1.

Quickstart.....................................................................................................

3

2.

Symbols............................................................................................................

4

3.

Intended use................................................................................................

4

4.

Basic Safety Instructions.............................................................

5

5.

General Information............................................................................

6

6.

Structure and function..................................................................

6

7.

Technical data............................................................................................

7

8.

Installation..................................................................................................

9

9.

Packaging, transport, storage.............................................

15

1.Quickstart

The operating instructions describe the entire life cycle of the device. Keep these instructions in a location which is easily accessible to every user and make these instructions available to every new owner of the device.

Important Safety Information!

Read Quickstart carefully and thoroughly. Study in particular the chapters entitled “Basic Safety Instructions” and “Intended use”.

• Quickstart must be read and understood.

Quickstart for globe control valve type 2301 explains, for example, how to install and start-up the device.

A detailed description of the device can be found in the operating instructions for Type 2301.

The operating instructions can be found on the Internet at: www.burkert.com

1.1. Definition of term / abbreviation

In these instructions, the term “device” always refers to the globe control valve type 2301.

The abbreviation “Ex” used in these instructions always stands for “explosion-protected”.

 

 

 

 

english

3

 

 

 

Type 2301

Symbols

2.Symbols

Danger!

Warns of an immediate danger!

Failure to observe the warning may result in a fatal or serious injury.

Warning!

Warns of a potentially dangerous situation!

Failure to observe the warning may result in serious injuries or death.

Caution!

Warns of a possible danger!

Failure to observe this warning may result in a moderately severe or minor injury.

Note!

Warns of material damage!

Important tips and recommendations.

Refers to information in these operating instructions or in other documentation.

→→designates a procedure which you must carry out.

3.Intended use

Non-intended use of the globe control valve type 2301 may be a hazard to people, nearby equipment and the environment.

The device is designed for the controlled flow of liquid and gaseous media. Operation is possible only in combination with a suitable control unit.

The admissible data, the operating conditions and conditions of use specified in the contract documents, operating instructions and on the type label are to be observed during use. These are described in the chapter entitled “Technical data”.

The device may be used only in conjunction with third-party devices and components recommended and authorised by Bürkert.

Correct transportation, correct storage and installation and careful use and maintenance are essential for reliable and faultless operation.

Use the device only as intended.

3.1. Restrictions

If exporting the system/device, observe any existing restrictions.

 

 

4

english

 

 

Type 2301

Basic Safety Instructions

4.Basic Safety Instructions

These safety instructions do not make allowance for any

contingencies and events which may arise during the installation, operation and maintenance of the devices.

local safety regulations; the operator is responsible for observing these regulations, also with reference to the installation personnel.

Danger!

Danger – high pressure!

Before loosening the lines and valves, turn off the pressure and vent the lines.

Risk of electric shock!

Before reaching into the device, switch off the power supply and secure to prevent reactivation!

Observe applicable accident prevention and safety regulations for electrical equipment!

Risk of burns!

The surface of the device may become hot during long-term operation.

• Do not touch the device with bare hands.

Risk of injury from moving parts in the device!

• Do not reach into openings.

Risk of injury when opening the actuator!

The actuator contains a tensioned spring. If the actuator is opened, there is a risk of injury from the spring jumping out.

• The actuator must not be opened.

General hazardous situations.

To prevent injury, ensure that:

In the potentially explosion-risk area the globe control valve type 2301 may be used only according to the specification on the separate Ex type label. For use observe the additional information enclosed with the device together with safety instructions for the explosion-risk area.

Devices without a separate Ex type label may not be used in a potentially explosive area.

The system cannot be activated unintentionally.

Installation and repair work may be carried out by authorised technicians only and with the appropriate tools.

After an interruption in the power supply or pneumatic supply, ensure that the process is restarted in a defined or controlled manner.

The device may be operated only when in perfect condition and in consideration of the operating instructions.

The general rules of technology apply to application planning and operation of the device.

To prevent damage to property of the device, ensure:

Supply the media connections only with those media which are specified as flow media in the chapter entitled “Technical data”.

Do not put any loads on the valve (e.g. by placing objects on it or standing on it).

Do not make any external modifications to the valves. Do not paint the body parts or screws.

 

 

 

 

english

5

 

 

 

Type 2301

General Information

5.General Information

5.1. Contact addresses

Germany

Bürkert Fluid Control Systems Sales Centre Christian-Bürkert-Str. 13-17 D-74653 Ingelfingen

Tel. + 49 (0) 7940 - 10 91 111

Fax + 49 (0) 7940 - 10 91 448 E-mail: info@de.buerkert.com

International

Contact addresses are found on the Internet under: www.burkert.com

6.Structure and function

The globe control valve Type 2301 can be operated only in combination with the following control units:

Positioner Type 8692, 8694, 8696 and 8792 Process controller Type 8693 and 8793

6.1. Structure

The valve seats are screwed in. A reduction in the orifices of the seats can be achieved by simply exchanging the threaded seats. The flow direction is always below seat.

6.2. Function

The seat of the valve is always closed against the medium flow. Spring force (CFA) or pneumatic pilot pressure (CFB and CFI) generates the closing force on the control cone. The force is transferred via a spindle which is connected to the actuator piston.

5.2. Warranty

The warranty is only valid if the device is used as authorized in accordance with the specified application conditions.

5.3. Information on the internet

The operating instructions and data sheets for Type 2301 can be found on the Internet at: www.burkert.com

6.2.1.Control functions (CF)

Warning!

For control function I – Danger if pilot pressure fails!

For control function I control and resetting occur pneumatically. If the pressure fails, no defined position is reached.

To ensure a controlled restart, first pressurize the device with pilot pressure, then switch on the medium.

A

A

Normally closed by spring action.

 

 

P

 

 

6

english

 

 

Type 2301

Technical data

B

 

 

 

A

 

 

 

 

 

 

Normally open by spring action.

 

 

 

 

 

 

 

 

 

 

 

 

P

 

I

 

 

 

A

 

 

 

 

 

 

Actuating function via reciprocal pressurization.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P

 

 

 

 

 

 

 

 

 

6.2.2.Flow direction below the seat

Depending on the version, the valve is closed against the medium flow with spring force (control function A, CFA) or with pilot pressure (control function B or I, CFB or CFI).

As the medium pressure is under the control cone, this pressure contributes to the opening of the valve.

Warning!

Medium may be discharged if minimum pilot pressure is too low or medium pressure too high!

If the minimum pilot pressure is too low for CFB and CFI or the permitted medium pressure is exceeded, leaks may occur.

Observe minimum pilot pressure.

Do not exceed medium pressure (see chapter “Pressure ranges”).

CFA

CFB / CFI

7.Technical data

7.1. Conformity

In accordance with the EC Declaration of conformity, Type 2301 ist compliant with the EC Directives.

7.2. Standards

The applied standards, which verify conformity with the EC Directives, can be found on the EC-Type Examination Certificate and / or the EC Declaration of Conformity.

7.3. Type label

 

 

 

 

 

 

 

Sealing material

 

 

 

 

 

Body material

 

 

Orifice of the seat /

 

 

 

 

 

 

 

 

 

Permitted medium pressure

 

 

 

 

 

 

 

actuator size

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Control function (CF)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Permitted pilot pressure

 

 

 

 

 

 

 

Type

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CE identification

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2301 A 25M PTFE VA

 

 

 

 

 

Pilot 5,5-7bar

 

 

 

 

 

 

 

 

 

 

Tmed -10°C - +185°C

 

 

 

 

Pmed 16,0bar

 

 

 

 

 

 

 

 

 

 

 

 

 

00189145

 

Flow

1

 

 

 

2

 

G1"

 

 

Kvs12,0 W3ZLT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Flow direction

 

 

 

 

 

 

 

 

 

Date of

Identification

 

 

 

 

 

 

 

 

 

number

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

manufacture

 

Permitted medium

Main dimensions of

Flow capacity in standard

 

 

 

 

 

temperature

 

 

line connection

production conditions

Fig. 1: Flow direction below the seat

(Rest open/closed, closing against medium)

 

 

 

 

english

7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Type 2301

 

 

 

 

 

 

 

 

 

 

Technical data

 

 

 

7.4. Operating conditions

7.4.2. Control medium

 

 

 

 

 

In conjunction with pneumatic control units (positioner and process

Observe permitted ranges on the type label of the device!

controllers), pilot air according to DIN ISO 8573-1 must be used:

• Class 3 (for water content)

7.4.1.Temperature ranges

Actuator

Actuator

Medium

 

 

 

 

size

Seat seal

Seat seal

Environment1)

material

[mm]

 

 

steel - steel

PTFE - steel

 

 

 

 

 

 

 

 

 

ø 50

 

 

 

0 ...

 

 

 

 

ø 70

PPS

-10 ...

-10 ...

+60 °C2)

ø 90

+185 °C

+130 °C

0 ...

 

ø 130

 

 

 

+100 °C3)

 

 

 

 

 

 

 

 

 

Tab. 1: Temperature ranges

 

 

1) If a pilot valve/control unit is used, the max. ambient temperature is +55 °C.

• Class 5 (for dust and oil content).

The specification is described in detail in the operating instructions of the respective positioner / process controller in the chapter entitled “Technical data”.

7.4.3.Pressure ranges

Maximum pilot pressure for valves without pneumatic control units

Actuator size (mm)

Actuator material

Max. permitted

pilot pressure4)

 

 

ø 50

 

 

ø 70

PPS

10 bar

ø 90

 

 

 

ø 130

 

7 bar

Tab. 2: Pilot pressure for valves without pneumatic control units

The globe control valve is suitable for steam sterilization.

2)Pilot air ports with push-in connector

3)Pilot air ports with threaded bushing

4) Observe the maximum pressure range according to the type label!

Minimum control pressure Pmin for control function A

Actuator size

50 / 70 / 90

130

130

[mm]

 

(Connection size

(Connection size

 

 

32 – 50 mm)

65 – 100 mm)

Pmin [bar]

5.5

5.5

5.6

Tab. 3: Minimum control pressure for CFA

 

 

8

english

 

 

Type 2301

Technical data

Pilot pressure for control function B

Actuator

Connection

Pilot pressure [bar]

Max. per-

for medium pressure

mitted medium

size [mm]

size [mm]

0 bar

 

max.

pressure [bar]

 

 

 

 

 

4 – 15

5.1

 

7.0

16

ø 50

20

5.1

 

7.0

9

 

25

5.1

 

7.0

5

 

4 – 15

5.2

 

6.2

16

ø 70

20

5.2

 

6.8

16

 

25

5.2

 

7.0

12

 

25

2.4

 

4.2

16

ø 90

32

2.5

 

5.3

16

40

2.5

 

6.5

16

 

 

 

50

2.5

 

7.0

14

 

32

2.7

 

4.0

16

 

40

2.7

 

4.5

16

ø 130

50

2.7

 

5.6

16

65

2.7

 

7.0

16

 

 

 

80

2.7

 

7.0

10

 

100

2.7

 

7.0

6

Tab. 4: Pilot pressure for control function B

The required minimum pilot pressure Pmin with control function B and I (flow below the seat) is dependent on the pressure of the medium.

The pressure diagrams are in the operating instructions on the Internet: www.burkert.com

7.5. General technical data

Media

 

Control medium

neutral gases, air

Flow media

Water, Alcohol, Fuel, Hydraulic liquids,

 

Saline solutions, Lyes, Organic solvents

Installation position

as required, preferably with actuator in

 

upright position

Protection class

IP67 in accordance with

 

IEC 529/EN 60529

Control functions (CF) The valve seat is always closed against the medium flow

Control function A Normally closed by spring action Control function B Normally open by spring action

Control function I Actuating function via reciprocal pressurization

8. Installation

8.1. Safety instructions

Danger!

Danger – high pressure in the equipment!

Before loosening the lines and valves, turn off the pressure and vent the lines.

 

 

 

 

english

9

 

 

 

Type 2301

Technical data

Warning!

Risk of injury from improper installation!

Installation may be carried out by authorised technicians only and with the appropriate tools!

Risk of injury from unintentional activation of the system and an uncontrolled restart!

Secure system from unintentional activation.

Following assembly, ensure a controlled restart.

For control function I – Danger if pilot pressure fails!

For control function I control and resetting occur pneumatically. If the pressure fails, no defined position is reached.

To ensure a controlled restart, first pressurize the device with pilot pressure, then switch on the medium.

Risk of injury from moving parts in the device!

• Do not reach into openings.

Devices with welded body

Remove the control unit from the actuator (if present): →→Clamp the valve body in a holding device. →→Loosen the fastening screws (2x).

→→Remove the control unit upwards.

Fastening

 

 

Control unit

screw (2x)

 

 

 

 

 

 

 

 

 

 

Actuator

 

 

 

Fig. 2: Disassembly the control unit

Remove the actuator from the valve body. →→Install collet (white grommet) in pilot air port 1.

8.2. Before installation

The globe control valve can be installed in any installation position, preferably with the actuator in upright position.

Before connecting the valve, ensure the pipelines are flush.

Make certain the flow direction is correct (Flow direction always below seat).

8.2.1.Preparatory work

→→Clean pipelines (Sealing material, swarf, etc.).

Note!

Damage to the seat seal or the seat contour!

When removing the actuator, ensure that the valve is in open position.

→→Control function A pressurize the pilot air port 1 (see “Fig. 3”) with compressed air (5 bar): valve opens.

→→Using a suitable open-end wrench, place the wrench flat on the pipe.

→→Unscrew the actuator from the valve body.

 

 

10

english

 

 

Type 2301

Technical data

Exhaust air port

 

 

 

 

 

Install collet:

CFA, CFB

2

 

 

 

 

 

 

Pilot air port CFI

1

 

 

 

 

 

 

 

 

 

 

 

 

Pilot air port

 

 

 

 

 

 

 

 

 

 

Actuator

CFA, CFB, CFI

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Nipple

Flats for open-end

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

wrench

 

 

 

 

 

 

 

Valve body

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fig. 3: Installation

Other device versions

→→Do not remove actuator unless this is a customer-specific requirement.

→→Procedure see “Devices with welded body”.

8.3. Installation

Dirt trap for devices with authorisation in accordance with DIN EN 161

In accordance with DIN EN 161 “Automatic shut-off valves for gas burners and gas appliances” a dirt trap must be connected upstream of the valve and prevent the insertion of a 1 mm plug gauge.

8.3.1. Installation of the valve body

Welded bodies

→→Weld valve body in pipeline system.

Other body versions

→→Connect body to pipeline.

8.3.2.Install actuator (welded body)

Graphite seal

Fig. 4: Graphite seal

→→Check the graphite seal and if required, replace it.

Warning!

Risk of injury from improper installation!

Assembly with unsuitable tools or non-observance of the tightening torque is dangerous as the device may be damaged.

For installation use an open-end wrench, never a pipe wrench.

Observe the tightening torque (see “Tab. 5”).

Warning!

Danger if incorrect lubricants used!

Unsuitable lubricant may contaminate the medium. In oxygen applications there is a risk of an explosion!

In specific applications, e.g. oxygen or analysis applications, use appropriately authorized lubricants only.

 

 

 

 

english

11

 

 

 

Type 2301

Technical data

→→Grease nipple thread before re-installing the actuator (e.g. with Klüber paste UH1 96-402 from Klüber).

Note!

Damage to the seat seal or the seat contour!

When installing the actuator, ensure that the valve is in open position.

→→Control function A pressurize the pilot air port 1 (see „Fig. 5“) with compressed air (5 bar): valve opens.

→→Screw actuator into the valve body. Observe tightening torque (see “Tab. 5”).

Tightening torques of valve body / nipples

DN

Tightening torque [Nm]

10/15

45 ±3

20

50 ±3

25

60 ±3

32/40

65 ±3

50

70 ±3

65

100 ±3

80

120 ±5

100

150 ±5

Tab. 5: Tightening torques of valve body / nipples

8.3.3.Install control unit

Before installation, check the position of the ports on the control unit and, if required, align the actuator.

Description see chapter “8.3.4. Rotating the actuator”.

→→Remove collet from pilot air port 1.

→→Check that the O-rings are correctly positioned in the pilot air ports.

→→Align the puck holder and the control unit until

1.the puck holder can be inserted into the guide rail of the control unit and

2.the supports of the control unit can be inserted into the pilot air ports of the actuator (see “Fig. 5”).

Note!

Damaged printed circuit board or malfunction!

• Ensure that the puck holder is situated flat on the guide rail.

Guide rail

Puck holder

Fig. 5: Aligning the puck holder

 

 

12

english

 

 

Burkert 2301 User Manual

Type 2301

Technical data

→→Push the control unit, without turning it, onto the actuator until no gap is visible on the form seal.

Note!

Too high torque when screwing in the fastening screw does not ensure protection class IP65 / IP67!

The fastening screws may be tightened to a maximum torque of 0.5 Nm only.

→→Attach the control unit to the actuator using the two side fastening screws. In doing so, tighten the screws only hand-tight (max. torque: 0.5 Nm).

Fastening screws

max. 0.5 Nm

Supports

Pilot air ports actuator

Fig. 6: Install control unit

8.3.4.Rotating the actuator

The position of the connections can be aligned steplessly by rotating the actuator through 360°.

Only the entire actuator can be rotated. The control unit cannot be rotated contrary to the actuator.

Note!

Damage to the seat seal or the seat contour!

When rotating the actuator, ensure that the valve is in open position.

Procedure:

→→Clamp the valve body in a holding device (applies only to valves which have not yet been installed).

→→Control function A:

Without unit control: pressurize the pilot air port 1 with compressed air (5 bar): valve opens.

With unit control: open the valve according to the operating instructions for the control unit.

→→Counter on the flats of the nipple with a suitable open-end wrench.

Warning!

Risk of injury from discharge of medium and pressure!

If the direction of rotation is wrong, the body interface may become detached.

Rotate the actuator module in the specified direction only

(see “Fig. 7”)!

→→Place suitable open-end wrench on the hexagon of the actuator.

 

 

 

 

english

13

 

 

 

Type 2301

Technical data

→→Rotate counter-clockwise (as seen from below) to bring the actuator into the required position.

Open-end wrench

Fig. 7: Rotating with open-end wrench

Risk of injury from unsuitable connection hoses!

Hoses which cannot withstand the pressure and temperature range may result in hazardous situations.

Use only hoses which are authorized for the indicated pressure and temperature range.

Observe the data sheet specifications from the hose manufacturers.

The pneumatic connection of the globe control valve can be carried out only in connection with the appropriate control unit.

Possible control units are:

Positioner Type 8692, 8694, 8696 and 8792 Process controller Type 8693 and 8793

8.4. Pneumatic connection

Danger!

Danger – high pressure in the equipment!

Before loosening the lines and valves, turn off the pressure and vent the lines.

Warning!

For control function I – Danger if pilot pressure fails!

For control function I control and resetting occur pneumatically. If the pressure fails, no defined position is reached.

To ensure a controlled restart, first pressurize the device with pilot pressure, then switch on the medium.

8.4.1.Connection of the control medium

→→Connect the control medium to the pilot air port (“Fig. 8”: 1) (3 – 7 bar; instrument air, free of oil, water and dust).

→→Fit the exhaust line or a silencer to the exhaust air port

(“Fig. 8”: 3) and, if available, to the additional exhaust air port (“Fig. 8”: 3.1).

If used in an aggressive environment, we recommend conveying all free pneumatic connections into a neutral atmosphere with the aid of a pneumatic hose.

 

 