KEYENCE NU-FS-N User Manual

96063E
Sensor Amplifier Communication Manual
Read this manual before use. Keep this manual in a safe place for future reference.

About This Manual

Compatible network units
CC-Link compatible network unit, NU-CL1 DeviceNet compatible network unit, NU-DN1
For specific communication procedures, refer to the manual of each network unit. For the functions of sensor amplifiers, refer to the manual of each sensor amplifier.
96063E
1
1
Network unit
1
FS-N14*
FS-N12*
FS-N10
CH1 CH2
3 4
2
ID number
Point

FS-N Series

Number of ID Numbers Occupied

The table below summarizes how many ID numbers are occupied by each model of sensor amplifier.
Model Number of ID numbers occupied
FS-N10 1 FS-N12* 1 FS-N14* 2
Connection example:

Data Assignments

Each ID number is assigned an output, setting value, current value, and external input.
Model Item Ch1 (1st ID number) Ch2 (2nd ID number)
Output Output
FS-N10 FS-N12*
FS-N14*
2
Setting value Setting value of output Current value Received light intensity External input External input Output Output 1 Output 2 Setting value Setting value of output 1 Setting value of output 2 Current value Received light intensity (Not used) External input External input (Not used)
The external input can be used after configuring the "Control Input"parameter of each sensor. (By default, "Control Input" is set to "0: Not use.") The models FS-N10/N12* do not have an external input wire, but they can utilize external input via network by using a network unit.
- Sensor Amplifier Network Manual -
-
1 FS-N Series
For the FS-N series, the data parameters that can be communicated via a network unit are specified as follows:
Parameter Available settings
Current Value 0 to 9999 Setting Value 0 to 9999
Current Value Prop­erty
Sensor Error
Sensor Warning
Key Lock
Product Code
Head Code (Not used with FS-N)
L-on/D-on (N.O./N.C.)
Over Range (Not used with FS-N) Under Range (Not used with FS-N) Invalid (Not used with FS-N)
0: No Error 1: Overcurrent Error 2: Not used 3: EEPROM Error 4: Not used 5: Not used 6: DATUM Correction Error 7: APC Error
0: No Warning 1: Limit Output ON
0: Unlock 1: Key Lock 2: PIN Code Lock 3: Communication Lock
FS-N10: 2000 FS-N12: 2000 FS-N14: 2001
0: OUT1: L-on / OUT2: L-on 1: OUT1: D-on / OUT2: L-on 2: OUT1: L-on / OUT2: D-on 3: OUT1: D-on / OUT2: D-on