Schneider Electric 865-V, 866-V, 885-V Installation Instructions

0 (0)
Schneider Electric 865-V, 866-V, 885-V Installation Instructions

Installation Instructions

i2/b3 865/866/885-V Controller

30-3001-985 Rev G.4

Alternative Damper Shaft

Mounting Screw Position

Damper Shaft

Hex Mounting Screws

Alternative Damper Shaft

Mounting Screw Position

Damper Shaft

Damper Shaft Collar

Cover Release

4-Position Dipswitch

 

 

 

 

Velocity Sensor

P1

(LO)

Inputs

P2

(Barbed fittings)

 

 

 

(HI)

Two CPU LEDs

 

 

 

 

 

Green = b3 controller

 

 

 

Yellow = i2 controller

 

 

 

Note: Input, Output, and Smart Sensor connections will vary per controller model.

Adjustable Stops

Mounting Clip

 

Actuator Clutch Release

(LOW)

 

AIR FLOW

866-V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INPUT

 

 

 

(HIGH)

 

CAUTION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MORE THAN ONE DISCONNECT SWITCH

 

 

 

 

 

MAY BE REQUIRED TO DE-ENERGIZE THIS

 

 

 

 

 

EQUIPMENT BEFORE SERVICING.

 

 

 

1

IN1

 

This equipment complies with part 15 of the FCC rules.

 

Operation is subject to the following two conditions.

RS-485

 

 

 

 

 

(1) This device may not cause harmful interference.

2

IN2

 

(2) This device must accept any interference received,

PORT

 

including interference that may cause undesired

 

 

 

 

 

operation.

 

 

 

3

RET

 

UNIVERSAL

 

 

 

 

 

 

 

 

 

 

 

4

IN3

 

INPUTS

ANALOG

 

 

 

 

 

5

IN4

 

 

 

 

 

OUTPUTS

 

 

 

 

 

0-10 VDC

 

 

6

RET

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7

SPWR

 

SMART

DIGITAL

 

 

 

 

 

8

RET

 

OUTPUTS

 

SENSOR

 

 

 

 

 

24VAC ,

9

IN5

 

 

 

 

 

 

USE COPPER CONDUCTORS ONLY

0.5A

 

10 24VAC

 

 

 

 

 

INPUT: CLASS 2 POWER ONLY

 

 

 

 

 

 

 

 

 

 

 

11

 

 

 

 

24VAC , 0.42A, 10VA, 50/60HZ

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COM 21

COM 20

SHIELD 19

A07 18

RET 17

AO6 16

TRIAC REF 15

OUT5 14

OUT4 13

OUT3 12

Mounting Bracket

Cover Release

 

Damper Position Indicator

Alternate

Mounting Bracket

Cover Release

Battery Location (Remove cover)

Service Port Location

(Remove cover)

Jumper for Actuator

Direction

TD LED = Yellow

RD LED = Green

Wireless LED = Red

Wiring Requirements: 300V

8A

22 - 12AWG

6 inch-lb screw tourque

i2/b3 865/866/885-V Controller Installation

To install the controller, follow these steps:

2.

The actuator is designed to mount over a 1/2” (12.7 mm) diameter

 

 

shaft with a minimum of 2.5” (63.5 mm) of exposed shaft. If the

 

 

damper shaft diameter is less than 1/

” (12.7 mm) an adapter is

1. Check the mounting location for the Andover Continuum i2 or b3

 

2

 

 

 

required. An adapter (p/n AM-135) is available from Schneider

865/866/885-V controller. The unit is typically mounted with the

 

Electric to allow mounting on 3/8” (9.5 mm) damper shaft. The

controller extending down or to the right from the damper shaft.

 

865/866/885-V controller will not work with larger damper shaft

However, the controller can be operated in any position within

 

diameters.

 

 

the vertical plane.

3.

If the exposed damper shaft is less than 2” (51 mm) but at least 1”

Note: Installing the controller to the right (with the barbed

 

(25.4 mm) long, move the two damper shaft mounting screws to the

fittings pointing down) helps prevent condensate from

 

alternate lower damper shaft positions.

migrating into the on-board velocity sensor.

4.

Select the mounting bracket location that provides the most stability

With a downward extension, the available area around the damp-

 

for the operation of the actuator. Position the mounting clip in the

er shaft must measure 6” (160 mm) down from the lower edge

 

desired mounting bracket. Do not insert the clip more than half-way

of the shaft, 4.5” (120 mm) to the right, 1.5” (40 mm) to the left

 

into the bracket. This allows the clip and the back of the actuator to

and 1.75” (45 mm) above the shaft. Ensure the location allows

 

properly align with the VAV box.

 

 

enough clearance for servicing.

 

 

 

 

 

 

 

 

 

© 2018 Schneider Electric, all rights reserved.

i2/b3 865/866/885-V Controller Installation (continued)

5.Press and hold the green actuator clutch release and rotate the VAV damper shaft by hand to the fully closed position. Note whether the damper is rotated clockwise (CW) or counter-clock- wise (CCW) to close.

6.Slip the controller over the damper shaft. Position the actuator and, using a self tapping sheet metal screw, secure the mounting clip to the VAV box.

7.Next, press the actuator toward the box until the actuator comes into contact with the VAV box, the mounting clip snaps into the bracket, or the back of the actuator comes into contact with the VAV box.

8.Press and hold the green actuator clutch release (see Figure  on cover page) and rotate the actuator collar to a nearly closed position, the 5° index mark, if the damper shaft was rotated counter-clockwise to close (Step 5). Rotate the actuator collar to the 85° index mark if the damper shaft was rotated clockwise to close (Step 5).

9.Tighten the two damper hex mounting screws using a 1/8” hex Allen wrench. The minimum torque required to secure the controller to the damper shaft depends on the shaft material. The maximum torque for the socket screws is 30 inch-pounds (3.4 Nm).

Note: The damper should rotate freely when the clutch is released. If it does not, the actuator may not be properly aligned with the damper shaft – it may be necessary to repeat Steps 4 through 9 using a new orientation.

10.If the damper does not provide a mechanical stop in the open direction, or it is not desirable to use the damper’s open stop, set the adjustable stops on the 865/866/885-V controller to the desired position. Use a 1/4” hex driver to adjust the screw stop on the controller.

Note: For the 866-V model only, you must calibrate the damper position feedback reporting option before using. You calibrate damper position feedback reporting by changing the damper’s output attribute, LCDState, from DISABLED to ENABLED. The attribute, OverrideValue, indicates the damper position as a fractional value from 0 (at the closed stop) to 1 (at the open stop).

Whenever the Actuator Clutch Release button is pressed and the Actuator is moved manually, you need to recalibrate damper position feedback reporting. During damper calibration, the damper output will rotate from one endstop to the other and then return to its original position. It is also recommended that you periodically recalibrate damper position feedback reporting using a Plain English (PE) program.

AC Power Connection

 

24 VAC Step-Down

 

or Isolation Transformer

 

X1

AC Line

10 24VAC

11

Power

 

 

X2

Optional Varistor

 

 

 

 

 

 

 

 

(Choose a voltage rating appropriate

Each controller on the network must have its own

 

 

 

 

 

 

 

to the input voltage applied.

 

 

 

 

 

 

Class 2 power only!

 

 

 

 

 

 

For example, 130V or 250V)

24V Step-Down or Isolation Transformer. Be sure to

 

 

wire the secondary of the 24V Step-Down Transformer

 

 

exactly as shown. Pin 11 must be connected to the grounded

 

 

side of the secondary on all transformers used in the system.

 

 

Otherwise, damage to one or more controllers may result.

 

Note: Use care when attaching power wiring to these connectors. They are not to be used as a strain relief. The connectors cannot withstand excessive bending or flexing.

Failing to install this transformer on remote controllers can damage it and other controllers on the network.

Wiring Rules

These modules are intended for installation within the enclosure of another product.

Do not remotely ground any part of the input sensor wiring.

When stripping wire, be careful not to drop small pieces of wire inside the cabinet.

Don’t run your input wiring in the same conduit with AC power.

Don’t run your input wiring in the same conduit with your output wiring.

Remote grounds connected to the return terminal could make the system operate incorrectly or damage the equipment.

The signal return is not true earth ground. It is an electronic reference point necessary to interpret the sensor properly.

For reliable input operation, follow these input wiring guidelines:

Never lay wires across the surface of a printed circuit board.

Wires should never be within 1” or 25 mm of any component on a printed circuit board.

Use shielded input wire.

Terminate the shield of the input wires at one end of the run only — preferably at the end where your I/O module is located.

Grounding the Controller

To insure proper operation of the controller, it must be connected to a good earth ground.The connection must be made as close to the module as possible.

Caution: Earth ground ( ) must be connected to avoid module damage.

Removing the Plastic Battery Tab

Before operating the controller, open the cover and remove the protective plastic battery tab. The battery location is shown in the illlustration on the cover page.

Connecting the Air Velocity Sensor

 

 

1. Connect the low pressure side of the velocity sensor to the barbed

 

fitting labeled P1 (LO) on the controller.

 

2. Connect the high pressure side of the velocity sensor to the fitting

 

labeled P2 (HI) on the controller.

 

Notes: Use a recommended maximum length of 4’ (1.2 m) FRPE

 

plyetheylene tubing or 0.25” (6.34 mm) O.D. and 0.125”

 

(3.175 mm) I.D. Tygon tubing.

 

Do not expose the velocity sensor to moisture. If moisture

4’

condensation is a potential problem, orient the tubing and

controller so that the barbed fittings are above the lowest

(1.2 m)

part of the tubing to create a moisture trap.

Tubing (Max.)

 

Connections for i2/b3 865-V Controller

Connections for i2/b3 866-V Controller

(LOW)

 

INPUT

865-V

 

 

AIR FLOW

 

(HIGH)

 

 

 

 

 

1IN 1

2IN 2

3RET

4IN 3

5IN 4

6RET

7SPWR

8RET

9IN 5

1024VAC

11

CAUTION

MORE THAN ONE DISCONNECT SWITCH MAY BE REQUIRED

TO DE-ENERGIZE THIS EQUIPMENT BEFORE SERVICING.

UNIVERSAL INPUTS

This equipment complies with part 15 of the FCC rules. Operation is subject to the following two conditions.

(1) This device may not cause harmful interference.

(2) This device must accept any interference received, including interference that may cause undesired operation.

SMART

SENSOR

USE COPPER CONDUCTORS ONLY

INPUT: CLASS 2 POWER ONLY

24VAC , 0.42A, 10VA, 50/60HZ

COM 18

RS-485 COM 17 PORT

SHIELD 16

 

TRIAC REF

15

DIGITAL

OUT5

14

OUTPUTS

 

 

24VAC ,

OUT4

13

0.5A

OUT3

12

 

(LOW)

 

INPUT

866-V

 

 

AIR FLOW

 

(HIGH)

 

 

 

 

 

1IN 1

2IN 2

3RET

4IN 3

5IN 4

6RET

7SPWR

8RET

9IN 5

1024VAC

11

CAUTION

MORE THAN ONE DISCONNECT

 

SWITCH MAY BE REQUIRED

RS-485

TO DE-ENERGIZE THIS EQUIPMENT

PORT

BEFORE SERVICING.

 

UNIVERSAL

INPUTS

This equipment complies with part 15 of the FCC rules. Operation is subject to the following two conditions.

(1) This device may not cause harmful interference.

(2) This device must accept any interference received, including interference that may cause undesired operation.

SMART

SENSOR

USE COPPER CONDUCTORS ONLY

INPUT: CLASS 2 POWER ONLY

24VAC, 0.42A, 10VA, 50/60HZ

ANALOG

OUTPUTS 0-10 VDC

DIGITAL OUTPUTS 24VAC, 0.5A

COM 21

COM 20

SHIELD 19

A07 18

RET 17

AO6 16

TRIAC REF 15

OUT5 14

OUT4 13

OUT3 12

Airflow Input

Airflow Input

One Low and one High connection

One Low and one High connection

Universal Inputs

Universal Inputs

Four input and two return connections — terminals 1-6

Four input and two return connections — terminals 1-6

Smart Sensor Bus Interface

Smart Sensor Bus Interface

One Smart Sensor connection — terminals 7-9

One Smart Sensor connection — terminals 7-9

Power Connection

Power Connection

One 24 VAC connection and ground — terminals 10-11

One 24 VAC connection and ground — terminals 10-11

Digital Outputs

Digital Outputs

Three output connections and one triac reference — terminals 12-15

Three output connections and one triac reference — terminals 12-15

RS-485 Port

Analog Outputs

One port for a BACnet MS/TP or Infinet connection — terminals 16-18

Two analog outputs and one return connection — terminals 16-18

 

RS-485 Port

 

One port for a BACnet MS/TP or Infinet connection — terminals 19-21

Loading...
+ 5 hidden pages