Type 2301
2/2-way Globe Control Valve 2/2-Wege-Geradsitzregelventil
Vanne de réglage à siège droit 2/2 voies
Quickstart
English Deutsch Français
We reserve the right to make technical changes without notice. Technische Änderungen vorbehalten.
Sous réserve de modifications techniques.
© 2008-2013 Bürkert Werke GmbH
Operating Instructions 1308/01_EU-ML_00810302 / Original DE
Type 2301
Quickstart
1. |
Quickstart..................................................................................................... |
3 |
2. |
Symbols............................................................................................................ |
4 |
3. |
Intended use................................................................................................ |
4 |
4. |
Basic Safety Instructions............................................................. |
5 |
5. |
General Information............................................................................ |
6 |
6. |
Structure and function.................................................................. |
6 |
7. |
Technical data............................................................................................ |
7 |
8. |
Installation.................................................................................................. |
9 |
9. |
Packaging, transport, storage............................................. |
15 |
1.Quickstart
The operating instructions describe the entire life cycle of the device. Keep these instructions in a location which is easily accessible to every user and make these instructions available to every new owner of the device.
Important Safety Information!
Read Quickstart carefully and thoroughly. Study in particular the chapters entitled “Basic Safety Instructions” and “Intended use”.
• Quickstart must be read and understood.
Quickstart for globe control valve type 2301 explains, for example, how to install and start-up the device.
A detailed description of the device can be found in the operating instructions for Type 2301.
The operating instructions can be found on the Internet at: www.burkert.com
1.1. Definition of term / abbreviation
In these instructions, the term “device” always refers to the globe control valve type 2301.
The abbreviation “Ex” used in these instructions always stands for “explosion-protected”.
|
|
|
|
english |
3 |
|
|
|
Type 2301
Symbols
2.Symbols
Danger!
Warns of an immediate danger!
•Failure to observe the warning may result in a fatal or serious injury.
Warning!
Warns of a potentially dangerous situation!
•Failure to observe the warning may result in serious injuries or death.
Caution!
Warns of a possible danger!
•Failure to observe this warning may result in a moderately severe or minor injury.
Note!
Warns of material damage!
Important tips and recommendations.
Refers to information in these operating instructions or in other documentation.
→→designates a procedure which you must carry out.
3.Intended use
Non-intended use of the globe control valve type 2301 may be a hazard to people, nearby equipment and the environment.
•The device is designed for the controlled flow of liquid and gaseous media. Operation is possible only in combination with a suitable control unit.
•The admissible data, the operating conditions and conditions of use specified in the contract documents, operating instructions and on the type label are to be observed during use. These are described in the chapter entitled “Technical data”.
•The device may be used only in conjunction with third-party devices and components recommended and authorised by Bürkert.
•Correct transportation, correct storage and installation and careful use and maintenance are essential for reliable and faultless operation.
•Use the device only as intended.
3.1. Restrictions
If exporting the system/device, observe any existing restrictions.
|
|
4 |
english |
|
|
Type 2301
Basic Safety Instructions
4.Basic Safety Instructions
These safety instructions do not make allowance for any
•contingencies and events which may arise during the installation, operation and maintenance of the devices.
•local safety regulations; the operator is responsible for observing these regulations, also with reference to the installation personnel.
Danger!
Danger – high pressure!
•Before loosening the lines and valves, turn off the pressure and vent the lines.
Risk of electric shock!
•Before reaching into the device, switch off the power supply and secure to prevent reactivation!
•Observe applicable accident prevention and safety regulations for electrical equipment!
Risk of burns!
The surface of the device may become hot during long-term operation.
• Do not touch the device with bare hands.
Risk of injury from moving parts in the device!
• Do not reach into openings.
Risk of injury when opening the actuator!
The actuator contains a tensioned spring. If the actuator is opened, there is a risk of injury from the spring jumping out.
• The actuator must not be opened.
General hazardous situations.
To prevent injury, ensure that:
•In the potentially explosion-risk area the globe control valve type 2301 may be used only according to the specification on the separate Ex type label. For use observe the additional information enclosed with the device together with safety instructions for the explosion-risk area.
•Devices without a separate Ex type label may not be used in a potentially explosive area.
•The system cannot be activated unintentionally.
•Installation and repair work may be carried out by authorised technicians only and with the appropriate tools.
•After an interruption in the power supply or pneumatic supply, ensure that the process is restarted in a defined or controlled manner.
•The device may be operated only when in perfect condition and in consideration of the operating instructions.
•The general rules of technology apply to application planning and operation of the device.
To prevent damage to property of the device, ensure:
•Supply the media connections only with those media which are specified as flow media in the chapter entitled “Technical data”.
•Do not put any loads on the valve (e.g. by placing objects on it or standing on it).
•Do not make any external modifications to the valves. Do not paint the body parts or screws.
|
|
|
|
english |
5 |
|
|
|
Type 2301
General Information
5.General Information
5.1. Contact addresses
Germany
Bürkert Fluid Control Systems Sales Centre Christian-Bürkert-Str. 13-17 D-74653 Ingelfingen
Tel. + 49 (0) 7940 - 10 91 111
Fax + 49 (0) 7940 - 10 91 448 E-mail: info@de.buerkert.com
International
Contact addresses are found on the Internet under: www.burkert.com
6.Structure and function
The globe control valve Type 2301 can be operated only in combination with the following control units:
Positioner Type 8692, 8694, 8696 and 8792 Process controller Type 8693 and 8793
6.1. Structure
The valve seats are screwed in. A reduction in the orifices of the seats can be achieved by simply exchanging the threaded seats. The flow direction is always below seat.
6.2. Function
The seat of the valve is always closed against the medium flow. Spring force (CFA) or pneumatic pilot pressure (CFB and CFI) generates the closing force on the control cone. The force is transferred via a spindle which is connected to the actuator piston.
5.2. Warranty
The warranty is only valid if the device is used as authorized in accordance with the specified application conditions.
5.3. Information on the internet
The operating instructions and data sheets for Type 2301 can be found on the Internet at: www.burkert.com
6.2.1.Control functions (CF)
Warning!
For control function I – Danger if pilot pressure fails!
For control function I control and resetting occur pneumatically. If the pressure fails, no defined position is reached.
•To ensure a controlled restart, first pressurize the device with pilot pressure, then switch on the medium.
A |
A |
|
Normally closed by spring action. |
||
|
||
|
P |
|
|
6 |
english |
|
|
Type 2301
Technical data
B |
|
|
|
A |
|
||
|
|
|
|
|
Normally open by spring action. |
||
|
|
|
|
|
|
|
|
|
|
|
|
|
P |
|
|
I |
|
|
|
A |
|
||
|
|
|
|
|
Actuating function via reciprocal pressurization. |
||
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|
P |
|
||
|
|
|
|
|
|
|
|
6.2.2.Flow direction below the seat
Depending on the version, the valve is closed against the medium flow with spring force (control function A, CFA) or with pilot pressure (control function B or I, CFB or CFI).
As the medium pressure is under the control cone, this pressure contributes to the opening of the valve.
Warning!
Medium may be discharged if minimum pilot pressure is too low or medium pressure too high!
If the minimum pilot pressure is too low for CFB and CFI or the permitted medium pressure is exceeded, leaks may occur.
•Observe minimum pilot pressure.
•Do not exceed medium pressure (see chapter “Pressure ranges”).
CFA |
CFB / CFI |
7.Technical data
7.1. Conformity
In accordance with the EC Declaration of conformity, Type 2301 ist compliant with the EC Directives.
7.2. Standards
The applied standards, which verify conformity with the EC Directives, can be found on the EC-Type Examination Certificate and / or the EC Declaration of Conformity.
7.3. Type label
|
|
|
|
|
|
|
Sealing material |
|
|
|
|
|
Body material |
|||||||||||||||||
|
|
Orifice of the seat / |
|
|
|
|
|
|
|
|
|
Permitted medium pressure |
||||||||||||||||||
|
|
|
|
|
|
|
actuator size |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||
Control function (CF) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Permitted pilot pressure |
||||||||||||||
|
|
|
|
|
|
|
Type |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
CE identification |
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
2301 A 25M PTFE VA |
|
|
|
|
|
Pilot 5,5-7bar |
|
||||||||||||||
|
|
|
|
|
|
|
|
|
Tmed -10°C - +185°C |
|
|
|
|
Pmed 16,0bar |
||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||
00189145 |
|
Flow |
1 |
|
|
|
2 |
|
G1" |
|
|
Kvs12,0 W3ZLT |
||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||
Flow direction |
|
|
|
|
|
|
|
|
|
Date of |
||||||||||||||||||||
Identification |
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||
number |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
manufacture |
||||||||||
|
Permitted medium |
Main dimensions of |
Flow capacity in standard |
|||||||||||||||||||||||||||
|
|
|
|
|
temperature |
|
|
line connection |
production conditions |
Fig. 1: Flow direction below the seat
(Rest open/closed, closing against medium)
|
|
|
|
english |
7 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Type 2301 |
|
|
|
|
|
|
||
|
|
|
|
|
Technical data |
|
|
|
|
||||
7.4. Operating conditions |
7.4.2. Control medium |
|||||
|
|
|
|
|
In conjunction with pneumatic control units (positioner and process |
|
Observe permitted ranges on the type label of the device! |
controllers), pilot air according to DIN ISO 8573-1 must be used: |
• Class 3 (for water content)
7.4.1.Temperature ranges
Actuator |
Actuator |
Medium |
|
||
|
|
|
|||
size |
Seat seal |
Seat seal |
Environment1) |
||
material |
|||||
[mm] |
|
||||
|
steel - steel |
PTFE - steel |
|
||
|
|
|
|||
|
|
|
|
|
|
ø 50 |
|
|
|
0 ... |
|
|
|
|
|
||
ø 70 |
PPS |
-10 ... |
-10 ... |
+60 °C2) |
|
ø 90 |
+185 °C |
+130 °C |
0 ... |
||
|
|||||
ø 130 |
|
|
|
+100 °C3) |
|
|
|
|
|
||
|
|
|
|
|
|
Tab. 1: Temperature ranges |
|
|
1) If a pilot valve/control unit is used, the max. ambient temperature is +55 °C.
• Class 5 (for dust and oil content).
The specification is described in detail in the operating instructions of the respective positioner / process controller in the chapter entitled “Technical data”.
7.4.3.Pressure ranges
Maximum pilot pressure for valves without pneumatic control units
Actuator size (mm) |
Actuator material |
Max. permitted |
|
pilot pressure4) |
|||
|
|
||
ø 50 |
|
|
|
ø 70 |
PPS |
10 bar |
|
ø 90 |
|
||
|
|
||
ø 130 |
|
7 bar |
Tab. 2: Pilot pressure for valves without pneumatic control units
The globe control valve is suitable for steam sterilization.
2)Pilot air ports with push-in connector
3)Pilot air ports with threaded bushing
4) Observe the maximum pressure range according to the type label!
Minimum control pressure Pmin for control function A
Actuator size |
50 / 70 / 90 |
130 |
130 |
[mm] |
|
(Connection size |
(Connection size |
|
|
32 – 50 mm) |
65 – 100 mm) |
Pmin [bar] |
5.5 |
5.5 |
5.6 |
Tab. 3: Minimum control pressure for CFA
|
|
8 |
english |
|
|
Type 2301
Technical data
Pilot pressure for control function B
Actuator |
Connection |
Pilot pressure [bar] |
Max. per- |
||
for medium pressure |
mitted medium |
||||
size [mm] |
size [mm] |
0 bar |
|
max. |
pressure [bar] |
|
|||||
|
|
|
|||
|
4 – 15 |
5.1 |
|
7.0 |
16 |
ø 50 |
20 |
5.1 |
|
7.0 |
9 |
|
25 |
5.1 |
|
7.0 |
5 |
|
4 – 15 |
5.2 |
|
6.2 |
16 |
ø 70 |
20 |
5.2 |
|
6.8 |
16 |
|
25 |
5.2 |
|
7.0 |
12 |
|
25 |
2.4 |
|
4.2 |
16 |
ø 90 |
32 |
2.5 |
|
5.3 |
16 |
40 |
2.5 |
|
6.5 |
16 |
|
|
|
||||
|
50 |
2.5 |
|
7.0 |
14 |
|
32 |
2.7 |
|
4.0 |
16 |
|
40 |
2.7 |
|
4.5 |
16 |
ø 130 |
50 |
2.7 |
|
5.6 |
16 |
65 |
2.7 |
|
7.0 |
16 |
|
|
|
||||
|
80 |
2.7 |
|
7.0 |
10 |
|
100 |
2.7 |
|
7.0 |
6 |
Tab. 4: Pilot pressure for control function B
The required minimum pilot pressure Pmin with control function B and I (flow below the seat) is dependent on the pressure of the medium.
The pressure diagrams are in the operating instructions on the Internet: www.burkert.com
7.5. General technical data
Media |
|
Control medium |
neutral gases, air |
Flow media |
Water, Alcohol, Fuel, Hydraulic liquids, |
|
Saline solutions, Lyes, Organic solvents |
Installation position |
as required, preferably with actuator in |
|
upright position |
Protection class |
IP67 in accordance with |
|
IEC 529/EN 60529 |
Control functions (CF) The valve seat is always closed against the medium flow
Control function A Normally closed by spring action Control function B Normally open by spring action
Control function I Actuating function via reciprocal pressurization
8. Installation
8.1. Safety instructions
Danger!
Danger – high pressure in the equipment!
•Before loosening the lines and valves, turn off the pressure and vent the lines.
|
|
|
|
english |
9 |
|
|
|
Type 2301
Technical data
Warning!
Risk of injury from improper installation!
•Installation may be carried out by authorised technicians only and with the appropriate tools!
Risk of injury from unintentional activation of the system and an uncontrolled restart!
•Secure system from unintentional activation.
•Following assembly, ensure a controlled restart.
For control function I – Danger if pilot pressure fails!
For control function I control and resetting occur pneumatically. If the pressure fails, no defined position is reached.
•To ensure a controlled restart, first pressurize the device with pilot pressure, then switch on the medium.
Risk of injury from moving parts in the device!
• Do not reach into openings.
Devices with welded body
Remove the control unit from the actuator (if present): →→Clamp the valve body in a holding device. →→Loosen the fastening screws (2x).
→→Remove the control unit upwards.
Fastening |
|
|
Control unit |
screw (2x) |
|
|
|
|
|
||
|
|
|
|
|
|
|
Actuator |
|
|
|
Fig. 2: Disassembly the control unit
Remove the actuator from the valve body. →→Install collet (white grommet) in pilot air port 1.
8.2. Before installation
•The globe control valve can be installed in any installation position, preferably with the actuator in upright position.
•Before connecting the valve, ensure the pipelines are flush.
•Make certain the flow direction is correct (Flow direction always below seat).
8.2.1.Preparatory work
→→Clean pipelines (Sealing material, swarf, etc.).
Note!
Damage to the seat seal or the seat contour!
•When removing the actuator, ensure that the valve is in open position.
→→Control function A pressurize the pilot air port 1 (see “Fig. 3”) with compressed air (5 bar): valve opens.
→→Using a suitable open-end wrench, place the wrench flat on the pipe.
→→Unscrew the actuator from the valve body.
|
|
10 |
english |
|
|
Type 2301
Technical data
Exhaust air port |
|
|
|
|
|
Install collet: |
|
CFA, CFB |
2 |
|
|
|
|
|
|
Pilot air port CFI |
1 |
|
|
|
|
|
|
|
|
|
|
|
|
||
Pilot air port |
|
|
|
|
|
|
|
|
|
|
|
Actuator |
|||
CFA, CFB, CFI |
|
|
|
|
|
||
|
|
|
|
|
|||
|
|
|
|
|
Nipple |
||
Flats for open-end |
|
|
|
|
|
||
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
wrench |
|
|
|
|
|
|
|
Valve body |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Fig. 3: Installation
Other device versions
→→Do not remove actuator unless this is a customer-specific requirement.
→→Procedure see “Devices with welded body”.
8.3. Installation
Dirt trap for devices with authorisation in accordance with DIN EN 161
In accordance with DIN EN 161 “Automatic shut-off valves for gas burners and gas appliances” a dirt trap must be connected upstream of the valve and prevent the insertion of a 1 mm plug gauge.
8.3.1. Installation of the valve body
Welded bodies
→→Weld valve body in pipeline system.
Other body versions
→→Connect body to pipeline.
8.3.2.Install actuator (welded body)
Graphite seal
Fig. 4: Graphite seal
→→Check the graphite seal and if required, replace it.
Warning!
Risk of injury from improper installation!
Assembly with unsuitable tools or non-observance of the tightening torque is dangerous as the device may be damaged.
•For installation use an open-end wrench, never a pipe wrench.
•Observe the tightening torque (see “Tab. 5”).
Warning!
Danger if incorrect lubricants used!
Unsuitable lubricant may contaminate the medium. In oxygen applications there is a risk of an explosion!
•In specific applications, e.g. oxygen or analysis applications, use appropriately authorized lubricants only.
|
|
|
|
english |
11 |
|
|
|
Type 2301
Technical data
→→Grease nipple thread before re-installing the actuator (e.g. with Klüber paste UH1 96-402 from Klüber).
Note!
Damage to the seat seal or the seat contour!
•When installing the actuator, ensure that the valve is in open position.
→→Control function A pressurize the pilot air port 1 (see „Fig. 5“) with compressed air (5 bar): valve opens.
→→Screw actuator into the valve body. Observe tightening torque (see “Tab. 5”).
Tightening torques of valve body / nipples
DN |
Tightening torque [Nm] |
10/15 |
45 ±3 |
20 |
50 ±3 |
25 |
60 ±3 |
32/40 |
65 ±3 |
50 |
70 ±3 |
65 |
100 ±3 |
80 |
120 ±5 |
100 |
150 ±5 |
Tab. 5: Tightening torques of valve body / nipples
8.3.3.Install control unit
Before installation, check the position of the ports on the control unit and, if required, align the actuator.
Description see chapter “8.3.4. Rotating the actuator”.
→→Remove collet from pilot air port 1.
→→Check that the O-rings are correctly positioned in the pilot air ports.
→→Align the puck holder and the control unit until
1.the puck holder can be inserted into the guide rail of the control unit and
2.the supports of the control unit can be inserted into the pilot air ports of the actuator (see “Fig. 5”).
Note!
Damaged printed circuit board or malfunction!
• Ensure that the puck holder is situated flat on the guide rail.
Guide rail |
Puck holder |
Fig. 5: Aligning the puck holder
|
|
12 |
english |
|
|
Type 2301
Technical data
→→Push the control unit, without turning it, onto the actuator until no gap is visible on the form seal.
Note!
Too high torque when screwing in the fastening screw does not ensure protection class IP65 / IP67!
•The fastening screws may be tightened to a maximum torque of 0.5 Nm only.
→→Attach the control unit to the actuator using the two side fastening screws. In doing so, tighten the screws only hand-tight (max. torque: 0.5 Nm).
Fastening screws
max. 0.5 Nm
Supports
Pilot air ports actuator
Fig. 6: Install control unit
8.3.4.Rotating the actuator
The position of the connections can be aligned steplessly by rotating the actuator through 360°.
Only the entire actuator can be rotated. The control unit cannot be rotated contrary to the actuator.
Note!
Damage to the seat seal or the seat contour!
•When rotating the actuator, ensure that the valve is in open position.
Procedure:
→→Clamp the valve body in a holding device (applies only to valves which have not yet been installed).
→→Control function A:
Without unit control: pressurize the pilot air port 1 with compressed air (5 bar): valve opens.
With unit control: open the valve according to the operating instructions for the control unit.
→→Counter on the flats of the nipple with a suitable open-end wrench.
Warning!
Risk of injury from discharge of medium and pressure!
If the direction of rotation is wrong, the body interface may become detached.
•Rotate the actuator module in the specified direction only
(see “Fig. 7”)!
→→Place suitable open-end wrench on the hexagon of the actuator.
|
|
|
|
english |
13 |
|
|
|
Type 2301
Technical data
→→Rotate counter-clockwise (as seen from below) to bring the actuator into the required position.
Open-end wrench
Fig. 7: Rotating with open-end wrench
Risk of injury from unsuitable connection hoses!
Hoses which cannot withstand the pressure and temperature range may result in hazardous situations.
•Use only hoses which are authorized for the indicated pressure and temperature range.
•Observe the data sheet specifications from the hose manufacturers.
The pneumatic connection of the globe control valve can be carried out only in connection with the appropriate control unit.
Possible control units are:
Positioner Type 8692, 8694, 8696 and 8792 Process controller Type 8693 and 8793
8.4. Pneumatic connection
Danger!
Danger – high pressure in the equipment!
•Before loosening the lines and valves, turn off the pressure and vent the lines.
Warning!
For control function I – Danger if pilot pressure fails!
For control function I control and resetting occur pneumatically. If the pressure fails, no defined position is reached.
•To ensure a controlled restart, first pressurize the device with pilot pressure, then switch on the medium.
8.4.1.Connection of the control medium
→→Connect the control medium to the pilot air port (“Fig. 8”: 1) (3 – 7 bar; instrument air, free of oil, water and dust).
→→Fit the exhaust line or a silencer to the exhaust air port
(“Fig. 8”: 3) and, if available, to the additional exhaust air port (“Fig. 8”: 3.1).
If used in an aggressive environment, we recommend conveying all free pneumatic connections into a neutral atmosphere with the aid of a pneumatic hose.
|
|
14 |
english |
|
|