Product Bulletin
DVC2000 Digital Valve Controller
D103167X012
62.1:DVC2000
March 2014
Fisherr FIELDVUEt DVC2000 Digital Valve
Controller
The FIELDVUE DVC2000 digital valve controller is
simple to use, compact, and designed for easy
mounting. It converts a 4-20 mA input signal into a
pneumatic output signal, which feeds the control valve
actuator. Instrument setup is performed with a push
button and liquid crystal display (LCD) interface. This
interface is protected from the environment within a
sealed enclosure. The interface supports multiple
languages, available in two language pack options.
The DVC2000 uses a two-stage positioner design. The
pre-amplifier stage provides high static gain for
responsiveness to small changes in the input signal.
The power amplifier stage delivers the right volume of
air to the actuator, combining superior dynamic
performance with minimal steady-state air
consumption.
The high performance, linkage-less feedback system
eliminates physical contact between the valve stem
and the positioner. There is no wear of parts so cycle
life is maximized. Additionally, the elimination of
levers and linkages reduces the number of mounting
parts and the mounting complexity. Positioner
replacement and maintenance is simplified because
the feedback parts stay connected to the actuator
stem.
Designed to meet intrinsically safe and non-incendive
requirements, this instrument delivers scalable
functionality and high performance in a small package.
www.Fisher.com
W8755
Product Bulletin
62.1:DVC2000
March 2014
Specifications
Available Mountings
J Integral mounting to the Fisher GX Control Valve
and Actuator System
J Sliding-stem applications
J Quarter-turn rotary applications
DVC2000 digital valve controllers can also be
mounted on other actuators that comply with
IEC 60534-6-1, IEC 60534-6-2, VDI/VDE 3845 and
NAMUR mounting standards.
DVC2000 Digital Valve Controller
Air Consumption
Supply pressure
At 1.5 bar (22 psig)
At 4 bar (58 psig)
Air Capacity
Supply pressure
At 1.5 bar (22 psig)
(167 scfh)
At 4 bar (58 psig)
(2)
D103167X012
(2)
(3)
: 0.06 normal m3/h (2.3 scfh)
(4)
: 0.12 normal m3/h (4.4 scfh)
(3)
: 4.48 normal m3/h
(4)
: 9.06 normal m3/h (338 scfh)
Input Signal
Analog Input Signal: 4-20 mA DC, nominal; can be
configured for split range
Minimum Voltage: Voltage available at instrument
terminals must be 8.5 volts for analog control, 9.0
volts for HARTr communication
Maximum Voltage: 30 VDC
Minimum Control Current: 4.0 mA (below 3.5 mA
may cause microprocessor restart)
Overcurrent Protection: Input circuitry limits current
to prevent internal damage
Reverse Polarity Protection: No damage occurs from
reversal of loop current
Output Signal
Pneumatic signal as required by the actuator, up to
full supply pressure
Minimum Span: 0.5 bar (7 psig)
Maximum Span: 7 bar (101 psig)
Action: Single Acting, direct
Supply Pressure
(1)
Recommended: 0.5 bar (7 psig) greater than the
maximum actuator requirements
Maximum: 7 bar (101 psig)
Supply pressure must be clean, dry air or
noncorrosive, nonflammable gas that meets the
requirements of ISA Standard 7.0.01. A maximum 40
micrometer particle size in the air system is
acceptable. Further filtration down to 5 micrometer
particle size is recommended. Lubricant content is
not to exceed 1 ppm weight (w/w) or volume (v/v)
basis. Condensation in the air supply should be
minimized.
Temperature Limits
(1)
-40 to 85_C (-40 to 185_F). LCD may not be readable
below -20_C (-4_F).
Independent Linearity
±0.5% of output span
Electromagnetic Compatibility
Meets EN 61326-1 (First Edition)
Immunity—Industrial locations per Table 2 of
the EN 61326-1 standard. Performance is
shown in table 1 below
Emissions—Class A
ISM equipment rating: Group 1, Class A
Tested to NAMUR NE21 requirements
Vibration Testing Method
Tested per ANSI/ISA-75.13.01 Section 5.3.5. A
resonant frequency search is performed on all three
axes. The instrument is subjected to the ISA specified
1/2 hour endurance test at each major resonance,
plus an additional two million cycles.
Input Impedance
The input impedance of the DVC2000 active
electronic circuit is not purely resistive. For
comparison to resistive load specifications, an
equivalent impedance of 450 ohms may be used. This
value corresponds to 9 V @ 20 mA.
Electrical Classification
Hazardous Area:
CSA—Intrinsically Safe and Non-incendive
FM—Intrinsically Safe and Non-incendive
ATEX—Intrinsically Safe
IECEx—Intrinsically Safe
Refer to tables 2, 3, 4, and 5 for additional
information
Electrical Housing:
CSA—IP66, Type 4X
FM, ATEX, IECEx—IP66
-continued-
2
DVC2000 Digital Valve Controller
D103167X012
Specifications (continued)
Product Bulletin
62.1:DVC2000
March 2014
Other Classifications/Certifications
GOST‐R—Russian GOST‐R
INMETRO—National Institute of Metrology,
Shaft Rotation
Minimum: 45_
Maximum: 90_
Quality and Technology (Brazil)
KGS— Korea Gas Safety Corporation (South Korea)
NEPSI—National Supervision and Inspection Centre
for Explosion Protection and Safety of
Instrumentation (China)
Mounting
Designed for direct actuator mounting. For
weatherproof housing capability, the vent must be
positioned at the lowest point of the instrument.
PESO CCOE—Petroleum and Explosives Safety
Organisation - Chief Controller of Explosives (India)
RTN—Russian Rostekhnadzor
Contact your Emerson Process Management sales
office for classification/certification specific
information
Connections
Standard
Supply and Output Pressure: G1/4 internal
Electrical: M20 internal
Optional
Supply and Output Pressure: 1/4 NPT internal
Electrical: 1/2 NPT internal
Materials of Construction
Housing and Cover: A03600 low copper aluminum
alloy
Elastomers: nitrile, fluorosilicone
Stem Travel
Minimum: 6.35 mm (0.25 inch)
Maximum: 606 mm (23-7/8 inches)
1. The pressure/temperature limits in this document and any applicable standard or code limitation should not be exceeded. Note: Temperature limits vary based on hazardous area approval.
2. Normal m
3. Low pressure relay: 0 to 3.4 bar (0 to 50 psig).
4. High pressure relay: 3.5 to 7.0 bar (51 to 102 psig).
5. Typical values when calibrated at temperature.
3
/hour - Normal cubic meters per hour at 0_C and 1.01325 bar, absolute. Scfh - Standard cubic feet per hour at 60_F and 14.7 psia.
Weight
1.5 kg (3.3 lbs)
Dimensions
Refer to figure 3
Options
J Airset: Fisher 67CFR with filter
Language Packs:
J Standard: English, German,
French, Italian, Spanish, Japanese, Chinese,
Portuguese, Russian, Polish, and Czech
J Optional: English, German, French, Italian, Spanish,
Japanese, Chinese, and Arabic
J Pipe-away vent
J Limit Switches: Two isolated switches, configurable
throughout calibrated travel range
Supply Voltage: 5-30 VDC
OFF State: 0.5 to 1.0 mA
ON State: 3.5 to 4.5 mA (above 5 volts)
Reference Accuracy: 2% of travel span
J
Transmitter: 4-20 mA output, isolated
(5)
Supply Voltage: 8-30 VDC
Fault Indication: offrange high or low
Reference Accuracy: 1% of travel span
(5)
Features
n Simplicity—The DVC2000 is easy to use. If you are
mounting the instrument for the first time, the
linkage-less feedback system is easy to install. Once
a magnet array is assembled to the valve stem,
positioner replacement is simple since there are no
physically connected parts.
At its very basic functionality, the DVC2000 digital
valve controller has a local user interface that will
allow you to configure, calibrate, and tune the
instrument. If the I/O Options Package is installed,
you can calibrate the 4-20 mA transmitter and
configure the limit switch action. Running the Quick
Setup routine calibrates and tunes the instrument
specifically for that actuator.
The full text display in the local interface is easy to
navigate, in part due to the selection of languages.
Each unit can be configured to display English,
German, French, Italian, Spanish, Japanese or
Chinese. The standard language pack also includes
Portuguese, Russian, Polish, and Czech. An optional
language pack replaces these four languages with
Arabic.
3