York DJ 036, DJ 048, DJ 060 User Manual

5 (1)

®

TECHNICAL GUIDE

SINGLE PACKAGE GAS/ELECTRIC UNITS AND SINGLE PACKAGE

AIR CONDITIONERS

DJ 036, 048 & 060

3, 4 & 5 NOMINAL TONS

13.40 to 13.50 SEER

036-21687-002-A-1105

DESCRIPTION

YORK Sunline Magnumunits are convertible single package air conditioners with a common cabinet and a common roof curb for the 3, 4 and 5 ton sizes. The units were designed for light commercial and commercial applications. They can easily be installed on a roof curb, slab, roof jack or frame.

All units include:

Powder Paint finish that meets ASTM-B-117 1000 hour salt spray standards

Permanently lubricated motors

Bottom or side air discharge configuration capability (field convertible)

Manufactured under the quality standards of ISO9001

SimplicityTM Control Board

Copper tube/aluminum fin coils

Easy access to all components

Rigging holes in base rails for lifting

Fork lift slots on three sides

Single point power connection

Complete factory package - tested, charged and wired

Belt Drive Indoor Blower

CSA agency listing on all units

WARRANTY

Factory Limited Parts Warranty

One-year parts warranty

A Five-year parts warranty on the compressor and electric heat elements.

Ten-year parts warranty on the gas-fired heat exchangers.

FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE

036-21687-002-A-1105

TABLE OF CONTENTS

DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 PRODUCT NOMENCLATURE . . . . . . . . . . . . . . . . . 3 FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 FACTORY-INSTALLED OPTIONS . . . . . . . . . . . . . 12 FIELD-INSTALLED ACCESSORIES . . . . . . . . . . . 13 GUIDE SPECIFICATIONS . . . . . . . . . . . . . . . . . . . 43

LIST OF FIGURES

Fig. #

Pg. #

1 UNIT CUTAWAY . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

2 TYPICAL FIELD POWER & CONTROL WIRING . . 36

3 UNIT DIMENSIONS (3 - 5 TON COOLING ONLY/ ELECTRIC HEAT) FRONT VIEW . . . . . . . . . . . . . . 37

4 UNIT DIMENSIONS (3 - 5 TON COOLING/GAS HEAT) FRONT VIEW . . . . . . . . . . . . . . . . . . . . . . . 37

5 UNIT WITH ECONOMIZER RAINHOOD . . . . . . . . 38

6 UNIT WITH FIXED OUTDOOR AIR/MOTORIZED DAMPER RAINHOOD . . . . . . . . . . . . . . . . . . . . . . . 38

7 UNIT DIMENSIONS (REAR VIEW) . . . . . . . . . . . . . 39

8 DISCONNECT/BLOWER ACCESS LOCATION . . . 39

9 TYPICAL APPLICATIONS . . . . . . . . . . . . . . . . . . . 40

10 FOUR AND SIX POINT LOADING . . . . . . . . . . . . . 41

11 ROOF CURB DIMENSIONS . . . . . . . . . . . . . . . . . . 42

LIST OF TABLES

Tbl. #

Pg. #

1 CAPACITY RATINGS - (ARI 210/240) . . . . . . . . . . 14

2 GAS HEAT RATINGS . . . . . . . . . . . . . . . . . . . . . . . 14

3 2 STAGE GAS HEAT RATINGS . . . . . . . . . . . . . . . 14

4 DJ036 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED INLET) . . . . . . . . . . . . . . 15

5 DJ036 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED DISCHARGE) . . . . . . . . 15

6 DJ036 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED INLET) . . . . . . . . . . . . . . . . . 16

7 DJ036 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED DISCHARGE) . . . . . . . . . . . 16

8 DJ048 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED INLET) . . . . . . . . . . . . . . 17

9 DJ048 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED DISCHARGE) . . . . . . . . 17

10 DJ048 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED INLET) . . . . . . . . . . . . . . . . . 18

11 DJ048 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED DISCHARGE) . . . . . . . . . . . 18

12 DJ060 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED INLET) . . . . . . . . . . . . . . 19

13 DJ060 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED DISCHARGE) . . . . . . . . 19

14 DJ060 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED INLET) . . . . . . . . . . . . . . . . 20

15 DJ060 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED DISCHARGE) . . . . . . . . . . . 20

16 DJ036 COOLING CAPACITIES (3 TON) . . . . . . . . 21

17 DJ048 COOLING CAPACITIES (4 TON) . . . . . . . . 22

18 DJ060 COOLING CAPACITIES (5 TON) . . . . . . . . 23

19SUPPLY AIR BLOWER PERFORMANCE (DJ036 BELT DRIVE) - SIDE DUCT APPLICATION . . . . . 24

20SUPPLY AIR BLOWER PERFORMANCE (DJ036

BELT DRIVE) - BOTTOM DUCT APPLICATION . . 25

21SUPPLY AIR BLOWER PERFORMANCE (DJ048 BELT DRIVE) - SIDE DUCT APPLICATION . . . . . 26

22SUPPLY AIR BLOWER PERFORMANCE (DJ048

BELT DRIVE) - BOTTOM DUCT APPLICATION . . 27

23SUPPLY AIR BLOWER PERFORMANCE (DJ060 BELT DRIVE) - SIDE DUCT APPLICATION . . . . . 28

24SUPPLY AIR BLOWER PERFORMANCE (DJ060

BELT DRIVE) - BOTTOM DUCT APPLICATION . . 29

25

BELT DRIVE BLOWER MOTOR AND DRIVE

 

 

DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

30

26

STATIC RESISTANCES . . . . . . . . . . . . . . . . . . . .

30

27

ELECTRIC HEATER CFM LIMITATIONS . . . . . . .

30

28ELECTRICAL DATA - DJ036, 048 & 060 BELT DRIVE W/O POWERED CONVENIENCE OUTLET . . . . . 31

29ELECTRICAL DATA - DJ036, 048 & 060 BELT DRIVE WITH POWERED CONVENIENCE OUTLET . . . . 33

30

PHYSICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . .

35

31

ELECTRIC HEAT CORRECTION FACTORS . . . .

35

32

VOLTAGE LIMITATIONS . . . . . . . . . . . . . . . . . . . .

35

33

UTILITIES ENTRY . . . . . . . . . . . . . . . . . . . . . . . . .

39

34

MINIMUM CLEARANCES . . . . . . . . . . . . . . . . . . .

39

35

DJ 4 AND 6 POINT LOADS WEIGHT

 

 

DISTRIBUTION . . . . . . . . . . . . . . . . . . . . . . . . . . .

41

36

CENTER OF GRAVITY . . . . . . . . . . . . . . . . . . . . .

41

37

OPERATING WEIGHTS (LBS.) . . . . . . . . . . . . . . .

42

2

Unitary Products Group

036-21687-002-A-1105

PRODUCT NOMENCLATURE

7RQ 6XQOLQH 0DJQXP 0RGHO 1XPEHU 1RPHQFODWXUH

' - 1 1 $ $$

3URGXFW &DWHJRU\

' $LU &RQG 6LQJOH 3NJ 5

3URGXFW ,GHQWLILHU

- 8OWUD (IILFLHQF\ %HOW 'ULYH 2QO\

1RPLQDO &RROLQJ

&DSDFLW\ 0%+

7RQ7RQ7RQ

+HDW 7\SH 1RPLQDO +HDW &DSDFLW\

& &RROLQJ 2QO\ 6XLWDEOH IRU ILHOG LQVWDOOHG HOHFWULF KHDW

*DV +HDW 2SWLRQV

1 0%+ 2XWSXW $OXPLQL]HG 6WHHO 6WDJH 1 0%+ 2XWSXW $OXPLQL]HG 6WHHO 6WDJH

1 0%+ 2XWSXW $OXPLQL]HG 6WHHO 6WDJH 1 0%+ 2XWSXW $OXPLQL]HG 6WHHO 6WDJH ' 0%+ 2XWSXW $OXPLQL]HG 6WHHO 6WDJH ' 0%+ 2XWSXW $OXPLQL]HG 6WHHO 6WDJH 6 0%+ 2XWSXW 6WDLQOHVV 6WHHO 6WDJH

6 0%+ 2XWSXW 6WDLQOHVV 6WHHO 6WDJH

6 0%+ 2XWSXW 6WDLQOHVV 6WHHO 6WDJH 6 0%+ 2XWSXW 6WDLQOHVV 6WHHO 6WDJH 7 0%+ 2XWSXW 6WDLQOHVV 6WHHO 6WDJH 7 0%+ 2XWSXW 6WDLQOHVV 6WHHO 6WDJH

(OHFWULF +HDW 2SWLRQV

( .: (OHFWULF +HDW ( .: (OHFWULF +HDW ( .: (OHFWULF +HDW ( .: (OHFWULF +HDW ( .: (OHFWULF +HDW ( .: (OHFWULF +HDW

' 7 0%+ 2XWSXW RQ 0RGHOV

$LUIORZ

1 %HOW 'ULYH

3 %HOW 'ULYH 6LQJOH ,QSXW (FRQR

5 %HOW 'ULYH 0RWRUL]HG 'DPSHU

< %HOW 'ULYH %$6 5HDG\ (FRQ 1R %$6 &RQWUROOHU Z 3OHDWHG )LOWHUV

3URGXFW *HQHUDWLRQ

)LUVW *HQHUDWLRQ

9ROWDJH

,QVWDOODWLRQ 2SWLRQV

$ 1R 2SWLRQV ,QVWDOOHG % 2SWLRQ

& 2SWLRQ

' 2SWLRQV ( 2SWLRQ

) 2SWLRQ

* 2SWLRQV + 2SWLRQV - 2SWLRQV

. 2SWLRQV / 2SWLRQV

0 2SWLRQV

1 2SWLRQV

3 2SWLRQV

4 2SWLRQV

5 2SWLRQV

6 2SWLRQ

7 2SWLRQV

8 2SWLRQV

9 2SWLRQV : 2SWLRQV ; 2SWLRQV

< 2SWLRQV = 2SWLRQV

2SWLRQV

'LVFRQQHFW

1RQ 3ZU G &RQY 2XOWHW6PRNH 'HWHFWRU 6 $6PRNH 'HWHFWRU 5 $3ZU G &RQY 2XWOHW

$GGLWLRQDO 2SWLRQV

6HH 1H[W 3DJH

Unitary Products Group

3

036-21687-002-A-1105

PRODUCT NOMENCLATURE - Continued

3-5T Sunline Model Number Nomenclature

 

Standard Cabinet

 

 

AA

None

AB

Phase Monitor

AC

Coil Guard

AD

Dirty Filter Switch

AE

Phase Monitor & Coil Guard

AF

Phase Monitor & Dirty Filter Switch

AG

Coil Guard & Dirty Filter Switch

AH

Phase Monitor, Coil Guard, & Dirty Filter Switch

AJ

SS Drain Pan

AK

SS Drain Pan & Phase Monitor

AL

SS Drain Pan & Coil Guard

AM

SS Drain Pan & Dirty Filter Switch

AN

SS Drain Pan, Phase Monitor, Coil Guard & Dirty Filter Switch

AS

Bottom Drain Connection

CA

CPC Controller with Dirty Filter Switch & Air Proving Switch

CB

CPC Controller, DFS, APS & Phase Monitor

CC

CPC Controller, DFS, APS & Coil Guard

CD

CPC Controller, DFS, APS, Phase Monitor, & Coil Guard

CE

CPC Controller, DFS, APS & Technicoat Cond. Coil

CF

CPC Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor

CG

CPC Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard

CH

CPC Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard

CJ

CPC Controller, DFS, APS & Technicoat Evap. Coil

CK

CPC Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor

CL

CPC Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard

CM

CPC Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard

CN

CPC Controller, DFS, APS & Technicoat Evap. & Cond Coils

CP

CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor

CQ

CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard

CR

CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard

CS

CPC Controller, DFS, APS, SS Drain Pan

CT

CPC Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard

CU

CPC Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils

CV

CPC Controller, DFS, APS, SS Drain Pan, & Technicoat Evap Coil

CW

CPC Controller, DFS, APS, SS Drain Pan, & Technicoat Evap and Cond Coils

CX

CPC Controller, DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils

JA

Johnson UNT Controller with Dirty Filter Switch & Air Proving Switch

JB

Johnson UNT Controller, DFS, APS & Phase Monitor

JC

Johnson UNT Controller, DFS, APS & Coil Guard

JD

Johnson UNT Controller, DFS, APS, Phase Monitor, & Coil Guard

JE

Johnson UNT Controller, DFS, APS & Technicoat Cond. Coil

JF

Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor

JG

Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard

JH

Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard

JJ

Johnson UNT Controller, DFS, APS & Technicoat Evap. Coil

JK

Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor

JL

Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard

JM

Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard

JN

Johnson UNT Controller, DFS, APS & Technicoat Evap. & Cond Coils

JP

Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor

JQ

Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard

4

Unitary Products Group

036-21687-002-A-1105

 

Standard Cabinet

 

 

JR

Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard

JS

Johnson UNT Controller, DFS, APS, SS Drain Pan

JT

Johnson UNT Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard

JU

Johnson UNT Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils

JV

Johnson UNT Controller, DFS, APS, SS Drain Pan, & Technicoat Evap Coil

JW

Johnson UNT Controller, DFS, APS, SS Drain Pan, & Technicoat Evap and Cond Coils

JX

Johnson UNT Controller, DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils

HA

Honeywell Excel 10 Controller with Dirty Filter Switch & Air Proving Switch

HB

Honeywell Excel 10 Controller, DFS, APS & Phase Monitor

HC

Honeywell Excel 10 Controller, DFS, APS & Coil Guard

HD

Honeywell Excel 10 Controller, DFS, APS, Phase Monitor, & Coil Guard

HE

Honeywell Excel 10 Controller, DFS, APS & Technicoat Cond. Coil

HF

Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor

HG

Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard

HH

Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard

HJ

Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. Coil

HK

Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor

HL

Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard

HM

Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard

HN

Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. & Cond Coils

HP

Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor

HQ

Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard

HR

Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard

HS

Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan

HT

Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard

HU

Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils

HV

Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan, & Technicoat Evap Coil

HW

Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan, & Technicoat Evap and Cond Coils

HX

Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils

NA

Novar ETC-3 Controller with Dirty Filter Switch & Air Proving Switch

NB

Novar ETC-3 Controller, DFS, APS & Phase Monitor

NC

Novar ETC-3 Controller, DFS, APS & Coil Guard

ND

Novar ETC-3 Controller, DFS, APS, Phase Monitor, & Coil Guard

NE

Novar ETC-3 Controller, DFS, APS & Technicoat Cond. Coil

NF

Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor

NG

Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard

NH

Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard

NJ

Novar ETC-3 Controller, DFS, APS & Technicoat Evap. Coil

NK

Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor

NL

Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard

NM

Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard

NN

Novar ETC-3 Controller, DFS, APS & Technicoat Evap. & Cond Coils

NP

Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor

NQ

Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard

NR

Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard

NS

Novar ETC-3 Controller, DFS, APS, SS Drain Pan

NT

Novar ETC-3 Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard

NU

Novar ETC-3 Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils

NV

Novar ETC-3 Controller, DFS, APS, SS Drain Pan, & Technicoat Evap Coil

NW

Novar ETC-3, DFS, APS, SS Drain Pan, & Technicoat Evap and Cond Coils

NX

Novar ETC-3 Controller, DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils

TA

Technicoat Condenser Coil

TB

Technicoat Condenser Coil & Phase Monitor

TC

Technicoat Condenser Coil & Coil Guard

Unitary Products Group

5

036-21687-002-A-1105

 

Standard Cabinet

 

 

TD

Technicoat Condenser Coil & Dirty Filter Switch

TE

Technicoat Condenser Coil, Phase Monitor, & Coil Guard

TF

Technicoat Condenser Coil, Phase Monitor, & Dirty Filter Switch

TG

Technicoat Condenser Coil, Coil Guard, & Dirty Filter Switch

TH

Technicoat Condenser Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch

TJ

Technicoat Evaporator Coil

TK

Technicoat Evaporator Coil & Phase Monitor

TL

Technicoat Evaporator Coil & Coil Guard

TM

Technicoat Evaporator Coil & Dirty Filter Switch

TN

Technicoat Evaporator Coil, Phase Monitor, & Coil Guard

TP

Technicoat Evaporator Coil, Phase Monitor, & Dirty Filter Switch

TQ

Technicoat Evaporator Coil, Coil Guard, & Dirty Filter Switch

TR

Technicoat Evaporator Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch

TS

Technicoat Evaporator & Condenser Coils

TT

Technicoat Evaporator & Condenser Coils & Phase Monitor

TU

Technicoat Evaporator & Condenser Coils & Coil Guard

TV

Technicoat Evaporator & Condenser Coils & Dirty Filter Switch

TW

Technicoat Evaporator & Condenser Coils, Phase Monitor, & Coil Guard

TX

Technicoat Evaporator & Condenser Coils, Phase Monitor, & Dirty Filter Switch

TY

Technicoat Evaporator & Condenser Coils, Coil Guard, & Dirty Filter Switch

TZ

Technicoat Evaporator & Condenser Coils, Phase Monitor, Coil Guard, & Dirty Filter Switch

T1

Technicoat Condenser & SS Drain Pan

T3

Technicoat Condenser Coil, SS Drain Pan, Phase Monitor, Coil Guard, & Dirty Filter Switch

T4

Technicoat Evaporator & SS Drain Pan

T6

Technicoat Evaporator Coil, SS Drain Pan, Phase Monitor, Coil Guard, & Dirty Filter Switch

T7

Technicoat Evaporator & Condenser Coils & SS Drain Pan

T9

Technicoat Evaporator & Condenser Coils, SS Drain Pan, Phase Monitor, Coil Guard, & Dirty Filter Switch

LA

Simplicity Intelli-Comfort Controller

LB

Simplicity Intelli-Comfort Controller, & Phase Monitor

LC

Simplicity Intelli-Comfort Controller, & Coil Guard

LD

Simplicity Intelli-Comfort Controller, Phase Monitor, & Coil Guard

LE

Simplicity Intelli-Comfort Controller, & Technicoat Cond. Coil

LF

Simplicity Intelli-Comfort Controller, Technicoat Cond. Coil, & Phase Monitor

LG

Simplicity Intelli-Comfort Controller, Technicoat Cond. Coil, & Coil Guard

LH

Simplicity Intelli-Comfort Controller, Technicoat Cond. Coil, Phase Monitor, & Coil Guard

LJ

Simplicity Intelli-Comfort Controller, & Technicoat Evap. Coil

LK

Simplicity Intelli-Comfort Controller, Technicoat Evap. Coil, & Phase Monitor

LL

Simplicity Intelli-Comfort Controller, Technicoat Evap. Coil, & Coil Guard

LM

Simplicity Intelli-Comfort Controller, Technicoat Evap. Coil, Phase Monitor, & Coil Guard

LN

Simplicity Intelli-Comfort Controller, & Technicoat Evap. & Cond Coils

LP

Simplicity Intelli-Comfort Controller, Technicoat Evap. & Cond Coils, & Phase Monitor

LQ

Simplicity Intelli-Comfort Controller, Technicoat Evap. & Cond Coils, & Coil Guard

LR

Simplicity Intelli-Comfort Controller, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard

LS

Simplicity Intelli-Comfort Controller, SS Drain Pan

LT

Simplicity Intelli-Comfort Controller, SS Drain Pan, Phase Monitor, & Coil Guard

LU

Simplicity Intelli-Comfort Controller, SS Drain Pan, & Technicoat Cond Coils

LV

Simplicity Intelli-Comfort Controller, SS Drain Pan, & Technicoat Evap Coil

LW

Simplicity Intelli-Comfort Controller, SS Drain Pan, & Technicoat Evap and Cond Coils

LX

Simplicity Intelli-Comfort Controller, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils

WA

Intelli-Comfort w/Mod Link Controller

WB

Intelli-Comfort w/Mod Link Controller, & Phase Monitor

WC

Intelli-Comfort w/Mod Link Controller, & Coil Guard

WD

Intelli-Comfort w/Mod Link Controller, Phase Monitor, & Coil Guard

WE

Intelli-Comfort w/Mod Link Controller, & Technicoat Cond. Coil

6

Unitary Products Group

036-21687-002-A-1105

 

Standard Cabinet

 

 

WF

Intelli-Comfort w/Mod Link Controller, Technicoat Cond. Coil, & Phase Monitor

WG

Intelli-Comfort w/Mod Link Controller, Technicoat Cond. Coil, & Coil Guard

WH

Intelli-Comfort w/Mod Link Controller, Technicoat Cond. Coil, Phase Monitor, & Coil Guard

WJ

Intelli-Comfort w/Mod Link Controller, & Technicoat Evap. Coil

WK

Intelli-Comfort w/Mod Link Controller, Technicoat Evap. Coil, & Phase Monitor

WL

Intelli-Comfort w/Mod Link Controller, Technicoat Evap. Coil, & Coil Guard

WM

Intelli-Comfort w/Mod Link Controller, Technicoat Evap. Coil, Phase Monitor, & Coil Guard

WN

Intelli-Comfort w/Mod Link Controller, & Technicoat Evap. & Cond Coils

WP

Intelli-Comfort w/Mod Link Controller, Technicoat Evap. & Cond Coils, & Phase Monitor

WQ

Intelli-Comfort w/Mod Link Controller, Technicoat Evap. & Cond Coils, & Coil Guard

WR

Intelli-Comfort w/Mod Link Controller, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard

WS

Intelli-Comfort w/Mod Link Controller, SS Drain Pan

WT

Intelli-Comfort w/Mod Link Controller, SS Drain Pan, Phase Monitor, & Coil Guard

WU

Intelli-Comfort w/Mod Link Controller, SS Drain Pan, & Technicoat Cond Coils

WV

Intelli-Comfort w/Mod Link Controller, SS Drain Pan, & Technicoat Evap Coil

WW

Intelli-Comfort w/Mod Link Controller, SS Drain Pan, & Technicoat Evap and Cond Coils

WX

Intelli-Comfort w/Mod Link Controller, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils

 

Hinged Filter Door & Toolless Access Cabinet

 

 

BA

Hinged Filter Door & Toolless Access Panels

BB

Phase Monitor, Hinged Filter Door & Toolless Access Panels

BC

Coil Guard, Hinged Filter Door & Toolless Access Panels

BD

Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels

BE

Phase Monitor & Coil Guard, Hinged Filter Door & Toolless Access Panels

BF

Phase Monitor & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels

BG

Coil Guard & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels

BH

Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels

BJ

SS Drain Pan & Hinged Filter Door & Toolless Access Panels

BK

SS Drain Pan & Phase Monitor, Hinged Filter Door & Toolless Access Panels

BL

SS Drain Pan & Coil Guard, Hinged Filter Door & Toolless Access Panels

BM

SS Drain Pan & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels

BN

SS Drain Pan & Phase Monitor & Coil Guard, Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels

BS

Bottom Drain Connection, Hinged Filter Door & Toolless Access Panels

DA

CPC Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Toolless Access Panels

DB

CPC Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Toolless Access Panels

DC

CPC Controller, DFS, APS & Coil Guard, Hinged Filter Door & Toolless Access Panels

DD

CPC Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels

DE

CPC Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels

DF

CPC Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels

DG

CPC Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels

DH

CPC Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels

DJ

CPC Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access Panels

DK

CPC Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels

DL

CPC Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels

DM

CPC Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels

DN

CPC Controller, DFS, APS & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access Panels

DP

CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access Panels

DQ

CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access Panels

DR

CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels

DS

CPC Controller, DFS, APS, SS Drain Pan Hinged Filter Door & Toolless Access Panels

DT

CPC Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard Hinged Filter Door & Toolless Access Panels

DU

CPC Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils Hinged Filter Door & Toolless Access Panels

DV

CPC Controller, DFS, APS, SS Drain Pan, & Technicoat Evap Coil Hinged Filter Door & Toolless Access Panels

DW

CPC Controller, DFS, APS, SS Drain Pan, & Technicoat Evap and Cond Coils Hinged Filter Door & Toolless Access Panels

Unitary Products Group

7

 

036-21687-002-A-1105

 

 

 

Hinged Filter Door & Toolless Access Cabinet

 

 

DX

CPC Controller, DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils Hinged Filter Door & Toolless

 

Access Panels

 

 

EA

Johnson UNT Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Toolless Access Panels

EB

Johnson UNT Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Toolless Access Panels

EC

Johnson UNT Controller, DFS, APS & Coil Guard, Hinged Filter Door & Toolless Access Panels

ED

Johnson UNT Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels

EE

Johnson UNT Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels

EF

Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels

EG

Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels

EH

Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels

EJ

Johnson UNT Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access Panels

EK

Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels

EL

Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels

EM

Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels

EN

Johnson UNT Controller, DFS, APS & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access Panels

EP

Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access Panels

EQ

Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access

 

Panels

ER

Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door &

 

Toolless Access Panels

 

 

ES

Johnson UNT Controller, DFS, APS, SS Drain Pan Hinged Filter Door & Toolless Access Panels

ET

Johnson UNT Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard Hinged Filter Door & Toolless Access Panels

EU

Johnson UNT Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils Hinged Filter Door & Toolless Access Panels

EV

Johnson UNT Controller, DFS, APS, SS Drain Pan, & Technicoat Evap Coil Hinged Filter Door & Toolless Access Panels

EW

Johnson UNT Controller, DFS, APS, SS Drain Pan, & Technicoat Evap and Cond Coils Hinged Filter Door & Toolless Access Panels

EX

Johnson UNT Controller, DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils Hinged Filter Door &

 

Toolless Access Panels

 

 

GA

Honeywell Excel 10 Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Toolless Access Panels

GB

Honeywell Excel 10 Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Toolless Access Panels

GC

Honeywell Excel 10 Controller, DFS, APS & Coil Guard, Hinged Filter Door & Toolless Access Panels

GD

Honeywell Excel 10 Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels

GE

Honeywell Excel 10 Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels

GF

Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels

GG

Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels

GH

Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access

 

Panels

 

 

GJ

Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access Panels

GK

Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels

GL

Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels

GM

Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access

 

Panels

 

 

GN

Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access Panels

GP

Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access

 

Panels

GQ

Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access Panels

GR

Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless

 

Access Panels

GS

Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan

GT

Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard

GU

Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils

GV

Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan, & Technicoat Evap Coil

GW

Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan, & Technicoat Evap and Cond Coils

GX

Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils

PA

Novar ETC-3 Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Toolless Access Panels

PB

Novar ETC-3 Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Toolless Access Panels

8

Unitary Products Group

036-21687-002-A-1105

 

Hinged Filter Door & Toolless Access Cabinet

 

 

PC

Novar ETC-3 Controller, DFS, APS & Coil Guard, Hinged Filter Door & Toolless Access Panels

PD

Novar ETC-3 Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels

PE

Novar ETC-3 Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels

PF

Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels

PG

Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels

PH

Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels

PJ

Novar ETC-3 Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access Panels

PK

Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels

PL

Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels

PM

Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels

PN

Novar ETC-3 Controller, DFS, APS & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access Panels

PP

Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access Panels

PQ

Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access Panels

PR

Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access

 

Panels

PS

Novar ETC-3 Controller, DFS, APS, SS Drain Pan

PT

Novar ETC-3 Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard

PU

Novar ETC-3 Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils

PV

Novar ETC-3 Controller, DFS, APS, SS Drain Pan, & Technicoat Evap Coil

PW

Novar ETC-3, DFS, APS, SS Drain Pan, & Technicoat Evap and Cond Coils

PX

Novar ETC-3 Controller, DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils

UA

Technicoat Condenser Coil, Hinged Filter Door & Toolless Access Panels

UB

Technicoat Condenser Coil & Phase Monitor, Hinged Filter Door & Toolless Access Panels

UC

Technicoat Condenser Coil & Coil Guard, Hinged Filter Door & Toolless Access Panels

UD

Technicoat Condenser Coil & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels

UE

Technicoat Condenser Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels

UF

Technicoat Condenser Coil, Phase Monitor, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels

UG

Technicoat Condenser Coil, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels

UH

Technicoat Condenser Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels

UJ

Technicoat Evaporator Coil, Hinged Filter Door & Toolless Access Panels

UK

Technicoat Evaporator Coil & Phase Monitor, Hinged Filter Door & Toolless Access Panels

UL

Technicoat Evaporator Coil & Coil Guard, Hinged Filter Door & Toolless Access Panels

UM

Technicoat Evaporator Coil & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels

UN

Technicoat Evaporator Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels

UP

Technicoat Evaporator Coil, Phase Monitor, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels

UQ

Technicoat Evaporator Coil, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels

UR

Technicoat Evaporator Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels

US

Technicoat Evaporator & Condenser Coils, Hinged Filter Door & Toolless Access Panels

UT

Technicoat Evaporator & Condenser Coils & Phase Monitor, Hinged Filter Door & Toolless Access Panels

UU

Technicoat Evaporator & Condenser Coils & Coil Guard, Hinged Filter Door & Toolless Access Panels

UV

Technicoat Evaporator & Condenser Coils & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels

UW

Technicoat Evaporator & Condenser Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels

UX

Technicoat Evaporator & Condenser Coils, Phase Monitor, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels

UY

Technicoat Evaporator & Condenser Coils, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels

UZ

Technicoat Evaporator & Condenser Coils, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels

U1

Technicoat Condenser & SS Drain Pan, Hinged Filter Door & Toolless Access Panels

U3

Technicoat Condenser Coil, SS Drain Pan, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels

U4

Technicoat Evaporator & SS Drain Pan, Hinged Filter Door & Toolless Access Panels

U6

Technicoat Evaporator Coil, SS Drain Pan, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels

U7

Technicoat Evaporator & Condenser Coils & SS Drain Pan, Hinged Filter Door & Toolless Access Panels

U9

Technicoat Evaporator & Condenser Coils, SS Drain Pan, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless

 

Access Panels

 

 

QA

Simplicity Intelli-Comfort Controller with Hinged Filter Door & Toolless Access Panels

QB

Simplicity Intelli-Comfort Controller, & Phase Monitor, Hinged Filter Door & Toolless Access Panels

QC

Simplicity Intelli-Comfort Controller, & Coil Guard, Hinged Filter Door & Toolless Access Panels

Unitary Products Group

9

 

036-21687-002-A-1105

 

 

 

Hinged Filter Door & Toolless Access Cabinet

 

 

QD

Simplicity Intelli-Comfort Controller, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels

QE

Simplicity Intelli-Comfort Controller, & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels

QF

Simplicity Intelli-Comfort Controller, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels

QG

Simplicity Intelli-Comfort Controller, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels

QH

Simplicity Intelli-Comfort Controller, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access

QJ

Simplicity Intelli-Comfort Controller, & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access Panels

QK

Simplicity Intelli-Comfort Controller, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels

QL

Simplicity Intelli-Comfort Controller, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels

QM

Simplicity Intelli-Comfort Controller, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access

QN

Simplicity Intelli-Comfort Controller, & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access Panels

QP

Simplicity Intelli-Comfort Controller, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access Pan

QQ Simplicity Intelli-Comfort Controller, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access Panels

QR

Simplicity Intelli-Comfort Controller, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless

QS

Simplicity Intelli-Comfort Controller, SS Drain Pan Hinged Filter Door & Toolless Access Panels

QT

Simplicity Intelli-Comfort Controller, SS Drain Pan, Phase Monitor, & Coil Guard Hinged Filter Door & Toolless Access Panels

QU

Simplicity Intelli-Comfort Controller, SS Drain Pan, & Technicoat Cond Coils Hinged Filter Door & Toolless Access Panels

QV

Simplicity Intelli-Comfort Controller, SS Drain Pan, & Technicoat Evap Coil Hinged Filter Door & Toolless Access Panels

QW

Simplicity Intelli-Comfort Controller, SS Drain Pan, & Technicoat Evap and Cond Coils Hinged Filter Door & Toolless Access Panels

QX

Simplicity Intelli-Comfort Controller, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils Hinged Filter Door &

 

Toolless Access Panels

 

 

XA

Intelli-Comfort w/Mod Link Controller, Hinged Filter Door & Toolless Access Panels

XB

Intelli-Comfort w/Mod Link Controller, & Phase Monitor, Hinged Filter Door & Toolless Access Panels

XC

Intelli-Comfort w/Mod Link Controller, & Coil Guard, Hinged Filter Door & Toolless Access Panels

XD

Intelli-Comfort w/Mod Link Controller, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels

XE

Intelli-Comfort w/Mod Link Controller, & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels

XF

Intelli-Comfort w/Mod Link Controller, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels

XG

Intelli-Comfort w/Mod Link Controller, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels

XH

Intelli-Comfort w/Mod Link Controller, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access

XJ

Intelli-Comfort w/Mod Link Controller, & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access Panels

XK

Intelli-Comfort w/Mod Link Controller, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels

XL

Intelli-Comfort w/Mod Link Controller, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels

XM

Intelli-Comfort w/Mod Link Controller, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access

XN

Intelli-Comfort w/Mod Link Controller, & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access Panels

XP

Intelli-Comfort w/Mod Link Controller, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access Pan

XQ

Intelli-Comfort w/Mod Link Controller, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access Panels

XR

Intelli-Comfort w/Mod Link Controller, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless

XS

Intelli-Comfort w/Mod Link Controller, SS Drain Pan Hinged Filter Door & Toolless Access Panels

XT

Intelli-Comfort w/Mod Link Controller, SS Drain Pan, Phase Monitor, & Coil Guard Hinged Filter Door & Toolless Access Panels

XU

Intelli-Comfort w/Mod Link Controller, SS Drain Pan, & Technicoat Cond Coils Hinged Filter Door & Toolless Access Panels

XV

Intelli-Comfort w/Mod Link Controller, SS Drain Pan, & Technicoat Evap Coil Hinged Filter Door & Toolless Access Panels

XW

Intelli-Comfort w/Mod Link Controller, SS Drain Pan, & Technicoat Evap and Cond Coils Hinged Filter Door & Toolless Access Panels

XXIntelli-Comfort w/Mod Link Controller, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils Hinged Filter Door & Toolless Access Panels

10

Unitary Products Group

036-21687-002-A-1105

FEATURES

All models are available with a wide variety of factorymounted options such as stainless steel heat exchangers, electric heaters, phase monitor, convenience outlet, dirty filter switch, disconnect switch, smoke detectors, and coil guard to make them suitable for almost every application.

All units are self-contained and assembled on full perimeter base rails with forklift holes on three sides and holes for overhead rigging. Every unit is completely piped, wired, charged and tested at the factory to simplify the field installation and to provide years of dependable operation.

All models (including those with an economizer) are suitable for either bottom or horizontal duct connections. For bottom duct, remove the sheet metal panels from the supply and return air openings through the base of the unit. For horizontal duct, remove the supply and return air panels on the rear of the unit.

All models are available with these “factory mounted” outdoor air damper options:

Single enthalpy economizer

Motorized outdoor air damper

Supply air blowers are equipped with a belt drive that can be adjusted to meet the exact requirements of the job.

All compressors are equipped with internal pressure relief. Every refrigerant circuit includes a liquid line filter-drier, a high pressure switch and a suction line with a freezestat and low pressure/loss of charge switch to protect all system components.

Simplicity™ Controls - Simplicity™ control boards have standardized a number of features previously available only as options or by utilizing additional controls.

Low Ambient - An integrated low-ambient control allows all units to operate in the cooling mode down to 0ºF outdoor ambient without additional assistance. Optionally, the control board can be programmed to lockout the compressors when the outdoor air temperature is low or when free cooling is available.

Anti-Short Cycle Protection - To aid compressor life, an anti-short cycle delay is incorporated into the standard controls. Compressor reliability is further ensured by programmable minimum run times. For testing, the anti short cycle delay can be temporarily overridden with the push of a button.

Fan Delays - Fan on and fan off delays are fully programmable and are independent of one another. All units are programmed with default values based upon their configuration of cooling and heat.

Safety Monitoring - The control board monitors the high and low-pressure switches, the freezestats, the

gas valve, if applicable, and the temperature limit switch on gas heat units. The unit control board will alarm on ignition failures, compressor lockouts and repeated limit switch trips.

Nuisance Trip Protection- To prevent nuisance trouble calls, the control board uses a “three strikes, you’re out” philosophy. The high and low-pressure switches and the freezestats must trip three times within two hours before the unit control board will lock out the compressor.

On Board Diagnostics - Each alarm will energize a trouble light on the thermostat, if so equipped, and flash an alarm code on the control board LED. Each high and low-pressure switch alarm as well as each freezestat alarm has its own flash code. The control board saves the five most recent alarms in memory, and these alarms can be reviewed at any time.

Alarms and programmed values are retained through the loss of power.

All units have long lasting powder paint cabinets with 1000 hour salt spray test approval under ASTM-B117 procedures.

All models are CSA listed.

Warranty - All models include a one-year limited parts warranty on the complete unit. Compressors and electric heater elements carry a five-year warranty. Gas heat exchangers carry a 10-year parts warranty.

Gas Heat Operation - All single phase models with gas heat have minimum annual fuel utilization efficiency (AFUE) of 80%. All three phase models with gas heat have minimum steady state efficiency of 80%. Each section includes a durable heat exchanger with aluminized steel or optional stainless steel tubes, a redundant gas valve, spark ignition, power venting, an ignition module for 100% shut-off and all of the safety controls required to meet the latest ANSI standards.

The gas supply piping can be routed into the heating compartment through a hole in the base pan of the unit or through a knockout in the piping panel on the front of the unit.

Electric Heat Operation - All electric heat models are wired for a single power source and include a bank of nickel chromium elements mounted at the discharge of the supply air blower to provide a high velocity and uniform distribution of air across the heating elements.

Every element is fully protected against excessive temperature by thermal limit switches.

The power supply wiring can be routed into the control box through a threaded pipe connection (field supplied) in the base pan of the unit or through a knockout in the wiring panel on the side of the unit.

BAS Controls - York’s Sunline™ series units offer factory mounted BAS controls such as SImplicity™ INTELLIComfort™, Novar, Honeywell, Johnson, and CPC.

Unitary Products Group

11

York DJ 036, DJ 048, DJ 060 User Manual

FIGURE 1 - UNIT CUTAWAY

FACTORY-INSTALLED OPTIONS

SINGLE INPUT ELECTRONIC ENTHALPY ECONOMIZERS - Includes a slide-in / plug-in damper assembly with fully modulating spring-return motor actuator capable of introducing up to 100% outdoor air with nominal 1% leakage type dampers.

The enthalpy system contains one sensor that monitors the outdoor air and determines when the air is cool enough and dry enough to provide free cooling.

The rainhood is painted to match the basic unit and must be field-assembled before installing.

MOTORIZED OUTDOOR AIR INTAKE DAMPER - Includes a slide-in / plug-in damper assembly with a 2- position, spring return motor actuator which opens to a pre-set position whenever the supply air blower is operating and will drive fully closed when the blower unit shuts down.

The rain hood is painted to match the basic unit and must be field assembled before installing.

PHENOLIC COATED EVAPORATOR AND CONDENSER COILS - Special coating process that utilizes Technicoat 10-1TM processes. Coating is applied by total immersion of the complete coil for maximum protection.

036-21687-002-A-1105

ELECTRIC HEATERS - Wired for single point power supply. These nickel chromium heater elements are provided with limit and automatic reset capability to prevent operation at excessive temperatures.

FILTER OPTIONS - Standard units are shipped with 1” throw-away filters installed. 2” pleated filters are offered as a factory installed option.

CONVENIENCE OUTLET - This 110 volt outlet can be “powered” by the unit with a stepdown transformer or the unit may be ordered with a “non-powered” convenience outlet that can be wired in the field.

DISCONNECT SWITCH - For gas heat units and cooling units with electric heat, a HACR breaker sized to the unit is provided. For cooling only units, a switch sized to the largest electric heat available for the particular unit is provided. Factory installed option only.

BAS - Building Automation System Controls Simplicity™ INTELLI-Comfort™ CONTROL - The York®

Simplicity™ INTELLI-Comfort™ control is factory installed. It includes a supply air sensor, a return air sensor, and an outside air sensor. There are provisions for a field installed dirty filter indicator switch, an air-proving switch, an Outside Air Humidity sensor, a Return Air Humidity sensor, an Inside IAQ sensor, and an Outside Air IAQ sensor. Construction mode operation, 365-day real time clock with 7 day programming plus holiday scheduling is built-in. Two different modes of demand ventilation are achieved through the INTELLI-Comfort™

12

Unitary Products Group

036-21687-002-A-1105

using CO2 sensors. It uses an inside CO2 sensor to perform Demand Ventilation. It can also use an Outside CO2 sensor to perform Differential Demand Ventilation. It uses a Patented Comfort Ventilation algorithm to provide comfortable ventilation air temperature. The patented econo- mizer-loading algorithm will protect the equipment when harsh operating conditions exist. Humidity in the occupied space or return duct can be monitored and controlled via humidity sensors and the on-board connection for hot gas re-heat system. It uses the INTELLI-Start™ algorithm to maximize energy savings by recovering the building from the Unoccupied Setpoints to the Occupied Setpoints just in time for the Occupied Time Period to begin. The Simplicity™ INTELLI-Comfort™ balances space temperature, ventilation air temperature, CO2 and humidity for ultimate comfort.

Simplicity™ INTELLI-Comfort™ with MOD LINK CONTROL - The York® Simplicity™ INTELLI-Comfort™ with Mod Link control is factory installed. It includes all the features of the INTELLI-Comfort™ control with an additional control to translate communications from MODBUS to the BACnet MSTP protocol.

Novar® BAS CONTROL - The Novar® ETC-3 building automation system controller is factory installed. Includes supply air sensor, return air sensor, dirty filter indicator switch, and air proving switch.

JOHNSON CONTROLS BAS CONTROL - The Johnson Control YK-UNT-1126 building automation system controller is factory installed. Includes supply air sensor, return air sensor, dirty filter indicator switch, and air proving switch.

CPC BAS CONTROL - The Computer Process Controls Model 810-3060 ARTC Advanced Rooftop building automation system controller is factory installed. Includes supply air sensor, return air sensor, dirty filter indicator switch and air proving switch.

HONEYWELL BAS CONTROL - The Honeywell W7750C building automation system controller is factory installed. Includes air supply sensor, return air sensor, dirty filter indicator switch, and air proving switch.

SMOKE DETECTORS - (supply air & return air) The smoke detectors stop operation of the unit by interrupting power to the control board if smoke is detected within the air compartment.

COIL GUARD - Customers can purchase a coil guard kit to protect the condenser coil from damage. This is not a hail guard kit.

STAINLESS STEEL HEAT EXCHANGER - For applications in corrosive environments, this option provides a full stainless steel heat exchanger assembly.

STAINLESS STEEL DRAIN PAN - An optional rustproof stainless steel drain pan is available to provide years of trouble-free operation in corrosive environments.

BOTTOM DRAIN CONNECTION - An optional bottom drain connection is available for inside the curb connections for applications in cold environments to reduce freezing drain lines.

PHASE MONITORS - Designed to prevent unit damage. The phase monitor will shut the unit down in an out-of- phase condition.

DIRTY FILTER SWITCH - This kit includes a differential pressure switch that energizes the fault light on the unit thermostat, indicating that there is an abnormally high pressure drop across the filters. Factory installed option or field installed accessory.

HINGED FILTER DOOR/“TOOLLESS” BLOWER AND ACCESS PANELS (not hinged) - This option allows for easy access and maintenance.

NOTE:Knobs are shipped inside the unit to prevent shipping damage. These must be field installed for tool-less operation.

FIELD-INSTALLED ACCESSORIES

SINGLE INPUT ELECTRONIC ENTHALPY ECONOMIZERS - Includes a slide-in / plug-in damper assembly with fully modulating spring-return motor actuator capable of introducing up to 100% outdoor air with nominal 1% leakage type dampers.

The enthalpy system contains one sensor that monitors the outdoor air and determines when the air is cool enough and dry enough to provide free cooling.

The rainhood is painted to match the basic unit and must be field-assembled before installing.

MOTORIZED OUTDOOR AIR INTAKE DAMPER - Includes a slide-in / plug-in damper assembly with a 2- position, spring return motor actuator which opens to some pre-set position whenever the supply air blower is operating and will drive fully closed when the blower unit shuts down.

The rain hood is painted to match the basic unit and must be field assembled before installing.

ELECTRIC HEATERS wired for single point power supply. These nickel chromium heater elements are provided with limit and automatic reset capability to prevent operation at excessive temperatures.

Unitary Products Group

13

ROOF CURBS - Eight and fourteen-inch high roof curbs provide a water-tight seal between the unit and the finished roof. These full perimeter curbs meet the requirements of the National Roofing Contractors Association (NRCA) and are shipped knocked-down for field assembly.

Roof curbs are designed to fit inside the base rails of the unit and include both a wood nailing strip and duct hanger supports.

HIGH ALTITUDE NATURAL GAS - Burner orifices and pilot orifices are provided for proper furnace operation at altitudes up to 6,000 feet.

PROPANE - Burner orifices, pilot orifices and gas valve parts are provided to convert a natural gas furnace to propane.

HIGH ALTITUDE PROPANE - Burner orifices and pilot orifices are provided for proper furnace operation at altitudes up to 6,000 feet. This accessory supplements the basic propane conversion kit.

LOW NOX KIT - Required to reduce the emission of nitrogen oxides below 40 nano grams per joule.

POWER EXHAUST - Our single input economizer options are available with power exhaust. Whenever the outdoor air intake dampers are opened for free cooling, the exhaust fan will be energized to prevent the conditioned space from being over-pressurized during economizer operation.

The power exhaust option can only be used on bottom duct configurations.

TABLE 1: CAPACITY RATINGS - (ARI 210/240)1

 

 

EER2

SEER3

 

SOUND

MODEL

MBH

CFM

RATING

 

 

 

 

 

(Db)4

DJ036

35.8

11.65

13.50

1200

84

DJ048

46.5

11.75

13.45

1600

83

DJ060

56.5

11.15

13.40

1800

81

1.80/67°F Indoor and 95°F outdoor.

2.EER = Energy Efficiency Ratio at full load - the cooling capacity in Btu’s per hour (Btuh) divided by the power input in watts, expressed in Btuh per watt (Btuh/watt).

3.SEER = Seasonal Energy Efficiency Ratio.

4.Rated in accordance with ARI 270 Standard.

036-21687-002-A-1105

BAROMETRIC RELIEF DAMPER - This damper accessory can be used to relieve internal building air pressure on units with an economizer without power exhaust. This accessory includes a rain hood, a bird screen and a fully assembled damper. With bottom duct connections, the damper should be mounted over the opening in the return air panel. With horizontal ductwork, the accessory should be mounted on the return air duct.

ENTHALPY ACCESSORY CONTROL KIT - This kit contains the required components to convert a single enthalpy economizer to dual enthalpy.

BURGLAR BARS - Mount in the supply and return openings to prevent entry into the duct work.

FLUE EXHAUST EXTENSION KIT - In locations with wind or weather conditions which may interfere with proper exhausting of furnace combustion products, this kit can be installed to prevent the flue exhaust from entering nearby fresh air intakes.

CO2 SENSOR - Senses CO2 levels and automatically overrides the economizer when levels rise above the present limits.

COIL GUARD - Customers can purchase a coil guard kit to protect the condenser coil from damage. This is not a hail guard kit.

HAIL GUARD - Hail Guard kit is available to prevent unit from hail damage. This is a sloped hood that fits above the coil.

GAS PIPING KIT - This kit supplies all necessary fittings and shut off valve.

TABLE 2: GAS HEAT RATINGS1

MODEL

MBH

MBH

AFUE

TEMP

INPUT

OUTPUT

(%)

RISE ºF

 

DJ036N04

50

40

80.9

15 - 45

DJ036N08

100

80

80.5

40 - 70

DJ048N06

75

60

80.9

25 - 55

DJ048N10

125

100

80.3

45 - 75

 

 

 

 

 

DJ060N08

100

80

80.5

25 - 55

DJ060N10

125

100

80.3

35 - 65

1. All units are single-stage heating.

TABLE 3: 2 STAGE GAS HEAT RATINGS

MODEL1

MBH INPUT

MBH OUTPUT

STEADY STATE EFFICIENCY

RISE

MINIMUM HEATING

1ST STAGE

2ND STAGE

1ST STAGE

2ND STAGE

1ST STAGE

2ND STAGE

MIN.

MAX.

AIRFLOW (CFM)

 

DJ036D06

45

75

35.8

60.8

79.4

81.1

35

70

790

DJ036D10

69

115

55.2

92

80.0

80.2

55

90

950

DJ048D06

45

75

35.7

60.8

79.4

81.1

25

70

790

DJ048D10

75

125

60.4

100.6

80.5

80.5

45

75

1230

DJ060D06

45

75

35.8

60.8

79.4

81.1

35

70

1010

DJ060D10

75

125

60.4

100.6

80.5

80.5

45

75

1230

1. Models are 3Ø only.

14

Unitary Products Group

036-21687-002-A-1105

TABLE 4: DJ036 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED INLET)

UNIT DESCRIPTION / MODEL

 

 

DJ036 / 3 Ton / Belt Drive

 

 

CONFIGURATION

 

 

 

Horizontal Ducted Inlet

 

 

 

Indoor Blower Speed (RPM)

630

631

879

885

Blower Static Pressure (IWG)

0.2

0.3

0.2

0.7

Airflow (CFM)

1116

928

1979

1020

Blower Motor BHP

0.41

0.37

0.76

0.53

 

ID Blower

Cooling

ID Blower

Cooling

ID Blower

 

Cooling

ID Blower

Cooling

Octave Center Freq.

Operation2

Operation2

 

Operation2

Operation2

 

Only (dB)

(dB)

Only (dB)

(dB)

Only (dB)

 

(dB)

Only (dB)

(dB)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

63

80

82

80

82

78

 

83

81

85

125

76

77

76

77

82

 

83

81

82

250

56

59

56

60

60

 

61

58

60

500

50

50

49

50

54

 

54

51

52

1000

40

43

39

42

49

 

50

44

45

2000

41

42

40

42

49

 

49

43

44

4000

41

41

41

41

49

 

49

41

41

8000

45

45

45

45

47

 

47

45

45

1.Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment.

2.Cooling Operation – ID blower, compressor and outdoor fan operating.

3.Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).

4.Test duct termination is flush with reverberation room wall.

5.Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.

TABLE 5: DJ036 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED DISCHARGE)

UNIT DESCRIPTION / MODEL

 

 

DJ036 / 3 Ton / Belt Drive

 

 

CONFIGURATION

 

 

Horizontal Ducted Discharge

 

 

Indoor Blower Speed (RPM)

630

631

879

885

Blower Static Pressure (IWG)

0.2

0.3

0.2

0.7

Airflow (CFM)

1116

928

1979

1020

Blower Motor BHP

0.41

0.37

0.76

0.53

 

ID Blower

Cooling

ID Blower

Cooling

ID Blower

Cooling

ID Blower

Cooling

Octave Center Freq.

Operation2

Operation2

Operation2

Operation2

 

Only (dB)

(dB)

Only (dB)

(dB)

Only (dB)

(dB)

Only (dB)

(dB)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

63

80

84

80

83

85

87

84

87

125

74

77

74

76

80

82

80

83

250

58

61

58

61

68

68

63

65

500

48

51

47

50

58

58

53

54

1000

41

45

39

43

55

55

49

50

2000

39

41

37

39

53

53

46

47

4000

41

41

38

38

55

55

49

49

8000

45

45

44

44

52

53

47

47

1.Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment.

2.Cooling Operation – ID blower, compressor and outdoor fan operating.

3.Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).

4.Test duct termination is flush with reverberation room wall.

5.Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.

Unitary Products Group

15

Loading...