LG MU5M40 INSTALLATION MANUAL

P/NO : MFL68883802
INSTALLATION MANUAL
AIR CONDITIONER
www.lg.com
[
Representative] LG Electronics Inc. EU Representative : LG Electronics European Shared Service Center B.V.
Krijgsman 1, 1186 DM Amstelveen, The Netherlands
[
Manufacturer] LG Electronics Inc. Changwon 2nd factory 84, Wanam-ro, Seongsan-gu, Changwon-si,
Gyeongsangnam-do, KOREA
For more information, Refer to the CD or LG Web site (www.lg.com).
Please read this installation manual completely before installing the product. Installation work must be performed in accordance with the national wiring standards by authorized personnel only. Please retain this installation manual for future reference after reading it thoroughly.
Ɠ
This product contains Fluorinated Greenhouse Gases. (R410A)
[
Representative] LG Electronics Inc. EU Representative : LG Electronics European Shared Service Center B.V.
Krijgsman 1, 1186 DM Amstelveen, The Netherlands
[
Manufacturer] LG Electronics Inc. Changwon 2nd factory 84, Wanam-ro, Seongsan-gu, Changwon-si,
Gyeongsangnam-do, KOREA
For more information, Refer to the CD or LG Web site (www.lg.com).
MULTI Original instruction
ENGLISH ITALIANO ESPAÑOL FRANÇAIS DEUTSCH
ΕΛΛΗΝΙΚΆ
ČEŠTINA
NEDERLANDS
POLSKI
LIMBA ROMÂNĂ
2
IMPORTANT SAFETY INSTRUCTIONS
ENGLISH
IMPORTANT SAFETY INSTRUCTIONS
READ ALL INSTRUCTIONS BEFORE USING THE APPLIANCE.
Always comply with the following precautions to avoid dangerous situations and ensure peak performance of your product
WARNING
It can result in serious injury or death when the directions are ignored
CAUTION
It can result in minor injury or product damage when the directions are ignored
WARNING
• Installation or repairs made by unqualified persons can result in hazards to you and others.
• Installation work must be performed in accordance with the National Electric Code by qualified and authorized personnel only.
• The information contained in the manual is intended for use by a qualified service technician familiar with safety procedures and equipped with the proper tools and test instruments.
• Failure to carefully read and follow all instructions in this manual can result in equipment malfunction, property damage, personal injury and/or death.
Installation
• Do not use a defective or underrated circuit breaker. Use the correctly rated breaker and fuse. There is risk of fire or electric shock.
• For electrical work, contact the dealer, seller, a qualified electrician, or an Authorized Service Center. Do not disassemble or repair the product by yourself. There is risk of fire or electric shock.
• Always ground the product as per the wiring diagram. Do not connect the ground wire to gas or water pipes lightening rod or telephone ground wire. There is risk of fire or electric shock.
• Install the panel and the cover of control box securely. There is risk of fire or electric shock due to dust , water etc.
• Use the correctly rated breaker or fuse. There is risk of fire or electric shock.
• Do not modify or extend the power cable. If the power cable or cord has scrathes or skin peeled off or deteriorated then it must be replaced. There
!
!
!
IMPORTANT SAFETY INSTRUCTIONS
3
ENGLISH
is risk of fire or electric shock.
• For installation, removal or reinstall , always contact the dealer or an Authorized Service Center. There is risk of fire, electric shock, explosion, or injury.
• Do not install the product on a defective installation stand. Be sure that the installation area does not deteriorate with age. It may cause product to fall.
• Never install the outdoor unit on a moving base or a place from where it can fall down. The falling outdoor unit can cause damage or injury or even death of a per­son.
• In outdoor unit the step-up capacitor supplies high voltage electricity to the electrical components. Be sure to discharge the capacitor completely before conducting the repair work. An charged capacitor can cause electrical shock.
• When installing the unit, use the installation kit provided with the product. Otherwise the unit may fall and cause severe injury.
• Indoor/outdoor wiring connections must be secured tightly and the cable should be routed properly so that there is no force pulling the cable from the connection terminals. Improper or loose connections can cause heat generation or fire.
• Safely dispose off the packing materials. Like screws, nails, batteries, bro­ken things etc after installation or svc and then tear away and throw away the plastic packaging bags. Children may play with them and cause injury.
• Be sure to check the refrigerant to be used. Please read the label on the product. Incorrect refrigerant used can prevent the normal operation of the unit.
Operation
• When the product is soaked (flooded or submerged) in water , contact an Authorized Service Center for repair before using it again. There is risk of fire or eletric shock.
• Be sure to use only those parts which are listed in the svc parts list. Never attempt to modify the equipment. The use of inappropriate parts can cause an electrical shock, excessive heat generation or fire.
• Do not touch , operate, or repair the product with wet hands. Hold the plug by hand when taking out. There is risk of electric shock or fire.
• Do not place a heater or other heating appliances near the power cable. There is risk of fire and electric shock.
4
IMPORTANT SAFETY INSTRUCTIONS
ENGLISH
• Do not allow water to run into electric parts. Install the unit away from water sources. There is risk of fire, failure of the product, or electric shock.
• Do not store or use or even allow flammable gas or combustibles near the product. There is risk of fire.
• Do not use the product in a tightly closed space for a long time. Perform ventilation regularly. Oxygen deficiency could occur and hence harm your health.
• Do not open the front grille of the product during operation. (Do not touch the electrostatic filter, if the unit is so equipped.) There is risk of physical injury, electric shock, or product failure.
• If strange sound, smell or smoke comes from product.Immediately turn the breaker off or disconnect the power supply cable. There is risk of elec­tric shock or fire.
• Ventilate the product room from time to time when operating it together with a stove, or heating element etc. Oxygen deficiency can occur and hence harm your health.
• When the product is not to be used for a long time, disconnect the power supply plug or turn off the breaker. There is risk of product damage or fail­ure, or unintended operation.
• Take care to ensure that nobody especially kids could step on or fall onto the outdoor unit. This could result in personal injury and product damage.
• Take care to ensure that power cable could not be pulled out or damaged during operation. There is risk of fire or electric shock.
• Do not place ANYTHING on the power cable. There is risk of fire or elec­tric shock.
• When flammable gas leaks, turn off the gas and open a window for venti­lation befor turning on the product. Do not use the telephone or turn switches on or off. There is risk of explosion or fire.
CAUTION
Installation
• Two or more people must lift and transport the product. Avoid personal injury.
• Do not install the product where it will be exposed to sea wind (salt spray) directly. It may cause corrosion on the product.
• Install the drain hose to ensure that the condensed water is drained away properly. A bad connection may cause water leakage.
• Keep level even when installing the product. To avoid vibration or noise.
!
IMPORTANT SAFETY INSTRUCTIONS
5
ENGLISH
• Do not install the product where the noise or hot air from the outdoor unit could damage or disturb the neighborhoods. It may cause a problem for your neighbors and hence dispute.
• Always check for gas (refrigerant) leakage after installation or repair of product. Low refrigerant levels may cause failure of product.
• Please install safely at a place that can sufficiently endure the weight of the product. If the strength is not sufficient, the product may fall and cause injury.
Operation
• Do not use the product for special purposes, such as preserving foods, works of art, etc. It is a consumer air conditioner, not a precision refrigera­tion system. There is risk of damage or loss of property.
• Do not block the inlet or outlet of air flow. It may cause product failure.
• Use a soft cloth to clean. Do not use harsh detergents, solvents or splash­ing water etc. There is risk of fire, electric shock, or damage to the plastic parts of the product.
• Do not touch the metal parts of the product when removing the air filter. There is risk of personal injury.
• Do not step on or put anyting on the product. (outdoor units) There is risk of personal injury and failure of product.
• Always insert the filter securely after cleaning. Clean the filter every two weeks or more often if necessary. A dirty filter reduces the efficiency.
• Do not insert hands or other objects through the air inlet or outlet while the product is operating. There are sharp and moving parts that could cause personal injury.
• Be cautious when unpacking and installing the product. Sharp edges could cause injury.
• If the refrigerant gas leaks during the repair, do not touch the leakaing refrigerant gas. The refrigernat gas can cause frostbite (cold burn).
• Do not tilt the unit when removing or uninstalling it. The condensed water inside can spill.
• Do not mix air or gas other than the specified refrigerant used in the sys­tem. If air enters the refrigerant system, an excessively high pressure results, causing equipment damage or injury.
• If the refrigerant gas leaks during the installation, ventilate the area imme­diately. Otherwise it can be harmfull for your health.
• Dismantling the unit, treatment of the refrigerant oil and eventual parts should be done in accordance with local and national standards.
6
IMPORTANT SAFETY INSTRUCTIONS
ENGLISH
• Replace the all batteries in the remote control with new ones of the same type. Do not mix old and new batteries or different types of batteries. There is risk of fire or product failure.
• Do not recharge or disassemble the batteries. Do not dispose off batteries in a fire. They may burn or explode.
• If the liquid from the batteries gets onto your skin or clothes, wash it well with clean water. Do not use the remote if the batteries have leaked. The chemicals in batteries could cause burns or other health hazards.
• If you eat the liquid from the batteries, brush your teeth and see doctor. Do not use the remote if the batteries have leaked. The chemicals in bat­teries could cause burns or other health hazards.
• Do not let the air conditioner run for a long time when the humidity is very high and a door or a window is left open. Moisture may condense and wet or damage furniture.
• Do not expose your skin or kids or plants to the cool or hot air draft. This could harm to your health.
• Do not drink the water drained from the product. It is not sanitary and could cause serious health issues.
• Use a firm stool or ladder when cleaning, maintaining or repairing the product at an height. Be careful and avoid personal injury.
TABLE OF CONTENTS
7
ENGLISH
2 IMPORTANT SAFETY
INSTRUCTIONS
8 INSTALLATION 9 INSTALLATION OF
INDOOR, OUTDOOR UNIT
9 Select the best location 10 Fixing Installation Plate 11 Refrigerant charge 11 Piping length and elevation 12 Preparing work for Installation (ART
COOL Type Only)
13 INSTALLATION OF
WIRED REMOTE CON­TROLLER
13 Drill a hole in the wall 15 Wired remote controller installation
16 FLARING WORK AND
CONNECTION OF PIPING
16 Flaring work 17 Connection of piping - Indoor 19 Connection of piping - Outdoor
20 CONNECTING THE CABLE
BETWEEN INDOOR UNIT AND OUTDOOR UNIT
20 Connect the cable to the Indoor unit 22 Connect the cable to the Outdoor unit
24 CHECKING THE
DRAINAGE AND FORM­ING THE PIPINGS
24 Checking the Drainage 25 Forming the Piping
26 AIR PURGING AND EVAC-
UATION
26 Checking method 27 Evacuation
28 PANEL FRONT ASSEM-
BLY (ART COOL TYPE ONLY)
29 INSTALLATION PI485 30 TEST RUNNING 31 FUNCTION
31 Dip S/W Setting 32 Forced Cooling Operation 33 Wiring Error Check 33 Saving Power Consumption 34 Night Quiet Mode 35 Mode Lock 35 SLC (Smart Load Control) Mode 36 PCB Display(14/16/18/21k Model Only)
37 MAX COMBINATION
CAPACITY
38 INSTALLATION GUIDE AT
THE SEASIDE
38 SEASONAL WIND AND
CAUTIONS IN WINTER
39 Model Designation 39 Airborne Noise Emission 39 Limiting concentration
TABLE OF CONTENTS
8
INSTALLATION
ENGLISH
INSTALLATION
Installation plate
Type "B" screws
Type "A" screw (6 EA) Type "A" screw (8 EA) Type "A" screw (7 EA)
Holder Remote Control
Type "A" screw and plastic anchors
Installation Parts
Clearance of side discharge unit [Unit : mm(inch)]
Do not install the product where sufficient ventilation is not secured. The performance may be decreased or the product may not be operated.
h In case of series or another installation, please refer to related PDB.
6) or less
1
00(19-11/
ore
300(11-13/16)
19-11/16) or le
0(
50
or m
ss
erom ro
)8/ 3-93(0001
H
300(11-13/16)
D
L
or more
3/8)
-
39
00(
10
or more
5
30
0
(
11-13
or
m
/16
ore
)
600(23-19
or more
/32)
600(23-19/32) or more
1000(39-3/8) or more
00 0
1 (39-3/8) or more
11-13/16)
300(
or more
300(11-13/16) or more
2000(78-3/4) or more
INSTALLATION OF INDOOR, OUTDOOR UNIT
9
ENGLISH
Read completely, then follow step by step. You need to select adequate installation location
considering the following conditions, and make sure to acquire the consent of the user.
Select the best location
1 Do not have any heat or steam near the unit. 2 Select a place where there are no obstacles
in front of the unit.
3 Make sure that condensation drainage can be
conveniently routed away.
4 Do not install near a doorway. 5
Ensure the spaces indicated by arrows from the wall, ceiling, fence or other obstacles.
6 Use a stud finder to locate studs to prevent
unnecessary damage to the wall.
1 If an awning is built over the unit to prevent
direct sunlight or rain exposure, make sure that heat radiation from the condenser is not restricted.
2 Ensure that the spaces indicated by arrows
around front, back and side of the unit.
3 Do not place animals and plants in the path of
the warm air.
4 Take the air conditioner weight into account
and select a place where noise and vibration are minimum.
5 Select a place so that the warm air and noise
from the air conditioner do not disturb neigh­bors.
6 Place that can sufficiently endure the weight
and vibration of the outdoor unit and where even installation is possible.
7 Place that has no direct influence of snow or
rain.
8 Place with no danger of snowfall or icicle
drop.
9 Place without weak floor or base such as
decrepit part of the building or with a lot of snow accumulation.
10 Sufficient ventilation is secured.
If the outdoor unit is installed on a roof structure, be sure to level the unit. Ensure the roof struc­ture and anchoring method are adequate for the unit location. Consult local codes regarding rooftop mounting.
Indoor unit
Outdoor unit
Rooftop Installations
Install the indoor unit on the wall where the height from the floors more than 2.3 meters. (ART COOL Type Only 1.5m)
CAUTION
!
More than 20cm
More than
10cm
More than 2.3m
More than
10cm
More than 20cm
More than
10cm
More than 2.3m
More than
10cm
More than 20cm
More
than 50cm
More than 1.5m
More
than 50cm
More than 20cm
More than
10cm
More than 2.3m
More than
10cm
more than
70cm
more than
30cm
more than
30cm
more than
60cm
more than 60cm
more than
70cm
more than
30cm
more than 60cm
more than
30cm
more than
60cm
INSTALLATION OF INDOOR, OUTDOOR UNIT
10
INSTALLATION OF INDOOR, OUTDOOR UNIT
ENGLISH
Fixing Installation Plate
The wall you select should be strong and solid enough to prevent vibration
1 Mount the installation plate on the wall
with type "A" screws. If mounting the unit on a concrete wall, use anchor bolts.
- Mount the installation plate horizontally by aligning the centerline using a level.
<Type 1>
2 Measure the wall and mark the centerline.
It is also important to use caution concern­ing the location of the installation plate­routing of the wiring to power outlets is through the walls typically. Drilling the hole through the wall for piping connections must be done safely.
<Type 2>
<Type 3>
<Type 4>
<Type 1>
<Type 2>
<Type 3>
<Type 4>
Chassis
Hook
Installation Plate
Type “A”
Installation Plate
Type “A”
Installation Plate
Chassis
Hook
Type "A" Screws
Unit Outline
Left Rear Piping
Right Rear Piping
Place a level on raised tab
(Unit : mm)
Installation plate
Ø65
Ø65
184
220
156
307
460 567
Chassis
Hook
Installation Plate
Type “A”
Indoor Type
Capacity
(kBtu/h)
Type
Wall mounted
/ART COOL
Mirror
7, 9, 12 1, 3
18, 24 2, 4
Installation plate
Left rear piping Right rear piping
Ø65
Ø65
105mm
105mm
65mm
55mm
45mm
140mm
Ø65
65mm65mm
65mm
45mm
Ø65
Installation plate
Left rear piping Right rear piping
Installation plate
Left rear piping Right rear piping
Ø65
133mm
101mm
101mm
Ø65
100mm
INSTALLATION OF INDOOR, OUTDOOR UNIT
11
ENGLISH
Piping length and elevation
Multiple Piping Models (Unit: m)
Phase Capacity(kBtu/h) Total Length Max Length(A/B)
Max Elevation
(h1)
In - In Elevation
(h2)
14/16 30 20 15 7.5
18 50 25 15 7.5 21 50 25 15 7.5
24/27 70 25 15 7.5
30 75 25 15 7.5 40 85 25 15 7.5
Capacity is based on standard length and maximum allowance length is on the basis of reliability. If outdoor unit is at higher elevation than the indoor units, after 24m of vertical height, 1 oil trap is required.
CAUTION
!
Refrigerant charge
The calculation of the additional charge should be taken in account for the length of extra pipe.
Multiple Piping Models (Unit: m)
• Multiple Piping Models Additional charge (g) = ((A Room Installation Length – Standard Length ) x 20g/m
+ (B Room Installation Length – Standard Length ) x 20g/m +.. )
- CF(Correction Factor) x 150
h CF = Max. number of connectable indoor unit – Total number of connected indoor unit
Phase Capacity(kBtu/h)
Standard
Length(m)
Max Piping for
one room(m)
Max total Piping
Length
Additional
Charge(g/m)
14/16 7.5 20 30 20
18 7.5 25 50 20 21 7.5 25 50 20
24/27 7.5 25 70 20
30 7.5 25 75 20 40 7.5 25 85 20
A
h2
h1
B
Multiple Piping Type
12
INSTALLATION OF INDOOR, OUTDOOR UNIT
ENGLISH
Preparing work for Installation (ART COOL Type Only)
1 First, push the front panel backward and lift it up to remove the two screws. 2 The moment of lifting the both lower parts of panel front, you can hear sound this panel came
out, In this time panel front is separated
3 After pull down this panel a bit, and separate connecting wire with product.
1 Remove two screws(for fixing cover pipe) 2 Pull up the cover side of desired connecting direction, then
cover side is separated.
3 In case of connecting direction is left or right, path through
the hole of cover side.
1 Remove the rubber stopple of desired direction of drainage. 2 As the following picture, Insert drain hose in the handle of
drain pan, and join drain hose and connecting hose.
After removing the pipe hole, cut the burr for safety.
CAUTION
!
Pipe hole
rubber cap
Only one
desiring direction
Connecting
part
Adhesive
Drain
hose
NOTE
!
When connecting pipe path through rear wall, don’t remove the hole.
Open panel front
Remove cover pipe and cover side
Drain hose junction
Panel Front
Connector
Panel Front
Connector
INSTALLATION OF WIRED REMOTE CONTROLLER
13
ENGLISH
Drill a hole in the wall
Drill the piping hole with a Ø65mm hole core drill. Drill the piping hole at either the right or the left with the hole slightly slanted to the outdoor side.
1 Please fix tightly using provided screw after placing remote controller setup board on the
place where you like to setup.
- Please set it up not to bend because poor setup could take place if setup board bends. Please set up remote controller board fit to the reclamation box if there is a reclamation box.
2 Can set up Wired remote controller cable into three directions.
- Setup direction: the surface of wall reclamation, upper, right
- If setting up remote controller cable into upper and right side, please set up after removing remote controller cable guide groove.
h Remove guide groove with long nose.
Reclamation to the surface of the wallUpper part guide grooveRight part guide groove
2
2
1
3
3
<Wire guide grooves>
INSTALLATION OF WIRED REMOTE CON­TROLLER
WALL
Indoor
Outdoor
5-7mm
(3/16"~5/16")
14
INSTALLATION OF WIRED REMOTE CONTROLLER
ENGLISH
4 Please connect indoor unit and remote controller using connection cable.
5 Please use extension cable if the distance between wired remote controller and indoor unit is
more than 10m.
Please check if connector is normally connected.
Connecting cable
Indoor Unit side
When installing the wired remote controller, do not bury it in the wall. (It can cause damage in the temperature sensor.) Do not install the cable to be 50m or above. (It can cause communication error.)
• When installing the extension cable, check the connecting direction of the connector of the remote controller side and the product side for correct installation.
• If you install the extension cable in the opposite direction, the connector will not be con­nected.
• Specification of extension cable: 2547 1007 22# 2 core 3 shield 5 or above.
CAUTION
!
3 Please fix remote controller upper part into the
setup board attached to the surface of the wall, as the picture below, and then, connect with setup board by pressing lower part.
- Please connect not to make a gap at the remote controller and setup board’s upper and lower, right and left part.
When separating remote controller from setup board, as the picture below, after inserting into the lower separating hole using screw driver and then, spinning clockwise, remote controller is separated.
- There are two separating holes. Please individu-
ally separate one at a time.
- Please be careful not to damage the inside
components when separating.
Wal l Side
Wal l Side
Wal l Side
Wal l Side
<Connecting order>
<Separating order>
INSTALLATION OF WIRED REMOTE CONTROLLER
15
ENGLISH
Fig.1 Typical locations for remote controller
Wired remote controller installation
- Since the room temperature sensor is in the remote controller, the remote controller box should be installed in a place away from direct sunlight, high humidity and direct supply of cold air to maintain proper space temperature. Install the remote controller about 5ft(1.5m) above the floor in an area with good air circulation at an average temperature.
Do not install the remote controller where it can be affected by:
- Drafts, or dead spots behind doors and in corners.
- Hot or cold air from ducts.
- Radiant heat from sun or appliances.
- Concealed pipes and chimneys.
- Uncontrolled areas such as an outside wall behind the remote controller.
- This remote controller is equipped with a seven segment LED. display. For proper display of the remote controller LED's, the remote controller should be installed properly as shown in Fig.1. (The standard height is 1.2~1.5 m from floor level.)
yes
no
no
5feet
no
(1.5meters)
16
FLARING WORK AND CONNECTION OF PIPING
ENGLISH
Flaring work
Main cause for gas leakage is due to defect in flaring work. Carry out correct flaring work in the following procedure.
Cut the pipes and the cable
- Use the piping kit accessory or the pipes pur­chased locally.
- Measure the distance between the indoor and the outdoor unit.
- Cut the pipes a little longer than measured distance.
- Cut the cable 1.5m longer than the pipe length.
Burrs removal
- Completely remove all burrs from the cut cross section of pipe/tube.
- Put the end of the copper tube/pipe in a downward direction as you remove burrs in order to avoid dropping burrs into the tubing.
Putting nut on
- Remove flare nuts attached to indoor and outdoor unit, then put them on pipe/tube having completed burr removal. (not possible to put them on after flaring work)
Flaring work
- Carry out flaring work using flaring tool as shown below.
Firmly hold copper pipe in a bar in the dimension shown in the table below.
Copper
tube
90°
Slanted Uneven Rough
Pipe
Reamer
Point down
Flare nut
Copper tube
Bar
Copper pipe
Clamp handle
Red arrow mark
Cone
Yoke
Handle
Bar
"A"
Outside diameter
A
mm inch mm Ø6.35 1/4 1.1~1.3 Ø9.52 3/8 1.5~1.7 Ø12.7 1/2 1.6~1.8
Ø15.88 5/8 1.6~1.8 Ø19.05 3/4 1.9~2.1
FLARING WORK AND CONNECTION OF PIP­ING
FLARING WORK AND CONNECTION OF PIPING
17
ENGLISH
Check
- Compare the flared work with figure below.
- If flare is noted to be defective, cut off the flared section and do flaring work again.
Connection of piping - Indoor
Preparing the indoor unit's piping and drain hose for installation through the wall.
1 Route the indoor tubing and the drain hose in the direction of rear left or right
2 Tape the tubing, drain hose and the connecting cable. Be sure that the drain hose is located at
the lowest side of the bundle. Locating at the upper side can cause drain pan to overflow inside the unit.
Inclined
Inside is shining without scratches.
Smooth all round
Even length
all round
Surface
damaged
Cracked Uneven
thickness
= Improper flaring =
If the drain hose is routed inside the room, insulate the hose with an insulation material* so that dripping from "sweating"(condensation) will not damage furniture or floors. *Foamed polyethylene or equivalent is recommended.
CAUTION
!
Drain hose
Drain hose
Drain hose
Tape
Connecting pipe
Drain hose
Connecting cable
Tape
Connecting pipe
Drain hose
Connecting cable
Connecting cable
Drain hose
Gas side piping
Liquid side piping
Loop
18
FLARING WORK AND CONNECTION OF PIPING
ENGLISH
Indoor unit installation Hook the indoor unit onto the upper portion of the installation plate.(Engage the two hooks of the rear top of the indoor unit with the upper edge of the installation plate.) Ensure that the hooks are properly seated on the installation plate by moving it left and right. Press the lower left and right sides of the unit against the installation plate until the hooks engage into their slots(clicking sound).
Connecting the pipings to the indoor unit and drain hose to drain pipe
- Align the center of the pipings and sufficient­ly tighten the flare nut by hand.
- Tighten the flare nut with a wrench.
- When extending the drain hose at the indoor unit, install the drain pipe.
Wrap the insulation material around the con­necting portion.
- Overlap the connection pipe insulation mate­rial and the indoor unit pipe insulation materi­al. Bind them together with vinyl tape so that there is no gap.
- Wrap the area which accommodates the rear piping housing section with vinyl tape.
Drain hose
Connecting
Indoor unit tubing
Flare nut
Pipings
Torque wrench
Indoor unit tubing
Spanner (fixed)
Connection pipe
Flare nut
Vinyl tape(narrow)
Adhesive
Drain pipe
Indoor unit drain hose
Plastic bands
Insulation material
Vinyl tape(narrow)
Connection pipe
Connecting cable
Vinyl tape (wide)
Wrap with vinyl tape
Indoor unit pipe
Pipe
Outside diameter
Torque
mm inch N.m Ø6.35 1/4 16±2 Ø9.52 3/8 38±4 Ø12.7 1/2 55±6
Ø15.88 5/8 75±7 Ø19.05 3/4 110±10
FLARING WORK AND CONNECTION OF PIPING
19
ENGLISH
- Bundle the piping and drain hose together by wrapping them with vinyl tape over the range within which they fit into the rear pip­ing housing section.
Good case Press on the upper side of clamp and unfold the tubing to downward slowly.
Bad case Following bending type from left to right could cause problem of pipe damage.
Connection of piping - Outdoor
Align the center of the piping and sufficiently tighten the flare nut by hand.
Connecting pipe order
1) ROOM A~E gas side pipe
2) ROOM A~E liquid side pipe
Finally, tighten the flare nut with torque wrench until the wrench clicks.
- When tightening the flare nut with torque wrench ensure the direction for tightening fol­lows the arrow on the wrench.
Wrap with vinyl tape
Drain hose
Pipe
Vinyl tape(wide)
Ø12.7(1/2 inch) Connector
Outdoor unit
Main gas side valve
Main liquid side valve
Gas side piping
ROOM A
ROOM B
ROOM C
ROOM D
ROOM E
Liquid side piping
Installation Information (For right piping) For right piping, follow the instruction below.
CAUTION
!
Outside diameter
Torque
mm inch N.m Ø6.35 1/4 16±2 Ø9.52 3/8 38±4 Ø12.7 1/2 55±6
Ø15.88 5/8 75±7 Ø19.05 3/4 110±10
20
CONNECTING THE CABLE BETWEEN INDOOR UNIT AND OUTDOOR UNIT
ENGLISH
Connect the cable to the Indoor unit
Connect the cable to the indoor unit by connecting the wires to the terminals on the control board individually according to the outdoor unit connection. (Ensure that the color of the wires of the outdoor unit and the terminal No. are the same as those of the indoor unit.) The earth wire should be longer than the common wires. The circuit diagram is not subject to change without notice. When installing, refer to the circuit diagram behind the panel front of Indoor Unit the wiring dia­gram on the Control Cover Inside Outdoor Unit.
• The circuit diagram is not subject to change without notice.
• Be sure to connect wires according to the wiring diagram.
• Connect the wires firmly, so that not to be pulled out easily.
• Connect the wires according to color codes by referring the wiring diagram.
CAUTION
!
CONNECTING THE CABLE BETWEEN INDOOR UNIT AND OUTDOOR UNIT
2 Unit 3 Unit
4 Unit 5 Unit
CONNECTING THE CABLE BETWEEN INDOOR UNIT AND OUTDOOR UNIT
21
ENGLISH
The power cord connected to the outdoor unit should be complied with the following speci­fications (Cable type approved by HAR or SAA).
The power connecting cable connected to the indoor and outdoor unit should be complied with the following specifications (This equipment shall be provided with a cord set complying with the national regula­tion).
CAUTION
!
Provide a circuit breaker between power source and the unit as shown below.
CAUTION
!
GN/YL
20mm
NORMAL CROSS-SECTIONAL AREA 0.75mm
2
H07RN-F
ø7.5mm
GN/YL
20mm
Phase
Capacity (kBtu/h) 14 16 18 21 24 27 30 40
NORMAL CROSS SECTIONAL AREA 2.5 2.5 2.5 2.5 2.5 2.5 2.5 3.5
Cable Type H07RN-F
5 Unit
Main power source
Air
Conditioner
Circuit Breaker Use a circuit breaker or time delay fuse.
22
CONNECTING THE CABLE BETWEEN INDOOR UNIT AND OUTDOOR UNIT
ENGLISH
1 Remove the cover control from the unit by
loosening the screw. Connect the wires to the terminals on the control board individually as the following.
2 Secure the cable onto the control board
with the holder (clamper).
3 Refix the cover control to the original posi-
tion with the screw.
4 Use a recongnized circuit breaker between
the power source and the unit. A discon­nection device to adequately disconnect all supply lines must be fitted.
After the confirmation of the above conditions, prepare the wiring as follows.
1 Never fail to have an individual power circuit specifically for the air conditioner. As for the
method of wiring, be guided by the circuit diagram posted on the inside of control cover.
2 Firmly tighten the terminal screws to prevent them loosening. After tightening, pull the
wires lightly to confirm that they do not move. (If they are loose the unit, the unit will not
operate normally or it can cause burn-out of the wires.)
3 Specification of power source. 4 Confirm that electrical capacity is sufficient. 5 See to that the starting voltage is maintained at more than 90 percent of the rated volt-
age marked on the name plate.
6 Confirm that the cable thickness is as specified in the power source specification.
(Particularly note the relation between cable length and thickness.
7 Do not install an earth leakage circuit breaker in a wet or moist area. 8 The following would be caused by voltage drop.
- Vibration of a magnetic switch, which will damage the contact point, fuse breaking, dis­turbance of the normal function of the overload.
9
The means for disconnection from a power supply shall be incorporated in the fixed wiring and have an air gap contact separation of at least 3mm in each active(phase) conductors.
10 The Power cord connected to the unit should be selected according to the following
specifications.
CAUTION
!
Capacity (kBtu/h) 14 16 18 21 24 27 30 40
Circuit Breaker (A) 15 15 20 20 25 25 25 30
1Ø Models
Connect the cable to the Outdoor unit
Outdoor unit
Terminal block
Over 15mm
Holder for
power supply
cord
Cover control
Power cord
Connecting cable
Loosen terminal screw
Terminal block
CONNECTING THE CABLE BETWEEN INDOOR UNIT AND OUTDOOR UNIT
23
ENGLISH
Use round pressure terminals for connections to the power terminal block.
When none are available, follow the instructions below.
- Do not connect wiring of different thicknesses to the power terminal block. (Slack in the power wiring may cause abnormal heat.)
- When connecting wiring which is the same thickness, do as shown in the figure below.
- For wiring, use the designated power wire and connect firmly, then secure to prevent outside pressure being exerted on the terminal block.
- Use an appropriate screwdriver for tightening the terinal screws. A screwdriver with a small head will strip the head and make proper tighterning impossible.
- Over-tightening the terminal screws may break them.
Round pressure terminal
Power wire
Connect same thickness wiring to both sides.
It is forbidden to connect two to one side.
It is forbidden to connect wiring of different thicknesses.
Precautions when laying power wiring
Checking the Drainage
To check the drainage.
1 Pour a glass of water on the evaporator. 2 Ensure the water flows through the drain
hose of the indoor unit without any leak­age and goes out the drain exit.
Drain piping
1 The drain hose should point downward for
easy drain flow.
2 Do not make drain piping.
Downward slope
Do not raise
Water leakage
Accumulated drain water
Air
Waving
Water leakage
Tip of drain hose dipped in water
Water leakage
Ditch
Less than 50mm gap
CHECKING THE DRAINAGE AND FORMING THE PIPINGS
24
CHECKING THE DRAINAGE AND FORMING THE PIPINGS
ENGLISH
Connecting area
drain hose
Leakage
checking
Drain pan
Drain
hose
Leakage
checking
CHECKING THE DRAINAGE AND FORMING THE PIPINGS
25
ENGLISH
Forming the Piping
Form the piping by wrapping the connecting portion of the indoor unit with insulation mate­rial and secure it with two kinds of vinyl tape.
- If you want to connect an additional drain hose, the end of the drain outlet should be routed above the ground. Secure the drain hose appropriately.
In cases where the outdoor unit is installed below the indoor unit perform the following.
1 Tape the piping, drain hose and connecting
cable from down to up.
2 Secure the tapped piping along the exterior
wall using saddle or equivalent.
• Trap is required to prevent water from entering into electrical parts.
Plastic band
Taping
Drain hose
Pipings
Connecting cable
Power supply cord
Seal a small opening around the pipings with gum type sealer.
In cases where the Outdoor unit is installed above the Indoor unit perform the following.
1 Tape the piping and connecting cable from
down to up.
2 Secure the taped piping along the exterior
wall. Form a trap to prevent water entering the room.
3 Fix the piping onto the wall by saddle or
equivalent.
Seal a small opening around the pipings with gum type sealant.
Trap
Trap
26
AIR PURGING AND EVACUATION
ENGLISH
Check that each tube(both liquid and gas side tubes) between the indoor and outdoor units have been properly connected and all wiring for the test run has been completed. Remove the service valve caps from both the gas and the liquid side on the outdoor unit. Check that both the liquid and the gas side service valves on the outdoor unit are kept closed at this stage.
Connect the manifold valve(with pressure gauges) and dry nitrogen gas cylinder to this service port with charge hoses.
CAUTION
Be sure to use a manifold valve for leakage test. If it is not available, use a stop valve for this purpose. The "Hi" knob of the manifold valve must always be kept close.
- Pressurize the system to no more than 551 P.S.I.G. with dry nitrogen gas and close the cylinder valve when the gauge reading reached 551 P.S.I.G. Next, test for leaks with liquid soap.
!
CAUTION
To avoid nitrogen entering the refrigerant system in a liquid state, the top of the cylinder must be higher than its bottom when you pressurize the system. Usually, the cylinder is used in a vertical standing position.
!
- Do a leakage test of all joints of the tubing(both indoor and outdoor) and both gas and liquid side service valves. Bubbles indicate a leak. Be sure to wipe off the soap with a clean cloth.
- After the system is found to be free of leaks, relieve the nitrogen pressure by loosening the charge hose connector at the nitrogen cylinder. When the system pressure is reduced to normal, disconnect the hose from the cylinder.
The air and moisture remaining in the refriger­ant system have undesirable effects as indi­cated below.
- Pressure in the system rises.
- Operating current rises.
- Cooling(or heating) efficiency drops.
- Moisture in the refrigerant circuit may freeze and block capillary tubing.
- Water may lead to corrosion of parts in the refrigeration system.
Therefore, after evacuating the system, take a leak test for the piping and tubing between the indoor and outdoor unit.
Checking method
Preparation
Leakage test
AIR PURGING AND EVACUATION
Indoor unit
Manifold valve
Outdoor unit
Lo Hi
Pressure gauge
Charge hose
Nitrogen gas cylinder(in vertical standing position)
AIR PURGING AND EVACUATION
27
ENGLISH
- When the desired vacuum is reached, close the "Lo" knob of the manifold valve and stop the vacuum pump.
Required time for evacuation when 30 gal/h
vacuum pump is used
If tubing length is
less than 10m (33 ft)
If tubing length is
longer than 10m (33
ft)
Less than 0.5 Torr Less than 0.5 Torr
- Replace the valve caps at both gas and liquid side service valves and fasten them tight.
This completes air purging with a vacuum pump. The air conditioner is now ready to test run.
- With a service valve wrench, turn the valve stem of liquid side valve counter-clockwise to fully open the valve.
- Turn the valve stem of gas side valve counter­clockwise to fully open the valve.
- Loosen the charge hose connected to the gas side service port slightly to release the pressure, then remove the hose.
- Replace the flare nut and its bonnet on the gas side service port and fasten the flare nut secure­ly with an adjustable wrench. This process is very important to prevent leakage from the sys­tem.
Lo Hi
Manifold valve
Vacuum pump
Open
Open
Pressure gauge
Indoor unit
Outdoor unit
Finishing the Job
Use a vacuum pump or Inert (nitrogen) gas when doing leakage test or air purge. Do not compress air or Oxygen and do not use Flammable gases. Otherwise, it may cause fire or explosion.
- There is the risk of death, injury, fire or explosion.
WARNING
!
Evacuation
- Connect the charge hose end described in the preceding steps to the vacuum pump to evacuate the tubing and indoor unit. Confirm the "Lo" knob of the manifold valve is open. Then, run the vacuum pump. The operation time for evacuation varies with tubing length and capacity of the pump. The following table shows the time required for evacuation.
28
PANEL FRONT ASSEMBLY (ART COOL TYPE ONLY)
ENGLISH
1 First, Check the side cover assembly
exactly, Fix power cord in the bottom groove of cover side left.
2 Assemble connecting lead wire with con-
troller and first fix the upper part of panel front, then match the lower part of panel front
3 Suspend hook of front panel in the groove
after contract lower of 2 screws.
Panel Front
Connector
Panel Front
Connector
PANEL FRONT ASSEMBLY (ART COOL TYPE ONLY)
INSTALLATION PI485
29
ENGLISH
Fix the PI485 PCB as shown in Fig. Detailed installation method refer to PI485 Installation Manual.
18kBtu/h, 21kBtu/h
24kBtu/h, 27kBtu/h, 30kBtu/h
1Ø : 40kBtu/h
INSTALLATION PI485
T
h
i
s
l
a
b
e
l
i
s
s
h
o
u
l
d b
e
a
p
p
l
i
e
d
i
n
t
h
e
l
o
c
a
t
i
o
n w
h
e
r
e
T
his
l
a
b
e
l
i
s
sh
ou
ld be
a
p
plie
d
in t
he
l
oc
a
t
i
o
n
wh
e
r
e
L
G
A
P(
Su
b
PC
B
f
o
r
C
e
n
t
r
a
l
C
o
n
t
r
o
l
l
e
r
i
s
i
n
s
t
a
l
l
e
d
.
L
G
AP(
Su
b P
C
B
f
or
C
e
n
t
r
a
l
C
on
t
r
o
l
le
r
i
s
i
n
s
t
a
ll
e
d
.
Pl
e
a
s
e
c
o
n
n
e
c
t
t
h
e
w
i
r
e
a
f
t
e
r
i
ns
t
a
l
l
i
n
g
t
h
e
L
G
A
P
.
Pl
e
a
s
e
c
o
nn
e
c
t
th
e
wir
e
a
f
t
e
r
i
n
s
t
a
ll
i
ng
t
h
e
LG
A
P
.
T
h
i
s
i
s
t
h
e
s
p
a
c
e
f
o
r
i
n
s
t
a
l
l
a
ti
o
n
o
f
P
I
4
8
5
G
a
te
w
a
y.T
h
is
i
s
th
e
s
p
a
c
e
fo
r
in
s
ta
l
la
t
i
o
n
o
f
P
I
4
8
5
G
a
t
e
w
a
y.
(
Ac
c
e
s
s
o
ry
)
(A
cc
e
s
s
o
ry
)
P
l
e
a
s
e
c
o
n
n
e
c
t
t
h
e
w
i
r
e
a
fte
r
i
n
s
ta
l
l
i
n
g
P
I
4
8
5
Plea
s
e
co
n
n
ec
t
t
h
e
w
i
r
e
a
f
te
r
in
s
t
a
l
l
in
g
P
I
4
8
5
G
a
te
w
a
y.
G
at
e
wa
y.
Screw HoleScrew Hole
Screw HoleScrew Hole
M
EZ30
1
7
1
8
0
2
M
E
Z30
1
7
18
0
2
30
TEST RUNNING
ENGLISH
Remove the battery cover by pulling it accord­ing to the arrow direction.
Insert new batteries making sure that the (+) and (–) of battery are installed correctly.
Reattach the cover by pushing it back into position.
- Check that all tubing and wiring have been properly connected.
- Check that the gas and liquid side service valves are fully open.
Prepare remote control
Bolt
Tubing connection
Discharge temperature
Discharge air
Intake temperature
Discharge temperature
Discharge air
Intake temperature
Discharge temperature
Discharge air
Intake temperature
Operate unit for 15~20 minutes, then check the system refrigerant charge:
- Measure the pressure of the gas side service valve.
- Measure the temperature of the intake and discharge of air.
- Ensure the difference between the intake temperature and the discharge is more than 8°C.
- For reference, the gas side pressure of opti­mum condition is as below.(Cooling)
Refrigerant
Outside ambi-
ent TEMP.
The pressure of
the gas side
service valve.
R410A 35°C (95°F)
8.5~9.5kg/cm2G
(120~135 P.S.I.G.)
NOTE
!
If the actual pressure are higher than shown, the system is most likely over­charged, and charge should be removed. If the actual pressure are lower than shown, the system is most likely under­charged, and charge should be added. The air conditioner is now ready for use.
Evaluation of the performance
NOTE
!
• Use 2 AAA(1.5volt) batteries. Do not use rechargeable batteries.
• Remove the batteries from the remote control if the system is not going to be used for a long time.
TEST RUNNING
FUNCTION
31
ENGLISH
Dip S/W Setting
If you set the Dip Switch when power is on, the change in setting is not applicable. The changing setting is enabled only when Power is reset.
When you set the dip switch, you should turn off the circuit breaker or shut the power source of the product down.
WARNING
!
CAUTION
• Unless the applicable dip switch is set properly, the product may not work.
• If you want to set a specific function, request that the installer sets the dip switch appropriately during installation.
!
FUNCTION
Dip Switch
Function
1234
Normal Operation (No Function)
Forced Cooling Operation
Wiring Error Check
Saving Power Consumption (Step 1)
Saving Power Consumption (Step 2)
Mode Lock (Cooling)
Mode Lock (Heating)
Night Quiet Mode (Step 1)
Night Quiet Mode (Step 2)
Mode Lock (Cooling) + Night Quiet Mode (Step 1)
Mode Lock (Cooling) + Night Quiet Mode (Step 2)
Mode Lock (Cooling) + Saving Power Consumption (Step 1)
Mode Lock (Cooling) + Saving Power Consumption (Step 2)
Mode Lock (Heating) + Saving Power Consumption (Step 1)
Mode Lock (Heating) + Saving Power Consumption (Step 2)
SLC (Smart Load Control) Mode
32
FUNCTION
ENGLISH
14/16/18/21(1Ø) kBtu/h 40(1Ø) kBtu/h
24/27/30(1Ø) kBtu/h
DIP-SW
SW01N
DIP SW2
Forced Cooling Operation
Adding the refrigerant in winter.
Setting Procedure
1 Set the Dip Switch as follow after shutting
the power source down.
2 Reset the power. 3 Check that the Red LED of PCB is on dur-
ing work. (The indoor unit is operated by force.)
4 Add the specific amount of refrigerant.
- When the green LED of PCB is on, compressor is going to be off because of low pressure.
- You should return the Dip Switch to operate normally after finishing the operation.
CAUTION
!
FUNCTION
33
ENGLISH
Saving Power Consumption
Saving Power Consumption operation is the function which enables efficient operation by lowering the maximum power consumption value.
Setting Procedure
1 Set the Dip Switch as follow after shutting
the power source down.
2 Reset the power.
1sec1sec
1sec
LED1
(Red)
LED1
(Green)
1sec
3
3
2
2
CAUTION
• If Indoor unit doesn’t communicate to out­door Unit, function could not be operated correctly.
• Only the wrong wiring connection is dis­played. You should change connection cor­rectly to operate the product.
• If Outdoor and Indoor temperature is too low in winter, the wiring error check func­tion will not be operated. (Red LED is lighting)
!
Step 1 Step 2
Wiring Error Check
You can check whether or not the wiring is correct.
Setting Procedure
1 Set the Dip Switch as follow after shutting
the power source down.
2 Reset the power. 3 Check that the Re and Green LED of PCB
are on during work. (The indoor unit is operated by force.)
4 If the wiring is correct, the Green LED will
light up. If the wiring is wrong, display as below (Display only wrong connection.)
• Red LED : Piping Number
• Green LED : Wiring Number (Room)
Example) If the Red LED blinks twice and the Green LED blinks 3 times, 2nd pipe is connected to 3rd room.
5 You should return the Dip Switch to oper-
ate normally after finishing wiring error check.
Power
consumption
and current
Nomal
Time
34
FUNCTION
ENGLISH
Saving Power Consumption Current level.
Night Quiet Mode
Night Quiet Mode operation lowers the noise level of the outdoor unit by changing the comp fre­quency and fan speed. This function is operated all night long.
Setting Procedure
1 Set the Dip Switch as follow after shutting the power source down.
2 Reset the power.
Night Quiet Mode with Mode Lock.
Saving Power Consumption with Mode Lock.
Phase
Model 14k 16k 18k 21k 24k 27k 30k 40k
Step1(A) 889912131522
Step2(A) 778810111318
Saving Power Consumption (step 1) + Mode Lock (Cooling)
Saving Power Consumption (step 2) + Mode Lock (Cooling)
Saving Power Consumption (step 1) + Mode Lock (Heating)
Saving Power Consumption (step 2) + Mode Lock (Heating)
Mode Lock (Cooling) + Night Quiet Mode (step 1)
Mode Lock (Cooling) + Night Quiet Mode (step 2)
Step 1 Step 2
h Noise level :Step 1 > Step 2
CAUTION
• If comp frequency and fan speed are down, the cooling capacity may decrease accordingly.
• This function is only available for Cooling Mode.
• If you want to stop the Night Quiet Mode, Change the Dip Switch.
• If operating indoor unit is set by the fan speed “Power”, Night Quiet Mode will be stopped until fan speed “Power” is changed.
!
FUNCTION
35
ENGLISH
Mode Lock
Setting Procedure
1 Set the Dip Switch as follow after shutting the power source down.
2 Reset the power.
Mode Lock with Night Quiet Mode
Saving Power Consumption with Mode Lock.
Mode Lock (Cooling) + Night Quiet Mode (step 1)
Mode Lock (Cooling) + Night Quiet Mode (step 2)
Mode Lock (Cooling) + Saving Power Consumption (step 1)
Mode Lock (Heating) + Saving Power Consumption (step 1)
Mode Lock (Cooling) + Saving Power Consumption (step 2)
Mode Lock (Heating) + Saving Power Consumption (step 2)
Only Cooling Mode Only Heating Mode
Through the most efficient operation accord­ing to the in/outdoor load, must minimize the energy consumption.
Setting Procedure
1 Set the Dip Switch as follow after the
power source down.
2 Reset the power.
SLC (Smart Load Control)
CAUTION
• The cooling/heating capacity may decrease depending on the in/outdoor load.
• If you want to stop the SLC Mode, Change the Dip Switch.
!
SLC (Smart Load Control) Mode
18~40(1Ø) kBtu/h
Power
consumption
Normal
Time
36
FUNCTION
ENGLISH
PCB Display(14/16/18/21k Model Only)
It is useful to check the cycle data without LGMV.
Whenever you push the Tact Switch, the cycle information will be shown as below. h After 1page is displayed, subsequently 2page is displayed.
Tact S/W
Item
Display
14/16k 18/21k Example 1page 2page
- 1 time Low Pressure 890kpa ‘LP’ ’ 89’
- 2 time Hi Pressure 2900kpa ‘HP’ ‘290’
1 time 3 time Discharge Temp. 85°C ‘DS’ ’ 85’
2 time 4 time Cond Out Temp. -10°C ‘CS’ ‘-10’
3 time 5 time Suction Temp. -10°C ‘SS’ ‘-10’
4 time 6 time ODU Air Temp. -10°C ‘AS’ ‘-10’
5 time 7 time Current 15A ‘A’ ‘ 15’
6 time 8 time Voltage 230V ‘V’ ‘230’
7 time 9 time Comp Hz 100Hz ‘F’ ‘100’
8 time 10 time DC Link Voltage 230V ‘dc’ ‘230’
When you push the Tact Switch, use the material non-conducting electricity.
WARNING
!
Operating Method
TACT-SW1
MAX COMBINATION CAPACITY
37
ENGLISH
Multi Piping Type
The combination of indoor unit is to be decided that the sum of indoor unit capacity index must be smaller than the maximum combination capacity of outdoor unit. We recommend to calculate indoor unit capacity like below.
If you do not follow our recommendation, it will have some problems in low ambient condition i.e. some indoor unit will not be able to heat very well in heating mode.
CALCULATION METHOD FOR THE CONNECTABLE TOTAL CAPACITY OF INDOOR UNIT
Sum up the capacity of all indoor unit, but high static duct type indoor unit capacity weights 1.3 times
Ex)
1 Outdoor unit : A9UW566FA3(FM56AH)(connectable maximum capacity is 73kBtu)
Indoor unit: AMNH186BHA0[MB18AH],AMNH246BHA0[MB24AH],AMNH246BHA0[MB24AH] (18 + 24 + 24) x 1.3 = 66 x 1.3 = 85.8kBtu: this combination has a some problem
2 Out door unit: FM56AH
Indoor unit: AMNH186BHA0[MB18AH],AMNH246BHA0[MB24AH],AMNH18GD5L0[MS18AH] (18 + 24) x 1.3 + 18 + 72.6: this combination can be ok
Capacity
(kBtu/h)
Max Room No.
Combination Indoor Capacity
(kBtu/h)
Max Combination Capacity
(kBtu/h) 14 2 5,7,9,12 21 16 2 5,7,9,12 24 18 3 5,7,9,12,18 30 21 3 5,7,9,12,18 33 24 4 5,7,9,12,18,24 39 27 4 5,7,9,12,18,24 41 30 5 5,7,9,12,18,24 48 40 5 5,7,9,12,18,24 52
MAX COMBINATION CAPACITY
38
INSTALLATION GUIDE AT THE SEASIDE
ENGLISH
If the outdoor unit is to be installed close to the seaside, direct exposure to the sea wind should be avoided. Install the outdoor unit on the opposite side of the sea wind direction.
In case, to install the outdoor unit on the seaside, set up a windbreak not to be exposed to the sea wind.
- It should be strong enough like concrete to prevent the sea wind from the sea.
- The height and width should be more than 150% of the outdoor unit.
- It should be keep more than 70 cm of space between outdoor unit and the windbreak for easy air flow.
Place with fluent water draining
- Install at a place with fluent water draining to prevent damage from localized heavy rain and avoid frequent flooded area.
SEASONAL WIND AND CAUTIONS IN WINTER
- Sufficient measures are required in a snow area or severe cold area in winter so that product can be operated well.
- Get ready for seasonal wind or snow in win­ter even in other areas.
- Install a suction and discharge duct not to let in snow or rain.
- Install the outdoor unit not to come in con­tact with snow directly. If snow piles up and freezes on the air suction hole, the system may malfunction. If it is installed at snowy area, attach the hood to the system.
- Install the outdoor unit at the higher installa­tion console by 50cm than the average snowfall (annual average snowfall) if it is installed at the area with much snowfall.
- Where snow accumulated on the upper part of the Outdoor Unit by more than 10cm, always remove snow for operation.
Sea wind
Sea wind Sea wind
Windbreak
• Periodic ( more than once/year ) clean­ing of the dust or salt particles stuck on the heat exchanger by using water.
• Air conditioners should not be installed in areas where corrosive gases, such as acid or alkaline gas, are produced.
• Do not install the product where it could be exposed to sea wind (salty wind) directly. It can result corrosion on the product. Corrosion, particularly on the condenser and evaporator fins, could cause product malfunction or inefficient performance.
• If outdoor unit is installed close to the seaside, it should avoid direct exposure to the sea wind. Otherwise it needs additional anticorrosion treatment on the heat exchanger.
CAUTION
!
Selecting the location(Outdoor Unit)
INSTALLATION GUIDE AT THE SEASIDE
SEASONAL WIND AND CAUTIONS IN WINTER
39
ENGLISH
Model Designation
Indoor unit
Outdoor unit
Airborne Noise Emission
The A-weighted sound pressure emitted by this product is below 70 dB.
** The noise level can vary depending on the
site.
The figures quoted are emission level and are not necessarily safe working levels. Whilst there is a correlation between the emission and exposure levels, this cannot be used reli­ably to determine whether or not further pre­cautions are required. Factor that influence the actual level of exposure of the workforce include the characteristics of the work room and the other sources of noise, i.e. the num­ber of equipment and other adjacent process­es and the length of time for which an opera­tor exposed to the noise. Also, the permissi­ble exposure level can vary from country to country. This information, however, will enable the user of the equipment to make a better evaluation of the hazard and risk.
Limiting concentration
Limiting concentration is the limit of Freon gas concentration where immediate measures can be taken without hurting human body when refrigerant leaks in the air. The limiting con­centration shall be described in the unit of kg/m3(Freon gas weight per unit air volume) for facilitating calculation.
Calculate refrigerant concentration
Refrigerant concentration
=
Limiting concentration: 0.44kg/m3(R410A)
Total amount of replenished refrig-
erant in refrigerant facility (kg)
Capacity of smallest room where
indoor unit is installed (m
3
)
1 The height of H frame must be more
than 2 times the snowfall and its width shall not exceed the width of the prod­uct. (If width of the frame is wider than that of the product, snow may accumu­late)
2 Don't install the suction hole and dis-
charge hole of the Outdoor Unit facing the seasonal wind.
SMAWR09 BN0
Serial number
Indoor
Detailed product type AQ : Deluxe SQ : Standard AH* : Panel type color_Gallery(1), Silvr(V), Red(E), Gold(G), White Silver(H) AW* : Mirror type color_Mirror(R), Silver( White(W) AH : Ceiling cassette L : Low static No mark for Standard Inverter indoor units
Nominal Capacity EX) 9,000 Btu/h Class ’09’ 24,000 Btu/h Class ’24’ Type
Model Type M : Multi Indoor unit C : Common Indoor unit for Universal and Multi
S : Wall mounted/ARTCOOL Mirror J : Wall mounted A : ARTCOOL Panel T : Cassette B : Duct V : Floor-ceiling Q : Console
Chassis name
MU4
M27
Pipe Connecting Type M : Multiple pipes
Nominal capacity Ex) 18,000 Btu/h Class ’18’
Serial number Outdoor unit chassis name
Indicates that this is multi system outdoor unit using R410A Ex)
MU3 : Connectable max. 3 indoor units
MU4 : Connectable max. 4 indoor units
U4 2
FM
40 U3 2AH
Model type
Outdoor unit chassis name
Serial number
H : Heat pump Type of refrigerant
A : R410A Nominal capacity
Ex) 48,000 Btu/h Class ’48’ Model type
FM : Inverter multi ststem of Distributor Box type
40
ENGLISH
Loading...