The tekmar Boiler Control 270 can control the supply water temperature from a single modulating boiler based on outdoor temperature
or domestic hot water requirements. A large easy to read display provides current system temperatures and operating status.
Additional functions include:
• Outdoor Reset
• Installer and Advanced access levels
• Primary pump output
• Pump exercising
• Pump purging
• DHW demand for domestic hot water loads
• Optional indoor sensor for room air temperature control
• Test sequence to ensure proper component operation
• Setback input for energy savings
• CSA C US certified
• Boiler demand for space heating loads
Input
Boiler
Demand
Menu Item
Boiler Control 270
One Modulating Boiler & DHW
1
2
3
4 5NL6
DHW
Dem
Prim
P1
Boil
Com
Dem
Dem
Boiler Demand
DHW Demand
Modulation
DHW Priority Override
7 89 1011
DHW
Power
Pmp/Vlv
Boiler
Pmp P2
AdvancedOff
InstallerExercise
Test
off not testing
red
red
For maximum heat
press & hold Test
button for 3 second
Made in Canada by
tekmar Control Systems Ltd.
tektra 969-03
Power 115 V ±10% 50/60 Hz 600 VA
Relays 230 V (ac) 5 A 1/3 hp, pilot duty 240 VA
Demands 20 to 260 V (ac) 2 VA
This brochure is organized into four main sections. They are: 1) Sequence of Operation, 2) Installation, 3) Control Settings, and
4) Testing and Troubleshooting. The Sequence of Operation section has six sub-sections. We recommend reading Section A: General
of the Sequence of Operation, as this contains important information on the overall operation of the control. Then read the sub
sections that apply to your installation.
The Control Settings section (starting at DIP Switch Settings) of this brochure describes the various items that are adjusted and
displayed by the control. The control functions of each adjustable item are described in the Sequence of Operation.
Table of Contents
User Interface ..................................................Pg 2
The control uses a Liquid Crystal Display (LCD) as the method of supplying information. You use the LCD in order to setup and
monitor the operation of your system. The control has four push buttons (Menu, Item, , ) for selecting and adjusting settings. As
you program your control, record your settings in the ADJUST menu table, which is found in the second half of this brochure.
Menu
All of the items displayed by the control are organized into two menus (View and Adjust).
These menus are listed on the top left hand side of the display (Menu Field). To select
a menu, use the Menu button. By pressing and releasing the Menu button, the display
sequences between the two menus. Once a menu is selected, there will be a group of
items that can be viewed within the menu.
Item
The abbreviated name of the selected item will be displayed in the item field of the
display. To view the next available item, press and release the Item button. Once you
have reached the last available item in a menu, pressing and releasing the Item button
will return the display to the first item in the selected menu.
The items can be quickly scrolled through by holding the Item button and then pressing
button. To rapidly scroll through the items in the reverse order, hold the Item
the
button and press the button.
Adjust
To make an adjustment to a setting in the control, begin by selecting the ADJUST menu
using the Menu button. Then select the desired item using the Item button. Finally, use
the , and / or button to make the adjustment.
Additional information can be gained by observing the Status field of the LCD. The
status field will indicate which of the control’s outputs are currently active. Most
symbols in the status field are only visible when the VIEW menu is selected.
The following defined terms and symbols are used throughout this manual to bring attention to the presence of hazards of various risk
levels, or to important information concerning the life of the product.
- Warning Symbol: Indicates presence of hazards which can cause severe personal injury, death or
substantial property damage if ignored.
INSTALLATION
CATEGORY II
- Double insulated
- Local level, appliances
Sequence of Operation
Section A
General
Operation
Page 4 - 5
Section B
Boiler
Operation
Page 5 - 7
Section C
Pump
Operation
Page 8
Section D
Boiler Reset
Operation
Page 8 - 10
Section E
DHW
Operation
Page 10 - 13
Section A: General Operation
POWERING UP THE CONTROL
When the control is powered up, all segments in the LCD are turned on for 2 seconds. Next, the control displays the control type
number in the LCD for 2 seconds. Next, the software version is displayed for 2 seconds. Finally, the control enters into the normal
operating mode.
OPERATION
The control stages or modulates the boiler to control supply water temperature to a hydronic system. The supply water temperature
is based on outdoor reset or a fixed temperature for DHW.
Outdoor Reset
When a boiler demand signal from the heating system is present, the control operates the boiler(s) to maintain the supply
temperature based on the outdoor air temperature and the Characterized Heating Curve settings. Refer to section D.
DHW
When a DHW demand is present, the control operates the boiler to maintain the supply water temperature at least as hot as the
DHW exchange setting or high enough to satisfy tank temperature. Refer to section E.
SETBACK (Occ and UnOcc)
14
To provide greater energy savings, the control has a setback feature. With setback, the
supply water temperature in the system is reduced when the building is unoccupied. By
reducing the supply water temperature, the air temperature in the space may be reduced
even when thermostat(s) are not turned down. Any time the UnO Sw (18) and the Com (17)
are shorted together, the control operates in the unoccupied mode.
When in the unoccupied mode, the UNOCC segment is displayed in the LCD. The control
adjusts the supply water temperature based on the UNOCC settings made in the control.
The control has a built-in exercising feature that is selected through the Exercise / Off DIP switch. To enable the exercising feature
set the Exercise / Off DIP switch to Exercise. If exercising is enabled, the control ensures that each pump is operated at least
once every 3 days. If a pump has not been operated at least once every 3 days, the control turns on the output for 10 seconds.
This minimizes the possibility of the pump seizing during a long period of inactivity. While the control is exercising, the Test LED
flashes quickly.
Note: The exercising function does not work if power to the control or pumps is disconnected.
RUNNING TIMES
The control displays the accumulated running time of the boiler in the VIEW menu.
Resetting the Running Time
To reset the running time for the boiler, select the running time in the VIEW menu. Next press the and buttons simultaneously
until CLR is displayed.
FACTORY D EFAULTS
The control comes preset with several factory defaults. These are based on the terminal unit selection. To fine-tune building
requirements, these defaults may be changed.
To reload the factory default, power down the control and wait for 10 seconds. Power up the control while simultaneously
holding the Menu and buttons. An E01 error occurs forcing the installer to go through the ADJUST menu to ensure the
settings are correct.
Section B: Boiler Operation
BOILER TARGET TEMPERATURE
The boiler target temperature is determined by the type of demand received by the control. A boiler demand calculates a boiler
target based on the characterized heating curve settings and the outdoor air temperature. A DHW demand has a temperature
setting to which the boiler is operated to meet.
The control displays the temperature that it is currently trying to maintain as the boiler supply temperature. If the control does not
presently have a requirement for heat, it does not show a boiler target temperature. Instead, “– – –” is displayed in the LCD.
BOILER MINIMUM
The boiler minimum is the lowest temperature that the control is
allowed to use as a boiler target temperature. During mild conditions,
if the control calculates a boiler target temperature that is below the
Boiler Minimum setting, the boiler target temperature is adjusted to at
least the Boiler Minimum setting. During this condition, if the boiler is
operating, the minimum segment is turned on in the display when viewing
either the boiler supply temperature or the boiler target temperature. Set
the Boiler Minimum setting to the boiler manufacturer’s recommended
temperature.
BOILER MAXIMUM
The boiler maximum is the highest temperature that the control is
allowed to use as a boiler target temperature. If the control does target
the Boiler Maximum setting, and the boiler temperature is near the boiler
maximum temperature, the maximum segment will be displayed in the
LCD while either the boiler target temperature or the boiler temperature
is being viewed. At no time does the control operate the boiler above
248°F (120°C).
MIN Segment On
MAX Segment
On
Boiler
Contact Closes
Boiler
Fires
MAX Segment
On
FIRE DELAY
The Fire Delay is the time delay that occurs between the time that the control
closes a stage contact to fire a stage and the burner fires for that stage.
The Boiler Control 270 provides a modulating output signal to operate a single modulating boiler. The control first closes the boiler
contact on to ignite the ignition sequence. The boiler is then modulated from the minimum modulation using Proportional, Integral
and Derivative (PID) logic in order to satisfy the boiler target temperature.
MOTOR SPEED
The Motor Speed is the amount of time the boiler requires to go from 0%
modulation to 100% modulation.
Gas valve actuating motors have a design time from fully closed to
fully open which can be found in the manufacturer’s manual. The
Motor Speed should be set to this time.
The Motor Speed setting for a Variable Frequency Drive (VFD) is the
amount of time required to go from a stopped position to 100% fan
speed. Since a VFD has a very quick response rate, it may be necessary
to increase the Motor Speed setting in order to increase the stability of
the boiler modulation.
MODULATION RANGE (0 to 10 V (dc), 2 to 10 V (dc), 0 to 20 mA, 4 to 20 mA)
The modulation output can be adjusted from a 0 to 10 V (dc) or to a 2 to 10 V (dc) output range using the Boil Modulation setting.
If a 0 to 20 mA range is required, set the Boil Modulation item to 0 to 10 V (dc) and cut the jumper wire located next to the modulation
output.
If a 4 to 20 mA range is required, set the Boil Modulation item to 2 to 10 V (dc) and cut the jumper wired located next to the
modulation output.
MINIMUM MODULATION
The minimum modulation defines the minimum output signal from the control to the boiler
burner. It is based on a percentage of the control’s output signal range.
The Minimum Modulation setting for boilers with power burners is typically set to
0%.
For boilers with electronic operators, the boiler’s input signal range may not match the
output signal range of the 270 control. The Minimum Modulation setting limits the control
output range in order to match the boiler’s input range.
To calculate the Minimum Modulation, use the following formula:
For 0 to 10 V (dc):
Minimum Modulation =
0 V (dc) – Boiler’s Minimum Input Signal
0 – 10 V (dc)
x 100%
For 2 to 10 V (dc):
Minimum Modulation =
2 V (dc) – Boiler’s Minimum Input Signal
2 – 10 V (dc)
x 100%
MINIMUM MODULATION
Control's
Output
Signal
Range
Minimum
Modulation
100%10 V (dc)10 V (dc)
Boiler's
Input
Signal
Range
18%
0%0 V (dc)
1.8 V (dc)
Boiler's Minimum
Input Signal
Example:
A boiler requires a 1.8 V (dc) signal to fire the boiler at low fire. The boiler can be modulated to 10 V (dc) where it reaches high fire. This
means the boiler’s input signal range is 1.8 to 10 V (dc). The 270 control has an output signal range of 0 to 20 mA.
To make the two signal ranges the same, the Minimum Modulation required is:
0 V – 1.8 V
Minimum Modulation
=
0 V – 10 V
x 100% = 18%
MAXIMUM MODULATION
The maximum modulation defines the maximum output signal from the control
to the boiler burner. It is based on a percentage of the control’s output signal
range.
The Maximum Modulation setting for boilers with power burners is
typically set to 100%.
For boilers with electronic operators, the boiler’s input signal range may not
match the output signal range of the 270 control. The Maximum Modulation
setting limits the control output range in order to match the boiler’s input
range.
To calculate the Maximum Modulation, use the following formula:
For 0 to 10 V (dc):
Maximum Modulation =
0 V (dc) – Boiler’s Maximum Input Signal
0 – 10 V (dc)
x 100%
For 2 to 10 V (dc):
Maximum Modulation =
2 V (dc) – Boiler’s Maximum Input Signal
2 – 10 V (dc)
x 100%
Example:
A boiler’s input signal range is 2 to 9 V (dc). The 270 control has an output signal range of 2 to 10 V (dc).
To make the two signal ranges the same, the Maximum Modulation required is:
Maximum Modulation =
2 V – 9 V
2 V – 10 V
x 100% = 88%
BOILER MASS
The Boiler Mass setting allows the installer to adjust the control to the thermal mass of the type of heat sources used in the
application. The modulation of the boiler can become unstable if the incorrect Boiler Mass setting is chosen. A key sign of the boiler
modulation being unstable is the flame will continue to increase and then decrease in short periods of time. By choosing a lower
Boiler Mass setting, the boiler response will become more stable.
Lo (1)
The Lo setting is selected if the boiler that is used has a low thermal mass. This means that the boiler has a very small water
content and has very little metal in the heat exchanger. A boiler that has a low thermal mass comes up to temperature quite rapidly
when fired. This is typical of many copper fin-tube boilers. The Lo Mass setting provides a fast response to the heating system.
Med (2)
The Med setting is selected if the boiler that is used has a medium thermal mass. This means that the boiler either has a large
water content and a low metal content or a low water content and a high metal content. This is typical of many modern residential
cast iron boilers or steel tube boilers. The Med Mass setting provides a moderate response to the heating system.
Hi (3)
The Hi setting is selected if the boiler that is used has a high thermal mass. This means that the boiler has both a large water
content and a large metal content. A boiler that has a high thermal mass is relatively slow in coming up to temperature. This is
typical of many commercial cast iron and steel tube boilers. The Hi Mass setting provides a slow response to the heating system.
DIFFERENTIAL
A modulating boiler must be operated with a differential while operating in low fire. The boiler differential is divided around the boiler
target temperature. The boiler burner ignites at low fire when the supply water temperature is ½ of the Boiler Differential setting
below the boiler target temperature. The boiler is shut off in low fire as the supply temperature reaches at least ½ of the differential
above the boiler target temperature. With the control, either a fixed or an auto differential may be selected.
When the boiler is modulating above low fire, the differential does not apply. Instead, the modulation output signal is determined
using Proportional, Integral and Derivative (PID) logic in order to satisfy the boiler target temperature.
Desired temperature
Fixed Differential
If the user desires to have a fixed differential, this is set using the
Boiler Differential setting in the ADJUST menu.
160°F (71°C)
Boiler Off
Boiler On
165°F (74°C)
a
r
e
p
m
e
T
e
s
i
r
e
r
u
t
155°F (68°C)
T
e
m
p
e
r
a
t
u
Differential
10°F (6°C)
r
e
f
a
l
l
Time
Auto Differential
If the Auto Differential is selected, the control automatically determines
the best differential as the load changes. This reduces potential short
cycling during light load conditions.
The primary pump operates under the following conditions:
• A boiler demand is present and the control is not in Warm Weather
Shut Down (WWSD).
• A DHW demand is present and DHW MODE is set to 3 or 4.
Primary
Primary Pump Purge
Pump
After a demand is removed, the control continues to operate the primary
pump for a period of time. The maximum length of time that the primary
pump continues to run is adjustable using the Primary Pump Purge
setting. The primary pump continues to run until either the purging
time has elapsed or the boiler supply temperature drops more than a
differential below the Boiler Minimum setting.
BOILER PUMP OPERATION
The boiler pump turns on prior to the boiler firing (pre-purge) and continues to run after the boiler is turned off (post-purge). The
boiler pump pre-purge time is determined by the Boiler Mass setting. As the Boiler Mass setting is increased, the boiler pump pre-
purge time of the boiler also increases.
Boiler Pump Purge
The amount of time that the boiler pump continues to run after the boiler turns off is adjustable using the Boiler Pump Purge setting.
DHW
Pump
Boiler
Sensor
Boiler
Pump
Section D: Boiler Reset Operation
BOILER DEMAND
A boiler demand is required in order for the control to provide heat to
the heating system. A boiler demand is generated by applying a voltage
between 24 and 230 V (ac) across the Boiler Demand terminals (1 and
2). Once voltage is applied, the Boiler Demand pointer is displayed in
the LCD. If the control is not in Warm Weather Shut Down (WWSD), the
control closes the primary pump contact. The control calculates a boiler
target supply temperature based on the outdoor air temperature and the
characterized heating curve settings. The control then fires the boiler, if
24 to 230 V (ac)
L
N
required, to maintain the target supply temperature.
OUTDOOR DESIGN TEMPERATURE
The outdoor design temperature is the outdoor air temperature that is the typical coldest temperature of the year where the building
is located. This temperature is used when doing the heat loss calculations for the building. If a cold outdoor design temperature is
selected, the boiler supply temperature rises gradually as the outdoor temperature drops. If a warm outdoor design temperature is
selected, the boiler supply temperature rises rapidly as the outdoor temperature drops.
The control varies the supply water temperature based on the outdoor air
temperature. The control takes into account the type of terminal unit that
the system is using. Since different types of terminal units transfer heat
to a space using different proportions of radiation, natural convection
and forced convection, the supply water temperature must be controlled
differently. Once a terminal unit is selected, the control varies the supply
water temperature according to the type of terminal unit. This improves
the control of the air temperature in the building.
BOILER DESIGN TEMPERATURE
The boiler design supply temperature is the supply water temperature
required to heat the building when the outdoor air temperature is as cold
as the outdoor design temperature.
BOILER INDOOR DESIGN TEMPERATURE
The indoor design temperature is the room temperature that was used in
the original heat loss calculations for the building. This setting establishes
the beginning of the characterized heating curve.
Boiler Characterized
Boiler Characterized
Heating Curve
Heating Curve
BOIL MIN
BOIL INDR
80
(27)
60
(16)
Outdoor Air Temperature
OUT DSGN
WWSD OCC
WWSD UNOCC
ROOM OCC
ROOM UNOCC
40
(5)
BOIL DSGN
20
(-7)
BOIL MAX
0
(-18)
ROOM
The Room setting is the desired room temperature for the building and provides a parallel shift of the heating curve. The room
temperature desired by the occupants is often different from the design indoor temperature. If the room temperature is not correct,
adjusting the Room setting increases or decreases the amount of heat available to the building. A Room setting is available for both
the occupied (day) and unoccupied (night) periods.
Supply Water Temperature
INDOOR SENSOR
With the indoor sensor connected, the control is able to sense the actual room temperature. Indoor temperature feedback finetunes the supply water temperature in the heating system to maintain room temperature. To adjust the room temperature, use the
Room Occ or Room UnOcc setting in the ADJUST menu at the control.
The indoor sensor is connected to the Indr and Com terminals (17 and 18). In addition, power must be applied to the Boiler Demand
terminals (1 and 2) as described in the Boiler Demand section.
If a multiple zone system is used with an indoor sensor, proper placement of the indoor sensor is essential. The indoor sensor
should be located in an area which best represents the average air temperature of the zones.
TERMINAL UNITS
The control provides for a selection between six different terminal unit types: two types of radiant floor heat, fancoil, fin-tube
convector, radiator and baseboard. When a terminal unit is selected, the control automatically loads the design supply temperature,
maximum supply temperature, and minimum supply temperature. The factory defaults are listed below. These factory defaults can
be changed to better match the installed system.
This type of a hydronic radiant floor is embedded in either a thick concrete or gypsum
pour. This heating system has a large thermal mass and is slow acting.
Low Mass Radiant (2)
This type of radiant heating system is either attached to the bottom of a wood sub-floor,
suspended in the joist space, or sandwiched between the sub-floor and the surface.
This type of radiant system has a relatively low thermal mass and responds faster than
a high mass system.
A fancoil terminal unit or Air Handling Unit (AHU) consists of a hydronic heating coil and
either a fan or blower. Air is forced across the coil at a constant velocity by the fan or
blower, and is then delivered into the building space.
Fin-Tube Convector (4)
A convector terminal unit is made up of a heating element with fins on it. This type of
terminal unit relies on the natural convection of air across the heating element to deliver
heated air into the space. The amount of natural convection to the space is dependent
on the supply water temperature to the heating element and the room air temperature.
Radiator (5)
A radiator terminal unit has a large heated surface that is exposed to the room. A radiator
provides heat to the room through radiant heat transfer and natural convection.
Baseboard (6)
A baseboard terminal unit is similar to a radiator, but has a low profile and is installed at
the base of the wall. The proportion of heat transferred by radiation from a baseboard is
greater than that from a fin-tube convector.
WARM WEATHER SHUT DOWN (OCC AND UNOCC)
The warm weather shut down (WWSD) disables the space heating system during warm outdoor weather. There is a separate
WWSD for both the occupied and the unoccupied periods. When the outdoor air temperature rises above the WWSD setting, the
control turns on the WWSD pointer in the display. When the control is in WWSD, the Boiler Demand pointer is displayed if there is
a boiler demand. However, the control does not operate the heating system to satisfy this demand. The control does respond to a
DHW demand and operates as described in section E.
Section E1: Domestic Hot Water Operation
DHW DEMAND
A DHW Demand is required in order for the control to provide heat to the DHW system. A
DHW aquastat or setpoint control is used as a switch in the DHW demand circuit. Once
the control detects a DHW demand, the DHW Demand pointer turns on in the LCD and the
control operates the boiler to provide a sufficient boiler supply water temperature to the
DHW tank. The control operates the pumps as described below.
The control registers a DHW Demand when a voltage between 24 and 230 V (ac) is applied
across the DHW Demand terminals (2 and 3).
24 to 230 V (ac)
L
N
BOILER TARGET DURING DHW GENERATION
The DHW demand overrides the reset water temperature, except when the reset water temperature requirement is higher than that
of the DHW tank. When the control receives a DHW demand through an aquastat, the boiler target temperature is at least as hot
as the DHW heat exchange setting (DHW XCHG).
Com
Dem
3
2
DHW
Dem
DHW MODE AND PRIORITY OPERATION
The control has four different modes of DHW operation, which depends on the piping arrangement of the DHW tank. It is often
desirable to limit or even stop the flow of heat to the heating system when the DHW tank calls for heat. This allows for a faster
recovery of the DHW tank.
When a DHW Demand is present, the DHW Pmp / Vlv contact
(terminals 7 and 8) closes. The primary pump contact does not turn
on, but may operate based on a boiler demand.
DHW Mode 2 - DHW in Parallel with Priority
When a DHW Demand is present, the DHW Pmp / Vlv contact
(terminals 7 and 8) closes and the primary pump contact is opened.
DHW Mode 3 - DHW in Primary / Secondary no Priority
When a DHW Demand is present, the DHW Pmp / Vlv contact
(terminals 7 and 8) is closed and the primary pump contact is closed.
This mode can be used if DHW tank is piped in direct return and a DHW
valve is installed.
DHW Mode 4 - DHW in Primary / Secondary with Priority
When a DHW Demand is present, the DHW Pmp / Vlv contact
(terminals 7 and 8) is closed and the primary pump contact is closed.
Priority can only be obtained using external wiring. During a priority
override, the DHW Pmp / Vlv contact is opened until the heating
system has recovered before returning to DHW operation.
Th is mo d e can b e used if a DHW t ank is piped i n dir e c t retur n and
a DHW valve is installed.
Primary
Pump
Primary
Pump
Disable
Using External
Wiring
Power from
DHW Pump / Vlv
Contact
Primary
Primary
L
DHW
Pump
Pump
DHW
Pump
Pump
DHW
Pump
Boiler
Pump
Boiler
Pump
Boiler
Pump
Boiler
Pump
L
COIL
N
N.C.
Power to External
Boiler Zones
N
N.O.
DHW
Pump
DHW MODE 4
External Priority
Interlock
DHW PRIORITY OVERRIDE
The DHW Priority Override applies to DHW modes 2 and 4. To prevent
the building from cooling off too much or the possibility of a potential
freeze up during DHW priority, the control limits the amount of time
for DHW priority. As the outdoor air temperature becomes colder, the
length of time that the control provides DHW priority is reduced. Once
the allowed time for priority has elapsed, the control overrides the DHW
priority and resumes space heating.
To provide external DHW priority, the space heating zones must be
interlocked with the DHW Pmp / Vlv contact. During demands, the
DHW Pmp / Vlv contact must remove any power to all space heating
zone valves or zone pumps.
The Conditional DHW Priority Override applies to DHW MODE 2 and Boiler Minimum is not set to OFF. If the boiler supply
temperature is maintained at or above the required temperature during DHW generation, this indicates that the boiler has enough
capacity for DHW and possibly heating as well. As long as the boiler supply temperature is maintained near its target, DHW and
heating occurs simultaneously.
DHW POST PURGE
After the DHW Demand is removed, the control performs a purge on the boiler. The control shuts off the boiler and continues
to operate either the DHW pump or the DHW valve and the system and boiler pump if applicable. This purges the residual heat
from the boiler into the DHW tank. The control continues this purge for a maximum of four minutes or until the boiler supply water
temperature drops 20°F (11°C) below the boiler target temperature during the DHW operation. The control also stops the purge if
the boiler supply temperature drops below the current boiler target temperature.
DHW MIXING PURGE
After DHW operation, the boiler is extremely hot. At the same time,
the heating zones may have cooled off considerably after being off for
a period of time. To avoid thermally shocking the boiler after DHW in
parallel with priority (DHW MODE 2), the control shuts off the boiler, but
continues to operate the DHW pump while restarting the heating system.
This allows some of the DHW return water to mix with the cool return
water from the zones and temper the boiler return water.
Primary
Pump
DHW
Pump
Boiler
Pump
DHW DURING UNOCCUPIED
When an external DHW Demand is present, the control can either continue operation of the DHW system as it would during the
occupied period or the control can ignore a call for DHW as long as the control is in an unoccupied mode.
Section E2: DHW with Low Temperature Boilers
If DHW is to be incorporated into a low temperature system such as a
radiant heating system, a mixing device is often installed to isolate the high
DHW supply temperature from the lower system temperature. If a mixing
device is not installed, high temperature water could be supplied to the
low temperature system while trying to satisfy the DHW demand. This may
result in damage to the low temperature heating system. The control is
capable of providing DHW in such a system while maximizing the chance
that the temperature in the heating system does not exceed its allowed
Boiler Maximum setting.
Primary
Pump
To prevent high temperature water from being introduced into the heating
system, the primary pump (Prim P1) must be turned off during a call for
DHW. To do this, the control must be set to DHW MODE2 or DHWMODE4
and BoilMIN must be set to OFF.
DHW MODE 2 OPERATION
On a call for DHW, the control provides DHW priority by shutting off the primary pump (Prim P1) for a period of time. This time
is based on the outdoor air temperature as described in the DHW Priority Override section. However, if the DHWDemand is not
satisfied within the allotted time, the boiler shuts off and the heat of the boiler is purged into the DHW tank.
Once the boiler supply temperature is sufficiently reduced, the DHW Pmp / Vlv contact shuts off. The heating system is turned on
for a period of time to prevent the building from cooling off. After a period of heating, and if the DHW Demand is still present, the
control shuts off the heating system and provides heat to the DHW tank once again.
For correct operation, close attention must be paid to the mechanical layout of the system. When the control turns off the primary
pump (Prim P1), flow to the heating system must stop. If flow is not stopped, the temperature in the heating system can exceed the
maximum desired temperature and can result in damage to the heating system.
In DHW MODE 4, the space heating zones must be prevented from coming on during DHW demands using external wiring. This
can be done using an external relay to remove power from zone pumps or zone valves while a DHW Demand is present. This
external relay is interlocked with the DHW Pmp / Vlv contact.
During a DHW Demand, the control closes the primary pump (Prim P1) contact and the DHW Pmp / Vlv contact. Once the DHW
Demand is removed, or during a DHW priority override, the DHW Pmp / Vlv contact is opened, and the external wiring should allow
the space heating zones to operate.
There is no mixing purge available in DHW MODE 4. After DHW priority, the boiler supply water temperature may exceed the design
water temperature of the space heating system and can result in damage to the heating system.
Installation
CAUTION
Improper installation and operation of this control could result in damage to the equipment and possibly even personal injury. It is
your responsibility to ensure that this control is safely installed according to all applicable codes and standards. This electronic
control is not intended for uses as a primary limit control. Other controls that are intended and certified as safety limits must be
placed into the control circuit. Do not open the control. Refer to qualified personnel for servicing. Opening voids warranty and could
result in damage to the equipment and possibly even personal injury.
STEP ONE
Check the c ontents of this package. If any of the contents listed are missing or damaged, please contact your wholesaler or tekmar
sales representative for assistance.
Type 270 includes: One Boiler Control 270, One Outdoor Sensor 070, One Universal Sensor 082, Data Brochures D 270, D 070,
D 001, Application Brochure A 270.
Note: Carefully read the details of the Sequence of Operation to ensure that you have chosen the proper control for your application.
STEP TWO
Remove the control from its base by pressing down on the release clip in the wiring chamber and sliding the control away from it.
The base is then mounted in accordance with the instructions in the Data Brochure D 001.
STEP THREE
All electrical wiring terminates in the control base wiring chamber. The base has standard
common wiring hardware and conduit fittings. Before removing the knockouts, check the wiring diagram and select those sections
of the chamber with common voltages. Do not allow the wiring to cross between sections, as the wires will interfere with safety
dividers which should be installed at a later time.
Power must not be applied to any of the wires during the rough-in wiring stage.
All wires are to be stripped to a length of
Install the Outdoor Sensor 070 according to the installation instructions in the Data Brochure D 070 and run the wiring back to
the control.
Install the Boiler Supply Sensor 082 according to the installation instructions in the Data Brochure D 070 and run the wiring
back to the control.
GETTING READY
MOUNTING THE BASE
ROUGH-IN WIRING
3
in (9 mm) to ensure proper connection to the control.
8
7
in (22 mm) knockouts, which accept
8
If an Indoor Sensor 076 or 077 is used, install the indoor sensor according to the instructions in the Data Brochure D 074 and
run the wiring back to the control.
Run wire from other system components (pumps, boiler, etc.) to the control.
Run wires from the 115 V (ac) power to the control. Use a clean power source with a 15 A circuit to ensure proper operation.
Multi-strand 16 AWG wire is recommended for all 115 V (ac) wiring due to its superior flexibility and ease of installation into
the terminals.
The installer should test to confirm that no voltage is present at any of the wires. Push the control into the base and slide it down
until it snaps firmly into place.
5
Powered Input Connections
115 V (ac) Power
Connect the 115 V (ac) power supply to the Power L and Power N terminals (5 and 6).
This connection provides power to the microprocessor and display of the control.
As well, this connection provides power to the Prim P1 terminal (4) from the Power L
terminal (5).
Boiler Demand
To gener a t e a Boiler Demand, a voltage between 24 V (ac) and 230 V (ac) must be
applied across the Boil Dem and Com Dem terminals (1 and 2).
115 V (ac)
L
N
24 to 230 V (ac)
L
N
L
Boil
Dem
Power
1
N
Com
Dem
6
2
DHW Demand
To gener a t e a DHW Demand, a voltage between 24 V (ac) and 230 V (ac) must be
applied across the Com Dem and DHW Dem terminals (2 and 3).
Caution: The same power supply must be used to power both the DHW Demand and
the Boiler Demand circuits since they both share the Com Dem terminal.
Output Connections
Primary Pump Contact (Prim P1)
The Prim P1 output terminal (4) is a powered output. When the relay in the control
closes, 115 V (ac) is provided to the Prim P1 terminal (4) from the Power L terminal (5).
To operate the primary pump, connect one side of the primary pump circuit to terminal 4
and the second side of the pump circuit to the neutral (Power N) side of the 115 V (ac)
power supply.
DHW Pmp / Vlv Contact
The DHW Pmp / Vlv terminals (7 and 8) are an isolated output. There is no power
available on these terminals from the control. These terminals are to be used as a
switch to either make or break power to the DHW pump or the DHW valve. Since this
is an isolated contact, it may switch a voltage between 24 V (ac) and 230 V (ac).
24 to 230 V (ac)
L
N
115 V (ac)
N
L
24 to 230 V (ac)
L
N
M
3
2
DHW
Com
Dem
Dem
6
5
4
Power
Prim
or
N
L
P1
8
7
DHW
Pmp/Vlv
Boiler Pmp P2 Contact
The Boiler Pmp P2 terminals (9 and 10) are isolated output in the control. There is no
power available on these terminals from the control. These terminals are to be used
as a switch to either make or break power to a boiler pump. Since this is an isolated
contact, it may switch a voltage between 24 V (ac) and 230 V (ac).
The Modulation Output terminals (11 and 12) provide a 0 to 10 V (dc) or a 2 to 10 V (dc)
output to the boiler. If a 0 to 20 mA or a 4 to 20 mA output is required, cu t the jumper wire
located next to the modulation output.
The modulating outputs replace any mechanical operator such as a T991. Observe
polarity when connecting the control to the boiler.
SENSOR AND UNPOWERED INPUT CONNECTIONS
Do not apply power to these terminals as this will damage the control.
Outdoor Sensor
Connect the two wires from the Outdoor Sensor 070 to the Com and Out terminals (17 and
16). The outdoor sensor is used by the control to measure the outdoor air temperature.
Boiler Supply Sensor
Connect the two wires from the Boiler Supply Sensor 082 to the Com and Boil terminals
(13 and 15). The boiler supply sensor is used by the control to measure the boiler supply
water temperature.
11
Mod V(dc)
+--
Cut jumper
*
for 0-20 mA
or 4-20 mA
12
12
11
Mod V (dc)
–
+
–
+
V (dc)
Connection to Operate
Modulating Boiler
17
16
Com
Out
15
14
13
Boil
UnO
Com
Sw
UnOccupied Switch
If an external timer (tekmar Timer 032) or switch is used, connect the two wires from the
external switch to the Com and UnO Sw terminals (13 and 14). When these two terminals
are shorted together, the control registers an unoccupied (UNOCC) signal.
STEP FIVE
——————
TESTING THE WIRING
General
Each terminal block must be unplugged from its header on the control before power is applied for testing. To remove the terminal
block, pull straight down from the control.
The following tests are to be performed using standard testing practices and procedures and should only be carried out by
properly trained and experienced persons.
A good quality electrical test meter, capable of reading from at least 0 to 300 V (ac) and at least 0 to 2,000,000 Ω, is essential to
properly test the wiring and sensors.
Test The Sensors
In order to test the sensors, the actual temperature at each sensor
location must be measured. A good quality digital thermometer with
a surface temperature probe is recommended for ease of use and
accuracy. Where a digital thermometer is not available, a spare sensor
can be strapped alongside the one to be tested and the readings
compared. Test the sensors according to the instructions in the Data
Brochure D 070.
Make sure exposed wires and bare terminals are not in contact with
other wires or grounded surfaces. Turn on the power and measure
the voltage between the Power L and Power N terminals (5 and 6)
using an AC voltmeter, the reading should be between 103.5 and
126.5 V (ac).
Test the Powered Inputs
Boiler Demand
If a boiler demand is used, measure the voltage between the
Boil Demand terminals (1 and 2). When the boiler demand device
calls for heat, between 20 and 260 V (ac) shoul d be measur e d at th e
terminals. When the boiler demand device is off, less than 5 V (ac)
should be measured.
V
5
Power
L
Dem
Boil
2
103.5 to 126.5 V (ac)
20 to 260 V (ac)
6
N
1
Com
Dem
DHW Demand
If a DHW demand is used, measure the voltage between the
DHW Dem and the Com Dem terminals (2 and 3). When the DHW
Com
Dem
3
2
DHW
Dem
20 to 260 V (ac)
demand device calls for heat, between 20 and 260 V (ac) should b e
measured at the terminals. When the DHW demand device is off,
less than 5 V (ac) should be measured.
TEST THE OUTPUTS
Primary Pump (Prim P1)
If a primary pump is connected to the Prim P1 terminal (4), make sure that power to the terminal block is off and install a jumper
between the Power L and Prim P1 terminals (5 and 4). When power is applied to the Power L and Power N terminals (5 and 6),
the primary pump should start. If the pump does not turn on, check the wiring between the terminal block and pump and refer to
any installation or troubleshooting information supplied with the pump. If the pump operates properly, disconnect the power and
remove the jumper.
Boiler Pmp P2
If a b o i ler pump is connected t o t he Boiler Pmp P2 terminals (9 and 10),
make sure that power to the terminal block is off and install a jumper
between the terminals. When power is applied to circuit, the boiler
pump should start. If the pump does not turn on, check the wiring
between the terminal block and pump and refer to any installation or
troubleshooting information supplied with the pump. If the pump operates properly, disconnect the power and remove the jumper.
24 to 230 V (ac)
L
N
9
Boiler
Pmp P2
10
DHW Pump Or Valve (DHW Pmp / Vlv)
If a DHW pump or DHW valve is connected to the DHW Pmp / Vlv
terminals (7 and 8), make sure the power to the pump or valve circuit
is off and install a jumper between those terminals. When the DHW
circuit is powered up, the DHW pump should turn on or the DHW valve
should open completely. If the DHW pump or valve fails to operate,
check the wiring between the terminals and the pump or valve and refer
to any installation or troubleshooting information supplied with these
devices. If the DHW pump or valve operates correctly, disconnect the
power and remove the jumper.
Make sure all power to the devices and terminal blocks is off, and remove any remaining
jumpers from the terminals.
Reconnect the terminal blocks to the control by carefully aligning them with their respective
headers on the control, and then pushing the terminal blocks into the headers. The terminal
blocks should snap firmly into place.
Install the supplied safety dividers between the unpowered sensor inputs and the powered
or 115 V (ac) wiring chambers.
Apply power to the control. The operation of the control on power up is described in the
Sequence of Operation section of the brochure.
TEST THE MODULATING OUTPUT
If a modulating device is used, connect an ammeter to the modulating
output Mod V (dc) terminals (11 and 12) and observe the current reading
during operation. For example, when using a 0 to 10 V (dc) output, the
initial percentage output is zero and the meter should read 0 V (dc). As
the Boiler Modulation in the VIEW menu increases, the meter reading
should increase until the Boiler Modulation reaches 100% at which point
the meter should read 10 V (dc). When the 0 to 10 V (dc) modulation
decreases, the meter should start at 10 V (dc) and eventually reach
0 V (dc) when the display shows 0% Boiler Modulation.
V
Prim
P1
4
L
Power
Pmp/Vlv
N
11
ModV(dc)
+
DHW
12
-
8
7
6
5
Cleaning the Control
The control’s exterior can be cleaned using a damp cloth. Moisten the cloth with water and wring out prior to wiping control. Do not
use solvents or cleaning solutions.
DIP Switch Settings
GENERAL
The DIP switch settings on the control are very important and should be set
to the appropriate settings prior to making any adjustments to the control
through the User Interface. The DIP switch settings change the items that
are available to be viewed and / or adjusted in the User Interface.
If a DIP switch is c hanged while the cont rol is powered up, the control respond s
to the change in setting by returning the display to the VIEW menu.
Advanced / Installer
The Advanced / Installer DIP switch selects the access level of the control. In the
Installer access level, a limited number of items may be viewed and / or adjusted. In the
Advanced access level, all items may be viewed and / or adjusted.
DIP Switches
Boiler Demand
DHW Demand
Modulation
DHW Priority Override
Menu Item
Boiler Control 270
One Modulating Boiler & DHW
AdvancedOff
InstallerExercise
Advanced Off
Installer Exercise
Test
ting
s
te
t
o
n
ff
o
ting
s
te
d
e
r
d
e
s
u
a
p
ting
s
e
t
d
e
r
t
a
e
h
m
u
im
x
a
m
r
o
F
t
s
e
T
d
l
o
h
&
s
s
e
r
p
.
s
d
n
o
c
e
s
3
r
o
f
n
o
tt
u
b
:
B
s
s
la
C
ts
e
e
M
S
E
C
I
n
ia
d
a
n
a
C
Made in Canada by
tekmar Control Systems Ltd.
Power 115 V ±10% 50/60 Hz 600 VA
Relays 230 V (ac) 5 A 1/3 hp, pilot duty 240 VA
Demands 20 to 260 V (ac) 2 VA
Signal wiring must be rated at least 300 V.
5
1
t
r
a
P
C
C
F
e
d
o
C
e
t
a
D
Off / Exercise
The Off / Exercise DIP switch selects whether or not the control is to exercise the primary
AdvancedOff
pump and boiler pumps. If the DIP switch is set to Exercise, the pumps are operated for
10 seconds after every three days of inactivity.
Outdoor Current outdoor air temperature as measured by the
outdoor sensor.
Room Current room air temperature as measured by the indoor
sensor.
This item is only available when an indoor sensor is connected to
the control.
Boiler Supply Current boiler supply water temperature as measured
by the boiler supply sensor.
Boiler Target Boiler target temperature is the temperature the
control is currently trying to maintain at the boiler supply sensor
+/- ½ of the differential.
Boiler Modulation Current percent modulation of the boiler’s burner.
Range
-76 to 149°F
(-60 to 65°C)
23 to 113°F
(-5 to 45°C)
-22 to 266°F
(-30 to 130°C)
– – –, 35 to 230°F
(– – –, 2 to 110°C)
0 to 100%
Boiler Hours The total running time of the boiler since this item
was last cleared. To clear this item, press the and button
simultaneously while viewing this item.
The control has a built-in test routine that is used to test the main control
functions. The control continually monitors the sensors and displays an
error message whenever a fault is found. See the following pages for a
list of the control’s error messages and possible causes. When the Test
button is pressed, the Test light is turned on. The individual outputs and
relays are tested in the following test sequence.
TEST SEQUENCE
Each step in the test sequence lasts 10 seconds.
During the test routine, if a demand from the system is present, the test sequence may be paused by pressing the Test button.
If the Test button is not pressed again for 5 minutes while the test sequence is paused, the control exits the entire test routine. If
the test sequence is paused, the Te st button can be pressed again to advance to the next step. This can also be used to rapidly
advance through the test sequence. To reach the desired step, repeatedly press and release the Tes t button until the appropriate
device and segment in the display turn on.
Step 1 – The primary pump contact is closed.
Step 2 – The boiler pump contact is closed.
Step 3 – The Boiler contact is closed and the modulation output is set to the Minimum Modulation setting.
Step 4 –
Step 5 –
Step 6 – The Boiler and boiler pump contacts are opened.
– If DHW MODE is set to 1 or 2, the DHW Pmp / Vlv contact is closed and the primary pump contact is opened.
– If DHW MODE is set to 3 or 4, the DHW Pmp / Vlv contact is closed and the primary pump contact remains closed.
Step 7 – After the test sequence is completed, the control resumes its normal operation.
If there is a demand present, the modulation output increases to Maximum Modulation according to the Motor Speed setting.
If there is a demand present, the modulation output decreases to Minimum Modulation according to the Motor Speed setting.
The control has a function called Max Heat. In this mode, the control turns on and operates the system up to the maximum set
temperatures as long as there is a demand for heat. The control continues to operate in this mode for up to 24 hours or until the
Item, Menu or Tes t button is pressed. This mode may be used for running all circulators during system start-up in order to purge
air from the piping. To enable the Max Heat feature, use the following procedure.
1) Press and hold the Test button for more than 3 seconds. At this point, the control flashes
the MAX segment and displays the word OFF
2) Using the
or buttons, select the word On. After 3 seconds, the control turns on all
outputs. However, the max heat mode is still limited by the BOIL MAX setting.
3) To cancel the Max Heat mode, press the Item, Menu, or Test button.
4) Once the Max Heat mode has either ended or is cancelled, the control resumes
normal operation.
The control was unable to read a piece of information stored in its memory. Because of this, the control
was required to reload the factory settings into all of the items in the ADJUST menu. The control will
stop operation until all of the items in the ADJUST menu of the control have been checked by the user
or installer.
Note: The Advanced / Installer DIP switch must be set to Advanced in order to clear the error.
Boil Supply Sensor Short
The control is no longer able to read the boiler supply sensor due to a short circuit. The control will not
operate the boiler until the sensor is repaired. Locate and repair the problem as described in the Data
Brochure D 070. To clear the error message from the control after the sensor has been repaired, press
either the Menu or Item button.
Boil Supply Sensor Open
The control is no longer able to read the boiler supply sensor due to an open circuit. The control will not
operate the boiler until the sensor is repaired. Locate and repair the problem as described in the Data
Brochure D 070. To clear the error message from the control after the sensor has been repaired, press
either the Menu or Item button.
Outdoor Sensor Short
The control is no longer able to read the outdoor sensor due to a short circuit. In this case the control
assumes an outdoor temperature of 32°F (0°C) and continues operation. Locate and repair the problem
as described in the Data Brochure D 070. To clear the error message from the control after the sensor
has been repaired, press either the Menu or Item button.
Outdoor Sensor Open
The control is no longer able to read the outdoor sensor due to an open circuit. In this case the control
assumes an outdoor temperature of 32°F (0°C) and continues operation. Locate and repair the problem
as described in the Data Brochure D 070. To clear the error message from the control after the sensor
has been repaired, press either the Menu or Item button.
Indoor Sensor Short
The control is no longer able to read the indoor sensor due to a short circuit. The control will operate the
system as if an indoor sensor where not installed until the indoor sensor is repaired. Locate and repair
the problem as described in the Data Brochure D 074. To clear the error message from the control after
the sensor has been repaired, press either the Menu or Item button.
Indoor Sensor Open
The control is n o lon ger a ble to read t he indoor sens or du e to an o p en circui t. T he control wil l operate the
system as if an indoor sensor where not installed until the indoor sensor is repaired. Locate and repair
the problem as described in the Data Brochure D 074. To clear the error message from the control after
the sensor has been repaired, press either the Menu or Item button.
Literature — D 270, A 270, D 001, D 070.
Control — Microprocessor PID control; This is not a safety (limit) control.
Packaged weight — 3.3 lb. (1500 g), Enclosure A , blue modified PVC plastic
Dimensions — 6-5/8” H x 7-9/16” W x 2-13/16” D (170 x 193 x 72 mm)
Approvals — CSA C US, meets ICES & FCC regulations for EMI/RFI.
Ambi ent conditions — Indoor use only, 32 to 104°F (0 to 40°C), < 90% RH non-condensing.
Power supply — 115 V (ac) ±10% 50/60 Hz 600 VA
Relay capacit y — 230 V (ac) 5 A 1/3 hp pilot duty 240 VA
Modulation Output — 0 – 10 V (dc)
Demands — 20 to 260 V (ac) 2 VA
Boiler Demand
DHW Demand
Modulation
DHW Priority Override
Sensors included — NTC thermistor, 10 k @ 77°F (25°C ±0.2°C) ß=3892
Outdoor Sensor 070 and Universal Sensor 082
Optional devices — Indoor Sensor 076/077
Menu Item
Boiler Control 270
One Modulating Boiler & DHW
1
2
3
4 5NL6
7 89 1011
Boil
Com
DHW
Dem
Dem
Dem
DHW
Prim
Power
P1
Pmp/Vlv
Pmp P2
Boiler
The installer must ensure that this control and its wiring are isolated and/or shielded from strong sources of electromagnetic noise. Conversely, this Class B digital apparatus
complies with Part 15 of the FCC Rules and meets all requirements of the Canadian Interference-Causing Equipment Regulations. However, if this control does cause harmful
interference to radio or television reception, which is determined by turning the control off and on, the user is encouraged to try to correct the interference by re-orientating
or relocating the receiving antenna, relocating the receiver with respect to this control, and/or connecting the control to a different circuit from that to which the receiver is
connected.
Cet appareil numérique de la classe B respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada.
Caution The nonmetallic enclosure does not provide grounding between conduit connec tions. Use grounding type bushings and jumper wires.
Attention Un boîtier nonmétallique n´assure pas la continuité électrique des conduits. Utiliser des manchons ou des fils de ac cord spécialement conçus pour la mise
á la terre.
AdvancedOff
InstallerExercise
Tes t
ff
o
te
d
re
te
d
re
or m
F
s
s
pre
to
ut
b
Made in Canada by
tekmar Control Systems Ltd.
tektra 969-03
Power 115 V ±10% 50/60 Hz 600 VA
Relays 230 V (ac) 5 A 1/3 hp, pilot duty 240 VA
Demands 20 to 260 V (ac) 2 VA
Signal wiring must be rated at least 300 V.
Do not apply power
12 13 14 15 16 17 18
Mod V(dc)Out Com Indr
UnO Boil
Com
+--
Sw
g
testin
t
o
n
ting
s
d
e
s
u
a
p
ting
s
at
e
h
um
im
x
a
t
s
e
hold T
&
ds.
n
o
ec
for 3 s
n
:
B
s
las
ts C
ee
M
S
E
IC
n
ia
d
a
an
C
5
rt 1
a
P
C
C
F
e
d
o
C
e
t
a
D
H2039A
Limited Warranty and Product Return Procedure
Limited Warranty The liability of tekmar under this warranty is limited. The
Purchaser, by taking receipt of any tekmar product (“Product ”), acknowledges the terms of the Limited Warranty in effect at the time of such Product
sale and acknowledges that it has read and understands same.
The tekmar Limited Warranty to the Purchaser on the Products sold hereunder
is a manufacturer’s pass-through warranty which the Purchaser is authorized
to pass through to its customers. Under the Limited Warranty, each tekmar
Product is warranted against defects in workmanship and materials if the Product is installed and used in compliance with tekmar’s instructions, ordinary
wear and tear excepted. The pass-through warranty period is for a period of
twenty-four (24) months from the production date if the Product is not installed
during that period, or twelve (12) months from the documented date of installation if installed within twenty-four (24) months from the production date.
The liability of tekmar under the Limited Warranty shall be limited to, at tekmar’s
sole discretion: the cost of parts and labor provided by tekmar to repair defects in
materials and/or workmanship of the defective product; or to the exchange of the
defective product for a warranty replacement product; or to the granting of credit
limited to the original c ost of the defective product, and such repair, exchange or
credit shall be the sole remedy available from tekmar, and, without limiting the
foregoing in any way, tekmar is not responsible, in contract, tort or strict product liabilit y, for any other losses, costs, expenses, inconveniences, or damages,
whether direct, indirect, special, secondar y, incidental or consequential, arising
fro m ownership or u se of t he produc t, or f ro m defe cts i n workmanship o r materials,
including any liability for fundamental breach of contract.
The pass-through Limited Warranty applies only to those defective Pro ducts
returned to tekmar during the warrant y period. This Limited Warranty does not
cover the cost of the parts or labor to remove or transport the defective Product, or
to reinstall the repaired or replacement Product, all such costs and expenses being
subject to Purchaser’s agreement and warranty with its customers.
Any representations or warranties about the Products made by Purchaser to its
customers which are different from or in excess of the tekmar Limited Warranty are
the Purchaser’s sole responsibility and obligation. Purchaser shall indemnify and
hold tekmar harmless from and against any and all claims, liabilities and damages
of any kind or nature which arise out of or are related to any such representations
or warranties by Purchaser to its customers.
The pass-through Limited Warranty does not ap ply if the returned Product has
been damaged by negligence by persons other than tekmar, accident, fire, Act
of God, abuse or misuse; or has been damaged by modifications, alterations or
attachments made subsequent to purchase which have not been authorized by
tekmar; or if the Product was not installed in compliance with tekmar’s instructions
and/or the local codes and ordinanc es; or if due to defec tive installation of the
Product; or if the Product was not used in compliance with tekmar’s instructions.
THIS WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR
IMPLIED, WHICH THE GOVERNING LAW ALLOWS PARTIES TO CONTRACTUALLY EXCLUDE, INCLUDING, WITHOUT LIMITATION, IMPLIED WARRANTIES
OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, DURABILITY OR DESCRIPTION OF THE PRODUCT, ITS NON-INFRINGEMENT OF
ANY RELEVANT PATENTS OR TRADEMARKS, AND ITS COMPLIANCE WITH
OR NON-VIOLATION OF ANY APPLICABLE ENVIRONMENTAL, HEALTH OR
SAFETY LEGISL ATION; THE TERM OF ANY OTHER WARRANTY NOT HEREBY
CONTRACTUALLY EXCLUDED IS LIMITED SUCH THAT IT SHALL NOT EXTEND
BEYOND TWENTY-FOUR (24) MONTHS FROM THE PRODUCTION DATE, TO
THE EXTENT THAT SUCH LIMITATION IS ALLOWED BY THE GOVERNING
LAW.
Product Warranty Return Procedure All Products that are believed to have
defects in workmanship or materials must be returned, together with a written
description of the defect, to the tekmar Representative assigned to the territor y in
which such Product is located. If tekmar receives an inquiry from someone other
than a tekmar Representative, including an inquiry from Purchaser (if not a tekmar
Representative) or Purchaser’s customers, regarding a potential warranty claim,
tekmar’s sole obligation shall be to provide the address and other contact information regarding the appropriate Representative.
tekmar Control Systems Ltd., Canada
Control Systems
tekmar Control Systems, Inc., U.S.A.
Head Office: 5100 Silver Star Road
Vernon, B.C. Canada V1B 3K4
(250) 545 -7749 Fax. (250) 545-0650
Web Site: www.tekmarcontrols.com