tekmar 529 Quick Start

tekmarNet®2 Thermostat 529
Location1. Remove Mounting Base2.
Interior
Wall
5 feet
1.5 m
Exterior
Wall
Install Mounting Base3. Wiring4.
Zoning
Q 529
12/11
Replaces: 01/11
Plate 007
Thermostat
Base
Switch Settings5.
Switch
1
2
3
4
Adaptor
Thermostat
Base
OR
Switch
Box
Position
ON
OFF OFF No setback schedule response.
ON
OFF OFF No scene response.
ON
OFF
ON Not used
OFF Not used
Action
SETBACK Allow thermostat to respond to
available schedule. Requires Timer 033.
SCENE Allow thermostat to respond to scenes. Requires User Switch 479.
LOCK Locked to ‘User’ access level. Set to Lock when installation completed. UNLOCK Unlock to access all settings. Set to Unlock during installation.
Wall
Two Stage Method 2
W R
Heating Equipment
Two Stage Method 1
tN2
tN2
Zone 1
Zone 1
Stage 1 Stage 2
tN2tN2
Zone 2
Close Thermostat6.
pivot
tab
6
W2
5
Rh
For instructions see brochure Use at least 65°C conductors
No Power
tN21tN2
Sensor
2
34
529
ON
Switch Settings:
1023-03
Scene
Lock
Setback
Unlock
Off
Off
1234
12 34
Not used
Not used
Mmm YYYY
Meets Class B:
Canadian ICES
tNt 529
Two Stage Heat
Relays: 24V (ac) 2A
Switch Setting Location
Slab Sensor 079, or
Outdoor Sensor 070, or
Indoor Sensor 076, 077, 084
Lot # 12345
FCC Part 15
1 of 2 © 2010 Q 529 - 12/11
User Interface7.
Critical Settings8.
The following settings are essential to the successful operation of the system. Important Note: Set switch setting #3 and tekmarNet® system control to Unlock to change Access level to Installer. Return
to Lock setting once installation has been completed.
Press
• Press and hold down both the and buttons for 2 seconds to change from one step to the next.
• Release both buttons once the step has been reached.
+
• Press the or the button to change the setting, if available.
• Press and hold down both the and buttons for 2 seconds to go to the next step, OR
Toget her
• After 10 seconds of no button activity, the display goes back to normal operation.
Display Range Access Description Set to
ROOM SENSOR
Select whether the built-in air temperature sensor is
On or Off
Default = On
Installer
on or off. Available when:
A floor sensor or room sensor is installed on the auxiliary sensor input.
AUXILIARY SENSOR
Off, Room,
Outdoor,
Floor, Floor
dSP
Installer
Select the type of auxiliary sensor. Floor dSP = Show floor sensor reading in upper
number field. Available when: Auxiliary sensor automatically detected.
HEAT 1 SUPPLY PUMP
Select whether the system supply pump should turn
OFF, On
Default = On
Installer
on during a call for first stage heat, or be off to allow a zone group pump per manifold. Available when:
A reset control is present on the tekmarNet® system.
HEAT 1 SUPPLY PUMP DELAY
OFF, On
Default = Off
Installer
Select whether or not the system supply pump should be delayed by 3 minutes before coming on (for thermal motor or wax actuator).
HEAT 2 SOURCE
bLr,
M1, M2, or
M3, otH
Default = bLr
Installer
Select whether the second stage heat is on the boiler bus (bLr), mix 1 (M1), mix 2 (M2), or mix 3 (M3) bus, or non-hydronic other (otH). Available when:
A reset control is present on the tekmarNet There is an active room sensor.
®
system.
For a full list of settings and operational details, please refer to the thermostat Installation and Operation Manual (D529) included with this thermostat or download the brochure from www.tekmarcontrols.com
tekmar Control Systems Ltd., Canada, tekmar Control Systems, Inc., U.S.A.