this document and reserves the right to make changes, additions or deletions. Schneider Electric Buildings AB assumes no responsibility for
possible mistakes or errors that might appear in this document.
Do not use the product for other purposes than those indicated in this document.
Only licensed users of the product and the document are permitted to use the document or any information therein. Distribution, disclosure,
copying, storing or use of the product, the information or the illustrations in the document on the part of non-licensed users, in electronic or
mechanical form, as a recording or by other means, including photo copying or information storage and retrieval systems, without the express
written permission of Schneider Electric Buildings AB, will be regarded as a violation of copyright laws and is strictly prohibited.
Trademarks and registered trademarks are the property of their respective owners.
Zone Controller, TAC Xenta 102-ES1 Documentation and Terminology
1Documentation and Terminology
1.1Documentation
Enclosed Documentation
TAC Xenta 102-ES is delivered with an installation instruction:
TAC Xenta 102-ES, Installation instruction
Other documentation
There is additional information about TAC Xenta 102-ES in the following documents:
•Data sheet for TAC Xenta 102-ES
•Data sheet for ZS 101–ZS 105
•Data sheet for STR100–STR107
•Data sheet for STR150
•Data sheet for STR350
•TAC Xenta Network Guide
•TAC Xenta OP Handbook
•TAC Xenta, Zone System Guidelines
All the above mentioned documents can be found on the internet at
nearest Schneider Electric service point.
1.2Terminology
Some useful terms and abbreviations regarding the zone controller's
application and network communication are explained in the table
below.
Table 1.1: Terminology
or can be ordered from your
neuron
node
SNVTStandard Network Variable Type
Schneider Electric Buildings AB, Mar 20109 (88)
04-00069-01-en
communication processor with built-in
protocol
communication unit on the network
1 Documentation and Terminology Zone Controller, TAC Xenta 102-ES
Table 1.1: Terminology
nvixxxvariable that gets its value from another
unit on the network
nvoxxxvariable that is sent to another unit on the
network
ncixxx configuration parameter; variable that gets
its value from another unit on the network and keeps it during a power failure
service pinfunction that can be used during installa-
tion on the network
wink
confirmation that the connection to a controller via the network is working (a LED
is lit for appr. 20 seconds)
LNS
LonWork
®
Network Services. System tool
for installation, configuration and maintenance of LonWorks network
TAOThermal Actuator Output.
10 (88)Schneider Electric Buildings AB, Mar 2010
04-00069-01-en
REFERENCE
2Zone Controller TAC Xenta 102-ES
3Installation
4Configuration Parameters
5Functional Description
6Troubleshooting
7Technical Data
8Communication
Zone Controller, TAC Xenta 102-ES2 Zone Controller TAC Xenta 102-ES
2Zone Controller TAC Xenta 102-ES
2.1General
The zone controller TAC Xenta 102-ES is intended for VAV applications in offices and other large buildings. The VAV controller maintains
a constant temperature in the zone by regulating the flow of air at a constant temperature into the room.
The Controller’s Basic Functions
The controller have a number of built-in functions that are designed to
handle normal control situations. There are four operating modes to
choose from (comfort, economy, bypass and off) and five modes to
force the controller (auto, heating, cooling, night purge and off). The air
flow is measured with a built-in air flow sensor. The zone temperature
is measured using a permanent thermistor sensor or a temperature node
connected to the network. Setpoint calculations are made in line with
defined methods. The controller is equipped with an air qu ality function
if it has been connected to a carbon dioxide sensor.
There is a detailed description of all the basic functions in Section 5.2,
“The Controller’s Basic Functions”, on page 41.
More About Functions
Apart from the controller’s basic functions, there are a number of other
functions for controlling the climate in the zone; these are described in
detail in Section 5.3, “More About Functions”, on page 49. Additional
external functions that can be connected are also described in this chapter, these include window contact sensor and occupancy sensor.
Communications
The controller can work either as a stand-alone unit, without being connected to a network during operation, or be a part of a larger system with
several other units such as TAC Xenta 300/400 and other zone controllers in the TAC Xenta family (Fig. 2.1). A detailed description of how
units work together in a larger zone system, is found in “Zone Systems
Guidelines”, part number 0-004-7637.
TAC Vista is an excellent tool for reading variables as well as a configuration tool for commissioning and/or operation purposes. When TAC
Vista is not part of the system, reading and configuration of variables
can be made from the operating panel TAC Xenta OP, version 3.11 or
later.
Schneider Electric Buildings AB, Mar 201013 (88)
04-00069-01-en
Fig. 2.1: Zone controller in a larger system together with TAC Vista
2 Zone Controller TAC Xenta 102-ES Zone Controller, TAC Xenta 102-ES
The controller is LonMark® approved and communicates on a Lon-
®
TP/FT-10 network via a twisted-pair, unpolarized cable. If you
Talk
want to know more about the LonWorks
®
technology, visit the internet
addresses www.echelon.com or www.lonmark.org.
14 (88)Schneider Electric Buildings AB, Mar 2010
04-00069-01-en
Zone Controller, TAC Xenta 102-ES2 Zone Controller TAC Xenta 102-ES
Select button
Increase/Decrease
buttons
Bypass/On-Off
button
Display
2.2Wall Modules
A temperature sensor must be mounted somewhere in the controlled
zone. In the STR series of wall modules the temperature sensor is combined with various types of user interfaces. Several STR models are
well suited for TAC Xenta 102-ES regarding desired functionality and
user interface.
•STR350/351. Wall unit with temperature sensor and LCD display.
Extensive functionality for zone control. Communicates with the
controller over LonWorks.
•STR150. Wall unit with temperature sensor and LCD display.
Have the most common functions for zone control. One-way serial
communication with the controller.
•STR100-104. Wall module with temperature sensor and controls
for the most common functions for zone control. STR100-107 signals are hard-wired to TAC Xenta 102-ES.
2.2.1STR350/351
STR350/351 communicates on LonWorks. LonWorks is used for all
data exchange between the room unit and the controller.
Regarding TAC Xenta 102-ES, STR350/351 has the following functionality:
•Temperature sensor . Use either the built in thermistor element or
another temperature sensor available on the LonWorks network
•Actual temperature display. The actual zone temperature can be
displayed on the LCD, but can also be hidden if desired.
•Temperature setpoint display. The temperature setpoint can be
displayed, either as an absolute value or as an offset.
Schneider Electric Buildings AB, Mar 201015 (88)
04-00069-01-en
2 Zone Controller TAC Xenta 102-ES Zone Controller, TAC Xenta 102-ES
Fig. 2.2: Wall module STR150
Bypass button
Increase/Decrease
buttons
Fan speed control
Display
•Temperature setpoint adjustment. The temperature setpoint can
be adjusted, either as an absolute value or as an offset.
•Bypass or on/off button. There is a bypass function which forces
the controller to comfort mode for a configurable period of time.
The same button can alternatively be used as an on/off button.
•Mode Indicator. An On/Off symbol in the LCD indicates the
mode of the control.
For technical details of the functionality listed above, additional functionality and for configuration details, see the STR350/351 configuration and data sheets.
Use the LNS plug-in to configure STR350/351.
2.2.2STR150
16 (88)Schneider Electric Buildings AB, Mar 2010
STR150 connects to TAC Xenta 102-ES with two or three wires. The
third wire is used only if mode indication in the LCD is desired. On the
other two wires information is sent from the wall unit to the controller:
•Zone temperature. The temperature sensed by the thermistor ele-
•Temperature setpoint. The temperature setpoint, which is dis-
•Bypass button. The bypass button forces the controller to comfort
The mode indication signaled on the third wire is connected to the man
symbol in the LCD:
•Comfort mode (On) is indicated by a steady man symbol
ment.
played as an absolute temperature, but transmitted as an offset to
the configured reference temperature.
mode for a fixed period of time (2 h).
04-00069-01-en
Zone Controller, TAC Xenta 102-ES2 Zone Controller TAC Xenta 102-ES
Fig. 2.3: Wall module STR104
Mode indicator
On/Off
Bypass button
Temperature
setting wheel
Fan speed control
•Economy (Standby) mode is indicated by a flashing man symbol.
•Unoccupied (Off-mode) is indicated by the man symbol being off.
There is no communication from the controller to the unit so if a setpoint
is changed from TAC Vista, this new value cannot be displayed on
STR150.
Configuration of STR150 is done using the buttons and display on the
unit. See STR150 configuration and data sheets for details.
2.2.3STR100-104
STR100-104 is a series of room units that connects to I/O terminals of
TAC Xenta 102-ES. The functionality of the various models is given in
the Table 2.1, “STR100-104 functionality”.
Table 2.1: STR100-104 functionality
ModelTemp Sensor
STR100X
STR101XX
STR102XXX
STR103XXX
STR104XXXX
Mode
Indicator
Setpoint
Adjustment
STR104 is shown in Fig. 2.3 as an example.
Bypass Button
Note
•The T AC Xenta OP is normally connected direct ly to the controller, not the wall module. The TAC Xenta 101-VF has a TAC
Xenta OP access connecter (type RJ-10) on the controller instead
of dedicated terminals for the wall module.
Schneider Electric Buildings AB, Mar 201017 (88)
04-00069-01-en
2 Zone Controller TAC Xenta 102-ES Zone Controller, TAC Xenta 102-ES
Depending on model the following functionality may be present:
•Temperature Sensor. All models have a 1.8Kohms@25°C ther-
mistor element.
•Temperature Adjustment. The temperature setpoint can be
adjusted. Using the plastic keys on the rear of the core panel the
adjustment range can be set.
•Mode Indicator. The green LED indicates the control mode:
•Comfort mode (On) is indicated by a steady green light
•Economy (Standby) mode is indicated by a flashing green
light.
•Unoccupied (Off-mode) is indicated by the LED being off.
•Bypass button. The bypass button forces the controller to comfort
mode for a configurable period of time.
Refer to STR100-107 data sheet and installation sheet for details.
2.2.4Wall Module Configuration
Wall Module Choice
STR150 is enabled by nciAppOptions bit 14:
•0 = ZS and STR100-104 or STR350/351 (default)
•1 = STR150
This can be set using the LonMaker Xenta100 plug-ins in Toolp ack ver-
sion 2.01 or higher, or by means of TAC Xenta OP.
Initial Start Up Status
•SpaceTemp in the application is set to +20.00 Celsius (This can be
read in the nvoSpaceTemp, but not in nviSpaceTemp.)
•Fan is set to Fan Auto
TAC Xenta is now waiting for data from the STR module.
If no room temperature readings are received within 10 minutes, the
SpaceTemp in the application is set to “invalid”. This is shown as
“invalid” in nvoSpaceTemp.
When the first update is received , then the 10 minute limit is changed
to 5 minutes.
18 (88)Schneider Electric Buildings AB, Mar 2010
04-00069-01-en
Zone Controller, TAC Xenta 102-ES2 Zone Controller TAC Xenta 102-ES
Unless there is a restart, the Offset + Fan values are not cleared and the
last value is valid..
Note
•Fore more information on how to configure and engineer the
STR series of wall modules see the documents for each product
respectively.
2.3Applications
2.3.1General
The TAC Xenta 102-ES controller incorporates several features including
•a built-in air flow sensor and controller algorithms.
•the facility to connect a window contact sensor to stop the heating
and cooling functions should a window be opened (Section 5.3.5,
“Window Contact”, on page 52).
•an occupancy sensor that can detect the presence of a person in the
controlled zone and change the controller from economy to comfort mode (Section 5.3.6, “Occupancy Sensor”, on page 52).
•an air quality control function that can be activated if a carbon dixoide sensor is connected. When a sensor is connected, the controller ensures that the concentration of carbon dioxide in the zone
between preset limits (Section 5.3.4, “Air Quality Control”, on
page 51).
•an auxiliary temperature sensor that can be connected to measure
any temperature and present it as a SNVT (Section 5.3.9, “Additional Features”, on page 55).
2.3.2The Zone Controller TAC Xenta 102-ES
The controller is designed for the following applications:
•Damper control only
•Damper control with primary heating and one free network output
•Damper control with primary and secondary heating
For fan control applications see Section 5.3.3, “Fan Control”, on
page 50.
Damper Control Only
The zone temperature is maintained by controlling of the airflow
damper. The airflow is limited to maximum and minimum.
An optional occupancy and/or a CO2 sensor can be connected.
Schneider Electric Buildings AB, Mar 201019 (88)
04-00069-01-en
2 Zone Controller TAC Xenta 102-ES Zone Controller, TAC Xenta 102-ES
Fig. 2.4: Damper control for TAC Xenta 102-ES
Widow contact
Air flow sensor
Damper
Free Network
control output
CO
2
sensor
Wall module
Occupancy sensor
Auxiliary temperature
sensor
The free network output (V6) can be used in this application.
For applications with fan control, see Section 5.3.3, “Fan Control”, on
page 50.
Damper and Primary Heating Control
The zone temperature is maintained by sequence control of the airflow
damper and primary reheating. The airflow is limited to maximum and
minimum. The reheat control is achieved by an increase/decrease or
thermal actuator.
An optional occupancy and/or a CO2 sensor can be connected.
The free network controlled output (V6) can be used in this application
(see Section 5.3.9, “Additional Features”, on page 55).
20 (88)Schneider Electric Buildings AB, Mar 2010
04-00069-01-en
Zone Controller, TAC Xenta 102-ES2 Zone Controller TAC Xenta 102-ES
Fig. 2.5: Damper and reheat control for TAC Xenta 102-ES
Widow contact
Air flow sensor
Damper
Free Network
control output
CO
2
sensor
Wall module
Occupancy sensor
Auxiliary temperature
sensor
Fan
Relay
Actuator
Valve
reheat
For applications with fan control, Section 5.3.3, “Fan Control”, on
page 50.
Damper Control and Two Stages of Reheat Control
The zone temperature is maintained by sequence control of the airflow
damper, primary reheating and secondary reheating. The airflow is limited to maximum and minimum. The reheat control is achieved by an
increase/decrease or a thermal actuator for primary reheat and thermal
actuator for secondary reheat.
An optional occupancy sensor and a CO2 sensor can be connected.
Schneider Electric Buildings AB, Mar 201021 (88)
04-00069-01-en
2 Zone Controller TAC Xenta 102-ES Zone Controller, TAC Xenta 102-ES
Fig. 2.6: Damper and two stages of reheat control for
TAC Xenta 102-ES.
Widow contact
Air flow sensor
Damper
Thermal actuator
CO
2
sensor
Wall module
Occupancy sensor
Auxiliary temperature
sensor
Fan
Relay
Actuator
Radiators
For applications with fan control, see Chapter 5.3.3, “Fan Control”, on
page 50.
22 (88)Schneider Electric Buildings AB, Mar 2010
04-00069-01-en
Zone Controller, TAC Xenta 102-ES3 Installation
Fig. 3.1: TAC Xenta 102-ES fixed to a DIN rail
3Installation
3.1Mechanical Installation
3.1.1Fitting
TAC Xenta 102-ES can either be snapped onto a DIN rail (Fig. 3.1) or
fixed to a level surface with two screws. (Fig. 3.2).
To fasten the controller onto a DIN rail:
1Place the controller on the top of the rail as shown by arrow 1.
2Twist the controller downwards until it snaps onto the rail as
shown by arrow 2.
3To remove, use a screwdriver to locate the lock on the bottom of
the controller and pull down. Then lift the controller diagonally
upwards and off the rail.
Schneider Electric Buildings AB, Mar 201023 (88)
04-00069-01-en
3 Installation Zone Controller, TAC Xenta 102-ES
Fig. 3.2: TAC Xenta
102-ES fixed to a
level surface
!
Fixing the Controller to on a Level Surface:
Use the two sockets provided for fixing the controller; the maximum
screw size is M4 or ST 3,5 (Ø 0.15"). The head of the screw should not
exceed 7,5 mm (0.3") in diameter.
3.2Electrical Installation
3.2.1General
Warning
•All mains supply cables must be installed by authorized electricians.
1Each controller or group of controllers must use max. 6 A fuses.
2Avoid hanging or loose cables by using clamps to secure them to
the controller.
3A switch to cut off the power supply to the controller or compete
unit must be easily accessible.
4When no carbon dioxide sensor is connected to the terminals a
jumper must be used to connect U1 and M.
5When several Xenta controllers receive power from a common
transformer, it is important that all Gs are connected to each other
and that all G0s are connected to each other. NB! the connections
are not interchangeable. Important exception: the G0 on the wall
module should be connected to the terminal OP on the controller
and not to the other G0's. The G0 should be grounded at the transformer to prevent interference. At the transformer, G0 should be
connected to protective earth. This is to get an grounding point for
interference diversion.
24 (88)Schneider Electric Buildings AB, Mar 2010
04-00069-01-en
Zone Controller, TAC Xenta 102-ES3 Installation
6To ensure that the spec ified measuring accuracy is achieved, the
two M terminals must be connected to the wall module.
Note that this equipment has been tested and found to comply with the
limits for a Class B digital device, pursuant to part 15 of the FCC Rules.
These limits are designed to provide reasonable protection against
harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed
and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that
interference will not occur in a particular installation. If this equipment
does cause harmful interference to radio or television reception, which
can be determined by turning the equipment off and on, the user is
encouraged to try to correct the interference by one or more of the following measures:
•Reorient or relocate the receiving antenna.
•Increase the separation between the equipment and receiver.
•Connect the equipment into an outlet on a circuit different from
that to which the receiver is connected.
•Consult the dealer or an experienced radio/TV technician for help.
Safety Standard
Transformers supplying the controller must comply to the safety standard EN 60 742 or any other relevant safety standard for ELV, 24 V AC.
When equipment with a power supply of its own is connected, this
power supply must also comply with this norm.
Cable Lengths
For information on communication cable lengths, see TAC Xenta Network Guide, part number 0-004-7460. For all other cables, maximum
length is 30 m (100 feet) and min. area is 0,7 mm
2
(AWG-19).
The Wall Modules
The STR100-104 is primarily intended for use with the Xenta 103. The
wall module STR150 can also be used, but in this case the fan speed button is not used. For more information about how to connect and configure wall modules, please refer to the documentation for each respective
product.
Schneider Electric Buildings AB, Mar 201025 (88)
04-00069-01-en
3 Installation Zone Controller, TAC Xenta 102-ES
Connection Terminals
The designation of the connection terminals can be found on the label
on the front of the controller and the numbers of the terminals can be
found on the edge of the printed circuit board.
Termin.Design.FunctionType
1C1TP/FT-10 communication channel2C2TP/FT-10 communication channel-
a
3
4MMeasurement neutral-
a
5
6B2Optional temperature sensorThermistor input
7MMeasurement neutral8U1Carbon dioxide sensor or jumperThermistor input
9D1LED on wall moduleDigital output
10MMeasurement neutral
11X1Bypass key on wall moduleDigital input
12R1Setpoint adjustment on wall module10k Ohm linear potentiometer
13MMeasurement neutral14B1Zone temperature sensorThermistor input
15G24V AC (G)Input
16G024 V AC (G0)Input
b
17
18G24 V AC supply for TA C Xenta OP19V1Damper actuator: increaseTriac
20G24V AC (G) supply for V1, V221V2Damper actuator: decreaseTriac
22V3Reheat actuator: increase
23G24 V AC (G) supply for V3, V424V4Reheat actuator: decrease
25V5Fan on/off controlTriac
26G24 V AC (G) supply for V5, V627V6Thermal actuator or free network outputTriac
28Y1Primary reheat demandOutput 0-10 V
a. See chapter 4 Configuration parameters
b. Connected to G0 on the wall module. Do not connect to G0 on the controller..
X3Window contact
Closed contact=closed window)
X2Occupancy sensorDigital input
OP24 V AC supply for TAC Xenta OP-
Thermo actuator: on/off parallel V4
Thermo actuator: on/off parallel V3
Digital input
Triac
Triac
26 (88)Schneider Electric Buildings AB, Mar 2010
04-00069-01-en
Zone Controller, TAC Xenta 102-ES3 Installation
Optional temperature input
Carbon dioxide sensor
Occupancy sensor
Window contact
Junction Box
20
G
G0
G
15
16
G
OP
17
18
19
V1
C2
C1
1
2
X3
3
4
X2
5
6
24
22
21
V2
23
V3
V4
25
Y1
26
27
28
10
8
7
B2
U
1
D
1
9
X1
11
R
1
12
13
B1
14
TAC Xenta
102-ES
GW1 GX1GQ1
G
G
V5
V6
Lon Talk"
TP/FT-10
COM
INC.
24 VAC
Damper actuator
Network controlled output
DEC.
6
9
(mm)
+
–
2
M
M
M
M
OP
C1
C2
Wall Module
2122
2423
G
M
Therm
LED
Pot/Pot+R
Mx
Switch
12
11
13
14
15
16
STR101-104
3
1
U1 should not be left unconnected. If no sensor will be used, connect U1 to M.
2
Tubing. Should be connected before the controller is mounted on the wall.
3
Air flow sensor, e.g. TAC GV
2
Fig. 3.3: Wiring of TAC Xenta 102-ES
3.2.2Wiring of Xenta 102-ES, Application with Damper Control Only
Read Section 3.2.1, “General”, on page 24 before you connect the
cables as shown in the wiring diagram in Fig. 3.3.
Schneider Electric Buildings AB, Mar 201027 (88)
04-00069-01-en
Loading...
+ 61 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.