Bosch SV007, SV012, SV009, SV018, SV024 Installation, Operation And Maintenance Manual

...
4 (1)
Model SV - i Series Geothermal Heat Pump
SV007 Thru SV070
Installation, Operation and Maintenance Manual
Made in Florida
8 733 914 818 (2014/08)
2 | SV Heat PumpSeries
Model Nomenclature.......................................................... 3
General Description........................................................... 4
Moving and Storage...........................................................4
Initial Inspection................................................................5
Location............................................................................ 5
Water Quality ....................................................................6
Installation........................................................................ 7
Duct Flanges ...............................................................7
Mounting Vertical Units................................................. 7
Mounting Horizontal Units .............................................7
Hanging Bracket Kit.......................................................8
Converting Horizontal Supply Air Configuration .................. 9
Condensate Connections ................................................... 9
Duct System...................................................................... 9
Piping .............................................................................10
Electrical - High Voltage ...................................................11
Models with Dual Power Supplies.................................11
460 V Models with Constant Air Flow Motors .................11
Transformer Settings for 208/230 V Units ....................11
Constant CFM ECM Blower Motor......................................30
Unit Start Up................................................................... 31
Maintenance................................................................... 31
Unit Check Out Sheet................................................. 32
Troubleshooting.............................................................. 33
Temperature/Pressure Table ........................................... 38
Waterside Pressure Drop Table........................................ 44
Water Coil Volume......................................................44
Compressor Characteristics ............................................ 45
Corner Weights (HZ) ....................................................... 46
Wiring Diagrams ............................................................. 47
Dimensional Drawings..................................................... 54
Vertical .................................................................... 54
Horizontal ................................................................ 55
Counter-Flow............................................................ 56
Notes ............................................................................. 57
Electrical - Low Voltage ....................................................11
Unit Controls - UPM ......................................................... 12
ECM Interface Board .................................................. 12
Airflow selector..........................................................13
Dehumidification Method Selector ............................... 13
Sequence of Operation............................................... 14
General ....................................................................15
Cooling and Heating Modes .........................................15
UPM Safety Features..................................................15
Options...........................................................................19
Extended Range Option ..............................................19
Unit Mounted Non-Fused Disconnect Switch.................. 19
Hot Gas Reheat.......................................................... 19
DDC Controls ............................................................19
Internal 2-Way Water Valve ......................................... 19
Application Considerations ..............................................20
Boiler/Cooling Tower Systems .....................................20
Geothermal Closed Loop Systems................................21
Certified Performance Table ............................................ 22
Fan Motor Options ...........................................................23
Permanent Split Capacitor Motors (PSC).......................23
Constant Torque Motors (ECM).................................... 24
Constant Airflow Motors (ECM).................................... 26
Standard Blower Motor ....................................................28
Constant torque ECM blower Motor....................................29
SV Heat Pump Series8 733 914 818 (2014?08) Subject to change without prior notice
MODEL NOMENCLATURE
SV 018 - 1
VT
C - F L T P U A- XXSAMXXXX 5A X X
X
1XXX X
SV AIR FILTRATION
1 - STANDARD THROWAWAY FILTER w/
Size 2-SIDED FILTER RACK 1"
007
009
012
015
018
024
H - Hot Gas Reheat - On/Off
030 036
041 A - EMS relay
042
048 J - Disconnect Switch
060 N - Comfort Alert
07
T - Fault LED
X - As default for non used electrical codes
Voltage
1 208-230/60/1 Application
2 277/60/1 S - STANDARD RA NGE (Boiler/Tower)
3 208-230/60/3 G - EXTENDED RANGE (Geothermal)
4 460/60/3
Cabinet Construction
A - G90 Steel / 1/2" Standard 1.5LB Dual Density Fiberglass
C - G90 Steel / 1/2" Closed Cell Foam
Cabinet Configuration D - G90 Steel / 1/2" Standard 1.5LB
HZ - Horizontal Dual Density Fiberglass, Extra Quiet
VT - Vertical
F - G90 Steel / 1/2" Closed Cell Foam, Extra Quiet
CF - Downflow (Counterflow)
Electric Heat
X - None
Coax Options
A - Current
C - Copper
N - Cupro-Nickel
Air Coil
U - Uncoated
D - DuoGuard
Water Connections
F - Front Fan/Motor Options
P - Standard PSC
A - Constant Airflow ECM
T - Constant Torque ECM
Return Air Configuration
L - Left
R - Right S - Straight
B - Bottom
4 - MERV 8 - 2" w/ 4-SIDED FILTER RACK
5 - MERV13 - 2" w/ 4-SIDED FILTER RACK
X - None
Refrigeration Circuit Options
E - Pump/valve relay
General Electrical Options (up to 5 available per unit)
Model Nomenclature | 3Revised 08/14
T - Top
Revision Level
E - End
Discharge Air Configuration
8 733 914 818 (2014/08)SV Heat Pump Series
4 | General Description SV Heat PumpSeries
SAFETY CONSIDERATIONS GENERAL DESCRIPTION
WARNING: Installation and servicing of this
equipment can be hazardous due to system pressure and electrical components. Only trained and qualified personnel should install, repair, or service the equipment.
DANGER: Before performing service or maintenance operations on the system, turn off main power to the unit. Electrical shock could cause personal injury or death.
CAUTION: When working on equipment, always observe precautions described in the literature, tags, and labels attached to the unit. Follow all safety codes. Wear safety glasses and work gloves. Use a quenching cloth for brazing, and place a fire extinguisher close to the work area.
NOTE: To avoid the release of refrigerant into the atmosphere, the refrigerant circuit of this unit must be serviced only by technicians who meet local, state, and federal proficiency requirements.
NOTE: All refrigerant discharged from this unit must be recovered WITHOUT EXCEPTION. Technicians must follow industry accepted guidelines and all local, state, and federal statutes for the recovery and disposal of refrigerants. If a compressor is removed from this unit, refrigerant circuit oil will remain in the compressor. To avoid leakage of compressor oil, refrigerant lines of the compressor must be sealed after it is removed.
The SV series water-to-air heat pump provides an unmatched combination of performance, features and flexibility for both high performance new construction applications and replacement of existing water-to-air heat pumps. All units are certified by the Air conditioning, Heating and Refrigeration Institute (AHRI) to AHRI/ANSI/ ASHRAE/ISO standard 13256-1 for water-to-air and brine-to-air heat pumps at both Water Loop Heat Pump and Ground Loop Heat Pump application points.
All Water-to-Air Heat Pumps conform to UL 1995 standard and are certified to CAN/CSA C22.2 No 236 by Intertek-ETL.
These units meet all current applicable requirements of ASHRAE 90.1.
SV series units are designed to operate with entering fluid temperatures between 60°F and 100°F in cooling and 50°F and 80°F in heating with the base configuration. With the extended range option, SV series models can operate with entering fluid temperatures between 50°F and 110°F in cooling and between 20°F and 80°F in heating. SV units can accommodate a wide range of air temperatures, however, standard SV models should not be used for 100% outside air without consulting the factory applications group. 100% outside air routinely requires higher levels of dehumidification than is available from equipment designed for return air applications.
SV series units are available in three basic configurations: vertical top supply air (VT), horizontal end supply air or straight through supply air (HZ) and counter flow down supply air (CF). Each of these configurations are available with either left or right hand return air. HZ models can have the supply air field converted from end discharge air to straight through with no extra parts required.
NOTE: To avoid equipment damage, DO NOT use these units as a source of heating or cooling during the construction process. Doing so may affect the unit’s warranty. The mechanical components and filters will quickly become clogged with construction dirt and debris, which may cause system damage.
SV units are designed and rated for indoor installation only. SV units should not be installed in environments that fall below freezing or exceed 100°F ambient. SV cabinets are constructed of heavy gauge G-90 galvanized steel and will resist most common types of corrosion for the life of the equipment.
SV Heat Pump Series8 733 914 818 (2014?08) Subject to change without prior notice
Moving and Storage | 5Revised 08/14
SV series units are offered with a wide range of factory installed options including: PSC, constant torque ECM or constant air flow ECM fan motors, hot gas reheat, tin plated air coils, on board DDC controls, copper or cupro nickel water coils and more.
Some options are offered in limited sizes and/or voltages.
On board safety features will protect the major unit components from damage under most foreseeable installation and operation problems.
MOVING AND STORAGE
If the equipment is not needed for immediate installation upon arrival at the job site, it should be left in its packaging and stored in a clean, dry area. Units must be moved and stored in the normal upright position at all times.
Use caution to avoid damage to filter racks and duct flanges when storing or handling units.
NOTE: Never lift or move units by filter racks, external piping or attached options/ accessories.
NOTE: Never stack units when
transporting them.
NOTE: When storing units:
Do not stack units larger than 6 tons capacity!
Do not stack vertical or counter flow units under 6 tons capacity more than 2 high
Do not stack horizontal units 6 tons capacity more than 3 high
INITIAL INSPECTION
Be certain to inspect all cartons or crates on each unit as received at the job site before signing the freight bill. Verify that all items have been received and that there is no visible damage. Note any damage or shortage on all copies of the freight bill. In the event of damage or a shortage it is the responsibility of the purchaser to file the necessary claims with the carrier. Concealed damage not discovered until after removing the units from packaging must be reported to the carrier within 24 hours of receipt.
LOCATION
Locate the unit in an indoor area that allows easy access to the filter, front access panel and blower access panel, and has enough room for service personnel to perform maintenance and repair work. Provide sufficient room to make fluid, electrical and duct work connections.
Locate the unit in conditioned space and avoid installation in corrosive environments.
If the unit is installed in a confined space, such as a closet, provisions must be made for return air to freely enter the face of the unit’s air coil.
Unit condensate drains are not internally trapped. Allow room below the unit base for horizontal and counter flow models for an adequate condensate trap.
NOTE: Do not locate the unit above supply piping. Do not locate the unit in areas subject to freezing or in areas subject to temperature or humidity extremes.
NOTE: SV series packaged units are not approved for outdoor installation. Units must be installed in conditioned space that is not subject to extremes of temperature or humidity to avoid cabinet sweating and/or equipment damage.
NOTE: Do not use SV series units for temporary heating, air conditioning or ventilation during construction, especially when plastering, sanding or painting. Care should be taken to avoid introduction of dust, paint or debris into the air coil.
8 733 914 818 (2014/08)SV Heat Pump Series
6 | Water Quality Table SV Heat PumpSeries
WATER QUALITY TABLE
Table 1: Water Quality
POTENTIAL PROBLEM
SCALING
CORROSION
Water Characteristic Acceptable Value
Copper Cupro-Nickel
pH (Acidity/Alkalinity) 7-9 7-9
Hardness (CaCO3, MgCO3)
Ryznar Stability Index
Langelier Saturation Index -0.5 - +0.5 -0.5 - +0.5
Hydrogen Sulfide (H2S) < 0.5 ppm * 10-50 ppm
Sulfates
Chlorine
Chlorides
Carbon Dioxide
Ammonia
Ammonia Chloride
Ammonia Nitrate
Ammonia Hydroxide
< 350 ppm < 350 ppm
6.0 - 7.5 6.0 - 7.5
< 125 ppm < 125 ppm
< 0.5 ppm < 0.5 ppm
< 20 ppm < 150 ppm
< 50 ppm < 50 ppm
< 2 ppm < 2 ppm
< 0.5 ppm < 0.5 ppm
< 0.5 ppm < 0.5 ppm
< 0.5 ppm < 0.5 ppm
Ammonia Sulfate
Dissolved Solids
Iron (Fe2+ Iron Bacteria
IRON FOULING
EROSION
* No "rotten egg" smell present at < 0.5 ppm H2S.
** Equivalent to 30 mesh strainer
Potential)
Iron Oxide
Suspended Solids < 10 ppm, < 600 µm size ** < 10 ppm, < 600 µm size **
Maximum Water Velocity
WATER QUALITY
NOTE: Failure to insure proper water quality
and flow rates can shorten the life of the heat pump and potentially void the unit warranty.
Maintaining proper water quality is important for insuring a long and trouble free service life for an SV series heat pump.
< 0.5 ppm < 0.5 ppm
< 1,000 ppm < 1,500 ppm
< 0.2 ppm < 0.2 ppm
< 1 ppm < 1 ppm
6 ft/sec 6 ft/sec
For closed loop and boiler/tower systems water chemistry can be checked and easily maintained to insure that corrosive elements, dissolved oxygen and pH levels are kept in check. It is important to insure that any additive, antifreeze or corrosion inhibitor that is added to the water loop is compliant with all applicable laws and regulations and is compatible with copper, brass and bronze alloys. Insure that all recommended safety precautions are followed when handling or adding chemicals to the water loop.
SV Heat Pump Series8 733 914 818 (2014?08) Subject to change without prior notice
Installation | 7Revised 08/14
For open loop systems, water quality is very important. Table #1 shows acceptable ranges for a variety of water quality factors. The three main concerns in open loop installations are scaling, corrosion and fouling.
In installations with hard water, scaling due to a buildup of carbonates on the heat exchanger wall can gradually degrade the heat pump performance over time. Heat pumps that are affected by scaling may exhibit low suction pressures in heating and high head pressures in cooling with a gradual loss of capacity and efficiency. Scaled heat exchangers can be cleaned by a qualified technician but care should be taken to avoid scaling in the first place.
To limit scaling, water flow rates should be kept at 3 gallons/minute per nominal cooling ton (a 10°F temperature rise in cooling) and care should be taken to avoid air in the water lines from suction side leaks. Cupro-nickel coils are generally recommended.
In installations with high hydrogen sulfide, chlorine or ammonia, corrosion is a potential problem. In these installations a cupro-nickel heat exchanger is recommended along with maintaining proper flow and keeping air out of the system. If water quality is outside of the values in Table #1, then a closed loop is recommended.
Fouling due to iron bacteria can also pose problems in some open loop installations. Iron bacteria fouling can quickly degrade system performance and plug heat exchangers.
Air in the water system will greatly accelerate the fouling or corrosion process.
Mounting Vertical Units
SV Series vertical and counter flow units should be mounted level on a vibration absorbing pad slightly larger than the unit base in order to minimize vibration transmission from the unit to the building structure. See Figure #1. It is generally not necessary to anchor the unit unless required by local code.
All major service access for the SV Series vertical and counter flow models is from the front side of the unit. When installing the unit in a confined space such as a closet, insure that the service panel screws are accessible, that the filter can be replaced without damage and that water and electrical connections are accessible. For models with a unit mounted disconnect switch, make sure the switch can be easily seen and operated.
To reduce sound transmission, units should be installed using flexible electrical conduit and hose kits. Care should be taken to insure that no part of the unit cabinet is touching part of the building structure. For ducted return applications, a flexible duct connection should be used. Refer to Figure’s #14, #15 and #13.
INSTALLATION
The following are instructions to follow for installation of all SV Series components.
Duct Flanges
SV heat pumps feature fold-out return and supply air duct flanges. These fold-out flanges allow the heat pumps to more easily fit through doorways and other tight spaces, and also prevent damage in shipping and handling.
It is recommended that all fold-out flanges be folded-out once the heat pump is installed to insure that return and supply air flow is not obstructed. These flanges can be easily folded using standard or duckbill pliers. Once folded out these flanges can be used to support light duct work loads.
Vibration Mounting Pad
Figure # 1 Mounting Vertical Units
Mounting Horizontal Units
While horizontal units may be installed on any level surface strong enough to hold their weight, they are typically suspended above a ceiling by threaded rods. The rods are usually attached to the unit corners by hanger bracket kits (P/N 930-008).
8 733 914 818 (2014/08)SV Heat Pump Series
8 | Hanging Bracket Kit SV Heat PumpSeries
Units larger than six tons include an integral angle iron frame with mounting holes present. (See unit horizontal detail drawing).
Horizontal units installed above the ceiling must conform to all local codes. An auxiliary drain pan if required by code, should be at least four inches larger than the bottom of the heat pump.
Plumbing connected to the heat pump must not come in direct contact with joists, trusses, walls, etc. Some applications require an attic floor installation of the horizontal unit. In this case the unit should be set in a full size secondary drain pan on top of a vibration absorbing mesh.
The secondary drain pan prevents possible condensate overflow or water leakage damage to the ceiling. The secondary drain pan is usually placed on a plywood base isolated from the ceiling joists by additional layers of vibration absorbing mesh. In both cases, a 3/4" drain connected to this secondary pan should be run to an eave at a location that will be noticeable.
NOTE: If the unit is located in a crawl space, the bottom of the unit must be at least 4" above grade to prevent flooding of the electrical parts due to heavy rains.
HANGING BRACKET KIT
Installation Instructions
All horizontal units come with Hanging Bracket kit to facilitate suspended unit mounting using threaded rod. Hanging Brackets are to be installed as shown in figure # 2
(10) Bolts 1/4-28x1/2” Hex Bolt ( not used on this model)
The following are needed and are to be field provided:
Threaded rod (3/8” max dia) Hex Nuts Washers (1-3/4” min O.D.)
1. Remove and discard factory provided screws from location where Hanging Brackets will be installed shown in Figure#3
Figure # 3
2. Mount 5 brackets to unit corner post using the bolts provided in the kit as shown on Figure # 4
WARNING: Do not re-use screws removed from the unit on step 1 to mount the hanging Brackets to the unit.
Figure # 2
This kit includes the following: (5) Brackets. (5) Rubber Vibrators Isolators. (8) Screws # 10x1/2”
Figure # 4
WARNING: Follow all applicable codes
requirements when hanging this unit.
Selecting threaded rod material, etc.
3. Install Rubber Grommet on the Bracket as shown in Figure#5
SV Heat Pump Series8 733 914 818 (2014?08) Subject to change without prior notice
Converting Horizontal Supply Air Configuration | 9Revised 08/14
4. Hang the unit and assemble the field provided Thread Rod, Nuts and washers on to the Brackets as shown in Figure#5
CAUTION: Rods must be securely anchored to the ceiling.
CONVERTING HORIZONTAL SUPPLY AIR CONFIGURATION
The supply air location on SV Series Horizontal units can be quickly field converted from end blow to straight through or vice-versa. To convert the supply air direction, follow the steps below:
1. If connected to power, shut off the unit and disconnect switch or circuit breaker.
2. Unscrew and remove the blower access panel.
3. Disconnect the wires from the unit electrical box to the blower motor. Note which speed taps are wired for units with PSC or constant torque motors.
4. Unscrew and carefully remove the blower panel with the blower and motor attached. Be careful not to damage the refrigerant coils or any other internal unit components.
5. Remove the blower support brackets from the bottom of the blower housing and relocate them to the top of the blower housing.
6. Turn the blower panel 180° so that the blower support brackets are now at the bottom of the blower.
7. Insert the blower panel with the blower and motor into the desired location. Be careful not to damage the refrigerant coils or any other internal unit components. Screw the panel into place.
8. Replace the wires between the blower motor and electrical box. Make sure to connect wires to the proper speed taps.
9. Replace the blower access panel.
10. Reconnect power to the unit.
CONDENSATE CONNECTIONS
A drain line must be connected to the heat pump and pitched away from the unit a minimum of 1/8” per foot to allow the condensate to flow away from the unit. This connection must be in conformance with local plumbing codes. A trap must be installed in the condensate line to insure free condensate flow. (Heat Pumps are not internally trapped). A vertical air vent is sometimes required to avoid
air pockets.(See Figure #6).
Figure # 5 Condensate Drain
The depth of the trap depends on the amount of positive or negative pressure on the drain pan. A second trap must not be included.
The horizontal unit should be pitched approximately 1/4” towards the drain in both directions, to facilitate condensate removal. (See Figure #6)
Figure # 6 Pitched Unit
DUCT SYSTEM
All SV Series models are provided with a return air duct flange and supply air duct connections.
Refer to unit Dimensional Drawings for physical dimensions of the collar and flange. (Pg#50)
8 733 914 818 (2014/08)SV Heat Pump Series
10 | Piping SV Heat PumpSeries
A flexible connector is recommended for supply and return air duct connections on metal duct systems. All metal ducting should be insulated with a minimum of 1” (one inch) duct insulation to avoid heat loss or gain and prevent condensate from forming during the cooling operation. Application of the unit to no insulated duct work is not recommended as the unit’s performance will be adversely affected.
NOTE: Do not connect discharge ducts directly to the blower outlet.
The factory filter rack should be left in place on a free return system.
If the unit will be installed in a new installation with new duct work, the installation should be designed using current ASHRAE procedures for duct sizing. If the unit will be connected to an existing duct system, a check should be made to assure that the duct system has the capacity to handle the air required for the unit application. If the duct system is too small, larger duct work must be installed. Be certain to check for existing leaks and repair.
The duct system and all diffusers should be sized to handle the designed air flow quietly. To maximize sound attenuation of the unit blower, the supply and return air plenums should be insulated. There should be no direct straight air path through the air grill into the heat pump. The return air inlet to the heat pump must have at least one 90° turn away from the space return air grill. If air noise or excessive air flow are a problem, the blower speed can be changed to a lower speed to reduce air flow.
In conditions anticipating moderate scale formation or in brackish water a cupro-nickel heat exchanger is recommended. Both the supply and discharge water lines will sweat if subjected to low water temperature. These lines should be insulated to prevent damage from condensation.
All manual flow valves used in the system must be ball valves. Globe and gate valves must not be used due to high pressure drop and poor throttling characteristics. Always check carefully for water leaks and repair appropriately. Units are equipped with female pipe thread fittings. Consult the specification sheets for sizes.
Teflon tape sealer should be used when connecting water piping connections to the units to insure against leaks and possible heat exchanger fouling. Do not overtighten the connections. Flexible hoses should be used between the unit and the rigid system to avoid possible vibration. Ball valves should be installed in the supply and return lines for unit isolation and unit water flow balancing.
Pressure/temperature ports are recommended in both the supply and return lines for system flow balancing. The water flow can be accurately set by measuring the water-to- refrigerant heat exchangers water side pressure drop. See the unit specification sheets for the water flow and pressure drop information.
NOTE: Water piping exposed to extreme, low ambient temperatures is subject to freezing
PIPING
Supply and return piping must be as large as the unit connections on the heat pump (larger on long runs). Never use flexible hoses of a smaller inside diameter than that of the water connections on the unit. SV Units are supplied with either a copper or optional cupro-nickel condenser. Copper is adequate for ground water that is not high in mineral content. Refer to Table #1.
Should your well driller express concern regarding the quality of the well water available or should any known hazards exist in your area, we recommend proper testing to assure the well water quality is suitable for use with water source equipment. (Refer to Table #1)
NOTE: Never exceed the recommended water flow rates. Serious damage or erosion of the water to refrigerant heat exchanger could occur.
SV Heat Pump Series8 733 914 818 (2014?08) Subject to change without prior notice
Electrical - High Voltage | 11Revised 08/14
ELECTRICAL - HIGH VOLTAGE
All field installed wiring must comply with the National Electric Code as well as all applicable local codes. Refer to the unit electrical data on the unit name plate for wire and branch circuit protection sizing. Supply power voltage and phasing should match the required voltage and phasing shown on the unit name plate. Operating the unit below the minimum voltage, above the maximum voltage or with incorrect phasing can result in poor system performance or damage to the heat pump. All field wiring should be installed by qualified and trained personnel. Refer to the unit wiring diagram for field connection requirements.
NOTE: All power connections must be properly torque to avoid the risk of overheating.
Power wiring to the heat pump should be enclosed in flexible conduit to minimize the transmission of vibration from the unit cabinet to the building.
For heat pumps with unit mounted disconnect switches, field power should be connected to the marked terminals on the disconnect switch. For heat pumps without unit mounted disconnect switches (except for 460 volt units noted below and units with dual power supply), power is connected to the line (L) side of the compressor contactor and the ground lug in the unit electrical box.
Models with Dual Power Supplies
For models with dual power supplies, one power supply feeds the compressor and a second power supply feeds the unit fan motor and control circuit. The compressor power supply should be connected to the line (L) side of the compressor contactor. The fan motor and control circuit power supply should be connected to a provided terminal block. Care should be taken to insure that each power supply meets the voltage, amperage and phase requirements of its load. Refer to the unit nameplates for requirements.
460 V Models with Constant Air Flow Motors (SV015-SV070)
460 volt SV heat pumps with the constant airflow motor option require a properly sized neutral wire with the power supply wiring in addition to the three high voltage wires and the ground wire. These units employ a 265 V motor that requires power from one phase of the 460 V supply and the neutral wire.
WARNING: The power supply ground wire should never be used as a neutral wire.
For 460 V models with constant air flow motors and a unit mounted disconnect switch, the power wires and neutral wire should be connected to the appropriate terminals on the disconnect switch and its enclosure. For units without a disconnect switch, power and neutral wires should be connected to a provided 4 pole terminal block in the unit electrical box
Transformer Settings for 208/230 V Units
As factory built, all 208/230 V units are wired for 230 V operation. For job sites with a 208 V power supply, the primary leads on the unit transformer will need to be changed from 240 V to 208 V. Refer to the unit wiring diagram for details.
ELECTRICAL - LOW VOLTAGE
For heat pumps with PSC or constant torque fan motors, all thermostat wiring is connected to a terminal block located in the unit electrical box. For heat pumps with a constant air flow fan motor, thermostat wiring is connected to a removable terminal strip located on the ECM motor control board located in the electrical box. Refer to the unit wiring diagram for connection details.
WARNING: Never route control wiring through the same conduit as power supply wiring.
Unless provided with DDC controls, the SV heat pump can be controlled by most commonly available single stage heat pump thermostats. Note that the reversing valve on the SV series is energized when the unit is in the cooling mode. Thermostats should be located on an interior wall away from supply ducts. Avoid locations subject to direct sunlight or drafts, or external walls. Thermostat wiring should be 18 AWG. Refer to the installation instructions for the thermostat for further details.
Exceptionally long runs of thermostat wire should be avoided to prevent voltage drops in the control circuit.
SV heat pumps are supplied with a 75 VA control transformer as standard. The VA capacity of the transformer should be considered when connecting low voltage accessories to the heat pump such as thermostats or solenoid valves.
8 733 914 818 (2014/08)SV Heat Pump Series
12 | Unit Controls - UPM SV Heat PumpSeries
Table #2 shows the VA draw of factory mounted components in the SV heat pump. The total VA draw of the heat pump internal components plus any attached accessories must be lower than the VA capacity of the unit control transformer.
NOTE: Exceeding the transformer capacity can result in low control voltage, erratic unit operation or damage to the heat pump.
Table 2: Low Voltage VA Draw
Standard
Hot Gas Reheat
Construction
Component
Blower Relay (PSC motors only)
Reversing Valve Solenoid
Compressor Contactor
VA
6-7
8-9
6-8
Component
Total from ‘Standard’
Additional Control Relays
Hot Gas Reheat Solenoid
VA
22-26
12-14
8-9
10
8
9
7
1
546
Figure # 7
[1] Motor harness plug [2] Blower CFM adjustment [3] Motor settings [4] Dehumidification indication [5] Thermostat contact inputs [6] CFM count indicator [7] Thermostat input status indication [8] Reheat digital outputs [9] Thermostat outputs [10] 24 VAC [11] Dehumidification method selector
3
11
UPM board
Total VA draw
2
22-26
Total VA draw
42-49
UNIT CONTROLS - UPM
ECM Interface Board
Thermostat wiring is connected to the 10 pin screw type terminal block on the lower center portion of the ECM Interface Board (Refer to Figure #7, item [5]). In addition to providing a connecting point for thermostat wiring, the interface board also translates thermostat inputs into control commands for the Electronic Commutated Motor (ECM) DC fan motor and displays an LED indication of operating status. The thermostat connections and their functions are as Follows.
CFM LED indication is an approximation. Utilize conventional Test and Balance equipment for accurate airflow measurement.
CFM Count Indicator (Figure #7, Item [5]) blinks to indicate approximate airflow in CFM and may flicker when unit is off. Each blink of the LED represents approximately 100 CFM of air delivery, for example, if the LED blinks 12 times, pauses, blinks 12 times, etc. the blower is delivering approximately 1200 CFM.
Thermostat Options
Y1 First Stage Compressor Operation
G Fan
O Reversing Valve (energized in cooling)
W1 Auxiliary Electric Heat (runs in
conjunction with compressor)
NC Transformer 24 VAC Common (extra
connection)
SV Heat Pump Series8 733 914 818 (2014?08) Subject to change without prior notice
Unit Controls - UPM | 13Revised 08/14
Thermostat Options
Y1 First Stage Compressor Operation
C1 Transformer 24 VAC Common (primary
connection)
R Transformer 24 VAC Hot
H Dehumidification Mode
Airflow Selector
The airflow selector (Figure #7, items [2] & [3]) allows airflow adjustment to meet application requirements and to ease troubleshooting.
Only one switch can be enabled at a time. Refer to Figure #9 for each airflow setting.
NOTE: CFM Selector (FIg #7, Item [2]) must remain with only “A” being enabled.
ADJUST Selector can be adjusted to NOM, (+), (-), or TEST. NOM, (+) and (-) can be adjusted as needed by application. TEST is used for troubleshooting to override unit airflow to 100%
NOTE: Always disconnect power before changing jumper positions on the interface board and reset the unit afterward.
Dehumidification Method Selector
Dehumidification method selector (Figure #7, item [11]) is used to select between the following two methods:
1. Units equipped with optional Hot Gas Reheat, on dehumidification call (the “H” terminal on the thermostat is energized) the reheat outputs will energize the hot gas reheat valve in the circuit and the heat pump will start in dehumidification mode. Dehumidification selector (Figure #7, item [11]) should be selected to ‘YES’.
2. Units without optional Hot Gas Reheat, on dehumidification call, the heat pump fan will operate at a lower speed to increase dehumidification while cooling. Dehumidification selector ((Figure #7, item [11]) should be selected to ‘NO’.
In this mode, the heat pump will only dehumidify the space when it is running in cooling mode.
Figure # 8
NOTE: Do not set the ADJ DIP switch to the
(-) setting when electric heaters are installed. Doing so may cause the heaters to cycle on their thermal overload switches, potentially shortening the life of the switches.
3. To the left of the red and green status LED’s is a row of 1/4” male quick connects. These are used to pass thermostat inputs on to the rest of the control circuit. Remember to always turn off unit power at the circuit breaker before attaching or disconnecting any wiring from these connections to avoid accidental short circuits that can damage unit control components.
Dehumidification indicator LED (Figure #7, item [4]) will energize when dehumidification call is present. Refer to Figure #9.
The other DIP switch bank is used to select the proper program in the ECM motor for the unit.
Figure # 9
8 733 914 818 (2014/08)SV Heat Pump Series
14 | Unit Controls - UPM SV Heat PumpSeries
Sequence of Operation
START
YES
Y1 = ON
NO
RESET ON
Y
NO
RESET ON R
R = 24VAC
YES
POWER/ SWITCHES/SENSOR
STATUS CHECK
V > 18VAC
NO
YES
HPC =
CLOSED
NO
YES
LPC
=CLOSED
NO
YES
FRZ >TEMP
LIMIT
NO
START TIMER
START TIMER
YES
CLEAR FAULTS
TIME > 120
NO
TIME > 30
BLINK CODE ON STATUS LED
SOFT LOCKOUT
RECORD ALARM
START COUNTER (IF APPLICABLE)
LOCKOUT CAN BE SET
TO 4 VIA DIP SWITCH
BLINK CODE
SEC
SEC
YES
ON STATUS LED
YES
NO
COUNTER NEEDED?
YES
COUNT = 2
OR
COUNT = 4
NO
YES
NO
HARD
LOCKOUT?
YES
BLINK CODE ON STATUS LED
DISPLAY OUTPUT = PULSE
ALR OUTPUT = ON/PULSE
NO
YES
CON > 0
YES
INITIAL
POWER UP
YES
NO
NO
NO
START
ANTI SHORT CYCLE
START
RANDOM START UP
NO
T > ASC OR
RS SEC
CC OUTPUT = OFF
YES
CC
CC OUTPUT = ON
LEGEND: HPC - HIGH PRESSURE CUTOUT LPC - LOW PRESSURE CUTOUT FRZ - FREEZE PROTECTION CONDITION CON - CONDENSATE OVERFLOW CONDITION CC - COMPRESSOR COIL ASC - ANTI SHORT CYCLE RS - RANDDOM START
SV Heat Pump Series8 733 914 818 (2014?08) Subject to change without prior notice
Unit Controls - UPM | 15Revised 08/14
General
SV series heat pumps are designed to be controlled by a standard 1 heat / 1 cool heat pump thermostat. The heat pump control circuit operates on 24 VAC control voltage regardless of the unit supply voltage. If direct digital control is required then the heat pump needs to be supplied with a DDC control option.
Fan operation is controlled by the “G” terminal on the heat pump thermostat terminal block. When “G” is energized the unit fan motor will start operating. For heat pumps with PSC motors, the fan will immediately ramp up to 100% air flow. For heat pumps with constant torque ECM motors, the fan will ramp up to 100% air flow over a 30 second period. For heat pumps with constant air flow ECM motors the fan will ramp up to 70% air flow over a 30 second period if there is no call for compressor operation (“Y”). If there is a call for compressor operation along with a call for fan operation, then the fan will ramp to 100% air flow.
Compressor operation is controlled by the “Y” terminal on the heat pump thermostat terminal block. When “Y” is energized, a signal to start the compressor is sent to the Unit Protection Module (UPM). The UPM checks a number of safety features before then starting the compressor. If any of the safety features connected to the UPM is in a fault condition, the UPM will not start the compressor and will flash a fault code on the red status LED indicating the nature of the fault.
Additionally the UPM will delay compressor operation randomly on initial start up (random start delay) and will prevent the compressor from restarting with less than 5 minutes of off time (anti short cycle delay). Once all faults are cleared and the time delays are satisfied, the UPM will energize the compressor. The compressor will operate as long as the thermostat calls for “Y” and there are no faults. Refer to the troubleshooting chart for fault diagnostics.
Cooling and Heating Modes
SV series heat pumps operate in cooling with the reversing valve energized. When the “O” terminal is energized, the heat pump will be in the cooling mode, however, will not be actively cooling until the “Y” and “G” terminals are also energized. If the “Y” and “G” terminals are energized without the “O” terminal, then the heat pump will operate in the heating mode.
UPM Safety Features
11
1213
1
2
3
4
5
17
6
[1] Board Power Indicator [2] UPM Status LED Indicator [3] Water Coil Freeze Protection Temperature
Selection [4] Air Coil Freeze Protection Temperature
Selection [5] UPM Board Settings [6] Water Coil Freeze Connection [7] Air Coil Freeze Connection [8] LED Unit Display Connection [9] 24VAC Power Input [10] Compressor Contact Output [11] High Pressure Switch Connection [12] Call for Compressor Y1 [13] Low Pressure Switch Connection [14] 24VAC Power Common [15] Condensate Overflow Sensor [16] Dry Contact [17] UPM Ground Standoff
If the unit is being connected to a thermostat with a malfunction light, this connection is made at the unit malfunction output or relay.
If the thermostat is provided with a malfunction light powered off of the common (C) side of the transformer, a jumper between “R” and “COM” terminal of “ALR” contacts must be made.
15
14
7
Figure # 10
8
16
9
10
8 733 914 818 (2014/08)SV Heat Pump Series
16 | Unit Controls - UPM SV Heat PumpSeries
If the thermostat is provided with a malfunction light powered off of the hot (R) side of the transformer, then the thermostat malfunction light connection should be connected directly to the (ALR) contact on the unit’s UPM board.
Each unit is factory provided with a Unit Protection Module (UPM) that controls the compressor
operation and monitors the safety controls that protect the unit.
Safety controls include the following:
High pressure switch located in the refrigerant discharge line and wired across the HPC terminals on the UPM
Low pressure switch located in the unit refrigerant suction line and wired across terminals LPC1 and LPC2 on the UPM.
UPM Board Dry Contacts are Normally Open (NO)
Water side freeze protection sensor, mounted close to condensing water coil, monitors refrigerant temperature between condensing water coil and expansion valve or capillary tube. If temperature drops below or remains at freeze limit trip for 30 seconds, the controller will shut down the compressor and enter into a soft lockout condition. The default freeze limit trip is 26°F, however this can be changed to 15°F by cutting the R30 or Freeze1 resistor located on top of DIP switch SW1.
Evaporator freeze protection sensor, mounted after the thermal expansion device and the evaporator, monitors refrigerant temperature between the evaporator coil and thermal expansion valve. If temperature drops below or remains at freeze limit trip for 30 seconds, the controller will shut down the compressor and enter into a soft lockout condition. The default freeze limit trip is 26°F. (Figures #11 and #12)
Figure # 12
The condensate overflow protection sensor is located in the drain pan of the unit and connected to the ‘COND’ terminal on the UPM board. (Figure #13)
NOTE: If unit is employing a fresh water system (no anti-freeze protection), it is extremely important to have the Freeze1 R30 resistor set to 26°F in order to shut down the unit at the appropriate leaving water temperature and protect your heat pump from freezing if a freeze sensor is included.
Figure # 11
Figure # 13
SV Heat Pump Series8 733 914 818 (2014?08) Subject to change without prior notice
Unit Controls - UPM | 17Revised 08/14
UPM Board Factory Default Settings
TEMP
LOCKOUT
RESET
ALARM
TEST
26°F
2
Y
PULSE
NO
UPM DIP SWITCH DEFAULT POSITION
lockout 42
reset
alarm
test
Table 3: UPM Fault Blink Codes
LED Blinks Fault Fault Criteria
None None
1 High Pressure
2 Low Pressure
Water Coil
Freeze
3
4
5
6 Brown Out
Condition
Condensate
Overflow
Air Coil Freeze
Condition
RY
Cont pulse
yes no
All fault conditions
nominal
Refrigerant discharge
pressure has
exceeded 600 PSIG
Refrigerant suction pressure has fallen
below 40 PSIG
Refrigerant
temperature to the
water coil has fallen
below 30°F for 30
seconds
Condensate levels in
the unit drain pan are
too high
Refrigerant
temperature to the air
coil has fallen below
30°F for 30 seconds
Control voltage has
fallen below 18 VAC
RANDOM START: Each controller has an unique
random start delay ranging from 270 to 300 seconds on initial power up to reduce the chance of multiple unit simultaneously starting at the same time after power up or after a power interruption, thus avoiding creating large electrical spike.
LOW PRESSURE BYPASS TIMER: If the
compressor is running and the low pressure switch opens, the controller will keep the compressor ON for 120 seconds. After 120 seconds if the low pressure switch remains open, the controllers will shut down the compressor and enter a soft lockout. The compressor will not be energized until the low pressure switch closes and the anti-short cycle time delay expires. If the low pressure switch opens 2-4 times in 1 hour, the unit will enter a hard lockout. In order to exit hard lockout power to the unit would need to be reset.
BROWNOUT/SURGE/POWER INTERRUPTION PROTECTION: The brownout
protection in the UPM board will shut does the compressor if the incoming power falls below 18 VAC. The compressor will remain OFF until the voltage is above 18 VAC and ANTI-SHORT CYCLE TIMER (300 seconds) times out. The unit will not go into a hard lockout.
MALFUNCTION OUTPUT: Alarm output is
Normally Open (NO) dry contact.
If pulse is selected the alarm output will be pulsed. The fault output will depend on the dip switch setting for "ALARM". If it is set to "CONST", a constant signal will be produced to indicate a fault has occurred and the unit requires inspection to determine the type of fault. If it is set to "PULSE", a pulse signal is produced and a fault code is detected by a remote device indicating the fault. See L.E.D Fault Indication below for blink code explanation. The remote device must have a malfunction detection capability when the UPM board is set to "PULSE".
If 24 VAC output is needed R must be wired to ALR-COM terminal; 24 VAC will be available o the ALR-OUT terminal when the unit is in the alarm condition.
The UPM Board includes the following features:
ANTI-SHORT CYCLE TIMER: 5 minute delay on
break timer to prevent compressor short cycling.
DISPLAY OUTPUT: The Display output is a pulse
output connected to the Unit Diagnostic Display (UDD) and it pulses 24VAC when the unit is in an lockout alarm condition.
8 733 914 818 (2014/08)SV Heat Pump Series
Loading...
+ 39 hidden pages