Schneider Electric TAC Xenta 102-ES Users Manual

TAC Vista
TAC Pangaea
WorkStation
TAC Xenta 102-ES
Product Manual
TAC Vista
TAC Xenta 102-ES
Product Manual
Copyright © 2004-2010 Schneider Electric Buildings AB. All rights reserved. This document, as well as the product it refers to, is only intended for licensed users. Schneider Electric Buildings AB owns the copyright of
Do not use the product for other purposes than those indicated in this document. Only licensed users of the product and the document are permitted to use the document or any information therein. Distribution, disclosure,
copying, storing or use of the product, the information or the illustrations in the document on the part of non-licensed users, in electronic or mechanical form, as a recording or by other means, including photo copying or information storage and retrieval systems, without the express written permission of Schneider Electric Buildings AB, will be regarded as a violation of copyright laws and is strictly prohibited.
Trademarks and registered trademarks are the property of their respective owners.
Zone Controller, TAC Xenta 102-ES Contents

Contents

INTRODUCTION
1 Documentation and Terminology 9
1.1 Documentation........................................................................................................... 9
1.2 Terminology............................................................................................................... 9
REFERENCE
2 Zone Controller TAC Xenta 102-ES 13
2.1 General....................................................................................................................... 13
2.2 Wall Modules............................................................................................................. 15
2.2.1 STR350/351 ............................................................................................................... 15
2.2.2 STR150 ...................................................................................................................... 16
2.2.3 STR100-104............................................................................................................... 17
2.2.4 Wall Module Configuration....................................................................................... 18
2.3 Applications ............................................................................................................... 19
2.3.1 General....................................................................................................................... 19
2.3.2 The Zone Controller TAC Xenta 102-ES .................................................................. 19
3 Installation 23
3.1 Mechanical Installation.............................................................................................. 23
3.1.1 Fitting......................................................................................................................... 23
3.2 Electrical Installation ................................................................................................. 24
3.2.1 General....................................................................................................................... 24
3.2.2 Wiring of Xenta 102-ES, Application with Damper Control Only ........................... 27
3.2.3 Wiring of Xenta 102-ES, Application with Damper and Reheat Control.................. 28
3.2.4 Wiring of Xenta 102-ES, Application with Damper and Two- Stages of Reheat Control 29
3.2.5 Connecting to STR150............................................................................................... 30
3.2.6 Air Flow Balancing Procedure................................................................................... 30
3.3 Commissioning .......................................................................................................... 32
3.3.1 General....................................................................................................................... 32
3.3.2 Node Status ................................................................................................................32
3.3.3 Configuration Parameters (nci´s)............................................................................... 33
3.3.4 Network Installation.............................................................. ..... ................................ 33
3.3.5 Network Variable Binding.................................................... ..... ................................ 34
3.3.6 Function Test..............................................................................................................34
4 Configuration Parameters 35
4.1 Basic Parameters...................................................... .................................................. 36
4.2 Other Configuration Parameters ................................................................................ 37
Schneider Electric Buildings AB, Mar 2010 5 (88) 04-00069-01-en
Contents Zone Controller, TAC Xenta 102-ES
5 Functional Description 41
5.1 General ....................................................................................................................... 41
5.2 The Controller’s Basic Functions............................................................................... 41
5.2.1 Operation Modes ......................................................................... .... ........................... 41
5.2.2 Application, Manual and Emergency Modes............................................................. 43
5.2.3 Measuring Zone Temperature .................................................................................... 45
5.2.4 Setpoint Calculation ................................................................................................... 46
5.2.5 Temperature Control Sequence for TAC Xenta 102-ES............................................ 48
5.3 More About Functions................................................................................................ 49
5.3.1 Cooling Control............................................................................................. ............. 49
5.3.2 Heating Control .......................................................................................................... 50
5.3.3 Fan Control................................................................................................................. 50
5.3.4 Air Quality Control..................................................................................................... 51
5.3.5 Window Contact......................................................................................................... 52
5.3.6 Occupancy Sensor ...................................................................................................... 52
5.3.7 Alarm.......................................................................................................................... 53
5.3.8 Master/slave Operation............................................................................................... 54
5.3.9 Additional Features ................................................... .... ............................................. 55
6 Troubleshooting 57
6.1 General ....................................................................................................................... 57
6.2 Inputs and Outputs (nvi/nvo)...................................................................................... 57
6.3 Troubleshooting Guide............................................................................................... 59
7 Technical Data 61
7.1 Technical Data............................................................................................................ 61
7.2 Dimensions................................................................................................................. 64
8 Communication 65
8.1 General ....................................................................................................................... 65
8.2 Default Settings and Power On .................................................................................. 65
8.3 Monitoring Network Variables, Heartbeat................................................................. 66
8.4 Not Accepted Values.................................................................................................. 66
8.5 The Node Object......................................................................................................... 67
8.5.1 The Node Object’s Inputs (nvi).................................................................................. 68
8.5.2 The Node Object’s Outputs (nvo) .............................................................................. 68
8.5.3 The Node Object’s Configuration Parameters (nci)................................................... 68
8.6 The Controller Object................................................................................................. 69
8.6.1 The Controller Objects Inputs (nvi) ........................................................................... 71
8.6.2 The Controller Objects Outputs (nvo)........................................................................ 72
8.6.3 The Controller Object’s Configuration Parameters (nci)........................................... 73
APPENDIX
A Setpoint Calculation 77
B Commissioning Protocol 81
Index 85
6 (88) Schneider Electric Buildings AB, Mar 2010
04-00069-01-en

INTRODUCTION

1 Documentation and Terminology

Zone Controller, TAC Xenta 102-ES 1 Documentation and Terminology

1 Documentation and Terminology

1.1 Documentation

Enclosed Documentation
TAC Xenta 102-ES is delivered with an installation instruction: TAC Xenta 102-ES, Installation instruction
Other documentation
There is additional information about TAC Xenta 102-ES in the follow­ing documents:
Data sheet for TAC Xenta 102-ES
Data sheet for ZS 101–ZS 105
Data sheet for STR100–STR107
Data sheet for STR150
Data sheet for STR350
TAC Xenta Network Guide
TAC Xenta OP Handbook
TAC Xenta, Zone System Guidelines All the above mentioned documents can be found on the internet at
nearest Schneider Electric service point.

1.2 Terminology

Some useful terms and abbreviations regarding the zone controller's application and network communication are explained in the table below.
Table 1.1: Terminology
or can be ordered from your
neuron
node SNVT Standard Network Variable Type
Schneider Electric Buildings AB, Mar 2010 9 (88) 04-00069-01-en
communication processor with built-in protocol
communication unit on the network
1 Documentation and Terminology Zone Controller, TAC Xenta 102-ES
Table 1.1: Terminology
nvixxx variable that gets its value from another
unit on the network
nvoxxx variable that is sent to another unit on the
network
ncixxx configuration parameter; variable that gets
its value from another unit on the net­work and keeps it during a power failure
service pin function that can be used during installa-
tion on the network
wink
confirmation that the connection to a con­troller via the network is working (a LED is lit for appr. 20 seconds)
LNS
LonWork
®
Network Services. System tool for installation, configuration and mainte­nance of LonWorks network
TAO Thermal Actuator Output.
10 (88) Schneider Electric Buildings AB, Mar 2010
04-00069-01-en

REFERENCE

2 Zone Controller TAC Xenta 102-ES
3 Installation
4 Configuration Parameters
5 Functional Description
6 Troubleshooting
7 Technical Data
8 Communication

Zone Controller, TAC Xenta 102-ES 2 Zone Controller TAC Xenta 102-ES

2 Zone Controller TAC Xenta 102-ES

2.1 General

The zone controller TAC Xenta 102-ES is intended for VAV applica­tions in offices and other large buildings. The VAV controller maintains a constant temperature in the zone by regulating the flow of air at a con­stant temperature into the room.
The Controller’s Basic Functions
The controller have a number of built-in functions that are designed to handle normal control situations. There are four operating modes to choose from (comfort, economy, bypass and off) and five modes to force the controller (auto, heating, cooling, night purge and off). The air flow is measured with a built-in air flow sensor. The zone temperature is measured using a permanent thermistor sensor or a temperature node connected to the network. Setpoint calculations are made in line with defined methods. The controller is equipped with an air qu ality function if it has been connected to a carbon dioxide sensor.
There is a detailed description of all the basic functions in Section 5.2, “The Controller’s Basic Functions”, on page 41.
More About Functions
Apart from the controller’s basic functions, there are a number of other functions for controlling the climate in the zone; these are described in detail in Section 5.3, “More About Functions”, on page 49. Additional external functions that can be connected are also described in this chap­ter, these include window contact sensor and occupancy sensor.
Communications
The controller can work either as a stand-alone unit, without being con­nected to a network during operation, or be a part of a larger system with several other units such as TAC Xenta 300/400 and other zone control­lers in the TAC Xenta family (Fig. 2.1). A detailed description of how units work together in a larger zone system, is found in “Zone Systems Guidelines”, part number 0-004-7637.
TAC Vista is an excellent tool for reading variables as well as a config­uration tool for commissioning and/or operation purposes. When TAC Vista is not part of the system, reading and configuration of variables can be made from the operating panel TAC Xenta OP, version 3.11 or later.
Schneider Electric Buildings AB, Mar 2010 13 (88) 04-00069-01-en
103-A103-A103-A103-A
102-EF102-EF102-EF102-EF102-EF
102-ES102-ES102-ES102-ES102-ES102-ES
102-B 102-B102-B
101-1VF 101-2VF101-1VF101-1VF101-1VF101-1VF101-1VF101-1VF101-1VF
Analog
I/O
Digital
I/O
TAC
Xenta
300
Router
Router
Router
TAC
Xenta
400
TAC
Xenta
400
3rd
floor
Office 3:1 Office 3:2
Office 3:3 Office 3:4
Office 3:5
Office 3:6 Office 3:7 Office 3:8 Office 3:9
2nd
floor
Office 2:1
Office 2:2
Office 2:3
Office 2:4 Office 2:5
Office 2:6Room 2:1
Master
Room 2:2
Slave
Room 2:3
Slave
TAC Vista
1st
floor
Room
1:1
Slave
Room 1:2
Slave
Room
1:4
Slave
Room 1:3
Slave
Room 1:5
Master
Office 1:1
Office 1:2
Office 1:3
Office 1:4
4th
floor
Ground
floor
Fig. 2.1: Zone controller in a larger system together with TAC Vista
2 Zone Controller TAC Xenta 102-ES Zone Controller, TAC Xenta 102-ES
The controller is LonMark® approved and communicates on a Lon-
®
TP/FT-10 network via a twisted-pair, unpolarized cable. If you
Talk want to know more about the LonWorks
®
technology, visit the internet
addresses www.echelon.com or www.lonmark.org.
14 (88) Schneider Electric Buildings AB, Mar 2010
04-00069-01-en
Zone Controller, TAC Xenta 102-ES 2 Zone Controller TAC Xenta 102-ES
Select button
Increase/Decrease buttons
Bypass/On-Off button
Display

2.2 Wall Modules

A temperature sensor must be mounted somewhere in the controlled zone. In the STR series of wall modules the temperature sensor is com­bined with various types of user interfaces. Several STR models are well suited for TAC Xenta 102-ES regarding desired functionality and user interface.
STR350/351. Wall unit with temperature sensor and LCD display. Extensive functionality for zone control. Communicates with the controller over LonWorks.
STR150. Wall unit with temperature sensor and LCD display. Have the most common functions for zone control. One-way serial communication with the controller.
STR100-104. Wall module with temperature sensor and controls for the most common functions for zone control. STR100-107 sig­nals are hard-wired to TAC Xenta 102-ES.
2.2.1 STR350/351
STR350/351 communicates on LonWorks. LonWorks is used for all data exchange between the room unit and the controller.
Regarding TAC Xenta 102-ES, STR350/351 has the following func­tionality:
Temperature sensor . Use either the built in thermistor element or another temperature sensor available on the LonWorks network
Actual temperature display. The actual zone temperature can be displayed on the LCD, but can also be hidden if desired.
Temperature setpoint display. The temperature setpoint can be displayed, either as an absolute value or as an offset.
Schneider Electric Buildings AB, Mar 2010 15 (88) 04-00069-01-en
2 Zone Controller TAC Xenta 102-ES Zone Controller, TAC Xenta 102-ES
Fig. 2.2: Wall module STR150
Bypass button
Increase/Decrease buttons
Fan speed control
Display
Temperature setpoint adjustment. The temperature setpoint can
be adjusted, either as an absolute value or as an offset.
Bypass or on/off button. There is a bypass function which forces
the controller to comfort mode for a configurable period of time. The same button can alternatively be used as an on/off button.
Mode Indicator. An On/Off symbol in the LCD indicates the
mode of the control.
For technical details of the functionality listed above, additional func­tionality and for configuration details, see the STR350/351 configura­tion and data sheets.
Use the LNS plug-in to configure STR350/351.
2.2.2 STR150
16 (88) Schneider Electric Buildings AB, Mar 2010
STR150 connects to TAC Xenta 102-ES with two or three wires. The third wire is used only if mode indication in the LCD is desired. On the other two wires information is sent from the wall unit to the controller:
Zone temperature. The temperature sensed by the thermistor ele-
Temperature setpoint. The temperature setpoint, which is dis-
Bypass button. The bypass button forces the controller to comfort
The mode indication signaled on the third wire is connected to the man symbol in the LCD:
Comfort mode (On) is indicated by a steady man symbol
ment.
played as an absolute temperature, but transmitted as an offset to the configured reference temperature.
mode for a fixed period of time (2 h).
04-00069-01-en
Zone Controller, TAC Xenta 102-ES 2 Zone Controller TAC Xenta 102-ES
Fig. 2.3: Wall module STR104
Mode indicator On/Off
Bypass button
Temperature setting wheel
Fan speed control
Economy (Standby) mode is indicated by a flashing man symbol.
Unoccupied (Off-mode) is indicated by the man symbol being off.
There is no communication from the controller to the unit so if a setpoint is changed from TAC Vista, this new value cannot be displayed on STR150.
Configuration of STR150 is done using the buttons and display on the unit. See STR150 configuration and data sheets for details.
2.2.3 STR100-104
STR100-104 is a series of room units that connects to I/O terminals of TAC Xenta 102-ES. The functionality of the various models is given in the Table 2.1, “STR100-104 functionality”.
Table 2.1: STR100-104 functionality
Model Temp Sensor
STR100 X STR101 X X STR102 X X X STR103 X X X STR104 X X X X
Mode
Indicator
Setpoint
Adjustment
STR104 is shown in Fig. 2.3 as an example.
Bypass Button
Note
The T AC Xenta OP is normally connected direct ly to the control­ler, not the wall module. The TAC Xenta 101-VF has a TAC Xenta OP access connecter (type RJ-10) on the controller instead of dedicated terminals for the wall module.
Schneider Electric Buildings AB, Mar 2010 17 (88) 04-00069-01-en
2 Zone Controller TAC Xenta 102-ES Zone Controller, TAC Xenta 102-ES
Depending on model the following functionality may be present:
Temperature Sensor. All models have a 1.8Kohms@25°C ther-
mistor element.
Temperature Adjustment. The temperature setpoint can be
adjusted. Using the plastic keys on the rear of the core panel the adjustment range can be set.
Mode Indicator. The green LED indicates the control mode:
Comfort mode (On) is indicated by a steady green light
Economy (Standby) mode is indicated by a flashing green light.
Unoccupied (Off-mode) is indicated by the LED being off.
Bypass button. The bypass button forces the controller to comfort
mode for a configurable period of time.
Refer to STR100-107 data sheet and installation sheet for details.
2.2.4 Wall Module Configuration
Wall Module Choice
STR150 is enabled by nciAppOptions bit 14:
0 = ZS and STR100-104 or STR350/351 (default)
1 = STR150 This can be set using the LonMaker Xenta100 plug-ins in Toolp ack ver-
sion 2.01 or higher, or by means of TAC Xenta OP.
Initial Start Up Status
SpaceTemp in the application is set to +20.00 Celsius (This can be read in the nvoSpaceTemp, but not in nviSpaceTemp.)
Fan is set to Fan Auto
TAC Xenta is now waiting for data from the STR module. If no room temperature readings are received within 10 minutes, the
SpaceTemp in the application is set to “invalid”. This is shown as “invalid” in nvoSpaceTemp.
When the first update is received , then the 10 minute limit is changed to 5 minutes.
18 (88) Schneider Electric Buildings AB, Mar 2010
04-00069-01-en
Zone Controller, TAC Xenta 102-ES 2 Zone Controller TAC Xenta 102-ES
Unless there is a restart, the Offset + Fan values are not cleared and the last value is valid..
Note
Fore more information on how to configure and engineer the STR series of wall modules see the documents for each product respectively.

2.3 Applications

2.3.1 General
The TAC Xenta 102-ES controller incorporates several features includ­ing
a built-in air flow sensor and controller algorithms.
the facility to connect a window contact sensor to stop the heating and cooling functions should a window be opened (Section 5.3.5, “Window Contact”, on page 52).
an occupancy sensor that can detect the presence of a person in the controlled zone and change the controller from economy to com­fort mode (Section 5.3.6, “Occupancy Sensor”, on page 52).
an air quality control function that can be activated if a carbon dix­oide sensor is connected. When a sensor is connected, the control­ler ensures that the concentration of carbon dioxide in the zone between preset limits (Section 5.3.4, “Air Quality Control”, on page 51).
an auxiliary temperature sensor that can be connected to measure any temperature and present it as a SNVT (Section 5.3.9, “Addi­tional Features”, on page 55).
2.3.2 The Zone Controller TAC Xenta 102-ES
The controller is designed for the following applications:
Damper control only
Damper control with primary heating and one free network output
Damper control with primary and secondary heating
For fan control applications see Section 5.3.3, “Fan Control”, on page 50.
Damper Control Only
The zone temperature is maintained by controlling of the airflow damper. The airflow is limited to maximum and minimum.
An optional occupancy and/or a CO2 sensor can be connected.
Schneider Electric Buildings AB, Mar 2010 19 (88) 04-00069-01-en
2 Zone Controller TAC Xenta 102-ES Zone Controller, TAC Xenta 102-ES
Fig. 2.4: Damper control for TAC Xenta 102-ES
Widow contact
Air flow sensor
Damper
Free Network
control output
CO
2
sensor
Wall module
Occupancy sensor
Auxiliary temperature
sensor
The free network output (V6) can be used in this application. For applications with fan control, see Section 5.3.3, “Fan Control”, on
page 50.
Damper and Primary Heating Control
The zone temperature is maintained by sequence control of the airflow damper and primary reheating. The airflow is limited to maximum and minimum. The reheat control is achieved by an increase/decrease or thermal actuator.
An optional occupancy and/or a CO2 sensor can be connected. The free network controlled output (V6) can be used in this application
(see Section 5.3.9, “Additional Features”, on page 55).
20 (88) Schneider Electric Buildings AB, Mar 2010
04-00069-01-en
Zone Controller, TAC Xenta 102-ES 2 Zone Controller TAC Xenta 102-ES
Fig. 2.5: Damper and reheat control for TAC Xenta 102-ES
Widow contact
Air flow sensor
Damper
Free Network
control output
CO
2
sensor
Wall module
Occupancy sensor
Auxiliary temperature
sensor
Fan
Relay
Actuator
Valve reheat
For applications with fan control, Section 5.3.3, “Fan Control”, on page 50.
Damper Control and Two Stages of Reheat Control
The zone temperature is maintained by sequence control of the airflow damper, primary reheating and secondary reheating. The airflow is lim­ited to maximum and minimum. The reheat control is achieved by an increase/decrease or a thermal actuator for primary reheat and thermal actuator for secondary reheat.
An optional occupancy sensor and a CO2 sensor can be connected.
Schneider Electric Buildings AB, Mar 2010 21 (88) 04-00069-01-en
2 Zone Controller TAC Xenta 102-ES Zone Controller, TAC Xenta 102-ES
Fig. 2.6: Damper and two stages of reheat control for TAC Xenta 102-ES.
Widow contact
Air flow sensor
Damper
Thermal actuator
CO
2
sensor
Wall module
Occupancy sensor
Auxiliary temperature
sensor
Fan
Relay
Actuator
Radiators
For applications with fan control, see Chapter 5.3.3, “Fan Control”, on page 50.
22 (88) Schneider Electric Buildings AB, Mar 2010
04-00069-01-en

Zone Controller, TAC Xenta 102-ES 3 Installation

Fig. 3.1: TAC Xenta 102-ES fixed to a DIN rail
3 Installation

3.1 Mechanical Installation

3.1.1 Fitting
TAC Xenta 102-ES can either be snapped onto a DIN rail (Fig. 3.1) or fixed to a level surface with two screws. (Fig. 3.2).
To fasten the controller onto a DIN rail:
1 Place the controller on the top of the rail as shown by arrow 1. 2 Twist the controller downwards until it snaps onto the rail as
shown by arrow 2.
3 To remove, use a screwdriver to locate the lock on the bottom of
the controller and pull down. Then lift the controller diagonally upwards and off the rail.
Schneider Electric Buildings AB, Mar 2010 23 (88) 04-00069-01-en
3 Installation Zone Controller, TAC Xenta 102-ES
Fig. 3.2: TAC Xenta 102-ES fixed to a level surface
!
Fixing the Controller to on a Level Surface:
Use the two sockets provided for fixing the controller; the maximum screw size is M4 or ST 3,5 (Ø 0.15"). The head of the screw should not exceed 7,5 mm (0.3") in diameter.

3.2 Electrical Installation

3.2.1 General
Warning
All mains supply cables must be installed by authorized electri­cians.
1 Each controller or group of controllers must use max. 6 A fuses. 2 Avoid hanging or loose cables by using clamps to secure them to
the controller.
3 A switch to cut off the power supply to the controller or compete
unit must be easily accessible.
4 When no carbon dioxide sensor is connected to the terminals a
jumper must be used to connect U1 and M.
5 When several Xenta controllers receive power from a common
transformer, it is important that all Gs are connected to each other and that all G0s are connected to each other. NB! the connections are not interchangeable. Important exception: the G0 on the wall module should be connected to the terminal OP on the controller and not to the other G0's. The G0 should be grounded at the trans­former to prevent interference. At the transformer, G0 should be connected to protective earth. This is to get an grounding point for interference diversion.
24 (88) Schneider Electric Buildings AB, Mar 2010
04-00069-01-en
Zone Controller, TAC Xenta 102-ES 3 Installation
6 To ensure that the spec ified measuring accuracy is achieved, the
two M terminals must be connected to the wall module.
Note that this equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment gener­ates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful inter­ference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the fol­lowing measures:
Reorient or relocate the receiving antenna.
Increase the separation between the equipment and receiver.
Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
Consult the dealer or an experienced radio/TV technician for help.
Safety Standard
Transformers supplying the controller must comply to the safety stan­dard EN 60 742 or any other relevant safety standard for ELV, 24 V AC. When equipment with a power supply of its own is connected, this power supply must also comply with this norm.
Cable Lengths
For information on communication cable lengths, see TAC Xenta Net­work Guide, part number 0-004-7460. For all other cables, maximum length is 30 m (100 feet) and min. area is 0,7 mm
2
(AWG-19).
The Wall Modules
The STR100-104 is primarily intended for use with the Xenta 103. The wall module STR150 can also be used, but in this case the fan speed but­ton is not used. For more information about how to connect and config­ure wall modules, please refer to the documentation for each respective product.
Schneider Electric Buildings AB, Mar 2010 25 (88) 04-00069-01-en
3 Installation Zone Controller, TAC Xenta 102-ES
Connection Terminals
The designation of the connection terminals can be found on the label on the front of the controller and the numbers of the terminals can be found on the edge of the printed circuit board.
Termin. Design. Function Type
1 C1 TP/FT-10 communication channel ­2 C2 TP/FT-10 communication channel -
a
3
4 M Measurement neutral -
a
5 6 B2 Optional temperature sensor Thermistor input 7 M Measurement neutral ­8 U1 Carbon dioxide sensor or jumper Thermistor input 9 D1 LED on wall module Digital output 10 M Measurement neutral 11 X1 Bypass key on wall module Digital input 12 R1 Setpoint adjustment on wall module 10k Ohm linear potentiometer 13 M Measurement neutral ­14 B1 Zone temperature sensor Thermistor input 15 G24 V AC (G) Input 16 G0 24 V AC (G0) Input
b
17 18 G24 V AC supply for TA C Xenta OP ­19 V1 Damper actuator: increase Triac 20 G24 V AC (G) supply for V1, V2 ­21 V2 Damper actuator: decrease Triac 22 V3 Reheat actuator: increase
23 G 24 V AC (G) supply for V3, V4 ­24 V4 Reheat actuator: decrease
25 V5 Fan on/off control Triac 26 G 24 V AC (G) supply for V5, V6 ­27 V6 Thermal actuator or free network output Triac 28 Y1 Primary reheat demand Output 0-10 V
a. See chapter 4 Configuration parameters b. Connected to G0 on the wall module. Do not connect to G0 on the controller..
X3 Window contact
Closed contact=closed window)
X2 Occupancy sensor Digital input
OP 24 V AC supply for TAC Xenta OP -
Thermo actuator: on/off parallel V4
Thermo actuator: on/off parallel V3
Digital input
Triac
Triac
26 (88) Schneider Electric Buildings AB, Mar 2010
04-00069-01-en
Zone Controller, TAC Xenta 102-ES 3 Installation
Optional temperature input
Carbon dioxide sensor
Occupancy sensor
Window contact
Junction Box
20
G
G0
G
15
16
G
OP
17
18
19
V1
C2
C1
1
2
X3
3
4
X2
5
6
24
22
21
V2
23
V3
V4
25
Y1
26
27
28
10
8
7
B2
U
1
D
1
9
X1
11
R
1
12
13
B1
14
TAC Xenta 102-ES
GW1 GX1 GQ1
G
G
V5
V6
Lon Talk" TP/FT-10
COM
INC.
24 VAC
Damper actuator
Network controlled output
DEC.
6 9
(mm)
+
2
M
M
M
M
OP
C1
C2
Wall Module
21 22
2423
G
M
Therm
LED
Pot/Pot+R
Mx
Switch
12
11
13
14
15
16
STR101-104
3
1
U1 should not be left unconnected. If no sensor will be used, connect U1 to M.
2
Tubing. Should be connected before the controller is mounted on the wall.
3
Air flow sensor, e.g. TAC GV
2
Fig. 3.3: Wiring of TAC Xenta 102-ES
3.2.2 Wiring of Xenta 102-ES, Application with Damper Control Only
Read Section 3.2.1, “General”, on page 24 before you connect the cables as shown in the wiring diagram in Fig. 3.3.
Schneider Electric Buildings AB, Mar 2010 27 (88) 04-00069-01-en
Loading...
+ 61 hidden pages