Schneider Electric 3BZ2, FBZ2, EOCR-i3BZ, iFBZ User Manual

5 (2)
Schneider Electric 3BZ2, FBZ2, EOCR-i3BZ, iFBZ User Manual

The world's first EOCR with built-in ZCT

(bottom hole & terminal type)

will save space, time and wiring through unique development design during installation.

with compact size, possible to be applied to various panel size. the protection function added for high groud fault current.

most suitable for low frequency circumstance (5Hz~, Inveter use) can cover wide range current through product innovation,

so it leads to the decrease of customer's managing stocks and simplicity of replacement.

Samwha EOCR has been developing the products only related to EOCR for around 30 years, since established and now challenging the conquering of world market with the real speciality for EOCR that other companies never have.

Customer care center 1588-3473 | www.eocr.com

Applications

Building

Industrial facilities

Office, commercial business, residence, school, hospital

Petrochemical, electronic, glass, steel, semiconductor,

 

chemical, medicine, cement, paint

Control power

24 VDC

85~260 VAC/DC, 50/60 Hz

Composition by function

Earth Fault

i3BZ, iFBZ (with Modbus RS-485)

3BZ2, FBZ2 (without Modbus RS-485)

Contact contact

A-Type

95-96(b), 97-98(a) : OL

57-58(a) : GR

C-Type

95-96(b), 97-98(a) : OL/GR

07-08(a) : AL/UL/TO

Public institutions

Rated current

Over current : 0.5~80A (Definite)

GF current : 0.03A~10A

5~200Hz Variable frequency measurement

Motor protection

Thermal Overload

Over/under current

Stall/Jam

EF current

Phase loss/lmbalance

Network communication

Modbus RS-485

Gas, water supply and drainage, airport, train, port

EOCR-i3BZ/iFBZ/3BZ2/FBZ2

EOCR-i3BZ / iFBZ : Intelligent Digital Over-Current, Earth Fault Relay with built-in ZCT,

EOCR-3BZ2 / FBZ2 : Economic Digital Over-Current, Earth Fault Relay with built-in ZCT

EOCR-i3BZ / i3BZ2 Bottom hole type

 

EOCR-iFBZ / iFBZ2 Bottom hole type

 

 

 

 

 

 

EOCR-i3BZi / 3BZ2 Terminal type

 

EOCR-iFBZ / iFBZ2 Terminal type

 

 

 

General Features

Earth fault detection by built-in ZCT

Multifunctional motor protection for rated motor currents up to 80A (Definite Overcurrent protection) : Over Current, Under Current, Phase Loss, Phase Reversal, Stall, Jam, Current Imbalance, Earth Fault

Thermal Inverse / Inverse overload protection up to 32Amps by integrated CTs.

Real Time Processing / High Precision

Ancillary Functions : Fail Safe, Alert(“C” Type Only), Accumulated Running Hour, 3 Fault records & limitation of auto-reset attempt.

Communication : Modbus-RTU/RS-485(i3BZ/iFBZ only)

Reinforced Monitoring Function : Real Time Monitoring up to 400M, 3 Phase Current Display, Pre-alarm & Cause of Trip indication.

Load ratio indication of Load Current to over-current threshold.

Support Single-phase and 3 Phase Motor

For iFBZ / FBZ2, normal operation except display is guaranteed when PDM is disconnected

6

EOCR-i3BZ/iFBZ/3BZ2/FBZ2

EOCR-i3BZ / iFBZ : Intelligent Digital Over-Current, Earth Fault Relay with built-in ZCT,

EOCR-3BZ2 / FBZ2 : Economic Digital Over-Current, Earth Fault Relay with built-in ZCT

Protection functions

Item

Operating Condition & Setting Range

Operation Time

Over Current (oc)

Load current(In) exceeds threshold(Is)

Definite(Def) : 0.2~30s Adjustable

Setting Range : 0.5~80A(Def), 0.5~32A(Inv & th)

Inverse(Inv) & Thermal(th) : 1~30 Class

 

 

 

 

Under Current (uc)

Load current(In) less than threshold(uc) In <= uc

oFF, 1~30s Adjustable

uc should be less than oc Setting

 

 

 

 

 

Phase Loss (PL)

max imbalance is more than 85% among 3 phase current,

oFF, 0.5~5s Adjustable

Enable or disable : Selectable

 

 

 

 

 

Reverse Phase(rP)

Reversed phase sequence input on EOCR.

Within 0.15s

Enable or disable : Selectable

 

 

 

 

 

 

Active only in motor starting, In ≥Stall threshold (Sc×OC).

 

Stall (Sc)

Setting Range : Adjustable

Immediately after D-Time elapsed

 

2~8 times of oc setting if Sc×OC doesn’t exceed 250A

 

 

 

 

 

Active only in motor running, In ≥Jam threshold (JA×OC).

 

Jam (JA)

Setting Range :

0.2~10s Adjustable

 

1.5~8 times of oc setting if JA×OC doesn’t exceed 250A

 

 

 

 

 

Current unbalance ≥threshold1~10s Adjustable.

 

Unbalance (ub)

Setting Range : 10~50%

1~10s Adjustable

Unbalance[%] = 100 ×(Max phase current - Min phase current)/

 

 

 

Max phase current

 

 

 

 

Earth Fault (EF)

EF current(Ie) exceeds threshold(Ies)

0.1~10s Adjustable

Setting Range : oFF, 0.03~10A

 

 

 

 

 

 

Auxillary functions

Password

Secure configuration, available only with i3BZ/iFBZ

 

 

Communication

Serial network communication for monitoring of metering, status, and fault history

 

 

Fail Safe

Enable/Disable fail-safe operation of OL trip output

 

 

Phase selection

Select a Single-phase motor or 3-Phase motor

 

 

Total Running-Hour

Record of total running from installation which cannot be modified or cleared

 

 

Running-Hour

Accumulated running hour from preset point which can be cleared to zero, when motor stops

 

 

Fault History

Records for recent 3 faults each phase current which stored in a non-volatile memory

 

 

Limitation of autoreset attempt

Block auto-reset if the reset count exceeds the pre-set count within 30 minutes

 

 

Communication function (Applicable to i3BZ/iFBZ)

Item

Setting

 

 

Remark

Protocol type

Modbus RTU

 

 

 

 

 

 

 

 

Communication type

RS-485

 

 

 

 

 

 

 

 

Baud rate

1.2, 2.4, 4.8, 9.6, 19.2, 38.4 kbps

 

 

 

 

 

 

 

 

Maximum length of the bus

Maximum 1.2kM

 

 

Depend on the environment

 

 

 

 

 

Type of trunk cable

RS-485 Shielded Twist 2-Pair Cable

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 