On October 1st, 2009, TAC became the Buildings Business of its parent company Schneider Electric. This document reflects the visual identity of Schneider Electric,
howev
er there remains references to TAC as a corporate brand in the body copy. As each document is updated, the body copy will be changed to reflect appropriate
corporate brand changes.
All brand names, trademarks and registered trademarks are the property of their respective owners. Information contained within this document is subject to change
without notice.
I/A Series MicroNet BACnet Smoke Control Manual vii
Table of Contents
viii I/A Series MicroNet BACnet Smoke Control Manual
Preface
Preface
Purpose of this
Manual
This manual is intended for use by qualified, authorized engineers and
technicians who are responsible for meeting a UL 864 UUKL/UUKL7 project
specification. The specification, created by the smoke-control system designer,
should have already considered the selected mechanical equipment design.
Proper duct sizing and layout, motor/blower selection, and damper selection must
be completed by the smoke-control system designer to provide the planned
smoke-control pressurization under all possible expected environmental (wind,
weather, etc.) and building (door, elevator hoistway, leakage, system response,
stairwell, occupied mode, etc.) conditions.
Note:
• UUKL7, which is referred to throughout this manual, is the Category Code
Number (CCN) for smoke-control system equipment certified for use in
Canada.
• Throughout this manual, all references to UUKL are intended to refer to
UUKL7 also (i.e. UUKL/UUKL7).
• Throughout this manual, all references to the MNB-V1 equally apply to the
MNB-V1-2 and all references to the MNB-V2 equally apply to the MNB-V2-2.
This manual’s purpose is to provide the fundamentals for the controls engineer
and technicians to meet a properly designed smoke-control specification. General
topologies, specific requirements, and exceptions to our published literature that
are required by Underwriters Laboratories, Inc. for UL 864 UUKL/UUKL7 are
provided. This manual does not provide guidelines for mechanical system
selection and design. Recognized smoke pressurization program models are
available for this purpose.This manual also does not cover all installation and
wiring requirements for TAC I/A Series
be used along with the I/A Series MicroNet BACnet Wiring, Networking, and Best Practices Guide, F-27360, and applicable I/A Series BACnet controller installation
instructions.
®
MicroNet™ BACnet™ controllers. It must
F-27419-2TAC I/A Series MicroNet BACnet Smoke Control Systems Manual ix
x TAC I/A Series MicroNet BACnet Smoke Control Systems ManualF-27419-2
DefinitionsBACnet
The following are definitions of terms related to BACnet.
InstanceA device’s instance number, also known as its
Smoke Control
The following definitions of terms related to smoke control are found in
NFPA 92A, Recommended Practice for Smoke-Control Systems.
Area of RefugeAn area of the building separated from other
Preface
BACnet Device Object Identifier.
spaces by fire-rated smoke barriers in which a
tenable environment is maintained for the
period of time that such areas may need to be
occupied at time of fire.
Authority Having
Jurisdiction
End Process VerificationA method that provides positive confirmation
Firefighter’s Smoke
Control Station
Positive/Negative
Pressurization
Smoke BarrierA continuous membrane, either vertical or
The organization, office, or individual
responsible for approving equipment,
materials, an installation, or a procedure.
that the desired result (i.e.airflow, damper
position, etc.) has been achieved when a
controlled device has been activated, such as
during smoke control, testing, or manual
override operations, where failure or cessation
of such positive confirmation results in an
off-normal indication.
A system that provides graphical monitoring
and manual overriding capability over
smoke-control systems and equipment at
designated location(s) within the building for
the use of the fire department.
The desired pressure difference between the
protected space and an adjacent space
measured at the boundary of the protected
space under a specified set of conditions with
the smoke-control system operating.
horizontal, such as a wall, floor, or ceiling
assembly, that is designed and constructed to
restrict the movement of smoke.
Smoke Control ModeA predefined operational configuration of a
system or device for the purpose of smoke
control.
Smoke-Control SystemAn engineered system that uses mechanical
fans to produce pressure differences across
smoke barriers to inhibit smoke movement.
F-27419-2TAC I/A Series MicroNet BACnet Smoke Control Systems Manual xi
Smoke Control ZoneA space within a building enclosed by smoke
barriers, including the top and bottom, that is
part of a zoned smoke-control system.
Smoke Exhaust SystemA mechanical or gravity system intended to
move smoke from the smoke zone to the
exterior of the building, including smoke
removal, purging, and venting systems, as
well as the function of exhaust fans utilized to
reduce the pressure in a smoke zone.
Smoke ZoneThe smoke-control zone in which the fire is
located.
Applicable
Standards
Stairwell Pressurization
System
Tenable EnvironmentAn environment in which smoke and heat is
Zoned Smoke-Control
System
This manual should be used in conjunction with the following standards
which apply to the Schneider Electric UL 864, 9th ed. Listing.
Underwriters Laboratories (UL) Standards
A type of smoke-control system in which stair
shafts are mechanically pressurizaed, with
respect to the fire area, with outdoor air to
keep smoke from contaminating them during a
fire event.
limited or otherwise restricted to maintain the
impact on occupants to a level that is not life
threatening.
A smoke-control system that includes smoke
exhaust for the smoke zone and
pressurization for all contiguous
smoke-control zones.
• UL 864, 9th ed. (2003) Control Units for Fire Protective Signaling
Systems
• UUKL Smoke-Control System Equipment (Category under UL 864)
• CAN/ULC-S527-99 Standard For Control Units For Fire Alarm Systems
• ULC/ORD-C100-92 Smoke Control System Equipment
• UUKL7 Category for Smoke-Control System Equipment Certified for
Use in Canada
National Fire Protection Association (NFPA) Standards
• NFPA 70 National Electrical Code
• NFPA 72 National Fire Alarm Code, 2007 Edition
This standard covers the application, installation, performance, and
maintenance of protective signaling systems and their components.
• NFPA 92A Standard for Smoke-Control Systems Utilizing Barriers and
Pressure Differences, 2009 Edition
This standard covers the design, installation, testing, operation, and
maintenance of new and retrofitted mechanical air conditioning and ven-
xii TAC I/A Series MicroNet BACnet Smoke Control Systems ManualF-27419-2
Preface
tilation systems for the purpose of controlling smoke.
• NFPA 92B Standard for Smoke Management Systems in Malls, Atria,
and Large Areas, 2005 Edition
This standard provides technical data relevant to the design, installation,
testing, operation, and maintenance of new and retrofitted smoke management systems. It is intended for buildings having large volume
spaces, for the management of smoke within the space where the fire
exists, or between spaces not separated by smoke barriers.
Other Standards
• Canadian Electrical Code, Part 1
Conventions Used
in this Manual
The following conventions apply to this printed manual:
• Menu commands appear in bold.
Example — On the Special menu, point to Security, then click Log On.
• Italics is used for emphasis in a statement, such as:
If maximum closed switch voltage is not more than 1.0 V and minimum
open switch voltage is at least 4.5 V, then solid state switches may be
used for a UI or a DI.
It is also used when referring to a document, such as:
Refer to the WorkPlace Tech Tool 5.x Engineering Guide Supplement,
F-27356.
Acrobat (PDF) Conventions
If you are reading this manual online in Adobe
numerous hypertext links exist, both in normal black text and in blue text.
®
Acrobat® (.PDF file format),
• Hypertext links in this document include all entries in the Table of
Contents, as well as cross-references within the body text. For ease of
recognition, cross-reference links within the body text appear in blue
type, for example Manual Summary. A link is indicated whenever the
mouse pointer changes to a hand with a pointing finger.
• When viewing this guide with Adobe Acrobat, you can display various
“bookmark” links on the left side of your screen by choosing “Bookmarks
and Page” from the “View” menu. As with the links described above,
these “bookmark” links will also cause the mouse pointer to change to a
hand with a pointing finger.
Manual SummaryThis manual contains five chapters and two appendices.
Chapter 1 - Introduction
This chapter explains the UL 864 UUKL/UUKL7 Listing and defines various
terms related to Smoke-Control Systems.
Chapter 2 - High-rise Smoke Control
This chapter provides application guidelines for using I/A Series MicroNet
BACnet controllers in a five-floor, high-rise office building that requires the
UL 864 UUKL/UUKL7 Listing for Smoke-Control Systems.
F-27419-2TAC I/A Series MicroNet BACnet Smoke Control Systems Manual xiii
Chapter 3- Warehouse Smoke Control
This chapter provides application guidelines for using I/A Series MicroNet
BACnet controllers in a single-story warehouse building that requires the
UL 864 UUKL/UUKL7 Listing for Smoke-Control Systems.
Chapter 4 - Campus Smoke Control
This chapter provides application guidelines for using I/A Series MicroNet
BACnet controllers in a large campus with multiple buildings that require the
UL 864 UUKL/UUKL7 Listing for Smoke-Control Systems.
Chapter 5 - Restrictions and General Comments
This chapter lists any restrictions associated with the application of
I/A Series MicroNet BACnet controllers to UL 864 UUKL/UUKL7
Smoke-Control Systems. This chapter also includes general comments that
may provide additional insight or flexibility during the engineering process.
Appendix A - Additional Information
Appendix A presents additional information related to the wiring of an
I/A Series MicroNet BACnet Smoke-Control System.
Appendix B - Approved Part Numbers
Appendix B lists the part numbers of all I/A Series MicroNet BACnet
equipment that have been UL 864 UUKL/UUKL7 listed.
Appendix C - Applicable Documentation
Appendix C lists, by F-number, applicable documentation that is required to
install, apply, engineer, operate, and troubleshoot I/A Series MicroNet
BACnet and related equipment.
Appendix D - References
Appendix D lists additional reference documents that are relevant to the
design of Smoke-Control Systems.
xiv TAC I/A Series MicroNet BACnet Smoke Control Systems ManualF-27419-2
Chapter 1
Introduction
Schneider Electric has worked with Underwriters Laboratories, Inc. to gain
the UL 864 UUKL/UUKL7 listing. This UL listing involves testing both
hardware and software for reliability by Underwriters Laboratories, Inc. as it
pertains to this standard and sub-category.
What is the UL 864 UUKL/UUKL7 Listing?
According to Underwriters Laboratories, the UL 864 UUKL/UUKL7 is a
category that has been established for Smoke-Control System Equipment.
“The products covered by this category are intended to be installed in
conjunction with heating-ventilating-air conditioning (HVAC) equipment to
form a system for controlling the flow of smoke in a building during a fire
condition in accordance with Smoke-Control Systems, NFPA 92A or 92B.”
Additionally, according to Underwriters Laboratories (UL), smoke-control
equipment is assigned one or more of the following attributes:
Note: Schneider Electric is listed for all of the following UUKL attributes.
1
1. Operation
Manual—Activation of the smoke-control system occurs as a result of
the intervention of an authorized person.
Automatic—Activation of the smoke-control system occurs as a result of
an alarm condition from a fire detection device, such as a smoke detector or heat detector, or fire alarm control unit.
2. Type
Nondedicated—A system which provides the building HVAC function
under normal conditions and provides a smoke-control objective during
a fire alarm condition.
Dedicated—A system which is normally inactive and is used exclusively
for the purpose of smoke control.
3. Use
Stairwell—Configuration of equipment which provides pressurizing of
stairwells for the purpose of maintaining a tenable environment for building egress.
1. Underwriters Laboratories, Heating, Cooling, Ventilating, Cooking and Food Safety
Equipment Directory 2006.
F-27419-2TAC I/A Series MicroNet BACnet Smoke Control Systems Manual1
Chapter 1
Zoned Smoke Control—A configuration which provides the exhausting of the
smoke area and pressurizing all of the other contiguous areas of the build-
2
ing.”
The design of an overall smoke-control system is a complete system engineered
to the particular installation. The interconnection of the smoke-control equipment
to the HVAC equipment, and to other system equipment, is intended to be in
accordance with a specific installation diagram that is generated by either the
smoke-control equipment listee or by another responsible party.
In practice, Schneider Electric, as a UL Smoke Control Equipment Listee, and its
associated field offices do not design the smoke-control system. Rather, the
Schneider Electric field office works closely with the smoke-control system
designer to develop the interface between the controls and equipment supplied by
Schneider Electric and the mechanical equipment that provides smoke-control
pressurization. The Schneider Electric field office then generates the control
system installation diagrams based on the total smoke-control system design.
What Was Required to Gain the UL 864 UUKL/UUKL7 Listing?
UL 864 UUKL/UUKL7 testing has two basic elements: hardware and software.
Each element was reviewed and tested to meet the UL 864 UUKL/UUKL7
acceptance criteria.
HardwareThe hardware has been designed to meet UL 864 transient testing requirements
on all communications and input/output points. This includes EIA-485 (formerly
RS-485) ports, Ethernet ports, power, and all I/O points. The result of these
modifications has been to protect the I/A Series BACnet products against high
level transients and further reduce the susceptibility of the I/A Series BACnet
controllers to static electricity and lightning. This does not mean that lightning
protection is not required. In fact, lightning protection is still required whenever
communication lines enter or leave a building.
SoftwareA systems level application was created, documented, and tested to prove
I/A Series BACnet controllers could perform a smoke-control sequence within the
guidelines of UL 864 UUKL/UUKL7 and NFPA 92A. This systems level application
used a representative selection of I/A Series BACnet hardware. Three additional
systems applications were created to provide a guideline for applying I/A Series
BACnet controllers to generic smoke-control situations. These applications are
briefly explained here and detailed in Chapters 2 through 4.
• High-rise Smoke Control Using MNB-300, MNB-Vx, and MNB-1000
Controllers
Detailed in Chapter 2, this application provides guidelines for using I/A Series
BACnet controllers in a five-floor, high-rise office building that requires the
UL 864 UUKL/UUKL7 listing for Smoke-Control Systems. This application
performs the smoke-control sequences by controlling stairwell pressurization
2. Underwriters Laboratories, Heating, Cooling, Ventilating, Cooking and Food Safety
Equipment Directory 2006.
TAC I/A Series MicroNet BACnet Smoke Control Systems ManualF-27419-2
2
Introduction
systems, terminal boxes, dedicated smoke-control dampers, and central air
handling unit (AHU) systems. The normally open (N.O.) relay contacts of a
UOJZ fire alarm panel are monitored for smoke/fire alarm signals which initiate automatic activation of the smoke-control sequences. The UUKL listed
Firefighter’s Smoke Control Station (FSCS) is monitored for manual activation
and overrides. Control of the FSCS visual and audible status indicators is also
provided.
• Warehouse Smoke Control Using MNB-300 and MNB-1000 Controllers
Detailed in Chapter 3, this application provides guidelines for using I/A Series
BACnet controllers in a single-story warehouse building that requires the
UL 864 UUKL/UUKL7 listing for Smoke-Control Systems. This application
performs the smoke-control sequences by controlling several zoned AHU systems. The N.O. relay contacts of a UOJZ fire alarm panel are monitored for
smoke/fire alarm signals which initiate automatic activation of the smoke-control sequences. The UUKL listed Firefighter’s Smoke Control Station (FSCS)
is monitored for manual activation and overrides. Control of the FSCS visual
and audible status indicators is also provided.
• Campus Smoke Control Using MNB-300, MNB-Vx, and MNB-1000
Controllers
Detailed in Chapter 4, this application provides guidelines for using I/A Series
BACnet controllers in a large campus with multiple buildings that require the
UL 864 UUKL/UUKL7 listing for Smoke-Control Systems. This application
performs the smoke-control sequences by controlling terminal boxes, dedicated smoke-control dampers, and several AHU systems. The N.O. relay
contacts of a UOJZ fire alarm panel are monitored for smoke/fire alarm signals which initiate automatic activation of the smoke-control sequences. The
UUKL listed Firefighter’s Smoke Control Station (FSCS) is monitored for manual activation and overrides. Control of the FSCS visual and audible status
indicators is also provided. Multiple Fire Alarm Panels and FSCSs are used.
What are Your UL 864 UUKL/UUKL7 Responsibilities?
Schneider Electric field offices can now contract for smoke-control systems that
require the UL 864 UUKL/UUKL7 listing for a BACnet system. The I/A Series
BACnet system, however, is not the system that initiates or annunciates the
smoke/fire alarm. That is the responsibility of the primary system, a dedicated fire
alarm system that is listed for the UOJZ category of the UL 864 standard. The
primary system provides the means for detecting, indicating, and annunciating the
smoke/fire alarm. I/A Series BACnet controllers interface to the primary fire alarm
system to monitor the smoke/fire alarm panel output contacts and subsequently
control the HVAC equipment, as required, in the event of a fire/smoke condition.
In addition, the automation system may redundantly (as a secondary system)
annunciate fire/smoke alarms.
The applications produced and the guidelines provided by Schneider Electric in
the I/A Series Micronet BACnet Smoke-Control Systems Manual are intended as
a reference. They must be reviewed and revised to fit the individual installation
and the project’s specifications. It is the individual field office’s responsibility to
ensure that the I/A Series BACnet system meets the requirements of the project’s
F-27419-2TAC I/A Series MicroNet BACnet Smoke Control Systems Manual3
Chapter 1
specifications, but not necessarily to perform the system’s mechanical design
function. The smoke-control system designer should have already completed the
mechanical system design, and validated the design’s concept using a proven
smoke-control system program model.
Proper duct sizing and layout, motor/blower selection, and damper selection must
be completed by the smoke-control system designer to provide the planned
smoke-control pressurization under all possible expected environmental (wind,
weather, etc.) and building (door, elevator hoistway, leakage, system response,
stairwell, occupied mode, etc.) conditions. Adjacent corridors and zones should
have been considered by the smoke-control system designer because they have
a direct impact on pressurization.
The smoke-control system designer should also specify the required controls
sequence, and realizing that there are reaction and confirmation times for HVAC
controls, specify any critical response times that are necessary to meet the
requirements of the smoke-control system design.
Each field office is responsible for the implementation of the smoke-control
sequence as specified by the smoke-control system designer. Additionally, it is the
responsibility of the field office to work with the smoke-control system designer
and gain the smoke-control system approval from the Authority Having
Jurisdiction (AHJ) — and there could be several. I/A Series BACnet equipment
installation must be in strict adherence to the appropriate UL, NFPA, and local
authority requirements. The field office is responsible for following the installation
standards and guidelines set forth by Schneider Electric in this document and as
approved by UL.
Explanation of Smoke-Control Systems
This documentation is intended to be used in conjunction with the NFPA 92A and
UL 864 UUKL/UUKL7 standards. The explanation of smoke-control systems here
consists of highlights from these standards.
Building
Pressurization
Dedicated and
Nondedicated
Systems
The primary means of controlling smoke movement is by creating air pressure
differences between smoke-control zones. The basic concept of building
pressurization is to establish a higher pressure in adjacent spaces than in the
smoke zone. In this way, air moves into the smoke zone from the adjacent areas
and smoke is prevented from dispersing throughout the building.
Smoke control systems are either dedicated or nondedicated. A dedicated
smoke-control system is intended for smoke-control purposes only. It is a
separate system of air moving and distribution equipment that does not function
under normal building operating conditions. When activated, this type of system
performs a specific smoke-control function.
smoke-control systems are stairwell pressurization fans and exhaust dampers
that operate only when in a smoke-control situation.
3. National Fire Protection Association, Inc., NFPA 92A, Standard for Smoke-Control Systems Utilizing Barriers and Pressure Differences, 2009 ed., chap. 1, para. 1.2.1.
4. NFPA 92A, 2009 ed., chap 3, para. 3.3.11.1, 3.3.11.2..
4
Examples of dedicated
3
TAC I/A Series MicroNet BACnet Smoke Control Systems ManualF-27419-2
4
Introduction
Nondedicated smoke-control systems are systems that share components with
some other systems such as the building automation (HVAC) system. When
activated, the system changes its mode of operation to achieve the smoke-control
objectives.
building that supplies several smoke-control zones. Under normal HVAC
operation, the central air handler modulates the outdoor, exhaust, and return air
dampers to maintain a desired discharge temperature. When a smoke-control
sequence is initiated, the control objective changes from maintaining a desired
discharge temperature to a smoke-control sequence that drives the outdoor and
exhaust air dampers fully open and the return air damper fully closed to provide
the maximum amount of outdoor air.
5
An example of this type of system is the central air handler for a
Basic System
Types
Building smoke-control systems can generally be divided into two basic types:
shaft protection and floor protection. Shaft protection consists of stairwell
pressurization systems and elevator hoistway systems. Floor protection involves
several variations of zoned smoke control. Use of a particular system or
combination of systems is dependent on building and fire code requirements, as
well as specific occupancy and life safety requirements of the situation being
considered.
Note: Recent trends have indicated areas of refuge are being designed into
many buildings as dictated by the Americans for Disabilities Act (ADA).
Specifications may refer to these areas of refuge which are typically located
adjacent to stairwells or elevator hoistways. These refuge zones may require
special pressure compensated systems in order to maintain a tenable
environment. The requirements for these systems must be dictated by the
building’s smoke-control system designer based on the smoke-control system
design and its associated sequence of operation. When these types of zones are
encountered, additional time and resources may be required to establish and
verify compliance to the specification. These areas of refuge are not part of the
UUKL listing requirements.
Shaft Protection
Stairwell Pressurization Systems
The goal of pressurized stairwells is to maintain “a tenable environment within exit
stairwells for the time necessary to allow occupants to exit the building.”
6
A
tenable environment is defined as “An environment in which the products of
combustion, including toxic gases, particulates, and heat, are limited or otherwise
restricted to maintain the impact on occupants to a level that is not life
threatening.”
staging area for firefighters.
pressurized, with respect to the fire area, with outdoor air to keep smoke from
contaminating them during a fire incident.”
A secondary objective of stairwell pressurization is to provide a
8
This is achieved when “stair shafts are mechanically
9
F-27419-2TAC I/A Series MicroNet BACnet Smoke Control Systems Manual5
Chapter 1
There are two types of stairwell systems: noncompensated and compensated. In
a noncompensated system, supply air is provided to the stairwell by starting a fan.
This provides two or more positive pressure differentials: one differential with all of
the doors closed, a second differential with one door open, and so on.
10
In a
compensated system, supply air is also provided to the stairwell by starting a fan,
but the fan system adjusts the positive differential pressure based on the various
combinations of opened and closed doors. This adjustment may be accomplished
by either modulating supply airflows or by relieving excess pressure from the
stairwell.
motor-operated dampers, an automatically opening stairwell door to the outside at
ground level, or an exhaust fan.
11
Typically, over-pressure relief may utilize barometric dampers,
12
Elevator Smoke Control
“Historically, elevator hoistways have proved to be a readily available conduit for
the movement of smoke throughout buildings.”
13
Although several methods for
correcting this problem have been proposed and investigated, there are no firm
recommendations regarding elevator smoke control. Refer to the NFPA 92A and
UL 864 UUKL/UUKL7 standards for additional information. Remember, the local
AHJ and project specifications may require control beyond that specified in the
above standards.
Floor Protection
Zoned Smoke Control
Pressurized stairwells, discussed above, “are intended to control smoke to the
extent that they inhibit smoke infiltration into the stairwell. However, in a building
with just a pressurized stairwell, smoke can flow through cracks in floors and
partitions and through other shafts to threaten life or damage property at locations
remote from the fire. The concept of zoned smoke control …is intended to limit
this type of smoke movement within a building.”
With zoned smoke control, smoke movement is inhibited by dividing the building
“into smoke-control zones, with each zone separated from the others by smoke
barriers.”
closed. When a fire occurs in one of these smoke-control zones, it is called a
smoke zone.
by mechanical fans and operating dampers can be used to limit the smoke to the
zone in which the fire originated.
15
These smoke barriers can be partitions, floors, or doors that can be
16
In the event of a fire, pressure differences and airflows produced
17
When a fire/smoke condition occurs, all of the
nonsmoke zones that are contiguous to the smoke zone are positively
pressurized and the smoke zone is negatively pressurized. Optionally, all of the
remaining smoke-control zones in the building may also be positively
pressurized.
18
With the smoke contained to the smoke zone, it can then be
14
10.NFPA 92A, 2009 ed., annex B, para. B.1.
11.NFPA 92A, 2009 ed., annex B, para. B.2.
12.NFPA 92A, 2009 ed., annex B, para. B.4.
13.NFPA 92A, 2009 ed., annex A, para. A.5.4.
14.NFPA 92A, 2009 ed., annex A, para. A.5.5, annex A, para. A.8.1.
15.NFPA 92A, 2009 ed., chap. 5, para. 5.5.1.1.
16.NFPA 92A, 2009 ed., chap. 3 para. 3.3.15.
17.NFPA 92A, 2009 ed., annex A, para. A.5.5.
18.NFPA 92A, 2009 ed., annex A, para. A.5.5.1.1.1.
TAC I/A Series MicroNet BACnet Smoke Control Systems ManualF-27419-2
6
Introduction
exhausted. Typically, the fire/smoke signals from a protective signaling
system (UOJZ, a UL 864 Listed Fire Alarm Control Unit; i.e. fire alarm panel)
are used to activate the zoned smoke-control sequence.
19
HVAC EquipmentHVAC equipment normally provides a means of supplying, returning and
exhausting air to, or from, a space. Most HVAC equipment “can be adapted
to provide the necessary logic and control sequences to configure HVAC
systems for smoke control.”
ducts are interconnected as part of the normal HVAC operation, smoke
dampers are needed to separate the supply and exhaust air during a
smoke-control sequence (return air damper).
use centralized HVAC equipment in main mechanical areas to serve multiple
floors or zones. These central systems may require fire and smoke shaft
dampering to provide exhaust of the fire floor and pressurization of the
adjacent floors with outdoor air. Due to their capacity, central systems should
include a means to prohibit excessive pressures within the duct system and
prevent rupture, collapse, or other damage.
Typically, fan coil units and water source heat pump units can be excluded
from performing smoke-control sequences. However, if these units have the
ability to supply outdoor air, any of the units that are within the smoke zone
should be shut down so that the zone can be negatively pressurized.
induction-type air handling unit is used within a smoke zone, it should be
shut down or have its primary air supply closed off.
20
However, when the supply and return air
21
Additionally, some buildings
22
24
23
If an
Smoke-Control
System Activation
Some VAV systems bypass supply air to the return air inlet of the fan. In
these cases, the bypasses must be closed when the unit is in the
smoke-control mode. Additionally, the VAV system fan and terminal unit
controls should be configured to supply the maximum amount of outdoor air
to pressurize the nonsmoke zones.
supplying the smoke zone, the terminal fan should be turned off. “Terminal
units serving zones adjacent to the smoke zone can continue to operate.”
25
If a fan-powered terminal unit is
26
“Operating controls of the HVAC system shall be designed or modified to
provide the smoke-control mode with the highest priority over all other
control modes.”
27
Normally the smoke-control sequences are activated
automatically, but in some cases, manual activation may be more
appropriate. In either case, “the smoke-control system shall be capable of
being manually overridden and manually deactivated.”
28
The automatic
smoke-control system “shall be automatically activated in response to
signals received from a specific fire detection device or a combination of fire
detection devices.”
19.NFPA 92A, 2009 ed., chap. 6, para. 6.4.5.1.1.
20.NFPA 92A, 2009 ed., annex A, para. A.6.4.2.
21.NFPA 92A, 2009 ed., chap. 6, para. 6.2.3.
22.NFPA 92A, 2009 ed., annex C, para. C.3.
23.NFPA 92A, 2009 ed., annex C, para. C.4.
24.NFPA 92A, 2009 ed., annex C, para. C.5.
25.NFPA 92A, 2009 ed., annex C, para. C.7.
26.NFPA 92A, 2009 ed., annex C, para. C.8.
27.NFPA 92A, 2009 ed., chap. 6, para. 6.4.2.
28.NFPA 92A, 2009 ed., chap. 6, para. 6.4.3.3.
29.NFPA 92A, 2009 ed., chap. 6, para. 6.4.3.4.
29
Fire detection devices “include automatic devices such
F-27419-2TAC I/A Series MicroNet BACnet Smoke Control Systems Manual7
Chapter 1
as smoke detectors, waterflow switches, and heat detectors.”30 Manual fire
alarm pull stations should generally not be used to activate automatic
smoke-control systems, other than stairwell pressurization systems,
because of the likelihood of a person signaling an alarm from a station
outside the smoke zone of origin.
31
Response TimeSmoke control system activation should be started immediately after
receiving an activation command. A maximum of 10 seconds transmission
time is allowed, from the initiation of an activation signal (i.e. fire alarm
input), to the time it reaches the MicroNet BACnet smoke control system
(i.e. binary input of a MicroNet controller). The smoke-control sequence
should activate individual components in the sequence necessary to prevent
physical damage to fans, ducts, dampers, and other equipment. The total
response time of the individual component starts from the moment the
smoke-control command is issued (whether automatic or manual) to the final
action. This time is 60 seconds for fan operation at the desired state and
75 seconds for the completion of the damper travel.
component fail, the time lapse from the moment the component should have
reached its final state and the moment its associated trouble signal
annunciates, should not exceed 10 seconds.
33
annunciation of the trouble signal for a fan must occur within 70 seconds of
the automatic or manual activation command. The annunciation of the
damper trouble signal must occur within 85 seconds of the automatic or
manual activation command.
32
Should an individual
This means that the
Firefighter’s Smoke
Control Station
The Firefighter's Smoke Control Station (FSCS) “shall provide status
indication, fault condition indication, and manual control of all smoke-control
system components.”
over all smoke-control systems and equipment. “
take precedence over fire suppression, electrical protection, or personnel
protection devices.”
34
“The FSCS shall have the highest priority control
36
For more information, refer to the NFPA 92A and
35
“FSCS control shall not
UL 864 UUKL/UUKL7 standards.
The FSCS should contain a building diagram that clearly indicates the type
and location of all smoke control equipment, such as fans and dampers.
37
The areas of the building that are affected by the equipment and the actual
status of all of the smoke control equipment should be clearly indicated at
the FSCS. Status indication should be provided for each fan showing
whether it is ON or OFF. Status indication of the full-closed and full-open
positions of each smoke control damper should also be shown on the
38
FSCS.
30.NFPA 92A, 2009 ed., annex 6, para. A.6.4.3.4.
31.NFPA 92A, 2009 ed., chap. 6, para’s 6.4.3.5.2 and 6.4.3.5.3, and annex A,
32.Underwriters Laboratories Inc., UL 864, Control Units and Accessories for Fire
33.UL 864, 9th ed., para. 49.2.b
34.NFPA 92A, 2009 ed., chap. 6, para. 6.4.3.7.3.
35.NFPA 92A, 2009 ed., chap. 6, para. 6.4.3.7.11.
36.NFPA 92A, 2009 ed., chap. 6, para. 6.4.3.7.14, and UL 864, 9th ed., para. 48.3.
37.NFPA 92A, 2009 ed., chap. 6, para 6.4.3.7.10 and annex D, para D.1 (2).
Proof of air flow should be used to determine the fan status. Proof
para’s A.6.4.3.5.2 and A.6.4.3.5.3.
Alarm Systems, 9th ed. (2003), para. 49.2.c.
TAC I/A Series MicroNet BACnet Smoke Control Systems ManualF-27419-2
8
Introduction
of damper positions should be done using end process verification. This may
be done through the use of damper degree-of-opening switches, flow
stations, etc.
Whenever the communications fails between any of the I/A Series MicroNet
BACnet controllers that are integral to the smoke-control equipment or
sequences, including instances when a controller loses power, a system
trouble visual indicator (i.e. LED) at the FSCS should illuminate and an
audible signal must sound.
also be generated if any of the smoke-control equipment proof sensors fail
to operate within a specified period of time during the smoke-control
sequence or when under control of the FSCS.
indicators must annunciate an audible sound. In addition to the status
indication that is required for all of the smoke-control equipment, each
dedicated piece of smoke-control equipment must also provide a visual
trouble indicator specifically for that device.
39
The visual and audible trouble indicators must
40
In general, all visual trouble
41
Control Sequence
for Stair
Pressurization
Systems
Control Sequence
for Zoned
Smoke-Control
Systems
Any time a smoke/fire detector trips (refer to NFPA 92A and
UL 864 UUKL/UUKL7 for acceptable signaling device types), initiating an
automatic smoke-control sequence, all stairwell pressurization fans shall be
energized
determines that operation of all stairwell pressurization fans is not required
to achieve the design objective, only the stairwell pressurizaiton fans
identified during the analysis shall be required to be activated.”
detector should be provided in the air supply to each fan that stops the
respective pressurization fan when smoke is detected.
switch for each fan should be provided at the FSCS that allows the stairwell
fans to restart after they have been shutdown due to the supply air smoke
detectors,
entering the fan than smoke migrating into the stairwell. When a stairwell
pressurization sequence is used in conjunction with zoned smoke control,
care must be taken to prevent the interrelation of the two sequences from
adversely affecting each other.
“Automatic activation of systems and equipment for zoned smoke control
should have the highest priority over all other sources of automatic control
within the building.”
used for normal building control such as HVAC systems, the equipment
control should be pre-empted as required by the smoke-control sequence.
“The following controls should not be automatically overridden:
42
, with one exception. “Where an engineering analysis
43
A smoke
44
A manual override
45
should it be determined that a lessor hazard exists from smoke
46
47
For example, when the smoke-control equipment is
• Static pressure high limits.
38.NFPA 92A, 2009 ed., chap 6, para’s 6.4.3.7.3 through 6.4.3.7.10, and annex D,
para D.1 (5).
39.UL 864, 9th ed., para’s 48.5, 49.4, 49.6, and 49.7.
40.UL 864, 9th ed., para’s 48.5 and 49.6.
41.NFPA 92A, 2009 ed., chap 6, para’s 6.4.3.7.3 and UL 864, 9th ed., para 49.6.
42.NFPA 92A, 2009 ed., chap 6, para 6.4.4.1.
43.NFPA 92A, 2009 ed., chap 6, para 6.4.4.1.1.
44.NFPA 92A, 2009 ed., chap 6, para’s 6.4.4.2.1 and 6.4.4.2.2.
45.NFPA 92A, 2009 ed., chap 6, para 6.4.4.4.
46.NFPA 92A, 2009 ed., annex A, para. A.5.7.
47.NFPA 92A, 2009 ed., chap. 6, para. 6.4.5.2.1.
F-27419-2TAC I/A Series MicroNet BACnet Smoke Control Systems Manual9
Chapter 1
• Duct smoke detectors on supply air systems.”
Manual activation or deactivation of zoned smoke-control systems and equipment
(at the FSCS) should take priority over automatic activation, as well as take
priority over all other sources of automatic control within the building.
controls provided specifically for this purpose should be clearly marked as to the
zone and function served (typically part of the FSCS).
Any time a smoke/fire detector trips initiating an automatic smoke-control
sequence, all stairwell pressurization sequences should operate as stated
previously.
several smoke-control zones, the supply and return fan for the AHUs are
commanded ON. The outdoor and exhaust air dampers for each AHU drive to the
full-open position and the return air damper drives to the full-closed position. All
exhaust air dampers in the smoke zone drive to the full-open position and the
supply air dampers drive to the full-closed position. All smoke-control zones
contiguous to the smoke zone (and optionally all remaining smoke-control
zones
their exhaust air dampers driven to the full-closed position. Pressurization of the
non-contiguous (optional) smoke-control zones is dependent upon the
smoke-control system design and its associated specification. Regardless of
whether or not non contiguous zones are positively pressurized, sufficient
differential pressure must be achieved to limit the smoke spread to the zone in
which the fire originated.
This smoke-control sequence provides the maximum amount of outdoor air to the
nonsmoke zones causing them to be positively pressurized. Since the exhaust air
dampers are fully open in the smoke zone and no supply air is being provided, the
AHU begins exhausting the smoke from the smoke zone. With the nonsmoke
zones being positively pressurized in this manner, smoke is inhibited from
migrating outside of the smoke zone.
51
For applications where each central air handling unit (AHU) supplies
52
) should have their supply air dampers driven to the full-open position and
48
50
49
Manual
Automatic
Response To
Multiple Signals
Maintaining
System
Integrity
TAC I/A Series MicroNet BACnet Smoke Control Systems ManualF-27419-2
10
Once an automatic activation has occurred, subsequent alarm signals that would
normally result in the automatic actuation of a smoke-control sequence should be
annunciated only. No fans or dampers should be actuated in response to any
subsequent automatic alarm signal in order to avoid the possibility of defeating
any smoke-control sequence which is in process.
A prime concern with any emergency signaling system is maintaining system
integrity. This is typically accomplished by electrical supervision of wiring,
however, since the proper operation of the fans and dampers associated with a
smoke-control system may involve mechanically and pneumatically operated
devices, as well as electrically operated devices, end-process verification is
considered an acceptable alternative.
Smoke control system equipment is required to verify that a fan or damper has
achieved its required end function. This end function verification consists of
monitoring fans by differential pressure switches, flow stations, and etc., and
51.NFPA 92A, 2009 ed., chap 6, para’s 6.4.4.1 and 6.4.4.1.1.
52.NFPA 92A, 2009 ed., annex A, para. A.5.5.1.1.1.
Introduction
monitoring dampers by degree-of-opening switches, differential pressure
switches, and etc. These verification devices should be connected back to
the smoke-control system equipment (I/A Series BACnet, for example) and
the system programmed to expect the appropriate signal within the specified
amount of time.
Any change in a smoke-control signal input (i.e. FAP, FSCS, etc) must be
received into the smoke-control system in 10 seconds or less. Fans and
dampers have 60 and 75 seconds, respectively, from the time the signal
input is received, to successfully respond to smoke-control sequence
commands. If a fan or damper fails to achieve its desired state within the
times referenced above, the failures have to be annunciated within an
additional 10 seconds. Other trouble signals, such as communication
failures (supervised through software), have up to 200 seconds to
annunciate their failures.
Annunciation of the end function sensor is not required if the proof sensor
operates as intended, but if the proof sensor fails to operate, an audible and
visual trouble signal must be generated at the FSCS. This would be typical
of the operation of the smoke-control system during an emergency
condition.
For operation during a nonemergency condition, the means for verifying
system integrity varies based on whether the smoke-control system is a
dedicated or nondedicated system. Nondedicated smoke-control systems
and equipment consist of HVAC components within a building which are
operated regularly. Therefore, the normal “comfort” level associated with the
operability or inoperability of the equipment is considered an acceptable
means of maintaining system integrity.
53
54
55
Smoke-Control
System Schedule
Dedicated smoke-control systems and equipment are used solely for the
purpose of smoke-control and are not operated in a nonemergency
condition. Dedicated system equipment is therefore required to incorporate
an automatic weekly self-test of each smoke-control function. The self-test
consists of the smoke-control system automatically commanding the
associated function to operate and expecting that the associated proof
sensor operates within a specified period of time (refer to response times
noted earlier). A valid proof sensor operation is not required to annunciate,
however, the lack of an expected proof sensor operation must produce an
audible trouble signal, as well as indicate the specific device that did not
operate (for example, LED at the FSCS).
Each different smoke-control system configuration/sequence should be
defined in a schedule, typically a matrix chart. The schedule should list all
dedicated and nondedicated smoke-control equipment and show the
equipment response for each sensor that activates an automatic sequence.
At a minimum, the schedule should include the following information:
• Each smoke zone in which a smoke-control system automatically
activates.
53.NFPA 92A, 2009 ed., chap. 6, para. 6.4.6. and annex A, para. A.6.4.6.
54.UL 864, 9th ed., para. 36.1.2 (c), 49.2 (b).
55.NFPA 92A, 2009 ed., chap. 2, para. 2.1.2. and 2.1.5., and UL 864, 9th ed.,
para’s 49.7.
F-27419-2TAC I/A Series MicroNet BACnet Smoke Control Systems Manual11
Chapter 1
• The type of alarm signal that activates the smoke-control system (smoke
detector, sprinkler water flow, and etc.)
• The smoke zones where maximum mechanical exhaust to the outside is
implemented and no supply air is provided.
• The positively pressurized smoke-control zones where maximum supply air is
implemented and no exhaust to the outside is provided.
• The fans that are ON as required to implement the smoke-control system.
Multiple-speed fans should be further noted as FAST or MAX VOLUME to
ensure that the intended control configuration is achieved.
• The fans that are OFF as required to implement the smoke-control system.
• The dampers that are Open where maximum air flow must be achieved.
• The dampers that are Closed where no air flow should take place.
• Any additional functions that may be required to achieve the smoke-control
objective or that may be desirable in addition to smoke control. Changes or
override of normal static pressure control setpoints should also be indicated if
applicable.
• Damper position at fan failure.
56
Conclusion
When applying I/A Series BACnet controllers to smoke-control sequences, review
this introductory information along with the NFPA 92A and UL 864 UUKL/UUKL7
standards. This information should be used in conjunction with the sample
smoke-control applications (Chapters 2 through 4) and the restrictions and
general comments (Chapter 5) that are part of the total smoke-control
documentation provided by Schneider Electric.
56.NFPA 92A, 2009 ed., annex A, para 6.4.5.3 (10).
TAC I/A Series MicroNet BACnet Smoke Control Systems ManualF-27419-2
12
Chapter 2
High-rise Smoke Control
Purpose
This application provides guidelines for using I/A Series MicroNet BACnet
controllers in a five-floor, high-rise office building (Figure–2.1) that requires
the UL 864 UUKL/UUKL7 listing for Smoke-Control Systems. This
application uses MNB-300, MNB-Vx, and MNB-1000 controllers that perform
HVAC functions when in the normal control mode. When in the
smoke-control mode, they perform the required smoke-control sequences
by controlling the stairwell pressurization fans, the individual terminal boxes,
the dedicated smoke-control dampers, and the central air handling unit
(AHU) fans. Additionally, they control all supply, exhaust, and return air
dampers, and provide the feedback of all end-process verification required.
The I/A Series BACnet controllers monitor N.O. relay contacts of a UOJZ
listed fire alarm panel for automatic activation of the smoke-control
sequences and monitor a UL 864 UUKL/UUKL7 Listed Firefighter’s Smoke
Control Station (FSCS) for manual activation commands and overrides. In
this example, an ADI FSCS is used, which supports the ADI ModBus
interface to the MNB-1000. This interface provides control over all the FSCS
visual and audible status indicators, as well as receipt of the FSCS override
commands, thus eliminating the need to allocate additional controllers to
interface to the FSCS through individual I/O points.
Sequence of Operation
Normal HVAC
Control
F-27419-2TAC I/A Series MicroNet BACnet Smoke Control Systems Manual13
Under normal conditions, the central AHU follows an occupied schedule that
determines when the AHU operates. During the unoccupied mode, the
outdoor and exhaust air dampers are in the full-closed position. The return
air damper is in the full-open position. The supply and return fans are
commanded OFF. During the occupied mode, the supply and return fans are
commanded ON. The outdoor, exhaust, and return air dampers modulate as
required to maintain a mixed air temperature setpoint. The central AHU can
have a wide variety of additional control sequences that determine its
operation and establish its operating priorities (for example, low limit stats
and minimum outdoor air).
Chapter 2
Figure–2.1 High-rise Building Layout.
Central Air Handling Unit
Exhaust Air Damper
Return Air Damper
Return AirSupply Fan
Exhaust
Air
Damper
Exhaust
Air
Damper
Exhaust
Air
Damper
Eight MNB-Vx Controllers
Eight MNB-Vx Controllers
Eight MNB-Vx Controllers
Outdoor Air Damper
Supply Air
Damper
5th Floor
Supply Air
Damper
4th Floor
Supply Air
Damper
Stairwell #2Stairwell #1
Pull
Station
Pull
Station
Pressurization
Fan - Stair 1
Duct Smoke
Detector
SD
3rd Floor
Exhaust
Air
Damper
Exhaust
Air
Damper
Note: All references to the MNB-V1 equally apply to the
MNB-V1-2 and all references to the MNB-V2 equally
apply to the MNB-V2-2.
Eight MNB-Vx Controllers
2nd Floor
Eight MNB-Vx Controllers
1st Floor
Supply Air
Damper
Supply Air
Damper
Pressurization
Fan - Stair 1
SD
Duct Smoke
Detector
TAC I/A Series MicroNet BACnet Smoke Control Systems ManualF-27419-2
14
Loading...
+ 106 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.