The thermostat’s display has four distinct fields. These fields are the Menu field, the Item
field, the Number field and the Status field. The four buttons on the face of the thermostat are
used to navigate through the menus and items to view and / or adjust the desired settings.
The thermostat operation is based on cycles per hour.
The number of cycles per hour is adjustable through
the HEAT CYCLE and COOL CYCLE settings in the
Adjust menu. During each cycle that heating or cooling
is required, the thermostat turns on the Heat or Cool
relay(s) for a calculated amount of time. This amount of
time is the “on time”. The on time is calculated based on
the requirements of the zone. If the zone requires more heating or cooling, the appropriate
on time is increased. If the zone requires less heat or cooling, the appropriate on time is
reduced.
In order to prevent short cycling of the heating relay(s), the thermostat ensures that the
relay(s) remains on or off for a minimum amount of time. In order to prevent short cycling
of the Cool relay, the minimum cooling on time and minimum cooling off time settings are
adjusted in the Adjust menu of the 512.
An Auto Cycle setting is available for both the heating cycle and the cooling cycle. This
setting allows the thermostat to determine the best number of cycles per hour that balances
both temperature swings and equipment cycles.
Cycles Per Hour
ononon
offoff
⇐ Cycle Length ⇒
Time
off
EARLY START (
)
Heating - The early start function for heating
ensures that the zone is up to the proper
70°F (21°C)
62°F (17°C)
Early Start OFF
temperature at the beginning of each period.
The thermostat learns the recovery rate over
multiple setback events in order to determine
the proper lead time for the zone. If both an
air sensor and a slab sensor are used, the
lead time is the greater of the air sensor’s or
70°F (21°C)
62°F (17°C)
Early Start ON
UnOccupied
Occupied
the slab sensor’s requirements.
Cooling - The early start function, when used with cooling, allows the cooling system to
turn on 30 minutes prior to the beginning of a period that requires cooling.
NOTE: The Early Start feature occurs when the schedule changes from a low temperature
to a higher temperature.
The thermostat has a single built-in sensor to measure air temperature at the thermostat. In
addition to the built-in sensor, the thermostat has terminals to connect up to two separate
sensors. These sensors can be either indoor sensors, slab sensors, a remote sensor, or
an outdoor sensor.
Indoor Sensor
An indoor sensor is used to measure the air temperature in the zone that the thermostat
is controlling. The temperature being read by the indoor sensor is used in the calculations
of the on times for the relay(s) in the thermostat. Either one or both of the auxiliary sensor
inputs can be configured for indoor sensors. This setting is made through the Adjust menu
of the thermostat. If more than one sensor, either the built-in sensor or an auxiliary sensor
set as an indoor sensor, is being used to measure the zone temperature, the temperature
of the active sensors is averaged and used to calculate the on time of the relay(s).
Slab Sensor
A slab sensor is used to measure the slab temperature in the zone that the thermostat
is controlling. The temperature being read by the slab sensor is used in the calculations
of the on time for the Heat relay and allows the thermostat to operate the slab between
the slab minimum and slab maximum settings. If more than one slab sensor is used, the
slab temperatures are averaged by the thermostat.
Remote Sensor
A single remote sensor can be connected to the thermostat. The temperature
measured by a remote sensor does not affect the on time of the relays and is only
used for display purposes.
Outdoor Sensor
A single outdoor sensor can be connected to the thermostat. The temperature measured
by an outdoor sensor does not affect the on time of the relays and is only used for display
purposes.
ACCESS LEVELS
The tekmar Programmable Thermostat has two
access levels. These access levels restrict the
number of items available in the menus of the
Made in Canada
Meets Class B:
Canadian ICES
thermostat. The two access levels are User and
Installer. This selection is made using the DIP
switch located on the circuit board inside the
FCC Part 15
02
938-
512
thermostat.
A
Switch Settings:
e/Heat-Cool
Installer/User
2 Stag
60 Hz 3 VA
V (ac) 2
24
Power: 24 V ± 10%
Relay:
Class 2
The Installer access level allows the installer to
adjust all of the settings in the thermostat including
those required to match the thermostat to the
mechanical system and the devices used.
The User access level allows the end user to
adjust the time, temperatures and schedules used
by the thermostat.
The two stage mode of operation is selected using the DIP switch located on the circuit
board inside the thermostat.
In cases where a one stage heating system can not provide sufficient heat under all
conditions, a second stage of heat can be added to supplement the first stage. A two stage
system therefore has one thermostat controlling two output relays.
Two Stage Logic
The temperature in a two stage zone is controlled by varying the on time of the Heat 1
and Heat 2 relays during a cycle. Under light loads, the Heat 1 relay is cycled on and
off. As the load increases, the Heat 1 relay on time is increased until it reaches the
maximum of the cycle length or, if a slab sensor is used, the slab temperature reaches
the slab maximum setting. The Heat 2 relay is then cycled and its on time is increased
as the load increases. When the heating load decreases, the on time of the Heat 2
relay is reduced until the Heat 2 relay is turned off completely. The thermostat then
reduces the on time of the Heat 1 relay
.
NOTE: When using a slab sensor, the Heat 2 relay may be on while the Heat 1 relay is
off if the slab temperature has reached the slab maximum setting.
Air Sensor(s) Only Operation
When operating with only an air sensor, the on times for the Heat 1 and Heat 2 relays
are calculated to satisfy the requirements of the air sensor.
Slab Sensor Only Operation
When operating with only a slab sensor, the on times for the Heat 1 and Heat 2 relays
are calculated to satisfy the requirements of the slab sensor. The thermostat operates to
maintain the slab at the minimum slab temperature setting
.
NOTE: Operating with only a slab sensor can lead to either overheating or underheating
of the space.
Air and Slab Sensor Operation
When operating with both air and slab sensors, the thermostat calculates an on time for
the Heat 1 relay to satisfy the slab sensor’s requirements and on times for the Heat 1
and Heat 2 relays to satisfy the air sensor’s requirements. The thermostat operates the
Heat 1 relay for the longer of these two on times.
While the minimum slab temperature is satisfied, the on times of the Heat 1 and Heat 2
relays are calculated to satisfy the air temperature requirements
.
During heavy loads, the maximum slab temperature setting limits the on time of the Heat
1 relay. In this situation, the Heat 2 relay may be on while the Heat 1 relay is off.
NOTE: During light heating loads, overheating can occur due to the minimum slab
temperature requirements
.
Mode
Heat In the heat mode, the Heat 1 and Heat 2 relays are operated to satisfy the
temperature requirement of the zone
.
Off In the Off mode, the Heat 1 and Heat 2 relays are not operated.
NOTE: If an air or slab sensor is active in the Off mode, a freeze protection is enabled
that allows the relays to be operated to keep the zone above 35°F (2°C).
The Heat / Cool mode of operation is selected using the DIP switch located on the circuit
board inside the thermostat
.
Air Sensor(s) Only Operation
When operating with only an air sensor, the on times of the Heat 1 relay and the Cool
relay are calculated to satisfy the requirements of the air sensor
.
Slab Sensor Only Operation
When operating with only a slab sensor, the on time of the Heat 1 relay is calculated to
satisfy the requirements of the slab sensor. The thermostat operates to maintain the slab
at the minimum slab temperature setting
.
NOTE: When operating with only a slab sensor, the Cool relay does not operate.
Operating with only a slab sensor can lead to either overheating or underheating of the
space.
Air and Slab Sensor Operation
When operating with both air and slab sensors, the thermostat calculates an on time
for the Heat 1 relay to satisfy the slab sensor’s requirements and an on time to satisfy
the air sensor’s requirements. The Heat 1 relay operates for the longer of these two
on times. The thermostat also calculates an on time for the Cool relay to satisfy the air
sensor’s requirements. In this situation, heating and cooling can happen at the same
time to prevent the space from overheating. This is most likely to occur when the slab is
operating at the slab minimum temperature
.
While the minimum slab temperature is satisfied, the Heat 1 relay on time is calculated
to satisfy the air temperature setting. However, the maximum slab temperature setting
limits the Heat 1 relay on time when the slab temperature becomes too warm. In this
situation, underheating can occur in the space.
Mode
Auto In the Auto mode, the thermostat automatically switches between heating and
cooling the space. However, the heating operation has priority over the cooling
operation. In this mode, the minimum slab temperature is maintained even when
the thermostat is cooling the air.
Heat In the Heat mode, the Heat 1 relay is operated to satisfy the heating
temperature requirement of the zone and cooling is disabled.
Cool In the Cool mode, the Cool relay is operated to satisfy the cooling temperature
requirement of the zone and heating is disabled. If a slab sensor is used, the slab
minimum is ignored.
Off In the Off mode, the Heat 1 and Cool relays are not operated.
NOTE: If an air or slab sensor is active in the Off mode, a freeze protection is enabled that
allows the Heat 1 relay to be operated to keep the zone above 35°F (2°C).
In order to prevent frequent changes between heating and cooling, the thermostat
has a Cooling Interlock setting. Once the Heat 1 relay has been off for a minimum of
one heating cycle or the length of the Cooling Interlock, (whichever is longer) cooling
is permitted.
Temperature Interlock
When in the Auto mode, the cooling temperature is limited to 3°F (1.5°C) above the
heating temperature. If the cooling temperature is set below the heating temperature,
the thermostat automatically adjusts the cooling setpoint.
When operating in the Cool mode, there is no interlock between the heating and cooling
temperature.
View Menu (1 of 1)
ROOM TARGET
The current desired air temperature for the space. This item is
only available in the Installer access level.
(Must have an active air sensor.)
ROOM
The current air temperature for the space.
(Must have at least one active air sensor. This is the average of
all active air sensors.)
OUTDOOR
The current temperature at the outdoor sensor .
(Sens 2 must be set to Out.)
SLAB
The current slab temperature.
(Must have an active slab sensor. If two slab sensors are present,
this is the average temperature.)