The tekmar Steam Control 279 can operate a single on-off steam boiler or an on-off steam valve using outdoor reset. The
control determines the on time of the boiler or valve based on the measured outdoor temperature and settings entered by
the installer. A large LCD displays the current status and operating temperatures.
This brochure is organized into four main sections. They
are: 1) Sequence of Operation, 2) Installation, 3) Control
Settings, and 4) Testing and Troubleshooting. The Sequence
of Operation section has fourteen sub-sections. We
recommend reading ‘Section A: General’ of the Sequence
of Operation, as this contains important information on the
overall operation of the control. Then read the sub sections
that apply to your installation.
Table of Contents
User Interface ............................................................... 2
Display and Symbol Description ...................................3
The Control Settings section (starting at Switch Settings) of
this brochure describes the various items that are adjusted
and displayed by the control. The control functions of
each adjustable item are described in the Sequence of
Operation.
The control uses a Liquid Crystal Display (LCD) as the
method of supplying information. Use the LCD in order to
setup and monitor the operation of the system. The control
has four push buttons (Menu, Item, , ) for selecting and
adjusting settings. As the control is programmed, record
the settings in the ADJUST Menu table which is found in
the second half of this brochure.
Menu
All of the items displayed by the control are organized into
four menus: View, Adjust, Time, and Schedule. These
menus are listed on the top of the display (Menu Field).
To select a menu, use the Menu button. By pressing and
releasing the Menu button, the display will advance to the
next available menu. Once a menu is selected, there will be
a group of items that can be viewed within the menu.
Note: The TIME and SCHEDULE menus are not available
when Setback is turned off.
MenuItem
Item
The abbreviated name of the selected item will be displayed
in the item field of the display. To view the next available
item, press and release the Item button. Once you have
reached the last available item in a menu, pressing and
releasing the Item button will return the display to the first
item in the selected menu.
The items can be quickly scrolled through by holding the
Item button and then pressing the button. To rapidly scroll
through the items in the reverse order, hold the Item button
and press the button.
MenuItem
Adjust
To make an adjustment to a setting in the control, begin
by selecting the appropriate menu using the Menu button.
Then select the desired item using the Item button. Finally,
use the and/or button to make the adjustment.
Additional information can be gained by observing the
Status field of the LCD. The status field will indicate which
of the control’s outputs are currently active. Most symbols
in the status field are only visible when the VIEW Menu
is selected.
The following defined terms and symbols are used throughout this manual to bring attention to the presence of hazards of
various risk levels, or to important information concerning the life of the product.
Caution: Refer to accompanying documents.
Sequence of Operation
General Section A
Powering up the control
When the control is powered on, all segments in the LCD
are turned on for 2 seconds. Next, the control displays the
control type number in the LCD for 2 seconds. Next, the
software version is displayed for 2 seconds. Last, the control
enters into the normal operating mode.
Boiler Contact Operation
In single on-off steam boiler applications, the control uses
the boiler contact to connect to the thermostat terminals
(T-T) on the boiler. The pressure control and all other safety
devices and circuits must continue to be wired in series to
the burner circuit. The boiler contact on the control is used
to turn on or off the steam boiler burner.
In steam valve applications, the boiler contact on the control
is used to power the valve motor to open the valve. When
power is removed, the valve must close.
Status
The control has a status field on the right hand side of the
control. A pointer is shown in the status field once the boiler
contact is turned on. The pointer indicates at which point
of the steam heating system cycle the control is currently
operating at.
Each of these steps are described in detail in the following
sections.
Establishing Steam Section B
In steam heating systems, there is a time delay between
when the steam boiler or steam valve is turned on and
when the steam finally reaches the furthest radiator in the
system. It is important for the control to determine how
long this time delay is in order to ensure proper heating in
all rooms. When heat is required, the control activates the
boiler relay but does not consider the heating cycle to start
until steam has been established at the furthest radiator.
While the control is waiting to establish steam, the Status
field will have a pointer indicating Establishing Steam.
The control can use one of two methods to determine the
time to establish steam.
The Universal Sensor 071 included with the control can be
used to measure the temperature of the condensate return
pipe. In a one pipe system, it is recommended to install the
sensor on the bottom of the pipe just before it enters the last
radiator. In a two pipe system, it is recommended to install
the Condensate Sensor on the bottom of the condensate
return pipe of the radiator furthest from the boiler. In cases
where access to the furthest radiator is not possible, an
alternative is to locate the sensor on the bottom of the
condensate return pipe in the mechanical room. Once the
condensate sensor is installed, ensure the Condensate
Sensor/Off Switch Setting to Condensate Sensor. The
measured condensate return temperature reading is visible
in the View menu.
The Adjust menu includes a Steam Established setting that
Establishing Steam
(warm-up period)
Establishing Steam
(warm-up period)
delays the start of the heating cycle until the condensate
sensor has reached a set temperature.
One method to set the Steam Established setting requires
two people with two-way radios. One person is at the
control location; the other person is at the furthest radiator
One Pipe System:
Last Radiator
location. The steam system can be manually started using
the Max Heat feature. Once the furthest radiator starts
to get steam, exit the Max Heat feature and view the
Condensate temperature in the View menu. The measured
condensate return temperature can be entered as the
Steam Established setting.
Most Distant Radiator
Two Pipe System:
Main
Air Vent
OK
Condensate Return
Sensor Location
Off
Boiler
Operation
220°F
210°F 200°F 190°F 180°F 170°F 160°F -
Condensate Return
Temperature
150°F 140°F -
Best
-
(warm-up period)
Establishing Steam
on
Supply Main
15 minutes
on time
est.
Steam established
temperature setting
Thermostatic
Radiator
Vent
Return
Air Vent
Steam established - start cycle
Boiler OffBoiler On
60 minute cycle60 minute cycle
off
Boiler On
15 minutes
on time
(warm-up period)
Establishing Steam
est.
on
Tra p
Best
Supply
Air Vent
Float &
Thermostatic
Tra p
Condensate Return
Sensor Location
Boiler Off
Steam established - start cycle
45 minutes off time45 minutes off time
off
25% on time with Condensate Return Sensor and ‘Steam Established’ set to 170°F
OK
Minimum On Time
In cases where a condensate return sensor cannot be
installed, a Minimum On Time can be set to account for the
establishing steam time period. Setting a Minimum On Time
for a steam system can be problematic because a system
takes more time to reach operating temperature from a cold
start than when it is hot from a previous cycle.
To set the Minimum On Time, manually start the steam
system using the Max Heat feature and at the same time,
start a stopwatch timer. Measure the amount of time required
for steam to reach the furthest radiator. Then, exit the Max
Heat feature and enter the recorded time as the Minimum
On Time setting.
Heating Cycle - Heating Curve Section C
Boiler Cycled
On/Off
Boiler On 100% of Heating Cycle
C
B
75%
65%
42%
Room @ 70°F
Room @ 55°F
Room @ 75°F
-
Boiler On 100% of Heating Cycle
-
-
-
-
-
-
-
-
-
0 (°F)102030405060
100%
90%
80%
70%
60%
50%
40%
30%
20%
10%
0%
Outdoor reset is a method of operating a heating system
based on the fact that the rate at which a building loses
heat to the outdoor environment is mostly dependent on
the surrounding outdoor air temperature. As the outdoor
temperature gets colder, the heat loss of the building
increases at a proportional rate. This relationship between
heat loss and colder outdoor temperatures is called a
heating curve.
Outdoor = 50°F
Outdoor = 30°F
Outdoor = 10°F
A = Indoor Design
B = Outdoor Design
C = Boiler Design %
A
70
80
C
Boiler Cycled
On/Off
B
Outdoor Air Temperature
Percent On Time Per Heating Cycle
Heat Load = 20%
Boiler On Time = 12 min
60 min
Heat Load = 60%
Boiler On Time = 36 min
60 min
Heat Load = 100%
Boiler On Time = 60 min
60 min
In order to calibrate the control to the heat loss rate of a
particular building, the installer is required to enter the
following heating curve settings:
Indoor Design
The Indoor Design is the starting point of the heating curve.
When the measured outdoor air temperature matches the
Indoor Design setting, the control calculates a 0% on time
is required for heating the building. The factory default is
to start the heating curve at 70°F (21°C).
Outdoor Design
The Outdoor Design is the end point of the heating curve.
When the measured outdoor air temperature matches
the Outdoor Design setting, the control calculates the
boiler on time to be at the Boiler Design % setting. The
Outdoor Design should be set to the average coldest annual
temperature recorded in the building area.
Boiler Design %
The Boiler Design % is the percent output capacity of the
boiler or steam system required to heat the building when
the measured outdoor air temperature matches the Outdoor
Design setting. The factory default is 100%. If the building
envelope has been upgraded to improve the building
insulation, the existing steam boiler or steam system may be
oversized for the building. In these cases, the Boiler Design
% can be reduced to fine tune the heating curve.
Room (Occupied and Unoccupied)
The Room setting is the desired temperature of the building.
When a setback schedule is selected, there is a Room
Occupied temperature setting and a Room Unoccupied
temperature setting. When the setback schedule is turned
off, only the Room setting is available.
When an indoor sensor(s) is not connected to the control,
the Room setting operates as a parallel shift of the heating
curve. This allows fine tuning of the heating system. If the
Room setting is set above the Indoor Design setting, the
entire heating curve is shifted higher, resulting in longer
percent on times being calculated. Similarly, if the Room
setting is set below the Indoor Design setting, the entire
heating curve is shifted lower, resulting in shorter percent
on times being calculated.
-
100%
-
90%
-
75%
65%
42%
Room @ 75°F
Room @ 70°F
Room @ 55°F
7080
Outdoor Air Temperature
2030405060
-
-
-
-
-
-
-
0 (°F)10
80%
70%
60%
50%
40%
30%
20%
10%
0%
Percent On Time Per Heating Cycle
When an indoor sensor(s) is connected to the control, the
Room setting becomes a Room Target temperature. The
control measures the current air temperature in the room
using the indoor sensors. The control then automatically
shifts the heating curve so that the measured room
temperature reaches the Room Target temperature.
The Adjust menu includes a setting called Cycle that
determines how often the heating system will run. During
each heating cycle the boiler is turned on once, and the
boiler is turned off once. Each building has a natural heat up
and a cool off rate. This is determined by many factors such
as the size and length of runs in the steam heating system,
the size and mass of the radiators, and the heat loss of the
building. The factory default is 60 minutes. When using
optional Indoor Sensors, an automatic setting is available
that allows the control to learn the natural temperature
swing of the building. If the optional Indoor Sensors are
not used, then the only method of adjustment is trial and
error by the installer.
50% On Time With a 30 Minute Heating Cycle
Off
Boiler
Operation
Boiler On
15 minutes
on time
30 minute cycle
Boiler Off
15 minutes
off time
OnOffOnOff
15 minutes
on time
30 minute cycle30 minute cycle30 minute cycle
15 minutes
off time
50% On Time With a 60 Minute Heating Cycle
OffOn
Boiler
Operation
Boiler On
30 minutes
on time
Boiler Off
30 minutes
off time
60 minute cycle
The control is designed to operate on/off steam boilers or
steam valves. These systems can only produce heat at
a fixed rate (on = 100%, off = 0%). In order to match the
heat loss of the building, the steam heating system must
be cycled on and off. To determine the boiler on time, the
control uses the percent on time required by the heating
curve and multiplies this by the heating cycle time. While
operating in the heating cycle, the Status field will have a
pointer indicating Heat Cycle.
Example:
When the outdoor temperature is 32°F (0°C), the
heating curve may determine a 50% on time is required. If the
heating cycle is 60 minutes, then the boiler on time is: Boiler On
Time Per Heating Cycle = 0.5 x 60 minutes = 30 minutes.
OnOff
15 minutes
on time
OnOff
15 minutes
off time
30 minutes
on time
15 minutes
60 minute cycle
on time
30 minutes
15 minutes
off time
off time
On
Lockout Differential Section E
The Adjust menu includes a setting called Lockout Differential.
When a condensate return sensor is present, a lockout
differential can be set to ensure that any remaining steam
in the system condenses and the condensate has time to
return to the boiler. This increases the efficiency of the system
by removing the latent heat of the steam remaining after
the burner is shut down, and lengthening the cycle so that
remaining heat is allowed to radiate into the building.
The lockout differential is the number of degrees the
condensate return sensor temperature must fall below the
steam established setting before the control can operate
the heating system for the next cycle. During the lockout
differential, the heating system is held off, and the Status
field will have a pointer indicating Lockout Differential. The
factory default is a 25°F lockout differential.
There is no exact method to set the Lockout Differential for
a particular building; it is a process of trial and error. If the
building tends to over heat, the lockout differential should
be increased to allow the steam system to cool down further
before starting the next cycle. If the building tends to under
heat, the lockout differential should be decreased to allow
the next heating cycle to start sooner.
Boiler On
Steam established - start cycle
15 minutes
on time
off
Lockout Period
(warm-up period)
Establishing Steam
Steam Established
onon
Lockout Period
(warm-up period)
Establishing Steam
Optional Indoor Sensors Section F
Multiple indoor sensors can be added to improve the
temperature accuracy within the building. Available indoor
sensors include the 076, 077 and 084.
Indoor Sensors 084, 077 and 076
The control allows two indoor sensors to be directly
connected to the control. Once an indoor sensor is
connected to the indoor sensor S1 input, the Indoor S1/Off
switch setting must be set to S1. Likewise, once an indoor
sensor is connected is connected to the S2 input, the Indoor
S2/Off switch setting must be set to S2.
When indoor sensor 1 is present, the Room 1 temperature
is visible in the View menu. Likewise, when indoor sensor
2 is present, the Room 2 temperature is visible in the View
menu. Also shown in the View menu is the current Room
Target temperature. The room target can be changed by
adjusting the Room Occupied or Room Unoccupied setting
in the Adjust menu.
Should additional indoor sensors be desired, a square
number (4, 9, 16, etc.) of sensors can be wired in seriesparallel to a single indoor sensor input.
To Indoor Sensor Input
Series - Parallel
Wiring
When using two indoor sensor inputs, the control can
operate either based upon an average of the two temperature
measurements or the control can operate on the lowest of
the two temperature measurements.
Temperature Averaging
To operate the steam system based upon the average of
the two indoor sensor temperature measurements, set the
Average/Off switch setting to Average.
Lowest of Two Temperatures
To operate the steam system based upon the lowest of
the two indoor sensor temperature measurements, set the
Average/Off switch setting to Off.
Built-in Timer Section G
The control includes a built-in time clock that is turned on once the Setback/Off switch setting is set to Setback. The time
is set in the Time menu. The clock can be set to use either 12 or 24 hour time.
Programmable Schedule Section H
The control includes a programmable schedule that is
turned on once the Setback/Off switch setting is set to
Setback. The programmable schedule is set in the Schedule
menu. The schedule can be repeated on a 24 hour, 5-1-1,
or 7 day schedule. Each schedule allows a time to be set
for the Occupied event and another time to be set for the
Unoccupied event. Should it be desired to skip an Occupied
or Unoccupied event, set the event time to --:--, which can be
found between 11:50 PM (23:50) and 12:00 AM (0:00).
Warm Weather Shut Down Section I
The control includes a Warm Weather Shut Down (WWSD)
setting in the Adjust menu. When the Setback/Off switch
setting is set to Setback, the control includes WWSD Occupied
and WWSD Unoccupied settings.
Once the measured outdoor air temperature exceeds the
WWSD setting, the steam system is automatically shut down.
Once the measured outdoor air temperature falls below the
WWSD, the control is able to start a new heating cycle.