Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety
Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1
your local Rockwell Automation sales office or online at http://www.rockwellautomation.com/literature/
important differences between solid-state equipment and hard-wired electromechanical devices. Because of this difference,
and also because of the wide variety of uses for solid-state equipment, all persons responsible for applying this equipment
must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the
use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or
liability for actual use based on the examples and diagrams.December
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or
software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation,
Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
available from
) describes some
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment,
which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property
damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous
voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may
reach dangerous temperatures.
Identifies information that is critical for successful application and understanding of the product.
Allen-Bradley, CompactLogix, ControlFLASH, FactoryTalk, FLEX, Integrated Architecture, Kinetix, Lo gix5000, PanelView, POINT I/O, PowerFlex, Rockwell Software, Rockwell Automation, RSLinx, RSLogix, Stratix
6000, Studio 5000, and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Follow the path that matches your hardware and network configuration.
PORT
MOD
NET B
NET A
STS
Create a Logix Designer Project
Prepare the CompactLogix 5370 L1
Controller Hardware
Prepare the Computer and Load
Controller Firmware
Configure the EtherNet/IP
Network
Required
Required
Optional
Required
page 17
page 31
page 45
page 51
Optional
POINT I/O™
Modules
Kinetix® 350
Drive
Power Flex® 40
Drive
PowerFlex 70
Drive
Panel View™
Plus Terminal
For more information on using each optional
device, see Table 1 on page 12
.
00:00:BC:2E:69:F6
Where to Start
1734-AENTR
02
0
POINT I O
Module
Status
Network
Activity
Network
Status
Point Bus
Status
Link 1
Activity/
System
Status
Power
Field
Power
IP ADDRESS
Link 2
Activity/
Status
00:00:BC:2E:69:F6
Rockwell Automation Publication IASIMP-QS024B-EN-P - December 20123
Where to Start
PORT
MOD
NET B
NET A
STS
1
2
34
56
78
Kinetix 350 Drive
Stratix 6000
™
Switch
CompactLogix 5370 L1
Control System
PowerFlex 70 Drive with
20-COMM-E Adapter
PowerFlex 40 Drive with
22-COMM-E Adapter
PanelView Plus Terminal with Built-in
EtherNet/IP Port
Compu ter
Distributed POINT I/O Modules with
1734-AENT Adapter
Star Network Topology
Application Configuration
How Hardware is Connected
This quick start, in use with the additional quick starts listed in Ta bl e 1 on pag e 12 , describes a
™
CompactLogix
5370 L1 control system as shown in Figure 1.
Figure 1 - CompactLogix 5370 L1 Controller in a Star Network Topology
4Rockwell Automation Publication IASIMP-QS024B-EN-P - December 2012
Where to Start
IMPORTANT
PORT
MOD
NET B
NET A
STS
AC Line Filter
PowerFlex 70 DriveKinetix 350 Drive
Line Interface
Module
CompactLogix 5370 L1
Control System
Ethernet Switch
Distributed POINT I/O
Modules
Through-the-door
Disconnect
PanelView Plus Terminal
E-stop Push Button
Power Flex 40
Drive
Sample Panel Layout
The sample panel layout shows the orientation of an example CompactLogix 5370 L1 control
system using an EtherNet/IP network.
The graphic below is an example panel layout. The specific layout of CompactLogix 5370 L1 control systems varies
by application.
Rockwell Automation Publication IASIMP-QS024B-EN-P - December 20125
Where to Start
Notes:
6Rockwell Automation Publication IASIMP-QS024B-EN-P - December 2012
Table of Contents
Preface
Prepare the CompactLogix 5370 L1
Controller Hardware
8Rockwell Automation Publication IASIMP-QS024B-EN-P - December 2012
Preface
IMPORTANT
This quick start describes how to use CompactLogix 5370 L1 controllers to install a simple
CompactLogix 5370 L1 control system and execute a task with a local 1734 POINT I/O output
module. The programming examples included are not complex, and offer solutions to verify that
devices are functioning and communicating properly.
Consider the following points:
• A typical CompactLogix 5370 L1 control system includes more components than listed in this quick start. For
example, you can use 1734 POINT I/O modules over an EtherNet/IP network in a CompactLogix 5370 L1 control
system. Other quick starts describe how to use additional components with your control system.
For a list of quick starts describing how to use other components in Logix5000™ control systems, see Choose to
Integrate Optional Devices on page 12.
• Not all tasks described in this quick start are required to complete the final task, that is, use ladder logic to test a
1769-OB16 output module as described beginning on page 51. For example, you do not need a DeviceNet
configuration file to test the module.
We expect that you might attempt to complete additional tasks with your control system by using the publications
listed on page 12. When you use those publications, some assumptions are made. For example, if you use a
PanelView Plus terminal over an EtherNet/IP network in a CompactLogix 5370 L3 control system, you must have
already created project and assigned an IP address to the controller.
If you complete all of the tasks described in this quick start, you can easily complete the tasks described in the
publications listed on page 12.
The following topics are described in this quick start:
• Installing hardware for a basic CompactLogix 5370 L1 control system
• Installing software required for the basic CompactLogix 5370 L1 control system
Rockwell Automation Publication IASIMP-QS024B-EN-P - December 20129
Preface
IMPORTANT
IMPORTANT
• Configuring an EtherNet/IP network
You are not required to install nor configure an EtherNet/IP network to complete the tasks described in this quick
start. However, before you can complete the tasks described in some of the publications listed on page 12, you
must first install an EtherNet/IP network.
For example, Chapter 4, on Create a Logix Designer Project on page 51 describes how to use ladder logic to test a
1734-OB4E output module. The test is completed by using the output module in a local expansion slot in the
CompactLogix 5370 L1 control system and does not require use of a 1783-EMS08T Stratix 6000 managed switch
because it can be done via a USB connection to the controller.
If you use 1734 POINT I/O modules over an EtherNet/IP network in your CompactLogix 5370 L1 control system, as
described in the Logix5000 Control Systems: POINT I/O over an EtherNet/IP Network Quick Start, publication
IASIMP-QS027, you must install and configure an EtherNet/IP network.
Completing all of the tasks described in this quick start will assist you when attempting to complete the tasks in
some other quick starts, such as publication IASIMP-QS027.
• Creating a Logix Designer project
About the CompactLogix 5370 L1 Controllers
These CompactLogix 5370 L1 controllers are available:
• 1769-L16ER-BB1B
• 1769-L18ER-BB1B
• 1769-L18ERM-BB1B
The tasks described in this publication use a 1769-L18ERM-BB1B controller.
10Rockwell Automation Publication IASIMP-QS024B-EN-P - December 2012
These features are available on CompactLogix 5370 L1 controllers:
• Embedded 24V DC input nonisolated power supply
• Secure Digital (SD) card for nonvolatile memory storage
• Network connections:
– USB (single port)
– Support for EtherNet/IP network- Option to use the controller in device-level ring
(DLR), linear, and star topologies on EtherNet/IP networks
• I/O module options:
– Sixteen embedded 24V DC digital input points
– Sixteen embedded 24V DC digital output points
Preface
– 1734 POINT I/O modules as local expansion module
– Control of distributed I/O modules over an EtherNet/IP network
• Support for Integrated Motion on the EtherNet/IP network with the 1769-L18ERM-
BB1B controller only.
• For more information on using the 1769-L18ERM-BB1B controller in an application that
includes Integrated Motion on the EtherNet/IP network, see Appendix A, Understand ing
Other Application Options on page 65.
This graphic shows an example CompactLogix 5370 L1 control system.
00:00:BC:2E:69:F6
Rockwell Automation Publication IASIMP-QS024B-EN-P - December 201211
Preface
02
0
1734-AENTR
Module
Status
Network
Activity
Network
Status
Point Bus
Status
System
Power
Field
Power
POINT I O
Link 1
Activity/
Status
Link 2
Activity/
Status
IP ADDRESS
PORT
MOD
NET B
NET A
STS
Choose to Integrate Optional Devices
This table describes additional optional devices and their related documentation that you might
use in a CompactLogix 5370 L1 control system on an EtherNet/IP network.
You can view or download publications at http://www.rockwellautomation.com/literature/
.
Table 1 - Devices in Logix5000 Control System
Device TypeProduct Line
(1)
Additional Resource with More Information
Distributed I/OPOINT I/OLogix5000 Control Systems: Connect POINT I/O Modules over an EtherNet/IP Network
Quick Start, publication IASIMP-QS027
DrivesPowerFlex40Logix5000 Control Systems: Connect PowerFlex 40 Drives over an EtherNet/IP
Network Quick Start, publication IASIMP-QS029
PowerFlex 70Logix5000 Control Systems: Connect PowerFlex 70 Drives over an EtherNet/IP
Network Quick Start, publication IASIMP-QS031
Kinetix 350Logix5000 Control Systems: Connect Kinetix 350 Drives over an EtherNet/IP Network
Quick Start, publication IASIMP-QS032
HMI terminalsPanelView PlusLogix5000 Control Systems: Connect PanelView Plus Terminals over an EtherNet/IP
Network Quick Start, publication IASIMP-QS033
(1) You can use other I/O modules, drives, and HMI terminals in Logix5000 control systems. These product lines are used for example purposes.
12Rockwell Automation Publication IASIMP-QS024B-EN-P - December 2012
Preface
Studio 5000 Environment
The Studio 5000™ Engineering and Design Environment combines engineering and design
elements into a common environment. The first element in the Studio 5000 environment is the
Logix Designer application. The Logix Designer application is the rebranding of RSLogix™ 5000
software and will continue to be the product to program Logix5000 controllers for discrete,
process, batch, motion, safety, and drive-based solutions.
The Studio 5000 environment is the foundation for the future of Rockwell Automation
engineering design tools and capabilities. It is the one place for design engineers to develop all of
the elements of their control system.
Rockwell Automation Publication IASIMP-QS024B-EN-P - December 201213
Preface
Required Software
Before attempting to complete any of the tasks described in this publication, verify that your
computer meets the following operating system and service pack compatibility requirements:
• Microsoft Windows 7 Professional (64-bit) with Service Pack 1
• Microsoft Windows 7 Home Premium (64-bit) with Service Pack 1
• Microsoft Windows 7 Home Premium (32-bit) with Service Pack 1
• Microsoft Windows Server 2008 R2 Standard Edition with Service Pack 1
If your computer does not meet the operating system and service pack compatibility
requirements, perform the necessary upgrades before continuing.
Ta b l e 2
lists the software used in this quick start. Specific software requirements are listed at the
beginning of each chapter.
Table 2 - Software Used in This Quick Start
SoftwareMinimum VersionRequired
Studio 500021.00.00Yes
Logix Designer application21.00.00Yes
®
RSLinx
ControlFLASH™Automatically installed with the Studio 5000
Classic
3.51.00 or laterYes
Ye s
environment
14Rockwell Automation Publication IASIMP-QS024B-EN-P - December 2012
Preface
Parts List
Ta b l e 3 lists the hardware used in this quick start. Specific hardware requirements are listed at the
beginning of each chapter.
Table 3 - Parts Used with This Quick Start
QuantityCat. No.Description
1 or moreN/ADIN rail (steel, not aluminum)
1One of the following:
• 1769-L16ER-BB1B
• 1769-L18ER-BB1B
• 1769-L18ERM-BB1B
11606-XLP50ESwitched-mode power supply
11734-OB4EPOINT I/O 8-point 24V DC electronically-fused output module
CompactLogix 5370 L1 controller
The tasks described in this publication use a 1769-L18ERM-BB1B controller.
Additional Resources
These documents contain additional information concerning related products from
Rockwell Automation.
Table 4 - Additional Resources
ResourceDescription
CompactLogix 5370 Controllers User Manual,
publication 1769-UM021
Logix5000 Control Systems: Connect POINT I/O
Modules over an EtherNet/IP Network Quick
Start, publication IASIMP-QS027
Logix5000 Control Systems: Connect a
PowerFlex 40 Drive over a EtherNet/IP Network
Quick Start, publication IASIMP-QS029
Logix5000 Control Systems: Connect a
PowerFlex 70 Drive over an EtherNet/IP
Network Quick Start, publication IASIMP-
QS031
Rockwell Automation Publication IASIMP-QS024B-EN-P - December 201215
Describes how to design, install, operate, and troubleshoot a CompactLogix 5370
control system.
Describes basic steps required to include distributed POINT I/O modules over an
EtherNet/IP network in a Logix5000 control system, including hardware, firmware,
and software considerations.
Describes basic steps required to include PowerFlex 40 drives over an EtherNet/IP
network in a Logix5000 control system, including hardware, firmware, and software
considerations.
Describes basic steps required to include PowerFlex 70 drives over an EtherNet/IP
network in a Logix5000 control system, including hardware, firmware, and software
considerations.
Preface
Table 4 - Additional Resources
ResourceDescription
Logix5000 Control Systems: Connect a Kinetix
350 Multi-axis Servo Drive System over an
EtherNet/IP Network Quick Start, publication
IASIMP-QS032
Logix5000 Control Systems: Connect a
PanelView Plus Terminal over an EtherNet/IP
Network Quick Start, publication IASIMP-
EtherNet/IP Modules in Logix5000 Control
Systems, publication ENET-UM001
EtherNet/IP Media Planning and Installation
Manual, ODVA publication
Click here to access the publication
Industrial Automation Wiring and Grounding
Guidelines, publication 1770-4.1
Product Certifications website, http://
www.ab.com
Describes basic steps required to include Kinetix 350 Multi-axis Servo drives over an
EtherNet/IP network in a Logix5000 control system, including hardware, firmware,
and software considerations.
Describes basic steps required to include PanelView Plus terminals over an EtherNet/IP
network in a Logix5000 control system, including hardware, firmware, and software
considerations.
Provides details regarding the installation of ControlFLASH software and execution of
firmware upgrades.
Describes how to install, configure, and operate EtherNet/IP modules.
Describes how to design and install an EtherNet/IP network
Provides general guidelines for installing a Rockwell Automation® industrial system.
Provides declarations of conformity, certificates, and other certification details.
You can view or download publications at http://www.rockwellautomation.com/literature/. To
order paper copies of technical documentation, contact your local Allen-Bradley distributor or
Rockwell Automation sales representative.
16Rockwell Automation Publication IASIMP-QS024B-EN-P - December 2012
Chapter 1
Prepare the CompactLogix 5370 L1 Controller Hardware
This chapter describes how to install the hardware needed for your CompactLogix 5370 L1
control system.
What You Need
Ta b l e 5 lists the hardware components used in this chapter.
Table 5 - Parts Used with This Quick Start
QuantityCat. No.Description
1 or moreN/ADIN rail (steel, not aluminum)
1One of the following:
• 1769-L16ER-BB1B
• 1769-L18ER-BB1B
• 1769-L18ERM-BB1B
11606-XLP50ENEC Class 2/SELV switched-mode power supply
11734-OB4EPOINT I/O 8-point 24V DC electronically-fused output module
CompactLogix 5370 L1 controller
The tasks described in this publication use a 1769-L18ERM-BB1B controller.
Rockwell Automation Publication IASIMP-QS024B-EN-P - December 201217
Chapter 1 Prepare the CompactLogix 5370 L1 Controller Hardware
Install the Secure
Digital Card
Mount the
Controller
Make Network
Connections
page 20
Wire Power to
the Controller
page 25
page 22
page 28
Install the
EtherNet/IP
Network
page 19
Install the Local
Expansion Module
page 23
1
2
34
56
78
00:00:BC:2E:69:F6
00:00:BC:2E:69:F6
2428V
DC 24-28V
DC
ok
50W max.
DC ok
NEC Class 2
Power Supply
Follow These Steps
18Rockwell Automation Publication IASIMP-QS024B-EN-P - December 2012
Prepare the CompactLogix 5370 L1 Controller Hardware Chapter 1
Install the EtherNet/IP Network
You are not required to install an EtherNet/IP network to complete the tasks described in this
quick start. You can complete the tasks via a USB connection to the CompactLogix 5370 L1
controller. However, we recommend that you install an EtherNet/IP network.
You will likely complete some tasks described in the publications listed on page 12
. If you install
an EtherNet/IP network when using this quick start, you will complete the tasks described in the
publications listed on page 12
more easily.
For information on installing an EtherNet/IP network, see the publications listed in the
following table.
NetworkPublication TitlePublication Number
EtherNet/IPEtherNet/IP Media Planning and Installation ManualPublication maintained and made available
Stratix 6000 Ethernet Managed Switch User Manual1783-UM001
The publications listed previously describe how to install the communication network and not
how to connect your controller to the network. Make Network Connections on page 28
describes how to connect your controller to the network.
Rockwell Automation Publication IASIMP-QS024B-EN-P - December 201219
Chapter 1 Prepare the CompactLogix 5370 L1 Controller Hardware
UnlockedLocked
Install the Secure Digital Card
The SD card provides nonvolatile storage for the CompactLogix 5370 L1 controller. You can
store Logix Designer projects to an SD card or load a Logix Designer project from an SD card.
The following SD cards are available for use with your CompactLogix 5370 L1 controller:
• 1784-SD1 card - 1 GB of memory
• 1784-SD2 card - 2 GB of memory
The CompactLogix 5370 L1 controllers ship from the factory with the 1784-SD1 SD
card installed.
Complete these steps to re-install an SD card that has been removed from the controller back
into the controller or if installing a new SD card into the controller.
WARNING: When you insert or remove the SD card while power is on, an electrical arc can occur. This could cause an
explosion in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before proceeding.
1. Verify that the SD card is locked or unlocked according to your preference.
Consider these points when
deciding to lock the card before
installation:
• If the card is unlocked, the
controller can write data to it or
read data from it.
• If the card is locked, the controller can only read data from it.
20Rockwell Automation Publication IASIMP-QS024B-EN-P - December 2012
2. Open the door for the SD card.
3. Insert the SD card into the SD
card slot.
You can install the SD card in one
orientation only. The beveled
corner should be at the top. An
orientation logo is printed on
Prepare the CompactLogix 5370 L1 Controller Hardware Chapter 1
the card.
If you feel resistance when inserting the SD card, pull it out and change the orientation.
4. Gently press the card until it clicks into place.
5. Close the SD card door.
Rockwell Automation Publication IASIMP-QS024B-EN-P - December 201221
Chapter 1 Prepare the CompactLogix 5370 L1 Controller Hardware
Mount the Controller
1. Pull the locking tabs out.
2. Slide the controller into position
on the DIN rail and push the
locking tabs in.
3. Make sure the protective covering
on the right side of the controller
is removed.
The protective covering must be
removed to install a local
expansion module, as described
beginning on page 23
.
22Rockwell Automation Publication IASIMP-QS024B-EN-P - December 2012
Prepare the CompactLogix 5370 L1 Controller Hardware Chapter 1
Install the Local Expansion Module
This quick start uses a 1734-OB4E POINT I/O output module in a local expansion
module slot.
1. Make sure the DIN rail locking screw in the mounting base, for example, the 1734-TB
mounting base, is in the vertical position.
2. Align the tongue and groove slots
of the mounting base to the slots
on the right side of the controller
and push it back until it seats on
the DIN rail.
3. Use a small-bladed screwdriver to
rotate the DIN rail locking screw
to a horizontal position, locking
the mounting base in place.
4. Set the key position on the
mounting base before installing
the 1734-OB4E module.
This example shows position 1.
5. Make sure the output module’s key
position matches the position used
on the mounting base.
Rockwell Automation Publication IASIMP-QS024B-EN-P - December 201223
Chapter 1 Prepare the CompactLogix 5370 L1 Controller Hardware
6. Insert the module straight into the
mounting base and press to secure.
7. Insert the RTB end opposite the
handle into the base unit.
The end has a curved section that
engages with the mounting base.
8. Rotate the terminal block into the
mounting base to lock it in place.
9. Snap the RTB handle into place on
the module.
10. Connect an end cap to the right
side of the module.
24Rockwell Automation Publication IASIMP-QS024B-EN-P - December 2012
Prepare the CompactLogix 5370 L1 Controller Hardware Chapter 1
IMPORTANT
2428V
DC 24-28V
DC
ok
50W max.
DC ok
NEC Class 2
Power Supply
2428V
DC 24-28V
DC
ok
50W max.
DC ok
NEC Class 2
Power Supply
00:00:BC:2E:69:F6
Wire Power to the Controller
This quick start uses a 1606-XLP50E NEC Class 2/SELV switched-mode power supply to
power the CompactLogix 5370 L1 controller.
This section describes how to wire power to the controller. Note that the controller is grounded by its connection to the
DIN rail.
1. Verify that input power to the external power supply is turned off.
2. Mount the power supply on the DIN rail.
3. Wire input power to the power
supply using the following
terminals:
• (ground)
• N (neutral)
• L (line)
4. Connect a wire to the 24V DC+
terminal on the top of the
power supply.
5. Pull the removable connector off
of the CompactLogix 5370 L1
controllers.
Rockwell Automation Publication IASIMP-QS024B-EN-P - December 201225
Chapter 1 Prepare the CompactLogix 5370 L1 Controller Hardware
2428V
DC 24-28V
DC
ok
50W max.
DC ok
NEC Class 2
Power Supply
6. Open the top terminal on the
removable connector.
7. Insert the wire connected to the
24V DC+ terminal on the external
power supply to the VDC +
terminal on the removable
connector and close the terminal.
8. Connect a wire to a 24V DCterminal on the power supply.
9. Connect the other end of the wire
to the VDC - terminal on the
removable connector by repeating
steps 6
and 7.
10. Plug the removable connector into the controller.
26Rockwell Automation Publication IASIMP-QS024B-EN-P - December 2012
11. Secure the removable connector
IMPORTANT
in place.
This graphic shows the
1606-XLP50E switched-mode
power supply connected to the
CompactLogix 5370 L1
controller.
Prepare the CompactLogix 5370 L1 Controller Hardware Chapter 1
DC ok
DC 24-28V
50W max.
DC
ok
2428V
NEC Class 2
Power Supply
00:00:BC:2E:69:F6
12. Turn on incoming power to the external power supply.
You wire only the VDC+ and VDC- terminals on the CompactLogix 5370 L1 controller’s embedded power supply to
complete the tasks in this quick start.
In real-world applications, you will likely have additional considerations related to connected power in an application, such
as connecting power to multiple controllers or connecting power to input and output devices connected to the controller’s
embedded I/O modules and local expansion modules via the FP+, and FP- terminals on the removable terminal.
For more information on connecting power to the CompactLogix 5370 L1 control system, see the CompactLogix 5370
Controllers User Manual, publication 1769-UM021
.
Rockwell Automation Publication IASIMP-QS024B-EN-P - December 201227
Chapter 1 Prepare the CompactLogix 5370 L1 Controller Hardware
IMPORTANT
Make Network Connections
You can make these connections to a CompactLogix 5370 L1 controller:
• Make a USB Connection
• Make EtherNet/IP Network Connections
This section describes both methods of connecting your computer to your CompactLogix 5370 L1 controller. This quick
start was written under the assumption that you have installed an EtherNet/IP network.
Make a USB Connection
The controller has a USB port that uses a Type B receptacle. The port is USB 2.0-compatible and
operates at 12 Mbps.
Use a USB cable to connect your computer to the USB port. With this connection, you can
upgrade firmware and download programs to the controller directly from your computer.
ATTENTION: The USB port is intended for temporary local programming purposes only and not intended for
permanent connection.
The USB cable is not to exceed 3.0 m (9.84 ft) and must not contain hubs.
WARNING: Do not use the USB port in hazardous locations.
1. Plug one end of the USB cable into your CompactLogix 5370 L1 controller.
2. Plug the other end of the USB
cable into your computer.
28Rockwell Automation Publication IASIMP-QS024B-EN-P - December 2012
Prepare the CompactLogix 5370 L1 Controller Hardware Chapter 1
1
2
34
56
78
Make EtherNet/IP Network Connections
This section assumes you installed an EtherNet/IP network as described on page 19 and the
network includes a 1783-EMS08T Stratix 6000 Ethernet managed switch.
1. Plug a 1585J-M4TBJM-1,
Ethernet cable (straight-through)
into a port on the Stratix 6000
switch.
2. Plug the other end of the Ethernet
cable into one of the Ethernet
ports on the bottom of the
controller.
00:00:BC:2E:69:F6
Set the Network IP Address
Once you connect the CompactLogix 5370 L1 controller to an EtherNet/IP network, you must
assign the controller a unique IP address. For information about how to set the network IP
address for your controller, see Chapter 3, Configure the EtherNet/IP Network
on page 45.
Rockwell Automation Publication IASIMP-QS024B-EN-P - December 201229
Chapter 1 Prepare the CompactLogix 5370 L1 Controller Hardware
Notes:
30Rockwell Automation Publication IASIMP-QS024B-EN-P - December 2012
Chapter 2
Prepare the Computer and Load Controller Firmware
In this chapter, you install and configure the necessary programming and configuration software
on your computer and load firmware on your controller.
Before You Begin
Before you begin using this chapter, complete these tasks:
• Verify that your computer meets the software’s system requirements for installation and use
of the software listed in Ta bl e o n p a ge 14
• The tasks described in Chapter 1, Prepare the CompactLogix 5370 L1 Controller
.
Hardware on page 17, including the following:
– Install the EtherNet/IP network - Optional task because you can use a USB
cable connection.
– Install the controller and the local expansion module.
– Wire power to the controller.
– Make network connections.
Rockwell Automation Publication IASIMP-QS024B-EN-P - December 201231
Chapter 2 Prepare the Computer and Load Controller Firmware
What You Need
Ta b l e 6 lists the components you use in this chapter.
Table 6 - What You Need to Prepare the Computer
ComponentDescription
Studio 5000 environmentEnvironment that combines engineering and design elements into a common environment.
Logix Designer applicationSoftware used to create a project the CompactLogix 5370 L3 controller uses in your application.
RSLinx Classic softwareCommunication server that supports multiple software applications simultaneously, establishing
communication between devices on many different Rockwell Automation industrial networks.
IP addressA number in the form xxx.xxx.xxx.xxx where each xxx is a number from 000…254.
The IP address uniquely identifies the computer on the EtherNet/IP network.
Subnet MaskExtension of the IP address that allows a site to use a single network ID for multiple
physical networks.
If you change the subnet mask of an already-configured controller, you must cycle power to the
controller for the change to take effect.
ControlFLASH softwareSoftware used to upgrade the firmware on certain Allen-Bradley® products in a
CompactLogix 5370 L1 controller application.
Automatically installed with the Studio 5000 environment installation.
32Rockwell Automation Publication IASIMP-QS024B-EN-P - December 2012
Follow These Steps
Install Additional
Software - Optional
page 34
page 44
Install the Studio 5000
Environment
Set the IP Address for
the Computer
page 38
Load the Controller
Firmware
page 41
Configure an EtherNet/IP
Driver in RSLinx Classic
Software
page 36
Prepare the Computer and Load Controller Firmware Chapter 2
Rockwell Automation Publication IASIMP-QS024B-EN-P - December 201233
Chapter 2 Prepare the Computer and Load Controller Firmware
IMPORTANT
Install the Studio 5000 Environment
The Studio 5000 environment, version 21.00.00, installation process is configured so that,
among other software applications, RSLinx Classic software, version 3.51.00, is
automatically installed.
The automatic installation option is enabled by default. You can change the installation setting
and install RSLinx Classic software separately. We strongly recommend that you use the
installation process default settings described in this chapter.
The steps described in this section might vary slightly from the steps you complete during your Studio 5000
environment, version 21.00.00, installation.
1. Start the installation.
You c an lo ad th e so ft wa re f rom a CD or web download.
2. Choose a language, fill in the
appropriate information, and
click Next.
34Rockwell Automation Publication IASIMP-QS024B-EN-P - December 2012
3. Use the default selections and
click Install.
4. Read the license agreement
carefully.
5. Click Accept All.
Prepare the Computer and Load Controller Firmware Chapter 2
The installation process begins.
When installation is complete, your
computer will have the software
necessary required to complete the tasks
described in this publication.
Among other software, your computer
will have the following:
• Studio 5000 Environment, version
21.00.00
• RSLinx Classic software, version 3.51.00
You are prompted to activate the software. For more information on software activation, see
the following :
Rockwell Automation Publication IASIMP-QS024B-EN-P - December 201235
Chapter 2 Prepare the Computer and Load Controller Firmware
Automatic Installation of ControlFLASH Software
ControlFLASH software is used to upgrade a CompactLogix 5370 L1 controller’s firmware
revision. ControlFLASH software is automatically installed when you install the Studio 5000
environment.
For more information on loading firmware on your controller, see Load the Controller
Firmware on page 41.
Configure an EtherNet/IP Driver in RSLinx Classic Software
1. Start the software.
2. From the Communications pull-
down menu, choose Configure
Drivers.
The Configure Drivers dialog box appears.
36Rockwell Automation Publication IASIMP-QS024B-EN-P - December 2012
3. From the Available Driver Types
menu, choose EtherNet/IP Driver
or Ethernet devices and click
Add New.
We r e co mm e nd tha t yo u u se
EtherNet/IP Driver.
The Add New RSLinx Driver
dialog box appears.
4. Click OK to keep the default
name.
Prepare the Computer and Load Controller Firmware Chapter 2
A Configure driver:AB_ETHxxx dialog box appears. The full name of the dialog box varies
by what driver type was chosen in step 3
.
This example uses the EtherNet/IP Driver; the driver name is AB_ETHIP-1.
5. Select an Ethernet card and
click OK.
This new driver is available.
Rockwell Automation Publication IASIMP-QS024B-EN-P - December 201237
Chapter 2 Prepare the Computer and Load Controller Firmware
6. Verify that the driver’s Status is
Running and click Close.
Set the IP Address for the Computer
Your computer requires an Internet Protocol (IP) address to operate on an EtherNet/IP
network. The IP address uniquely identifies the controller and is in the form xxx .xxx.xxx.xxx
where each xxx is a number from 000…254 with some exceptions for reserved values.
A computer’s IP address can be set automatically or manually. The manual option is typically
used with isolated networks. This section describes how to set the IP address manually.
For more information on setting an IP address for your CompactLogix 5370 L1 controller, see
the CompactLogix 5370 Controllers User Manual, publication 1769-UM021
.
1. On your desktop, right-click
Network and choose Properties.
38Rockwell Automation Publication IASIMP-QS024B-EN-P - December 2012
2. Click adapter settings.
3. Right-click Local Area
Connection and
Prepare the Computer and Load Controller Firmware Chapter 2
choose Properties.
Rockwell Automation Publication IASIMP-QS024B-EN-P - December 201239
Chapter 2 Prepare the Computer and Load Controller Firmware
4. On the Networking tab, choose
Internet Protocol Version 4
(TCP/IPv4) and click Properties.
5. Select Use the following IP address
and enter an IP address and Subnet
mask for your computer.
6. Record the IP address and
subnet mask.
7. Click OK.
8. Close the Local Area Connection
Properties dialog box.
40Rockwell Automation Publication IASIMP-QS024B-EN-P - December 2012
Load the Controller Firmware
IMPORTANT
This section assumes that you downloaded the controller firmware from the Rockwell Automation technical support
website to install on your CompactLogix 5370 L1 controller. If not, download the firmware before following the
steps in this section.
The firmware is available with Logix Designer application or you can download it from the support website.
Go to http://www.rockwellautomation.com/support/.
This section describes how to load firmware on your CompactLogix 5370 L1 controller before setting an IP address
for the controller. In this case, you must connect from your workstation to the controller over the USB port.
With this quick start, you must use RSLinx Classic software, version 3.51.00 or later with CompactLogix 5370 L1
controllers. When the software is installed, a USB driver is automatically installed. When your computer is
connected to the CompactLogix 5370 L1 controller over a USB connection, the controller appears in the RSWho
window whenever you perform a Browse.
Prepare the Computer and Load Controller Firmware Chapter 2
1. Verify that the SD card in the controller is unlocked.
2. Connect to the controller via the USB port as described in Make a USB Connection
page 28.
The controller should be powered. If it is not, turn power on to the controller.
3. Start the
ControlFLASH software.
on
Rockwell Automation Publication IASIMP-QS024B-EN-P - December 201241
Chapter 2 Prepare the Computer and Load Controller Firmware
4. Click Next.
5. Select the controller catalog
number and click Next.
42Rockwell Automation Publication IASIMP-QS024B-EN-P - December 2012
6. Expand the USB driver, and select
TIP
RUN
REM
PROG
your controller.
7. Click OK.
8. If it’s not in the position already,
move the mode switch on the
controller to the REM position.
Prepare the Computer and Load Controller Firmware Chapter 2
9. Choose the desired firmware
revision and click Next.
Consider the following:
• If the Current Revision
matches the firmware
revision shown in the box
below it, click Cancel. You are
finished with this task.
• This example uses firmware
revision 21.001.23. Your
firmware revision may be a
different number.
You can access the
latest firmware revision
at the Rockwell
Automation Technical
Support webpage.
Rockwell Automation Publication IASIMP-QS024B-EN-P - December 201243
Chapter 2 Prepare the Computer and Load Controller Firmware
IMPORTANT
10. To s ta r t th e fi rm wa re up da te , cl ic k
Finish and then click Yes.
Before the firmware upgrade
begins, you see the following dialog
box. Take the appropriate action
for your application. In this
example, the upgrade continues
when OK is clicked.
When the update completes, the status box informs you that the update was successful.
Install Additional Software - Optional
Depending on your application, you may need to install additional software.
For example, if you are integrating a PanelView Plus terminal into your system, you must install
the following :
• RSLinx Enterprise software
You must install this software before you install any other additional software.
• FactoryTalk® View Machine Edition software
44Rockwell Automation Publication IASIMP-QS024B-EN-P - December 2012
Chapter 3
IMPORTANT
Configure the EtherNet/IP Network
In this chapter, you assign an IP address to your CompactLogix 5370 L1 controller.
This quick start does not describe how to use other devices on the EtherNet/IP network. It is
common to use other devices on an EtherNet/IP network in a CompactLogix 5370 L1 control
system. If you were to do so, for example, use a PanelView Plus terminal on an
EtherNet/IP network, you need to assign an IP address to those devices.
Not all tasks described in this quick start are required to complete the final task, that is, use ladder logic to test a
1734-OB4E output module as described beginning on page 51. For example, you do not need to install an
EtherNet/IP network to connect to a CompactLogix 5370 L3 controller because you can do so over a USB cable.
We expect that you might attempt to complete additional tasks with your control system by using the publications
listed on page 12 relating to using a component over an EtherNet/IP network in a Logix5000 control system. When you
use those publications, some assumptions are made. For example, if you use POINT I/O modules over an EtherNet/IP
network in a CompactLogix 5370 L1 control system, you must have already created a Logix Designer projectLogix
Designer projectand have an IP address assigned to the controller.
If you complete all of the tasks described in this chapter, you can easily complete the tasks described in the publications
listed on page 12 related to using an EtherNet/IP network.
Rockwell Automation Publication IASIMP-QS024B-EN-P - December 201245
Chapter 3Configure the EtherNet/IP Network Configure the EtherNet/IP Network
IMPORTANT
Before You Begin
Before you begin using this chapter, complete these tasks:
• The tasks described in Chapter 1, Prepare the CompactLogix 5370 L1 Controller
Hardware on page 17, including the following:
– Install the EtherNet/IP network.
– Mount the controller and install the local expansion module.
– Wire power to the controller.
– Make network connection.
If you connect all of the devices, including the computer, through an Ethernet switch, you can create an
isolated network. This chapter assumes you are using an isolated network. If you are not, contact your
network administrator to obtain IP addresses.
• The tasks described in Chapter 2, Prepare the Computer and Load Controller Firmware on
page 31, including the following:
– Install the Studio 5000 environment and RSLinx Classic software.
Logix Designer application is installed when you install the Studio 5000 environment.
– Configure an EtherNet/IP driver in RSLinx Classic software.
– Set the IP address for the computer.
– Load firmware on the controller.
• Verify that power is applied to all devices.
46Rockwell Automation Publication IASIMP-QS024B-EN-P - December 2012
Configure the EtherNet/IP Network Chapter 3
What You Need
Ta b l e 7 lists the software components you use in this chapter.
Table 7 - What You Need to Configure the EtherNet/IP Network
ComponentDescription
Studio 5000 environmentEnvironment that combines engineering and design elements into a common environment.
Logix Designer applicationSoftware used to create a project the CompactLogix 5370 L1 controller use in your application.
RSLinx Classic softwareCommunication server that supports multiple software applications simultaneously, establishing
communication between devices on many different Rockwell Automation industrial networks.
IP addressA number in the form xxx.xxx.xxx.xxx where each xxx is a number from 000…254.
The IP address uniquely identifies the controller on the EtherNet/IP network.
Subnet maskExtension of the IP address that allows a site to use a single network ID for multiple physical
networks.
If you change the subnet mask of a configured controller, you must cycle power to the controller
for the change to take effect.
Rockwell Automation Publication IASIMP-QS024B-EN-P - December 201247
Chapter 3Configure the EtherNet/IP Network Configure the EtherNet/IP Network
IMPORTANT
Assign an IP Address to the Controller over a USB Connection
At initial powerup, the CompactLogix 5370 L1 controller does not have an IP address. Use
RSLinx Classic software over a USB connection to assign an IP address. The following steps will
work only if the computer with RSLinx Classic software is connected to the controller via a
USB connection.
There are other methods to assign an IP address to the controller, such as using the BOOTP/DHCP utility. This section is
only one example of how to assign the IP address to the controller.
For more information on the methods of assign an IP address to the CompactLogix 5370 L1 controller, see the
CompactLogix 5370 Controllers User Manual, publication 1769-UM021.
1. Verify that your computer is connected to the USB port on the front of the controller.
2. From the Communications menu,
choose RSWho.
The RSWho dialog box appears.
3. Navigate to the USB connection.
4. Right-click the controller and
choose Module Configuration.
The Module Configuration dialog
box appears.
48Rockwell Automation Publication IASIMP-QS024B-EN-P - December 2012
5. Click the Port Configuration tab.
IMPORTANT
6. For Network Configuration Type,
click Static to permanently assign
this configuration to the port.
The controller’s default
configuration is Dynamic.
When the controller is
configured for Dynamic, on a
power cycle, it clears the
current IP address and resumes
sending BOOTP requests.
7. Enter the IP address and Network Mask for the controller.
Configure the EtherNet/IP Network Chapter 3
8. Enter other network parameters, if necessary.
9. Click OK.
For more information on setting the network IP address, see EtherNet/IP Network
Configuration User Manual, publication ENET-UM001
.
Rockwell Automation Publication IASIMP-QS024B-EN-P - December 201249
Chapter 3Configure the EtherNet/IP Network Configure the EtherNet/IP Network
Notes:
50Rockwell Automation Publication IASIMP-QS024B-EN-P - December 2012
Chapter 4
IMPORTANT
Create a Logix Designer Project
In this chapter you create a Logix Designer project. In the project you use ladder logic to create a
push button that controls a light on a digital output module.
You learn how to complete the following tasks:
• Create a Logix Designer project.
• Configure your 1769-L18ERM-BB1B controller.
• Add a local expansion module to the project.
• Add ladder logic to the project to test the local expansion module.
• Download the project to the controller.
You must use Logix Designer application with this quick start. The tasks described in this chapter are described with the
intention that you might reuse the project to complete the tasks described in publications listed on page 12.
Because you are likely to use other devices in your CompactLogix 5370 L1 control system, you can use the project created
in this chapter to complete the tasks described in the publications listed on page 12
.
Rockwell Automation Publication IASIMP-QS024B-EN-P - December 201251
Chapter 4 Create a Logix Designer Project
Before You Begin
Before you begin, complete these tasks:
• The tasks described in Chapter 1, Prepare the CompactLogix 5370 L1 Controller
Hardware on page 17, including the following:
– Install the EtherNet/IP network.
– Install the controller and the local expansion module.
– Wire power to the controller.
– Make network connections.
• The tasks described in Chapter 2, Prepare the Computer and Load Controller Firmware on
page 31, including the following:
– Install the Studio 5000 environment and RSLinx Classic software.
Logix Designer application is installed when you install the Studio 5000 environment.
– Configure an EtherNet/IP driver in RSLinx Classic software.
– Set the IP address for the computer.
– Load firmware on the controller.
• Set the IP address for the controller as described in Chapter 3 on page 45.
• Verify that all devices are powered.
What You Need
You need Logix Designer application to complete the tasks in this chapter.
52Rockwell Automation Publication IASIMP-QS024B-EN-P - December 2012
Follow These Steps
Create a Project
Configure the Controller
Add a Local
Expansion Module
Add Ladder Logic to Test
the Local Expansion
Module
Download to the
Controller
page 54
page 55
page 58
page 60
page 63
Create a Logix Designer Project Chapter 4
Rockwell Automation Publication IASIMP-QS024B-EN-P - December 201253
Chapter 4 Create a Logix Designer Project
Create a Project
1. Start the application.
2. Click New Project.
The New Controller dialog
box appears.
3. Choose your controller and name
the project.
4. Click Next.
54Rockwell Automation Publication IASIMP-QS024B-EN-P - December 2012
5. Set Expansion I/O to a number
RUN
REM
PROG
that exactly matches the number of
1734 POINT I/O modules
physically installed in the system.
In this case, the value is 1 Module.
6. Click Finish.
Configure the Controller
Create a Logix Designer Project Chapter 4
1. Verify that the mode switch on the
controller is in the REM position.
2. Click the RSWho icon.
Rockwell Automation Publication IASIMP-QS024B-EN-P - December 201255
Chapter 4 Create a Logix Designer Project
3. In the Who Active dialog box, expand the path to the controller and select it.
4. Click Set Project Path.
By clicking this button, you set the
path and do not have to browse to
the controller each time you use an
option in the Who Active dialog.
5. Click Go Online.
You must be online to set the
controller’s IP address in the Logix
Designer project.
6. Click Download twice on successive dialog boxes.
7. Click Yes to change the controller
mode to Remote Run.
8. Expand the I/O Configuration
tree.
9. Right-click the controller and
choose Properties.
56Rockwell Automation Publication IASIMP-QS024B-EN-P - December 2012
Create a Logix Designer Project Chapter 4
IMPORTANT
10. Use the tabs on the Controller
Properties dialog box to configure
the controller.
The IP address is set on the
Internet Protocol tab.
Make sure you set an IP
Address and Subnet Mask
that matches the values set in
Set the IP Address for the
Computer on page 38.
There are many configurable parameters on various tabs in the Controller Properties dialog
box. For more information on configuring your CompactLogix 5370 L1 controller, see the
CompactLogix 5370 Controllers User Manual, publication 1769-UM021
.
11. Click OK.
12. Go offline.
Rockwell Automation Publication IASIMP-QS024B-EN-P - December 201257
Chapter 4 Create a Logix Designer Project
TIP
Add a Local Expansion Module
1. Right-click PointIO and choose
New Module.
The Select Module Type dialog
box appears.
2. Select the 1734-OB4E module
and click Create.
You can use the Search
feature in Logix Designer
application to quickly find
the I/O module you need to
add to your project.
The New Module dialog box
appears for the module created.
58Rockwell Automation Publication IASIMP-QS024B-EN-P - December 2012
3. Use the tabs to create the
IMPORTANT
parameters for the I/O module.
For the purposes of this
exercise, make sure you
change the Module
Definition parameters so
Electronic Keying is set to
Disable Keying.
4. When the module configuration
is complete, click OK.
The module is added to the I/O
Configuration.
Create a Logix Designer Project Chapter 4
Rockwell Automation Publication IASIMP-QS024B-EN-P - December 201259
Chapter 4 Create a Logix Designer Project
IMPORTANT
Add Ladder Logic to Test the Local Expansion Module
If you do not have a 1734-OB4E module, you can use ladder logic with an embedded output point on the CompactLogix
5370 L1 controller in a similar fashion.
When using an embedded output point, instead of choosing an output point on the local expansion module, as
described in step 13 on page 62, you choose an embedded digital output point on the CompactLogix 5370 L1 controller.
1. Expand the Tasks folders.
2. Right-click MainRoutine and
choose Open.
A blank MainRoutine opens.
3. From the Element Toolbar, drag
and drop an Examine On and an
Output Energize element onto the
rung.
60Rockwell Automation Publication IASIMP-QS024B-EN-P - December 2012
4. Double-click the ? in the Examine
On element.
5. Ty p e PB (for push button).
6. Press Enter.
7. Right-click PB and choose
New ‘PB’.
Create a Logix Designer Project Chapter 4
8. Keep the default settings and click
one of the Create options.
Rockwell Automation Publication IASIMP-QS024B-EN-P - December 201261
Chapter 4 Create a Logix Designer Project
IMPORTANT
9. Double-click the ? in the Output
Energize element.
10. Name the Output Energize
element OB4E_Light and
press Enter.
Do not use spaces in the tag name. Use underscores (_) instead.
11. Right-click the OB4E_Light tag
name and choose New
‘OB4E_Light’.
OB4E_Light is an alias tag for the
I/O point tag name. With an alias
tag, you can assign a simple name to a physical I/O point address.
12. From the Type pull-down menu,
choose Alias.
13. From the Alias For pull-down
menu, browse to the 1734-OB4E
digital output module and choose
any bit.
This example uses
Local:2:O.Data.0.
62Rockwell Automation Publication IASIMP-QS024B-EN-P - December 2012
14. Close the dialog box.
The graphic shows the Output
Energize after assigning the Alias
tag to a point on the output
module.
15. Save your changes.
Download to the Controller
1. From the mode pull-down menu,
choose Download.
Create a Logix Designer Project Chapter 4
2. When the dialog box appears with
information about the download,
click Download.
3. Click Yes to change the controller
mode to Remote Run mode.
Rockwell Automation Publication IASIMP-QS024B-EN-P - December 201263
Chapter 4 Create a Logix Designer Project
RUN
REM
PROG
4. Move the mode switch on your
controller to the RUN position.
5. In the Main Routine, select the PB
Examine On instruction.
6. Press Ctrl+T to toggle the state
from 0 to 1, or Off to On.
7. Verify that the status indicator on
the digital output module turns on after you toggle the state to 1 or On.
8. Press Ctrl+T to toggle the state back to 0 or Off.
9. Go Offline.
64Rockwell Automation Publication IASIMP-QS024B-EN-P - December 2012
Understanding Other Application Options
IMPORTANT
This chapter describes two application options available with a CompactLogix 5370
L1 controller:
• Using the controller in a DLR network topology
• Using the controller in an application that includes Integrated Motion on an
EtherNet/IP network - 1769-L18ERM-BB1B controller only
Appendix A
This chapter does not describe specific steps required to use the CompactLogix 5370 L1 controller in applications with
DLR networks or Integrated Motion over an EtherNet/IP network.
The purpose is to introduce you to these other applications.
See the following publications for more information on using the application options:
• Using the controller in a DLR network topology:
– CompactLogix 5370 Controllers User Manual, publication 1769-UM021
– EtherNet/IP Embedded Switch Technology Application Guide,
publication ENET-AP005
• Using the controller in an application that includes Integrated Motion on the EtherNet/IP
network:
– CompactLogix 5370 Controllers User Manual, publication 1769-UM021
– CIP Motion Configuration and Startup User Manual, publication MOTION-UM003
– Integrated Architecture and CIP Sync Configuration Application Technique,
publication IA-AT003
Rockwell Automation Publication IASIMP-QS024B-EN-P - December 201265
Appendix A Understanding Other Application Options
02
0
1734-AENTR
Module
Status
Network
Activity
Network
Status
Point Bus
Status
System
Power
Field
Power
POINT I O
Link 1
Activity/
Status
Link 2
Activity/
Status
IP ADDRESS
Kinetix 6500 Drives
CompactLogix 5370 L1
Control System
1794-AENTR FLEX
™
I/O EtherNet/IP
Adapter with FLEX I/O Modules
PanelView Plus Terminal
Connected via a1783-ETAP
EtherNet/IP Tap
Computer Connected via a
1783-ETAP EtherNet/IP Tap
1734-AENTR POINT I/O
EtherNet/IP Adapter with
POINT I/O Modules
Kinetix 350 Drive
Connected via a1783-ETAP
EtherNet/IP Tap
DLR Network Topology
A DLR network topology is a single-fault-tolerant ring network in which DLR-capable
Rockwell Automation devices use embedded technology and dual EtherNet/IP ports to establish
a network that is resilient to single points of failure, recovers faster when single faults occur, and
does not require switches.
Configuring a DLR network topology requires you to complete a few tasks that do not apply to
using a CompactLogix 5370 L1 controller in a linear or star network topology. For example, a
DLR network topology requires that one supervisor-capable network device be configured as
the active ring supervisor. CompactLogix 5370 L1 controllers are supervisor-capable devices on a
DLR network.
This graphic shows a DLR network topology with a CompactLogix 5370 L1 controller.
66Rockwell Automation Publication IASIMP-QS024B-EN-P - December 2012
Follow These Steps
Begin Physical
Device Installation
Create a Logix
Designer Project
Complete Physical
Device Installation
Understanding Other Application Options Appendix A
1734-AENTR
02
0
POINT I O
Module
Status
Network
Activity
Network
Status
Point Bus
Status
Link 1
Activity/
System
Status
Power
Field
Power
IP ADDRESS
Link 2
Activity/
Status
1734-AENTR
02
0
POINT I O
Module
Status
Network
Activity
Network
Status
Point Bus
Status
Link 1
Activity/
System
Status
Power
Field
Power
IP ADDRESS
Link 2
Activity/
Status
For a complete description of the tasks required, such as configuring at least one device on the
network to be the Active Supervisor, to use a CompactLogix 5370 L1 controller in a DLR
application, see the EtherNet/IP Embedded Switch Technology Application Guide, publication
ENET-AP005.
Rockwell Automation Publication IASIMP-QS024B-EN-P - December 201267
Appendix A Understanding Other Application Options
Create a Logix
Designer Project
Configure Driver
Run Application
Integrated Motion on the EtherNet/IP Network
Integrated Motion on the EtherNet/IP network is an integrated motion solution on a standard,
unmodified EtherNet/IP network that delivers high performance with lower costs and simpler
design or configuration when compared to traditional, multi-network motion applications.
The 1769-L18ERM-BB1B controller supports Integrated Motion on the EtherNet/IP network.
Follow These Steps
For a complete description of the tasks required to using Integrated Motion on the EtherNet/IP
network with a CompactLogix 5370 L1 controller, see the CIP Motion Configuration and
Startup User Manual, publication MOTION-UM003
68Rockwell Automation Publication IASIMP-QS024B-EN-P - December 2012
Index
C
CompactLogix 5370 L1 controllers
10
available
devices to integrate
features
install
load
11
36
41
ControlFLASH software
controller firmware
12
14, 32
D
devices
Kinetix 350 drives
PanelView Plus terminals
POINT I/O modules
PowerFlex 40 drives
PowerFlex 70 drives
to integrate in controller application
DLR network topology 65, 66
12
12
12
1212
E
EtherNet/IP network
45
configure
connection
network topologies11, 66
29
F
features
common to all controllers
firmware
load on controller
11
41
H
hardware 10, 15, 17
connections to other devices
optional system devices
4
12
I
I/O support 58
Integrated Motion on the EtherNet/IP
65, 68
network
internal energy storage solution
11
12
M
motion support
Integrated Motion on the EtherNet/IP
65, 68
network
N
networks
configure an EtherNet/IP network
connect to an EtherNet/IP network
USB connection
nonvolatile memory
SD card
28
11
P
panel layout
5
sample
PanelView Plus terminals 12
POINT I/O modules
power supplies
25
wire
PowerFlex 40 drives
PowerFlex 70 drives
12
1212
R
required parts 15
RSLinx Classic software
14, 32, 47
S
SD card 11
installation
software
ControlFLASH
install ControlFLASH
install the Studio 5000 environment
Logix Designer
required
RSLinx Classic
Studio 5000 environment
install
20
14
36
14, 32, 47, 51
14
14, 32, 47
34
U
USB connection 28
45
29
34
K
Kinetix 350 drives 12
L
Logix Designer application 14, 32, 47, 51
Rockwell Automation Publication IASIMP-QS024B-EN-P - December 201269
Index
Notes:
70Rockwell Automation Publication IASIMP-QS024B-EN-P - December 2012
Rockwell Automation Support
Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400
Rockwell Automation provides technical information on the Web to assist you in using its products.
At http://www.rockwellautomation.com/support
code and links to software service packs, and a MySupport feature that you can customize to make the best use of these
tools. You can also visit our Knowledgebase at http://www.rockwellautomation.com/knowledgebase
information, support chat and forums, software updates, and to sign up for product notification updates.
For an additional level of technical phone support for installation, configuration, and troubleshooting, we offer
TechConnect support programs. For more information, contact your local distributor or Rockwell Automation
representative, or visit http://www.rockwellautomation.com/support/
Installation Assistance
If you experience a problem within the first 24 hours of installation, review the information that is contained in this
manual. You can contact Customer Support for initial help in getting your product up and running.
United States or Canada1.440.646.3434
Outside United States or CanadaUse the Wor ldwi de Lo cato r at http://www.rockwellautomation.com/support/americas/phone_en.html, or contact your local Rockwell
Automation representative.
, you can find technical manuals, technical and application notes, sample
for FAQs, technical
.
New Product Satisfaction Return
Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from the
manufacturing facility. However, if your product is not functioning and needs to be returned, follow these procedures.
United StatesContact your distributor. You must provide a Customer Support case number (c all the phone number above to obtain one) to your
Outside United StatesPlease contact your local Rockwell Automation representative for the return procedure.
distributor to complete the return process.
Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this
document, complete this form, publication RA-DU002
, available at http://www.rockwellautomation.com/literature/.