tekmar 279 User Manual

- Data Brochure
Steam Control 279
D 279
05/10
The tekmar Steam Control 279 can operate a single on-off steam boiler or an on-off steam valve using outdoor reset. The
control determines the on time of the boiler or valve based on the measured outdoor temperature and settings entered by the installer. A large LCD displays the current status and operating temperatures.
CSA approved for use in USA and Canada
Outdoor Reset
Manual Override
Includes Outdoor Sensor
Includes Condensate Sensor
Large LCD Display Optional Indoor Sensors
DHW Tankless Coil Operation
Warm Weather Shut Down
Built-in Programmable Timer
24 Hour, 5-1-1, 7 Day Schedule
Two or Four Schedule Events Per Day
Two Alert Level Relays
Input
115 V (ac)
Power Supply
Menu Item
Steam Control 279
One Stage
2N3
4
1
Power
Alert 1 Boiler
L
STATUS Establishing Steam Heat Cycle Lockout Differential DHW Tankless Coil Heating
6785
Alert 2
LowHigh
Average Indoor S2 Indoor S1
Installer
User
Condensate Sensor DHW Tankless Coil Sensor Setback
Off
Test
off red red
For manual operation, press and hold Test button for 3 seconds.
Com Sen
Meets Class B: Canadian ICES FCC Part 15
16
15
14
Out
Cdn
Sen
Sen
Made in Canada By tekmar Control Systems Ltd. tektra 969-04
Power 115 V ±10% 50/60 Hz 3.5 VA Relays 230 V (ac) 5 A 1/3 hp, pilot duty 240 VA
Signal wiring must be rated at least 300 V.
Do not apply power
12
11
10
Com Sen
9
Com Sen
DHW
Sen
13
Indr
Indr
S2
S1
not testing testing testing paused
Date Code
H2046A
Input
Outdoor Sensor
Included
Output
High Priority
Alert
Output
Low Priority
Alert
OR
Output
Boiler or On/Off
Steam Valve
M
Input
Universal Sensor
Optional
Input
Indoor Sensor
Optional
Input
Indoor Sensor
Optional
Input
Universal Sensor
Included
1 of 24 © 2010 D 279 - 05/10
How to Use the Data Brochure
This brochure is organized into four main sections. They are: 1) Sequence of Operation, 2) Installation, 3) Control Settings, and 4) Testing and Troubleshooting. The Sequence of Operation section has fourteen sub-sections. We recommend reading ‘Section A: General’ of the Sequence of Operation, as this contains important information on the overall operation of the control. Then read the sub sections that apply to your installation.
Table of Contents
User Interface ............................................................... 2
Display and Symbol Description ...................................3
Definitions .....................................................................4
Sequence of Operation .................................................4
General ................................................................. 4
Establishing Steam ...............................................4
Heating Cycle .......................................................6
Lockout Differential ...............................................7
Optional Indoor Sensors .......................................8
Built-in Timer ........................................................8
Programmable Schedule ......................................8
Warm Weather Shut Down ...................................8
Optimum Start ......................................................9
Boost ....................................................................9
Limited Occupied ..................................................9
The Control Settings section (starting at Switch Settings) of this brochure describes the various items that are adjusted and displayed by the control. The control functions of each adjustable item are described in the Sequence of Operation.
Alert Relay Operation ...........................................9
Domestic Hot Water Tankless Coil ..................... 10
Installation .................................................................. 10
Cleaning the Control ................................................... 14
Switch Settings ........................................................... 15
Display Menus ............................................................ 16
View Menu .......................................................... 16
Adjust Menu ........................................................ 17
Time Menu .......................................................... 19
Schedule Menu ................................................... 20
Testing the Control ......................................................20
Troubleshooting .......................................................... 21
Error Messages ..........................................................22
Technical Data ............................................................ 24
Limited Warranty ........................................................24
User Interface
The control uses a Liquid Crystal Display (LCD) as the method of supplying information. Use the LCD in order to setup and monitor the operation of the system. The control has four push buttons (Menu, Item, , ) for selecting and adjusting settings. As the control is programmed, record the settings in the ADJUST Menu table which is found in the second half of this brochure.
Menu
All of the items displayed by the control are organized into four menus: View, Adjust, Time, and Schedule. These menus are listed on the top of the display (Menu Field). To select a menu, use the Menu button. By pressing and releasing the Menu button, the display will advance to the next available menu. Once a menu is selected, there will be a group of items that can be viewed within the menu.
Note: The TIME and SCHEDULE menus are not available when Setback is turned off.
Menu Item
Item
The abbreviated name of the selected item will be displayed in the item field of the display. To view the next available item, press and release the Item button. Once you have reached the last available item in a menu, pressing and releasing the Item button will return the display to the first item in the selected menu.
The items can be quickly scrolled through by holding the Item button and then pressing the button. To rapidly scroll through the items in the reverse order, hold the Item button and press the button.
Menu Item
Adjust
To make an adjustment to a setting in the control, begin by selecting the appropriate menu using the Menu button. Then select the desired item using the Item button. Finally, use the and/or button to make the adjustment.
Additional information can be gained by observing the Status field of the LCD. The status field will indicate which of the control’s outputs are currently active. Most symbols in the status field are only visible when the VIEW Menu is selected.
© 2010 D 279 - 05/10 2 of 24
Menu Item
Display
°°F°
Menu Field
Displays the
current menu
Item Field
Displays the current
item selected.
Buttons
Selects Menus, Items
and adjusts settings
Symbol Description
Number Field
Displays the current value of the selected item
Menu Item
Status Field
Displays the current status of the control’s inputs, outputs and operation
STATUS Establishing Steam Heat Cycle Lockout Differential DHW Tankless Coil Heating
C
POINTER
Displays the control operation as indicated by the text.
°F, °C
Units of measurement.
OCCUPIED SCHEDULE
Displays when the control is in the Occupied event period.
UNOCCUPIED SCHEDULE
Displays when the control is in the Unoccupied event period.
BURNER
Displays when the boiler contact is turned on.
WARNING 1 2
Displays when an error exists or when a limit has been reached. A 1 indicates a high level alert, a 2 indicates a low level alert.
USER ACCESS LEVEL
Displays when the Installer/User Switch Setting is set to the User access level.
STEAM ESTABLISHED
Displays once the condensate sensor reaches a temperature sufficient for steam to reach the furthest radiator.
BOOST
Displays while the boost feature extends the boiler on time to allow recovery after night setback.
OPTIMUM START
Displays while the Optimum Start feature extends the boiler on time to allow recovery after night setback.
WWSD
Displays while the control is in Warm Weather Shut Down.
3 of 24 © 2010 D 279 - 05/10
STATUS Establishing Steam
Defi nitions
The following defined terms and symbols are used throughout this manual to bring attention to the presence of hazards of various risk levels, or to important information concerning the life of the product.
Caution: Refer to accompanying documents.
Sequence of Operation
General Section A
Powering up the control
When the control is powered on, all segments in the LCD are turned on for 2 seconds. Next, the control displays the control type number in the LCD for 2 seconds. Next, the software version is displayed for 2 seconds. Last, the control enters into the normal operating mode.
Boiler Contact Operation
In single on-off steam boiler applications, the control uses the boiler contact to connect to the thermostat terminals (T-T) on the boiler. The pressure control and all other safety devices and circuits must continue to be wired in series to the burner circuit. The boiler contact on the control is used to turn on or off the steam boiler burner.
In steam valve applications, the boiler contact on the control is used to power the valve motor to open the valve. When power is removed, the valve must close.
Status
The control has a status field on the right hand side of the control. A pointer is shown in the status field once the boiler contact is turned on. The pointer indicates at which point of the steam heating system cycle the control is currently operating at.
The steps are as follows:
Establishing Steam
Heat Cycle
Lockout Differential
DHW Tankless Coil Heating
STATUS Establishing Steam Heat Cycle Lockout Differential DHW Tankless Coil Heating
Each of these steps are described in detail in the following sections.
Establishing Steam Section B
In steam heating systems, there is a time delay between when the steam boiler or steam valve is turned on and when the steam finally reaches the furthest radiator in the system. It is important for the control to determine how long this time delay is in order to ensure proper heating in all rooms. When heat is required, the control activates the boiler relay but does not consider the heating cycle to start until steam has been established at the furthest radiator. While the control is waiting to establish steam, the Status field will have a pointer indicating Establishing Steam.
The control can use one of two methods to determine the time to establish steam.
© 2010 D 279 - 05/10 4 of 24
Condensate Return Sensor
The Universal Sensor 071 included with the control can be used to measure the temperature of the condensate return pipe. In a one pipe system, it is recommended to install the sensor on the bottom of the pipe just before it enters the last radiator. In a two pipe system, it is recommended to install the Condensate Sensor on the bottom of the condensate return pipe of the radiator furthest from the boiler. In cases where access to the furthest radiator is not possible, an alternative is to locate the sensor on the bottom of the condensate return pipe in the mechanical room. Once the condensate sensor is installed, ensure the Condensate Sensor/Off Switch Setting to Condensate Sensor. The measured condensate return temperature reading is visible in the View menu.
The Adjust menu includes a Steam Established setting that
Establishing Steam
(warm-up period)
Establishing Steam
(warm-up period)
delays the start of the heating cycle until the condensate sensor has reached a set temperature.
One method to set the Steam Established setting requires two people with two-way radios. One person is at the control location; the other person is at the furthest radiator
One Pipe System:
Last Radiator
location. The steam system can be manually started using the Max Heat feature. Once the furthest radiator starts to get steam, exit the Max Heat feature and view the Condensate temperature in the View menu. The measured condensate return temperature can be entered as the Steam Established setting.
Most Distant Radiator
Two Pipe System:
Main
Air Vent
OK
Condensate Return Sensor Location
Off
Boiler
Operation
220°F 210°F ­200°F ­190°F ­180°F ­170°F ­160°F -
Condensate Return
Temperature
150°F ­140°F -
Best
-
(warm-up period)
Establishing Steam
on
Supply Main
15 minutes
on time
est.
Steam established
temperature setting
Thermostatic
Radiator Vent
Return
Air Vent
Steam established - start cycle
Boiler OffBoiler On
60 minute cycle 60 minute cycle
off
Boiler On
15 minutes
on time
(warm-up period)
Establishing Steam
est.
on
Tra p
Best
Supply
Air Vent
Float &
Thermostatic
Tra p
Condensate Return
Sensor Location
Boiler Off
Steam established - start cycle
45 minutes off time45 minutes off time
off
25% on time with Condensate Return Sensor and ‘Steam Established’ set to 170°F
OK
Minimum On Time
In cases where a condensate return sensor cannot be installed, a Minimum On Time can be set to account for the establishing steam time period. Setting a Minimum On Time for a steam system can be problematic because a system takes more time to reach operating temperature from a cold start than when it is hot from a previous cycle.
5 of 24 © 2010 D 279 - 05/10
To set the Minimum On Time, manually start the steam system using the Max Heat feature and at the same time, start a stopwatch timer. Measure the amount of time required for steam to reach the furthest radiator. Then, exit the Max Heat feature and enter the recorded time as the Minimum On Time setting.
Heating Cycle - Heating Curve Section C
Boiler Cycled
On/Off
Boiler On 100% of Heating Cycle
C
B
75% 65%
42%
Room @ 70°F
Room @ 55°F
Room @ 75°F
-
Boiler On 100% of Heating Cycle
-
-
-
-
-
-
-
-
-
­0 (°F)102030405060
100% 90% 80% 70% 60% 50% 40% 30% 20% 10% 0%
Outdoor reset is a method of operating a heating system based on the fact that the rate at which a building loses heat to the outdoor environment is mostly dependent on the surrounding outdoor air temperature. As the outdoor temperature gets colder, the heat loss of the building increases at a proportional rate. This relationship between heat loss and colder outdoor temperatures is called a heating curve.
Outdoor = 50°F
Outdoor = 30°F
Outdoor = 10°F
A = Indoor Design B = Outdoor Design C = Boiler Design %
A
70
80
C
Boiler Cycled
On/Off
B
Outdoor Air Temperature
Percent On Time Per Heating Cycle
Heat Load = 20%
Boiler On Time = 12 min
60 min
Heat Load = 60%
Boiler On Time = 36 min
60 min
Heat Load = 100%
Boiler On Time = 60 min
60 min
In order to calibrate the control to the heat loss rate of a particular building, the installer is required to enter the following heating curve settings:
Indoor Design
The Indoor Design is the starting point of the heating curve. When the measured outdoor air temperature matches the Indoor Design setting, the control calculates a 0% on time is required for heating the building. The factory default is to start the heating curve at 70°F (21°C).
Outdoor Design
The Outdoor Design is the end point of the heating curve. When the measured outdoor air temperature matches the Outdoor Design setting, the control calculates the boiler on time to be at the Boiler Design % setting. The Outdoor Design should be set to the average coldest annual temperature recorded in the building area.
Boiler Design %
The Boiler Design % is the percent output capacity of the boiler or steam system required to heat the building when the measured outdoor air temperature matches the Outdoor Design setting. The factory default is 100%. If the building envelope has been upgraded to improve the building insulation, the existing steam boiler or steam system may be oversized for the building. In these cases, the Boiler Design % can be reduced to fine tune the heating curve.
Room (Occupied and Unoccupied)
The Room setting is the desired temperature of the building. When a setback schedule is selected, there is a Room Occupied temperature setting and a Room Unoccupied temperature setting. When the setback schedule is turned off, only the Room setting is available.
When an indoor sensor(s) is not connected to the control, the Room setting operates as a parallel shift of the heating curve. This allows fine tuning of the heating system. If the Room setting is set above the Indoor Design setting, the entire heating curve is shifted higher, resulting in longer percent on times being calculated. Similarly, if the Room setting is set below the Indoor Design setting, the entire heating curve is shifted lower, resulting in shorter percent on times being calculated.
-
100%
-
90%
-
75% 65%
42%
Room @ 75°F
Room @ 70°F
Room @ 55°F
7080
Outdoor Air Temperature
2030405060
-
-
-
-
-
-
-
­0 (°F)10
80% 70% 60% 50% 40% 30% 20% 10% 0%
Percent On Time Per Heating Cycle
When an indoor sensor(s) is connected to the control, the Room setting becomes a Room Target temperature. The control measures the current air temperature in the room using the indoor sensors. The control then automatically shifts the heating curve so that the measured room temperature reaches the Room Target temperature.
© 2010 D 279 - 05/10 6 of 24
Heating Cycle - Cycle Length Section D
30 minutes
on time
30 minutes
off time
30 minutes
on time
30 minutes
off time
15 minutes
on time
15 minutes
off time
15 minutes
on time
15 minutes
off time
15 minutes
on time
15 minutes
off time
15 minutes
on time
15 minutes
off time
Establishing Steam
(warm-up period)
Lockout Period
Establishing Steam
(warm-up period)
Lockout Period
The Adjust menu includes a setting called Cycle that determines how often the heating system will run. During each heating cycle the boiler is turned on once, and the boiler is turned off once. Each building has a natural heat up and a cool off rate. This is determined by many factors such as the size and length of runs in the steam heating system, the size and mass of the radiators, and the heat loss of the building. The factory default is 60 minutes. When using optional Indoor Sensors, an automatic setting is available that allows the control to learn the natural temperature swing of the building. If the optional Indoor Sensors are not used, then the only method of adjustment is trial and error by the installer.
50% On Time With a 30 Minute Heating Cycle
Off
Boiler
Operation
Boiler On
15 minutes
on time
30 minute cycle
Boiler Off
15 minutes
off time
On Off On Off
15 minutes
on time
30 minute cycle 30 minute cycle 30 minute cycle
15 minutes
off time
50% On Time With a 60 Minute Heating Cycle
Off On
Boiler
Operation
Boiler On
30 minutes
on time
Boiler Off
30 minutes
off time
60 minute cycle
The control is designed to operate on/off steam boilers or steam valves. These systems can only produce heat at a fixed rate (on = 100%, off = 0%). In order to match the heat loss of the building, the steam heating system must be cycled on and off. To determine the boiler on time, the control uses the percent on time required by the heating curve and multiplies this by the heating cycle time. While operating in the heating cycle, the Status field will have a pointer indicating Heat Cycle.
Example:
When the outdoor temperature is 32°F (0°C), the heating curve may determine a 50% on time is required. If the heating cycle is 60 minutes, then the boiler on time is: Boiler On Time Per Heating Cycle = 0.5 x 60 minutes = 30 minutes.
On Off
15 minutes
on time
On Off
15 minutes
off time
30 minutes
on time
15 minutes
60 minute cycle
on time
30 minutes
15 minutes
off time
off time
On
Lockout Differential Section E
The Adjust menu includes a setting called Lockout Differential. When a condensate return sensor is present, a lockout differential can be set to ensure that any remaining steam in the system condenses and the condensate has time to return to the boiler. This increases the efficiency of the system by removing the latent heat of the steam remaining after the burner is shut down, and lengthening the cycle so that remaining heat is allowed to radiate into the building.
The lockout differential is the number of degrees the condensate return sensor temperature must fall below the steam established setting before the control can operate
Boiler OffBoiler On Boiler Off
Steam established - start cycle
15 minutes
on time
Boiler
Operation
220°F ­210°F -
7 of 24 © 2010 D 279 - 05/10
200°F ­190°F ­180°F ­170°F ­160°F ­150°F ­140°F -
Condensate Return Temperature
45 minutes off time 45 minutes off time
60 minute cycle 60 minute cycle
off
30°F Lockout Differential Setting
Steam established
temperature setting
the heating system for the next cycle. During the lockout differential, the heating system is held off, and the Status field will have a pointer indicating Lockout Differential. The factory default is a 25°F lockout differential.
There is no exact method to set the Lockout Differential for a particular building; it is a process of trial and error. If the building tends to over heat, the lockout differential should be increased to allow the steam system to cool down further before starting the next cycle. If the building tends to under heat, the lockout differential should be decreased to allow the next heating cycle to start sooner.
Boiler On
Steam established - start cycle
15 minutes
on time
off
Lockout Period
(warm-up period)
Establishing Steam
Steam Established
on on
Lockout Period
(warm-up period)
Establishing Steam
Optional Indoor Sensors Section F
Multiple indoor sensors can be added to improve the temperature accuracy within the building. Available indoor sensors include the 076, 077 and 084.
Indoor Sensors 084, 077 and 076
The control allows two indoor sensors to be directly connected to the control. Once an indoor sensor is connected to the indoor sensor S1 input, the Indoor S1/Off switch setting must be set to S1. Likewise, once an indoor sensor is connected is connected to the S2 input, the Indoor S2/Off switch setting must be set to S2.
When indoor sensor 1 is present, the Room 1 temperature is visible in the View menu. Likewise, when indoor sensor 2 is present, the Room 2 temperature is visible in the View menu. Also shown in the View menu is the current Room Target temperature. The room target can be changed by adjusting the Room Occupied or Room Unoccupied setting in the Adjust menu.
Should additional indoor sensors be desired, a square number (4, 9, 16, etc.) of sensors can be wired in series­parallel to a single indoor sensor input.
To Indoor Sensor Input
Series - Parallel
Wiring
When using two indoor sensor inputs, the control can operate either based upon an average of the two temperature measurements or the control can operate on the lowest of the two temperature measurements.
Temperature Averaging
To operate the steam system based upon the average of the two indoor sensor temperature measurements, set the Average/Off switch setting to Average.
Lowest of Two Temperatures
To operate the steam system based upon the lowest of the two indoor sensor temperature measurements, set the Average/Off switch setting to Off.
Built-in Timer Section G
The control includes a built-in time clock that is turned on once the Setback/Off switch setting is set to Setback. The time is set in the Time menu. The clock can be set to use either 12 or 24 hour time.
Programmable Schedule Section H
The control includes a programmable schedule that is turned on once the Setback/Off switch setting is set to Setback. The programmable schedule is set in the Schedule menu. The schedule can be repeated on a 24 hour, 5-1-1, or 7 day schedule. Each schedule allows a time to be set
for the Occupied event and another time to be set for the Unoccupied event. Should it be desired to skip an Occupied or Unoccupied event, set the event time to --:--, which can be found between 11:50 PM (23:50) and 12:00 AM (0:00).
Warm Weather Shut Down Section I
The control includes a Warm Weather Shut Down (WWSD) setting in the Adjust menu. When the Setback/Off switch setting is set to Setback, the control includes WWSD Occupied and WWSD Unoccupied settings.
Once the measured outdoor air temperature exceeds the WWSD setting, the steam system is automatically shut down. Once the measured outdoor air temperature falls below the WWSD, the control is able to start a new heating cycle.
© 2010 D 279 - 05/10 8 of 24
Loading...
+ 16 hidden pages