TECHNICAL GUIDE
SINGLE PACKAGE GAS/ELECTRIC UNITS AND SINGLE PACKAGE
AIR CONDITIONERS
DJ 036, 048 & 060
3, 4 & 5 NOMINAL TONS
13.40 to 13.50 SEER
036-21687-002-A-1105
DESCRIPTION
YORK Sunline Magnum™ units are convertible single package air conditioners with a common cabinet and a common roof curb for the 3, 4 and 5 ton sizes. The units were designed for light commercial and commercial applications. They can easily be installed on a roof curb, slab, roof jack or frame.
All units include:
•Powder Paint finish that meets ASTM-B-117 1000 hour salt spray standards
•Permanently lubricated motors
•Bottom or side air discharge configuration capability (field convertible)
•Manufactured under the quality standards of ISO9001
•SimplicityTM Control Board
•Copper tube/aluminum fin coils
•Easy access to all components
•Rigging holes in base rails for lifting
•Fork lift slots on three sides
•Single point power connection
•Complete factory package - tested, charged and wired
•Belt Drive Indoor Blower
•CSA agency listing on all units
WARRANTY
•Factory Limited Parts Warranty
•One-year parts warranty
•A Five-year parts warranty on the compressor and electric heat elements.
•Ten-year parts warranty on the gas-fired heat exchangers.
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
036-21687-002-A-1105
TABLE OF CONTENTS
DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 PRODUCT NOMENCLATURE . . . . . . . . . . . . . . . . . 3 FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 FACTORY-INSTALLED OPTIONS . . . . . . . . . . . . . 12 FIELD-INSTALLED ACCESSORIES . . . . . . . . . . . 13 GUIDE SPECIFICATIONS . . . . . . . . . . . . . . . . . . . 43
LIST OF FIGURES
Fig. # |
Pg. # |
1 UNIT CUTAWAY . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2 TYPICAL FIELD POWER & CONTROL WIRING . . 36
3 UNIT DIMENSIONS (3 - 5 TON COOLING ONLY/ ELECTRIC HEAT) FRONT VIEW . . . . . . . . . . . . . . 37
4 UNIT DIMENSIONS (3 - 5 TON COOLING/GAS HEAT) FRONT VIEW . . . . . . . . . . . . . . . . . . . . . . . 37
5 UNIT WITH ECONOMIZER RAINHOOD . . . . . . . . 38
6 UNIT WITH FIXED OUTDOOR AIR/MOTORIZED DAMPER RAINHOOD . . . . . . . . . . . . . . . . . . . . . . . 38
7 UNIT DIMENSIONS (REAR VIEW) . . . . . . . . . . . . . 39
8 DISCONNECT/BLOWER ACCESS LOCATION . . . 39
9 TYPICAL APPLICATIONS . . . . . . . . . . . . . . . . . . . 40
10 FOUR AND SIX POINT LOADING . . . . . . . . . . . . . 41
11 ROOF CURB DIMENSIONS . . . . . . . . . . . . . . . . . . 42
LIST OF TABLES
Tbl. # |
Pg. # |
1 CAPACITY RATINGS - (ARI 210/240) . . . . . . . . . . 14
2 GAS HEAT RATINGS . . . . . . . . . . . . . . . . . . . . . . . 14
3 2 STAGE GAS HEAT RATINGS . . . . . . . . . . . . . . . 14
4 DJ036 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED INLET) . . . . . . . . . . . . . . 15
5 DJ036 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED DISCHARGE) . . . . . . . . 15
6 DJ036 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED INLET) . . . . . . . . . . . . . . . . . 16
7 DJ036 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED DISCHARGE) . . . . . . . . . . . 16
8 DJ048 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED INLET) . . . . . . . . . . . . . . 17
9 DJ048 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED DISCHARGE) . . . . . . . . 17
10 DJ048 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED INLET) . . . . . . . . . . . . . . . . . 18
11 DJ048 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED DISCHARGE) . . . . . . . . . . . 18
12 DJ060 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED INLET) . . . . . . . . . . . . . . 19
13 DJ060 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED DISCHARGE) . . . . . . . . 19
14 DJ060 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED INLET) . . . . . . . . . . . . . . . . 20
15 DJ060 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED DISCHARGE) . . . . . . . . . . . 20
16 DJ036 COOLING CAPACITIES (3 TON) . . . . . . . . 21
17 DJ048 COOLING CAPACITIES (4 TON) . . . . . . . . 22
18 DJ060 COOLING CAPACITIES (5 TON) . . . . . . . . 23
19SUPPLY AIR BLOWER PERFORMANCE (DJ036 BELT DRIVE) - SIDE DUCT APPLICATION . . . . . 24
20SUPPLY AIR BLOWER PERFORMANCE (DJ036
BELT DRIVE) - BOTTOM DUCT APPLICATION . . 25
21SUPPLY AIR BLOWER PERFORMANCE (DJ048 BELT DRIVE) - SIDE DUCT APPLICATION . . . . . 26
22SUPPLY AIR BLOWER PERFORMANCE (DJ048
BELT DRIVE) - BOTTOM DUCT APPLICATION . . 27
23SUPPLY AIR BLOWER PERFORMANCE (DJ060 BELT DRIVE) - SIDE DUCT APPLICATION . . . . . 28
24SUPPLY AIR BLOWER PERFORMANCE (DJ060
BELT DRIVE) - BOTTOM DUCT APPLICATION . . 29
25 |
BELT DRIVE BLOWER MOTOR AND DRIVE |
|
|
DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
30 |
26 |
STATIC RESISTANCES . . . . . . . . . . . . . . . . . . . . |
30 |
27 |
ELECTRIC HEATER CFM LIMITATIONS . . . . . . . |
30 |
28ELECTRICAL DATA - DJ036, 048 & 060 BELT DRIVE W/O POWERED CONVENIENCE OUTLET . . . . . 31
29ELECTRICAL DATA - DJ036, 048 & 060 BELT DRIVE WITH POWERED CONVENIENCE OUTLET . . . . 33
30 |
PHYSICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . |
35 |
31 |
ELECTRIC HEAT CORRECTION FACTORS . . . . |
35 |
32 |
VOLTAGE LIMITATIONS . . . . . . . . . . . . . . . . . . . . |
35 |
33 |
UTILITIES ENTRY . . . . . . . . . . . . . . . . . . . . . . . . . |
39 |
34 |
MINIMUM CLEARANCES . . . . . . . . . . . . . . . . . . . |
39 |
35 |
DJ 4 AND 6 POINT LOADS WEIGHT |
|
|
DISTRIBUTION . . . . . . . . . . . . . . . . . . . . . . . . . . . |
41 |
36 |
CENTER OF GRAVITY . . . . . . . . . . . . . . . . . . . . . |
41 |
37 |
OPERATING WEIGHTS (LBS.) . . . . . . . . . . . . . . . |
42 |
2 |
Unitary Products Group |
036-21687-002-A-1105
PRODUCT NOMENCLATURE
7RQ 6XQOLQH 0DJQXP 0RGHO 1XPEHU 1RPHQFODWXUH
' - 1 1 $ $$
3URGXFW &DWHJRU\
' $LU &RQG 6LQJOH 3NJ 5
3URGXFW ,GHQWLILHU
- 8OWUD (IILFLHQF\ %HOW 'ULYH 2QO\
1RPLQDO &RROLQJ
&DSDFLW\ 0%+
7RQ7RQ7RQ
+HDW 7\SH 1RPLQDO +HDW &DSDFLW\
& &RROLQJ 2QO\ 6XLWDEOH IRU ILHOG LQVWDOOHG HOHFWULF KHDW
*DV +HDW 2SWLRQV
1 0%+ 2XWSXW $OXPLQL]HG 6WHHO 6WDJH 1 0%+ 2XWSXW $OXPLQL]HG 6WHHO 6WDJH
1 0%+ 2XWSXW $OXPLQL]HG 6WHHO 6WDJH 1 0%+ 2XWSXW $OXPLQL]HG 6WHHO 6WDJH ' 0%+ 2XWSXW $OXPLQL]HG 6WHHO 6WDJH ' 0%+ 2XWSXW $OXPLQL]HG 6WHHO 6WDJH 6 0%+ 2XWSXW 6WDLQOHVV 6WHHO 6WDJH
6 0%+ 2XWSXW 6WDLQOHVV 6WHHO 6WDJH
6 0%+ 2XWSXW 6WDLQOHVV 6WHHO 6WDJH 6 0%+ 2XWSXW 6WDLQOHVV 6WHHO 6WDJH 7 0%+ 2XWSXW 6WDLQOHVV 6WHHO 6WDJH 7 0%+ 2XWSXW 6WDLQOHVV 6WHHO 6WDJH
(OHFWULF +HDW 2SWLRQV
( .: (OHFWULF +HDW ( .: (OHFWULF +HDW ( .: (OHFWULF +HDW ( .: (OHFWULF +HDW ( .: (OHFWULF +HDW ( .: (OHFWULF +HDW
' 7 0%+ 2XWSXW RQ 0RGHOV
$LUIORZ
1 %HOW 'ULYH
3 %HOW 'ULYH 6LQJOH ,QSXW (FRQR
5 %HOW 'ULYH 0RWRUL]HG 'DPSHU
< %HOW 'ULYH %$6 5HDG\ (FRQ 1R %$6 &RQWUROOHU Z 3OHDWHG )LOWHUV
3URGXFW *HQHUDWLRQ
)LUVW *HQHUDWLRQ
9ROWDJH
,QVWDOODWLRQ 2SWLRQV
$ 1R 2SWLRQV ,QVWDOOHG % 2SWLRQ
& 2SWLRQ
' 2SWLRQV ( 2SWLRQ
) 2SWLRQ
* 2SWLRQV + 2SWLRQV - 2SWLRQV
. 2SWLRQV / 2SWLRQV
0 2SWLRQV
1 2SWLRQV
3 2SWLRQV
4 2SWLRQV
5 2SWLRQV
6 2SWLRQ
7 2SWLRQV
8 2SWLRQV
9 2SWLRQV : 2SWLRQV ; 2SWLRQV
< 2SWLRQV = 2SWLRQV
2SWLRQV
'LVFRQQHFW
1RQ 3ZU G &RQY 2XOWHW6PRNH 'HWHFWRU 6 $6PRNH 'HWHFWRU 5 $3ZU G &RQY 2XWOHW
$GGLWLRQDO 2SWLRQV
6HH 1H[W 3DJH
Unitary Products Group |
3 |
036-21687-002-A-1105
PRODUCT NOMENCLATURE - Continued
3-5T Sunline Model Number Nomenclature
|
Standard Cabinet |
|
|
AA |
None |
AB |
Phase Monitor |
AC |
Coil Guard |
AD |
Dirty Filter Switch |
AE |
Phase Monitor & Coil Guard |
AF |
Phase Monitor & Dirty Filter Switch |
AG |
Coil Guard & Dirty Filter Switch |
AH |
Phase Monitor, Coil Guard, & Dirty Filter Switch |
AJ |
SS Drain Pan |
AK |
SS Drain Pan & Phase Monitor |
AL |
SS Drain Pan & Coil Guard |
AM |
SS Drain Pan & Dirty Filter Switch |
AN |
SS Drain Pan, Phase Monitor, Coil Guard & Dirty Filter Switch |
AS |
Bottom Drain Connection |
CA |
CPC Controller with Dirty Filter Switch & Air Proving Switch |
CB |
CPC Controller, DFS, APS & Phase Monitor |
CC |
CPC Controller, DFS, APS & Coil Guard |
CD |
CPC Controller, DFS, APS, Phase Monitor, & Coil Guard |
CE |
CPC Controller, DFS, APS & Technicoat Cond. Coil |
CF |
CPC Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor |
CG |
CPC Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard |
CH |
CPC Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard |
CJ |
CPC Controller, DFS, APS & Technicoat Evap. Coil |
CK |
CPC Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor |
CL |
CPC Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard |
CM |
CPC Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard |
CN |
CPC Controller, DFS, APS & Technicoat Evap. & Cond Coils |
CP |
CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor |
CQ |
CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard |
CR |
CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard |
CS |
CPC Controller, DFS, APS, SS Drain Pan |
CT |
CPC Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard |
CU |
CPC Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils |
CV |
CPC Controller, DFS, APS, SS Drain Pan, & Technicoat Evap Coil |
CW |
CPC Controller, DFS, APS, SS Drain Pan, & Technicoat Evap and Cond Coils |
CX |
CPC Controller, DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils |
JA |
Johnson UNT Controller with Dirty Filter Switch & Air Proving Switch |
JB |
Johnson UNT Controller, DFS, APS & Phase Monitor |
JC |
Johnson UNT Controller, DFS, APS & Coil Guard |
JD |
Johnson UNT Controller, DFS, APS, Phase Monitor, & Coil Guard |
JE |
Johnson UNT Controller, DFS, APS & Technicoat Cond. Coil |
JF |
Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor |
JG |
Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard |
JH |
Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard |
JJ |
Johnson UNT Controller, DFS, APS & Technicoat Evap. Coil |
JK |
Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor |
JL |
Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard |
JM |
Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard |
JN |
Johnson UNT Controller, DFS, APS & Technicoat Evap. & Cond Coils |
JP |
Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor |
JQ |
Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard |
4 |
Unitary Products Group |
036-21687-002-A-1105
|
Standard Cabinet |
|
|
JR |
Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard |
JS |
Johnson UNT Controller, DFS, APS, SS Drain Pan |
JT |
Johnson UNT Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard |
JU |
Johnson UNT Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils |
JV |
Johnson UNT Controller, DFS, APS, SS Drain Pan, & Technicoat Evap Coil |
JW |
Johnson UNT Controller, DFS, APS, SS Drain Pan, & Technicoat Evap and Cond Coils |
JX |
Johnson UNT Controller, DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils |
HA |
Honeywell Excel 10 Controller with Dirty Filter Switch & Air Proving Switch |
HB |
Honeywell Excel 10 Controller, DFS, APS & Phase Monitor |
HC |
Honeywell Excel 10 Controller, DFS, APS & Coil Guard |
HD |
Honeywell Excel 10 Controller, DFS, APS, Phase Monitor, & Coil Guard |
HE |
Honeywell Excel 10 Controller, DFS, APS & Technicoat Cond. Coil |
HF |
Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor |
HG |
Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard |
HH |
Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard |
HJ |
Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. Coil |
HK |
Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor |
HL |
Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard |
HM |
Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard |
HN |
Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. & Cond Coils |
HP |
Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor |
HQ |
Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard |
HR |
Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard |
HS |
Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan |
HT |
Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard |
HU |
Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils |
HV |
Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan, & Technicoat Evap Coil |
HW |
Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan, & Technicoat Evap and Cond Coils |
HX |
Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils |
NA |
Novar ETC-3 Controller with Dirty Filter Switch & Air Proving Switch |
NB |
Novar ETC-3 Controller, DFS, APS & Phase Monitor |
NC |
Novar ETC-3 Controller, DFS, APS & Coil Guard |
ND |
Novar ETC-3 Controller, DFS, APS, Phase Monitor, & Coil Guard |
NE |
Novar ETC-3 Controller, DFS, APS & Technicoat Cond. Coil |
NF |
Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor |
NG |
Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard |
NH |
Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard |
NJ |
Novar ETC-3 Controller, DFS, APS & Technicoat Evap. Coil |
NK |
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor |
NL |
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard |
NM |
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard |
NN |
Novar ETC-3 Controller, DFS, APS & Technicoat Evap. & Cond Coils |
NP |
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor |
NQ |
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard |
NR |
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard |
NS |
Novar ETC-3 Controller, DFS, APS, SS Drain Pan |
NT |
Novar ETC-3 Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard |
NU |
Novar ETC-3 Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils |
NV |
Novar ETC-3 Controller, DFS, APS, SS Drain Pan, & Technicoat Evap Coil |
NW |
Novar ETC-3, DFS, APS, SS Drain Pan, & Technicoat Evap and Cond Coils |
NX |
Novar ETC-3 Controller, DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils |
TA |
Technicoat Condenser Coil |
TB |
Technicoat Condenser Coil & Phase Monitor |
TC |
Technicoat Condenser Coil & Coil Guard |
Unitary Products Group |
5 |
036-21687-002-A-1105
|
Standard Cabinet |
|
|
TD |
Technicoat Condenser Coil & Dirty Filter Switch |
TE |
Technicoat Condenser Coil, Phase Monitor, & Coil Guard |
TF |
Technicoat Condenser Coil, Phase Monitor, & Dirty Filter Switch |
TG |
Technicoat Condenser Coil, Coil Guard, & Dirty Filter Switch |
TH |
Technicoat Condenser Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch |
TJ |
Technicoat Evaporator Coil |
TK |
Technicoat Evaporator Coil & Phase Monitor |
TL |
Technicoat Evaporator Coil & Coil Guard |
TM |
Technicoat Evaporator Coil & Dirty Filter Switch |
TN |
Technicoat Evaporator Coil, Phase Monitor, & Coil Guard |
TP |
Technicoat Evaporator Coil, Phase Monitor, & Dirty Filter Switch |
TQ |
Technicoat Evaporator Coil, Coil Guard, & Dirty Filter Switch |
TR |
Technicoat Evaporator Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch |
TS |
Technicoat Evaporator & Condenser Coils |
TT |
Technicoat Evaporator & Condenser Coils & Phase Monitor |
TU |
Technicoat Evaporator & Condenser Coils & Coil Guard |
TV |
Technicoat Evaporator & Condenser Coils & Dirty Filter Switch |
TW |
Technicoat Evaporator & Condenser Coils, Phase Monitor, & Coil Guard |
TX |
Technicoat Evaporator & Condenser Coils, Phase Monitor, & Dirty Filter Switch |
TY |
Technicoat Evaporator & Condenser Coils, Coil Guard, & Dirty Filter Switch |
TZ |
Technicoat Evaporator & Condenser Coils, Phase Monitor, Coil Guard, & Dirty Filter Switch |
T1 |
Technicoat Condenser & SS Drain Pan |
T3 |
Technicoat Condenser Coil, SS Drain Pan, Phase Monitor, Coil Guard, & Dirty Filter Switch |
T4 |
Technicoat Evaporator & SS Drain Pan |
T6 |
Technicoat Evaporator Coil, SS Drain Pan, Phase Monitor, Coil Guard, & Dirty Filter Switch |
T7 |
Technicoat Evaporator & Condenser Coils & SS Drain Pan |
T9 |
Technicoat Evaporator & Condenser Coils, SS Drain Pan, Phase Monitor, Coil Guard, & Dirty Filter Switch |
LA |
Simplicity Intelli-Comfort Controller |
LB |
Simplicity Intelli-Comfort Controller, & Phase Monitor |
LC |
Simplicity Intelli-Comfort Controller, & Coil Guard |
LD |
Simplicity Intelli-Comfort Controller, Phase Monitor, & Coil Guard |
LE |
Simplicity Intelli-Comfort Controller, & Technicoat Cond. Coil |
LF |
Simplicity Intelli-Comfort Controller, Technicoat Cond. Coil, & Phase Monitor |
LG |
Simplicity Intelli-Comfort Controller, Technicoat Cond. Coil, & Coil Guard |
LH |
Simplicity Intelli-Comfort Controller, Technicoat Cond. Coil, Phase Monitor, & Coil Guard |
LJ |
Simplicity Intelli-Comfort Controller, & Technicoat Evap. Coil |
LK |
Simplicity Intelli-Comfort Controller, Technicoat Evap. Coil, & Phase Monitor |
LL |
Simplicity Intelli-Comfort Controller, Technicoat Evap. Coil, & Coil Guard |
LM |
Simplicity Intelli-Comfort Controller, Technicoat Evap. Coil, Phase Monitor, & Coil Guard |
LN |
Simplicity Intelli-Comfort Controller, & Technicoat Evap. & Cond Coils |
LP |
Simplicity Intelli-Comfort Controller, Technicoat Evap. & Cond Coils, & Phase Monitor |
LQ |
Simplicity Intelli-Comfort Controller, Technicoat Evap. & Cond Coils, & Coil Guard |
LR |
Simplicity Intelli-Comfort Controller, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard |
LS |
Simplicity Intelli-Comfort Controller, SS Drain Pan |
LT |
Simplicity Intelli-Comfort Controller, SS Drain Pan, Phase Monitor, & Coil Guard |
LU |
Simplicity Intelli-Comfort Controller, SS Drain Pan, & Technicoat Cond Coils |
LV |
Simplicity Intelli-Comfort Controller, SS Drain Pan, & Technicoat Evap Coil |
LW |
Simplicity Intelli-Comfort Controller, SS Drain Pan, & Technicoat Evap and Cond Coils |
LX |
Simplicity Intelli-Comfort Controller, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils |
WA |
Intelli-Comfort w/Mod Link Controller |
WB |
Intelli-Comfort w/Mod Link Controller, & Phase Monitor |
WC |
Intelli-Comfort w/Mod Link Controller, & Coil Guard |
WD |
Intelli-Comfort w/Mod Link Controller, Phase Monitor, & Coil Guard |
WE |
Intelli-Comfort w/Mod Link Controller, & Technicoat Cond. Coil |
6 |
Unitary Products Group |
036-21687-002-A-1105
|
Standard Cabinet |
|
|
WF |
Intelli-Comfort w/Mod Link Controller, Technicoat Cond. Coil, & Phase Monitor |
WG |
Intelli-Comfort w/Mod Link Controller, Technicoat Cond. Coil, & Coil Guard |
WH |
Intelli-Comfort w/Mod Link Controller, Technicoat Cond. Coil, Phase Monitor, & Coil Guard |
WJ |
Intelli-Comfort w/Mod Link Controller, & Technicoat Evap. Coil |
WK |
Intelli-Comfort w/Mod Link Controller, Technicoat Evap. Coil, & Phase Monitor |
WL |
Intelli-Comfort w/Mod Link Controller, Technicoat Evap. Coil, & Coil Guard |
WM |
Intelli-Comfort w/Mod Link Controller, Technicoat Evap. Coil, Phase Monitor, & Coil Guard |
WN |
Intelli-Comfort w/Mod Link Controller, & Technicoat Evap. & Cond Coils |
WP |
Intelli-Comfort w/Mod Link Controller, Technicoat Evap. & Cond Coils, & Phase Monitor |
WQ |
Intelli-Comfort w/Mod Link Controller, Technicoat Evap. & Cond Coils, & Coil Guard |
WR |
Intelli-Comfort w/Mod Link Controller, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard |
WS |
Intelli-Comfort w/Mod Link Controller, SS Drain Pan |
WT |
Intelli-Comfort w/Mod Link Controller, SS Drain Pan, Phase Monitor, & Coil Guard |
WU |
Intelli-Comfort w/Mod Link Controller, SS Drain Pan, & Technicoat Cond Coils |
WV |
Intelli-Comfort w/Mod Link Controller, SS Drain Pan, & Technicoat Evap Coil |
WW |
Intelli-Comfort w/Mod Link Controller, SS Drain Pan, & Technicoat Evap and Cond Coils |
WX |
Intelli-Comfort w/Mod Link Controller, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils |
|
Hinged Filter Door & Toolless Access Cabinet |
|
|
BA |
Hinged Filter Door & Toolless Access Panels |
BB |
Phase Monitor, Hinged Filter Door & Toolless Access Panels |
BC |
Coil Guard, Hinged Filter Door & Toolless Access Panels |
BD |
Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels |
BE |
Phase Monitor & Coil Guard, Hinged Filter Door & Toolless Access Panels |
BF |
Phase Monitor & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels |
BG |
Coil Guard & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels |
BH |
Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels |
BJ |
SS Drain Pan & Hinged Filter Door & Toolless Access Panels |
BK |
SS Drain Pan & Phase Monitor, Hinged Filter Door & Toolless Access Panels |
BL |
SS Drain Pan & Coil Guard, Hinged Filter Door & Toolless Access Panels |
BM |
SS Drain Pan & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels |
BN |
SS Drain Pan & Phase Monitor & Coil Guard, Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels |
BS |
Bottom Drain Connection, Hinged Filter Door & Toolless Access Panels |
DA |
CPC Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Toolless Access Panels |
DB |
CPC Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Toolless Access Panels |
DC |
CPC Controller, DFS, APS & Coil Guard, Hinged Filter Door & Toolless Access Panels |
DD |
CPC Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels |
DE |
CPC Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels |
DF |
CPC Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels |
DG |
CPC Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels |
DH |
CPC Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels |
DJ |
CPC Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access Panels |
DK |
CPC Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels |
DL |
CPC Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels |
DM |
CPC Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels |
DN |
CPC Controller, DFS, APS & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access Panels |
DP |
CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access Panels |
DQ |
CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access Panels |
DR |
CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels |
DS |
CPC Controller, DFS, APS, SS Drain Pan Hinged Filter Door & Toolless Access Panels |
DT |
CPC Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard Hinged Filter Door & Toolless Access Panels |
DU |
CPC Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils Hinged Filter Door & Toolless Access Panels |
DV |
CPC Controller, DFS, APS, SS Drain Pan, & Technicoat Evap Coil Hinged Filter Door & Toolless Access Panels |
DW |
CPC Controller, DFS, APS, SS Drain Pan, & Technicoat Evap and Cond Coils Hinged Filter Door & Toolless Access Panels |
Unitary Products Group |
7 |
|
036-21687-002-A-1105 |
|
|
|
Hinged Filter Door & Toolless Access Cabinet |
|
|
DX |
CPC Controller, DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils Hinged Filter Door & Toolless |
|
Access Panels |
|
|
EA |
Johnson UNT Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Toolless Access Panels |
EB |
Johnson UNT Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Toolless Access Panels |
EC |
Johnson UNT Controller, DFS, APS & Coil Guard, Hinged Filter Door & Toolless Access Panels |
ED |
Johnson UNT Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels |
EE |
Johnson UNT Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels |
EF |
Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels |
EG |
Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels |
EH |
Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels |
EJ |
Johnson UNT Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access Panels |
EK |
Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels |
EL |
Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels |
EM |
Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels |
EN |
Johnson UNT Controller, DFS, APS & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access Panels |
EP |
Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access Panels |
EQ |
Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access |
|
Panels |
ER |
Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & |
|
Toolless Access Panels |
|
|
ES |
Johnson UNT Controller, DFS, APS, SS Drain Pan Hinged Filter Door & Toolless Access Panels |
ET |
Johnson UNT Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard Hinged Filter Door & Toolless Access Panels |
EU |
Johnson UNT Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils Hinged Filter Door & Toolless Access Panels |
EV |
Johnson UNT Controller, DFS, APS, SS Drain Pan, & Technicoat Evap Coil Hinged Filter Door & Toolless Access Panels |
EW |
Johnson UNT Controller, DFS, APS, SS Drain Pan, & Technicoat Evap and Cond Coils Hinged Filter Door & Toolless Access Panels |
EX |
Johnson UNT Controller, DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils Hinged Filter Door & |
|
Toolless Access Panels |
|
|
GA |
Honeywell Excel 10 Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Toolless Access Panels |
GB |
Honeywell Excel 10 Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Toolless Access Panels |
GC |
Honeywell Excel 10 Controller, DFS, APS & Coil Guard, Hinged Filter Door & Toolless Access Panels |
GD |
Honeywell Excel 10 Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels |
GE |
Honeywell Excel 10 Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels |
GF |
Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels |
GG |
Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels |
GH |
Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access |
|
Panels |
|
|
GJ |
Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access Panels |
GK |
Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels |
GL |
Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels |
GM |
Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access |
|
Panels |
|
|
GN |
Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access Panels |
GP |
Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access |
|
Panels |
GQ |
Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access Panels |
GR |
Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless |
|
Access Panels |
GS |
Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan |
GT |
Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard |
GU |
Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils |
GV |
Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan, & Technicoat Evap Coil |
GW |
Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan, & Technicoat Evap and Cond Coils |
GX |
Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils |
PA |
Novar ETC-3 Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Toolless Access Panels |
PB |
Novar ETC-3 Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Toolless Access Panels |
8 |
Unitary Products Group |
036-21687-002-A-1105
|
Hinged Filter Door & Toolless Access Cabinet |
|
|
PC |
Novar ETC-3 Controller, DFS, APS & Coil Guard, Hinged Filter Door & Toolless Access Panels |
PD |
Novar ETC-3 Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels |
PE |
Novar ETC-3 Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels |
PF |
Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels |
PG |
Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels |
PH |
Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels |
PJ |
Novar ETC-3 Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access Panels |
PK |
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels |
PL |
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels |
PM |
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels |
PN |
Novar ETC-3 Controller, DFS, APS & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access Panels |
PP |
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access Panels |
PQ |
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access Panels |
PR |
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access |
|
Panels |
PS |
Novar ETC-3 Controller, DFS, APS, SS Drain Pan |
PT |
Novar ETC-3 Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard |
PU |
Novar ETC-3 Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils |
PV |
Novar ETC-3 Controller, DFS, APS, SS Drain Pan, & Technicoat Evap Coil |
PW |
Novar ETC-3, DFS, APS, SS Drain Pan, & Technicoat Evap and Cond Coils |
PX |
Novar ETC-3 Controller, DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils |
UA |
Technicoat Condenser Coil, Hinged Filter Door & Toolless Access Panels |
UB |
Technicoat Condenser Coil & Phase Monitor, Hinged Filter Door & Toolless Access Panels |
UC |
Technicoat Condenser Coil & Coil Guard, Hinged Filter Door & Toolless Access Panels |
UD |
Technicoat Condenser Coil & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels |
UE |
Technicoat Condenser Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels |
UF |
Technicoat Condenser Coil, Phase Monitor, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels |
UG |
Technicoat Condenser Coil, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels |
UH |
Technicoat Condenser Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels |
UJ |
Technicoat Evaporator Coil, Hinged Filter Door & Toolless Access Panels |
UK |
Technicoat Evaporator Coil & Phase Monitor, Hinged Filter Door & Toolless Access Panels |
UL |
Technicoat Evaporator Coil & Coil Guard, Hinged Filter Door & Toolless Access Panels |
UM |
Technicoat Evaporator Coil & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels |
UN |
Technicoat Evaporator Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels |
UP |
Technicoat Evaporator Coil, Phase Monitor, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels |
UQ |
Technicoat Evaporator Coil, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels |
UR |
Technicoat Evaporator Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels |
US |
Technicoat Evaporator & Condenser Coils, Hinged Filter Door & Toolless Access Panels |
UT |
Technicoat Evaporator & Condenser Coils & Phase Monitor, Hinged Filter Door & Toolless Access Panels |
UU |
Technicoat Evaporator & Condenser Coils & Coil Guard, Hinged Filter Door & Toolless Access Panels |
UV |
Technicoat Evaporator & Condenser Coils & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels |
UW |
Technicoat Evaporator & Condenser Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels |
UX |
Technicoat Evaporator & Condenser Coils, Phase Monitor, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels |
UY |
Technicoat Evaporator & Condenser Coils, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels |
UZ |
Technicoat Evaporator & Condenser Coils, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels |
U1 |
Technicoat Condenser & SS Drain Pan, Hinged Filter Door & Toolless Access Panels |
U3 |
Technicoat Condenser Coil, SS Drain Pan, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels |
U4 |
Technicoat Evaporator & SS Drain Pan, Hinged Filter Door & Toolless Access Panels |
U6 |
Technicoat Evaporator Coil, SS Drain Pan, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels |
U7 |
Technicoat Evaporator & Condenser Coils & SS Drain Pan, Hinged Filter Door & Toolless Access Panels |
U9 |
Technicoat Evaporator & Condenser Coils, SS Drain Pan, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless |
|
Access Panels |
|
|
QA |
Simplicity Intelli-Comfort Controller with Hinged Filter Door & Toolless Access Panels |
QB |
Simplicity Intelli-Comfort Controller, & Phase Monitor, Hinged Filter Door & Toolless Access Panels |
QC |
Simplicity Intelli-Comfort Controller, & Coil Guard, Hinged Filter Door & Toolless Access Panels |
Unitary Products Group |
9 |
|
036-21687-002-A-1105 |
|
|
|
Hinged Filter Door & Toolless Access Cabinet |
|
|
QD |
Simplicity Intelli-Comfort Controller, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels |
QE |
Simplicity Intelli-Comfort Controller, & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels |
QF |
Simplicity Intelli-Comfort Controller, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels |
QG |
Simplicity Intelli-Comfort Controller, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels |
QH |
Simplicity Intelli-Comfort Controller, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access |
QJ |
Simplicity Intelli-Comfort Controller, & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access Panels |
QK |
Simplicity Intelli-Comfort Controller, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels |
QL |
Simplicity Intelli-Comfort Controller, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels |
QM |
Simplicity Intelli-Comfort Controller, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access |
QN |
Simplicity Intelli-Comfort Controller, & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access Panels |
QP |
Simplicity Intelli-Comfort Controller, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access Pan |
QQ Simplicity Intelli-Comfort Controller, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access Panels |
|
QR |
Simplicity Intelli-Comfort Controller, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless |
QS |
Simplicity Intelli-Comfort Controller, SS Drain Pan Hinged Filter Door & Toolless Access Panels |
QT |
Simplicity Intelli-Comfort Controller, SS Drain Pan, Phase Monitor, & Coil Guard Hinged Filter Door & Toolless Access Panels |
QU |
Simplicity Intelli-Comfort Controller, SS Drain Pan, & Technicoat Cond Coils Hinged Filter Door & Toolless Access Panels |
QV |
Simplicity Intelli-Comfort Controller, SS Drain Pan, & Technicoat Evap Coil Hinged Filter Door & Toolless Access Panels |
QW |
Simplicity Intelli-Comfort Controller, SS Drain Pan, & Technicoat Evap and Cond Coils Hinged Filter Door & Toolless Access Panels |
QX |
Simplicity Intelli-Comfort Controller, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils Hinged Filter Door & |
|
Toolless Access Panels |
|
|
XA |
Intelli-Comfort w/Mod Link Controller, Hinged Filter Door & Toolless Access Panels |
XB |
Intelli-Comfort w/Mod Link Controller, & Phase Monitor, Hinged Filter Door & Toolless Access Panels |
XC |
Intelli-Comfort w/Mod Link Controller, & Coil Guard, Hinged Filter Door & Toolless Access Panels |
XD |
Intelli-Comfort w/Mod Link Controller, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels |
XE |
Intelli-Comfort w/Mod Link Controller, & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels |
XF |
Intelli-Comfort w/Mod Link Controller, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels |
XG |
Intelli-Comfort w/Mod Link Controller, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels |
XH |
Intelli-Comfort w/Mod Link Controller, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access |
XJ |
Intelli-Comfort w/Mod Link Controller, & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access Panels |
XK |
Intelli-Comfort w/Mod Link Controller, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels |
XL |
Intelli-Comfort w/Mod Link Controller, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels |
XM |
Intelli-Comfort w/Mod Link Controller, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access |
XN |
Intelli-Comfort w/Mod Link Controller, & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access Panels |
XP |
Intelli-Comfort w/Mod Link Controller, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access Pan |
XQ |
Intelli-Comfort w/Mod Link Controller, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access Panels |
XR |
Intelli-Comfort w/Mod Link Controller, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless |
XS |
Intelli-Comfort w/Mod Link Controller, SS Drain Pan Hinged Filter Door & Toolless Access Panels |
XT |
Intelli-Comfort w/Mod Link Controller, SS Drain Pan, Phase Monitor, & Coil Guard Hinged Filter Door & Toolless Access Panels |
XU |
Intelli-Comfort w/Mod Link Controller, SS Drain Pan, & Technicoat Cond Coils Hinged Filter Door & Toolless Access Panels |
XV |
Intelli-Comfort w/Mod Link Controller, SS Drain Pan, & Technicoat Evap Coil Hinged Filter Door & Toolless Access Panels |
XW |
Intelli-Comfort w/Mod Link Controller, SS Drain Pan, & Technicoat Evap and Cond Coils Hinged Filter Door & Toolless Access Panels |
XXIntelli-Comfort w/Mod Link Controller, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils Hinged Filter Door & Toolless Access Panels
10 |
Unitary Products Group |
036-21687-002-A-1105
FEATURES
All models are available with a wide variety of factorymounted options such as stainless steel heat exchangers, electric heaters, phase monitor, convenience outlet, dirty filter switch, disconnect switch, smoke detectors, and coil guard to make them suitable for almost every application.
All units are self-contained and assembled on full perimeter base rails with forklift holes on three sides and holes for overhead rigging. Every unit is completely piped, wired, charged and tested at the factory to simplify the field installation and to provide years of dependable operation.
All models (including those with an economizer) are suitable for either bottom or horizontal duct connections. For bottom duct, remove the sheet metal panels from the supply and return air openings through the base of the unit. For horizontal duct, remove the supply and return air panels on the rear of the unit.
All models are available with these “factory mounted” outdoor air damper options:
•Single enthalpy economizer
•Motorized outdoor air damper
Supply air blowers are equipped with a belt drive that can be adjusted to meet the exact requirements of the job.
All compressors are equipped with internal pressure relief. Every refrigerant circuit includes a liquid line filter-drier, a high pressure switch and a suction line with a freezestat and low pressure/loss of charge switch to protect all system components.
•Simplicity™ Controls - Simplicity™ control boards have standardized a number of features previously available only as options or by utilizing additional controls.
•Low Ambient - An integrated low-ambient control allows all units to operate in the cooling mode down to 0ºF outdoor ambient without additional assistance. Optionally, the control board can be programmed to lockout the compressors when the outdoor air temperature is low or when free cooling is available.
•Anti-Short Cycle Protection - To aid compressor life, an anti-short cycle delay is incorporated into the standard controls. Compressor reliability is further ensured by programmable minimum run times. For testing, the anti short cycle delay can be temporarily overridden with the push of a button.
•Fan Delays - Fan on and fan off delays are fully programmable and are independent of one another. All units are programmed with default values based upon their configuration of cooling and heat.
•Safety Monitoring - The control board monitors the high and low-pressure switches, the freezestats, the
gas valve, if applicable, and the temperature limit switch on gas heat units. The unit control board will alarm on ignition failures, compressor lockouts and repeated limit switch trips.
•Nuisance Trip Protection- To prevent nuisance trouble calls, the control board uses a “three strikes, you’re out” philosophy. The high and low-pressure switches and the freezestats must trip three times within two hours before the unit control board will lock out the compressor.
•On Board Diagnostics - Each alarm will energize a trouble light on the thermostat, if so equipped, and flash an alarm code on the control board LED. Each high and low-pressure switch alarm as well as each freezestat alarm has its own flash code. The control board saves the five most recent alarms in memory, and these alarms can be reviewed at any time.
Alarms and programmed values are retained through the loss of power.
All units have long lasting powder paint cabinets with 1000 hour salt spray test approval under ASTM-B117 procedures.
All models are CSA listed.
•Warranty - All models include a one-year limited parts warranty on the complete unit. Compressors and electric heater elements carry a five-year warranty. Gas heat exchangers carry a 10-year parts warranty.
•Gas Heat Operation - All single phase models with gas heat have minimum annual fuel utilization efficiency (AFUE) of 80%. All three phase models with gas heat have minimum steady state efficiency of 80%. Each section includes a durable heat exchanger with aluminized steel or optional stainless steel tubes, a redundant gas valve, spark ignition, power venting, an ignition module for 100% shut-off and all of the safety controls required to meet the latest ANSI standards.
The gas supply piping can be routed into the heating compartment through a hole in the base pan of the unit or through a knockout in the piping panel on the front of the unit.
•Electric Heat Operation - All electric heat models are wired for a single power source and include a bank of nickel chromium elements mounted at the discharge of the supply air blower to provide a high velocity and uniform distribution of air across the heating elements.
Every element is fully protected against excessive temperature by thermal limit switches.
The power supply wiring can be routed into the control box through a threaded pipe connection (field supplied) in the base pan of the unit or through a knockout in the wiring panel on the side of the unit.
•BAS Controls - York’s Sunline™ series units offer factory mounted BAS controls such as SImplicity™ INTELLIComfort™, Novar, Honeywell, Johnson, and CPC.
Unitary Products Group |
11 |
FIGURE 1 - UNIT CUTAWAY
FACTORY-INSTALLED OPTIONS
•SINGLE INPUT ELECTRONIC ENTHALPY ECONOMIZERS - Includes a slide-in / plug-in damper assembly with fully modulating spring-return motor actuator capable of introducing up to 100% outdoor air with nominal 1% leakage type dampers.
The enthalpy system contains one sensor that monitors the outdoor air and determines when the air is cool enough and dry enough to provide free cooling.
The rainhood is painted to match the basic unit and must be field-assembled before installing.
•MOTORIZED OUTDOOR AIR INTAKE DAMPER - Includes a slide-in / plug-in damper assembly with a 2- position, spring return motor actuator which opens to a pre-set position whenever the supply air blower is operating and will drive fully closed when the blower unit shuts down.
The rain hood is painted to match the basic unit and must be field assembled before installing.
•PHENOLIC COATED EVAPORATOR AND CONDENSER COILS - Special coating process that utilizes Technicoat 10-1TM processes. Coating is applied by total immersion of the complete coil for maximum protection.
036-21687-002-A-1105
•ELECTRIC HEATERS - Wired for single point power supply. These nickel chromium heater elements are provided with limit and automatic reset capability to prevent operation at excessive temperatures.
•FILTER OPTIONS - Standard units are shipped with 1” throw-away filters installed. 2” pleated filters are offered as a factory installed option.
•CONVENIENCE OUTLET - This 110 volt outlet can be “powered” by the unit with a stepdown transformer or the unit may be ordered with a “non-powered” convenience outlet that can be wired in the field.
•DISCONNECT SWITCH - For gas heat units and cooling units with electric heat, a HACR breaker sized to the unit is provided. For cooling only units, a switch sized to the largest electric heat available for the particular unit is provided. Factory installed option only.
•BAS - Building Automation System Controls Simplicity™ INTELLI-Comfort™ CONTROL - The York®
Simplicity™ INTELLI-Comfort™ control is factory installed. It includes a supply air sensor, a return air sensor, and an outside air sensor. There are provisions for a field installed dirty filter indicator switch, an air-proving switch, an Outside Air Humidity sensor, a Return Air Humidity sensor, an Inside IAQ sensor, and an Outside Air IAQ sensor. Construction mode operation, 365-day real time clock with 7 day programming plus holiday scheduling is built-in. Two different modes of demand ventilation are achieved through the INTELLI-Comfort™
12 |
Unitary Products Group |
036-21687-002-A-1105
using CO2 sensors. It uses an inside CO2 sensor to perform Demand Ventilation. It can also use an Outside CO2 sensor to perform Differential Demand Ventilation. It uses a Patented Comfort Ventilation algorithm to provide comfortable ventilation air temperature. The patented econo- mizer-loading algorithm will protect the equipment when harsh operating conditions exist. Humidity in the occupied space or return duct can be monitored and controlled via humidity sensors and the on-board connection for hot gas re-heat system. It uses the INTELLI-Start™ algorithm to maximize energy savings by recovering the building from the Unoccupied Setpoints to the Occupied Setpoints just in time for the Occupied Time Period to begin. The Simplicity™ INTELLI-Comfort™ balances space temperature, ventilation air temperature, CO2 and humidity for ultimate comfort.
•Simplicity™ INTELLI-Comfort™ with MOD LINK CONTROL - The York® Simplicity™ INTELLI-Comfort™ with Mod Link control is factory installed. It includes all the features of the INTELLI-Comfort™ control with an additional control to translate communications from MODBUS to the BACnet MSTP protocol.
•Novar® BAS CONTROL - The Novar® ETC-3 building automation system controller is factory installed. Includes supply air sensor, return air sensor, dirty filter indicator switch, and air proving switch.
•JOHNSON CONTROLS BAS CONTROL - The Johnson Control YK-UNT-1126 building automation system controller is factory installed. Includes supply air sensor, return air sensor, dirty filter indicator switch, and air proving switch.
•CPC BAS CONTROL - The Computer Process Controls Model 810-3060 ARTC Advanced Rooftop building automation system controller is factory installed. Includes supply air sensor, return air sensor, dirty filter indicator switch and air proving switch.
•HONEYWELL BAS CONTROL - The Honeywell W7750C building automation system controller is factory installed. Includes air supply sensor, return air sensor, dirty filter indicator switch, and air proving switch.
•SMOKE DETECTORS - (supply air & return air) The smoke detectors stop operation of the unit by interrupting power to the control board if smoke is detected within the air compartment.
•COIL GUARD - Customers can purchase a coil guard kit to protect the condenser coil from damage. This is not a hail guard kit.
•STAINLESS STEEL HEAT EXCHANGER - For applications in corrosive environments, this option provides a full stainless steel heat exchanger assembly.
•STAINLESS STEEL DRAIN PAN - An optional rustproof stainless steel drain pan is available to provide years of trouble-free operation in corrosive environments.
•BOTTOM DRAIN CONNECTION - An optional bottom drain connection is available for inside the curb connections for applications in cold environments to reduce freezing drain lines.
•PHASE MONITORS - Designed to prevent unit damage. The phase monitor will shut the unit down in an out-of- phase condition.
•DIRTY FILTER SWITCH - This kit includes a differential pressure switch that energizes the fault light on the unit thermostat, indicating that there is an abnormally high pressure drop across the filters. Factory installed option or field installed accessory.
•HINGED FILTER DOOR/“TOOLLESS” BLOWER AND ACCESS PANELS (not hinged) - This option allows for easy access and maintenance.
NOTE:Knobs are shipped inside the unit to prevent shipping damage. These must be field installed for tool-less operation.
FIELD-INSTALLED ACCESSORIES
•SINGLE INPUT ELECTRONIC ENTHALPY ECONOMIZERS - Includes a slide-in / plug-in damper assembly with fully modulating spring-return motor actuator capable of introducing up to 100% outdoor air with nominal 1% leakage type dampers.
The enthalpy system contains one sensor that monitors the outdoor air and determines when the air is cool enough and dry enough to provide free cooling.
The rainhood is painted to match the basic unit and must be field-assembled before installing.
•MOTORIZED OUTDOOR AIR INTAKE DAMPER - Includes a slide-in / plug-in damper assembly with a 2- position, spring return motor actuator which opens to some pre-set position whenever the supply air blower is operating and will drive fully closed when the blower unit shuts down.
The rain hood is painted to match the basic unit and must be field assembled before installing.
•ELECTRIC HEATERS wired for single point power supply. These nickel chromium heater elements are provided with limit and automatic reset capability to prevent operation at excessive temperatures.
Unitary Products Group |
13 |
•ROOF CURBS - Eight and fourteen-inch high roof curbs provide a water-tight seal between the unit and the finished roof. These full perimeter curbs meet the requirements of the National Roofing Contractors Association (NRCA) and are shipped knocked-down for field assembly.
Roof curbs are designed to fit inside the base rails of the unit and include both a wood nailing strip and duct hanger supports.
•HIGH ALTITUDE NATURAL GAS - Burner orifices and pilot orifices are provided for proper furnace operation at altitudes up to 6,000 feet.
•PROPANE - Burner orifices, pilot orifices and gas valve parts are provided to convert a natural gas furnace to propane.
•HIGH ALTITUDE PROPANE - Burner orifices and pilot orifices are provided for proper furnace operation at altitudes up to 6,000 feet. This accessory supplements the basic propane conversion kit.
•LOW NOX KIT - Required to reduce the emission of nitrogen oxides below 40 nano grams per joule.
•POWER EXHAUST - Our single input economizer options are available with power exhaust. Whenever the outdoor air intake dampers are opened for free cooling, the exhaust fan will be energized to prevent the conditioned space from being over-pressurized during economizer operation.
The power exhaust option can only be used on bottom duct configurations.
TABLE 1: CAPACITY RATINGS - (ARI 210/240)1
|
|
EER2 |
SEER3 |
|
SOUND |
MODEL |
MBH |
CFM |
RATING |
||
|
|
|
|
|
(Db)4 |
DJ036 |
35.8 |
11.65 |
13.50 |
1200 |
84 |
DJ048 |
46.5 |
11.75 |
13.45 |
1600 |
83 |
DJ060 |
56.5 |
11.15 |
13.40 |
1800 |
81 |
1.80/67°F Indoor and 95°F outdoor.
2.EER = Energy Efficiency Ratio at full load - the cooling capacity in Btu’s per hour (Btuh) divided by the power input in watts, expressed in Btuh per watt (Btuh/watt).
3.SEER = Seasonal Energy Efficiency Ratio.
4.Rated in accordance with ARI 270 Standard.
036-21687-002-A-1105
•BAROMETRIC RELIEF DAMPER - This damper accessory can be used to relieve internal building air pressure on units with an economizer without power exhaust. This accessory includes a rain hood, a bird screen and a fully assembled damper. With bottom duct connections, the damper should be mounted over the opening in the return air panel. With horizontal ductwork, the accessory should be mounted on the return air duct.
•ENTHALPY ACCESSORY CONTROL KIT - This kit contains the required components to convert a single enthalpy economizer to dual enthalpy.
•BURGLAR BARS - Mount in the supply and return openings to prevent entry into the duct work.
•FLUE EXHAUST EXTENSION KIT - In locations with wind or weather conditions which may interfere with proper exhausting of furnace combustion products, this kit can be installed to prevent the flue exhaust from entering nearby fresh air intakes.
•CO2 SENSOR - Senses CO2 levels and automatically overrides the economizer when levels rise above the present limits.
•COIL GUARD - Customers can purchase a coil guard kit to protect the condenser coil from damage. This is not a hail guard kit.
•HAIL GUARD - Hail Guard kit is available to prevent unit from hail damage. This is a sloped hood that fits above the coil.
•GAS PIPING KIT - This kit supplies all necessary fittings and shut off valve.
TABLE 2: GAS HEAT RATINGS1
MODEL |
MBH |
MBH |
AFUE |
TEMP |
|
INPUT |
OUTPUT |
(%) |
RISE ºF |
||
|
|||||
DJ036N04 |
50 |
40 |
80.9 |
15 - 45 |
|
DJ036N08 |
100 |
80 |
80.5 |
40 - 70 |
|
DJ048N06 |
75 |
60 |
80.9 |
25 - 55 |
|
DJ048N10 |
125 |
100 |
80.3 |
45 - 75 |
|
|
|
|
|
|
|
DJ060N08 |
100 |
80 |
80.5 |
25 - 55 |
|
DJ060N10 |
125 |
100 |
80.3 |
35 - 65 |
1. All units are single-stage heating.
TABLE 3: 2 STAGE GAS HEAT RATINGS
MODEL1 |
MBH INPUT |
MBH OUTPUT |
STEADY STATE EFFICIENCY |
RISE |
MINIMUM HEATING |
|||||
1ST STAGE |
2ND STAGE |
1ST STAGE |
2ND STAGE |
1ST STAGE |
2ND STAGE |
MIN. |
MAX. |
AIRFLOW (CFM) |
||
|
||||||||||
DJ036D06 |
45 |
75 |
35.8 |
60.8 |
79.4 |
81.1 |
35 |
70 |
790 |
|
DJ036D10 |
69 |
115 |
55.2 |
92 |
80.0 |
80.2 |
55 |
90 |
950 |
|
DJ048D06 |
45 |
75 |
35.7 |
60.8 |
79.4 |
81.1 |
25 |
70 |
790 |
|
DJ048D10 |
75 |
125 |
60.4 |
100.6 |
80.5 |
80.5 |
45 |
75 |
1230 |
|
DJ060D06 |
45 |
75 |
35.8 |
60.8 |
79.4 |
81.1 |
35 |
70 |
1010 |
|
DJ060D10 |
75 |
125 |
60.4 |
100.6 |
80.5 |
80.5 |
45 |
75 |
1230 |
1. Models are 3Ø only.
14 |
Unitary Products Group |
036-21687-002-A-1105
TABLE 4: DJ036 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED INLET)
UNIT DESCRIPTION / MODEL |
|
|
DJ036 / 3 Ton / Belt Drive |
|
|
||||
CONFIGURATION |
|
|
|
Horizontal Ducted Inlet |
|
|
|
||
Indoor Blower Speed (RPM) |
630 |
631 |
879 |
885 |
|||||
Blower Static Pressure (IWG) |
0.2 |
0.3 |
0.2 |
0.7 |
|||||
Airflow (CFM) |
1116 |
928 |
1979 |
1020 |
|||||
Blower Motor BHP |
0.41 |
0.37 |
0.76 |
0.53 |
|||||
|
ID Blower |
Cooling |
ID Blower |
Cooling |
ID Blower |
|
Cooling |
ID Blower |
Cooling |
Octave Center Freq. |
Operation2 |
Operation2 |
|
Operation2 |
Operation2 |
||||
|
Only (dB) |
(dB) |
Only (dB) |
(dB) |
Only (dB) |
|
(dB) |
Only (dB) |
(dB) |
|
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
63 |
80 |
82 |
80 |
82 |
78 |
|
83 |
81 |
85 |
125 |
76 |
77 |
76 |
77 |
82 |
|
83 |
81 |
82 |
250 |
56 |
59 |
56 |
60 |
60 |
|
61 |
58 |
60 |
500 |
50 |
50 |
49 |
50 |
54 |
|
54 |
51 |
52 |
1000 |
40 |
43 |
39 |
42 |
49 |
|
50 |
44 |
45 |
2000 |
41 |
42 |
40 |
42 |
49 |
|
49 |
43 |
44 |
4000 |
41 |
41 |
41 |
41 |
49 |
|
49 |
41 |
41 |
8000 |
45 |
45 |
45 |
45 |
47 |
|
47 |
45 |
45 |
1.Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment.
2.Cooling Operation – ID blower, compressor and outdoor fan operating.
3.Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).
4.Test duct termination is flush with reverberation room wall.
5.Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.
TABLE 5: DJ036 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED DISCHARGE)
UNIT DESCRIPTION / MODEL |
|
|
DJ036 / 3 Ton / Belt Drive |
|
|
|||
CONFIGURATION |
|
|
Horizontal Ducted Discharge |
|
|
|||
Indoor Blower Speed (RPM) |
630 |
631 |
879 |
885 |
||||
Blower Static Pressure (IWG) |
0.2 |
0.3 |
0.2 |
0.7 |
||||
Airflow (CFM) |
1116 |
928 |
1979 |
1020 |
||||
Blower Motor BHP |
0.41 |
0.37 |
0.76 |
0.53 |
||||
|
ID Blower |
Cooling |
ID Blower |
Cooling |
ID Blower |
Cooling |
ID Blower |
Cooling |
Octave Center Freq. |
Operation2 |
Operation2 |
Operation2 |
Operation2 |
||||
|
Only (dB) |
(dB) |
Only (dB) |
(dB) |
Only (dB) |
(dB) |
Only (dB) |
(dB) |
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
63 |
80 |
84 |
80 |
83 |
85 |
87 |
84 |
87 |
125 |
74 |
77 |
74 |
76 |
80 |
82 |
80 |
83 |
250 |
58 |
61 |
58 |
61 |
68 |
68 |
63 |
65 |
500 |
48 |
51 |
47 |
50 |
58 |
58 |
53 |
54 |
1000 |
41 |
45 |
39 |
43 |
55 |
55 |
49 |
50 |
2000 |
39 |
41 |
37 |
39 |
53 |
53 |
46 |
47 |
4000 |
41 |
41 |
38 |
38 |
55 |
55 |
49 |
49 |
8000 |
45 |
45 |
44 |
44 |
52 |
53 |
47 |
47 |
1.Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment.
2.Cooling Operation – ID blower, compressor and outdoor fan operating.
3.Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).
4.Test duct termination is flush with reverberation room wall.
5.Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.
Unitary Products Group |
15 |