Schneider Electric TAC I/A Series Operation Manual

Page 1
TAC I/A Series MicroNet BACnet
Smoke-Control Systems Manual
Page 2
Page 3
TAC I/A Series MicroNet BACnet
Smoke-Control Systems Manual
Printed in U.S.A. 9-10 F-27419-2
Page 4
On October 1st, 2009, TAC became the Buildings Business of its parent company Schneider Electric. This document reflects the visual identity of Schneider Electric, howev
er there remains references to TAC as a corporate brand in the body copy. As each document is updated, the body copy will be changed to reflect appropriate
All brand names, trademarks and registered trademarks are the property of their respective owners. Information contained within this document is subject to change without notice.
Schneider Electric
F-27419-2 September 2010 ptm
© 2010 Schneider Electric. All rights reserved.
Page 5

Table of Contents

Preface
Purpose of this Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ix
Abbreviations Used in this Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . x
Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xi
Applicable Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .xii
Conventions Used in this Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . xiii
Manual Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xiii
Chapter 1 Introduction
What is the UL 864 UUKL/UUKL7 Listing? . . . . . . . . . . . . . . . . . . . . .1-1
What Was Required to Gain the UL 864 UUKL/UUKL7 Listing? . . . . . 1-2
Hardware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-2
Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
What are Your UL 864 UUKL/UUKL7 Responsibilities? . . . . . . . . . . . . 1-3
Explanation of Smoke-Control Systems . . . . . . . . . . . . . . . . . . . . . . . . 1-4
Building Pressurization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
Dedicated and Nondedicated Systems . . . . . . . . . . . . . . . . . . . . . .1-4
Basic System Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-5
Shaft Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-5
Floor Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-6
HVAC Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-7
Smoke-Control System Activation . . . . . . . . . . . . . . . . . . . . . . . . . . 1-7
Response Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-8
Firefighter’s Smoke Control Station . . . . . . . . . . . . . . . . . . . . . . . . . 1-8
Control Sequence for Stair Pressurization Systems . . . . . . . . . . . .1-9
Control Sequence for Zoned Smoke-Control Systems . . . . . . . . . .1-9
Automatic Response To Multiple Signals . . . . . . . . . . . . . . . . . . . .1-10
Maintaining System Integrity . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-10
Smoke-Control System Schedule . . . . . . . . . . . . . . . . . . . . . . . . . 1-11
Conclusion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-12
I/A Series MicroNet BACnet Smoke Control Manual iii
Page 6
Table of Contents
Chapter 2 High-rise Smoke Control
Purpose . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-13
Sequence of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-13
Normal HVAC Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-13
Smoke Control Sequences . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-17
Smoke-Control System Configuration Schedule . . . . . . . . . . . . . . . . 2-20
Firefighter’s Smoke Control Station (FSCS) . . . . . . . . . . . . . . . . . . . 2-22
Location and Access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-22
Physical Arrangement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-22
Status Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-22
Audible Annunciation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-23
Control Capability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-23
Additional Control Requirements . . . . . . . . . . . . . . . . . . . . . . . . . 2-23
System Topologies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-25
MNB-1000 Controllers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-25
Ethernet/IP Infrastructure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-25
Wiring Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-26
Central System Interface and Overlay Devices . . . . . . . . . . . . 2-26
MNB-Vx Topology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-28
MS/TP Bus Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-28
MNB-1000 Interface to FSCS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-30
Fire Alarm Panel Interface and Remaining System Topology . . . 2-32
Comments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-33
Chapter 3 Warehouse Smoke Control
Purpose . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-35
Sequence of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-35
Normal HVAC Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-35
Smoke Control Sequences . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-36
Smoke-Control System Configuration Schedule . . . . . . . . . . . . . . . . 3-39
Firefighter’s Smoke Control Station (FSCS) . . . . . . . . . . . . . . . . . . . 3-40
System Topologies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-40
Warehouse Building Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-40
Ethernet/IP Infrastructure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-41
Wiring Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-41
Central System Interface and Overlay Devices . . . . . . . . . . . . 3-41
MNB-1000 Interface to FSCS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-43
Fire Alarm Panel Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-43
Comments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-46
Chapter 4 Campus Smoke Control
Purpose . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-47
Sequence of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-47
Normal HVAC Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-47
Smoke Control Sequences . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-49
iv I/A Series MicroNet BACnet Smoke Control Manual
Page 7
Smoke-Control System Configuration Schedule . . . . . . . . . . . . . . . .4-53
Firefighter’s Smoke Control Station (FSCS) . . . . . . . . . . . . . . . . . . . .4-55
System Topologies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-55
Campus Topology with MNB-1000 Controllers . . . . . . . . . . . . . . . 4-55
Ethernet/IP Infrastructure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-55
Wiring Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-56
Central System Interface and Overlay Devices . . . . . . . . . . . . . . .4-56
MNB-V2 Topology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-59
MS/TP Bus Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-59
MNB-1000 Interface to FSCS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-61
Fire Alarm Panel Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-63
Comments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-63
Chapter 5 Restrictions and General Comments
Purpose . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-65
Restrictions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-65
Software Access Levels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-65
System Overrides . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-66
Approved Fire Alarm Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-67
Approved Firefighter’s Smoke Control Stations . . . . . . . . . . . . . . .5-67
Approved IP/Ethernet Infrastructure Devices . . . . . . . . . . . . . . . . . 5-71
Approved MS/TP Repeaters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-72
Use of MNB-1000 IP Switch Feature . . . . . . . . . . . . . . . . . . . . . . . 5-74
Dedicated Supply Air Dampers . . . . . . . . . . . . . . . . . . . . . . . . . . .5-74
Class 2 Powered Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-75
EIA-485 Termination and Bias Resistors . . . . . . . . . . . . . . . . . . . .5-75
System Self-Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-75
Transformers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-76
Enclosures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-76
Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-77
Hardware and Firmware Upgrade Process Requirements . . . . . . .5-78
UL-1459 (Abnormal Overvoltage) Compliance . . . . . . . . . . . . . . .5-78
General Comments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-78
FSCS Requirement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-78
MNB-1000 Using ADI ModBus Interface . . . . . . . . . . . . . . . . . . . .5-78
Job Estimating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-78
Spare I/O Points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-80
Lost Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-80
Use of BACnet Priority Structures . . . . . . . . . . . . . . . . . . . . . . . . .5-83
Use of Transient Suppressor on MNB-300 DO . . . . . . . . . . . . . . .5-84
Multiple MNB-V1/-V2 Controllers for Pressure Summation . . . . . .5-85
VAV Zone Pressure or Position Indication . . . . . . . . . . . . . . . . . . .5-85
I/A Series BACnet Applications . . . . . . . . . . . . . . . . . . . . . . . . . . .5-85
Table of Contents
I/A Series MicroNet BACnet Smoke Control Manual v
Page 8
Table of Contents
Appendix A Additional Information
MicroNet BACnet Controllers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1
Common Controller Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1
MNB-300 Unitary Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-2
MNB-V1, MNB-V2 VAV Controllers . . . . . . . . . . . . . . . . . . . . . . . . A-4
MNB-1000 Plant Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-6
Input and Output Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-8
Universal Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-8
Universal Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-9
Digital Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-9
Digital Outputs, Triac . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-10
20 Vdc Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-12
Inputs from MN-Sx MicroNet Sensor . . . . . . . . . . . . . . . . . . . . A-12
Velocity Pressure Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-13
Communication Circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-14
Intermixing of Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-14
Sensor Link (S-Link) Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . A-15
MicroNet MS/TP Network Wiring . . . . . . . . . . . . . . . . . . . . . . . A-15
ADI Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-16
Ethernet Network Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-16
MicroNet MS/TP Network Wiring . . . . . . . . . . . . . . . . . . . . . . . . . A-16
Cable Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-17
Approved Cable Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-17
Signaling Line Circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-18
ADI Wiring Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-18
I/O Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-19
Intermixing of Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-19
Universal Inputs (UI), Universal Outputs (UO), and Digital Inputs (DI)
A-19
Power Supply Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-20
Appendix B Approved Part Numbers
Controllers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-1
Final Assemblies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-1
Subassemblies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-1
Transformers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-2
Final Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-2
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-3
Subassemblies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-3
Enclosures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-3
Third Party UUKL Listed Products . . . . . . . . . . . . . . . . . . . . . . . . . . . B-4
Appendix C Applicable Documentation
Installation Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-1
Manuals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-2
Release Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-2
vi I/A Series MicroNet BACnet Smoke Control Manual
Page 9
Table of Contents
Appendix D
References
Other Reference Publications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D-1
I/A Series MicroNet BACnet Smoke Control Manual vii
Page 10
Table of Contents
viii I/A Series MicroNet BACnet Smoke Control Manual
Page 11

Preface

Preface

Purpose of this Manual

This manual is intended for use by qualified, authorized engineers and technicians who are responsible for meeting a UL 864 UUKL/UUKL7 project specification. The specification, created by the smoke-control system designer, should have already considered the selected mechanical equipment design. Proper duct sizing and layout, motor/blower selection, and damper selection must be completed by the smoke-control system designer to provide the planned smoke-control pressurization under all possible expected environmental (wind, weather, etc.) and building (door, elevator hoistway, leakage, system response, stairwell, occupied mode, etc.) conditions.
Note:
UUKL7, which is referred to throughout this manual, is the Category Code
Number (CCN) for smoke-control system equipment certified for use in Canada.
Throughout this manual, all references to UUKL are intended to refer to
UUKL7 also (i.e. UUKL/UUKL7).
Throughout this manual, all references to the MNB-V1 equally apply to the
MNB-V1-2 and all references to the MNB-V2 equally apply to the MNB-V2-2.
This manual’s purpose is to provide the fundamentals for the controls engineer and technicians to meet a properly designed smoke-control specification. General topologies, specific requirements, and exceptions to our published literature that are required by Underwriters Laboratories, Inc. for UL 864 UUKL/UUKL7 are provided. This manual does not provide guidelines for mechanical system selection and design. Recognized smoke pressurization program models are available for this purpose.This manual also does not cover all installation and wiring requirements for TAC I/A Series be used along with the I/A Series MicroNet BACnet Wiring, Networking, and Best Practices Guide, F-27360, and applicable I/A Series BACnet controller installation instructions.
®
MicroNet™ BACnet™ controllers. It must
F-27419-2 TAC I/A Series MicroNet BACnet Smoke Control Systems Manual ix
Page 12

Abbreviations Used in this Manual

ADA Americans for Disabilities Act
ADI Automation Displays, Inc.
AHJ Authority Having Jurisdiction
AHU Air Handling Unit
AI Analog Input
CCN Category Code Number (UL)
CFM Cubic Feet per Minute
DI Digital Input
DO Digital Output
EOL End of Line (Termination)
EOL JPR End-of-Line Jumper (EOL resistor and/or bias
resistor engaged through on-board jumper)
FAP Fire Alarm Panel
FSCS Firefighter’s Smoke Control Station
HVAC Heating-Ventilating-Air Conditioning
I/O Input/Output
IP Internet Protocol
ITE Information Technology Equipment
JPR Jumper
LAN Local Area Network
LED Light Emitting Diode
NEC National Electrical Code
NFPA National Fire Protection Association
N.O. Normally Open
NW Network
O.A. Outside Air
UI Universal Input
UL Underwriters Laboratories, Inc.
VAV Variable Air Volume
WP Tech WorkPlace Tech Tool
x TAC I/A Series MicroNet BACnet Smoke Control Systems Manual F-27419-2
Page 13

Definitions BACnet

The following are definitions of terms related to BACnet.
Instance A device’s instance number, also known as its
Smoke Control
The following definitions of terms related to smoke control are found in NFPA 92A, Recommended Practice for Smoke-Control Systems.
Area of Refuge An area of the building separated from other
Preface
BACnet Device Object Identifier.
spaces by fire-rated smoke barriers in which a tenable environment is maintained for the period of time that such areas may need to be occupied at time of fire.
Authority Having Jurisdiction
End Process Verification A method that provides positive confirmation
Firefighter’s Smoke Control Station
Positive/Negative Pressurization
Smoke Barrier A continuous membrane, either vertical or
The organization, office, or individual responsible for approving equipment, materials, an installation, or a procedure.
that the desired result (i.e.airflow, damper position, etc.) has been achieved when a controlled device has been activated, such as during smoke control, testing, or manual override operations, where failure or cessation of such positive confirmation results in an off-normal indication.
A system that provides graphical monitoring and manual overriding capability over smoke-control systems and equipment at designated location(s) within the building for the use of the fire department.
The desired pressure difference between the protected space and an adjacent space measured at the boundary of the protected space under a specified set of conditions with the smoke-control system operating.
horizontal, such as a wall, floor, or ceiling assembly, that is designed and constructed to restrict the movement of smoke.
Smoke Control Mode A predefined operational configuration of a
system or device for the purpose of smoke control.
Smoke-Control System An engineered system that uses mechanical
fans to produce pressure differences across smoke barriers to inhibit smoke movement.
F-27419-2 TAC I/A Series MicroNet BACnet Smoke Control Systems Manual xi
Page 14
Smoke Control Zone A space within a building enclosed by smoke
barriers, including the top and bottom, that is part of a zoned smoke-control system.
Smoke Exhaust System A mechanical or gravity system intended to
move smoke from the smoke zone to the exterior of the building, including smoke removal, purging, and venting systems, as well as the function of exhaust fans utilized to reduce the pressure in a smoke zone.
Smoke Zone The smoke-control zone in which the fire is
located.

Applicable Standards

Stairwell Pressurization System
Tenable Environment An environment in which smoke and heat is
Zoned Smoke-Control System
This manual should be used in conjunction with the following standards which apply to the Schneider Electric UL 864, 9th ed. Listing.
Underwriters Laboratories (UL) Standards
A type of smoke-control system in which stair shafts are mechanically pressurizaed, with respect to the fire area, with outdoor air to keep smoke from contaminating them during a fire event.
limited or otherwise restricted to maintain the impact on occupants to a level that is not life threatening.
A smoke-control system that includes smoke exhaust for the smoke zone and pressurization for all contiguous smoke-control zones.
UL 864, 9th ed. (2003) Control Units for Fire Protective Signaling
Systems
UUKL Smoke-Control System Equipment (Category under UL 864)
CAN/ULC-S527-99 Standard For Control Units For Fire Alarm Systems
ULC/ORD-C100-92 Smoke Control System Equipment
UUKL7 Category for Smoke-Control System Equipment Certified for
Use in Canada
National Fire Protection Association (NFPA) Standards
NFPA 70 National Electrical Code
NFPA 72 National Fire Alarm Code, 2007 Edition
This standard covers the application, installation, performance, and maintenance of protective signaling systems and their components.
NFPA 92A Standard for Smoke-Control Systems Utilizing Barriers and
Pressure Differences, 2009 Edition
This standard covers the design, installation, testing, operation, and maintenance of new and retrofitted mechanical air conditioning and ven-
xii TAC I/A Series MicroNet BACnet Smoke Control Systems Manual F-27419-2
Page 15
Preface
tilation systems for the purpose of controlling smoke.
NFPA 92B Standard for Smoke Management Systems in Malls, Atria,
and Large Areas, 2005 Edition
This standard provides technical data relevant to the design, installation, testing, operation, and maintenance of new and retrofitted smoke man­agement systems. It is intended for buildings having large volume spaces, for the management of smoke within the space where the fire exists, or between spaces not separated by smoke barriers.
Other Standards
Canadian Electrical Code, Part 1

Conventions Used in this Manual

The following conventions apply to this printed manual:
Menu commands appear in bold.
Example — On the Special menu, point to Security, then click Log On.
Italics is used for emphasis in a statement, such as:
If maximum closed switch voltage is not more than 1.0 V and minimum open switch voltage is at least 4.5 V, then solid state switches may be used for a UI or a DI.
It is also used when referring to a document, such as:
Refer to the WorkPlace Tech Tool 5.x Engineering Guide Supplement, F-27356.
Acrobat (PDF) Conventions
If you are reading this manual online in Adobe numerous hypertext links exist, both in normal black text and in blue text.
®
Acrobat® (.PDF file format),
Hypertext links in this document include all entries in the Table of

Contents, as well as cross-references within the body text. For ease of recognition, cross-reference links within the body text appear in blue type, for example Manual Summary. A link is indicated whenever the mouse pointer changes to a hand with a pointing finger.

When viewing this guide with Adobe Acrobat, you can display various
“bookmark” links on the left side of your screen by choosing “Bookmarks and Page” from the “View” menu. As with the links described above, these “bookmark” links will also cause the mouse pointer to change to a hand with a pointing finger.
Manual Summary This manual contains five chapters and two appendices.
Chapter 1 - Introduction
This chapter explains the UL 864 UUKL/UUKL7 Listing and defines various terms related to Smoke-Control Systems.
Chapter 2 - High-rise Smoke Control
This chapter provides application guidelines for using I/A Series MicroNet BACnet controllers in a five-floor, high-rise office building that requires the UL 864 UUKL/UUKL7 Listing for Smoke-Control Systems.
F-27419-2 TAC I/A Series MicroNet BACnet Smoke Control Systems Manual xiii
Page 16
Chapter 3- Warehouse Smoke Control
This chapter provides application guidelines for using I/A Series MicroNet BACnet controllers in a single-story warehouse building that requires the UL 864 UUKL/UUKL7 Listing for Smoke-Control Systems.
Chapter 4 - Campus Smoke Control
This chapter provides application guidelines for using I/A Series MicroNet BACnet controllers in a large campus with multiple buildings that require the UL 864 UUKL/UUKL7 Listing for Smoke-Control Systems.
Chapter 5 - Restrictions and General Comments
This chapter lists any restrictions associated with the application of I/A Series MicroNet BACnet controllers to UL 864 UUKL/UUKL7 Smoke-Control Systems. This chapter also includes general comments that may provide additional insight or flexibility during the engineering process.
Appendix A - Additional Information
Appendix A presents additional information related to the wiring of an I/A Series MicroNet BACnet Smoke-Control System.
Appendix B - Approved Part Numbers
Appendix B lists the part numbers of all I/A Series MicroNet BACnet equipment that have been UL 864 UUKL/UUKL7 listed.
Appendix C - Applicable Documentation
Appendix C lists, by F-number, applicable documentation that is required to install, apply, engineer, operate, and troubleshoot I/A Series MicroNet BACnet and related equipment.
Appendix D - References
Appendix D lists additional reference documents that are relevant to the design of Smoke-Control Systems.
xiv TAC I/A Series MicroNet BACnet Smoke Control Systems Manual F-27419-2
Page 17
Chapter 1 Introduction
Schneider Electric has worked with Underwriters Laboratories, Inc. to gain the UL 864 UUKL/UUKL7 listing. This UL listing involves testing both hardware and software for reliability by Underwriters Laboratories, Inc. as it pertains to this standard and sub-category.

What is the UL 864 UUKL/UUKL7 Listing?

According to Underwriters Laboratories, the UL 864 UUKL/UUKL7 is a category that has been established for Smoke-Control System Equipment. “The products covered by this category are intended to be installed in conjunction with heating-ventilating-air conditioning (HVAC) equipment to form a system for controlling the flow of smoke in a building during a fire condition in accordance with Smoke-Control Systems, NFPA 92A or 92B.” Additionally, according to Underwriters Laboratories (UL), smoke-control equipment is assigned one or more of the following attributes:
Note: Schneider Electric is listed for all of the following UUKL attributes.
1
1. Operation
Manual—Activation of the smoke-control system occurs as a result of the intervention of an authorized person. Automatic—Activation of the smoke-control system occurs as a result of an alarm condition from a fire detection device, such as a smoke detec­tor or heat detector, or fire alarm control unit.
2. Type
Nondedicated—A system which provides the building HVAC function under normal conditions and provides a smoke-control objective during a fire alarm condition. Dedicated—A system which is normally inactive and is used exclusively for the purpose of smoke control.
3. Use
Stairwell—Configuration of equipment which provides pressurizing of stairwells for the purpose of maintaining a tenable environment for build­ing egress.
1. Underwriters Laboratories, Heating, Cooling, Ventilating, Cooking and Food Safety
Equipment Directory 2006.
F-27419-2 TAC I/A Series MicroNet BACnet Smoke Control Systems Manual 1
Page 18
Chapter 1
Zoned Smoke Control—A configuration which provides the exhausting of the smoke area and pressurizing all of the other contiguous areas of the build-
2
ing.”
The design of an overall smoke-control system is a complete system engineered to the particular installation. The interconnection of the smoke-control equipment to the HVAC equipment, and to other system equipment, is intended to be in accordance with a specific installation diagram that is generated by either the smoke-control equipment listee or by another responsible party.
In practice, Schneider Electric, as a UL Smoke Control Equipment Listee, and its associated field offices do not design the smoke-control system. Rather, the Schneider Electric field office works closely with the smoke-control system designer to develop the interface between the controls and equipment supplied by Schneider Electric and the mechanical equipment that provides smoke-control pressurization. The Schneider Electric field office then generates the control system installation diagrams based on the total smoke-control system design.

What Was Required to Gain the UL 864 UUKL/UUKL7 Listing?

UL 864 UUKL/UUKL7 testing has two basic elements: hardware and software. Each element was reviewed and tested to meet the UL 864 UUKL/UUKL7 acceptance criteria.

Hardware The hardware has been designed to meet UL 864 transient testing requirements

on all communications and input/output points. This includes EIA-485 (formerly RS-485) ports, Ethernet ports, power, and all I/O points. The result of these modifications has been to protect the I/A Series BACnet products against high level transients and further reduce the susceptibility of the I/A Series BACnet controllers to static electricity and lightning. This does not mean that lightning protection is not required. In fact, lightning protection is still required whenever communication lines enter or leave a building.

Software A systems level application was created, documented, and tested to prove

I/A Series BACnet controllers could perform a smoke-control sequence within the guidelines of UL 864 UUKL/UUKL7 and NFPA 92A. This systems level application used a representative selection of I/A Series BACnet hardware. Three additional systems applications were created to provide a guideline for applying I/A Series BACnet controllers to generic smoke-control situations. These applications are briefly explained here and detailed in Chapters 2 through 4.
High-rise Smoke Control Using MNB-300, MNB-Vx, and MNB-1000
Controllers
Detailed in Chapter 2, this application provides guidelines for using I/A Series BACnet controllers in a five-floor, high-rise office building that requires the UL 864 UUKL/UUKL7 listing for Smoke-Control Systems. This application performs the smoke-control sequences by controlling stairwell pressurization
2. Underwriters Laboratories, Heating, Cooling, Ventilating, Cooking and Food Safety
Equipment Directory 2006.
TAC I/A Series MicroNet BACnet Smoke Control Systems Manual F-27419-2
2
Page 19
Introduction
systems, terminal boxes, dedicated smoke-control dampers, and central air handling unit (AHU) systems. The normally open (N.O.) relay contacts of a UOJZ fire alarm panel are monitored for smoke/fire alarm signals which ini­tiate automatic activation of the smoke-control sequences. The UUKL listed Firefighter’s Smoke Control Station (FSCS) is monitored for manual activation and overrides. Control of the FSCS visual and audible status indicators is also provided.
Warehouse Smoke Control Using MNB-300 and MNB-1000 Controllers
Detailed in Chapter 3, this application provides guidelines for using I/A Series BACnet controllers in a single-story warehouse building that requires the UL 864 UUKL/UUKL7 listing for Smoke-Control Systems. This application performs the smoke-control sequences by controlling several zoned AHU sys­tems. The N.O. relay contacts of a UOJZ fire alarm panel are monitored for smoke/fire alarm signals which initiate automatic activation of the smoke-con­trol sequences. The UUKL listed Firefighter’s Smoke Control Station (FSCS) is monitored for manual activation and overrides. Control of the FSCS visual and audible status indicators is also provided.
Campus Smoke Control Using MNB-300, MNB-Vx, and MNB-1000
Controllers
Detailed in Chapter 4, this application provides guidelines for using I/A Series BACnet controllers in a large campus with multiple buildings that require the UL 864 UUKL/UUKL7 listing for Smoke-Control Systems. This application performs the smoke-control sequences by controlling terminal boxes, dedi­cated smoke-control dampers, and several AHU systems. The N.O. relay contacts of a UOJZ fire alarm panel are monitored for smoke/fire alarm sig­nals which initiate automatic activation of the smoke-control sequences. The UUKL listed Firefighter’s Smoke Control Station (FSCS) is monitored for man­ual activation and overrides. Control of the FSCS visual and audible status indicators is also provided. Multiple Fire Alarm Panels and FSCSs are used.

What are Your UL 864 UUKL/UUKL7 Responsibilities?

Schneider Electric field offices can now contract for smoke-control systems that require the UL 864 UUKL/UUKL7 listing for a BACnet system. The I/A Series BACnet system, however, is not the system that initiates or annunciates the smoke/fire alarm. That is the responsibility of the primary system, a dedicated fire alarm system that is listed for the UOJZ category of the UL 864 standard. The primary system provides the means for detecting, indicating, and annunciating the smoke/fire alarm. I/A Series BACnet controllers interface to the primary fire alarm system to monitor the smoke/fire alarm panel output contacts and subsequently control the HVAC equipment, as required, in the event of a fire/smoke condition. In addition, the automation system may redundantly (as a secondary system) annunciate fire/smoke alarms.
The applications produced and the guidelines provided by Schneider Electric in the I/A Series Micronet BACnet Smoke-Control Systems Manual are intended as a reference. They must be reviewed and revised to fit the individual installation and the project’s specifications. It is the individual field office’s responsibility to ensure that the I/A Series BACnet system meets the requirements of the project’s
F-27419-2 TAC I/A Series MicroNet BACnet Smoke Control Systems Manual 3
Page 20
Chapter 1
specifications, but not necessarily to perform the system’s mechanical design function. The smoke-control system designer should have already completed the mechanical system design, and validated the design’s concept using a proven smoke-control system program model.
Proper duct sizing and layout, motor/blower selection, and damper selection must be completed by the smoke-control system designer to provide the planned smoke-control pressurization under all possible expected environmental (wind, weather, etc.) and building (door, elevator hoistway, leakage, system response, stairwell, occupied mode, etc.) conditions. Adjacent corridors and zones should have been considered by the smoke-control system designer because they have a direct impact on pressurization.
The smoke-control system designer should also specify the required controls sequence, and realizing that there are reaction and confirmation times for HVAC controls, specify any critical response times that are necessary to meet the requirements of the smoke-control system design.
Each field office is responsible for the implementation of the smoke-control sequence as specified by the smoke-control system designer. Additionally, it is the responsibility of the field office to work with the smoke-control system designer and gain the smoke-control system approval from the Authority Having Jurisdiction (AHJ) — and there could be several. I/A Series BACnet equipment installation must be in strict adherence to the appropriate UL, NFPA, and local authority requirements. The field office is responsible for following the installation standards and guidelines set forth by Schneider Electric in this document and as approved by UL.

Explanation of Smoke-Control Systems

This documentation is intended to be used in conjunction with the NFPA 92A and UL 864 UUKL/UUKL7 standards. The explanation of smoke-control systems here consists of highlights from these standards.

Building Pressurization

Dedicated and Nondedicated Systems

The primary means of controlling smoke movement is by creating air pressure differences between smoke-control zones. The basic concept of building pressurization is to establish a higher pressure in adjacent spaces than in the smoke zone. In this way, air moves into the smoke zone from the adjacent areas and smoke is prevented from dispersing throughout the building.
Smoke control systems are either dedicated or nondedicated. A dedicated smoke-control system is intended for smoke-control purposes only. It is a separate system of air moving and distribution equipment that does not function under normal building operating conditions. When activated, this type of system performs a specific smoke-control function. smoke-control systems are stairwell pressurization fans and exhaust dampers that operate only when in a smoke-control situation.
3. National Fire Protection Association, Inc., NFPA 92A, Standard for Smoke-Control Systems Utilizing Barriers and Pressure Differences, 2009 ed., chap. 1, para. 1.2.1.
4. NFPA 92A, 2009 ed., chap 3, para. 3.3.11.1, 3.3.11.2..
4
Examples of dedicated
3
TAC I/A Series MicroNet BACnet Smoke Control Systems Manual F-27419-2
4
Page 21
Introduction
Nondedicated smoke-control systems are systems that share components with some other systems such as the building automation (HVAC) system. When activated, the system changes its mode of operation to achieve the smoke-control objectives. building that supplies several smoke-control zones. Under normal HVAC operation, the central air handler modulates the outdoor, exhaust, and return air dampers to maintain a desired discharge temperature. When a smoke-control sequence is initiated, the control objective changes from maintaining a desired discharge temperature to a smoke-control sequence that drives the outdoor and exhaust air dampers fully open and the return air damper fully closed to provide the maximum amount of outdoor air.
5
An example of this type of system is the central air handler for a

Basic System Types

Building smoke-control systems can generally be divided into two basic types: shaft protection and floor protection. Shaft protection consists of stairwell pressurization systems and elevator hoistway systems. Floor protection involves several variations of zoned smoke control. Use of a particular system or combination of systems is dependent on building and fire code requirements, as well as specific occupancy and life safety requirements of the situation being considered.
Note: Recent trends have indicated areas of refuge are being designed into many buildings as dictated by the Americans for Disabilities Act (ADA). Specifications may refer to these areas of refuge which are typically located adjacent to stairwells or elevator hoistways. These refuge zones may require special pressure compensated systems in order to maintain a tenable environment. The requirements for these systems must be dictated by the building’s smoke-control system designer based on the smoke-control system design and its associated sequence of operation. When these types of zones are encountered, additional time and resources may be required to establish and verify compliance to the specification. These areas of refuge are not part of the UUKL listing requirements.
Shaft Protection
Stairwell Pressurization Systems
The goal of pressurized stairwells is to maintain “a tenable environment within exit stairwells for the time necessary to allow occupants to exit the building.”
6
A tenable environment is defined as “An environment in which the products of combustion, including toxic gases, particulates, and heat, are limited or otherwise restricted to maintain the impact on occupants to a level that is not life threatening.” staging area for firefighters. pressurized, with respect to the fire area, with outdoor air to keep smoke from contaminating them during a fire incident.”
5. NFPA 92A, 2009 ed., chap 3, para. 3.3.11.2.
6. NFPA 92A, 2009 ed., chap. 4, para. 4.1.2 (2), annex A, para. A.8.1.
7. NFPA 92A, 2009 ed., chap. 4, para 4.1.2 (2).
8. NFPA 92A, 2009 ed., annex A, para A.4.1.2 (1).
9. NFPA 92A, 2009 ed., chap 3, para 3.3.6..
7
A secondary objective of stairwell pressurization is to provide a
8
This is achieved when “stair shafts are mechanically
9
F-27419-2 TAC I/A Series MicroNet BACnet Smoke Control Systems Manual 5
Page 22
Chapter 1
There are two types of stairwell systems: noncompensated and compensated. In a noncompensated system, supply air is provided to the stairwell by starting a fan. This provides two or more positive pressure differentials: one differential with all of the doors closed, a second differential with one door open, and so on.
10
In a compensated system, supply air is also provided to the stairwell by starting a fan, but the fan system adjusts the positive differential pressure based on the various combinations of opened and closed doors. This adjustment may be accomplished by either modulating supply airflows or by relieving excess pressure from the stairwell. motor-operated dampers, an automatically opening stairwell door to the outside at ground level, or an exhaust fan.
11
Typically, over-pressure relief may utilize barometric dampers,
12
Elevator Smoke Control
“Historically, elevator hoistways have proved to be a readily available conduit for the movement of smoke throughout buildings.”
13
Although several methods for correcting this problem have been proposed and investigated, there are no firm recommendations regarding elevator smoke control. Refer to the NFPA 92A and UL 864 UUKL/UUKL7 standards for additional information. Remember, the local AHJ and project specifications may require control beyond that specified in the above standards.
Floor Protection
Zoned Smoke Control
Pressurized stairwells, discussed above, “are intended to control smoke to the extent that they inhibit smoke infiltration into the stairwell. However, in a building with just a pressurized stairwell, smoke can flow through cracks in floors and partitions and through other shafts to threaten life or damage property at locations remote from the fire. The concept of zoned smoke control …is intended to limit this type of smoke movement within a building.”
With zoned smoke control, smoke movement is inhibited by dividing the building “into smoke-control zones, with each zone separated from the others by smoke barriers.” closed. When a fire occurs in one of these smoke-control zones, it is called a smoke zone. by mechanical fans and operating dampers can be used to limit the smoke to the zone in which the fire originated.
15
These smoke barriers can be partitions, floors, or doors that can be
16
In the event of a fire, pressure differences and airflows produced
17
When a fire/smoke condition occurs, all of the nonsmoke zones that are contiguous to the smoke zone are positively pressurized and the smoke zone is negatively pressurized. Optionally, all of the remaining smoke-control zones in the building may also be positively pressurized.
18
With the smoke contained to the smoke zone, it can then be
14
10.NFPA 92A, 2009 ed., annex B, para. B.1.
11.NFPA 92A, 2009 ed., annex B, para. B.2.
12.NFPA 92A, 2009 ed., annex B, para. B.4.
13.NFPA 92A, 2009 ed., annex A, para. A.5.4.
14.NFPA 92A, 2009 ed., annex A, para. A.5.5, annex A, para. A.8.1.
15.NFPA 92A, 2009 ed., chap. 5, para. 5.5.1.1.
16.NFPA 92A, 2009 ed., chap. 3 para. 3.3.15.
17.NFPA 92A, 2009 ed., annex A, para. A.5.5.
18.NFPA 92A, 2009 ed., annex A, para. A.5.5.1.1.1.
TAC I/A Series MicroNet BACnet Smoke Control Systems Manual F-27419-2
6
Page 23
Introduction
exhausted. Typically, the fire/smoke signals from a protective signaling system (UOJZ, a UL 864 Listed Fire Alarm Control Unit; i.e. fire alarm panel) are used to activate the zoned smoke-control sequence.
19

HVAC Equipment HVAC equipment normally provides a means of supplying, returning and

exhausting air to, or from, a space. Most HVAC equipment “can be adapted to provide the necessary logic and control sequences to configure HVAC systems for smoke control.” ducts are interconnected as part of the normal HVAC operation, smoke dampers are needed to separate the supply and exhaust air during a smoke-control sequence (return air damper). use centralized HVAC equipment in main mechanical areas to serve multiple floors or zones. These central systems may require fire and smoke shaft dampering to provide exhaust of the fire floor and pressurization of the adjacent floors with outdoor air. Due to their capacity, central systems should include a means to prohibit excessive pressures within the duct system and prevent rupture, collapse, or other damage.
Typically, fan coil units and water source heat pump units can be excluded from performing smoke-control sequences. However, if these units have the ability to supply outdoor air, any of the units that are within the smoke zone should be shut down so that the zone can be negatively pressurized. induction-type air handling unit is used within a smoke zone, it should be shut down or have its primary air supply closed off.
20
However, when the supply and return air
21
Additionally, some buildings
22
24
23
If an

Smoke-Control System Activation

Some VAV systems bypass supply air to the return air inlet of the fan. In these cases, the bypasses must be closed when the unit is in the smoke-control mode. Additionally, the VAV system fan and terminal unit controls should be configured to supply the maximum amount of outdoor air to pressurize the nonsmoke zones. supplying the smoke zone, the terminal fan should be turned off. “Terminal units serving zones adjacent to the smoke zone can continue to operate.”
25
If a fan-powered terminal unit is
26
“Operating controls of the HVAC system shall be designed or modified to provide the smoke-control mode with the highest priority over all other control modes.”
27
Normally the smoke-control sequences are activated automatically, but in some cases, manual activation may be more appropriate. In either case, “the smoke-control system shall be capable of being manually overridden and manually deactivated.”
28
The automatic smoke-control system “shall be automatically activated in response to signals received from a specific fire detection device or a combination of fire detection devices.”
19.NFPA 92A, 2009 ed., chap. 6, para. 6.4.5.1.1.
20.NFPA 92A, 2009 ed., annex A, para. A.6.4.2.
21.NFPA 92A, 2009 ed., chap. 6, para. 6.2.3.
22.NFPA 92A, 2009 ed., annex C, para. C.3.
23.NFPA 92A, 2009 ed., annex C, para. C.4.
24.NFPA 92A, 2009 ed., annex C, para. C.5.
25.NFPA 92A, 2009 ed., annex C, para. C.7.
26.NFPA 92A, 2009 ed., annex C, para. C.8.
27.NFPA 92A, 2009 ed., chap. 6, para. 6.4.2.
28.NFPA 92A, 2009 ed., chap. 6, para. 6.4.3.3.
29.NFPA 92A, 2009 ed., chap. 6, para. 6.4.3.4.
29
Fire detection devices “include automatic devices such
F-27419-2 TAC I/A Series MicroNet BACnet Smoke Control Systems Manual 7
Page 24
Chapter 1
as smoke detectors, waterflow switches, and heat detectors.”30 Manual fire alarm pull stations should generally not be used to activate automatic smoke-control systems, other than stairwell pressurization systems, because of the likelihood of a person signaling an alarm from a station outside the smoke zone of origin.
31

Response Time Smoke control system activation should be started immediately after

receiving an activation command. A maximum of 10 seconds transmission time is allowed, from the initiation of an activation signal (i.e. fire alarm input), to the time it reaches the MicroNet BACnet smoke control system (i.e. binary input of a MicroNet controller). The smoke-control sequence should activate individual components in the sequence necessary to prevent physical damage to fans, ducts, dampers, and other equipment. The total response time of the individual component starts from the moment the smoke-control command is issued (whether automatic or manual) to the final action. This time is 60 seconds for fan operation at the desired state and 75 seconds for the completion of the damper travel. component fail, the time lapse from the moment the component should have reached its final state and the moment its associated trouble signal annunciates, should not exceed 10 seconds.
33
annunciation of the trouble signal for a fan must occur within 70 seconds of the automatic or manual activation command. The annunciation of the damper trouble signal must occur within 85 seconds of the automatic or manual activation command.
32
Should an individual
This means that the
Firefighter’s Smoke Control Station
The Firefighter's Smoke Control Station (FSCS) “shall provide status indication, fault condition indication, and manual control of all smoke-control system components.” over all smoke-control systems and equipment. “ take precedence over fire suppression, electrical protection, or personnel protection devices.”
34
“The FSCS shall have the highest priority control
36
For more information, refer to the NFPA 92A and
35
“FSCS control shall not
UL 864 UUKL/UUKL7 standards.
The FSCS should contain a building diagram that clearly indicates the type and location of all smoke control equipment, such as fans and dampers.
37
The areas of the building that are affected by the equipment and the actual status of all of the smoke control equipment should be clearly indicated at the FSCS. Status indication should be provided for each fan showing whether it is ON or OFF. Status indication of the full-closed and full-open positions of each smoke control damper should also be shown on the
38
FSCS.
30.NFPA 92A, 2009 ed., annex 6, para. A.6.4.3.4.
31.NFPA 92A, 2009 ed., chap. 6, para’s 6.4.3.5.2 and 6.4.3.5.3, and annex A,
32.Underwriters Laboratories Inc., UL 864, Control Units and Accessories for Fire
33.UL 864, 9th ed., para. 49.2.b
34.NFPA 92A, 2009 ed., chap. 6, para. 6.4.3.7.3.
35.NFPA 92A, 2009 ed., chap. 6, para. 6.4.3.7.11.
36.NFPA 92A, 2009 ed., chap. 6, para. 6.4.3.7.14, and UL 864, 9th ed., para. 48.3.
37.NFPA 92A, 2009 ed., chap. 6, para 6.4.3.7.10 and annex D, para D.1 (2).
Proof of air flow should be used to determine the fan status. Proof
para’s A.6.4.3.5.2 and A.6.4.3.5.3.
Alarm Systems, 9th ed. (2003), para. 49.2.c.
TAC I/A Series MicroNet BACnet Smoke Control Systems Manual F-27419-2
8
Page 25
Introduction
of damper positions should be done using end process verification. This may be done through the use of damper degree-of-opening switches, flow stations, etc.
Whenever the communications fails between any of the I/A Series MicroNet BACnet controllers that are integral to the smoke-control equipment or sequences, including instances when a controller loses power, a system trouble visual indicator (i.e. LED) at the FSCS should illuminate and an audible signal must sound. also be generated if any of the smoke-control equipment proof sensors fail to operate within a specified period of time during the smoke-control sequence or when under control of the FSCS. indicators must annunciate an audible sound. In addition to the status indication that is required for all of the smoke-control equipment, each dedicated piece of smoke-control equipment must also provide a visual trouble indicator specifically for that device.
39
The visual and audible trouble indicators must
40
In general, all visual trouble
41

Control Sequence for Stair Pressurization Systems

Control Sequence for Zoned Smoke-Control Systems

Any time a smoke/fire detector trips (refer to NFPA 92A and UL 864 UUKL/UUKL7 for acceptable signaling device types), initiating an automatic smoke-control sequence, all stairwell pressurization fans shall be energized determines that operation of all stairwell pressurization fans is not required to achieve the design objective, only the stairwell pressurizaiton fans identified during the analysis shall be required to be activated.” detector should be provided in the air supply to each fan that stops the respective pressurization fan when smoke is detected. switch for each fan should be provided at the FSCS that allows the stairwell fans to restart after they have been shutdown due to the supply air smoke detectors, entering the fan than smoke migrating into the stairwell. When a stairwell pressurization sequence is used in conjunction with zoned smoke control, care must be taken to prevent the interrelation of the two sequences from adversely affecting each other.
“Automatic activation of systems and equipment for zoned smoke control should have the highest priority over all other sources of automatic control within the building.” used for normal building control such as HVAC systems, the equipment control should be pre-empted as required by the smoke-control sequence. “The following controls should not be automatically overridden:
42
, with one exception. “Where an engineering analysis
43
A smoke
44
A manual override
45
should it be determined that a lessor hazard exists from smoke
46
47
For example, when the smoke-control equipment is
Static pressure high limits.
38.NFPA 92A, 2009 ed., chap 6, para’s 6.4.3.7.3 through 6.4.3.7.10, and annex D,
para D.1 (5).
39.UL 864, 9th ed., para’s 48.5, 49.4, 49.6, and 49.7.
40.UL 864, 9th ed., para’s 48.5 and 49.6.
41.NFPA 92A, 2009 ed., chap 6, para’s 6.4.3.7.3 and UL 864, 9th ed., para 49.6.
42.NFPA 92A, 2009 ed., chap 6, para 6.4.4.1.
43.NFPA 92A, 2009 ed., chap 6, para 6.4.4.1.1.
44.NFPA 92A, 2009 ed., chap 6, para’s 6.4.4.2.1 and 6.4.4.2.2.
45.NFPA 92A, 2009 ed., chap 6, para 6.4.4.4.
46.NFPA 92A, 2009 ed., annex A, para. A.5.7.
47.NFPA 92A, 2009 ed., chap. 6, para. 6.4.5.2.1.
F-27419-2 TAC I/A Series MicroNet BACnet Smoke Control Systems Manual 9
Page 26
Chapter 1
Duct smoke detectors on supply air systems.”
Manual activation or deactivation of zoned smoke-control systems and equipment (at the FSCS) should take priority over automatic activation, as well as take priority over all other sources of automatic control within the building. controls provided specifically for this purpose should be clearly marked as to the zone and function served (typically part of the FSCS).
Any time a smoke/fire detector trips initiating an automatic smoke-control sequence, all stairwell pressurization sequences should operate as stated previously. several smoke-control zones, the supply and return fan for the AHUs are commanded ON. The outdoor and exhaust air dampers for each AHU drive to the full-open position and the return air damper drives to the full-closed position. All exhaust air dampers in the smoke zone drive to the full-open position and the supply air dampers drive to the full-closed position. All smoke-control zones contiguous to the smoke zone (and optionally all remaining smoke-control zones their exhaust air dampers driven to the full-closed position. Pressurization of the non-contiguous (optional) smoke-control zones is dependent upon the smoke-control system design and its associated specification. Regardless of whether or not non contiguous zones are positively pressurized, sufficient differential pressure must be achieved to limit the smoke spread to the zone in which the fire originated.
This smoke-control sequence provides the maximum amount of outdoor air to the nonsmoke zones causing them to be positively pressurized. Since the exhaust air dampers are fully open in the smoke zone and no supply air is being provided, the AHU begins exhausting the smoke from the smoke zone. With the nonsmoke zones being positively pressurized in this manner, smoke is inhibited from migrating outside of the smoke zone.
51
For applications where each central air handling unit (AHU) supplies
52
) should have their supply air dampers driven to the full-open position and
48
50
49
Manual

Automatic Response To Multiple Signals

Maintaining System Integrity

TAC I/A Series MicroNet BACnet Smoke Control Systems Manual F-27419-2
10
Once an automatic activation has occurred, subsequent alarm signals that would normally result in the automatic actuation of a smoke-control sequence should be annunciated only. No fans or dampers should be actuated in response to any subsequent automatic alarm signal in order to avoid the possibility of defeating any smoke-control sequence which is in process.
A prime concern with any emergency signaling system is maintaining system integrity. This is typically accomplished by electrical supervision of wiring, however, since the proper operation of the fans and dampers associated with a smoke-control system may involve mechanically and pneumatically operated devices, as well as electrically operated devices, end-process verification is considered an acceptable alternative.
Smoke control system equipment is required to verify that a fan or damper has achieved its required end function. This end function verification consists of monitoring fans by differential pressure switches, flow stations, and etc., and
48.NFPA 92A, 2009 ed., chap. 6, para. 6.4.5.2.1.2.
49.NFPA 92A, 2009 ed., chap. 6, para. 6.4.5.2.2.
50.NFPA 92A, 2009 ed., chap. 6, para. 6.4.5.2.4.1.
51.NFPA 92A, 2009 ed., chap 6, para’s 6.4.4.1 and 6.4.4.1.1.
52.NFPA 92A, 2009 ed., annex A, para. A.5.5.1.1.1.
Page 27
Introduction
monitoring dampers by degree-of-opening switches, differential pressure switches, and etc. These verification devices should be connected back to the smoke-control system equipment (I/A Series BACnet, for example) and the system programmed to expect the appropriate signal within the specified amount of time.
Any change in a smoke-control signal input (i.e. FAP, FSCS, etc) must be received into the smoke-control system in 10 seconds or less. Fans and dampers have 60 and 75 seconds, respectively, from the time the signal input is received, to successfully respond to smoke-control sequence commands. If a fan or damper fails to achieve its desired state within the times referenced above, the failures have to be annunciated within an additional 10 seconds. Other trouble signals, such as communication failures (supervised through software), have up to 200 seconds to annunciate their failures.
Annunciation of the end function sensor is not required if the proof sensor operates as intended, but if the proof sensor fails to operate, an audible and visual trouble signal must be generated at the FSCS. This would be typical of the operation of the smoke-control system during an emergency condition.
For operation during a nonemergency condition, the means for verifying system integrity varies based on whether the smoke-control system is a dedicated or nondedicated system. Nondedicated smoke-control systems and equipment consist of HVAC components within a building which are operated regularly. Therefore, the normal “comfort” level associated with the operability or inoperability of the equipment is considered an acceptable means of maintaining system integrity.
53
54
55

Smoke-Control System Schedule

Dedicated smoke-control systems and equipment are used solely for the purpose of smoke-control and are not operated in a nonemergency condition. Dedicated system equipment is therefore required to incorporate an automatic weekly self-test of each smoke-control function. The self-test consists of the smoke-control system automatically commanding the associated function to operate and expecting that the associated proof sensor operates within a specified period of time (refer to response times noted earlier). A valid proof sensor operation is not required to annunciate, however, the lack of an expected proof sensor operation must produce an audible trouble signal, as well as indicate the specific device that did not operate (for example, LED at the FSCS).
Each different smoke-control system configuration/sequence should be defined in a schedule, typically a matrix chart. The schedule should list all dedicated and nondedicated smoke-control equipment and show the equipment response for each sensor that activates an automatic sequence. At a minimum, the schedule should include the following information:
Each smoke zone in which a smoke-control system automatically
activates.
53.NFPA 92A, 2009 ed., chap. 6, para. 6.4.6. and annex A, para. A.6.4.6.
54.UL 864, 9th ed., para. 36.1.2 (c), 49.2 (b).
55.NFPA 92A, 2009 ed., chap. 2, para. 2.1.2. and 2.1.5., and UL 864, 9th ed.,
para’s 49.7.
F-27419-2 TAC I/A Series MicroNet BACnet Smoke Control Systems Manual 11
Page 28
Chapter 1
The type of alarm signal that activates the smoke-control system (smoke
detector, sprinkler water flow, and etc.)
The smoke zones where maximum mechanical exhaust to the outside is
implemented and no supply air is provided.
The positively pressurized smoke-control zones where maximum supply air is
implemented and no exhaust to the outside is provided.
The fans that are ON as required to implement the smoke-control system.
Multiple-speed fans should be further noted as FAST or MAX VOLUME to ensure that the intended control configuration is achieved.
The fans that are OFF as required to implement the smoke-control system.
The dampers that are Open where maximum air flow must be achieved.
The dampers that are Closed where no air flow should take place.
Any additional functions that may be required to achieve the smoke-control
objective or that may be desirable in addition to smoke control. Changes or override of normal static pressure control setpoints should also be indicated if applicable.
Damper position at fan failure.
56

Conclusion

When applying I/A Series BACnet controllers to smoke-control sequences, review this introductory information along with the NFPA 92A and UL 864 UUKL/UUKL7 standards. This information should be used in conjunction with the sample smoke-control applications (Chapters 2 through 4) and the restrictions and general comments (Chapter 5) that are part of the total smoke-control documentation provided by Schneider Electric.
56.NFPA 92A, 2009 ed., annex A, para 6.4.5.3 (10).
TAC I/A Series MicroNet BACnet Smoke Control Systems Manual F-27419-2
12
Page 29
Chapter 2 High-rise Smoke Control

Purpose

This application provides guidelines for using I/A Series MicroNet BACnet controllers in a five-floor, high-rise office building (Figure–2.1) that requires the UL 864 UUKL/UUKL7 listing for Smoke-Control Systems. This application uses MNB-300, MNB-Vx, and MNB-1000 controllers that perform HVAC functions when in the normal control mode. When in the smoke-control mode, they perform the required smoke-control sequences by controlling the stairwell pressurization fans, the individual terminal boxes, the dedicated smoke-control dampers, and the central air handling unit (AHU) fans. Additionally, they control all supply, exhaust, and return air dampers, and provide the feedback of all end-process verification required.
The I/A Series BACnet controllers monitor N.O. relay contacts of a UOJZ listed fire alarm panel for automatic activation of the smoke-control sequences and monitor a UL 864 UUKL/UUKL7 Listed Firefighter’s Smoke Control Station (FSCS) for manual activation commands and overrides. In this example, an ADI FSCS is used, which supports the ADI ModBus interface to the MNB-1000. This interface provides control over all the FSCS visual and audible status indicators, as well as receipt of the FSCS override commands, thus eliminating the need to allocate additional controllers to interface to the FSCS through individual I/O points.

Sequence of Operation

Normal HVAC Control

F-27419-2 TAC I/A Series MicroNet BACnet Smoke Control Systems Manual 13
Under normal conditions, the central AHU follows an occupied schedule that determines when the AHU operates. During the unoccupied mode, the outdoor and exhaust air dampers are in the full-closed position. The return air damper is in the full-open position. The supply and return fans are commanded OFF. During the occupied mode, the supply and return fans are commanded ON. The outdoor, exhaust, and return air dampers modulate as required to maintain a mixed air temperature setpoint. The central AHU can have a wide variety of additional control sequences that determine its operation and establish its operating priorities (for example, low limit stats and minimum outdoor air).
Page 30
Chapter 2
Figure–2.1 High-rise Building Layout.
Central Air Handling Unit
Exhaust Air Damper
Return Air Damper
Return Air Supply Fan
Exhaust
Air
Damper
Exhaust
Air
Damper
Exhaust
Air
Damper
Eight MNB-Vx Controllers
Eight MNB-Vx Controllers
Eight MNB-Vx Controllers
Outdoor Air Damper
Supply Air Damper
5th Floor
Supply Air Damper
4th Floor
Supply Air Damper
Stairwell #2Stairwell #1
Pull Station
Pull Station
Pressurization Fan - Stair 1
Duct Smoke Detector
SD
3rd Floor
Exhaust
Air
Damper
Exhaust
Air
Damper
Note: All references to the MNB-V1 equally apply to the
MNB-V1-2 and all references to the MNB-V2 equally apply to the MNB-V2-2.
Eight MNB-Vx Controllers
2nd Floor
Eight MNB-Vx Controllers
1st Floor
Supply Air Damper
Supply Air Damper
Pressurization Fan - Stair 1
SD
Duct Smoke Detector
TAC I/A Series MicroNet BACnet Smoke Control Systems Manual F-27419-2
14
Page 31
High-rise Smoke Control
The terminal boxes are controlled by MNB-V1 and MNB-V2 controllers. During normal conditions and in the occupied mode, the terminal boxes maintain their respective zone temperature setpoints by modulating their primary air dampers and staging the electric reheat coils (if present). During the unoccupied mode, the terminal boxes either maintain their respective unoccupied zone temperature setpoints or drive to a fixed position.
In many cases, a dedicated motor-driven damper is required in the common supply air duct that feeds each smoke-control zone. The dampers are required to ensure that the smoke zones can be negatively pressurized (with respect to all contiguous smoke-control zones) within the 75 second response time required by NFPA 92A and UL 864 UUKL/UUKL7. Dedicated supply air dampers and their control are shown in this example to cover worst case MNB-V1 and MNB-V2 applications.The dedicated supply air dampers are controlled by digital output (DO) points from the MNB-Vx controllers associated with their respective zones. The dampers remain in the full-open position at all times, unless commanded otherwise due to a smoke-control related condition.
Note: The UL acceptance of the MNB-V1 and MNB-V2 controllers for UUKL/UUKL7 is based on the assumption that negative pressurization of a smoke zone is considered accomplished when the total CFM flow supplied to the zone drops below 50% of its maximum with its dedicated exhaust damper fully open. If the damper response time is acceptable (less than 75 seconds) under this condition and proper pressurization is achieved, dedicated supply air dampers are not necessary solely to meet response time requirements. In all cases, exhaust and supply air dampers should continue to be driven to their full-open and full-closed positions. The smoke-control system design and its associated specification will dictate whether additional requirements apply to the supply air dampers.
The exhaust air dampers associated with each floor (smoke-control zone) are considered dedicated smoke-control systems, and in this application, are controlled by digital output (DO) points from the MNB-Vx controllers associated with their respective zones. The dampers are always in the full-open position, unless commanded otherwise due to a smoke-control related condition. Typically, these dampers use actuators that spring-return to their “fail-safe” position upon power loss.
The dedicated stairwell pressurization fans are controlled by an MNB-300 controller. The status of each fan is monitored by a flow switch. Since these fans are considered dedicated smoke-control equipment, they are always OFF, unless commanded otherwise due to a smoke-control related condition.
The Fire Alarm Panel (i.e. Listed Fire Alarm Control Unit) is the primary indicator for fire alarm, smoke detector, and pull station conditions. It is also the primary initiator of the automatic smoke/fire alarm sequence. Upon detection of smoke and/or fire, a set of contacts in the Fire Alarm Panel (for the zone affected) close, indicating to the building automation system that a smoke or fire condition exists. In this application, a smoke detector is provided for each floor (smoke-control zone). Smoke detectors are also provided in the supply air for each stairwell
F-27419-2 TAC I/A Series MicroNet BACnet Smoke Control Systems Manual 15
Page 32
Chapter 2
pressurization fan. The contacts from the Fire Alarm Panel for the associated smoke detectors and stairwell pull stations are monitored by MNB-300 controllers.
Note: Any UOJZ listed fire alarm panel with programmable N.O. relay contacts can be used with I/A Series BACnet controllers.
The Automation Displays, Inc. Firefighter’s Smoke Control Station (i.e. Listed Smoke Control Panel) is the primary indicator for the status of all smoke control and related HVAC equipment. It also provides the interface for the manual activation commands and overrides for all smoke-control related equipment. An MNB-1000 controller is mounted internal to the FSCS and provides the ADI ModBus (control) interface to the FSCS. All commands issued from the FSCS are monitored and distributed throughout the network as required to implement the manual smoke-control sequences and overrides. The status of all of the smoke-control systems and equipment, as well as HVAC monitored trouble signals, are returned to the FSCS for visual indication and in some cases audible annunciation. The FSCS MNB-1000 will be the central coordinator of all smoke-control activity.
Note: Currently, only the UUKL Listed FSCS from Automation Displays, Inc. (ADI) supports the ADI ModBus interface. For those applications where the ADI ModBus serial communication interface is used, only the ADI FSCS can be used. Whenever discrete I/O points are used to communicate with the FSCS, any UUKL Listed FSCS can be used. When discrete I/O is used for this purpose, many additional I/A Series controllers will be required to provide the individual I/O point interfaces, and this should be considered when estimating a job.
During normal operating conditions, the nondedicated smoke-control equipment does not require an automatic self-test since this equipment consists of HVAC components that are operated on a regular basis. The normal “comfort” level associated with the operability or inoperability of the equipment is considered an acceptable means of maintaining system integrity.
Dedicated smoke-control equipment, however, is used only when a smoke-control situation occurs, and therefore an automatic weekly self-test of each dedicated smoke-control function is required. In this application, stairwell pressurization fan operation is verified using differential pressure sensors. The MNB-Vx damper position is verified by monitoring the cubic feet per minute (CFM) flow from the terminal box and/or its integral damper position feedback. Damper end switches are used to verify the end stroke of all other motor-driven dampers. If a valid proof of each function occurs, no annunciation needs to take place. Otherwise, if the expected proof sensor does not operate as required, an audible trouble signal is generated and an LED is illuminated at the FSCS indicating the specific device that did not operate.
TAC I/A Series MicroNet BACnet Smoke Control Systems Manual F-27419-2
16
Page 33
High-rise Smoke Control

Smoke Control Sequences

This application uses a combination of smoke-control systems to implement the smoke-control strategy. These systems consist of stairwell pressurization and zoned smoke control.
Anytime a fire alarm pull station is activated, the automatic stairwell pressurization sequence will be initiated. Since multiple pull stations will be present, activation of any station will initiate the sequence for both stairwells. When the automatic sequence is triggered in this manner, it will leave the remainder of the smoke-control system in its normal mode.
Anytime a smoke/fire detector trips, an automatic smoke-control sequence is initiated and both dedicated stairwell pressurization fans are energized. A smoke detector, provided in the air supply to each fan, stops the respective pressurization fan if smoke is detected.
57
A manual override switch (for each fan) provided at the FSCS allows the stairwell pressurization fans to be restarted after they have shutdown due to the air supply smoke detectors,
58
should it be determined that a lessor hazard exists from smoke entering the fan than from smoke migrating into the stairwell. The pressurization of the stairwell restricts the flow of smoke into the stairwell allowing ready evacuation of the smoke zone and providing a staging area for firefighters.
59
Zoned smoke control divides a building into a number of zones for the purpose of inhibiting smoke movement.
60
The zones are separated from each other by smoke barriers. In the event of a fire, pressure differences and airflows produced by mechanical fans and operating dampers are used to limit the smoke to the zone in which the fire originated.
61
In this application, each floor of the high-rise is considered a smoke-control zone. When smoke is detected in any zone, all of the nonsmoke zones that are contiguous to the smoke zone, and optionally, all nonsmoke zones in the building,
62
are positively pressurized and the smoke is
exhausted from the smoke zone. Pressurization of the noncontiguous (optional) smoke-control zones is dependent upon the smoke-control system design and its associated specification. Regardless of whether or not the noncontiguous smoke-control zones are positively pressurized, sufficient differential pressure must be achieved to limit smoke spread to the zone in which the fire originated.
If the smoke/fire detector for Floor 2 trips first, the automatic smoke-control sequence is initiated in the following manner.
1. The central AHU supply and return fans are commanded ON, the return air damper is driven to the full-closed position and the outdoor air and exhaust air dampers are driven to their full-open positions. This allows maximum fresh air to be delivered to the floors above and below the floor reporting the smoke condition. It also allows maximum exhausted air to be expelled from the zone reporting the smoke condition.
2. The dedicated exhaust air dampers for Floors 1, 3, 4, and 5 are driven to the full-closed position while the dedicated exhaust air damper for Floor 2 is driven to the full-open position.
57.National Fire Protection Association, Inc., NFPA 92A, Standard for Smoke-Control Systems Utilizing Barriers and Pressure Differences, NFPA 92A, 2009 ed., chap 6, para. 6.4.4.2.
58.NFPA 92A, 2009 ed., chap 6, para 6.4.4.4.
59.NFPA 92A, 2009 ed., chap. 4, para 4.1.2 (2) and annex A, para. A.4.1.2 (1).
60.NFPA 92A, 2009 ed., chap. 5, para. 5.5.1.1.
61.NFPA 92A, 2009 ed., annex A, para. A.5.5.
62.NFPA 92A, 2009 ed., annex A, para. A.5.5.1.1.1.
F-27419-2 TAC I/A Series MicroNet BACnet Smoke Control Systems Manual 17
Page 34
Chapter 2
3. The dedicated supply air damper for Floor 2 is driven to the full-closed position. The terminal box supply dampers may optionally be driven to the full-closed position also. This causes the smoke zone to become negatively pressurized.
Note: The UL acceptance of the MNB-V1 and MNB-V2 controllers for UUKL is based on the assumption that negative pressurization of a smoke zone is considered accomplished when the total CFM flow supplied to the zone drops below 50% of its maximum with its dedicated exhaust damper fully open. Sufficient differential pressure must be achieved to ensure smoke spread is confined to the zone in which the fire originated. In all cases, exhaust and supply air dampers should continue to be driven to their full-open and full-closed positions.
4. The dedicated supply air dampers for Floors 1, 3, 4, and 5 remain in the full-open position. The respective terminal box supply dampers, which are controlled by MNB-V1 and MNB-V2 controllers, modulate open. The CFM flow supplied to these floors causes them to be positively pressurized. The terminal box supply dampers continue to modulate open until they reach the full-open position.
Note: The UL acceptance of the MNB-V1 and MNB-V2 controllers for UUKL is based on the assumption that negative pressurization of a smoke zone is considered accomplished when the total CFM flow supplied to the zone drops below 50% of its maximum with its dedicated exhaust damper fully open. In all cases, exhaust and supply air dampers should be driven to their full-open and full-closed positions. Sufficient differential pressure must be achieved to ensure smoke spread is confined to the zone in which the fire originated. In all cases, exhaust and supply air dampers should continue to be driven to their full-open and full-closed positions.
5. The automatic smoke-control sequence takes priority over the normal HVAC control sequences and any HVAC control overrides. Static pressure high limits and duct smoke detectors on supply air systems should not be automatically overridden.
63
6. Once the automatic activation occurs, subsequent alarm signals that would normally initiate an automatic smoke-control sequence annunciate only. (For example if, in addition to the Floor 2 smoke/fire detector, the Floor 4 detector also trips, no change to the smoke-control sequence occurs and the Floor 4 smoke condition also annunciates at the FSCS.)
7. At any time, the FSCS is capable of overriding either partially, or in full, any automatic activation of a smoke-control sequence that may be in process.
64
8. The communications between all of the I/A Series BACnet controllers that are part of the smoke-control sequences must be monitored. If the communications between any of these controllers fails, at any time, the system trouble LED at the FSCS must illuminate and an audible signal must be generated.
63.NFPA 92A, 2009 ed., chap. 6, para’s 6.4.2 and 6.4.5.2.1.2.
64.NFPA 92A, 2009 ed., chap. 6, para 6.4.3.7.11.
65
TAC I/A Series MicroNet BACnet Smoke Control Systems Manual F-27419-2
18
Page 35
High-rise Smoke Control
9. If any of the smoke-control equipment proof sensors fail to operate within a specified period of time during the smoke-control sequence, or when under control of the FSCS, the system trouble LED at the FSCS illuminates and an audible signal is generated. If the failed smoke-control equipment is dedicated, its associated trouble LED also illuminates.
If the smoke/fire detector for Floor 3 trips first, the automatic smoke-control sequence is initiated in the following manner.
1. The central AHU supply and return fans are commanded ON, the return air damper is driven to the full-closed position and the outdoor air and exhaust air dampers are driven to their full-open positions. This allows maximum outdoor air to be delivered to the floors above and below the floor reporting the smoke condition. It also allows maximum exhausted air to be expelled from the zone reporting the smoke condition.
2. The dedicated exhaust air dampers for Floors 1, 2, 4, and 5 are driven to the full-closed position while the dedicated exhaust air damper for Floor 3 is driven to the full-open position.
3. The dedicated supply air damper for Floor 3 is driven to the full-closed position. The terminal box supply dampers may optionally be driven to the full-closed position also. This causes the smoke zone to become negatively pressurized.
Note: The UL acceptance of the MNB-V1 and MNB-V2 controllers for UUKL is based on the assumption that negative pressurization of a smoke zone is considered accomplished when the total CFM flow supplied to the zone drops below 50% of its maximum with its dedicated exhaust damper fully open. Sufficient differential pressure must be achieved to ensure smoke spread is confined to the zone in which the fire originated. In all cases, exhaust and supply air dampers should continue to be driven to their full-open and full-closed positions.
4. The dedicated supply air dampers for Floors 1, 2, 4, and 5 remain in the full-open position. The respective terminal box supply dampers, which are controlled by MNB-V1 and MNB-V2 controllers, modulate open. The CFM flow supplied to these floors causes them to be positively pressurized. The terminal box supply dampers will continue to modulate open until they reach the full-open position.
Note: The UL acceptance of the MNB-V1 and MNB-V2 controllers for UUKL is based on the assumption that negative pressurization of a smoke zone is considered accomplished when the total CFM flow supplied to the zone drops below 50% of its maximum with its dedicated exhaust damper fully open. Sufficient differential pressure must be achieved to ensure smoke spread is confined to the zone in which the fire originated. In all cases, exhaust and supply air dampers should continue to be driven to their full-open and full-closed positions.
65.Underwriters Laboratories Inc., UL 864, Control Units and Accessories for Fire Alarm
Systems, 9th ed. (2003), para’s 48.5, 49.4, 49.6, and 49.7.
F-27419-2 TAC I/A Series MicroNet BACnet Smoke Control Systems Manual 19
Page 36
Chapter 2
5. The automatic smoke-control sequence takes priority over the normal HVAC control sequences and any HVAC control overrides. Static pressure high limits and duct smoke detectors on supply air systems should not be automatically overridden.
6. Once the automatic activation occurs, subsequent alarm signals that would normally initiate an automatic smoke-control sequence annunciate only. (For example if, in addition to the Floor 3 smoke/fire detector, the Floor 2 detector also trips, no change to the smoke-control sequence occurs and the Floor 2 smoke condition also annunciates at the FSCS.)
66
7. At any time, the FSCS is capable of overriding either partially, or in full, any automatic activation of a smoke-control sequence that may be in process.
8. The communications between all of the I/A Series BACnet controllers that are part of the smoke-control sequences must be monitored. If the communications between any of these controllers fails, at any time, the system trouble LED at the FSCS must illuminate and an audible signal must be generated.
9. If any of the smoke-control equipment proof sensors fail to operate within a specified period of time during the smoke-control sequence, or when under control of the FSCS, the system trouble LED at the FSCS illuminates and an audible signal is generated. If the failed smoke-control equipment is dedicated, its associated trouble LED also illuminates.
68

Smoke-Control System Configuration Schedule

Each smoke-control system configuration should be defined in a schedule.69 The schedule should list all dedicated and nondedicated smoke-control equipment and show the equipment response for each sensor that activates an automatic smoke-control sequence. An example schedule for this application is shown in
Table–2.1.
Note:
According to NFPA 92A, only the smoke zones that are contiguous to the
zone reporting the smoke condition have to be positively pressurized. For this application, all non-smoke zones are being positively pressurized.
Pressurization of the noncontiguous (optional) smoke-control zones is
dependent upon the smoke-control system design and its associated specification. Regardless of whether or not noncontiguous smoke-control zones are positively pressurized, sufficient differential pressure must be achieved to ensure smoke spread is confined to the zone in which the fire originated.
67
66.NFPA 92A, 2009 ed., chap. 6, para’s 6.4.2 and 6.4.5.2.1.2.
67.NFPA 92A, 2009 ed., chap. 6, para 6.4.3.7.11.
68.UL 864, 9th ed., para’s 48.5, 49.4, 49.6, and 49.7.
69.NFPA 92A, 2009 ed., chap. 6, para 6.4.5.3 and annex A, para A.6.4.5.3.
TAC I/A Series MicroNet BACnet Smoke Control Systems Manual F-27419-2
20
Page 37
High-rise Smoke Control
Table–2.1 Schedule for Smoke-Control System Configuration.
Dedicated and
Nondedicated Smoke
Control Equipment
AHU Supply Fan ON ON ON ON ON
AHU Return Fan ONONONONON
AHU O.A. Damper Full Open Full Open Full Open Full Open Full Open
AHU Return Damper Full Closed Full Closed Full Closed Full Closed Full Closed
AHU Exhaust Damper Full Open Full Open Full Open Full Open Full Open
Stair 1 - Press. FanONONONONON
Stair 2 - Press. FanONONONONON
1st Floor Exhaust Damper
1st Floor Supply Damper Full Closed Full Open Full Open Full Open Full Open
1st Floor MNB-Vx Units 1 to 8
1st Floor as a Zone Neg. Press. Pos. Press. Pos. Press. Pos. Press. Pos. Press.
2nd Floor Exhaust Damper
2nd Floor Supply Damper Full Open Full Closed Full Open Full Open Full Open
2nd Floor MNB-Vx Units 9 to 16
2nd Floor as a Zone Pos. Press. Neg. Press. Pos. Press. Pos. Press. Pos. Press.
3rd Floor Exhaust Damper
3rd Floor Supply Damper Full Open Full Open Full Closed Full Open Full Open
3rd Floor MNB-Vx Units 17 to 24
3rd Floor as a Zone Pos. Press. Pos. Press. Neg. Press. Pos. Press. Pos. Press.
4th Floor Exhaust Damper
4th Floor Supply Damper Full Open Full Open Full Open Full Closed Full Open
4th Floor MNB-Vx Units 25 to 32
4th Floor as a Zone Pos. Press. Pos. Press. Pos. Press. Neg. Press. Pos. Press.
5th Floor Exhaust Damper
5th Floor Supply Damper Full Open Full Open Full Open Full Open Full Closed
5th Floor MNB-Vx Units 33 to 40
5th Floor as a Zone Pos. Press. Pos. Press. Pos. Press. Pos. Press. Neg. Press.
1st Floor
Smoke Detector
in Alarm
Full Open Full Closed Full Closed Full Closed Full Closed
Full Closed Full Open Full Open Full Open Full Open
Full Closed Full Open Full Closed Full Closed Full Closed
Full Open Full Closed Full Open Full Open Full Open
Full Closed Full Closed Full Open Full Closed Full Closed
Full Open Full Open Full Closed Full Open Full Open
Full Closed Full Closed Full Closed Full Open Full Closed
Full Open Full Open Full Open Full Closed Full Open
Full Closed Full Closed Full Closed Full Closed Full Open
Full Open Full Open Full Open Full Open Full Closed
2nd Floor
Smoke Detector
in Alarm
3rd Floor
Smoke Detector
in Alarm
4th Floor
Smoke Detector
in Alarm
5th Floor
Smoke Detector
in Alarm
F-27419-2 TAC I/A Series MicroNet BACnet Smoke Control Systems Manual 21
Page 38
Chapter 2

Firefighter’s Smoke Control Station (FSCS)

The requirements of the FSCS are described below. For more information regarding the FSCS requirements, refer to the NFPA 92A standard.

Location and Access

Physical Arrangement

Status Indicators

The FSCS should be located in proximity to other firefighter’s systems that are provided within the building. Means should be provided to ensure only authorized access to the FSCS.
The FSCS should be designed to depict graphically the physical building arrangement, smoke-control systems and equipment, and the areas served by the equipment (Figure–2.2).
Visual status indicators should be provided for all smoke-control equipment.71 For dampers, a green LED is used to indicate Open and a yellow LED is used to indicate Closed. For fans, a green LED is used to indicate the ON state and a yellow LED is used to indicate the OFF state. The visual indication requirements are:
70
72
All trouble indicators use red LEDs.
The Open and Closed positions of the central AHU supply, return, and exhaust
air dampers (non-dedicated equipment).
The ON and OFF status of the central AHU supply and return fans
(nondedicated equipment).
The Open and Closed positions of the exhaust air dampers (dedicated
equipment) for each floor, 1st through 5th.
A trouble indicator reflecting the ON (trouble) and OFF (normal) status of the
exhaust air dampers for each floor, 1st through 5th. This is required since the exhaust dampers are considered dedicated equipment.
The Open and Closed positions of the supply air dampers (combination
dedicated and nondedicated equipment) for each floor, 1st through 5th. The closed position is determined solely by the “dedicated” supply air damper. The Open position is determined by the combination of the supply air damper being fully Open and all of the MNB-Vx controllers modulating their dampers (non-dedicated equipment) Open.
A trouble indicator reflecting the ON (trouble) and OFF (normal) status of the
supply air dampers for each floor, 1st through 5th. This is required since the supply dampers are considered dedicated equipment.
A trouble indicator reflecting the ON (alarm) and OFF (normal) status of the
smoke alarm for each smoke-control zone (1st through 5th floors).
The ON and OFF status of the pressurization fans (dedicated equipment) for
stairwells 1 and 2.
A trouble indicator reflecting the ON (trouble) and OFF (normal) status of the
pressurization fans for stairwells 1 and 2. This is required since the pressurization fans are considered dedicated equipment.
A trouble indicator reflecting the ON (alarm) and OFF (normal) status of the
smoke detector in the supply duct of each stairwell pressurization fan.
70.NFPA 92A, 2009 ed., chap. 6, para 6.4.3.7.10 and annex D, para D.1 (2).
71.NFPA 92A, 2009 ed., annex D, para D.1 (2).
72.NFPA 92A, 2009 ed., annex D, para D.1 (2) (a) and D.1 (2) (b).
TAC I/A Series MicroNet BACnet Smoke Control Systems Manual F-27419-2
22
Page 39
High-rise Smoke Control
A system trouble indicator reflecting the ON (trouble) and OFF (normal) status
of the smoke-control system. This indicator is illuminated if any trouble exists in the system.

Audible Annunciation

Control Capability

Additional Control Requirements

All smoke alarm, dedicated trouble and general trouble indicators at the FSCS should also cause an audible annunciation of the condition to be generated.
“The FSCS shall have the highest priority control over all smoke-control systems and equipment” toggle or rotary switches are used to provide control as follows:
73
within the building. In this application, 3-position (ON-OFF-ON)
OPEN-AUTO-CLOSE control of the central AHU supply, return, and exhaust
air dampers.
ON-AUTO-OFF control of the central AHU supply and return fans.
OPEN-AUTO-CLOSE control of the exhaust air dampers for each floor, 1st
through 5th.
OPEN-AUTO-CLOSE control of the supply air dampers for each floor, 1st
through 5th.
ON-AUTO-OFF control of the pressurization fans for stairwells 1 and 2.
Provisions should be made at the FSCS for testing the visual indicators, providing audible device silencing and enabling/disabling the manual control capability of the FSCS. This would be done as follows:
A manual override enable key switch that can enable and disable the
functionality of the control switches mentioned previously. This will also enable and disable the audible device silence switch. A status indicator (i.e. green LED) is provided that will light when the FSCS override capability is enabled. The key associated with the switch should be non-removable when the FSCS is enabled.
An audible device silence switch (momentary push-button) that is functional
only when the FSCS is in the enable state.
A lamp test switch (momentary push-button) for testing all LEDs on the FSCS.
This switch will be enabled at all times.
All status indicators remain operational regardless of the enabled/disabled
state of the FSCS or the state of the control switches mentioned previously.
73.NFPA 92A, 2009 ed., chap. 6, para 6.4.3.7.11.
F-27419-2 TAC I/A Series MicroNet BACnet Smoke Control Systems Manual 23
Page 40
Chapter 2
Figure–2.2 Firefighter’s Smoke Control Station (FSCS).
TAC I/A Series MicroNet BACnet Smoke Control Systems Manual F-27419-2
24
Page 41

System Topologies

High-rise Smoke Control

MNB-1000 Controllers

The MNB-1000 (Instance 2000) controller provides a complete interface to the FSCS through its EIA-485 (RS-485) ADI ModBus interface. It is mounted inside the FSCS, along with its power supply. This controller is the master of the Smoke Control network since it monitors communications to all of the controllers that are part of the smoke-control system, distributes and receives global information between controllers in the network, initiates smoke-control sequences based on information received from the appropriate controllers, and provides additional HVAC control.
The MNB-1000 (Instance 1000) controller provides the central AHU control, monitors end process verification devices, distributes and receives global information between controllers in the network, monitors communications to all of the controllers beneath it, and initiates smoke-control sequences based on information received from the appropriate controllers. Its MS/TP communication trunk connects to the MNB-Vx controllers that provide HVAC control of the occupied spaces. These MNB-Vx controllers also control the common dedicated supply and exhaust air smoke dampers for each smoke-control zone.
The MNB-1000 (Instance 3000) controller monitors the damper proof-of-position for the dedicated supply and return air dampers associated with the smoke-control zones. Additionally, it distributes and receives global information between controllers in the network, monitors communications to all of the controllers beneath it, and initiates smoke-control sequences based on information received from the appropriate controllers. Its MS/TP communication trunk connects to the MNB-300 controllers that provide end process verification, control stairwell pressurization, and monitor smoke alarm and pull station contacts from the UOJZ Fire Alarm Panel. Other MS/TP BACnet controllers that are not UUKL Listed are connected to the same trunk, but are isolated from the UUKL Listed controllers through the use of an approved repeater. These other controllers provide HVAC control only.

Ethernet/IP Infrastructure

F-27419-2 TAC I/A Series MicroNet BACnet Smoke Control Systems Manual 25
Any UL 864 Listed IP infrastructure devices can be used to create the network topology. Currently, only the EIS8-100T and EIS6-100T/FT switching hubs from Contemporary Controls are available. The path through the Ethernet/IP network from any one UUKL device to another must use only UL 864 Listed infrastructure devices. The Ethernet/IP Smoke-Control System can coexist with the non-UL 864 networks as long as they are isolated from those networks through the use of UL 864 Listed IP infrastructure devices. Refer to Chapter 5, Restrictions and General
Comments, for additional information.
Note: At no time can any smoke control signals be passed over the public Internet.
Page 42
Chapter 2
Wiring Requirements
Since the I/O wiring between the I/A Series BACnet controllers and the FSCS (when an I/O wiring interface is used) and the UOJZ Fire Alarm Panel is unsupervised, the I/A Series BACnet controllers used for this purpose must be mounted within 20 ft of the panel to which they are connected. The I/O wiring must be run in conduit. The table below (Table–2.2) lists the general requirements for the wiring associated with an I/A Series BACnet smoke-control application.
Table–2.2 Wiring Requirements
Wiring Status
Ethernet/IP Supervised by block programming
Supervised by block programming. When
EIA-485 ADI ModBus
MS/TP Bus Supervised by block programming
I/O to FSCS
I/O to UOJZ FAP Contacts
Remaining I/O Unsupervised
MNB-1000 is mounted external to the FSCS, wiring must be run in conduit and controller must be located within 20 ft. of the panel.
Unsupervised, wiring must be run in conduit and controllers must be located within 20 ft. of the panel.
Unsupervised, wiring must be run in conduit and controllers must be located within 20 ft. of the panel.
Central System Interface and Overlay Devices
When UNC, Web Server, and/or other central-system type interfaces are attached to the Ethernet/IP network with the ability to access the smoke-control system, they must be isolated from the network through the use of UL 864 Listed IP infrastructure devices (Figure–2.3). This isolation is required by UL because these devices, PC’s and/or interfaces, are not UL 864 Listed. Therefore these devices cannot be used for smoke-control purposes.
Refer to Chapter 5, Restrictions and General Comments, for additional information.
TAC I/A Series MicroNet BACnet Smoke Control Systems Manual F-27419-2
26
Page 43
High-rise Smoke Control
Ethernet/IP
Ethernet/IP
Ethernet/IP
Web Access-1 (Internet Explorer)
Web Access-2 (Internet Explorer)
MS/TP
Converter
To remainder of
building's IT
network that is
not UUKL
To Any additional
controllers that are
part of the UUKL
control system
UNC-1
Instance=5000
ENC-2
Instance=4000
EIS8-100T
Switching Hub
EIS6-100T/FT Switching Hub
WP Tech and Tools (WP Tech, Commissioning Tool, and Flow Balance Tool)
Connections for
programming,
commissioning,
and servicing
NW # 864
NW # 864
NW # 864
NW # 3
To damper position proof switches
I/O
I/O
EOL JPR
EOL JPR
EOL JPR
To MNB-300
Instance=3001
To MNB-300
Instance=3001
MNB-1000 Instance=3000 MS/TP Addr=0
MNB-1000 Instance=1000 MS/TP Addr=0
MNB-1000
Instance=2000
Remote I/O Bus (EIA-485, ADI ModBus)
To FSCS
To Central AHU control and end process verification devices
NW # 1
2
3
3
3
3
3
3
4
1
1
4
4
4
5
6
5
6
5
6
7
2
3
4
Key
EOL JPR End-of-line resistor and/or bias
resistors are engaged through on-board jumpers.
Remote I/O Inputs and outputs remotely
provided by the ADI ModBus interface. The Remote I/O Port refers to the top EIA-485 port on the MNB-1000.
I/O Discrete input and output wiring to
or from controlled or monitored devices.
NW Network
1 At no time can any smoke control signals be
passed over the public Internet.
2 The UL 864 Ethernet switches shown must be
installed in UL-50 enclosures.
3 The UL 864 Listed Ethernet switches can be
used to provide isolation of non-UUKL devices from the UUKL Ethernet network. Refer to Chapter 5, "Restrictions and General Comments," for additional information regarding the use of Ethernet/IP networks and approved devices.
4 The path through the Ethernet/IP network from any one UUKL device to
another must only use UL 864 Listed Ethernet/IP infrastructure devices.
5 All UUKL controllers must be mounted in approved enclosures. Refer to
Chapter 5, "Restrictions and General Comments," for additional information.
6 See "Wiring Requirements" in this chapter.
7 The ADI ModBus interface to the ADI FSCS uses the Remote I/O Bus of the
MNB-1000, not the MSTP Bus.
8 Remote I/O Bus wiring must adhere to the installation requirements defined in
Chapter 5, "Restrictions and General Comments".
Remote I/O Port (ADI)
8
Note: Only specific UL wiring and installation
requirements are shown. For complete installation and wiring requirements, refer to the I/A Series MicroNet BACnet
Wiring and Networking Practices Guide, F-27360, and other appropriate
documentation listed in Appendix C.
Figure–2.3 Ethernet/IP Network Topology.
F-27419-2 TAC I/A Series MicroNet BACnet Smoke Control Systems Manual 27
Page 44
Chapter 2

MNB-Vx Topology In this application, each floor has eight MNB-Vx controllers that control the

VAV terminal boxes (Figure–2.4). During normal occupied mode, each MNB-Vx modulates its primary damper and stages the electric reheat coils, as required, to maintain their individual zone temperature setpoints. During the unoccupied mode, the terminal boxes either maintain their respective unoccupied zone temperature setpoints or drive to a fixed position. Although the MNB-Vx controllers are controlling individual spaces within a floor, each complete floor is considered a smoke-control zone.
In some applications, when MNB-Vx controllers are used to control the supply air to a smoke-control zone, a separate supply air damper must be installed in the common supply duct to each floor/zone. These dampers are used in this application and are required to guarantee acceptable damper response times. The dedicated supply air damper is used to close the supply air to its respective floor when it is considered the smoke zone. Used in conjunction with the dedicated exhaust air damper, it causes the zone to become negatively pressurized. Otherwise, this damper is always fully open. In this example, these dampers are controlled by a spare DO point on an MNB-Vx associated with the respective smoke-control zone.
A separate exhaust air damper must be installed in the common exhaust duct to each floor or zone. The dedicated exhaust air damper is used to open the exhaust air to its respective floor when it is considered the smoke zone. Used in conjunction with the dedicated return air damper, it causes the zone to become negatively pressurized. Otherwise, this damper is always fully open. The exhaust dampers are also controlled by a spare DO point on an MNB-Vx associated with the respective smoke-control zone.
The MNB-Vx controllers modulate their terminal box primary air dampers, as required, to provide positive pressurization to all smoke-control zones.
Note: The UL acceptance of the MNB-V1 and MNB-V2 controllers for UUKL is based on the assumption that negative pressurization of a smoke zone is considered accomplished when the total CFM flow supplied to the zone drops below 50% of its maximum with its dedicated exhaust damper fully open. Sufficient differential pressure must be achieved to ensure smoke spread is confined to the zone in which the fire originated. In all cases, exhaust and supply air dampers should continue to be driven to their full-open and full-closed positions.
MS/TP Bus Requirements
Typically, MS/TP repeaters are used to provide isolation between UUKL Listed and non-UUKL Listed devices, or to extend the maximum distance of the bus. The MS/TP bus can support up to a maximum of 128 devices. Because each TAC I/A Series MicroNet BACnet controller is only a 1/4-load node, a repeater is not necessary to support the maximum number of nodes, or to increase the number of nodes that can be connected to the bus. In cases where third-party devices are involved, a repeater may be used to increase the number of devices that can be connected to the bus. In the application discussed here, the B-LINK-AC-S repeater is used to extend the distance of the MS/TP bus.
For additional repeater information, refer to Chapter 5, Restrictions and
General Comments.
TAC I/A Series MicroNet BACnet Smoke Control Systems Manual F-27419-2
28
Page 45
Floor 5 Smoke Control Zone
Floor 4 Smoke Control Zone
Floor 3 Smoke Control Zone
Floor 2 Smoke Control Zone
Floor 1 Smoke Control Zone
MS/TP Bus
*
EOL
MNB-V2
Instance=1008
MS/TP Addr=08
MNB-V2
Instance=1007
MS/TP Addr=07
MNB-V2
Instance=1006
MS/TP Addr=06
MNB-V2
Instance=1005
MS/TP Addr=05
MNB-V2
Instance=1004
MS/TP Addr=04
MNB-V2
Instance=1003
MS/TP Addr=03
MNB-V2
Instance=1002
MS/TP Addr=02
MNB-V2
Instance=1001
MS/TP Addr=01
MNB-V2
Instance=1009
MS/TP Addr=09
MNB-V2
Instance=1010
MS/TP Addr=10
MNB-V2
Instance=1011
MS/TP Addr=11
MNB-V2
Instance=1012
MS/TP Addr=12
MNB-V2
Instance=1013
MS/TP Addr=13
MNB-V2
Instance=1014
MS/TP Addr=14
MNB-V2
Instance=1015
MS/TP Addr=15
MNB-V2
Instance=1016
MS/TP Addr=16
MNB-V2
Instance=1024
MS/TP Addr=24
MNB-V2
Instance=1023
MS/TP Addr=23
MNB-V2
Instance=1022
MS/TP Addr=22
MNB-V2
Instance=1021
MS/TP Addr=21
MNB-V2
Instance=1020
MS/TP Addr=20
MNB-V2
Instance=1019
MS/TP Addr=19
MNB-V2
Instance=1018
MS/TP Addr=18
MNB-V2
Instance=1017
MS/TP Addr=17
MNB-V2
Instance=1025
MS/TP Addr=25
MNB-V2
Instance=1026
MS/TP Addr=26
MNB-V2
Instance=1027
MS/TP Addr=27
MNB-V2
Instance=1028
MS/TP Addr=28
MNB-V2
Instance=1029
MS/TP Addr=29
MNB-V2
Instance=1030
MS/TP Addr=30
MNB-V2
Instance=1031
MS/TP Addr=31
MNB-V2
Instance=1032
MS/TP Addr=32
MNB-V2
Instance=1040
MS/TP Addr=40
MNB-V2
Instance=1039
MS/TP Addr=39
MNB-V2
Instance=1038
MS/TP Addr=38
MNB-V2
Instance=1037
MS/TP Addr=37
MNB-V2
Instance=1036
MS/TP Addr=36
MNB-V2
Instance=1035
MS/TP Addr=35
MNB-V2
Instance=1034
MS/TP Addr=34
MNB-V2
Instance=1033
MS/TP Addr=33
To MNB-1000
(Instance=1000)
Key
EOL End-of-line resistor, 120 Ω (part
number EMSC-546).
*
See "MS/TP Requirements" in
this chapter.
Note: Only specific UL wiring and installation requirements
are shown. For complete installation and wiring requirements, refer to the I/A Series MicroNet BACnet Wiring and Networking Practices Guide, F-27360, and other appropriate documentation listed in Appendix C.
Note: All references to the MNB-V1 equally apply to the
MNB-V1-2 and all references to the MNB-V2 equally apply to the MNB-V2-2.
Figure–2.4 MNB-V1 and MNB-V2 Controller Topology.
High-rise Smoke Control
F-27419-2 TAC I/A Series MicroNet BACnet Smoke Control Systems Manual 29
Page 46
Chapter 2

MNB-1000 Interface to FSCS

The MNB-1000 (Instance 2000) controller provides a complete interface to the FSCS through its EIA-485 (RS-485) ADI ModBus interface (Figure–2.5). It controls all the FSCS LEDs and monitors all the FSCS override switches. The FSCS (panel) Enable switch functionality is also enforced through programming in the MNB-1000 controller. Refer to Chapter 5, Restrictions
and General Comments, for an example of this programming and for
additional information on the FSCS interface.
When interfaced to the ADI FSCS, the MNB-1000 controller and its power supply are mounted inside the FSCS enclosure, eliminating the need for separate enclosures. This controller functions as the master of the smoke-control network. It monitors communications to all of the controllers that are part of the smoke-control system, distributes and receives global information between controllers in the network, initiates smoke-control sequences based on information received from the appropriate controllers, and integrates the FSCS functionality into the system. Optionally, it can also perform HVAC control functions.
Note: When using I/O points to interface to a UL 864 UUKL/UUKL7 Listed FSCS in place of using an ADI FSCS that supports the ADI ModBus protocol, many additional controllers will be required. Each installation must be carefully assessed to ensure that adequate quantities of devices have been allotted, to perform the necessary control and monitoring functions. Refer to "Job Estimating" on page 78 for point calculating specifics.
TAC I/A Series MicroNet BACnet Smoke Control Systems Manual F-27419-2
30
Page 47
High-rise Smoke Control
Key
EOL JPRa End-of-line resistor is engaged through an on-board
jumper on the MNB-1000. Refer to the MicroNet
BACnet MNB-1000 Plant Controller Installation Instructions, F-27347, for additional information.
Remote I/O Inputs and outputs remotely provided by the ADI
ModBus interface. The Remote I/O Port refers to the top EIA-485 port on the MNB-1000.
EOL JPRb End-of-line resistor is engaged through an on-board
jumper on the ADI FSCS. Refer to the documentation shipped with the unit.
Note: Only specific UL wiring and installation requirements
are shown. For complete installation and wiring requirements, refer to the I/A Series MicroNet BACnet Wiring and Networking Practices Guide, F-27360, and other appropriate documentation listed in Appendix C.
1 In this example, the MNB-1000 controller shown is
mounted inside the ADI FSCS enclosure, along with its dedicated power supply. This is an option that can be specified when ordering the ADI FSCS. Refer to Chapter 5, "Restrictions and General Comments," for additional information regarding the FSCS.
2 The UOJZ Listed N.O. contacts from the Fire Alarm
Panel (FAP) are wired to MNB-300 controllers. As an option, additional contact inputs can be specified when ordering the ADI FSCS, allowing the FAP contacts to be wired directly to the FSCS. Should this option be used, these controllers must be mounted within 20 ft. of the FAP, and the I/O wiring must be run in conduit because the I/O wiring between the FAP and the FSCS is unsupervised.
3 All UUKL controllers must be mounted inside approved
enclosures. Refer to Chapter 5, "Restrictions and General Comments" for additional information. When the ADI FSCS is ordered with the MNB-1000 and its power supply mounted internally, no additional enclosures are required.
4 The path through the Ethernet/IP network from any one
UUKL device to another must only use UL 864 Listed Ethernet/IP infrastructure devices.
5 If individual controllers use hard-wired I/O points to
interface to the FSCS, these controllers must be mounted within 20 ft. of the FAP, and the I/O wiring must be run in conduit because the I/O wiring is unsupervised.
6 The ADI ModBus interface to the ADI FSCS uses the
Remote I/O Bus of the MNB-1000, not the MSTP Bus.
7 Remote I/O Bus wiring must adhere to the installation
requirements defined in Chapter 5, "Restrictions and General Comments".
EOL
JPRb
Remote I/O Bus
(EIA-485, ADI ModBus)
EOL JPRa
1
3
6
7
2
5
4
MNB-1000
Instance=2000
To available port
on UL 864 Listed
Ethernet/IP
Switching Hub
Remote I/O Port (ADI)
Figure–2.5 MNB-1000 Interface to FSCS.
F-27419-2 TAC I/A Series MicroNet BACnet Smoke Control Systems Manual 31
Page 48
Chapter 2

Fire Alarm Panel Interface and Remaining System Topology

The MNB-1000 (Instance 3000) and the controllers beneath it provide additional controlling and monitoring functions, as well as the Fire Alarm Panel (FAP) interface. These controllers operate as follows:
The MNB-1000 (Instance 3000) controller monitors the damper
proof-of-position switches for the five dedicated supply air dampers and three of the dedicated exhaust air dampers associated with the smoke-control zones. It distributes and receives global information between controllers in the network, monitors communications to all of the controllers beneath it, and initiates smoke-control sequences based on information received from the appropriate controllers.
The MNB-300 (Instance 3001) controller monitors the damper
proof-of-position switches for the remaining two dedicated exhaust air dampers associated with the smoke-control zones. It distributes them to the remaining controllers as required for smoke-control purposes.
The MNB-300 (Instance 3002) controller interfaces to the UOJZ Fire
Alarm Panel to monitor stairwell duct smoke alarm and pull station contacts. It provides control of the stairwell pressurization systems and receives or distributes information to or from controllers as required for smoke-control purposes.
The MNB-300 (Instance 3003) controller also interfaces to the UOJZ
Fire Alarm Panel to monitor smoke alarm contacts associated with Floors 1-5. It distributes this information to controllers as required for smoke-control purposes.
The B-LINK-AC MS/TP repeater is used to extend the distance of the
MS/TP bus and provide isolation between UUKL and non-UUKL Listed devices. In this example, its main purpose is to isolate the trunk from non-UUKL Listed controllers that are used for HVAC purposes and perform no functions associated with smoke control.
The remaining two devices (Instances 3004 and 3005), are not UUKL
Listed. They are isolated from the UUKL Listed controllers through use of the B-LINK-AC repeater. These controllers perform HVAC functions that are unrelated to smoke control.
TAC I/A Series MicroNet BACnet Smoke Control Systems Manual F-27419-2
32
Page 49
MS/TP Bus
Figure–2.6 Fire Alarm Panel and Remaining Controllers.
High-rise Smoke Control
To MNB-1000 Instance=3000
*
UOJZ Listed
Fire Alarm Panel
SD
SD
SD
SD
SD
SD
SD
PS
PS
Floor 1 Smoke Alarm
Floor 2 Smoke Alarm
Floor 3 Smoke Alarm
Floor 4 Smoke Alarm
Floor 5 Smoke Alarm
Stair 1 Smoke Alarm
Stair 2 Smoke Alarm
Pull Station 1
Pull Station 2
1 Because the I/O wiring between the I/A Series BACnet
controllers and the UOJZ Listed Fire Alarm Panel (FAP) is unsupervised, these controllers must be mounted within 20 ft. of the FAP, and the I/O wiring must be run in conduit.
Note: Only specific UL wiring and installation requirements
are shown. For complete installation and wiring requirements, refer to the I/A Series MicroNet BACnet Wiring and Networking Practices Guide, F-27360, and other appropriate documentation listed in Appendix C.
I/O
MNB-300 Instance=3001 MS/TP Addr=1 (Damper End Switch Proof)
MNB-300
I/O
Instance=3002 MS/TP Addr=2 (Stairwell Pressurization, Smoke
1
I/O
Alarms, and Pull Stations)
MNB-300 Instance=3003 MS/TP Addr=3 (Floor 1, 5 Smoke Alarms)
RS-232
RD TD
300
1200
2400
Baud Rate
9600
B-LINK-AC
19200 38400
EOL
Andover Controls
76800
Spare
RS-485
RD TD
5
RD TD
Power
4
+
RD TD
SHLD
3
+
RD TD
SHLD
2
+
RD TD
SHLD
1
+
SHLD
+
SHLD (Input)
L
N
Line Voltage
Selector
B-LINK-AC MS/TP Repeater
115
(Used for MS/TP Isolation)
EOL
Non-UUKL Device Instance=3004 MS/TP Addr=4
Key
EOL End-of-line resistor, 120 Ω (part no. EMSC-546)
See "MS/TP Requirements" in this chapter.
*
I/O Discrete input and output wiring to or from controlled
or monitored devices.
EOL
Non-UUKL Device Instance=3005 MS/TP Addr=5

Comments

Always refer to the NFPA 92A, NFPA 92B, NFPA 72, and UL 864 UUKL/UUKL7 standards for additional Smoke-Control Systems information. Additionally, general system application comments and restrictions are provided in Chapter 5, Restrictions and General Comments and should be thoroughly reviewed to ensure compliance with the UL listing. It is the responsibility of the field office to work with the smoke-control system designer and gain the smoke-control system approval from the Authority Having Jurisdiction (AHJ).
F-27419-2 TAC I/A Series MicroNet BACnet Smoke Control Systems Manual 33
Page 50
Chapter 2
TAC I/A Series MicroNet BACnet Smoke Control Systems Manual F-27419-2
34
Page 51
Chapter 3 Warehouse Smoke Control

Purpose

This application provides guidelines for using I/A Series Micronet BACnet controllers in a single story warehouse (or similar single-story buildings with large open spaces) that require the UL 864 UUKL/UUKL7 listing for Smoke-Control Systems. This application utilizes only nondedicated smoke-control equipment. Multiple MNB-1000 controllers are used to perform the HVAC functions when in normal control mode. When in the smoke-control mode, they perform the required smoke-control sequences by controlling the individual air handling unit (AHU) fans and dampers (supply, exhaust, and return). One MNB-1000 controller monitors the N.O. relay contacts of a UOJZ Listed fire alarm panel for automatic activation of the smoke-control sequences, and monitors the UUKL Listed Firefighter’s Smoke Control Station (FSCS) for manual activation and overrides. This controller also provides control of the FSCS visual and audible status indicators.

Sequence of Operation

Normal HVAC Control

F-27419-2 TAC I/A Series MicroNet BACnet Smoke Control Systems Manual 35
Under normal conditions, each AHU follows an occupied schedule that determines when that AHU operates. In the case of the warehouse, a central occupied schedule is used for all of the units. During the unoccupied mode, the outdoor and exhaust air dampers are in the full-closed positions. The return air dampers are in the full-open positions. The supply and return fans are commanded OFF. During the occupied mode, the supply and return fans are commanded ON. The outdoor, exhaust, and return air dampers modulate in conjunction with typical heating and/or cooling coils or equipment to maintain the zone temperature setpoint associated with the respective AHU.
Each AHU can have a wide variety of additional control sequences that determine its operation and establish its operating priorities (for example, low limit stats and minimum outdoor air). One MNB-1000 controller is used for each AHU. Each one provides the basic control of the AHU and the monitoring of end process verification sensors, such as flow switches and position indication switches.
Page 52
Chapter 3
The Fire Alarm Panel (i.e. Listed Fire Alarm Control Unit) is the primary indicator for fire alarm conditions. It is also the primary initiator of the automatic smoke/fire alarm sequence. Upon detection of smoke or fire, a set of contacts in the Fire Alarm Panel (for the zone affected) close, indicating to the I/A Series BACnet building automation system that a smoke/fire condition exists. In this application, a smoke detector is provided for each zone (smoke-control zone) and each zone consists of the area served by a single AHU. The contacts from the Fire Alarm Panel for the associated smoke detectors are monitored by the MNB-1000 controller associated with the FSCS.
Note: Any UOJZ listed fire alarm panel with programmable N.O. relay contacts can be used with I/A Series BACnet controllers.
The Automation Displays, Inc. Firefighter’s Smoke Control Station (i.e. Listed Smoke Control Panel) is the primary indicator for the status of all smoke control and related HVAC equipment. It also provides the interface for manual activation commands and overrides for all smoke-control related equipment. An MNB-1000 controller is mounted internal to the FSCS and provides the ADI ModBus (control) interface to the FSCS. This controller is the central coordinator of all smoke-control activity. All commands issued from the FSCS are monitored and distributed throughout the network as required to implement the manual smoke-control sequences and overrides. The status of all of the smoke-control systems and equipment, as well as HVAC monitored trouble signals, are returned to the FSCS for visual indication and, in some cases, audible annunciation. Spare I/O points that exist on this controller may be used for other control purposes, if required.

Smoke Control Sequences

Note: Any UUKL listed FSCS can be used with I/A Series BACnet controllers, but only the Automation Displays, Inc. unit supports the ADI ModBus interface. When an FSCS from other vendors is used, many additional controllers will be required to provide the individual I/O point interfaces.
In this application, the complete smoke-control system is considered nondedicated. Therefore, the smoke-control equipment does not require an automatic self-test. Since this equipment consists of HVAC components that are operated on a regular basis, the normal “comfort” level associated with the operability or inoperability of the equipment is considered an acceptable means of maintaining system integrity. Fan operation is verified using differential pressure sensors. Supply, exhaust, and return air damper positions are verified by monitoring end-of-travel switches.
This application uses only one type of smoke-control system to implement the smoke-control strategy. This system consists of zoned smoke control. Zoned smoke control divides a building into a number of zones for the purpose of inhibiting smoke movement. smoke barriers. In the event of a fire, pressure differences and airflows produced by mechanical fans and operating dampers are used to limit the smoke to the zone in which the fire originated.
74.National Fire Protection Association, Inc., NFPA 92A, Standard for Smoke-Control Systems Utilizing Barriers and Pressure Differences, NFPA 92A, 2009 ed., chap. 5, para. 5.5.1.1.
74
The zones are separated from each other by
75
TAC I/A Series MicroNet BACnet Smoke Control Systems Manual F-27419-2
36
Page 53
Warehouse Smoke Control
Each area of the warehouse that is served by an AHU is considered a smoke-control zone. When smoke is detected in any zone, all of the nonsmoke zones that are contiguous to the smoke zone, or optionally, all nonsmoke zones in the building, is exhausted from the smoke zone. Pressurization of the noncontiguous (optional) smoke-control zones is dependent upon the smoke-control system design and its associated specification. Regardless of whether or not the noncontiguous smoke-control zones are positively pressurized, sufficient differential pressure must be achieved to limit smoke spread to the zone in which the fire originated.
Anytime a smoke/fire detector trips, an automatic smoke-control sequence is initiated. For example, if the smoke/fire detector for smoke-control Zone 5 trips first, the automatic smoke-control sequence is initiated in the following manner:
1. The AHU-5 supply fan is commanded OFF and the return fan is commanded ON. The return and outdoor air dampers are driven to their full-closed positions. The exhaust air damper is driven to the full-open position. This prevents any outdoor or return air from being delivered, by AHU-5, to the zone reporting the smoke condition. It also allows maximum exhausted air to be expelled from the smoke zone.
76
are positively pressurized and the smoke
2. The AHU-1, AHU-2, AHU-3, AHU-4, and AHU-6 supply fans are commanded ON and their return fans are commanded OFF. Their associated return and exhaust air dampers are driven to the full-closed positions. Their outdoor air dampers are driven full-open. This allows outdoor air to be delivered to each of the smoke-control zones that are contiguous to the zone reporting the smoke condition. This fresh air is used to positively pressurize the nonsmoke zones.
3. The automatic smoke-control sequence takes priority over the normal HVAC control sequences and any HVAC control overrides. Static pressure high limits and duct smoke detectors on supply air systems should not be automatically overridden.
77
4. Once the automatic activation has occurred, subsequent alarm signals that would normally initiate an automatic smoke-control sequence will annunciate only. (For example if, in addition to the AHU-5 smoke/fire detector, the AHU-6 detector also trips, no change to the smoke-control sequence occurs and the AHU-6 smoke condition also annunciates at the FSCS.)
5. At any time, the FSCS is capable of overriding either partially, or in full, any automatic activation of a smoke-control sequence that may be in process.
78
6. The communications between all of the I/A Series BACnet controllers that are part of the smoke-control sequences must be monitored. If the communications between any of these controllers fails, at any time, the system trouble LED at the FSCS must illuminate and an audible signal must be generated.
79
75.NFPA 92A, 2009 ed., annex A, para. A.5.5.
76.NFPA 92A, 2009 ed., annex A, para. A.5.5.1.1.1.
77.NFPA 92A, 2009 ed., chap. 6, para’s 6.4.2 and 6.4.5.2.1.2.
78.NFPA 92A, 2009 ed., chap. 6, para 6.4.3.7.11.
F-27419-2 TAC I/A Series MicroNet BACnet Smoke Control Systems Manual 37
Page 54
Chapter 3
7. If any of the smoke-control equipment proof sensors fail to operate within a specified period of time during the smoke-control sequence or when under control of the FSCS, the system trouble LED at the FSCS illuminates and an audible signal is generated.
If the smoke/fire detector for AHU-6 trips first, the automatic smoke-control sequence is initiated in the following manner:
1. The AHU-6 supply fan is commanded OFF and the return fan is commanded ON. The return and outdoor air dampers are driven to their full-closed positions. The exhaust air damper is driven to the full-open position. This prevents any outdoor or return air from being delivered, by AHU-6, to the zone reporting the smoke condition. It also allows maximum exhausted air to be expelled from the smoke zone, and negative pressurization in the area where the smoke was detected.
2. The AHU-1, AHU-2, AHU-3, AHU-4 and AHU-5 supply fans are commanded ON and their return fans are commanded OFF. Their associated return and exhaust air dampers are driven to the full-closed positions. The outdoor air dampers are driven full-open. This allows outdoor air to be delivered to each of the smoke-control zones. This outdoor air is used to positively pressurize the nonsmoke zones. Controlling AHU-3 and AHU-4 in this manner is considered optional since these zones are not contiguous to the smoke zone.
3. The automatic smoke-control sequence takes priority over the normal HVAC control sequences and any HVAC control overrides. Static pressure high limits and duct smoke detectors on supply air systems should not be automatically overridden.
80
4. Once the automatic activation has occurred, subsequent alarm signals that would normally initiate an automatic smoke-control sequence will annunciate only. (For example if, in addition to the AHU-6 smoke/fire detector, the AHU-2 detector also trips, no change to the smoke-control sequence occurs and the AHU-2 smoke condition also annunciates at the FSCS.)
5. At any time, the FSCS is capable of overriding either partially, or in full, any automatic activation of a smoke-control sequence that may be in process.
81
6. The communications between all of the I/A Series BACnet controllers that are part of the smoke-control sequences must be monitored. If the communications between any of these controllers fails, at any time, the system trouble LED at the FSCS must illuminate and an audible signal must be generated.
82
7. If any of the smoke-control equipment proof sensors fail to operate within a specified period of time during the smoke-control sequence or when under control of the FSCS, the system trouble LED at the FSCS illuminates and an audible signal is generated.
79.Underwriters Laboratories Inc., UL 864, Control Units and Accessories for Fire Alarm Systems, 9th ed. (2003), para’s 48.5, 49.4, 49.6, and 49.7.
80.NFPA 92A, 2009 ed., chap. 6, para’s 6.4.2 and 6.4.5.2.1.2.
81.NFPA 92A, 2009 ed., chap. 6, para 6.4.3.7.11.
82.UL 864, 9th ed., para’s 48.5, 49.4, 49.6, and 49.7.
TAC I/A Series MicroNet BACnet Smoke Control Systems Manual F-27419-2
38
Page 55
Warehouse Smoke Control

Smoke-Control System Configuration Schedule

Each smoke-control system configuration should be defined in a schedule.83 The schedule should list all dedicated and nondedicated equipment and show the equipment response for each sensor that activates an automatic smoke-control sequence. An example schedule for this application is shown below (Table–3.1).
Note:
According to NFPA 92A, only the smoke zones that are contiguous to the
zone reporting the smoke condition have to be positively pressurized. For this application, all non-smoke zones are being positively pressurized.
Pressurization of the noncontiguous (optional) smoke-control zones is
dependent upon the smoke-control system design and its associated specification. Regardless of whether or not noncontiguous smoke-control zones are positively pressurized, sufficient differential pressure must be achieved to ensure smoke spread is confined to the zone in which the fire originated.
Table–3.1 Schedule for Smoke-Control System Configuration .
Zone 1
Nondedicated Smoke
Control Equipment
AHU-1 Supply Fan OFF ON ON ON ON ON
AHU-1 Return Fan ON OFF OFF OFF OFF OFF
AHU-1 O.A. Damper Full Closed Full Open Full Open Full Open Full Open Full Open
AHU-1 Return Damper Full Closed Full Closed Full Closed Full Closed Full Closed Full Closed
AHU-1 Exhaust Damper Full Open Full Closed Full Closed Full Closed Full Closed Full Closed
Smoke Control Zone 1 Neg. Press. Pos. Press. Pos. Press. Pos. Press. Pos. Press. Pos. Press.
AHU-2 Supply Fan ON OFF ON ON ON ON
AHU-2 Return Fan OFF ON OFF OFF OFF OFF
AHU-2 O.A. Damper Full Open Full Closed Full Open Full Open Full Open Full Open
AHU-2 Return Damper Full Closed Full Closed Full Closed Full Closed Full Closed Full Closed
AHU-2 Exhaust Damper Full Closed Full Open Full Closed Full Closed Full Closed Full Closed
Smoke Control Zone 2 Pos. Press. Neg. Press. Pos. Press. Pos. Press. Pos. Press. Pos. Press.
AHU-3 Supply Fan ON ON OFF ON ON ON
AHU-3 Return Fan OFF OFF ON OFF OFF OFF
AHU-3 O.A. Damper Full Open Full Open Full Closed Full Open Full Open Full Open
AHU-3 Return Damper Full Closed Full Closed Full Closed Full Closed Full Closed Full Closed
AHU-3 Exhaust Damper Full Closed Full Closed Full Open Full Closed Full Closed Full Closed
Smoke Control Zone 3 Pos. Press. Pos. Press. Neg. Press. Pos. Press. Pos. Press. Pos. Press.
AHU-4 Supply Fan ON ON ON OFF ON ON
AHU-4 Return Fan OFF OFF OFF ON OFF OFF
AHU-4 O.A. Damper Full Open Full Open Full Open Full Closed Full Open Full Open
AHU-4 Return Damper Full Closed Full Closed Full Closed Full Closed Full Closed Full Closed
AHU-4 Exhaust Damper Full Closed Full Closed Full Closed Full Open Full Closed Full Closed
Smoke Detector in Alarm
Zone 2
Smoke Detector in Alarm
Zone 3
Smoke Detector in Alarm
Zone 4
Smoke Detector in Alarm
Zone 5
Smoke Detector in Alarm
Zone 6 Smoke
Detector
in Alarm
83.NFPA 92A, 2009 ed., chap. 6, para 6.4.5.3 and annex A, para A.6.4.5.3.
F-27419-2 TAC I/A Series MicroNet BACnet Smoke Control Systems Manual 39
Page 56
Chapter 3
Table–3.1 Schedule for Smoke-Control System Configuration (Continued).
Zone 1
Nondedicated Smoke
Control Equipment
Smoke Control Zone 4 Pos. Press. Pos. Press. Pos. Press. Neg. Press. Pos. Press. Pos. Press.
AHU-5 Supply Fan ONONONONOFFON
AHU-5 Return Fan OFF OFF OFF OFF ON OFF
AHU-5 O.A. Damper Full Open Full Open Full Open Full Open Full Closed Full Open
AHU-5 Return Damper Full Closed Full Closed Full Closed Full Closed Full Closed Full Closed
AHU-5 Exhaust Damper Full Closed Full Closed Full Closed Full Closed Full Open Full Closed
Smoke Control Zone 5 Pos. Press. Pos. Press. Pos. Press. Pos. Press. Neg. Press. Pos. Press.
AHU-6 Supply Fan ONONONONONOFF
AHU-6 Return Fan OFF OFF OFF OFF OFF ON
AHU-6 O.A. Damper Full Open Full Open Full Open Full Open Full Open Full Closed
AHU-6 Return Damper Full Closed Full Closed Full Closed Full Closed Full Closed Full Closed
AHU-6 Exhaust Damper Full Closed Full Closed Full Closed Full Closed Full Closed Full Open
Smoke Control Zone 6 Pos. Press. Pos. Press. Pos. Press. Pos. Press. Pos. Press. Neg. Press.
Smoke Detector in Alarm
Zone 2
Smoke Detector in Alarm
Zone 3
Smoke Detector in Alarm
Zone 4
Smoke Detector in Alarm
Zone 5 Smoke
Detector
in Alarm
Zone 6
Smoke Detector in Alarm

Firefighter’s Smoke Control Station (FSCS)

The requirements of the FSCS are similar to the ones shown in Chapter 2. The graphic depiction and smoke-control equipment used changes based on the sequence of operation for this application.

System Topologies

Warehouse Building Layout

In this application there are six individual AHUs, with each controlling the space temperatures for their associated zone (Figure–3.1 and Figure–3.2). Each AHU is controlled by a single MNB-1000 controller. These devices (Instances 10 through
60) monitor and control all of the I/O points that provide the normal HVAC control (including control priorities such as low limit stats, filter, etc.). Additionally, the end process verification sensors for the smoke-control equipment are monitored. These sensors would typically consist of flow switches and end switches that are associated with the supply and return fans, as well as the supply, return, and exhaust dampers. The proof sensor information is distributed throughout the network as required to perform the smoke-control strategies and update the FSCS. Events that initiate automatic and manual activation of smoke-control strategies are monitored by a separate MNB-1000 (Instance 70) controller in the network. It distributes the information to these controllers for implementation and subsequent feedback. Each zone controlled by an AHU is considered a smoke-control zone; therefore, the warehouse has six smoke-control zones.
The MNB-1000 (Instance 70) controller provides a complete interface to the FSCS through its EIA-485 (RS-485) ADI ModBus interface. It is mounted inside the FSCS, along with its power supply. This controller functions as the master of the Smoke Control network because it monitors communications to all the controllers that are part of the smoke-control system, distributes and receives
TAC I/A Series MicroNet BACnet Smoke Control Systems Manual F-27419-2
40
Page 57
Warehouse Smoke Control
global information between controllers in the network, initiates smoke-control sequences based on information received from the appropriate controllers, and provides additional HVAC control.

Ethernet/IP Infrastructure

Any UL 864 Listed IP infrastructure devices can be used to create the network topology. Currently, the only available units are the EIS8-100T and EIS6-100T/FT switching hubs from Contemporary Controls. The path through the Ethernet/IP network from any one UUKL device to another must use only UL 864 Listed infrastructure devices. The Ethernet/IP Smoke-Control System can coexist with the non-UL 864 networks, as long as they are isolated from those networks through the use of UL 864 Listed IP infrastructure devices. Refer to Chapter 5,
Restrictions and General Comments, for additional information.
Note: At no time can any smoke control signals be passed over the public Internet.
Wiring Requirements
Since the I/O wiring between the I/A Series BACnet controllers and the FSCS (when an I/O wiring interface is used) and the UOJZ Fire Alarm Panel is unsupervised, the I/A Series BACnet controllers used for this purpose must be mounted within 20 ft of the panel to which they are connected. The I/O wiring must be run in conduit. Table–3.2, below, lists the general requirements for the wiring associated with an I/A Series BACnet smoke-control application.
Table–3.2 Wiring Requirements.
Wiring Status
Ethernet/IP Supervised by block programming
Supervised by block programming. When MNB-1000 is
EIA-485 ADI ModBus
MS/TP Bus Supervised by block programming
I/O to FSCS
I/O to UOJZ FAP Contacts
mounted external to the FSCS, wiring must be run in conduit and controller must be located within 20 ft. of the panel.
Unsupervised, wiring must be run in conduit and controllers must be located within 20 ft. of the panel.
Unsupervised, wiring must be run in conduit and controllers must be located within 20 ft. of the panel.
Remaining I/O Unsupervised
Central System Interface and Overlay Devices
When a UNC, Web Server, and/or other central-system type interfaces are attached to the Ethernet/IP network with the ability to access the smoke-control system, they must be isolated from the network through the use of UL 864 Listed IP infrastructure devices (Figure–3.2). This isolation is required by UL because these devices, PC’s and/or interfaces, are not UL 864 Listed. Therefore these devices cannot be used for smoke-control purposes.
Refer to Chapter 5, Restrictions and General Comments, for additional information.
F-27419-2 TAC I/A Series MicroNet BACnet Smoke Control Systems Manual 41
Page 58
Chapter 3
AHU-1
Smoke Control
Zone 1
AHU-2
Smoke Control
Zone 2
AHU-3
Smoke Control
Zone 3
AHU-4
Smoke Control
Zone 4
AHU-5
Smoke Control
Zone 5
AHU-6
Smoke Control
Zone 6
EOL JPR
Remote I/O Bus (EIA-485, ADI ModBus)
To FSCS
To available ports
on UL 864 Listed
Ethernet/IP
Switching Hub
Note: Only specific UL wiring and installation requirements are shown. For
complete installation and wiring requirements, refer to the I/A Series MicroNet BACnet Wiring and Networking Practices Guide, F-27360, and other appropriate documentation listed in Appendix C.
Remote I/O Port (ADI)
1
2
1 The ADI ModBus interface to the ADI FSCS
uses the Remote I/O Bus of the MNB-1000, not the MSTP Bus.
2 Remote I/O Bus wiring must adhere to the
installation requirements defined in Chapter 5, "Restrictions and General Comments".
Key
EOL JPR End-of-line resistor and/or bias resistors
are engaged through on-board jumpers.
Remote I/O Inputs and outputs remotely provided by
the ADI ModBus interface. The Remote I/O Port refers to the top EIA-485 port on the MNB-1000.
I/O Discrete input and output wiring to or
from controlled or monitored devices.
To available port on UL 864 Listed Ethernet/IP Switching Hub
MNB-1000 Instance=10 MS/TP Addr=0
To available port on UL 864 Listed Ethernet/IP Switching Hub
MNB-1000 Instance=20 MS/TP Addr=0
To available port on UL 864 Listed Ethernet/IP Switching Hub
MNB-1000 Instance=40 MS/TP Addr=0
To available port on UL 864 Listed Ethernet/IP Switching Hub
MNB-1000 Instance=50 MS/TP Addr=0
To available port on UL 864 Listed Ethernet/IP Switching Hub
MNB-1000 Instance=60 MS/TP Addr=0
MNB-1000 Instance=30 MS/TP Addr=0
MNB-1000
Instance=70
Figure–3.1 Warehouse Building Layout.
TAC I/A Series MicroNet BACnet Smoke Control Systems Manual F-27419-2
42
Page 59
Warehouse Smoke Control

MNB-1000 Interface to FSCS

The MNB-1000 (Instance 70) controller provides a complete interface to the FSCS through its EIA-485 (RS-485) ADI ModBus interface (Figure–3.3). It controls all the FSCS LEDs and monitors all the FSCS override switches. The FSCS (panel) Enable switch functionality is also enforced through programming in the MNB-1000 controller. Refer to Chapter 5, Restrictions and General Comments for an example of this programming and for additional information on the FSCS interface.
When interfaced to the ADI FSCS, the MNB-1000 controller and its power supply are mounted inside the FSCS enclosure, eliminating the need for separate enclosures. This controller functions as the master of the smoke-control network. It monitors communications to all of the controllers that are part of the smoke-control system, distributes and receives global information between controllers in the network, initiates smoke-control sequences based on information received from the appropriate controllers, and integrates the FSCS functionality into the system. Optionally, it can also perform HVAC control functions.
Note: When using I/O points to interface to a UL 864 UUKL/UUKL7 Listed FSCS in place of using an ADI FSCS that supports the ADI ModBus protocol, many additional controllers will be required. Each installation must be carefully assessed to ensure that adequate quantities of devices have been allotted to perform the necessary control and monitoring functions. Refer to "Job Estimating"
on page 78 for point calculating specifics.

Fire Alarm Panel Interface

The UOJZ Listed N.O. contacts from the Fire Alarm Panel are wired directly to contact inputs of the FSCS (Figure–3.3). When ordering the ADI FSCS, contact inputs can be specified for this purpose. When this option is used, the FSCS and the FAP device supplying the contacts must be mounted within 20 ft. of each other, and the I/O wiring must be run in conduit because the I/O wiring is unsupervised.
When the FAP is interfaced to the FSCS in this manner, the statuses of the smoke alarms are received from the FSCS by the MNB-1000 (Instance 70) controller and distributed throughout the network, as required, to support the smoke-control sequence.
Note: When using controller I/O points to interface to UOJZ Listed N.O. contacts from a Fire Alarm Panel (instead of contact inputs of the ADI FSCS), several additional controllers will be required. Each installation must be carefully assessed to ensure that adequate quantities of devices have been allotted to perform the necessary control and monitoring functions. Refer to "Job Estimating"
on page 78 for point calculating specifics.
F-27419-2 TAC I/A Series MicroNet BACnet Smoke Control Systems Manual 43
Page 60
Chapter 3
Ethernet/IP
Ethernet/IP
Ethernet/IP
Web Access-1 (Internet Explorer)
Web Access-2
(Internet Explorer)
To remainder of
building's IT
network that is
not UUKL
To Any additional
controllers that are
part of the UUKL
control system
UNC-1 (UNC-520-2) Instance=5000
EIS8-100T
Switching Hub
EIS6-100T/FT Switching Hub
NW # 864
I/O
MNB-1000 Instance=10
To AHU-1 control and end process
verification devices
2
1
1
3
3
3
3
4
2
3
4
4
5
6
NW # 864
I/O
MNB-1000 Instance=20
To AHU-1 control and end process
verification devices
4
5
6
NW # 864
I/O
MNB-1000 Instance=30
MNB-1000 Instance=40
To AHU-1 control
and end process
verification devices
4
5
6
NW # 864
I/O
To AHU-1 control
and end process
verification devices
4
5
6
NW # 864
I/O
MNB-1000 Instance=50
To AHU-1 control
and end process
verification devices
4
5
6
NW # 864
I/O
MNB-1000 Instance=60
To AHU-1 control
and end process
verification devices
4
5
6
EOL JPR
MNB-1000
Instance=70
Remote I/O Bus (EIA-485, ADI ModBus)
To FSCS
4
5
6
Note: Only specific UL wiring and installation
requirements are shown. For complete installation and wiring requirements, refer to the I/A Series MicroNet BACnet Wiring
and Networking Practices Guide, F-27360, and other appropriate
documentation listed in Appendix C.
1 At no time can any smoke control signals
be passed over the public Internet.
2 The UL 864 Ethernet switches shown
must be installed in UL-50 enclosures.
3 The UL 864 Listed Ethernet switches can be used to provide isolation of
non-UUKL devices from the UUKL Ethernet network. Refer to Chapter 5, "Restrictions and General Comments," for additional information regarding the use of Ethernet/IP networks and approved devices.
4 The path through the Ethernet/IP network from any one UUKL device to
another must only use UL 864 Listed Ethernet/IP infrastructure devices.
5 All UUKL controllers must be mounted in approved enclosures. Refer to
Chapter 5, "Restrictions and General Comments," for additional information.
6 See "Wiring Requirements" in this chapter.
7 The ADI ModBus interface to the ADI FSCS uses the Remote I/O Bus of the
MNB-1000, not the MSTP Bus.
8 Remote I/O Bus wiring must adhere to the installation requirements defined
in Chapter 5, "Restrictions and General Comments".
Remote I/O Port (ADI)
7
8
Key
EOL JPR End-of-line resistor and/or bias
resistors are engaged through on-board jumpers.
Remote I/O Inputs and outputs remotely provided
by the ADI ModBus interface. The Remote I/O Port refers to the top EIA-485 port on the MNB-1000.
I/O Discrete input and output wiring to or
from controlled or monitored devices.
NW Network
Figure–3.2 Ethernet/IP Network Topology.
44
TAC I/A Series MicroNet BACnet Smoke Control Systems Manual F-27419-2
Page 61
Warehouse Smoke Control
Figure–3.3 FSCS Interface, UOJZ Fire Alarm Panel Interface, and Related MNB-1000 Controller.
UOJZ Listed
Fire Alarm Panel
SD
SD
SD
SD
SD
SD
1 In this example, the MNB-1000 controller shown is
mounted inside the ADI FSCS enclosure, along with its dedicated power supply. This is an option that can be specified when ordering the ADI FSCS. Refer to Chapter 5, "Restrictions and General Comments," for additional information regarding the FSCS.
2 The UOJZ Listed N.O. contacts from the Fire Alarm Panel
(FAP) are wired directly to contact inputs of the FSCS. When ordering the ADI FSCS, contact inputs can be specified for this purpose. When this option is used, the FAP device with the contacts and the FSCS must be mounted within 20 ft. of each other, and the I/O wiring must be run in conduit because the I/O wiring is unsupervised.
3 All UUKL controllers must be mounted inside approved
enclosures. Refer to Chapter 5, "Restrictions and General Comments" for additional information. When the ADI FSCS is ordered with the MNB-1000 and its power supply mounted internally, no additional enclosures are required.
4 The path through the Ethernet/IP network from any one UUKL
device to another must only use UL 864 Listed Ethernet/IP infrastructure devices.
5 If individual controllers use hard-wired I/O points to interface to
the FSCS, these controllers must be mounted within 20 ft. of the FAP, and the I/O wiring must be run in conduit because the I/O wiring is unsupervised.
6 The ADI ModBus interface to the ADI FSCS uses the
Remote I/O Bus of the MNB-1000, not the MSTP Bus.
7 Remote I/O
requirements defined in Chapter 5, "Restrictions and General Comments".
Note: Only specific UL wiring and installation
requirements are shown. For complete installation and wiring requirements, refer to the I/A Series MicroNet BACnet
Wiring and Networking Practices Guide, F-27360, and other appropriate
documentation listed in Appendix C.
Zone 1 Smoke Alarm
Zone 2 Smoke Alarm
Zone 3 Smoke Alarm
Zone 4 Smoke Alarm
Zone 5 Smoke Alarm
Zone 6 Smoke Alarm
Bus wiring must adhere to the installation
I/O
2
To available port
on UL 864 Listed
Ethernet/IP
Switching Hub
(EIA-485, ADI ModBus)
4
Remote I/O Bus
6
7
EOL JPRb
Remote I/O Port (ADI)
EOL JPRa
Smoke Control Panel
AHU-1
AHU-2
AHU-3
Zone 1
AHU-6
Zone 2
AHU-5
Zone 3
AHU-4
Zone 6
Zone 5
Zone 4
Key
EOL JPRa End-of-line resistor is engaged through an
EOL JPRb End-of-line resistor is engaged through an
Remote I/O Inputs and outputs remotely provided by the
I/O Discrete input and output wiring to or from
on-board jumper on the MNB-1000. Refer to the
MicroNet BACnet MNB-1000 Plant Controller Installation Instructions, F-27347, for additional
information.
on-board jumper on the ADI FSCS. Refer to the documentation shipped with the unit.
ADI ModBus interface. The Remote I/O Port refers to the top EIA-485 port on the MNB-1000.
controlled or monitored devices.
MNB-1000
Instance=70
1
3
5
F-27419-2 TAC I/A Series MicroNet BACnet Smoke Control Systems Manual 45
Page 62
Chapter 3

Comments

Always refer to the NFPA 92A, NFPA 92B, NFPA 72, and UL 864 UUKL/UUKL7 standards for additional Smoke-Control Systems information. Additionally, general system application comments and restrictions are provided in Chapter 5, Restrictions and General Comments and should be thoroughly reviewed to ensure compliance with the UL listing. It is the responsibility of the field office to work with the smoke-control system designer and gain the smoke-control system approval from the Authority Having Jurisdiction (AHJ).
TAC I/A Series MicroNet BACnet Smoke Control Systems Manual F-27419-2
46
Page 63
Chapter 4 Campus Smoke Control

Purpose

This application provides guidelines for using I/A Series MicroNet BACnet controllers on a large campus that requires the UL 864 UUKL/UUKL7 listing for Smoke-Control Systems. This application uses MNB-300, MNB-Vx, and MNB-1000 controllers that perform the HVAC functions when in normal control mode. When in the smoke-control mode, they perform the required smoke-control sequences by controlling the individual terminal boxes, dedicated smoke-control dampers, and central air handling unit (AHU) fans. Additionally, they control all supply, exhaust, and return air dampers, and provide the feedback of all required end-process verification. The I/A Series BACnet controllers monitor N.O. relay contacts of a UOJZ Listed fire alarm panel for automatic activation of the smoke-control sequences, and monitor UUKL Listed Firefighter’s Smoke Control Stations (FSCS) for manual activations and overrides. This example uses multiple ADI FSCSs that support the ADI ModBus interface to their respective MNB-1000 controllers. Each interface provides control of all of the FSCS’s visual and audible status indicators, as well as receipt of the FSCS’s override commands, eliminating the need to allocate numerous additional controllers to interface to the FSCS through individual I/O points.

Sequence of Operation

Normal HVAC Control

F-27419-2 TAC I/A Series MicroNet BACnet Smoke Control Systems Manual 47
Note: This application example assumes that each of the campus buildings are identical, therefore, the control equipment and sequences are the same for each building.
Under normal conditions, the central AHU for each building follows an occupied schedule that determines when the AHU operates. During the unoccupied mode, the outdoor and exhaust air dampers are in the full-closed position. The return air damper is in the full-open position. The supply and return fans are commanded OFF. During the occupied mode, the supply and return fans are commanded ON and the outdoor, exhaust, and return air dampers modulate as required to maintain a mixed air temperature setpoint. The central AHU can have a wide variety of additional control sequences that determine its operation and establish its operating priorities (for example, low limit stats and minimum outdoor air).
Page 64
Chapter 4
Each supply damper in a room consists of a terminal box controlled by an MNB-V2 and a dedicated motor-driven damper controlled by a digital output (DO) point from the same MNB-V2. The dedicated supply air damper remains in the full-open position at all times, unless commanded otherwise as a result of a smoke-control related condition. During normal, occupied mode conditions, the terminal box supply dampers maintain their respective zone temperature setpoints by modulating the primary air dampers and the hot water reheat. During the unoccupied mode, the terminal boxes either maintain their unoccupied zone temperature setpoints or drive to a fixed position.
Note: UL’s acceptance of the MNB-V1 and MNB-V2 controllers for UUKL is based on the assumption that negative pressurization of a smoke zone is considered accomplished when the total CFM flow supplied to the zone drops below 50% of its maximum with its dedicated exhaust damper fully open. If the damper’s response time is acceptable (less than 75 seconds) under this condition, and proper pressurization is achieved, dedicated supply air dampers are not necessary solely to meet response time requirements. In all cases, exhaust and supply air dampers should continue to be driven to their full-open and full-closed positions. The smoke-control system’s design and its associated specification will dictate whether additional requirements apply to the supply air dampers.
The exhaust air dampers associated with each room (smoke-control zone) are considered dedicated smoke-control systems. These dampers are always in the full-open position unless commanded otherwise due to a smoke-control situation. The dampers are controlled by digital output (DO) points from the MNB-V2 controllers in their respective zones.
The Fire Alarm Panel (i.e. Listed Fire Alarm Control Unit) is the primary indicator for fire alarm and smoke detector conditions. It is also the primary initiator of the automatic smoke or fire alarm sequence. Upon detection of smoke and/or fire, a set of contacts in the Fire Alarm Panel (for the zone affected) close, indicating to the building automation system that a smoke or fire condition exists. In this application, a smoke detector is provided for each room (smoke-control zone). The contacts from the Fire Alarm Panel for the associated smoke detectors are monitored by the FSCS’s MNB-1000 controllers. A single fire alarm panel may be located in a central building that handles all the remote buildings, or a separate fire alarm panel can be located in each protected building. The application of the panels is dependent upon the UL listings and NFPA 72 codes for which the panels are approved. In this application, a separate Fire Alarm Panel is located in each building. Check with the fire alarm panel’s manufacturer to determine which listings and approvals apply to the specific models. For additional information, refer to the applicable UL and NFPA 72 codes.
Note: Any UOJZ Listed fire alarm panel with programmable N.O. relay contacts can be used with I/A Series BACnet controllers.
The ADI Firefighter's Smoke Control Station (i.e. Listed Smoke Control Panel) is the primary indicator for the status of all smoke control and related HVAC equipment. It also provides the interface for manual activation commands and overrides for all smoke-control related equipment. An MNB-1000 controller is mounted internal to the FSCS and provides the ADI
TAC I/A Series MicroNet BACnet Smoke Control Systems Manual F-27419-2
48
Page 65
Campus Smoke Control
ModBus (control) interface to the FSCS. All commands issued from the FSCS are monitored and distributed throughout the network as required to implement the manual smoke-control sequences and overrides. The status of all of the smoke-control systems and equipment, as well as HVAC monitored trouble signals, are returned to the FSCS for visual indication, and in some cases, audible annunciation. Each MNB-1000 on an FSCS will be the central coordinator of all smoke-control activity for its respective building.
Note: Any UUKL Listed FSCS can be used with I/A Series BACnet controllers, but only the unit from Automation Displays, Inc. supports the ADI ModBus interface. When an FSCS from other vendors is used, many additional controllers will be required to provide the individual I/O point interfaces.
During normal operating conditions, the nondedicated smoke-control equipment does not require an automatic self-test since this equipment consists of HVAC components that are operated on a regular basis. The normal “comfort” level associated with the operability or inoperability of the equipment is considered an acceptable means of maintaining system integrity.
Dedicated smoke-control equipment, however, is used only when a smoke-control situation occurs, therefore an automatic weekly self-test of each dedicated smoke-control function is required. In this application, fan operation is verified using differential pressure sensors. The MNB-V2 damper position is verified by monitoring the cubic feet per minute (CFM) flow from the terminal box and/or its integral damper position feedback. Damper end switches are used to verify the end stroke of all dedicated supply and exhaust motor-driven dampers. All end process verifications of the dedicated zone dampers are monitored by UI points on the MNB-V2 controller associated with each zone. If a valid proof of each function occurs, no annunciation needs to take place. Otherwise, if the expected proof sensor does not operate as required, an audible trouble signal is generated and an LED is illuminated at the FSCS indicating the specific device that did not operate.

Smoke Control Sequences

F-27419-2 TAC I/A Series MicroNet BACnet Smoke Control Systems Manual 49
In this application, zoned smoke-control systems are used to implement the smoke-control strategies. Both dedicated and nondedicated smoke-control equipment are utilized as part of the zoned smoke-control systems.
Zoned smoke control divides a building into a number of zones for the purpose of inhibiting smoke movement. each other by smoke barriers. In the event of a fire, pressure differences and airflows produced by mechanical fans and operating dampers limit the smoke to the zone in which the fire originated.
In this application, each room on each floor of a building is considered a smoke-control zone. When smoke is detected in any zone, all of the nonsmoke zones that are contiguous to the smoke zone, and optionally, all
84.National Fire Protection Association, Inc., NFPA 92A, Standard for Smoke-Control Systems Utilizing Barriers and Pressure Differences, NFPA 92A, 2009 ed., chap. 5, para. 5.5.1.1.
85.NFPA 92A, 2009 ed., annex A, para. A.5.5.
84
The zones are separated from
85
Page 66
Chapter 4
nonsmoke zones in the building,86 are positively pressurized and the smoke is exhausted from the smoke zone. Pressurization of the noncontiguous (optional) smoke-control zones is dependent upon the smoke-control system design and its associated specification. Regardless of whether or not the noncontiguous smoke-control zones are positively pressurized, sufficient differential pressure must be achieved to limit smoke spread to the zone in which the fire originated.
Note: It is assumed that the smoke-control systems designer has considered all internal perimeters of the smoke-control zones such as corridors, restrooms, and closets. These internal perimeters require adequate pressurization that may not be achievable without supplementary fans or other mechanical equipment.
Anytime a smoke/fire detector trips, an automatic smoke-control sequence is initiated. For example, if the smoke/fire detector for Zone 6 of a building trips first, the automatic smoke-control sequence is initiated in the following manner.
1. The central AHU supply and return fans are commanded ON, the return air damper is driven to the full-closed position and the outdoor air and exhaust air dampers are driven to their full-open positions. This allows maximum outdoor air to be delivered to the nonsmoke zones. It also allows maximum exhausted air to be expelled from the zone reporting the smoke condition.
2. The dedicated exhaust air dampers for Zones 1, 2, 3, 5, 7, 9, 10, and 11 (zones contiguous to the smoke zone) are driven to the full-closed position while the exhaust air damper for Zone 6 (smoke zone) is driven to the full-open position. Optionally, the dedicated exhaust air dampers for the noncontiguous smoke-control zones may also be driven to the full-closed position.
3. The terminal box supply air damper and its associated dedicated supply damper for Zone 6 are driven to the full-closed position. This causes the smoke zone to become negatively pressurized.
Note: The UL acceptance of the MNB-V1 and MNB-V2 controllers for UUKL is based on the assumption that negative pressurization of a smoke zone is considered accomplished when the total CFM flow supplied to the zone drops below 50% of its maximum with its dedicated exhaust damper fully open. Sufficient differential pressure must be achieved to ensure smoke spread is confined to the zone in which the fire originated. In all cases, exhaust and supply air dampers should continue to be driven to their full-open and full-closed positions.
4. The terminal box supply air dampers and their associated dedicated supply dampers for Zones 1, 2, 3, 5, 7, 9, 10, and 11 (zones contiguous to the smoke zone) modulate open. The CFM flow supplied to these zones causes them to be positively pressurized. The terminal box supply dampers continue to modulate open until they reach the full-open position. Optionally, the terminal box supply air dampers for the noncontiguous smoke-control zones may also modulate open until their respective zones are positively pressurized.
86.NFPA 92A, 2009 ed., annex A, para. A.5.5.1.1.1.
TAC I/A Series MicroNet BACnet Smoke Control Systems Manual F-27419-2
50
Page 67
Campus Smoke Control
Note: The UL acceptance of the MNB-V1 and MNB-V2 controllers for UUKL is
based on the assumption that negative pressurization of a smoke zone is considered accomplished when the total CFM flow supplied to the zone drops below 50% of its maximum with its dedicated exhaust damper fully open. Sufficient differential pressure must be achieved to ensure smoke spread is confined to the zone in which the fire originated. In all cases, exhaust and supply air dampers should continue to be driven to their full-open and full-closed positions.
5. The automatic smoke-control sequence takes priority over the normal HVAC control sequences and any HVAC control overrides. Static pressure high limits and duct smoke detectors on supply air systems should not be automatically overridden.
6. Once the automatic activation has occurred, subsequent alarm signals that would normally initiate an automatic smoke-control sequence will annunciate only. (For example if, in addition to the Zone 6 smoke/fire detector, the Zone 10 detector also trips, no change to the smoke-control sequence occurs and the Zone 10 smoke condition also annunciates at the FSCS.)
87
7. At any time, the FSCS is capable of overriding either partially, or in full, any automatic activation of a smoke-control sequence that may be in process.
88
8. The communications between all of the I/A Series BACnet controllers that are part of the smoke-control sequences must be monitored. If the communications between any of these controllers fails at any time, the system trouble LED at the FSCS must illuminate and an audible signal must be generated.
89
9. If any of the smoke-control equipment proof sensors fail to operate within a specified period of time during the smoke-control sequence or when under control of the FSCS, the system trouble LED at the FSCS illuminates and an audible signal is generated. If the failed smoke-control equipment is dedicated, its associated trouble LED also illuminates.
Alternately, if the smoke/fire detector for Zone 10 trips first, the automatic smoke-control sequence is initiated in the following manner.
1. The central AHU supply and return fans are commanded ON, the return air damper is driven to the full-closed position and the outdoor air and exhaust air dampers are driven to their full-open positions. This allows maximum outdoor air to be delivered to the nonsmoke zones. It also allows maximum exhausted air to be expelled from the zone reporting the smoke condition.
2. The dedicated exhaust air dampers for Zones 5, 6, 7, 9, and 11 (zones contiguous to the smoke zone) are driven to the full-closed position while the exhaust air damper for Zone 10 (smoke zone) is driven to the full-open position. Optionally, the dedicated exhaust air dampers for the noncontiguous smoke-control zones may also be driven to the full-closed position.
87.NFPA 92A, 2009 ed., chap. 6, para’s 6.4.2 and 6.4.5.2.1.2.
88.NFPA 92A, 2009 ed., chap. 6, para 6.4.3.7.11.
89.UUnderwriters Laboratories Inc., UL 864, Control Units and Accessories for Fire Alarm
Systems, 9th ed. (2003), para’s 48.5, 49.4, 49.6, and 49.7.
F-27419-2 TAC I/A Series MicroNet BACnet Smoke Control Systems Manual 51
Page 68
Chapter 4
3. The terminal box supply air damper and its associated dedicated supply damper for Zone 10 are driven to the full-closed position. This causes the smoke zone to become negatively pressurized.
Note: The UL acceptance of the MNB-V1 and MNB-V2 controllers for UUKL is based on the assumption that negative pressurization of a smoke zone is considered accomplished when the total CFM flow supplied to the zone drops below 50% of its maximum with its dedicated exhaust damper fully open. Sufficient differential pressure must be achieved to ensure smoke spread is confined to the zone in which the fire originated. In all cases, exhaust and supply air dampers should continue to be driven to their full-open and full-closed positions.
4. The terminal box supply air dampers and their associated dedicated supply dampers for Zones 5, 6, 7, 9, and 11 (zones contiguous to the smoke zone) modulate open. The CFM flow supplied to these zones causes them to be positively pressurized. The terminal box supply dampers continue to modulate open until they reach the full-open position. Optionally, the terminal box supply air dampers for the noncontiguous smoke-control zones may also modulate open until their respective zones are positively pressurized.
Note: The UL acceptance of the MNB-V1 and MNB-V2 controllers for UUKL is based on the assumption that negative pressurization of a smoke zone is considered accomplished when the total CFM flow supplied to the zone drops below 50% of its maximum with its dedicated exhaust damper fully open. Sufficient differential pressure must be achieved to ensure smoke spread is confined to the zone in which the fire originated. In all cases, exhaust and supply air dampers should continue to be driven to their full-open and full-closed positions.
5. The automatic smoke-control sequence takes priority over the normal HVAC control sequences and any HVAC control overrides. Static pressure high limits and duct smoke detectors on supply air systems should not be automatically overridden.
90
6. Once automatic activation has occurred, subsequent alarm signals that would normally initiate an automatic smoke-control sequence will annunciate only. (For example if, in addition to the Zone 10 smoke/fire detector, the Zone 7 detector also trips, no change to the smoke-control sequence occurs and the Zone 7 smoke condition also annunciates at the FSCS.)
7. At any time, the FSCS is capable of overriding either partially, or in full, any automatic activation of a smoke-control sequence that may be in process.
91
8. The communications between all of the I/A Series BACnet controllers that are part of the smoke-control sequences must be monitored. If the communications between any of these controllers fails at any time, the system trouble LED at the FSCS must illuminate and an audible signal must be generated.
90.NFPA 92A, 2009 ed., chap. 6, para’s 6.4.2 and 6.4.5.2.1.2.
91.NFPA 92A, 2009 ed., chap. 6, para 6.4.3.7.11.
92.UL 864, 9th ed., para’s 48.5, 49.4, 49.6, and 49.7.
92
TAC I/A Series MicroNet BACnet Smoke Control Systems Manual F-27419-2
52
Page 69
Campus Smoke Control
9. If any of the smoke-control equipment proof sensors fail to operate within a specified period of time during the smoke-control sequence or when under control of the FSCS, the system trouble LED at the FSCS illuminates and an audible signal generates. If the failed smoke-control equipment is dedicated, its associated trouble LED also illuminates.

Smoke-Control System Configuration Schedule

Each smoke-control system configuration should be defined in a schedule.93 The schedule should list all dedicated and nondedicated smoke-control equipment and show the equipment response for each sensor that activates an automatic smoke-control sequence. An example schedule for this application is shown below (Table–4.1).
(Opn = Open, Clsd = Closed, “+” = Pos. Press., “-” = Neg. Press. F.O. = Full Open, F.C. = Full Closed, Terminal Box = VAV Box)
Note:
According to NFPA 92A, only the smoke zones that are contiguous to the
zone reporting the smoke condition have to be positively pressurized. For this application, all non-smoke zones are being positively pressurized.
Pressurization of the noncontiguous (optional) smoke-control zones is
dependent upon the smoke-control system design and its associated specification. Regardless of whether or not noncontiguous smoke-control zones are positively pressurized, sufficient differential pressure must be achieved to ensure smoke spread is confined to the zone in which the fire originated.
93.NFPA 92A, 2009 ed., chap. 6, para 6.4.5.3 and annex A, para A.6.4.5.3.
F-27419-2 TAC I/A Series MicroNet BACnet Smoke Control Systems Manual 53
Page 70
Chapter 4
Table–4.1 Schedule for Smoke-Control System Configuration .
Dedicated and
Nondedicated Smoke
Control Equipment
AHU Supply Fan ON ON ON ON ON ON ON ON ON ON ON ON AHU Return Fan OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF AHU O.A. Damper F.O. F.O. F.O. F.O. F.O. F.O. F.O. F.O. F.O. F.O. F.O. F.O. AHU Return Damper F.C. F.C. F.C. F.C. F.C. F.C. F.C. F.C. F.C. F.C. F.C. F.C. AHU Exhaust Damper F.C. F.C. F.C. F.C. F.C. F.C. F.C. F.C. F.C. F.C. F.C. F.C. Zone 1 Exhaust Damper Opn Clsd Clsd Clsd Clsd Clsd Clsd Clsd Clsd Clsd Clsd Clsd Zone 1 Supply Damper Clsd Opn Opn Opn Opn Opn Opn Opn Opn Opn Opn Opn Zone 1 VAV Box Supply Clsd Opn Opn Opn Opn Opn Opn Opn Opn Opn Opn Opn Zone 1 -+++++++++++ Zone 2 Exhaust Damper Clsd Opn Clsd Clsd Clsd Clsd Clsd Clsd Clsd Clsd Clsd Clsd Zone 2 Supply Damper Opn Clsd Opn Opn Opn Opn Opn Opn Opn Opn Opn Opn Zone 2 VAV Box Supply Opn Clsd Opn Opn Opn Opn Opn Opn Opn Opn Opn Opn Zone 2 + - ++++++++++ Zone 3 Exhaust Damper Clsd Clsd Opn Clsd Clsd Clsd Clsd Clsd Clsd Clsd Clsd Clsd Zone 3 Supply Damper Opn Opn Clsd Opn Opn Opn Opn Opn Opn Opn Opn Opn Zone 3 VAV Box Supply Opn Opn Clsd Opn Opn Opn Opn Opn Opn Opn Opn Opn Zone 3 ++ - +++++++++ Zone 4 Exhaust Damper Clsd Clsd Clsd Opn Clsd Clsd Clsd Clsd Clsd Clsd Clsd Clsd Zone 4 Supply Damper Opn Opn Opn Clsd Opn Opn Opn Opn Opn Opn Opn Opn Zone 4 VAV Box Supply Opn Opn Opn Clsd Opn Opn Opn Opn Opn Opn Opn Opn Zone 4 +++ - ++++++++ Zone 5 Exhaust Damper Clsd Clsd Clsd Clsd Opn Clsd Clsd Clsd Clsd Clsd Clsd Clsd Zone 5 Supply Damper Opn Opn Opn Opn Clsd Opn Opn Opn Opn Opn Opn Opn Zone 5 VAV Box Supply Opn Opn Opn Opn Clsd Opn Opn Opn Opn Opn Opn Opn Zone 5 ++++ - +++++++ Zone 6 Exhaust Damper Clsd Clsd Clsd Clsd Clsd Opn Clsd Clsd Clsd Clsd Clsd Clsd Zone 6 Supply Damper Opn Opn Opn Opn Opn Clsd Opn Opn Opn Opn Opn Opn Zone 6 VAV Box Supply Opn Opn Opn Opn Opn Clsd Opn Opn Opn Opn Opn Opn Zone 6 +++++ - ++++++ Zone 7 Exhaust Damper Clsd Clsd Clsd Clsd Clsd Clsd Opn Clsd Clsd Clsd Clsd Clsd Zone 7 Supply Damper Opn Opn Opn Opn Opn Opn Clsd Opn Opn Opn Opn Opn Zone 7 VAV Box Supply Opn Opn Opn Opn Opn Opn Clsd Opn Opn Opn Opn Opn Zone 7 ++++++ - +++++ Zone 8 Exhaust Damper Clsd Clsd Clsd Clsd Clsd Clsd Clsd Opn Clsd Clsd Clsd Clsd Zone 8 Supply Damper Opn Opn Opn Opn Opn Opn Opn Clsd Opn Opn Opn Opn Zone 8 VAV Box Supply Opn Opn Opn Opn Opn Opn Opn Clsd Opn Opn Opn Opn Zone 8 +++++++ - ++++ Zone 9 Exhaust Damper Clsd Clsd Clsd Clsd Clsd Clsd Clsd Clsd Opn Clsd Clsd Clsd Zone 9 Supply Damper Opn Opn Opn Opn Opn Opn Opn Opn Clsd Opn Opn Opn Zone 9 VAV Box Supply Opn Opn Opn Opn Opn Opn Opn Opn Clsd Opn Opn Opn Zone 9 ++++++++ - +++ Zone 10 Exhaust Damper Clsd Clsd Clsd Clsd Clsd Clsd Clsd Clsd Clsd Opn Clsd Clsd Zone 10 Supply Damper Opn Opn Opn Opn Opn Opn Opn Opn Opn Clsd Opn Opn Zone 10 VAV Box Supply Opn Opn Opn Opn Opn Opn Opn Opn Opn Clsd Opn Opn Zone 10 +++++++++ - ++ Zone 11 Exhaust Damper Clsd Clsd Clsd Clsd Clsd Clsd Clsd Clsd Clsd Clsd Opn Clsd Zone 11 Supply Damper Opn Opn Opn Opn Opn Opn Opn Opn Opn Opn Clsd Opn Zone 11 VAV Box Supply Opn Opn Opn Opn Opn Opn Opn Opn Opn Opn Clsd Opn Zone 11 ++++++++++- + Zone 12 Exhaust Damper Clsd Clsd Clsd Clsd Clsd Clsd Clsd Clsd Clsd Clsd Clsd Opn Zone 12 Supply Damper Opn Opn Opn Opn Opn Opn Opn Opn Opn Opn Opn Clsd Zone 12 VAV Box Supply Opn Opn Opn Opn Opn Opn Opn Opn Opn Opn Opn Clsd Zone 12 +++++++++++ -
123456789101112
Smoke Detector Zones In Alarm
TAC I/A Series MicroNet BACnet Smoke Control Systems Manual F-27419-2
54
Page 71

Firefighter’s Smoke Control Station (FSCS)

The requirements of the FSCS are similar to the ones shown in Chapter 2. The graphic depiction and smoke-control equipment used changes based on the sequence of operation for this application.

System Topologies

Campus Smoke Control

Campus Topology with MNB-1000 Controllers

The MNB-1000 (Instance 100) controller provides the central AHU control, monitors end process verification devices, distributes and receives global information between controllers in the network, monitors communications to all of the controllers beneath it, and initiates smoke-control sequences based on information received from the appropriate controllers (Figure–4.1). Its MS/TP communication trunk connects to the MNB-Vx controllers that provide HVAC control of the occupied spaces. These MNB-Vx controllers also control the dedicated supply and exhaust air smoke dampers to each smoke-control zone; and monitor the proof-of-position switches for the dedicated dampers.
The MNB-1000 (Instance 150) controller provides a complete interface to the FSCS through its EIA-485 (RS-485) ADI ModBus interface. It is mounted inside the FSCS, along with its power supply. This controller functions as the master of the smoke-control network in the building where it is installed. It monitors communications to all of the controllers that are part of the smoke-control system, distributes and receives global information between controllers in the network, and initiates smoke-control sequences based on information received from the appropriate controllers. Additionally, it’s UI and DI points interface to the N.O. contacts of the UOJZ Fire Alarm Panel to monitor each zone’s smoke or fire detector.
Note:
In this example application, all seven buildings have the same basic controller
requirements and topology. Therefore, the explanations describe only one building (Building 1) as a representative example.
To simplify the application, only a minimal number of controllers are shown for
each building. The actual number required depends on the actual size and programming complexity of the job.

Ethernet/IP Infrastructure

F-27419-2 TAC I/A Series MicroNet BACnet Smoke Control Systems Manual 55
Any UL 864 Listed IP infrastructure devices can be used to create the network topology. Currently, the only available units are the EIS8-100T and EIS6-100T/FT switching hubs from Contemporary Controls. The path through the Ethernet/IP network from any one UUKL device to another must use only UL 864 Listed infrastructure devices. The Ethernet/IP Smoke-Control System can coexist with the non-UL 864 networks, as long as they are isolated from those networks through the use of UL 864 Listed IP infrastructure devices. Refer to Chapter 5,
Restrictions and General Comments, for additional information. In this example
(Figure–4.1 and Figure–4.2), the fiber optic feature of the EIS6-100T/FT switching
Page 72
Chapter 4
hubs is used to connect the individual buildings, thus creating a fiber backbone. Once inside a building, the smoke-control system’s infrastructure is expanded through the use of EIS8-100T switching hubs.
Note: At no time can any smoke control signals be passed over the public Internet.
Wiring Requirements
Because the I/O wiring between the I/A Series BACnet controllers and the FSCS (when an I/O wiring interface is used) and the UOJZ Fire Alarm Panel is unsupervised, the I/A Series BACnet controllers used for this purpose must be mounted within 20 ft of the panel to which they are connected. The I/O wiring must be run in conduit. Table–4.2, below, lists the general requirements for the wiring associated with an I/A Series BACnet smoke-control application.
Table–4.2 Wiring Requirements.
Wiring Status
Ethernet/IP Supervised by block programming
Supervised by block programming. When MNB-1000 is mounted external to the
EIA-485 ADI ModBus
MS/TP Bus Supervised by block programming
I/O to FSCS
I/O to UOJZ FAP Contacts
Remaining I/O Unsupervised
FSCS, wiring must be run in conduit and controller must be located within 20 ft. of the panel.
Unsupervised, wiring must be run in conduit and controllers must be located within 20 ft. of the panel.
Unsupervised, wiring must be run in conduit and controllers must be located within 20 ft. of the panel.

Central System Interface and Overlay Devices

When a UNC, Web Server, and/or other central-system type interfaces are attached to the Ethernet/IP network with the ability to access the smoke-control system, they must be isolated from the network through the use of UL 864 Listed IP infrastructure devices (Figure–4.2). This isolation is required by UL because these devices, PC’s and/or interfaces, are not UL 864 Listed. Therefore these devices cannot be used for smoke-control purposes.
Refer to Chapter 5, Restrictions and General Comments, for additional information.
TAC I/A Series MicroNet BACnet Smoke Control Systems Manual F-27419-2
56
Page 73
Campus Smoke Control
Figure–4.1 Campus Topology with MNB-1000 Controllers.
To MNB-1000 on FSCS
and additional UUKL
MNB-1000
Instance=400
To MNB-1000 on FSCS
and additional UUKL
MNB-1000
Instance=300
To MNB-1000 on FSCS
and additional UUKL
MNB-1000
Instance=200
controllers
EOL JPR
MS/TP Bus
(EIA-485)
controllers
EOL JPR
MS/TP Bus
(EIA-485)
controllers
EOL JPR
MS/TP Bus
(EIA-485)
EIS6-100T/FT Switching Hub
EIS6-100T/FT Switching Hub
EIS6-100T/FT Switching Hub
Building 4 - Administration
To remainder of building's IT network that is not UUKL
FSCS
FAP
Building 3
To remainder of building's IT network that is
not UUKL
FSCS
and
FAP
Building 2
To remainder of building's IT network that is
not UUKL
FSCS
and
FAP
1
1
1
Building 5
To remainder of building's IT network that is not UUKL
FSCS
and
FAP
Building 6
To remainder of building's IT network that is not UUKL
FSCS
and
FAP
EOL JPR End-of-line resistor and/or bias resistors
and
are engaged through on-board jumpers
Note: Only specific UL wiring and installation
requirements are shown. For complete installation and wiring requirements, refer to the I/A Series MicroNet BACnet
Wiring and Networking Practices Guide, F-27360, and other appropriate
documentation listed in Appendix C.
To MNB-1000 on FSCS
and additional UUKL
controllers
EOL JPR
EIS6-100T/FT Switching Hub
EIS6-100T/FT Switching Hub
MS/TP Bus
(EIA-485)
To MNB-1000 on FSCS
and additional UUKL
controllers
EOL JPR
MS/TP Bus
(EIA-485)
Key
MNB-1000 Instance=500
MNB-1000 Instance=600
To MNB-1000 on FSCS
and additional UUKL
MNB-1000
Instance=100
controllers
EOL JPR
MS/TP Bus
(EIA-485)
EIS6-100T/FT Switching Hub
Building 1
To remainder of building's IT network that is
not UUKL
FSCS
and
FAP
Building 7
To remainder of building's IT network that is not UUKL
1
FSCS
and
FAP
1 In the example shown here, the communications
connections between buildings use fiber optic cabling, for lightning protection.
To MNB-1000 on FSCS
and additional UUKL
EIS6-100T/FT Switching Hub
controllers
EOL JPR
MS/TP Bus
(EIA-485)
MNB-1000 Instance=700
F-27419-2 TAC I/A Series MicroNet BACnet Smoke Control Systems Manual 57
Page 74
Chapter 4
Note: All references to the MNB-V1 equally apply to
the MNB-V1-2 and all references to the MNB-V2 equally apply to the MNB-V2-2.
Ethernet/IP
Ethernet/IP
Ethernet/IP
Web Access-1 (Internet Explorer)
Web Access-2
(Internet Explorer)
To remainder of
building's IT
network that is
not UUKL
To Any additional
controllers that are
part of the UUKL
control system
UNC-1 (UNC-520-2) Instance=5000
EIS8-100T
Switching Hub
EIS6-100T/FT
Switching Hub
2
1
1
3
3
3
4
I/O
MNB-1000 Instance=100 MS/TP Addr=0
To Building 1 AHU
control and end
process verification
devices
4
5
6
EOL JPR
EOL JPR
MNB-1000
Instance=150
To FSCS
4
5
6
2
3
4
1 At no time can any smoke control signals be passed over
the public Internet.
2 The UL 864 Ethernet switches shown must be installed in
UL 50 enclosures.
3 The UL 864 Listed Ethernet switches can be used to
provide isolation of non-UUKL devices from the UUKL Ethernet network. Refer to Chapter 5, "Restrictions and General Comments," for additional information regarding the use of Ethernet/IP networks and approved devices.
4 The path through the Ethernet/IP network from any one
UUKL device to another must only use UL 864 Listed Ethernet/IP infrastructure devices.
5 All UUKL controllers must be mounted in approved
enclosures. Refer to Chapter 5, "Restrictions and General Comments," for additional information.
6 See "Wiring Requirements" in this chapter.
7 The ADI ModBus interface to the ADI FSCS uses the
Remote I/O Bus of the MNB-1000, not the MSTP Bus.
8 Remote I/O Bus wiring must adhere to the installation
requirements defined in Chapter 5, "Restrictions and General Comments"
To MNB-V2
Instance=101
NW #1
To next building
From previous building
Fiber Optic Trunks
Remote I/O Bus (EIA-485, ADI ModBus)
7
8
Key
EOL JPR End-of-line resistor and/or bias resistors
are engaged through on-board jumpers.
Remote I/O Inputs and outputs remotely provided by
the ADI ModBus interface. The Remote I/O Port refers to the top EIA-485 port on the MNB-1000.
I/O Discrete input and output wiring to or
from controlled or monitored devices.
NW Network
Remote I/O Port (ADI)
Figure–4.2 Ethernet/IP Network Topology—Typical of Each Building.
TAC I/A Series MicroNet BACnet Smoke Control Systems Manual F-27419-2
58
Page 75
Campus Smoke Control

MNB-V2 Topology

Each building has a central AHU that serves the entire building and is controlled by an MNB-1000. Each room has an MNB-V2 that controls the VAV terminal box (Figure–4.3). During normal occupied conditions, each MNB-V2 modulates its primary damper and the hot water reheat, as required, to maintain its zone temperature setpoint. During the unoccupied mode, each terminal box either maintains its respective unoccupied zone temperature setpoint or is driven to a fixed position. Each room on a floor is considered a smoke-control zone. By controlling the VAV box, the MNB-V2 controls the supply air to each zone. A dedicated exhaust damper is required for each smoke-control zone and is controlled by a spare DO point from the MNB-V2 serving its zone. The dedicated exhaust dampers are always in the full-open position unless commanded otherwise due to a smoke-control condition.
In this example, each smoke-control zone shows a dedicated supply damper that is controlled by another spare DO point from the same MNB-V2. The dedicated supply dampers remain in the full-open position at all times, unless commanded otherwise as a result of a smoke-control related condition. This building layout is typical for all the buildings on the campus.
Note: UL’s acceptance of the MNB-V1 and MNB-V2 controllers for UUKL is based on the assumption that negative pressurization of a smoke zone is considered accomplished when the total CFM flow supplied to the zone drops below 50% of its maximum with its dedicated exhaust damper fully open. If the damper’s response time is acceptable (less than 75 seconds) under this condition, and proper pressurization is achieved, dedicated supply air dampers are not necessary solely to meet response time requirements. In all cases, exhaust and supply air dampers should continue to be driven to their full-open and full-closed positions. The smoke-control system’s design and its associated specification will dictate whether additional requirements apply to the supply air dampers.
Damper end switches are used to verify the end stroke of all dedicated supply and exhaust motor-driven dampers. All end process verification of the dedicated zone dampers is monitored by UI points on the MNB-V2 controller associated with each zone.
MS/TP Bus Requirements
A repeater is required for the MS/TP bus whenever there is a need to extend the maximum distance of the bus or increase the number of devices that can be connected to the bus. The B-LINK-AC repeater can be used for this purpose.
Refer to Chapter 5, Restrictions and General Comments for additional repeater information.
F-27419-2 TAC I/A Series MicroNet BACnet Smoke Control Systems Manual 59
Page 76
Chapter 4
1st
Floor
2nd
Floor
3rd
Floor
Building Air Handling Unit
Exhaust Air
Damper
Outside Air
Damper
Supply FanReturn Fan
Return Air Damper
Zone 7
Supply Air
Damper
MNB-V2
Zone 6
Supply Air
Damper
MNB-V2
Zone 5
Supply Air
Damper
Exhaust Damper
Exhaust Damper
Exhaust Damper
Exhaust Damper
Exhaust Damper
Exhaust Damper
Exhaust Damper
Exhaust Damper
Exhaust Damper
Exhaust Damper
Exhaust Damper
Exhaust Damper
MNB-V2
Zone 8
Supply Air
Damper
MNB-V2
Zone 11
Supply Air
Damper
MNB-V2
Zone 10
Supply Air
Damper
MNB-V2
Zone 9
Supply Air
Damper
MNB-V2
Zone 12
Supply Air
Damper
MNB-V2
Zone 3
Supply Air
Damper
MNB-V2
Zone 2
Supply Air
Damper
MNB-V2
Zone 1
Supply Air
Damper
MNB-V2
Zone 4
Supply Air
Damper
MNB-V2
MNB-1000
Note: All references to the MNB-V1 equally apply to the MNB-V1-2 and all
references to the MNB-V2 equally apply to the MNB-V2-2.
Figure–4.3 Typical Building Topology.
60
TAC I/A Series MicroNet BACnet Smoke Control Systems Manual F-27419-2
Page 77
Campus Smoke Control

MNB-1000 Interface to FSCS

In a multi-building application such as this, a separate FSCS is typically required for each protected premises or building. The following description is typical of each building, with the only difference being the controller instance numbers.
The MNB-1000 (Instance 150) controller (Building 1) provides a complete interface to the FSCS through its EIA-485 (RS-485) ADI ModBus interface (Figure–4.4). It controls all of the FSCS LEDs and monitors all of the FSCS override switches. The FSCS (panel) Enable switch functionality is also enforced through programming in the MNB-1000 controller. Refer to Chapter 5, Restrictions and General Comments for for an example of this programming and for additional information on the FSCS interface.
When interfaced to the ADI FSCS, the MNB-1000 controller and its power supply are mounted inside the FSCS enclosure, eliminating the need for separate enclosures. This controller functions as the master of the smoke-control network for the building where it is installed. One master exists in each building. It monitors communications to all of the controllers that are part of the smoke-control system, distributes and receives global information between controllers in the network, initiates smoke-control sequences based on information received from the appropriate controllers, and integrates the FSCS functionality into the system.
Note: When using I/O points to interface to a UL 864 UUKL/UUKL7 Listed FSCS in place of using an ADI FSCS that supports the ADI ModBus protocol, many additional controllers will be required. Each installation must be carefully assessed to ensure that adequate quantities of devices have been allotted to perform the necessary control and monitoring functions. Refer to "Job Estimating" on page 78 for point calculating specifics.
F-27419-2 TAC I/A Series MicroNet BACnet Smoke Control Systems Manual 61
Page 78
Chapter 4
EOL
To MNB-1000
(Instance=100)
Key
EOL End-of-line resistor, 120 Ω (part
number EMSC-546)
*
See "MS/TP Requirements" in
this chapter.
Smoke Control Zone 9Smoke Control Zone 10Smoke Control Zone 11Smoke Control Zone 12
MNB-V2
Instance=1012
MS/TP Addr=12
MNB-V2
Instance=1011
MS/TP Addr=11
MNB-V2
Instance=1010
MS/TP Addr=10
MNB-V2
Instance=109
MS/TP Addr=9
Smoke Control Zone 5Smoke Control Zone 6Smoke Control Zone 7Smoke Control Zone 8
MNB-V2
Instance=108
MS/TP Addr=8
MNB-V2
Instance=107
MS/TP Addr=7
MNB-V2
Instance=106
MS/TP Addr=6
MNB-V2
Instance=105
MS/TP Addr=5
Smoke Control Zone 1Smoke Control Zone 2Smoke Control Zone 3Smoke Control Zone 4
MNB-V2
Instance=104
MS/TP Addr=4
MNB-V2
Instance=103
MS/TP Addr=3
MNB-V2
Instance=102
MS/TP Addr=2
MNB-V2
Instance=101
MS/TP Addr=1
Floor 1
Floor 2
Floor 3
MS/TP Bus
*
Note: Only specific UL wiring and installation requirements
are shown. For complete installation and wiring requirements, refer to the I/A Series MicroNet BACnet Wiring and Networking Practices Guide, F-27360, and other appropriate documentation listed in Appendix C.
Note: All references to the MNB-V1 equally apply to the
MNB-V1-2 and all references to the MNB-V2 equally apply to the MNB-V2-2.
Figure–4.4 MNB-V2 Controller Topology—Typical of Each Building.
TAC I/A Series MicroNet BACnet Smoke Control Systems Manual F-27419-2
62
Page 79
Campus Smoke Control

Fire Alarm Panel Interface

In this application, a separate Fire Alarm Panel (FAP) is located in each building. Alternatively, a single FAP panel that handles all of the remote buildings may be located in a central building, instead. The manner in which the FAPs are applied is dependent upon the UL Listing and NFPA 72 codes for which the panels are approved. Check with the FAP manufacturer to determine which listings and approvals apply to specific models. For additional information, refer to the applicable UL and NFPA codes. The following description is typical of each building.
In Building 1, the UOJZ Listed N.O. contacts from the Fire Alarm Panel are wired directly to contact inputs of the FSCS MNB-1000 (Figure–4.5). When this option is used, the FSCS and the FAP device supplying the contacts must be mounted within 20 ft. of each other, and the I/O wiring must be run in conduit because the I/O wiring is unsupervised.
When the FAP is interfaced to the FSCS MNB-1000 in this manner, the statuses of the smoke alarms are received by the MNB-1000 (Instance 150) controller through its I/O points and distributed throughout the network, as required, to support the smoke-control sequence.
Note: When using controller I/O points to interface to UOJZ Listed N.O. contacts from a Fire Alarm Panel, several additional controllers will be required. Each installation must be carefully assessed to ensure that adequate quantities of devices have been allotted to perform the necessary control and monitoring functions. Refer to "Job Estimating" on page 78 for point calculating specifics.

Comments

Always refer to the NFPA 92A, NFPA 72, and UL 864 UUKL/UUKL7 standards for additional Smoke-Control Systems information. Additionally, general system application comments and restrictions are provided in Chapter 5, Restrictions and General Comments. This chapter should be thoroughly reviewed to ensure compliance with the UL listing. It is the responsibility of the field office to work with the smoke-control system designer and gain the smoke-control system approval from the Authority Having Jurisdiction (AHJ).
F-27419-2 TAC I/A Series MicroNet BACnet Smoke Control Systems Manual 63
Page 80
2
UOJZ Listed
Fire Alarm Panel
SD
SD
SD
SD
SD
SD
Zone 1 Smoke Alarm
Zone 2 Smoke Alarm
Zone 3 Smoke Alarm
Zone 4 Smoke Alarm
Zone 5 Smoke Alarm
Zone 6 Smoke Alarm
SD
SD
SD
SD
SD
SD
Zone 7 Smoke Alarm
Zone 8 Smoke Alarm
Zone 9 Smoke Alarm
Zone 10 Smoke Alarm
Zone 11 Smoke Alarm
Zone 12 Smoke Alarm
Note: Only specific UL wiring and installation requirements
are shown. For complete installation and wiring requirements, refer to the I/A Series MicroNet BACnet Wiring and Networking Practices Guide, F-27360, and other appropriate documentation listed in Appendix C.
Key
EOL JPRa End-of-line resistor is engaged through an on-board
jumper on the MNB-1000. Refer to the MicroNet
BACnet MNB-1000 Plant Controller Installation Instructions, F-27347, for additional information.
EOL JPRb End-of-line resistor is engaged through an on-board
jumper on the FSCS. Refer to the documentation shipped with the unit.
Remote I/O Inputs and outputs remotely provided by the ADI
ModBus interface. The Remote I/O Port refers to the top EIA-485 port on the MNB-1000.
I/O Discrete input and output wiring to or from controlled
or monitored devices.
1 In this example, the MNB-1000 controller shown is
mounted inside the ADI FSCS enclosure, along with its dedicated power supply. This is an option that can be specified when ordering the ADI FSCS. Refer to Chapter 5, "Restrictions and General Comments," for additional information regarding the FSCS.
2 The UOJZ Listed N.O. contacts from the Fire Alarm
Panel (FAP) are wired directly to contact inputs of the FSCS MNB-1000 controller. When this option is used, the FSCS and the FAP device with the contacts must be mounted within 20 ft. of each other, and the I/O wiring must be run in conduit because the I/O wiring is unsupervised.
3 All UUKL controllers must be mounted inside approved
enclosures. Refer to Chapter 5, "Restrictions and General Comments" for additional information. When the ADI FSCS is ordered with the MNB-1000 and its power supply mounted internally, no additional enclosures are required.
4 The path through the Ethernet/IP network from any one
UUKL device to another must only use UL 864 Listed Ethernet/IP infrastructure devices.
5 If individual controllers use hard-wired I/O points to
interface to the FSCS, these controllers must be mounted within 20 ft. of the FAP, and the I/O wiring must be run in conduit because the I/O wiring is unsupervised.
6 The ADI ModBus interface to the ADI FSCS uses the
Remote I/O Bus of the MNB-1000, not the MSTP Bus.
7 Remote I/O Bus wiring must adhere to the installation
requirements defined in Chapter 5, "Restrictions and General Comments".
EOL
JPRb
Remote I/O Bus
(EIA-485, ADI ModBus)
EOL JPRa
1
3
5
6
7
4
To available port
on UL 864 Listed
Ethernet/IP
Switching Hub
I/O
I/O
1st
Floor
2nd
Floor
3rd
Floor
Exhaust Air
Damper
Outside Air
Damper
Supply FanReturn Fan
Return Air Damper
Exhaust Air
Damper
Supply Air
Damper
Exhaust Air
Damper
Supply Air
Damper
Exhaust Air
Damper
Supply Air
Damper
Exhaust Air
Damper
Supply Air
Damper
Exhaust Air
Damper
Supply Air
Damper
Exhaust Air
Damper
Supply Air
Damper
Exhaust Air
Damper
Supply Air
Damper
Exhaust Air
Damper
Supply Air
Damper
Exhaust Air
Damper
Supply Air
Damper
Exhaust Air
Damper
Supply Air
Damper
Exhaust Air
Damper
Supply Air
Damper
Exhaust Air
Damper
Supply Air
Damper
Smoke Control Panel
Zone 5Zone 6Zone 7Zone 8
Zone 1Zone 2Zone 3Zone 4
Zone 9
Zone 10Zone 11Zone 12
Remote I/O Port (ADI)
MNB-1000
Instance=150
Figure–4.5 FSCS Interface—UOJZ Fire Alarm Panel Interface and Related MNB-1000 Controller.
Chapter 4
TAC I/A Series MicroNet BACnet Smoke Control Systems Manual F-27419-2
64
Page 81
Chapter 5 Restrictions and General Comments

Purpose

This chapter lists restrictions associated with the application of I/A Series MicroNet BACnet controllers to UL 864 UUKL/UUKL7 smoke-control systems. These restrictions take precedence over existing I/A Series BACnet literature and are required to meet the UL 864 UUKL/UUKL7 Listing. This chapter also includes general comments that may provide additional insight or flexibility during the engineering process.

Restrictions

Software Access Levels

There are three primary tools used with I/A Series MicroNet BACnet controllers: Flow Balance Tool, Commissioning Tool, and WorkPlace Tech Tool (WP Tech).
Flow Balance Tool and Commissioning Tool
The Flow Balance Tool and Commissioning Tool use their own, built-in, dual-level security configuration. Whenever either of these tools is used on a UUKL job site, the security must be configured and enabled. The two access levels are:
Manager Level: Anyone with manager-level access is considered to be at the “programmer” level and not a “day-to-day operator”.
User Level: Anyone with user-level access is considered to be a “day-to-day operator”. Typical changes made by the “day-to-day operator” will not affect the smoke-control sequence.
For each access level, a password of at least five characters must be assigned, "Auto-lock" must be enabled, and the "Auto-lock" time period must be set at 30 minutes or less. The "Auto-lock" time period defines the period of inactivity that must pass before the tool locks access to the program. When the program is locked in this way, the user or manager must log back into the system before operation can resume.
F-27419-2 TAC I/A Series MicroNet BACnet Smoke Control Systems Manual 65
Page 82
Chapter 5
WorkPlace Tech Tool
When using or leaving WP Tech at a UUKL job site, its security feature must be configured and enabled through the Commissioning Tool. When using the security feature with WP Tech, the following apply:
The “Auto-lock” feature is not available.
Only the manager level of access is valid. Users are not allowed to start
WP Tech.
The “Auto-lock” feature associated with the manager level must be configured
and handled by the Windows
When running WP Tech at the job site, a dedicated Windows be used. To define the password protection and “Auto-lock” aspects of each user account, right-click the Windows desktop, and then use the Screen Saver tab of the Windows Desktop Properties dialog box. Each account used for this purpose must have a password of at least five characters, have "Auto-lock" enabled, and have an "Auto-lock" time period of 30 minutes or less. These accounts must not be used for any other purpose.
®
account used by the individual.
user account must

System Overrides

Overrides that Require Removal
If a person with manager-level (programmer-level) access overrides any values or functions in the I/A Series BACnet controllers, in a manner that impedes the automatic smoke-control functions or interferes with the FSCS’s absolutely highest priority control over the system, then the overrides must be removed before the system is returned to normal operation. This rule always applies, whether the purpose of the override is for troubleshooting, service, programming, or temporary control.
Overrides that Do Not Require Removal
Overrides do not need to be removed before the system is returned to normal operation if they are initiated in a manner that does not impact the automatic smoke-control functions or the ability of the FSCS to have absolutely highest priority control over the system. Such overrides can be considered exceptions to the restriction described above, in Overrides that Require Removal.
This exception is only applicable if all automatic smoke-control functions are commanded through the BACnet priority level of “Automatic Life Safety (2)”, and all FSCS commands are commanded through the BACnet priority level of “Manual Life Safety (1)”.
Examples of these types of overrides include those initiated by any BACnet device or tool, at a priority below the “Automatic Life Safety” level.
Input Priority Levels: In a BACnet input name, the numeral in brackets signifies the level of priority. For example, the input name that the input, “Manual Life Safety,” has the highest BACnet priority level. “Automatic Life Safety (2)” means that this input has the second-highest priority level, and so forth.
Manual Life Safety (1)” means
TAC I/A Series MicroNet BACnet Smoke Control Systems Manual F-27419-2
66
Page 83
Restrictions and General Comments

Approved Fire Alarm Panels

Approved Firefighter’s Smoke Control Stations

Any UOJZ listed fire alarm panel with programmable N.O. relay contacts can be used with I/A Series BACnet controllers. The fire alarm panel (i.e. listed Fire Alarm Control Unit) is the primary indicator for smoke and fire alarm conditions. These panels are listed for the UOJZ category of the UL 864 standard. The dry contact outputs from the UOJZ listed fire alarm panel can be wired directly to the appropriate inputs of the I/A Series MicroNet BACnet controllers, or to inputs provided on the UUKL listed Firefighter’s Smoke Control Station (FSCS).
Any UUKL listed Firefighter’s Smoke Control Station (FSCS) can be used with I/A Series BACnet controllers. The FSCS (i.e. listed Smoke Control Panel) is the primary indicator for the status of all smoke control and related HVAC equipment. The FSCS also provides the interface for manual activation commands and overrides for all smoke control and related HVAC equipment. The FSCS is listed for the UUKL category of the UL 864 standard.
The Automation Displays, Inc. (ADI) series of graphic smoke-control panels are UUKL listed and can be used for smoke-control applications. They can be equipped with terminals that allow wiring to discrete I/O points, an ADI ModBus EIA-485 (RS-485) interface for controllers that support the ADI ModBus interface, or a hybrid of the two. If the ADI ModBus EIA-485 version is used with an MNB-1000 controller (which supports the ADI ModBus interface), the combination can take advantage of reduced I/O count requirements, reduced engineering and installation time, and use of the WP Tech ADI Wizard to expedite the process of FSCS and BACnet point creation in the application database.
Note: WP Tech ADI Wizard
The ADI Wizard, used in concert with the LED/Switch definition file (generated during the FSCS specification/ordering phase), provides the following productivity advantages:
Automatic creation of all LED and Switch objects.
Automatic naming of all ADI point objects, in accordance with specification
requirements.
Automatic configuration of the LED and Switch (ADI ModBus) bank and
register data.
Configuration of all ADI ModBus communication-related parameters.
Global and individual changes to the Switch output format (ON-OFF or
ON-NA).
Global and individual changes to Switch-enabled statuses for interlocking to
the FSCS Enable switch.
Drag-and-drop functionality on any page of a WP Tech application drawing.
Unique BACnet objects are automatically created for all ADI objects.
When using an ADI FSCS, the I/A Series BACnet Controllers and their transformers can be mounted either inside or outside the FSCS. If the controllers and transformers are mounted internally, they can be supplied to the FSCS vendor for pre-installation and wiring. If the controllers and transformers are to be mounted externally, they must comply with the installation requirements detailed throughout this manual and in the documentation listed in Appendix C.
F-27419-2 TAC I/A Series MicroNet BACnet Smoke Control Systems Manual 67
Page 84
Chapter 5
When ordering an ADI FSCS, it is necessary, as a minimum, to provide the vendor with the information listed below. Note that this list is provided only as a guide for organizing the process. The actual requirements must be worked out with the vendor.
A detailed drawing of the graphic required.
Switch quantities, types, locations, and related label text (if any).
LED quantities, locations, colors, and related label text (if any).
A spreadsheet listing the name (20 characters or less) of each LED and
switch position point, and their related descriptions. Note that this information is also used by the ADI Wizard to expedite the point creation process in WP Tech.
Panel size and any other requirements affecting the FSCS’s physical
construction.
Supporting dimensions and wiring diagrams associated with any controllers
and transformers that will be mounted inside the FSCS.
Whether the FSCS is to be supplied with terminals for wiring to discrete I/O
points, an ADI ModBus EIA-485 interface for controllers that support the ADI ModBus interface, or a hybrid of the two.
When applying the ADI FSCS to the I/A Series BACnet Smoke-Control System, certain programming must be implemented by the control applications to meet the requirements of UL 864 UUKL/UUKL7. Examples of this programming are shown in Figure–5.1 and Figure–5.2.
Figure–5.1 shows a method for implementing support for the FSCS Enable switch, required by UL 864 UUKL/UUKL7. When the switch is in the disabled position, it disables all switch inputs to the FSCS and turns OFF the LED associated with the FSCS Enable switch. As can be seen in the figure, the FSCS Enable and Alarm Silence switch inputs are always enabled, indicated by the green triangle present at the left side of their resource tags. This aspect of each switch is established through the use of the ADI Wizard. The figure also shows an example of the support required for the System Trouble Alarm Silence input from the FSCS.
Figure–5.2 shows an example of a method for implementing support for the System Trouble Annunciation (visual and audible), required by UL 864 UUKL/UUKL7. All individual smoke-control functions that must annunciate a system trouble, as well as lost communications to any smoke-control device, are logically “OR’d” together to generate a single System Trouble signal. This output controls the System Trouble LED at the FSCS. Depending upon the type of FSCS interface being used, this output can either go directly to the ADI ModBus interface resource tags associated with the FSCS, or control a discrete DO point tied to the FSCS. Refer to "Lost Communications" on page 80 for hardware and FSCS requirements for controlling the System Trouble LED.
TAC I/A Series MicroNet BACnet Smoke Control Systems Manual F-27419-2
68
Page 85
Inputs from FSCS (Switches)
Outputs to FSCS (LEDs)
Figure–5.1 FSCS Enable, System Trouble Alarm Silence, and FSCS Communication Status
Restrictions and General Comments
F-27419-2 TAC I/A Series MicroNet BACnet Smoke Control Systems Manual 69
Page 86
Chapter 5
Figure–5.2 Device Communication Status and System Trouble Annunciation
System Trouble Annunciation
Device Communication Status
TAC I/A Series MicroNet BACnet Smoke Control Systems Manual F-27419-2
70
Page 87
Restrictions and General Comments
Figure–5.3 IP/Ethernet UL 864 Listed Infrastructure Devices and Isolation.

Approved IP/Ethernet Infrastructure Devices

3
4
5
Ethernet/IP Ethernet/IP
2
8
3
4
5
Commissioning Tool
MNB-1000
2
RJ-45
Jack
To MS/TP Bus
(EIA-485)
UNC-1
RJ-45
Jack
3
5
Two IP/Ethernet switches have been identified as UL 864 Listed and can be used with the I/A Series BACnet MicroNet Smoke-Control System when constructing the IP/Ethernet infrastructure. These switches are shown in Appendix B. The EIS8-100T provides eight 10/100 Mbps RJ-45 ports.
Enterprise Server, WorkPlace Pro, Workbench and/or Web Browser
To rest of Building
1
EIS8-100T Switching Hub
6
WP Tech and/or
1 At no time can any smoke control signals be
2 When you follow the path from one UL 864
3 Non-UUKL (UL 864) IP/Ethernet devices can
4 All isolated devices that utilize a computer must
IT Network that is not UUKL
3
4
5
24 Vac
Enterprise Server,
WorkPlace Pro, Workbench
and/or Web Browser
RJ-45
Jack
MNB-1000
To MS/TP Bus
(EIA-485)
passed over the public Internet.
UUKL device to any other UL 864 UUKL/UUKL7 device, the path must consist of only UL 864 Listed devices.
be connected to the network, but must be isolated from the network through the use of a UL 864 Listed IP/Ethernet infrastructure device, or through connection to a port on one of these devices. Devices such as the UNC-5xx and/or ENC-5xx, as well as PCs running WorkPlace Tech, WorkPlace Tech Commissioning Tool, Enterprise Server, WorkPlace Pro, Workbench, Web browsers, etc. are examples of devices that fall into this category.
be Information Technology Equipment (ITE) or UL 60950 Listed, and should bear the respective UL marking.
WorkPlace Pro, Workbench
To any additional EIS
Switches that have
controllers that are
2
Enterprise Server,
and/or Web Browser
part of the UUKL
control system
2
8
RJ-45
Jack
MNB-1000
To MS/TP Bus
(EIA-485)
5 Devices such as the UNC-5xx and/or ENC-5xx, as
well as PCs running WorkPlace Tech, WorkPlace Tech Commissioning Tool, Enterprise Server, WorkPlace Pro, Workbench, Web browsers, etc. can only be used as “overlay” devices. They cannot be used for smoke control purposes or, through their use, interfere with the smoke control process.
6 Any of the appropriately sized transformers listed in
Appendix B can be used to power the EIS8-100T and EIS6-100T/FT IP/Ethernet switches shown. For additional installation instructions and cabling requirements, refer to the EISwitch Installation Guide associated with the product.
7 The fiber optic ports associated with the switches
can be used in the same manner as the wire ports to support extension of the IP/Ethernet network, or to provide isolation. Additionally, the fiber optic ports can be used when it is necessary to run the IP/Ethernet network between buildings, in accordance with the “UL-1459 (Abnormal Overvoltage) Compliance” section.
8 The IP/Ethernet infrastructure devices must be
mounted in approved UL enclosures. See the “Enclosures” section for more details.
EIS6-100T/FT Switching Hub
7
6
2
3
24 Vac
ENC-2
4
1
5
RJ-45 Jack
3
5
F-27419-2 TAC I/A Series MicroNet BACnet Smoke Control Systems Manual 71
Page 88
Chapter 5

Approved MS/TP Repeaters

When selecting an MS/TP repeater for use in a UUKL smoke-control system, be sure to consider the following:
Generally speaking, a UL 864-approved MS/TP repeater can be used
on a UUKL smoke-control system’s MS/TP bus to either extend wire distance, increase the number of devices allowed (when applicable), or both.
In most cases, the UL 864-approved MS/TP repeater will be used on a
UUKL smoke-control system to isolate the UUKL Listed controllers from those that are not listed.
When a repeater will be used with I/A Series BACnet MicroNet
controllers in a UUKL smoke-control application, it is recommended that you choose an MS/TP repeater that has been specifically tested, as listed in Appendix B.
When using “b-Link” repeaters, certain installation guidelines must be
followed. Figure–5.4 shows an example using the B-LINK-AC-S wire-only repeater. The same installation rules apply to the B-LINK-AC-F-S fiber optic repeater for those items common to both.
Coexistence and Isolation of Non-UL 864 Devices on the MS/TP Bus
When connecting one or more non-UL 864 Listed BACnet devices to an MS/TP bus that is involved in smoke control, a UL 864 Listed MS/TP repeater must be used to isolate those BACnet devices from the rest of the controllers. Figure–5.4 illustrates examples of this isolation. Optionally, instead of using an MS/TP repeater for isolation, the non-UUKL devices can be located together under other MNB-1000 controllers whose MS/TP bus are not involved in smoke control.
TAC I/A Series MicroNet BACnet Smoke Control Systems Manual F-27419-2
72
Page 89
Restrictions and General Comments
Figure–5.4 UL 864 Listed MS/TP Repeater and Isolation.
Non-UUKL
(Isolated)
2
4
EOL Bias
MNB-1000
4
UUKL Smoke
Control
5
MS/TP Bus (EIA-485)
MNB-1000
MS/TP Bus (EIA-485)
115/230 Vac
1
MNB-300
3
MNB-300
MNB-V2
MNB-300
Non-UUKL Device
MS/TP Bus (EIA-485)
MNB-300
Non-UUKL Device
MNB-V2
MNB-300
Non-UUKL
MNB-V2
EOL Bias
4
MNB-300
5
EOL
Device
4
Note: All references to the MNB-V1 equally apply
to the MNB-V1-2 and all references to the MNB-V2 equally apply to the MNB-V2-2.
EOL
4
1 The Input port of the repeater must have its MS/TP bus shield connected to the SHLD
terminal, which is isolated from Earth Ground. The incoming MS/TP shield must be grounded at only one point, at a location other than the repeater. Typically this is at the opposite end of the bus, or where the MNB-1000 parent controller resides.
2 All four of the repeater's Output ports have their SHLD terminals tied together, and tied to
Earth Ground internally, through the power supply's Earth Ground connection. For each MS/TP bus cable leaving these ports, the single point of ground for the shield is at the repeater and, therefore, the shield must not be grounded at any other point on the bus.
3 The AC power source for the repeater must provide a known, good, Earth Ground
connection to the Earth Ground terminal.
4 Anytime the MS/TP repeater is connected to a bus, the jumper-enabled end-of-line (EOL)
resistors associated with the MNB-1000 and MNB-300 controllers (on that bus) must be disabled. The same EOL resistor requirements still apply, except that external discrete terminators must be used. The 120 Ω termination resistor (part no. EMSC-546) has been provided for this purpose. If the repeater is the end-of-line for each bus, then each port
should have the 120 Ω termination resistor installed between the “MSTP +” and “MSTP–“ terminals. Likewise, the last device at the other end of each bus must also have the 120 Ω termination resistor installed between the “MSTP +” and “MSTP –“ terminals.
7
RS-232
+
5
SHLD
+
4
SHLD
+
3
SHLD
+
2
SHLD
+
1
SHLD (Input)
L N
Line Voltage
115
Selector
RS-485
RD TD
RD TD
RD TD
RD TD
RD TD
RD TD
Andover Controls
B-LINK-AC
Baud Rate
300 1200 2400 9600 19200 38400 76800 Spare
Power
6
MS/TP Bus
(EIA-485)
MNB-300
Bias
5
Non-UUKL
MNB-V2
Device
Non-UUKL
MNB-V2
Device
MNB-V2
EOL
4
5 Bias resistors must still be
applied to each bus, as outlined in the EIA-485 Termination and Bias Resistors section.
6 The integral enclosure associated
with the “B-LINK-AC-S” repeater meets the enclosure requirements of UUKL.
7 The RS-232 connection cannot
be used in UL 864 smoke control applications.
F-27419-2 TAC I/A Series MicroNet BACnet Smoke Control Systems Manual 73
Page 90
Chapter 5

Use of MNB-1000 IP Switch Feature

Dedicated Supply Air Dampers

IP switching, also known as port bridging, is enabled on the bottom Ethernet IP port (RJ-45 connector) of the MNB-1000 controller. However, when an MNB-1000 controller is applied to a UUKL smoke-control system, this IP switch feature cannot be used. For this reason, in UUKL applications all IP/Ethernet connections must be made to the top Ethernet IP port only. If there is a need to increase the number of IP or Ethernet nodes, the IP infrastructure devices noted earlier must be used. See "Approved
IP/Ethernet Infrastructure Devices" on page 71 and the list of devices in
Appendix B.
In many cases, a dedicated motor-driven damper may need to be installed in the common supply air duct feeding each smoke-control zone. This damper is required to provide smoke zones that are negatively pressurized with respect to all contiguous smoke-control zones, within the response time specified by NFPA 92A and UL 864 UUKL/UUKL7.
Note:
UL’s acceptance of the MNB-V1 and MNB-V2 MicroNet VAV controllers
for UUKL is based on the assumption that negative pressurization of a smoke zone is considered accomplished when the total flow rate (CFM) supplied to the zone drops below 50% of its maximum while its dedicated exhaust damper is fully open.
UL’s acceptance of the MNB-V1 and MNB-V2 MicroNet VAV controllers
for UUKL is based on the assumption that positive pressurization of a smoke-control zone is considered accomplished when the total flow rate (CFM) supplied to the zone exceeds 50% of its maximum while its dedicated exhaust damper is fully closed.
In a smoke-control zone, exhaust and supply air dampers should always
be driven to their full-open and full-closed positions. Sufficient differential pressure must be achieved between zones to ensure smoke spread is confined to the zone in which the fire originated.
The MNB-V1 and MNB-V2 MicroNet VAV controllers have a 3.0 minute travel time to achieve a 90° rotation when under continuous drive (forced open or closed). Since these controllers have an adjustable travel range from 45° to 90°, the worst case full-stroke travel time can vary from approximately 1.5 to 3.0 minutes. NFPA 92A and UL 864 UUKL/UUKL7 specify that achieving positive and negative pressurization of the smoke-control zones and smoke zones, respectively, must be accomplished within 75 seconds. Therefore, the application must be evaluated to determine if this time can be met without the use of dedicated supply air dampers.
Dedicated supply air dampers are not required if the damper response time is acceptable, under the following conditions:
Negative pressurization of the smoke zone is considered accomplished
when the total flow rate (CFM) supplied to the zone drops below 50% of its maximum while its associated dedicated exhaust damper is fully open.
TAC I/A Series MicroNet BACnet Smoke Control Systems Manual F-27419-2
74
Page 91
Restrictions and General Comments
Positive pressurization of a smoke-control zone is considered accomplished when the total flow rate (CFM) supplied to the zone reaches 50% of its maximum while its associated dedicated exhaust damper is fully closed.
Additionally, if the local Authority Having Jurisdiction (AHJ) determines that the longer damper travel times specified are acceptable, the dedicated supply air dampers can be omitted.

Class 2 Powered Devices

EIA-485 Termination and Bias Resistors

All I/A Series BACnet controllers that specify the use of a Class 2 power transformer must use one of the transformers listed in Appendix B. The use of these transformers, in conjunction with the published wiring and installation literature listed in Appendix C, provides compliance with the power-limited circuit requirements of UL 864 and the National Electrical Code (NEC).
With the exception of MS/TP buses that use the MS/TP repeaters listed in Appendix B, all other MS/TP bus installations must adhere to the application of EOL (end-of-line termination) and Bias resistor jumpers as overviewed here and detailed in the documents referenced in Appendix C. The MNB-1000 and MNB-300 controllers each provide jumpers that can enable or disable EOL and Bias resistors. The MNB-V1 and MNB-V2 controllers are not equipped with these jumpers.
Each MS/TP trunk must have an EOL resistor active at each end. When MNB-1000 and MNB-300 controllers are present at the ends, their EOL jumpers can be placed in the Enabled position to achieve this. If the device at the end of the MS/TP trunk is an MNB-V1 or MNB-V2 controller, then a 120 : resistor, EMSC-546, must be placed across the “MSTP +” and “MSTP –“ terminals. This is the EOL resistor specified in Appendix B. No other EOL resistors shall be present on the bus.
For Bias resistors, each MS/TP bus must have a minimum of one, and a maximum of two, sets active. The Bias resistors can be installed at any point on the bus. If two sets are active, each would typically be installed towards one of the ends of the bus. If only one set is active, then it would typically be installed towards the center of the bus length. The MNB-1000 and MNB-300 controllers are each equipped with two Bias resistor jumpers that can be placed in the Enabled or Disabled positions for this purpose. The MNB-V1 and MNB-V2 controllers do not feature user-configurable bias resistors.

System Self-Tests To maintain system integrity, dedicated system equipment must incorporate

an automatic weekly self-test of each smoke-control function. The self-test consists of the smoke-control system automatically commanding the associated function to operate, and expecting that the associated proof sensor operates within a specified period of time. The response time is 60 seconds for a fan and 75 seconds for a damper. For a discussion of response times, refer to "Response Time" on page 8.
Valid proof sensor operations are not required to be annunciated. However, the lack of an expected proof sensor operation must produce, at the FSCS, an audible trouble signal and an indication (with an LED) of the specific device that did not operate. Whenever an automatic test of the dedicated system equipment fails, annunciation of the failed state must be maintained
F-27419-2 TAC I/A Series MicroNet BACnet Smoke Control Systems Manual 75
Page 92
Chapter 5
at the FSCS until acknowledged by an operator. This acknowledgment is from the FSCS. It is acceptable for the failure state to require manual clearing from the I/A Series BACnet system to return it to normal operation, once the acknowledgment has been made.

Transformers Only the transformers listed in Appendix B can be used with I/A Series

BACnet controllers (UL 864 UUKL/UUKL7 Listed) that directly take part in smoke-control operation. Certain transformers must be mounted in enclosures to meet UL 864 UUKL/UUKL7 requirements, as shown in
Table–5.1.
Table–5.1 Transformer Enclosure Requirements.
Transformer Description Enclosure Required
EMSC-541
EMSC-542
EMSC-543
EMSC-583 75 VA, 120 V Pri., 24 V Sec., 50/60 Hz, Class 2
EMSC
EMSC
a. EMSC-541, EMSC-542, and EMSC-543 are not approved for use in smoke control applications in Canada, covered in ULC Standard
ULC-S527-99.
a
a
a
-616
-618
50 VA, 120 V Pri., 24 V Sec., 50/60 Hz, Fused (nonreplaceable) Primary
100 VA, 120 V Pri., 24 V Sec., 50/60 Hz, Fused (nonreplaceable) Primary
240 VA, 120 V Pri., 24 V Sec., 60 Hz, Fused (nonreplaceable) Primary
75 VA, 120 V Pri., 24 V Sec., 50/60 Hz, Class 2, Foot Mount Single Hub UL-Listed w/Circuit Breaker, Mounting Plate Included
96 VA, 120 V Pri., 24 V Sec., 50/60 Hz, Class 2, Foot Mount Single Hub UL-Listed w/Circuit Breaker, Mounting Plate Included
• No Enclosure Required
• No Enclosure Required
• UL-50 Listed Enclosure
• Uses conduit fittings or
• UL-50 Listed Enclosure
• Uses conduit fittings or
-50 Listed Enclosure
•UL
• Uses conduit fittings or
•UL
-50 Listed Enclosure
Enclosures Some of the controllers, repeaters, and IP infrastructure devices listed in
Appendix B do not feature integral enclosures. These devices must be mounted inside one of the enclosures approved for smoke-control applications. Table–5.2 lists these devices and the corresponding, required enclosures.
Table–5.2 Approved Enclosures for Smoke Control Applications.

Enclosures

Devices
-1000 X X X
MNB MNB-300 X X X MNB-V1 X X MNB-V2 X X
MS/TP Repeaters XX
IP Switches X
a. If allowed by the FSCS manufacturers listing. ADI FSCS panels provide this option.
TAC I/A Series MicroNet BACnet Smoke Control Systems Manual F-27419-2
76
MNB
-1000-ENC MNB-300-ENC MNA-FLO-1
FSCS
Enclosure
UL
Integral
a
-50
Listed
Page 93
Restrictions and General Comments

Wiring The FSCS can interface to I/A Series MicroNet BACnet controllers, either

through the ADI ModBus EIA-485 (RS-485) interface of the MNB-1000 or through individual I/O points.
ADI ModBus EIA-485 Interface
The Remote I/O bus of the MNB-1000 controller, when used with the ADI FSCS ModBus interface, requires use of the same type of wiring as specified for the MS/TP bus (Table–5.3). The MNB-1000 will typically be mounted inside the same enclosure as the FSCS. However, if the MNB-1000 is located external to the FSCS panel, then the wire length between the controller and the UUKL smoke-control system must not exceed 20 feet, and the I/O wiring must be run in conduit. End-of-line terminations must be present at both ends of the bus. This is accomplished by placing the I/O EOL jumper of the MNB-1000 in the Enabled position, and by installing a termination resistor at the FSCS end of the bus. Refer to the documentation associated with the ADI FSCS for additional information regarding ADI’s EIA-485 ModBus termination requirements.
Individual I/O Points
Anytime discrete I/O points are used and the FSCS manufacturer is approved to allow the installation of I/A Series BACnet controllers inside the FSCS panel, the distance and conduit requirements listed in Table–5.3 are not applicable. In all such cases, the wiring to the FSCS is still considered unsupervised.
The ADI ModBus interface wiring and I/O wiring that connects the I/A Series BACnet controllers to either the UUKL listed FSCS or the UOJZ listed fire alarm panel, are considered unsupervised. When this wiring is external to the UUKL listed FSCS or UOJZ listed fire alarm panel, the I/A Series BACnet controllers must be mounted within 20 feet of the panel to which they are connected, and the wiring must be run in conduit. Table–5.3 lists the general requirements for wiring associated with I/A Series BACnet smoke-control applications.
Table–5.3 Wiring Requirements.
Wiring Status
IP LAN Supervised by object programming
Ethernet LAN Supervised by object programming
MS/TP Bus Supervised by object programming
ADI ModBus Interface Supervised by object programming
Unsupervised. When the controller and the FSCS are
I/O to FSCS
I/O to Fire Alarm Panel
Remaining I/O Unsupervised
not located in the same panel, wiring must be run in conduit and controllers must be located within 20 ft of the panel
Unsupervised. Wiring must be run in conduit and controllers must be located within 20 ft of the panel.
F-27419-2 TAC I/A Series MicroNet BACnet Smoke Control Systems Manual 77
Page 94
Chapter 5

Hardware and Firmware Upgrade Process Requirements

UL-1459 (Abnormal Overvoltage) Compliance

Each MNB-1000, MNB-300, MNB-V1 or MNB-V2 controller is shipped from the factory with a label affixed to the unit, documenting its original firmware version. However, the firmware in these controllers may be field-upgraded by authorized personnel, using any version of firmware that is approved for use in UUKL Listed systems. Because of this, a means must be found to identify a unit’s currently installed firmware version. One such means is the WorkPlace Commissioning Tool. Using this tool, you can browse the network of controllers and employ one of two methods for identifying a controller’s firmware version. In the first method, you view the controller’s Properties, which shows the firmware version, as well as other data. In the second method, you enable the Firmware column on the Commissioning Tool’s main page so that it displays the current firmware version for each controller.
When applying I/A Series BACnet controllers to a UUKL smoke-control application, it is acceptable for the communication trunks (LANs and buses) to be run from one building to another. Whenever the cabling leaves a building in such an application, it must be isolated from the next building through the use of fiber optic cable. An MS/TP bus can be converted to fiber optic cable through use of the appropriate UUKL-approved repeater. Ethernet and IP LANs can be converted to fiber optic cable through the use of the appropriate UUKL-approved IP infrastructure devices. Refer to
"Approved MS/TP Repeaters" on page 72 and "Approved IP/Ethernet Infrastructure Devices" on page 71 for more information on the use of these
types of devices.

General Comments

FSCS Requirement In some cases, the FSCS may be considered optional. The Authority Having

Jurisdiction (AHJ) determines whether an FSCS is required.

MNB-1000 Using ADI ModBus Interface

Job Estimating When estimating a job using I/A Series BACnet devices for controlling

When using the MNB-1000’s ADI ModBus EIA-485 (RS-485) interface to communicate with an ADI ModBus FSCS, consider the following:
The MNB-1000’s unused I/O points, S-Link interface, and MS/TP bus
can be used for other related or unrelated purposes, as long as those purposes do not adversely impact the smoke-control sequence or violate any of the UUKL installation requirements.
Only UUKL listed or approved devices can be located inside the ADI
FSCS panel.
If an FSCS panel from a vendor other than ADI is used, check the
requirements of that vendor to determine the available mounting options.
smoke-control equipment (requiring UL 864 UUKL/UUKL7 and NFPA 92A compliance), consideration must be given to the number of additional devices that are required for end process verification and interfacing to the
TAC I/A Series MicroNet BACnet Smoke Control Systems Manual F-27419-2
78
Page 95
Restrictions and General Comments
FSCS. As seen below, whenever an MNB-1000 controller with ADI ModBus support is used to interface with an ADI ModBus FSCS, the number of additional points required to support the FSCS is substantially reduced.
Fans
For most fans, the following additional points are required:
One DI (digital input) point for fan flow.
Two DI points to serve the ON/OFF fan-control commands from the
FSCS.
One DO (digital output) point to send proof of the current fan condition
back to the FSCS.
Note: The two DI points for the ON/OFF commands from the FSCS, and the one DO point for the proof of current fan condition, are not required if the MNB-1000 with ADI ModBus support is used to interface with an ADI FSCS. These additional points are only required if discrete I/O points are hardwired to an FSCS.
Dampers
For most dampers, the following additional points are required:
Two DI points for monitoring the end-of-travel switches.
Two DI points for the drive open and drive closed commands from the
FSCS for controlling the dampers.
Two DO points to send proof of position back to the FSCS.
Note: The two DI points for the drive open/closed commands from the FSCS and the two DO points for the proof of position will not be required if the MNB-1000 with ADI ModBus support is used to interface with an ADI FSCS. These additional points will only be required if discrete I/O points are hardwired to an FSCS.
In some cases, a flow sensor or switch may be used to determine damper position. In these situations, only one AI (analog input) or DI may be required, instead of the two as noted above.
Additional points are required for monitoring the fire and smoke alarm contacts of the UOJZ listed fire alarm panel, and for controlling the trouble LEDs (general and dedicated) associated with the FSCS. The number of points required for these functions varies with each application but must be considered when estimating the job.
Note:
The additional points required to control the trouble LEDs associated
with the FSCS are not required if the MNB-1000 with ADI ModBus support is used to interface with an ADI FSCS. These additional points are only required if discrete I/O points are hardwired to an FSCS.
Any UOJZ listed fire alarm panel with programmable N.O. (normally
open) relay contacts can be used with I/A Series BACnet controllers.
F-27419-2 TAC I/A Series MicroNet BACnet Smoke Control Systems Manual 79
Page 96
Chapter 5

Spare I/O Points When I/A Series BACnet controllers interface to the FSCS or fire alarm

panel, any spare I/O points that exist on these controllers can be used for other control purposes, as long as those purposes do not adversely impact the smoke-control sequence or violate any of the UUKL installation requirements.

Lost Communications

Discrete I/O
In all I/A Series BACnet smoke-control systems where discrete I/O wiring is used to control the FSCS, one controller must be connected to the FSCS to control the system trouble output. The system trouble output must be applied in such a way that anytime this controller loses communication with its parent controller, or loses its power source, the system trouble output assumes the failure state.
Example—Lost Communication: A DO point within an I/A Series BACnet controller is connected to normally closed (N.C.) contacts within the FSCS. These contacts are, in turn, wired to the system trouble input. Whenever the controller containing the DO point is powered and communicating with its parent controller, and no other system troubles exist, the DO point is commanded ON and the N.C. contacts are open. This is the normal state, in which the system trouble indicator and audible alarm are OFF. If communication between this controller and its parent controller fails, or this controller loses power, the DO point is de-energized and the N.C. contacts close, causing the FSCS to illuminate the system trouble visual indicator and audible signal.
Lost Communication Between MNB-1000 and FSCS
When the MNB-1000 controller communicates with the ADI FSCS through the ADI ModBus interface, any loss of communication between these devices must cause the FSCS to activate its system trouble LED and audible alarm. Support must also be provided for silencing the audible annunciation in this situation. The ADI FSCS referenced in Appendix B provides, in its firmware, support for these features. A Communications Timeout value is provided on the Configuration tab of the ADI Object Configuration screen, within the ADI Wizard. This value defines the amount of time that can elapse, without communication, before the FSCS indicates a lost communication fault. More information is provided in the WorkPlace Tech Tool 5.7 Engineering Guide Supplement, F-27356.
IP, Ethernet, and MS/TP Networks
To assure compliance with UL mandated response times, all smoke-control systems require the use of object programming to detect lost communications between controllers on the IP, Ethernet, and MS/TP networks. Figure–5.5 shows the MSTP Status and Device Status objects available for this purpose. In the case of the Device Status object, the five possible configurations are included. Their design requires no timing adjustments by the application engineer. In some cases, they will be dependent upon network performance. UL states that the time between the occurrence of a transmission fault and its trouble annunciation shall not be more than 200 seconds.
TAC I/A Series MicroNet BACnet Smoke Control Systems Manual F-27419-2
80
Page 97
Restrictions and General Comments
Each smoke-control system must have at least one MNB-1000 controller present that coordinates the monitoring of the communication status of all devices on the various networks. As such, this controller is considered the master device of the network. This is the controller that provides the ADI ModBus interface and is typically located inside the FSCS panel. All communication status objects associated with the smoke-control system reside in this master controller. No communication status objects are required in any of the other controllers in the system.
The MSTP Status and Device Status objects are described in detail in the WorkPlace Tech Tool 5.7 Engineering Guide Supplement, F-27356, which is referenced in Appendix C. In all cases, the Status output of the objects is “100” if communication is lost and “0” if communication is good. A synopsis of their function and application in smoke-control systems is given in the notes in Figure–5.5.
F-27419-2 TAC I/A Series MicroNet BACnet Smoke Control Systems Manual 81
Page 98
Chapter 5
Example A – MSTP Status
This MSTP Status object is configured to monitor a single MSTP device. The monitored device is specified by the value of the object's MSTPAddr (MSTP address) property and the network number connected to the Network input property. In this case, device address 99 on network 31 is being monitored. This is the object most frequently used to monitor an MSTP device connected to an MNB-1000 controller.
Example B – Device Status
In this example, the Device Status object is configured to monitor a single MSTP device, device address 2 on network 31. The object's Configuration screen allows you to select different types of communication networks, including MS/TP. To monitor the chosen device, "MS/TP" was selected as the device type, the Network Number was set to "31," and the MS/TP Address (set by DIP switch) was set to "2." This object is most frequently used when it is necessary to poll for the device status based on Network Number and MSTP Address.
Example C – Device Status
In this example, the Device Status object is configured to monitor a single device based on its Instance Number. To do this, "Device ID" was selected as the device type and the Device Instance was set to "1100." With these settings, this object is monitoring device instance 1100 on the BACnet network (regardless of its communications type). This object is most frequently used when it is necessary to poll for the device status based solely on the Instance Number.
Example D – Device Status
In this example, the Device Status object is configured to monitor a single BACnet IP device. To do this, "BACnet IP" was selected as the device type, the Network Number was set to "1876," the IP Address was set to “10.1.144.99,” and the IP Port was set to "9." With these settings, this object is monitoring a BACnet IP device whose address is “10.1.144.99:9” on network 1876. This object is most frequently used when it is necessary to poll for the device status of an MNB-1000 controller configured for BACnet IP.
Example E – Device Status
In this example, the Device Status object is configured to monitor a single BACnet Ethernet device. To do this, "Ethernet" was selected as the device type, the Network Number was set to "888," and the Ethernet MAC Address was set to “00-01-F0-00-4A-95”. This example is monitoring a BACnet Ethernet device whose address MAC Address is “00-01-F0-00-4A-95” on network 888. This object is most frequently used when it is necessary to poll for the device status of a BACnet Ethernet configured MNB-1000 controller.
Example F – Device Status
In this example, the Device Status object is configured to monitor all devices on an MSTP bus under an MNB-1000 controller. Using this object in this manner requires that first an MSTP Status object is defined for each controller (to be monitored) on the MSTP bus. To set up this Device Status object, "Network" was selected as the device type and the Network Number was set to "30." With these settings, the Device Status object is configured to monitor the status of all MSTP Status objects that have been defined in the MNB-1000 controller and assigned a network number of 30. This object is specifically designed to logically “OR” the defined group of MSTP devices on a single network and provide a single Status output value.
Figure–5.5 Available Communication Status Monitoring Objects.
TAC I/A Series MicroNet BACnet Smoke Control Systems Manual F-27419-2
82
Page 99
Restrictions and General Comments
Custom Objects for MS/TP Communication Status
To expedite the process of setting up communication status monitoring of multiple MS/TP devices under multiple MNB-1000 controllers, two Custom Objects have been created and placed on an Application Objects Stencil as a published application. Go to Tech Zone, on the Schneider Electric Web site, “The Source.” These objects provide a means to add a single custom object for each MS/TP network (under an MNB-1000 controller) to be monitored. They automatically create and add, to the application, all of the objects required to monitor a network of 127 MS/TP devices. The user simply changes the network number associated with each device and deletes the MSTP Status objects for any controllers that are not required or present. The use of these Custom Objects, in conjunction with variations of the MSTP Status and Device Status objects discussed previously, provide the monitoring of communication status required to meet UUKL for the complete smoke-control network. In many cases, it is necessary to logically “OR” the outputs of these objects to generate a single output that is combined into the System Trouble LED control signal.
Preventing False Indication of Lost Communications
When downloading to controllers, resetting them, or cycling power to them, the system may annunciate a system trouble, which lights the System Trouble LED and sounds an audible alarm at the FSCS. Since these situations should only occur when a user with manager-level access (“programmer” or “authorized person”) makes adjustments to the system, that user must take appropriate steps to prevent false indications of lost communication, by temporarily overriding the System Trouble signal. Such overrides should only be performed by authorized personnel.

Use of BACnet Priority Structures

In this case, “false” implies that the loss of communication was not due to a failure but was, instead, caused by servicing of the system. Once the manager-level user has completed their activities, the temporary overrides must be removed and the system verified as having returned to a fully functional state.
An I/A Series MicroNet BACnet smoke-control system should be designed to use the BACnet priority structures associated with many of the BACnet objects. Adherence to the intended functional description for each priority input provides the system-wide support necessary to assure the integrity of the smoke-control system, while allowing other BACnet devices to provide overlay HVAC and day-to-day control. Therefore, use of the “Manual Life Safety (1)” and “Automatic Life Safety (2)” priority inputs of various objects on the application level lays the foundation for the use of non-UUKL devices, such as the UNC-520 and ENC-520 controllers, as overlay devices. These devices must be isolated (see "Coexistence and Isolation of Non-UL 864
Devices on the MS/TP Bus" on page 72) and must not in any way adversely
impact the ability of the smoke-control system to perform its function. The Command Priority object has been created specifically for this purpose and should be used whenever the integrity of the BACnet priority structures must be maintained.
F-27419-2 TAC I/A Series MicroNet BACnet Smoke Control Systems Manual 83
Page 100
Chapter 5
Figure–5.6 Installation of Transient Suppressor EMSC-621 on DOs of MNB-300.

Use of Transient Suppressor on MNB-300 DO

24H
24G COM
GND
TO1 (DO1)
C1
TO2 (DO2)
C2
TO3 (DO3)
C3
TO4 (DO4)
C4
TO5 (DO5)
C5
TO6 (DO6)
C6
If one or more I/O points of an MNB-300 are used for smoke control, then every used DO (Triac) point must have an EMSC-621 Transient Suppressor installed. The EMSC-621’s gray wires connect to any two used outputs (for example, TO1 and TO2) and the green wire connects to either 24 COM or GND, on the power connector. Figure–5.6 shows three typical scenarios for connectiing the EMSC-621 to the DO (Triac) terminals.
24H
OR
24G COM
GND
TO1 (DO1)
C1
TO2 (DO2)
C2
TO3 (DO3)
C3
Gray
To Load
OR
To Load
To Load
Installed on Two
Gray
Adjacent Used DOs
Green
Gray
EMSC-621
Installed on Two
Non-adjacent DOs
Green
Gray
To Load
EMSC-621
24H
24G COM
GND
TO1 (DO1)
C1
OR
1 When only one DO is being used,
install an EMSC-621 so that one
gray wire is inserted into the terminal of the active DO, while the free gray wire is inserted into the terminal of an unused DO. Optionally, the free gray wire may be capped with a wire nut.
Installed on Single
To Load
Gray
Green
Used DO
EMSC-621
TO2 (DO2)
C2
TO3 (DO3)
C3
TAC I/A Series MicroNet BACnet Smoke Control Systems Manual F-27419-2
84
1
Unused DO
Gray
Loading...