 

 

 

 

 

 

 

 

M10SKCV

M13SKCV

M16SKCV

 

M22NKCV1

M22SKCV

Cooling-only

RAS-4M26SACV

 

 

 

 

 

 

M10SDCV

M13SDCV

M16SDCV

 

M22SDCV

 

 

 

 

 

 

 

 

 

 

 

NOTES

1-room connection is not an option for the indoor units (you cannot connect only one indoor unit).

Be sure to connect indoor units in two rooms or more.

The contents noted in this service manual limit the indoor units to the RAS-M10SKCV, RAS-M13SKCV, RAS-M16SKCV, RAS-M22SKCV and RAS-M22NKCV1.

For other indoor units that can also be used in combination, see the service manual of each indoor unit.

Indoor unit

File No.

RAS-M10SDCV

RAS-M13SDCV

A07-002

RAS-M16SDCV

RAS-M22SDCV

– 5 –

2-1. Specifications

<Cooling only Models>

RAS-M10SKCV, RAS-M13SKCV, RAS-M16SKCV, RAS-M22NKCV1 / RAS-4M26SACV

Unit model

 

Indoor

 

 

RAS-M10SKCV, RAS-M13SKCV, RAS-M16SKCV, RAS-M22NKCV1

 

Outdoor

 

 

 

 

RAS-4M26SACV

 

 

 

 

 

 

 

 

Cooling capacity

 

 

 

 

 

(kW)

 

 

 

7.5

 

 

Cooling capacity range

 

(kW)

 

 

3.7 – 10.0

 

Heating capacity

 

 

 

 

 

(kW)

 

 

 

 

Heating capacity range

 

(kW)

 

 

 

 

Power supply

 

 

 

 

 

 

 

220–240 V, 1 Ph, 50Hz / 220 V, 1 Ph, 60Hz

 

 

 

 

 

 

 

Unit model

 

RAS-M10SKCV

 

RAS-M13SKCV

 

RAS-M16SKCV

 

RAS-M22NKCV1

 

 

Indoor

 

Running current

(A)

0.21 / 0.20 / 0.19

 

0.21 / 0.20 / 0.19

 

0.21 / 0.20 / 0.19

 

0.31 / 0.30 / 0.29

 

 

 

Power consumption

(W)

35

 

35

 

30

 

45

 

 

 

 

 

 

 

 

 

Electric

 

 

 

 

 

Power factor

(%)

75

 

75

 

65

 

45

 

 

 

 

 

Operation mode

 

 

 

Cooling

 

characteristics

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Running current

(A)

 

10.54 / 10.08 / 9.66

 

 

 

 

 

 

 

 

 

 

 

 

 

Total

 

 

Power consumption

(W)

 

2200

 

 

 

 

 

 

 

 

Power factor

(%)

 

 

 

95

 

 

 

 

 

 

 

 

Starting current

(A)

 

10.54 / 10.08 / 9.66

 

 

COP (Cooling)

 

 

 

 

 

 

 

3.41

 

 

 

 

 

 

 

 

Unit model

 

RAS-M10SKCV

 

RAS-M13SKCV

 

RAS-M16SKCV

 

RAS-M22NKCV1

 

 

Indoor

 

High

dB (A)

38 / –

 

39 / –

 

45 / –

 

45 / –

Operating

 

(Cooling/Heating)

 

Medium

dB (A)

33 / –

 

33 / –

 

40 / –

 

42 / –

noise

 

 

 

 

 

Low

dB (A)

26 / –

 

26 / –

 

30 / –

 

37 / –

 

 

Outdoor

 

Cooling

dB (A)

 

 

 

48

 

 

 

 

 

Heating

dB (A)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Unit model

 

 

RAS-M10SKCV

 

RAS-M13SKCV

 

RAS-M16SKCV

 

RAS-M22NKCV1

 

 

 

 

 

 

Height

(mm)

275

 

275

 

275

 

298

 

 

Dimension

 

Width

(mm)

790

 

790

 

790

 

998

Indoor unit

 

 

 

 

 

Depth

(mm)

205

 

205

 

205

 

220

 

 

Net weight

 

(kg)

9

 

9

 

9

 

13

 

 

Fan motor output

 

(W)

20

 

20

 

30

 

30

 

 

Air flow rate (Cooling/Heating)

(m³/h)

535 / –

 

565 / –

 

690 / –

 

850 / –

 

 

 

 

 

 

Height

(mm)

 

 

 

795

 

 

 

 

Dimension

 

Width

(mm)

 

 

 

900

 

 

 

 

 

 

 

 

Depth

(mm)

 

 

 

320

 

 

 

 

Net weight

 

(kg)

 

 

 

61

 

 

Outdoor unit

 

 

 

 

 

Motor output

(W)

 

2000

 

 

 

Compressor

 

Type

 

Twin rotary type with DC-inverter variable speed control

 

 

 

 

 

 

 

 

 

 

Model

 

 

 

DA220A1F-20L

 

 

 

Fan motor output

 

(W)

 

 

 

60

 

 

 

 

Air flow rate

 

(m³/h)

 

 

High : 3200, Medium : 2800

 

 

 

Type

 

 

 

 

 

 

Flare connection

 

 

 

 

 

 

 

Unit model

 

RAS-M10SKCV

 

RAS-M13SKCV

 

RAS-M16SKCV

 

RAS-M22NKCV1

 

 

Indoor unit

 

Liquid side

 

Ø6.35

 

Ø6.35

 

Ø6.35

 

Ø6.35

 

 

 

 

 

 

Gas side

 

Ø9.52

 

Ø9.52

 

Ø12.7

 

Ø12.7

 

 

 

 

 

 

A unit liquid side/gas side

 

Ø6.35 / Ø12.7

 

 

 

 

Outdoor unit

 

B unit liquid side/gas side

 

Ø6.35 / Ø9.52

 

 

 

 

 

C unit liquid side/gas side

 

Ø6.35 / Ø9.52

 

 

 

 

 

 

 

 

 

 

 

Piping

 

 

 

 

 

D unit liquid side/gas side

 

Ø6.35 / Ø9.52

 

 

 

Maximum length (per unit)

(m)

 

 

 

25

 

 

connection

 

 

 

 

 

 

 

Minimum length (per unit)

(m)

 

 

 

2

 

 

 

 

 

 

 

 

 

 

 

Maximum length (total)

(m)

 

 

 

70

 

 

 

 

Maximum chargeless length

 

 

 

 

70

 

 

 

 

Additional refrigerant

 

 

 

No additional refrigerant

 

 

 

Maximum height difference

(m)

 

 

 

15

 

 

 

 

Name of refrigerant

 

 

 

 

R410A

 

 

 

Weight

 

(kg)

 

2.20

 

 

Wiring connection

 

Power supply

 

 

 

 

3 wires : includes earth

 

 

Interconnection

 

 

 

4 wires : includes earth

 

 

 

 

 

 

 

 

 

Usable

 

 

Indoor

(Cooling/Heating)

(°C)

 

 

21 – 32 / –

 

temperature range

Outdoor

(Cooling/Heating)

(°C)

 

 

10 – 46 / –

 

 

 

 

 

 

 

Installation plate

 

 

1

 

 

 

1

 

 

 

 

 

 

Wireless remote controller

 

1

 

 

 

1

 

 

 

 

 

 

Batteries

 

 

2

 

 

 

2

 

 

 

 

 

 

Remote controller holder

 

1

 

 

 

1

 

 

 

 

 

 

Pan head wood screw

 

 

 

2 (Ø3.1 × 16L)

 

 

 

2 (Ø3.1 × 16L)

 

 

Indoor unit

 

Super Oxi Deo filter

 

 

1

 

 

 

Accessory

 

 

Super Steriling filter

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Zeolite plus sasa filter

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bio Gingo filter

 

 

 

 

 

 

1

 

 

 

 

 

 

Mounting screw

 

 

 

6 (Ø4 × 25L)

 

 

 

6 (Ø4 × 25L)

 

 

 

 

 

 

Owner’s manual

 

 

1

 

 

 

1

 

 

 

 

 

 

Installation manual

 

 

1

 

 

 

1

 

 

Outdoor unit

 

Owner’s manual

 

 

 

 

1

 

 

 

 

 

Installation manual

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

For performance when each indoor unit is combined with other unit, refer to the separate table.

The specifications may be subject to change without notice for purpose of improvement.

– 6 –

RAS-M22SKCV

Unit model

Indoor

 

 

RAS-M22SKCV

 

 

 

 

Outdoor

 

 

RAS-4M26SACV

 

 

 

 

 

 

 

 

Cooling capacity

 

 

(kW)

7.5

 

 

 

 

 

Cooling capacity range

 

(kW)

3.7 – 10.0

 

 

 

 

 

Heating capacity

 

 

(kW)

 

 

 

 

 

Heating capacity range

 

(kW)

 

 

 

 

 

Power supply

 

 

 

220–240 V, 1 Ph, 50Hz / 220 V, 1 Ph, 60Hz

 

 

 

 

 

 

 

Unit model

 

RAS-M22SKCV

 

 

 

 

 

Electric

Indoor

Running current

(A)

0.38 / 0.36 / 0.35

characteristics

Power consumption

(W)

50

 

 

 

 

 

 

 

 

Power factor

(%)

60

 

 

 

 

 

 

Indoor

High

dB (A)

47

 

 

 

 

Operating noise

Medium

dB (A)

41

Sound presure level

 

 

 

 

 

Low

dB (A)

35

 

 

 

 

 

 

 

 

 

Height

(mm)

320

 

 

 

 

 

 

Dimension

Width

(mm)

1050

 

 

 

 

 

Indoor unit

 

Depth

(mm)

228

 

 

 

 

Net weight

 

(kg)

13

 

 

 

 

 

 

 

 

Fan motor output

 

(W)

30

 

 

 

 

 

 

Air flow rate

 

(m³/h)

1080

 

 

 

 

 

 

Type

 

 

Flare connection

 

 

 

 

 

Piping connection

Indoor unit

Liquid side

 

Ø6.35

 

 

 

Gas side

 

Ø12.7

 

 

 

 

Name of refrigerant

 

 

R410A

 

 

 

 

 

Wiring connection

Indoor unit

Interconnection

 

4 wires : includes earth

 

 

 

 

 

Usable temperature range

Indoor

(°C)

21 – 32

 

 

 

 

 

 

 

Installation plate

 

1

 

 

 

 

 

 

 

Wireless remote controller

 

1

 

 

 

 

 

 

 

Batteries

 

2

 

 

 

 

 

 

 

Remote controller holder

 

1

 

 

 

 

 

Accessory

Indoor unit

Pan head wood screw

 

2 (Ø3.1 × 16L)

 

 

 

Super Oxi Deo filter

 

1

 

 

 

 

 

 

 

 

 

 

Super Steriling filter

 

1

 

 

 

 

 

 

 

Mounting screw

 

6 (Ø4 × 25L)

 

 

Owner’s manual

 

1

 

 

 

 

 

 

 

Installation manual

 

1

 

 

 

 

 

For performance when each indoor unit is combined with other unit, refer to the separate table.

The specifications may be subject to change without notice for purpose of improvement.

– 7 –

2-2. Specifications of Performance When Each Indoor Unit is Combined with Other Unit

<Current limited : Full operation / 220V>

Current

Power

Operating

 

Indoor unit

 

Operating

 

Cooling

Power

Operating

Outdoor

supply

 

 

 

capacity

consumption

current

noise

limited

status

 

 

 

 

 

 

 

 

 

 

(V)

A

 

B

C

 

D

A

B

C

D

(kW)

(W)

(A)

(dB)

 

 

 

 

 

 

 

10

 

2.70

2.7

750

4.49

48

 

 

 

 

(1.4 to 3.2)

(640 to 950)

(3.88 to 5.61)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

 

3.70

3.7

1200

6.06

48

 

 

1 unit

 

(1.4 to 4.4)

(640 to 1520)

(3.88 to 7.51)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

 

4.50

4.5

1650

8.15

48

 

 

 

 

 

 

 

 

(1.4 to 5.0)

(640 to 2000)

(3.88 to 9.67)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

22

 

6.00

6.0

2020

9.87

48

 

 

 

 

(2.4 to 6.8)

(660 to 2500)

(4.00 to 11.97)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

 

10

 

2.70

2.70

5.4

1560

7.71

48

 

 

 

 

 

(2.5 to 6.3)

(640 to 2040)

(3.88 to 9.97)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

 

10

 

3.41

2.49

5.9

1850

9.04

48

 

 

 

 

 

(2.7 to 6.6)

(660 to 2220)

(4.00 to 10.63)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

 

10

 

3.94

2.36

6.3

2040

9.86

48

 

 

 

 

 

(2.9 to 6.9)

(670 to 2400)

(4.06 to 11.50)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

 

13

 

3.15

3.15

6.3

2120

10.25

48

 

 

 

 

 

(2.9 to 6.9)

(670 to 2400)

(4.06 to 11.50)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

 

13

 

3.73

3.07

6.8

2290

10.97

48

 

 

2 units

 

 

(3.0 to 7.2)

(670 to 2570)

(4.06 to 12.31)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

 

16

 

3.60

3.60

7.2

2550

12.21

48

 

 

 

 

 

 

 

 

 

 

(3.2 to 7.5)

(670 to 2750)

(4.06 to 13.17)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

22

 

10

 

4.97

2.23

7.2

2250

10.78

48

 

 

 

 

 

(3.3 to 8.0)

(670 to 2690)

(4.06 to 12.88)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

22

 

13

 

4.64

2.86

7.5

2550

12.21

48

 

 

 

 

 

(3.4 to 8.3)

(700 to 2850)

(4.24 to 13.65)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

22

 

16

 

4.29

3.21

7.5

2500

11.97

48

 

 

 

 

 

(3.4 to 8.5)

(700 to 2880)

(4.24 to 13.79)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

22

 

22

 

3.75

3.75

7.5

2430

11.64

48

 

 

 

 

 

(3.4 to 9.0)

(700 to 2950)

(4.24 to 14.13)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

 

10

10

 

2.50

2.50

2.50

7.5

2400

11.50

48

 

 

 

 

 

(3.5 to 8.2)

(750 to 2720)

(4.43 to 13.03)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

 

10

10

 

3.04

2.23

2.23

7.5

2400

11.50

48

 

 

 

 

 

(3.5 to 8.4)

(750 to 2780)

(4.43 to 13.32)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

 

10

10

 

3.40

2.05

2.05

7.5

2400

11.50

48

 

 

 

 

 

(3.5 to 8.6)

(750 to 2840)

(4.43 to 13.60)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

 

13

10

 

2.75

2.75

2.00

7.5

2400

11.50

48

 

 

 

 

 

(3.5 to 8.6)

(750 to 2840)

(4.43 to 13.60)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

 

13

10

 

3.10

2.55

1.85

7.5

2400

11.50

48

 

 

 

 

 

(3.5 to 8.8)

(750 to 2900)

(4.43 to 13.89)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Full

220

 

13

 

13

13

 

2.50

2.50

2.50

7.5

2400

11.50

48

operation

 

 

 

(3.5 to 8.8)

(750 to 2900)

(4.43 to 13.89)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

 

16

10

 

2.88

2.88

1.74

7.5

2400

11.50

48

 

 

 

 

 

(3.5 to 8.9)

(750 to 2930)

(4.43 to 14.03)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3 units

16

 

13

13

 

2.84

2.33

2.33

7.5

2400

11.50

48

 

 

 

 

(3.5 to 8.9)

(750 to 2930)

(4.43 to 14.03)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

 

16

13

 

2.66

2.66

2.18

7.5

2400

11.50

48

 

 

 

 

 

(3.5 to 9.1)

(750 to 2990)

(4.43 to 14.32)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

 

16

16

 

2.50

2.50

2.50

7.5

2400

11.50

48

 

 

 

 

 

(3.5 to 9.3)

(750 to 3050)

(4.43 to 14.61)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

22

 

10

10

 

3.94

1.78

1.78

7.5

2400

11.50

48

 

 

 

 

 

(3.5 to 9.0)

(750 to 2950)

(4.43 to 14.13)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

22

 

13

10

 

3.63

2.24

1.63

7.5

2400

11.50

48

 

 

 

 

 

(3.5 to 9.1)

(750 to 2960)

(4.43 to 14.18)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

22

 

13

13

 

3.36

2.07

2.07

7.5

2400

11.50

48

 

 

 

 

 

(3.5 to 9.1)

(750 to 2960)

(4.43 to 14.18)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

22

 

16

10

 

3.41

2.56

1.53

7.5

2400

11.50

48

 

 

 

 

 

(3.5 to 9.1)

(750 to 2960)

(4.43 to 14.18)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

22

 

16

13

 

3.17

2.38

1.95

7.5

2400

11.50

48

 

 

 

 

 

(3.5 to 9.2)

(750 to 2970)

(4.43 to 14.23)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

 

10

10

10

1.88

1.88

1.88

1.88

7.5

2200

10.54

48

 

 

 

 

(3.7 to 9.5)

(800 to 3170)

(4.72 to 15.18)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

 

10

10

10

2.34

1.72

1.72

1.72

7.5

2200

10.54

48

 

 

 

 

(3.7 to 9.6)

(800 to 3200)

(4.72 to 15.33)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

 

10

10

10

2.67

1.61

1.61

1.61

7.5

2200

10.54

48

 

 

 

 

(3.7 to 9.8)

(800 to 3270)

(4.72 to 15.66)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

 

13

10

10

2.17

2.17

1.58

1.58

7.5

2200

10.54

48

 

 

 

 

(3.7 to 9.8)

(800 to 3270)

(4.72 to 15.66)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

 

13

10

10

2.48

2.04

1.49

1.49

7.5

2200

10.54

48

 

 

4 units

 

(3.7 to 9.9)

(800 to 3300)

(4.72 to 15.81)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

 

13

13

10

2.01

2.01

2.01

1.47

7.5

2200

10.54

48

 

 

 

 

 

 

 

 

(3.7 to 9.9)

(800 to 3300)

(4.72 to 15.81)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

 

13

13

10

2.31

1.90

1.90

1.39

7.5

2200

10.54

48

 

 

 

 

(3.7 to 10.0)

(800 to 3330)

(4.72 to 15.95)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

 

13

13

13

1.88

1.88

1.88

1.88

7.5

2200

10.54

48

 

 

 

 

(3.7 to 10.0)

(800 to 3330)

(4.72 to 15.95)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

 

16

10

10

2.34

2.34

1.41

1.41

7.5

2200

10.54

48

 

 

 

 

(3.7 to 10.0)

(800 to 3330)

(4.72 to 15.95)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

22

 

10

10

10

3.18

1.44

1.44

1.44

7.5

2200

10.54

48

 

 

 

 

(3.7 to 10.0)

(800 to 3300)

(4.72 to 15.81)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

– 8 –

<Current limited : Full operation / 230V>

Current

Power

Operating

 

Indoor unit

 

Operating

 

Cooling

Power

Operating

Outdoor

supply

 

 

 

capacity

consumption

current

noise

limited

status

 

 

 

 

 

 

 

 

 

 

(V)

A

 

B

C

 

D

A

B

C

D

(kW)

(W)

(A)

(dB)

 

 

 

 

 

 

 

10

 

2.70

2.7

750

4.29

48

 

 

 

 

(1.4 to 3.2)

(640 to 950)

(3.71 to 5.36)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

 

3.70

3.7

1200

5.80

48

 

 

1 unit

 

(1.4 to 4.4)

(640 to 1520)

(3.71 to 7.18)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

 

4.50

4.5

1650

7.80

48

 

 

 

 

 

 

 

 

(1.4 to 5.0)

(640 to 2000)

(3.71 to 9.25)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

22

 

6.00

6.0

2020

9.44

48

 

 

 

 

(2.4 to 6.8)

(660 to 2500)

(3.83 to 11.45)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

 

10

 

2.70

2.70

5.4

1560

7.37

48

 

 

 

 

 

(2.5 to 6.3)

(640 to 2040)

(3.71 to 9.54)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

 

10

 

3.41

2.49

5.9

1850

8.65

48

 

 

 

 

 

(2.7 to 6.6)

(660 to 2220)

(3.83 to 10.17)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

 

10

 

3.94

2.36

6.3

2040

9.44

48

 

 

 

 

 

(2.9 to 6.9)

(670 to 2400)

(3.88 to 11.00)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

 

13

 

3.15

3.15

6.3

2120

9.81

48

 

 

 

 

 

(2.9 to 6.9)

(670 to 2400)

(3.88 to 11.00)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

 

13

 

3.73

3.07

6.8

2290

10.49

48

 

 

2 units

 

 

(3.0 to 7.2)

(670 to 2570)

(3.88 to 11.77)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

 

16

 

3.60

3.60

7.2

2550

11.68

48

 

 

 

 

 

 

 

 

 

 

(3.2 to 7.5)

(670 to 2750)

(3.88 to 12.60)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

22

 

10

 

4.97

2.23

7.2

2250

10.31

48

 

 

 

 

 

(3.3 to 8.0)

(670 to 2690)

(3.88 to 12.32)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

22

 

13

 

4.64

2.86

7.5

2550

11.68

48

 

 

 

 

 

(3.4 to 8.3)

(700 to 2850)

(4.06 to 13.06)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

22

 

16

 

4.29

3.21

7.5

2500

11.45

48

 

 

 

 

 

(3.4 to 8.5)

(700 to 2880)

(4.06 to 13.19)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

22

 

22

 

3.75

3.75

7.5

2430

11.13

48

 

 

 

 

 

(3.4 to 9.0)

(700 to 2950)

(4.06 to 13.52)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

 

10

10

 

2.50

2.50

2.50

7.5

2400

11.00

48

 

 

 

 

 

(3.5 to 8.2)

(750 to 2720)

(4.23 to 12.46)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

 

10

10

 

3.04

2.23

2.23

7.5

2400

11.00

48

 

 

 

 

 

(3.5 to 8.4)

(750 to 2780)

(4.23 to 12.74)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

 

10

10

 

3.40

2.05

2.05

7.5

2400

11.00

48

 

 

 

 

 

(3.5 to 8.6)

(750 to 2840)

(4.23 to 13.01)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

 

13

10

 

2.75

2.75

2.00

7.5

2400

11.00

48

 

 

 

 

 

(3.5 to 8.6)

(750 to 2840)

(4.23 to 13.01)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

 

13

10

 

3.10

2.55

1.85

7.5

2400

11.00

48

 

 

 

 

 

(3.5 to 8.8)

(750 to 2900)

(4.23 to 13.29)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Full

230

 

13

 

13

13

 

2.50

2.50

2.50

7.5

2400

11.00

48

operation

 

 

 

(3.5 to 8.8)

(750 to 2900)

(4.23 to 13.29)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

 

16

10

 

2.88

2.88

1.74

7.5

2400

11.00

48

 

 

 

 

 

(3.5 to 8.9)

(750 to 2930)

(4.23 to 13.42)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3 units

16

 

13

13

 

2.84

2.33

2.33

7.5

2400

11.00

48

 

 

 

 

(3.5 to 8.9)

(750 to 2930)

(4.23 to 13.42)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

 

16

13

 

2.66

2.66

2.18

7.5

2400

11.00

48

 

 

 

 

 

(3.5 to 9.1)

(750 to 2990)

(4.23 to 13.70)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

 

16

16

 

2.50

2.50

2.50

7.5

2400

11.00

48

 

 

 

 

 

(3.5 to 9.3)

(750 to 3050)

(4.23 to 13.97)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

22

 

10

10

 

3.94

1.78

1.78

7.5

2400

11.00

48

 

 

 

 

 

(3.5 to 9.0)

(750 to 2950)

(4.23 to 13.52)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

22

 

13

10

 

3.63

2.24

1.63

7.5

2400

11.00

48

 

 

 

 

 

(3.5 to 9.1)

(750 to 2960)

(4.23 to 13.56)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

22

 

13

13

 

3.36

2.07

2.07

7.5

2400

11.00

48

 

 

 

 

 

(3.5 to 9.1)

(750 to 2960)

(4.23 to 13.56)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

22

 

16

10

 

3.41

2.56

1.53

7.5

2400

11.00

48

 

 

 

 

 

(3.5 to 9.1)

(750 to 2960)

(4.23 to 13.56)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

22

 

16

13

 

3.17

2.38

1.95

7.5

2400

11.00

48

 

 

 

 

 

(3.5 to 9.2)

(750 to 2970)

(4.23 to 13.61)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

 

10

10

10

1.88

1.88

1.88

1.88

7.5

2200

10.08

48

 

 

 

 

(3.7 to 9.5)

(800 to 3170)

(4.52 to 14.52)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

 

10

10

10

2.34

1.72

1.72

1.72

7.5

2200

10.08

48

 

 

 

 

(3.7 to 9.6)

(800 to 3200)

(4.52 to 14.66)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

 

10

10

10

2.67

1.61

1.61

1.61

7.5

2200

10.08

48

 

 

 

 

(3.7 to 9.8)

(800 to 3270)

(4.52 to 14.98)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

 

13

10

10

2.17

2.17

1.58

1.58

7.5

2200

10.08

48

 

 

 

 

(3.7 to 9.8)

(800 to 3270)

(4.52 to 14.98)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

 

13

10

10

2.48

2.04

1.49

1.49

7.5

2200

10.08

48

 

 

4 units

 

(3.7 to 9.9)

(800 to 3300)

(4.52 to 15.12)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

 

13

13

10

2.01

2.01

2.01

1.47

7.5

2200

10.08

48

 

 

 

 

 

 

 

 

(3.7 to 9.9)

(800 to 3300)

(4.52 to 15.12)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

 

13

13

10

2.31

1.90

1.90

1.39

7.5

2200

10.08

48

 

 

 

 

(3.7 to 10.0)

(800 to 3330)

(4.52 to 15.26)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

 

13

13

13

1.88

1.88

1.88

1.88

7.5

2200

10.08

48

 

 

 

 

(3.7 to 10.0)

(800 to 3330)

(4.52 to 15.26)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

 

16

10

10

2.34

2.34

1.41

1.41

7.5

2200

10.08

48

 

 

 

 

(3.7 to 10.0)

(800 to 3330)

(4.52 to 15.26)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

22

 

10

10

10

3.18

1.44

1.44

1.44

7.5

2200

10.08

48

 

 

 

 

(3.7 to 10.0)

(800 to 3300)

(4.52 to 15.12)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

– 9 –

<Current limited : Full operation / 240V>

Current

Power

Operating

 

Indoor unit

 

Operating

 

Cooling

Power

Operating

Outdoor

supply

 

 

 

capacity

consumption

current

noise

limited

status

 

 

 

 

 

 

 

 

 

 

(V)

A

 

B

C

 

D

A

B

C

D

(kW)

(W)

(A)

(dB)

 

 

 

 

 

 

 

10

 

2.70

2.7

750

4.11

48

 

 

 

 

(1.4 to 3.2)

(640 to 950)

(3.56 to 5.14)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

 

3.70

3.7

1200

5.56

48

 

 

1 unit

 

(1.4 to 4.4)

(640 to 1520)

(3.56 to 6.88)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

 

4.50

4.5

1650

7.47

48

 

 

 

 

 

 

 

 

(1.4 to 5.0)

(640 to 2000)

(3.56 to 8.87)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

22

 

6.00

6.0

2020

9.05

48

 

 

 

 

(2.4 to 6.8)

(660 to 2500)

(3.67 to 10.98)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

 

10

 

2.70

2.70

5.4

1560

7.07

48

 

 

 

 

 

(2.5 to 6.3)

(640 to 2040)

(3.56 to 9.14)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

 

10

 

3.41

2.49

5.9

1850

8.29

48

 

 

 

 

 

(2.7 to 6.6)

(660 to 2220)

(3.67 to 9.75)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

 

10

 

3.94

2.36

6.3

2040

9.04

48

 

 

 

 

 

(2.9 to 6.9)

(670 to 2400)

(3.72 to 10.54)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

 

13

 

3.15

3.15

6.3

2120

9.40

48

 

 

 

 

 

(2.9 to 6.9)

(670 to 2400)

(3.72 to 10.54)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

 

13

 

3.73

3.07

6.8

2290

10.05

48

 

 

2 units

 

 

(3.0 to 7.2)

(670 to 2570)

(3.72 to 11.28)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

 

16

 

3.60

3.60

7.2

2550

11.20

48

 

 

 

 

 

 

 

 

 

 

(3.2 to 7.5)

(670 to 2750)

(3.72 to 12.07)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

22

 

10

 

4.97

2.23

7.2

2250

9.88

48

 

 

 

 

 

(3.3 to 8.0)

(670 to 2690)

(3.72 to 11.81)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

22

 

13

 

4.64

2.86

7.5

2550

11.20

48

 

 

 

 

 

(3.4 to 8.3)

(700 to 2850)

(3.89 to 12.51)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

22

 

16

 

4.29

3.21

7.5

2500

10.98

48

 

 

 

 

 

(3.4 to 8.5)

(700 to 2880)

(3.89 to 12.64)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

22

 

22

 

3.75

3.75

7.5

2430

10.67

48

 

 

 

 

 

(3.4 to 9.0)

(700 to 2950)

(3.89 to 12.95)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

 

10

10

 

2.50

2.50

2.50

7.5

2400

10.54

48

 

 

 

 

 

(3.5 to 8.2)

(750 to 2720)

(4.06 to 11.94)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

 

10

10

 

3.04

2.23

2.23

7.5

2400

10.54

48

 

 

 

 

 

(3.5 to 8.4)

(750 to 2780)

(4.06 to 12.21)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

 

10

10

 

3.40

2.05

2.05

7.5

2400

10.54

48

 

 

 

 

 

(3.5 to 8.6)

(750 to 2840)

(4.06 to 12.47)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

 

13

10

 

2.75

2.75

2.00

7.5

2400

10.54

48

 

 

 

 

 

(3.5 to 8.6)

(750 to 2840)

(4.06 to 12.47)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

 

13

10

 

3.10

2.55

1.85

7.5

2400

10.54

48

 

 

 

 

 

(3.5 to 8.8)

(750 to 2900)

(4.06 to 12.73)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Full

240

 

13

 

13

13

 

2.50

2.50

2.50

7.5

2400

10.54

48

operation

 

 

 

(3.5 to 8.8)

(750 to 2900)

(4.06 to 12.73)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

 

16

10

 

2.88

2.88

1.74

7.5

2400

10.54

48

 

 

 

 

 

(3.5 to 8.9)

(750 to 2930)

(4.06 to 12.86)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3 units

16

 

13

13

 

2.84

2.33

2.33

7.5

2400

10.54

48

 

 

 

 

(3.5 to 8.9)

(750 to 2930)

(4.06 to 12.86)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

 

16

13

 

2.66

2.66

2.18

7.5

2400

10.54

48

 

 

 

 

 

(3.5 to 9.1)

(750 to 2990)

(4.06 to 13.13)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

 

16

16

 

2.50

2.50

2.50

7.5

2400

10.54

48

 

 

 

 

 

(3.5 to 9.3)

(750 to 3050)

(4.06 to 13.39)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

22

 

10

10

 

3.94

1.78

1.78

7.5

2400

10.54

48

 

 

 

 

 

(3.5 to 9.0)

(750 to 2950)

(4.06 to 12.95)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

22

 

13

10

 

3.63

2.24

1.63

7.5

2400

10.54

48

 

 

 

 

 

(3.5 to 9.1)

(750 to 2960)

(4.06 to 13.00)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

22

 

13

13

 

3.36

2.07

2.07

7.5

2400

10.54

48

 

 

 

 

 

(3.5 to 9.1)

(750 to 2960)

(4.06 to 13.00)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

22

 

16

10

 

3.41

2.56

1.53

7.5

2400

10.54

48

 

 

 

 

 

(3.5 to 9.1)

(750 to 2960)

(4.06 to 13.00)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

22

 

16

13

 

3.17

2.38

1.95

7.5

2400

10.54

48

 

 

 

 

 

(3.5 to 9.2)

(750 to 2970)

(4.06 to 13.04)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

 

10

10

10

1.88

1.88

1.88

1.88

7.5

2200

9.66

48

 

 

 

 

(3.7 to 9.5)

(800 to 3170)

(4.33 to 13.92)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

 

10

10

10

2.34

1.72

1.72

1.72

7.5

2200

9.66

48

 

 

 

 

(3.7 to 9.6)

(800 to 3200)

(4.33 to 14.05)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

 

10

10

10

2.67

1.61

1.61

1.61

7.5

2200

9.66

48

 

 

 

 

(3.7 to 9.8)

(800 to 3270)

(4.33 to 14.36)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

 

13

10

10

2.17

2.17

1.58

1.58

7.5

2200

9.66

48

 

 

 

 

(3.7 to 9.8)

(800 to 3270)

(4.33 to 14.36)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

 

13

10

10

2.48

2.04

1.49

1.49

7.5

2200

9.66

48

 

 

4 units

 

(3.7 to 9.9)

(800 to 3300)

(4.33 to 14.49)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

 

13

13

10

2.01

2.01

2.01

1.47

7.5

2200

9.66

48

 

 

 

 

 

 

 

 

(3.7 to 9.9)

(800 to 3300)

(4.33 to 14.49)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

 

13

13

10

2.31

1.90

1.90

1.39

7.5

2200

9.66

48

 

 

 

 

(3.7 to 10.0)

(800 to 3330)

(4.33 to 14.62)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

 

13

13

13

1.88

1.88

1.88

1.88

7.5

2200

9.66

48

 

 

 

 

(3.7 to 10.0)

(800 to 3330)

(4.33 to 14.62)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

 

16

10

10

2.34

2.34

1.41

1.41

7.5

2200

9.66

48

 

 

 

 

(3.7 to 10.0)

(800 to 3330)

(4.33 to 14.62)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

22

 

10

10

10

3.18

1.44

1.44

1.44

7.5

2200

9.66

48

 

 

 

 

(3.7 to 10.0)

(800 to 3300)

(4.33 to 14.49)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

– 10 –

<Current limited : 11A / 230V>

Current

Power

Operating

 

Indoor unit

 

Operating

 

Cooling

Power

Operating

Outdoor

supply

 

 

 

capacity

consumption

current

noise

limited

status

 

 

 

 

 

 

 

 

 

 

(V)

A

 

B

C

 

D

A

B

C

D

(kW)

(W)

(A)

(dB)

 

 

 

 

 

 

 

10

 

2.70

2.7

750

4.29

48

 

 

 

 

(1.4 to 3.2)

(640 to 950)

(3.71 to 5.36)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

 

3.70

3.7

1200

5.80

48

 

 

1 unit

 

(1.4 to 4.4)

(640 to 1520)

(3.71 to 7.18)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

 

4.50

4.5

1650

7.80

48

 

 

 

 

 

 

 

 

(1.4 to 5.0)

(640 to 2000)

(3.71 to 9.25)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

22

 

6.00

6.0

2020

9.44

48

 

 

 

 

(2.4 to 6.5)

(660 to 2400)

(3.83 to 11.00)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

 

10

 

2.70

2.70

5.4

1560

7.37

48

 

 

 

 

 

(2.5 to 6.3)

(640 to 2040)

(3.71 to 9.54)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

 

10

 

3.41

2.49

5.9

1850

8.65

48

 

 

 

 

 

(2.7 to 6.6)

(660 to 2220)

(3.88 to 10.17)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

 

10

 

3.94

2.36

6.3

2040

9.44

48

 

 

 

 

 

(2.9 to 6.9)

(670 to 2400)

(3.88 to 11.00)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

 

13

 

3.15

3.15

6.3

2120

9.81

48

 

 

 

 

 

(2.9 to 6.9)

(670 to 2400)

(3.88 to 11.00)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

 

13

 

3.73

3.07

6.8

2290

10.49

48

 

 

2 units

 

 

(3.0 to 7.1)

(670 to 2400)

(3.88 to 11.00)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

 

16

 

3.55

3.55

7.1

2400

11.00

48

 

 

 

 

 

 

 

 

 

 

(3.2 to 7.1)

(670 to 2400)

(3.88 to 11.00)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

22

 

10

 

4.97

2.23

7.2

2250

10.31

48

 

 

 

 

 

(3.3 to 7.3)

(670 to 2400)

(3.88 to 11.00)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

22

 

13

 

4.52

2.78

7.3

2400

11.00

48

 

 

 

 

 

(3.4 to 7.3)

(700 to 2400)

(4.06 to 11.00)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

22

 

16

 

4.17

3.13

7.3

2400

11.00

48

 

 

 

 

 

(3.4 to 7.3)

(700 to 2400)

(4.06 to 11.00)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

22

 

22

 

3.70

3.70

7.4

2400

11.00

48

 

 

 

 

 

(3.4 to 7.4)

(700 to 2400)

(4.06 to 11.00)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

 

10

10

 

2.50

2.50

2.50

7.5

2400

11.00

48

 

 

 

 

 

(3.5 to 7.5)

(750 to 2400)

(4.23 to 11.00)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

 

10

10

 

3.04

2.23

2.23

7.5

2400

11.00

48

 

 

 

 

 

(3.5 to 7.5)

(750 to 2400)

(4.23 to 11.00)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

 

10

10

 

3.40

2.05

2.05

7.5

2400

11.00

48

 

 

 

 

 

(3.5 to 7.5)

(750 to 2400)

(4.23 to 11.00)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

 

13

10

 

2.75

2.75

2.00

7.5

2400

11.00

48

 

 

 

 

 

(3.5 to 7.5)

(750 to 2400)

(4.23 to 11.00)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

 

13

10

 

3.10

2.55

1.85

7.5

2400

11.00

48

 

 

 

 

 

(3.5 to 7.5)

(750 to 2400)

(4.23 to 11.00)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

11A

230

 

13

 

13

13

 

2.50

2.50

2.50

7.5

2400

11.00

48

 

 

 

(3.5 to 7.5)

(750 to 2400)

(4.23 to 11.00)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

 

16

10

 

2.88

2.88

1.74

7.5

2400

11.00

48

 

 

 

 

 

(3.5 to 7.5)

(750 to 2400)

(4.23 to 11.00)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3 units

16

 

13

13

 

2.84

2.33

2.33

7.5

2400

11.00

48

 

 

 

 

(3.5 to 7.5)

(750 to 2400)

(4.23 to 11.00)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

 

16

13

 

2.66

2.66

2.18

7.5

2400

11.00

48

 

 

 

 

 

(3.5 to 7.5)

(750 to 2400)

(4.23 to 11.00)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

 

16

16

 

2.50

2.50

2.50

7.5

2400

11.00

48

 

 

 

 

 

(3.5 to 7.5)

(750 to 2400)

(4.23 to 11.00)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

22

 

10

10

 

3.94

1.78

1.78

7.5

2400

11.00

48

 

 

 

 

 

(3.5 to 7.5)

(750 to 2400)

(4.23 to 11.00)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

22

 

13

10

 

3.63

2.24

1.63

7.5

2400

11.00

48

 

 

 

 

 

(3.5 to 7.5)

(750 to 2400)

(4.23 to 11.00)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

22

 

13

13

 

3.36

2.07

2.07

7.5

2400

11.00

48

 

 

 

 

 

(3.5 to 7.5)

(750 to 2400)

(4.23 to 11.00)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

22

 

16

10

 

3.41

2.56

1.53

7.5

2400

11.00

48

 

 

 

 

 

(3.5 to 7.5)

(750 to 2400)

(4.23 to 11.00)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

22

 

16

13

 

3.17

2.38

1.95

7.5

2400

11.00

48

 

 

 

 

 

(3.5 to 7.5)

(750 to 2400)

(4.23 to 11.00)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

 

10

10

10

1.88

1.88

1.88

1.88

7.5

2200

10.08

48

 

 

 

 

(3.7 to 7.7)

(800 to 2400)

(4.52 to 11.00)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

 

10

10

10

2.34

1.72

1.72

1.72

7.5

2200

10.08

48

 

 

 

 

(3.7 to 7.7)

(800 to 2400)

(4.52 to 11.00)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

 

10

10

10

2.67

1.61

1.61

1.61

7.5

2200

10.08

48

 

 

 

 

(3.7 to 7.7)

(800 to 2400)

(4.52 to 11.00)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

 

13

10

10

2.17

2.17

1.58

1.58

7.5

2200

10.08

48

 

 

 

 

(3.7 to 7.7)

(800 to 2400)

(4.52 to 11.00)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

 

13

10

10

2.48

2.04

1.49

1.49

7.5

2200

10.08

48

 

 

4 units

 

(3.7 to 7.7)

(800 to 2400)

(4.52 to 11.00)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

 

13

13

10

2.01

2.01

2.01

1.47

7.5

2200

10.08

48

 

 

 

 

 

 

 

 

(3.7 to 7.7)

(800 to 2400)

(4.52 to 11.00)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

 

13

13

10

2.31

1.90

1.90

1.39

7.5

2200

10.08

48

 

 

 

 

(3.7 to 7.7)

(800 to 2400)

(4.52 to 11.00)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

 

13

13

13

1.88

1.88

1.88

1.88

7.5

2200

10.08

48

 

 

 

 

(3.7 to 7.7)

(800 to 2400)

(4.52 to 11.00)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

 

16

10

10

2.34

2.34

1.41

1.41

7.5

2200

10.08

48

 

 

 

 

(3.7 to 7.7)

(800 to 2400)

(4.52 to 11.00)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

22

 

10

10

10

3.18

1.44

1.44

1.44

7.5

2200

10.08

48

 

 

 

 

(3.7 to 7.7)

(800 to 2400)

(4.52 to 11.00)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

– 11 –

2-2-1. Operation Characteristic Curve

 

18

 

 

 

 

 

 

 

 

 

 

 

16

Conditions

 

 

 

 

 

 

 

 

 

 

Indoor

: DB27˚C/WB19˚C

 

 

 

 

 

 

 

 

 

 

 

220V

 

 

 

 

 

 

Outdoor

: DB35˚C

 

 

 

 

 

 

 

14

 

Air flow

: High

 

 

 

 

 

 

 

 

 

 

Pipe length : 5m × 4

 

 

 

 

 

 

 

 

12

 

4 units operating

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(A)

10

 

 

 

 

 

 

 

 

 

 

Current

 

 

 

 

 

 

 

 

 

 

8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

240V

 

 

 

 

 

 

 

 

 

 

 

 

 

6

 

 

 

 

 

 

 

 

 

 

 

4

 

 

 

 

 

 

230V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

0

10

20

30

40

50

60

70

80

90

Inverter output frequency (rps)

2-2-2. Capacity Variation Ratio According to Outdoor Temperature

Capacity ratio (%)

110

Current limited start

100

90

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

80

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

70

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Conditions

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor

 

: DB27˚C/WB19˚C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor

: DB35˚C

 

 

 

 

 

 

 

 

 

 

 

60

 

 

 

Indoor air flow : High

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pipe length

: 5m × 4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4 units operating

 

 

 

 

 

 

 

 

 

 

 

 

50

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

32

 

33

34

35

36

37

38

39

40

41

42

43

44

45

46

 

 

Outdoor temp. (˚C)

Capacity ratio 100% = 7.5kW

– 12 –

3. REFRIGERANT R410A

This air conditioner adopts the new refrigerant HFC (R410A) which does not damage the ozone layer.

The working pressure of the new refrigerant R410A is 1.6 times higher than conventional refrigerant (R22). The refrigerating oil is also changed in accordance with change of refrigerant, so be careful that water, dust, and existing refrigerant or refrigerating oil are not entered in the refrigerant cycle of the air conditioner using the new refrigerant during installation work or servicing.

The next section describes the precautions for air conditioner using the new refrigerant.

Conforming to contents of the next section together with the general cautions included in this manual, perform the correct and safe work.

3-1. Safety During Installation/Servicing

As R410A’s pressure is about 1.6 times higher than that of R22, improper installation/servicing may cause a serious problem. By using tools and materials exclusive for R410A, it is necessary to carry out installation/servicing safely while taking the following precautions into consideration.

1.Never use refrigerant other than R410A in an air conditioner which is designed to operate with R410A.

If other refrigerant than R410A is mixed, pressure in the refrigeration cycle becomes abnormally high, and it may cause personal injury, etc. by a rupture.

2.Confirm the used refrigerant name, and use tools and materials exclusive for the refrigerant R410A.

The refrigerant name R410A is indicated on the visible place of the outdoor unit of the air conditioner using R410A as refrigerant.

To prevent mischarging, the diameter of the service port differs from that of R22.

3.If a refrigeration gas leakage occurs during installation/servicing, be sure to ventilate fully.

If the refrigerant gas comes into contact with fire, a poisonous gas may occur.

4.When installing or removing an air conditioner, do not allow air or moisture to remain in the refrigeration cycle.

Otherwise, pressure in the refrigeration cycle may become abnormally high so that a rupture or personal injury may be caused.

5.After completion of installation work, check to make sure that there is no refrigeration gas leakage.

If the refrigerant gas leaks into the room, coming into contact with fire in the fan-driven heater, space heater, etc., a poisonous gas may occur.

6.When an air conditioning system charged with a large volume of refrigerant is installed in a small room, it is necessary to exercise care so that, even when refrigerant leaks, its concentration does not exceed the marginal level.

If the refrigerant gas leakage occurs and its concentration exceeds the marginal level, an oxygen-deficient accident may result.

7.Be sure to carry out installation or removal according to the installation manual.

Improper installation may cause refrigeration problem, water leakage, electric shock, fire, etc.

8.Unauthorized modifications to the air conditioner may be dangerous. If a breakdown occurs please call a qualified air conditioner technician or electrician.

Improper repair may result in water leakage, electric shock and fire, etc.

3-2. Refrigerant Piping Installation

3-2-1. Piping Materials and Joints Used

For the refrigerant piping installation, copper pipes and joints are mainly used.

Copper pipes and joints suitable for the refrigerant must be chosen and installed.

Furthermore, it is necessary to use clean copper pipes and joints whose interior surfaces are less affected by contaminants.

1.Copper Pipes

It is necessary to use seamless copper pipes which are made of either copper or copper alloy and it is desirable that the amount of residual oil is less than 40 mg/10 m.

Do not use copper pipes having a collapsed, deformed or discolored portion (especially on the interior surface).

Otherwise, the expansion valve or capillary tube may become blocked with contaminants.

As an air conditioner using R410A incurs pressure higher than when using R22, it is necessary to choose adequate materials.

Thicknesses of copper pipes used with R410A are as shown in Table 3-2-1.

Never use copper pipes thinner than 0.8 mm even when it is available on the market.

– 13 –

Table 3-2-1 Thicknesses of annealed copper pipes

 

 

 

Thickness (mm)

 

 

 

 

Nominal diameter

Outer diameter (mm)

R410A

R22

 

 

 

 

1/4

6.35

0.80

0.80

 

 

 

 

3/8

9.52

0.80

0.80

 

 

 

 

1/2

12.70

0.80

0.80

 

 

 

 

5/8

15.88

1.00

1.00

 

 

 

 

2.Joints

For copper pipes, flare joints or socket joints are used. Prior to use, be sure to remove all contaminants.

a)Flare Joints

Flare joints used to connect the copper pipes cannot be used for pipings whose outer diameter exceeds 20 mm. In such a case, socket joints can be used.

Sizes of flare pipe ends, flare joint ends and flare nuts are as shown in Tables 3-2-3 to 3-2-6 below.

b)Socket Joints

Socket joints are such that they are brazed for connections, and used mainly for thick pipings whose diameter is larger than 20 mm.

Thicknesses of socket joints are as shown in Table 3-2-2.

Table 3-2-2

Minimum thicknesses of socket joints

 

 

 

 

Nominal diameter

 

Reference outer diameter of

Minimum joint thickness

 

copper pipe jointed (mm)

(mm)

 

 

 

 

 

 

1/4

 

6.35

0.50

 

 

 

 

3/8

 

9.52

0.60

 

 

 

 

1/2

 

12.70

0.70

 

 

 

 

5/8

 

15.88

0.80

 

 

 

 

3-2-2. Processing of Piping Materials

When performing the refrigerant piping installation, care should be taken to ensure that water or dust does not enter the pipe interior, that no other oil than lubricating oils used in the installed air-water heat pump is used, and that refrigerant does not leak.

When using lubricating oils in the piping processing, use such lubricating oils whose water content has been removed. When stored, be sure to seal the container with an airtight cap or any other cover.

1.Flare processing procedures and precautions

a)Cutting the Pipe

By means of a pipe cutter, slowly cut the pipe so that it is not deformed.

b)Removing Burrs and Chips

If the flared section has chips or burrs, refrigerant leakage may occur. Carefully remove all burrs and clean the cut surface before installation.

c)Insertion of Flare Nut

– 14 –

d) Flare Processing

Make certain that a clamp bar and copper pipe have been cleaned.

By means of the clamp bar, perform the flare processing correctly.

Use either a flare tool for R410A or conventional flare tool.

Flare processing dimensions differ according to the type of flare tool.

When using a conventional flare tool, be sure to secure “Dimension A” by using a gauge for size adjustment.

ØD

A

Fig. 3-2-1 Flare processing dimensions

Table 3-2-3 Dimensions related to flare processing for R410A

 

Outer

 

 

 

A (mm)

 

 

 

 

 

 

 

Nominal

Thickness

 

 

 

diameter

Flare tool for R410A

Conventional flare tool

diameter

(mm)

(mm)

 

 

 

 

 

clutch type

Clutch type

Wing nut type

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1/4

6.35

0.8

 

0 to 0.5

1.0 to 1.5

1.5 to 2.0

 

 

 

 

 

 

 

3/8

9.52

0.8

 

0 to 0.5

1.0 to 1.5

1.5 to 2.0

 

 

 

 

 

 

 

1/2

12.70

0.8

 

0 to 0.5

1.0 to 1.5

2.0 to 2.5

 

 

 

 

 

 

 

5/8

15.88

1.0

 

0 to 0.5

1.0 to 1.5

2.0 to 2.5

 

 

 

 

 

 

 

 

Table 3-2-4 Dimensions related to flare processing for R22

 

 

 

 

 

 

 

 

 

Outer

 

 

 

A (mm)

 

 

 

 

 

 

 

Nominal

Thickness

 

 

 

diameter

Flare tool for R22

Conventional flare tool

diameter

(mm)

(mm)

 

 

 

 

 

clutch type

Clutch type

Wing nut type

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1/4

6.35

0.8

 

0 to 0.5

0.5 to 1.0

1.0 to 1.5

 

 

 

 

 

 

 

3/8

9.52

0.8

 

0 to 0.5

0.5 to 1.0

1.0 to 1.5

 

 

 

 

 

 

 

1/2

12.70

0.8

 

0 to 0.5

0.5 to 1.0

1.5 to 2.0

 

 

 

 

 

 

 

5/8

15.88

1.0

 

0 to 0.5

0.5 to 1.0

1.5 to 2.0

 

 

 

 

 

 

 

Table 3-2-5 Flare and flare nut dimensions for R410A

Nominal

Outer diameter

Thickness

 

Dimension (mm)

 

Flare nut width

 

 

 

 

 

 

diameter

(mm)

(mm)

A

 

B

C

 

D

(mm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1/4

6.35

0.8

9.1

 

9.2

6.5

 

13

17

 

 

 

 

 

 

 

 

 

 

3/8

9.52

0.8

13.2

 

13.5

9.7

 

20

22

 

 

 

 

 

 

 

 

 

 

1/2

12.70

0.8

16.6

 

16.0

12.9

 

23

26

 

 

 

 

 

 

 

 

 

 

5/8

15.88

1.0

19.7

 

19.0

16.0

 

25

29

 

 

 

 

 

 

 

 

 

 

– 15 –

Table 3-2-6 Flare and flare nut dimensions for R22

Nominal

Outer diameter

 

 

 

Thickness

 

 

Dimension (mm)

 

 

 

 

 

Flare nut width

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

diameter

 

(mm)

 

 

 

 

 

 

 

 

(mm)

 

A

 

B

 

C

 

D

(mm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1/4

6.35

 

 

 

 

 

 

0.8

 

9.0

 

9.2

6.5

 

 

13

17

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3/8

9.52

 

 

 

 

 

 

0.8

 

13.0

 

13.5

9.7

 

 

20

22

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1/2

12.70

 

 

 

 

 

 

0.8

 

16.2

 

16.0

12.9

 

 

20

24

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5/8

15.88

 

 

 

 

 

 

1.0

 

19.7

 

19.0

16.0

 

 

23

27

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3/4

19.05

 

 

 

 

 

 

1.0

 

23.3

 

24.0

19.2

 

 

34

36

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

to

46˚

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

45˚

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B

 

A

 

 

 

 

 

 

 

 

 

 

 

C

 

 

D

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

43˚

to

 

 

 

 

 

 

 

45˚

Fig. 3-2-2 Relations between flare nut and flare seal surface

2.Flare Connecting Procedures and Precautions

a)Make sure that the flare and union portions do not have any scar or dust, etc.

b)Correctly align the processed flare surface with the union axis.

c)Tighten the flare with designated torque by means of a torque wrench. The tightening torque for R410A is the same as that for conventional R22. Incidentally, when the torque is weak, the gas leakage may occur.

When it is strong, the flare nut may crack and may be made non-removable.

When choosing the tightening torque, comply with values designated by manufacturers. Table 3-2-7 shows reference values.

Table 3-2-7 Tightening torque of flare for R410A [Reference values]

Nominal

Outer diameter

Tightening torque

Tightening torque of torque

wrenches available on the market

diameter

(mm)

N•m (kgf•cm)

N•m (kgf•cm)

 

 

 

 

 

 

 

1/4

6.35

14 to 18 (140 to 180)

16 (160), 18 (180)

 

 

 

 

3/8

9.52

33 to 42 (330 to 420)

42 (420)

 

 

 

 

1/2

12.70

50 to 62 (500 to 620)

55 (550)

 

 

 

 

5/8

15.88

63 to 77 (630 to 770)

65 (650)

 

 

 

 

– 16 –

3-3. Tools

3-3-1. Required Tools

The service port diameter of packed valve of the outdoor unit in the air-water heat pump using R410A is changed to prevent mixing of other refrigerant.

To reinforce the pressure-resisting strength, flare processing dimensions and opposite side dimension of flare nut (For Ø12.7 copper pipe) of the refrigerant piping are lengthened.

The used refrigerating oil is changed, and mixing of oil may cause a trouble such as generation of sludge, clogging of capillary, etc. Accordingly, the tools to be used are classified into the following three types.

1.Tools exclusive for R410A (Those which cannot be used for conventional refrigerant (R22))

2.Tools exclusive for R410A, but can be also used for conventional refrigerant (R22)

3.Tools commonly used for R410A and for conventional refrigerant (R22)

The table below shows the tools exclusive for R410A and their interchangeability.

Tools exclusive for R410A (The following tools for R410A are required.)

Tools whose specifications are changed for R410A and their interchangeability

 

 

 

R410A

Conventional air-water

 

 

 

air-water heat pump installation

heat pump installation

No.

Used tool

Usage

 

 

 

Existence of

Whether conven-

Whether new equipment

 

 

 

 

 

 

new equipment

tional equipment

can be used with

 

 

 

for R410A

can be used

conventional refrigerant

 

 

 

 

 

 

1

Flare tool

Pipe flaring

Yes

*(Note 1)

¡

 

 

 

 

 

 

 

Copper pipe gauge for

Flaring by

 

*(Note 1)

*(Note 1)

2

adjusting projection

Yes

conventional flare tool

 

margin

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

Torque wrench

Connection of flare nut

Yes

×

×

(For Ø12.7)

 

 

 

 

 

 

4

Gauge manifold

Evacuating, refrigerant

Yes

×

×

 

 

5

Charge hose

charge, run check, etc.

 

 

 

 

 

 

 

 

 

 

6

Vacuum pump adapter

Vacuum evacuating

Yes

×

¡

7

Electronic balance for

Refrigerant charge

Yes

×

¡

refrigerant charging

 

 

 

 

 

 

8

Refrigerant cylinder

Refrigerant charge

Yes

×

×

9

Leakage detector

Gas leakage check

Yes

×

¡

10

Charging cylinder

Refrigerant charge

(Note 2)

×

×

(Note 1) When flaring is carried out for R410A using the conventional flare tools, adjustment of projection margin is necessary. For this adjustment, a copper pipe gauge, etc. are necessary.

(Note 2) Charging cylinder for R410A is being currently developed.

General tools (Conventional tools can be used.)

In addition to the above exclusive tools, the following equipments which serve also for R22 are necessary as the general tools.

1.

Vacuum pump

4. Reamer

9.

Hole core drill (Ø65)

 

Use vacuum pump by attaching

5.

Pipe bender

10.

Hexagon wrench

 

vacuum pump adapter.

 

6.

Level vial

 

(Opposite side 4mm)

2.

Torque wrench (For Ø6.35, Ø9.52)

 

7.

Screwdriver (+, –)

11.

Tape measure

3.

Pipe cutter

 

 

8.

Spanner or Monkey wrench

12.

Metal saw

 

 

Also prepare the following equipments for other installation method and run check.

1.

Clamp meter

3. Insulation resistance tester

 

 

2.

Thermometer

4. Electroscope

 

 

– 17 –

3-4. Recharging of Refrigerant

When it is necessary to recharge refrigerant, charge the specified amount of new refrigerant according to the following steps.

Recover the refrigerant, and check no refrigerant remains in the equipment.

Connect the charge hose to packed valve service port at the outdoor unit’s gas side.

Connect the charge hose to the vacuum pump adapter.

Open fully both packed valves at liquid and gas sides.

Place the handle of the gauge manifold Low in the fully opened position, and turn on the vacuum pump’s power switch. Then, evacuating the refrigerant in the cycle.

When the compound gauge’s pointer has indicated –0.1 Mpa (–76 cmHg), place the handle Low in the fully closed position, and turn off the vacuum pump’s power switch.

Keep the status as it is for 1 to 2 minutes, and ensure that the compound gauge’s pointer does not return.

Set the refrigerant cylinder to the electronic balance, connect the connecting hose to the cylinder and the connecting port of the electronic balance, and charge liquid refrigerant.

(For refrigerant charging, see the figure below.)

1.Never charge refrigerant exceeding the specified amount.

2.If the specified amount of refrigerant cannot be charged, charge refrigerant bit by bit in COOL mode.

3.Do not carry out additional charging.

When additional charging is carried out if refrigerant leaks, the refrigerant composition changes in the refrigeration cycle, that is characteristics of the air conditioner changes, refrigerant exceeding the specified amount is charged, and working pressure in the refrigeration cycle becomes abnormally high pressure, and may cause a rupture or personal injury.

(Indoor unit)

(Outdoor unit)

 

 

Opened

Refrigerant cylinder

 

(with siphon)

 

Check valve

Opened

 

Opened

 

Open/close

Closed

valve for charging

 

 

Service port

Electronic balance for refrigerant charging

 

Fig. 3-4-1 Configuration of refrigerant charging

– 18 –

1.Be sure to make setting so that liquid can be charged.

2.When using a cylinder equipped with a siphon, liquid can be charged without turning it upside down.

It is necessary for charging refrigerant under condition of liquid because R410A is mixed type of refrigerant.

Accordingly, when charging refrigerant from the refrigerant cylinder to the equipment, charge it turning the cylinder upside down if cylinder is not equipped with siphon.

[ Cylinder with siphon ]

[ Cylinder without siphon ]

Gauge manifold

Gauge manifold

OUTDOOR unit

OUTDOOR unit

Refrigerant

cylinder

Electronic

balance

R410A refrigerant is HFC mixed refrigerant.

Therefore, if it is charged with gas, the composition of the charged refrigerant changes and the characteristics of the equipment varies.

cylinder Refrigerant

Electronic

balance

Siphon

Fig. 3-4-2

3-5. Brazing of Pipes

3-5-1. Materials for Brazing

1.Silver brazing filler

Silver brazing filler is an alloy mainly composed of silver and copper. It is used to join iron, copper or copper alloy, and is relatively expensive though it excels in solderability.

2.Phosphor bronze brazing filler

Phosphor bronze brazing filler is generally used to join copper or copper alloy.

3.Low temperature brazing filler

Low temperature brazing filler is generally called solder, and is an alloy of tin and lead. Since it is weak in adhesive strength, do not use it for refrigerant pipes.

1.Phosphor bronze brazing filler tends to react with sulfur and produce a fragile compound water solution, which may cause a gas leakage. Therefore, use any other type of brazing filler at a hot spring resort, etc., and coat the surface with a paint.

2.When performing brazing again at time of servicing, use the same type of brazing filler.

3-5-2. Flux

1.Reason why flux is necessary

By removing the oxide film and any foreign matter on the metal surface, it assists the flow of brazing filler.

In the brazing process, it prevents the metal surface from being oxidized.

By reducing the brazing filler’s surface tension, the brazing filler adheres better to the treated metal.

– 19 –

2.Characteristics required for flux

Activated temperature of flux coincides with the brazing temperature.

Due to a wide effective temperature range, flux is hard to carbonize.

It is easy to remove slag after brazing.

The corrosive action to the treated metal and brazing filler is minimum.

It excels in coating performance and is harmless to the human body.

As the flux works in a complicated manner as described above, it is necessary to select an adequate type of flux according to the type and shape of treated metal, type of brazing filler and brazing method, etc.

3.Types of flux

Noncorrosive flux

Generally, it is a compound of borax and boric acid. It is effective in case where the brazing temperature is higher than 800°C.

Activated flux

Most of fluxes generally used for silver brazing are this type.

It features an increased oxide film removing capability due to the addition of compounds such as potassium fluoride, potassium chloride and sodium fluoride to the borax-boric acid compound.

4.Piping materials for brazing and used brazing filler/flux

Piping material

Used brazing filler

Used flux

 

 

 

Copper - Copper

Phosphor copper

Do not use

 

 

 

Copper - Iron

Silver

Paste flux

 

 

 

Iron - Iron

Silver

Vapor flux

 

 

 

1.Do not enter flux into the refrigeration cycle.

2.When chlorine contained in the flux remains within the pipe, the lubricating oil deteriorates.Therefore, use a flux which does not contain chlorine.

3.When adding water to the flux, use water which does not contain chlorine (e.g. distilled water or ion-exchange water).

4.Remove the flux after brazing.

3-5-3. Brazing

As brazing work requires sophisticated techniques, experiences based upon a theoretical knowledge, it must be performed by a person qualified.

In order to prevent the oxide film from occurring in the pipe interior during brazing, it is effective to proceed with brazing while letting dry Nitrogen gas (N2) flow.

Never use gas other than Nitrogen gas.

1.Brazing method to prevent oxidation

1)Attach a reducing valve and a flow-meter to the Nitrogen gas cylinder.

2)Use a copper pipe to direct the piping material, and attach a flow-meter to the cylinder.

3)Apply a seal onto the clearance between the piping material and inserted copper pipe for Nitrogen in order to prevent backflow of the Nitrogen gas.

4)When the Nitrogen gas is flowing, be sure to keep the piping end open.

5)Adjust the flow rate of Nitrogen gas so that it is lower than 0.05 m3/Hr or 0.02 MPa (0.2kgf/cm2) by means of the reducing valve.

6)After performing the steps above, keep the Nitrogen gas flowing until the pipe cools down to a certain extent (temperature at which pipes are touchable with hands).

7)Remove the flux completely after brazing.

M Flow meter

Stop valve

Nitrogen gas cylinder

From Nitrogen cylinder

Pipe Nitrogen gas

Rubber plug

Fig. 3-5-1 Prevention of oxidation during brazing

– 20 –

4. CONSTRUCTION VIEWS

4-1. Indoor Unit

RAS-M10SKCV, RAS-M13SKCV, RAS-M16SKCV

790

Front panel

Air filter

Air inlet

205

 

 

275

 

63

 

 

63

7

48

48

7

 

 

 

 

Heat exchanger

 

Knock out system

Knock out system

49

62 69

116

480

193

Installation plate hanger

Installation plate hanger

Drain hose (0.50m)

Connecting pipe (0.35m)

 

(For 10,13 series; Flare Ø9.52mm)

Connecting pipe (0.40m)

(For 16 series; Flare Ø12.7mm)

(Flare Ø6.35mm)

 

157

56

19

Wireless remote controller 125

 

 

 

 

 

 

 

63

26

 

84.5

 

621

 

 

84.5

Remote controller holder

 

 

 

235

235

 

 

 

 

 

 

 

215

215

 

 

 

 

 

 

 

Hanger

Minimum

65 more

 

 

 

 

 

 

distance

 

 

 

 

 

 

 

to ceiling

or

 

 

 

 

Minimum

 

 

 

 

 

45

 

 

 

 

 

 

Minimum

 

 

 

distance

 

 

 

 

distance

 

 

275

to wall

 

 

 

 

to wall

190

 

170 or more

 

 

 

 

170 or more

 

 

40

Hanger

 

 

Hanger

 

40

 

 

 

 

 

 

 

 

 

84.5

150

160.5

160.5

150

84.5

 

 

 

 

Center line

 

Installation plate outline

 

 

 

 

– 21 –

 

 

 

 

RAS-M22SKCV

1050

Front panel

Air filter

 

Air inlet

 

 

 

 

 

 

 

 

320

73.5

 

7

50

 

 

Heat exchanger

Knock out system

228

 

73.5

50

7

 

Knock out system

50

72 78

Installation plate hanger

204

132 568 200 150 56 24

Wireless remote controller

 

 

 

 

 

 

163

 

 

 

 

 

82

26

Installation plate hanger

 

 

 

Remote controller holder

 

 

 

 

 

Connecting plate (0.39m)

Drain hose

Connecting pipe (0.49m)

 

(Flare Ø12.70mm)

 

(0.5mm)

(Flare Ø6.35mm)

 

132

 

 

786

 

132

 

 

 

235

235

 

 

 

 

 

215

215

 

 

 

85

 

Hanger

 

 

23

 

 

 

 

 

 

320

 

 

 

 

 

 

40

 

 

 

 

40

 

 

 

Hanger

Hanger

 

 

 

47

215.5

262.5

262.5

153.5

109

 

 

Center line

Instrallation plate outline

 

 

 

– 22 –

 

 

 

RAS-M22NKCV1

Back body

998

 

Front panel

Air inlet

 

 

Grille inlet

 

 

220

 

 

 

 

 

298

 

 

75

 

 

75

7

 

50

8

51

 

Air outlet

 

Knock out system

Connection pipe (0.39 m) (Flare Ø12.7)

55 or more

Minimum distance to ceiling

Outline of indoor unit

 

298

 

Knock out system

50

75 56

160

 

 

Drain hose (0.54 m)

 

 

 

 

Connection pipe (0.49 m)

57

18

 

 

(Flare Ø6.35)

Wireless remote controller

 

998

 

 

 

 

 

 

 

763.5

 

(For stud bolt Ø6)

 

 

450

 

 

 

 

 

 

 

20

 

20

(For stud bolt Ø8 - Ø10)

 

 

 

 

 

48

10

 

29

 

 

 

 

 

41

48

 

 

 

 

55 55

 

 

 

 

 

55

 

 

Ø65

100

Installation

100

plate outline

 

 

Ø65

40

– 23 –

– 24 –

2-dia.12 × 17 U-shape hole (for dia.8-10 anchor bolt)

17.5

 

365

Anchor bolt long hole pitch

17.5

 

320 28

795

410

25

400

Knock out

2-dia.3.5 hole

Knock out

150

600

150

50

A log part

 

 

B log part

50

2-dia.12 × 17 long hole

(for dia.8-10 anchor bolt)

 

 

900

Fan guard

136

dia.510

 

Hanger

Liquid valve

38

 

514

53 53 53 53 53

 

53 53

 

90

Screw

 

Mounting dimensions of anchor bolt

When installing the outdoor unit,

 

 

 

 

2-dia.12 × 17 U-shape hole

600

leave open in at least two of

 

Intake

directions (A), (B), (C) and (D)

(for dia.8-10 anchor bolt)

 

shown in the figure below.

100 or more

 

D

 

 

Intake

 

 

600 or more

 

 

 

A

365

 

 

 

100 or more

 

Outside line

(Minimum distance from wall)

 

C

 

 

 

of product

 

 

 

 

600 or more

B

 

 

 

 

Outlet

2-dia.12 × 17 long hole

 

 

 

(for dia.8-10 anchor bolt)

164

 

 

91

Outdoor air temperature sensor

Fan guard

 

 

Gas valve

Hanger

Service port

 

Connecting pipe port :

Connecting pipe dia.6.35

D unit

Connecting pipe dia.9.52

Connecting pipe dia.6.35

C unit

Connecting pipe dia.9.52

Connecting pipe dia.6.35

B unit

Connecting pipe dia.9.52

Connecting pipe dia.6.35

A unit

Connecting pipe dia.12.7

98

 

 

Knock out

Detailed

A

log part

 

 

 

 

 

 

 

50

 

 

 

 

 

20

12

 

R14

 

 

Tightly seal the knock-out holes and

 

 

 

 

 

 

 

 

 

 

 

screw/thread areas using a silicon adhesive, etc.

365

 

 

 

 

 

to ensure that there is no water drippage.

R6

 

Outside line

 

 

Under some conditions, comdensation may form

 

600 of product

 

 

 

 

262

431

on the base plate and arain, use the drain pan.

 

 

 

 

 

 

 

 

 

Detailed

B

log part

 

600

 

Outside line

365

 

R6

of product

 

 

 

 

17

 

 

 

R20

12

 

 

 

 

 

 

50

 

 

units : mm

Drain long hole

Drain hole

 

dia.20 × 88 long hole

dia.25

5-dia.3.5 hole

RAS

.2-4

4M26SACV-

Unit Outdoor

5. WIRING DIAGRAM

5-1. Indoor Unit

RAS-M10SKCV, RAS-M13SKCV

Outdoor terminal block 1 2 3

Indoor terminal block

1 2 3

Heat exchanger

 

BLK

WHI RED

Power supply

GRN & YEL

(From Outdoor unit)

 

 

1 , 220 240V ~,

50Hz

 

 

1 , 220V ~,

60Hz

 

 

Sheet metal

 

 

 

BLK

 

 

 

CN02

3

1

 

 

CN01 CN51

 

 

 

 

 

 

 

 

 

 

 

 

1

1

 

 

 

 

 

 

 

 

 

 

 

3

3

 

 

 

 

 

 

 

 

 

 

 

5

5

 

 

 

 

 

 

 

Fuse F01

3

 

 

CN31

 

 

 

 

 

 

 

T3.15A

 

 

(WHI)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

1

 

 

 

 

 

1

1

CN63

 

 

 

2

2

 

 

 

 

 

2

2

(YEL)

 

 

 

3

3

Heat exchanger sensor

 

 

 

 

 

CN33

 

 

 

 

 

(WHI)

 

 

(TCJ)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

1

CN62

 

 

 

1

1

 

 

 

 

 

2

2

(BLU)

 

 

 

2

2

Heat exchanger sensor

 

 

Varistor

Line filter

 

3

3

 

 

(TC)

 

 

 

 

 

 

 

4

4

 

 

 

 

 

1

1

CN61

 

 

 

 

 

 

 

 

 

 

 

5

5

 

 

 

 

 

2

2

(WHI)

 

 

 

CN32

 

Thermo sensor

 

 

 

 

 

 

(WHI)

 

 

(TA)

 

 

 

 

 

 

 

CN22

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BLU

 

 

 

DC5V

 

 

(WHI)

 

 

1

1

1

1

 

 

 

 

1

 

 

 

BLU

 

 

 

 

 

 

 

2

2

2

2

 

DC12V

supplyPower circuit

2

 

unitWirelessassembly

5044-MCC

BLUBLU

 

 

12 12

12 12

 

 

 

 

 

 

 

3

3

BLU

3

3

 

 

 

 

3

 

 

 

4

4

BLU

4

4

 

 

 

 

4

 

 

 

5

5

BLU

5

5

 

 

 

 

 

 

 

 

6

6

BLU

6

6

 

 

 

 

 

 

 

 

7

7

BLU

7

7

 

 

 

 

 

 

 

 

BLU

 

 

 

 

 

 

 

 

8

8

8

8

 

 

 

 

 

 

 

 

BLU

 

 

 

 

 

 

 

 

9

9

9

9

 

 

 

 

 

 

 

 

BLU

 

 

 

 

 

 

 

 

10 10

10 10

 

 

 

 

 

 

 

 

11 11

BLU

11 11

 

 

 

 

 

 

 

 

13 13

BLU

13 13

 

 

 

 

 

 

 

 

14 14

14 14

Main P.C. board

 

 

 

 

 

15 15

WHI

15 15

 

 

 

 

 

 

MCC-5046

 

 

 

 

CN10

CN21

(WHI)

(WHI)

WHI

1

1

YEL

2

2

YEL

3

3

YEL

4

4

YEL

5

5

6

6

 

5

5

 

4

4

AC motor

3

3

 

2

2

 

1

1

 

 

 

Fan motor

Louver motor

Color

Identification

YEL : YELLOW BLK : BLACK WHI : WHITE RED : RED BLU : BLUE

GRN & YEL : GRAY & YELLOW

– 25 –

RAS-M16SKCV, RAS-M22SKCV

Outdoor terminal block

1

2 3

 

Indoor terminal block

1

2 3

Heat exchanger

 

 

BLK WHI

RED

Power supply

 

GRN & YEL

(From Outdoor unit)

 

 

 

1Ø, 220 – 240V ~, 50Hz

 

 

 

1Ø, 220V ~,

60Hz

 

 

 

Sheet metal

 

 

 

 

BLK

 

 

 

 

CN02

3

1

 

 

 

CN01 CN51

 

1 1

 

 

Fuse F01

 

3

3

 

 

DC motor

 

 

 

4

4

 

 

 

 

T3.15A

 

 

 

 

 

 

 

5

5

 

 

 

 

 

AC250V

 

 

 

 

 

 

 

6

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CN31

 

 

Fan motor

 

 

 

 

(WHI)

 

 

 

1

1

CN63

Varistor

 

 

 

 

 

2

2

(YEL)

1

1

WHI

1

1

Heat exchanger sensor

 

 

 

 

 

 

2

2

YEL

2

2

(TCJ)

 

 

 

1

1

CN62

 

3 3

YEL

3

3

2

2

(BLU)

 

4 4

YEL

4

4

Heat exchanger sensor

 

 

Line filter

5 5

YEL

5

5

 

 

CN32

 

 

Louver motor

(TC)

 

 

 

 

 

1

1

CN61

 

(WHI)

 

 

 

 

 

 

 

 

 

2

2

(WHI)

 

 

 

 

 

 

Thermo sensor

 

 

 

 

 

 

 

(TA)

 

 

 

 

 

CN22

 

 

 

 

 

 

 

DC5V

 

(WHI)

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

1

1

BLU

1

1

DC12V

supplyPower circuit

2

 

unitWirelessassembly 5044-MCC

WHI

RED

: RED

11 11

11 11

 

 

2

2

BLU

2

2

 

 

3

 

 

3

3

BLU

3

3

 

 

4

 

 

4

4

BLU

4

4

 

 

 

 

 

5

5

BLU

5

5

 

 

 

 

 

6

6

BLU

6

6

~

 

Color

 

 

 

BLU

 

 

 

Identification

 

7

7

7

7

– +

 

 

BLU

 

 

 

 

8

8

8

8

~

 

YEL

: YELLOW

 

BLU

 

 

 

9

9

9

9

 

 

BLK

: BLACK

 

BLU

 

 

 

10 10

10 10

 

 

WHI

: WHITE

 

 

 

 

 

 

 

CN10

 

CN21

Main P.C. board

 

BLU

: BLUE

 

 

 

GRN & YEL :

 

 

MCC-5045

 

 

(WHI)

 

(WHI)

 

GRAY & YELLOW

– 26 –

RAS-M22NKCV1

Louver motor

WHI

PNK

YEL

ORN

RED

BRW

 

6

5

4

3

2

1

 

6

5

4

3

2

1

CN07

 

 

 

 

 

5

 

 

 

 

3

2

 

 

F01

1

BLK

CN24

T3.15A, 250V

 

2

WHI

CN23

 

3

RED

CN21

 

Indoor

 

 

terminal block

 

 

GRN & YEL

Outdoor unit Indoor unit

1

2

3

CN11

1

2

3

 

Color

 

 

BRW

 

 

GRY

Identification

 

 

 

 

YEL

 

 

 

BRW : BROWN

RED : RED

WHI : WHITE

YEL : YELLOW

BLU : BLUE

BLK : BLACK

GRY : GRAY

ORN : ORANGE

GRN : GREEN

PNK : PINK

GRN & YEL :

GRAY & YELLOW

Infrared rays receive and indication parts MCC-819

1

2

3

4

5

6

7

8

9 10

 

1

2

3

4

5

6

7

8

9 10

CN25

BLU BLU BLU BLU BLU BLU BLU BLU BLU WHI

HA

JEM-A

1

2

3

4

5

6

7

8

9 10

 

 

 

 

 

 

1

2

3

4

5

6

7

8

9 10

CN14

1

2

3

4

CN08

 

 

 

 

 

 

 

4

 

 

 

 

 

 

 

 

 

 

 

 

Power supply

 

+12V DC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

circuit

 

+5V DC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fan motor

drive circuit Main P.C. board

(WP-004)

6

 

5

 

3

 

1

CN10

1

2

CN03

1

2

CN01

 

5

 

3

 

1

 

1

2

(WHI)

1

2

(BLU)

BLK

 

 

 

 

 

 

BLK

BLK

 

BLK

BLK

 

 

 

 

 

RED

WHI

 

 

 

 

 

 

 

1

2

3

4

5

6

 

Thermo.

Heat exchanger

1

2

3

4

5

6

 

sensor

 

sensor

 

 

 

 

 

 

 

 

(TA)

 

(TC)

 

145˚C

 

 

 

 

 

AC Fan motor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Simple check points for diagnosing faults

 

 

Check item

Diagnosis result

1

Check to see if the OPERATION indicator goes on and

Operation indicator

off when the main switch or breaker is turned on.

 

 

 

2

Check the power supply voltage between and .

Terminal block

(Refer to the name plate)

Check the voltage between and ƒ. (AC15 – 60V)

 

 

 

3

Check to see if the fuse blows out.

Fuse, 3.15A

 

 

 

4

Check the voltage at the No. 8 pin on CN14 connector

DC5V

of the infrared receiver.

 

 

 

5

Check the voltage at the brown lead of the louver motor.

DC12V

(Check the power supply circuit of the rated voltage.)

 

 

 

6

Check the voltage at the No. 1 pin of CN10 connector

AC220 – 240V

and CN24. (Check the F01)

 

 

 

For detailed diagnostic procedure, refer to the service data.

– 27 –

Toshiba RAS-M10SKCV, RAS-M22NKCV1, RAS-M22SKCV, RAS-4M26SACV, RAS-M13SKCV SERVICE MANUAL

5-2. Outdoor Unit

RAS-4M26SACV

 

 

Thermostat for

 

 

compressor

 

 

ORN

2 2

 

P501

ORN

1 1

 

P500

Fan motor

5

5

 

 

 

FM

4

4

CN802

3

3

CN301

 

 

2

2

 

 

1

1

 

3

3

 

2

2

CN300

1

1

CN608

 

 

 

6

6

 

 

PMV

5

5

 

CN607

4 4

CN704

 

D

3

3

BLU

 

 

 

 

2

2

 

 

 

1

1

 

CN606

 

6

6

 

 

PMV

5

5

 

CN605

4 4

CN703

 

C

3

3

RED

 

2

2

 

CN604

 

 

 

1

1

 

 

 

 

 

6

6

 

CN602

 

5

5

CN702

PMV

 

4 4

WHI

 

B

3

3

Fan

CN601

2

2

circuit

 

 

 

 

1

1

 

 

 

6

6

 

CN302

 

 

 

PMV

5

5

F300, Fuse

4 4

T3.15A, 250V~

A

3 3

CN701

CN800

 

2

2

YEL

 

 

1

1

 

 

 

 

Photo coupler

SUB P.C. Board

CN303

 

(MCC-818)

 

F500, Fuse

 

T6.3A, 250V~

CN501

 

 

 

 

P07 P03

 

P04

 

 

 

P05

 

 

 

P06

WHI

 

 

 

 

RED

 

 

 

 

ORN

 

PNK

 

 

 

YEL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 2 3

1 2 3

1 2 3

1 2 3

To

To

To

To

Indoor

Indoor

Indoor

Indoor

unit A

unit B

unit C

unit D

 

 

 

 

 

 

Color Identification

 

 

 

 

 

BLK : BLACK

 

PNK : PINK

 

ORN : ORANGE

 

 

 

BLU : BLUE

 

GRN : GREEN

YEL : YELLOW

 

 

 

RED : RED

 

WHI : WHITE

PUR : PURPLE

 

 

 

GRY : GRAY

 

BRW : BROWN

 

 

 

 

 

 

RED

 

 

P.C. Board

 

 

 

2

2

2 2

 

 

 

+

 

1

1

1 1

 

 

(MCC-1438)

 

 

Compressor

RED

 

CN20

T03 CT

 

BU

module

 

 

 

 

 

 

EU

 

 

 

 

WHI

 

CN21

T04 CT

 

BV

 

 

 

CM

 

 

EV

 

 

 

 

 

 

 

 

 

 

 

 

BLK

 

CN22

 

 

 

BW

IGBT

 

 

 

 

 

 

 

 

 

 

EW

2

2

 

 

TGd

 

Power supply circuit

 

BX

 

 

 

 

BY

 

 

 

 

 

1

1

BLU

 

 

(For P.C. Board)

 

BZ

 

3

3

 

 

 

 

F04

 

 

 

Q200

 

 

TGc

 

Fuse

 

 

 

 

 

 

 

GRN

 

T3.15A

 

 

 

 

 

1

1

 

 

 

 

250V~

 

P20

 

YEL

 

3

3

 

 

 

 

 

 

P19

 

 

 

 

 

TGb

 

 

 

P18

 

 

 

 

 

BRW

 

 

 

 

BLU

 

1

1

 

 

 

 

 

 

P17

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

3

 

 

 

 

 

C13

 

G IGBT

 

 

YEL

TGa

 

 

C12

 

1

1

 

 

 

 

 

C11

 

C (PFC)

 

 

 

 

 

 

E

 

2

2

2

2

BLU

 

 

C10

 

 

Q404

 

 

 

 

 

 

 

1

1

1

1

 

 

 

 

 

 

 

 

 

 

 

 

+ Diode

3

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

~ block

 

 

 

 

 

 

 

 

 

 

 

TD

 

 

 

 

F02

~ (PFC)

1

1

 

 

 

 

Power

 

DB02

 

 

 

 

 

Fuse

2

2

TO

 

 

relay

 

25A

 

 

 

1

1

 

 

RY02

 

250V~

P29

+

 

 

 

 

 

 

 

 

 

3

3

 

 

3 3

 

 

 

P21

~ Diode

 

BLU

 

 

 

P24

~ block

1

1

 

YEL

1

1

RB05

 

 

P28

 

 

 

 

 

 

 

 

BLK

CN04

 

 

 

 

 

5

5

 

5

5

 

 

P13

 

 

 

 

WHI

 

 

 

GRY

 

4

4

 

4

4

 

 

P12

 

 

 

BLU

 

 

 

 

 

3

3

 

3

3

CN06

 

 

 

Reactor

 

RED

 

 

 

2

2

 

2

2

 

 

P09

 

 

 

 

PNK

 

 

2 2

 

1

1

 

1

1

 

 

P08

 

 

 

 

 

1

1

 

2

2

 

PUR

2

2

 

 

 

 

 

CN05

T02 CT

 

 

 

 

ORN

 

 

 

1

1

 

1

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5 5

 

 

 

Surge

 

 

 

 

WHI

 

 

 

Varistor

absorber

 

 

 

 

 

 

 

 

 

 

3

3

 

3

3

 

 

 

 

 

 

 

 

 

F01, Fuse

 

 

 

 

 

 

 

 

 

 

 

 

 

1

1

 

RED

1 1

CN13

T25A,

 

 

 

 

250V~

 

 

 

 

 

Fuse,

 

 

CN01

 

CN02

 

CN03

 

 

T6.3A, 250V~

 

 

 

 

 

 

 

BLK

BLK WHI

BLK

WHI

 

 

Terminal block

L N

 

Power supply 220–240V ~50Hz 220–220V ~60Hz

– 28 –

6. SPECIFICATIONS OF ELECTRICAL PARTS

6-1. Indoor Unit

RAS-M10SKCV, RAS-M13SKCV, RAS-M16SKCV, RAS-M22SKCV

No.

 

Parts name

Type

 

Specifications

1

Fan motor

RAS-M10SKCV, M13SKCV

AFS-220-20-4AR

AC240V, 20W

(for indoor)

RAS-M16SKCV, M22SKCV

ICF-340-30-2B

DC340V, 30W

 

2

Room temp. sensor (TA-sensor)

( – )

10kΩ

at 25°C

3

Heat exchanger temp. sensor (TC-sensor)

( – )

10kΩ

at 25°C

4

Louver motor

 

MP24Z3T

Output (Rated) 1W, 16 poles, DC12V

 

 

 

 

 

 

RAS-M22NKCV1

No.

Parts name

Type

Specifications

1

Fan motor (for indoor)

AFS-220-31-4A

AC220–240V

2

Thermo. sensor (TA-sensor)

( – )

10kΩ at 25°C

3

DC-DC transformer (T01)

TT-10

198-264V, 6VA

4

Microcomputer

µPD780024AGK

 

5

Heat exchanger temp. sensor (TC-sensor)

( – )

10kΩ at 25°C

6

Line filter (L01)

SS11V-06270

27µH, AC 0.64A

7

Diode (DB01)

KBP06M

1.5A, 420V

8

Capacitor (C50)

LXV35VB2200MJ20

2200µF, 35V

9

Fuse (F01)

BET 3.15A, AC250V

T3.15A, 250V

10

Regulator IC (IC08)

NJM7812

DC12V, 1.5A max.

11

Regulator IC (IC11)

NJM7805

DC5V, 1.5A max

12

Resistor (R21, R109)

15G561K

560V

13

Louver motor

MP35EA12

DC12V

 

 

 

 

6-2. Outdoor Unit

RAS-4M26SACV

No.

Parts name

 

Model name

 

Rating

 

SC coil (Noise filter) (L01)

 

ADR2520R15TB

AC 250V, 20A, 0.15mH

1

SC coil (Noise filter) (L02)

 

SC-20-S03J

AC 250V, 20A, 0.3mH

 

 

SC coil (Noise filter) (L03)

 

ADR25H200RBTB

AC 250V, 20A, 0.88mH

 

 

 

 

 

Primary side DC 240 – 390V

2

DC-DC transformer

 

SWT-75

Secondary side :

7V × 1, 13V × 1

 

 

 

 

 

 

 

16V × 3

3

Outside fan motor

 

ICF-140-63-2R

DC 140V, 63W

 

5

Relay (Power relay)

 

G4A-1A-PE

Coil

: DC 12V

 

 

Contact : 20A, AC250V

 

 

 

 

 

6

Discharge temp. sensor (TD-sensor)

(Inverter attached)

64kΩ

(20°C)

 

7

Outside air temp. sensor (TO-sensor)

(Inverter attached)

10kΩ

(25°C)

 

8

Temp. sensor at A room gas side (TGA-sensor)

(Inverter attached)

10kΩ

(25°C)

 

9

Temp. sensor at B room gas side (TGB-sensor)

(Inverter attached)

10kΩ

(25°C)

 

10

Temp. sensor at C room gas side (TGC-sensor)

(Inverter attached)

10kΩ

(25°C)

 

11

Temp. Sensor at D room gas side (TGD-sensor)

(Inverter attached)

10kΩ

(25°C)

 

12

Terminal block (6P)

 

AC 250V, 20A

 

13

Terminal block (3P)

 

AC 250V, 20A

 

 

 

 

For protection of switching power source (F04)

AC 250V, 3.15A

 

 

 

 

For protection of power factor converter circuit breakage

AC 250V, 25A

 

14

Fuse

 

For protection of inverter input overcurrent

AC 250V, 25A

 

 

 

 

For protection of switching power source (F300)

AC 250V, 3.15A

 

 

 

 

For protection of power source

AC 250V, 6.3A

 

15

Electrolytic capacitor

 

LLQ2G761KHUATF

DC 400V, 760µF

 

16

Transistor module

 

6MBI40SS-060-51A

600V, 40A

 

17

Compressor

 

DA220A2F-20L

3 phases, 4 poles, 2000W

18

Compressor thermo.

 

US622KXTMQO

OFF : 125 ± 4°C, ON : 90 ± 5°C

19

Diode block (Rectifire)

 

S30VT80

AC 800V, 30A

 

20

Reactor (Main)

 

CH-47-Z-T

L = 8mH, 16A

 

 

 

 

 

 

 

 

 

– 29 –

7. REFRIGERANT CYCLE DIAGRAM

7-1. Indoor Unit and Ourdoor Unit

RAS-M10SKCV, RAS-M13SKCV, RAS-M16SKCV, RAS-M22SKCV, RAS-M22NKCV1 / RAS-4M26SACV

Temp. measurement T1

TCa

To

To

To

D room

C room

B room

Connecting pipe Thickness : 0.8mm Ø12.7 :

RAS-M22NKCV1, RAS-M16SKCV RAS-M22SKCV

Ø9.52 : RAS-M10SKCV, RAS-M13SKCV

To

To

To

Indoor unit A D room

C room

B room

Evaporator

Cross flow fan

TA

Connecting pipe Thickness : 0.8mm Ø6.35

Sectional shape of heat insulator

Allowable height difference : 15m

Allowable pipe length

Per 1 unit Max. : 25m Min. : 2m

Total

Max. : 70m 1 or 50m 2

(Ø9.52)

(Ø9.52)

(Ø9.52)

(Ø12.7)

(Ø6.35)

(Ø6.35)

(Ø6.35)

(Ø6.35)

 

 

 

 

 

Strainer

 

 

 

 

TGd

TGc

 

TGb

TGa

 

 

 

 

Pulse motor

 

 

 

 

 

valve at liquid side

 

 

 

 

 

 

 

 

 

(UKV-18D)

P Pressure

 

Packed valve (Gas side)

 

Packed valve (Liquid side)

measurement

 

(Ø12.7)

 

 

(Ø9.52)

 

 

Gauge attaching port

 

 

 

 

Vacuum pump

 

 

 

 

 

 

 

 

 

connecting port

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Muffler

 

 

 

 

Accumulating tank

 

 

 

 

Ø25 x 160L

 

 

 

 

 

 

 

 

 

 

 

 

 

1500cc

 

 

 

 

TD

 

 

 

 

 

 

 

 

 

Compressor

 

 

 

 

 

 

 

 

 

DA220A2F-20L

 

 

 

 

Temp. measurement

T2

TO

 

 

 

 

 

 

 

 

 

 

 

 

 

Propeller fan

Refrigerant amount : 2.2kg (R410A)

 

 

 

 

 

 

 

 

 

 

Outdoor unit

NOTE :

Gas leak check position

Refrigerant flow

NOTE :

1 In case of without the RAS-M22SKCV indoor unit.

2 In case of with the RAS-M22SKCV indoor unit.

The additional charging of refrigerant is unnecessary because this conditioner is designed with charge-less specification.

30 –

Loading...