96M0932
Safety Light Curtain
Power Supply Unit
SL-U2
Instruction Manual
The SL-U2 is a dedicated power supply unit designed for use with the Safety Light Curtain SL-C Series. The SL-U2 can be mounted on a DIN rail.
This Instruction Manual includes explanations of how to handle the SL-U2 power supply unit as well as important cautionary information. Please read it thoroughly before you use the SL-U2 power supply unit in order to take full advantage of the unit’s performance and store it so that it is easily accessible.
Finally, please see that this manual reaches the person or people who will be operating the power supply.
See the SL-C Series Instruction Manual for detailed information about the SL-C Series.
For safe usage
This manual’s format
This manual uses the following headings to make important sections easy to notice and understand. Always read these sections.
CAUTION
Failure to follow the instructions noted under this heading may result in damage to the product.
When using this device under the following conditions or operating environments, please consult with your KEYENCE sales representative in addition to implementing safety measures such as product operation that allows leeway with respect to features and use of failsafe provisions.
•Use of the product under conditions not described in SL-C Series instruction manual.
•Use of the product in applications involving nuclear power control, railroad facilities, aviation facilities, vehicles, fuel devices, medical equipment, and entertainment machinery.
•Use of the product in applications that may have a significant impact on human life or property, or that place a high priority on safety.
*Contact one of the Sales Offices listed on the back of this manual concerning Instruction Manuals.
General precautions
•Verify that this device is operating normally in terms of functionality and performance before the start of work and when operating the device.
•Implement safety measures as necessary to protect against possible damage that may result in the event that this product fails.
•Proceed with care when modifying the SL-U2, or when using it in a manner that falls outside of the ranges indicated in its specifications, since KEYENCE is unable to guarantee device functionality or performance in such situations.
•Use this product in combination with other devices only after careful consideration, since the SL-U2 may fail to satisfy its functionality and performance capabilities as a result of the conditions and environment in which it is used.
External dimensions |
|
Installation |
The SL-U2’s external dimensions are as indicated below.
Units: mm
|
35 |
3.5 |
|
2-ø4.2 |
11 |
||
(96.6) |
|||
|
24 |
||
|
|
25.8 |
|
|
|
35.9 |
|
|
100 |
111 |
|
|
11 |
|
The SL-U2 is installed to the left of the SL-R11 or SL-R12EX.
The connector is covered with a seal to protect it, so remove the seal before making the connection.
The connection methods are as follows. |
|
|
[1] When mounting on a DIN rail |
3. |
Slide one of the units to connect them both together. |
1. Refer to the figure above, and peel off the power |
4. |
Slide the SL-U2 connection hooks to fasten the |
supply connector seal. |
|
units together. |
2.Mount both the SL-R11 (SL-R12EX) and SL-U2 to the DIN rail.
* Install while being careful of the connectors
[2] When mounting on the wall with screws
1.Refer to the figure above, and peel off the power supply connector seal.
2.Refer to the figure above, and connect the two units.
3.Slide the SL-U2 connection hooks to fasten the units together.
4.Use M4 screws tightened to a torque of 0.7 N•m to mount both of the units to the wall.
Part names |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Wiring |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||
SL-U2 part names are as indicated below. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
How to connect wires |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||
Lock button |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Read the following precautions before connecting any |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
wires to the unit. Follow these tips when wiring the unit. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
SL-U2 |
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
SL-U2 |
|
|
|
|
|
|
|
|
|
|
|
|
(1) Twisting cables will decrease the effects of |
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||
Output indicator |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
OC |
|
||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
OC |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
induction. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
Terminal block cover |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
(2) Introducing a 1:1 isolation transformer or noise filter |
|
|
|
|
|
|
|
|
|
|
|
|
+ |
|
|||||||||||
|
|
|
|
|
|
|
|
+ |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
into the line will decrease power line noise. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
(3) Make wire lengths as short as possible. Separate |
|
|
|
|
|
|
|
|
|
|
|
|
- |
|
|||||||||||
DC 24 V output terminal |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
wires from power lines and signal lines that contain |
|
|
|
|
|
|
|
|
|
|
CAUTION AC 240V-100 ONLY |
|
|
L |
|
||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
- |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
noise. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||
PE terminal |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
D type ground |
|
|
N |
|
|||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||
|
|
|
|
|
|
|
CAUTION AC240V-100 ONLY |
|
|
|
L |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
AC100–240V |
(2)(3) |
|
|
(1) |
|
|
|
|
|
|
|||||||||||||||
terminal |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||
Power supply input |
|
|
|
|
|
|
|
|
|
|
N |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
10% |
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||
AC 100 V - 240 V |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Isolation transformer, |
|
|
|
|
|
|
|
|||||||
Lock button |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
noise filter, etc. |
|
|
|
|
|
|
|
|
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||
*LED indicator patterns are as follows: |
|
|
LED No. 1 |
2 3 4 5 6 |
|
|
|
|
*Tightening torque: 5.1 lb-in |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||
LED No. 1 Green ON during voltage output |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Wire Rating: AWG #22 - 14, |
stranded |
wire only, |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||
|
|
|
|
|
|
|
|
|
OC |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||||||||
LED No. 2 Green Output current at least 30% |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Copper wire only, 60˚C or higher |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||
LED No. 3 Green Output current at least 50% |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||
LED No. 4 Green Output current at least 60% |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||
LED No. 5 Green Output current at least 70% |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||
LED No. 6 Red |
Overcurrent detected |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||
When the yellow LED No. 5 is on, the current being used is approaching |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||||||
the power supply’s capacity. Consider the use of an additional power |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||||||
supply. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
WARRANTIES AND DISCLAIMERS |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Specifications |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
(1) KEYENCE warrants the Products to be free of defects in |
(4) |
OTHER |
|
THAN |
AS |
STATED |
HEREIN, |
THE |
||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
materials and workmanship for a period of one (1) year from the |
PRODUCTS/SAMPLES ARE PROVIDED WITH NO OTHER |
|||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
date of shipment. If any models or samples were shown to |
WARRANTIES WHATSOEVER. ALL EXPRESS, IMPLIED, AND |
|||||||||||||||
Model |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
SL-U2 |
|
Buyer, such models or samples were used merely to illustrate the |
STATUTORY |
WARRANTIES, |
INCLUDING, |
|
WITHOUT |
||||||||||||||
System |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Switching type |
|
general type and quality of the Products and not to represent that |
LIMITATION, THE WARRANTIES OF MERCHANTABILITY, |
|||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
the Products would necessarily conform to said models or |
FITNESS FOR A PARTICULAR PURPOSE, AND NON- |
|||||||||||||||||||||||
Input power supply voltage |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
AC100 to 240V 10% (50/60Hz) |
|
samples. Any Products found to be defective must be shipped to |
INFRINGEMENT OF PROPRIETARY RIGHTS, ARE EXPRESSLY |
||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
KEYENCE with all shipping costs paid by Buyer or offered to |
DISCLAIMED. |
IN NO |
EVENT |
SHALL KEYENCE AND |
ITS |
||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||
Overvoltage category |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
KEYENCE for inspection and examination. Upon examination by |
AFFILIATED ENTITIES |
BE |
LIABLE TO |
ANY |
PERSON |
OR |
||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
KEYENCE, KEYENCE, at its sole option, will refund the purchase |
ENTITY FOR ANY DIRECT, INDIRECT, INCIDENTAL, PUNITIVE, |
|||||||||||||||
Output voltage |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
DC24V 10%, Class2 |
|
price of, or repair or replace at no charge any Products found to |
SPECIAL OR CONSEQUENTIAL DAMAGES (INCLUDING, |
|||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
be defective. |
This warranty does not apply to any defects |
WITHOUT LIMITATION, ANY DAMAGES RESULTING FROM |
||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||
Ripple/noise |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
240 mVp-p or less |
|
resulting from any action of Buyer, including but not limited to |
LOSS OF USE, BUSINESS INTERRUPTION, LOSS OF |
||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
improper installation, improper interfacing, improper repair, |
INFORMATION, LOSS OR INACCURACY OF DATA, LOSS OF |
|||||||||||||||
Output capacity |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1.8 A |
|||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
unauthorized modification, misapplication and mishandling, such |
PROFITS, LOSS OF SAVINGS, THE COST OF PROCUREMENT |
||||||||||||||||||||
|
|
Ambient temperature |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
-10 to +55˚C (no freezing) |
|
as exposure |
to excessive current, heat, coldness, |
moisture, |
OF SUBSTITUTED GOODS, SERVICES OR TECHNOLOGIES, OR |
||||||||||||||||||||||||||||||||
Environment |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
vibration or outdoors air. Components which wear are not |
FOR ANY MATTER ARISING OUT OF OR IN CONNECTION |
||||||||||||||||||||||||||||||||||||
|
Ambient humidity |
|
|
|
|
|
|
|
|
|
|
|
|
35 to 85% RH (no condensation) |
|
warranted. |
|
|
WITH THE USE OR INABILITY TO USE THE PRODUCTS, EVEN |
|||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
(2) KEYENCE is pleased to offer suggestions on the use of its |
IF KEYENCE OR ONE OF ITS AFFILIATED ENTITIES WAS |
||||||||||||||||||||||||||||||||||||||
Pollution Degree |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2 |
|
|
various Products. They are only suggestions, and it is Buyer’s |
ADVISED OF A POSSIBLE THIRD PARTY’S CLAIM FOR |
||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
responsibility to ascertain the fitness of the Products for Buyer’s |
DAMEGES OR ANY OTHER CLAIM AGAINST BUYER. In some |
|||||||||||||||
Withstand voltage |
|
|
|
|
|
|
|
|
|
|
|
|
|
AC 1,500 V, 1 min. (between all external terminals and case) |
||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
intended use. KEYENCE will not be responsible for any damages |
jurisdictions, some of the foregoing warranty disclaimers or |
|||||||||||||||||||||||||||||||||||||||
Vibration resistance |
|
|
|
|
|
|
10 to 55 Hz, 0.7 mm compound amplitude, 20 sweeps each in X, Y, and Z directions |
|
that may result from the use of the Products. |
|
damage limitations may not apply. |
|
|
|
|
|||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
(3) The Products and any samples (“Products/Samples”) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||||||
Shock resistance |
|
|
|
|
|
|
|
100 m/s2 (about 10 G), 16 ms pulse, 1,000 iterations each in X, Y, and Z directions |
|
supplied to Buyer are not to be used internally in humans, for |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
human transportation, as safety devices or fail-safe systems, |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
Insulation resistance |
|
|
|
|
|
|
|
At least 50 MΩ |
(DC 500 V mega, between all external terminals and case) |
|
unless their written specifications state otherwise. Should any |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
Products/Samples be used in such a manner or misused in any |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
Power consumption |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
135VA |
|
way, KEYENCE assumes no responsibility, and additionally Buyer |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||
Instantaneous stop time |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
10 ms or less |
|
will indemnify KEYENCE and hold KEYENCE harmless from any |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
liability or damage whatsoever arising out of any misuse of the |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||
Weight (excluding dedicated brackets) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
About 240 g |
|
Products/Samples. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||
|
EMC |
|
|
|
|
|
|
|
|
|
|
|
|
|
EN61000-6-2, EN55011 Class A, FCC Part15B Class A |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||
Approved |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||
Standard |
|
Safety |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
EN60950, EN50178, UL60950, UL508 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
CAUTION
•Turn the power supply off before making any wire connections.
•Install the unit in a location that is not exposed to direct sunlight and that is characterized by an ambient temperature of -10 to +55˚C and by an ambient humidity of 35 to 85% RH. Avoid installation in locations prone to rapid temperature changes.
•Always connect the protective conductor terminal to the protective earthing line in your building or other facility.
•Use the power supply unit only inside a control board.
•Use the following crimp terminals, which are compatible with M4 terminal screws.
Max. 6.0 mm
Max. 6.0 mm
Copyright (c) 2002 KEYENCE CORPORATION. All rights reserved. 0932E 1094-3 96M0392
Printed in Japan