The tekmar Boiler Control 270 can control the supply water temperature from a single modulating boiler based on outdoor temperature
or domestic hot water requirements. A large easy to read display provides current system temperatures and operating status.
Additional functions include:
• Outdoor Reset
• Installer and Advanced access levels
• Primary pump output
• Pump exercising
• Pump purging
• DHW demand for domestic hot water loads
• Optional indoor sensor for room air temperature control
• Test sequence to ensure proper component operation
• Setback input for energy savings
• CSA C US certified
• Boiler demand for space heating loads
Input
Boiler
Demand
Menu Item
Boiler Control 270
One Modulating Boiler & DHW
1
2
3
4 5NL6
DHW
Dem
Prim
P1
Boil
Com
Dem
Dem
Boiler Demand
DHW Demand
Modulation
DHW Priority Override
7 89 1011
DHW
Power
Pmp/Vlv
Boiler
Pmp P2
AdvancedOff
InstallerExercise
Test
off not testing
red
red
For maximum heat
press & hold Test
button for 3 second
Made in Canada by
tekmar Control Systems Ltd.
tektra 969-03
Power 115 V ±10% 50/60 Hz 600 VA
Relays 230 V (ac) 5 A 1/3 hp, pilot duty 240 VA
Demands 20 to 260 V (ac) 2 VA
This brochure is organized into four main sections. They are: 1) Sequence of Operation, 2) Installation, 3) Control Settings, and
4) Testing and Troubleshooting. The Sequence of Operation section has six sub-sections. We recommend reading Section A: General
of the Sequence of Operation, as this contains important information on the overall operation of the control. Then read the sub
sections that apply to your installation.
The Control Settings section (starting at DIP Switch Settings) of this brochure describes the various items that are adjusted and
displayed by the control. The control functions of each adjustable item are described in the Sequence of Operation.
Table of Contents
User Interface ..................................................Pg 2
The control uses a Liquid Crystal Display (LCD) as the method of supplying information. You use the LCD in order to setup and
monitor the operation of your system. The control has four push buttons (Menu, Item, , ) for selecting and adjusting settings. As
you program your control, record your settings in the ADJUST menu table, which is found in the second half of this brochure.
Menu
All of the items displayed by the control are organized into two menus (View and Adjust).
These menus are listed on the top left hand side of the display (Menu Field). To select
a menu, use the Menu button. By pressing and releasing the Menu button, the display
sequences between the two menus. Once a menu is selected, there will be a group of
items that can be viewed within the menu.
Item
The abbreviated name of the selected item will be displayed in the item field of the
display. To view the next available item, press and release the Item button. Once you
have reached the last available item in a menu, pressing and releasing the Item button
will return the display to the first item in the selected menu.
The items can be quickly scrolled through by holding the Item button and then pressing
button. To rapidly scroll through the items in the reverse order, hold the Item
the
button and press the button.
Adjust
To make an adjustment to a setting in the control, begin by selecting the ADJUST menu
using the Menu button. Then select the desired item using the Item button. Finally, use
the , and / or button to make the adjustment.
Additional information can be gained by observing the Status field of the LCD. The
status field will indicate which of the control’s outputs are currently active. Most
symbols in the status field are only visible when the VIEW menu is selected.
The following defined terms and symbols are used throughout this manual to bring attention to the presence of hazards of various risk
levels, or to important information concerning the life of the product.
- Warning Symbol: Indicates presence of hazards which can cause severe personal injury, death or
substantial property damage if ignored.
INSTALLATION
CATEGORY II
- Double insulated
- Local level, appliances
Sequence of Operation
Section A
General
Operation
Page 4 - 5
Section B
Boiler
Operation
Page 5 - 7
Section C
Pump
Operation
Page 8
Section D
Boiler Reset
Operation
Page 8 - 10
Section E
DHW
Operation
Page 10 - 13
Section A: General Operation
POWERING UP THE CONTROL
When the control is powered up, all segments in the LCD are turned on for 2 seconds. Next, the control displays the control type
number in the LCD for 2 seconds. Next, the software version is displayed for 2 seconds. Finally, the control enters into the normal
operating mode.
OPERATION
The control stages or modulates the boiler to control supply water temperature to a hydronic system. The supply water temperature
is based on outdoor reset or a fixed temperature for DHW.
Outdoor Reset
When a boiler demand signal from the heating system is present, the control operates the boiler(s) to maintain the supply
temperature based on the outdoor air temperature and the Characterized Heating Curve settings. Refer to section D.
DHW
When a DHW demand is present, the control operates the boiler to maintain the supply water temperature at least as hot as the
DHW exchange setting or high enough to satisfy tank temperature. Refer to section E.
SETBACK (Occ and UnOcc)
14
To provide greater energy savings, the control has a setback feature. With setback, the
supply water temperature in the system is reduced when the building is unoccupied. By
reducing the supply water temperature, the air temperature in the space may be reduced
even when thermostat(s) are not turned down. Any time the UnO Sw (18) and the Com (17)
are shorted together, the control operates in the unoccupied mode.
When in the unoccupied mode, the UNOCC segment is displayed in the LCD. The control
adjusts the supply water temperature based on the UNOCC settings made in the control.
The control has a built-in exercising feature that is selected through the Exercise / Off DIP switch. To enable the exercising feature
set the Exercise / Off DIP switch to Exercise. If exercising is enabled, the control ensures that each pump is operated at least
once every 3 days. If a pump has not been operated at least once every 3 days, the control turns on the output for 10 seconds.
This minimizes the possibility of the pump seizing during a long period of inactivity. While the control is exercising, the Test LED
flashes quickly.
Note: The exercising function does not work if power to the control or pumps is disconnected.
RUNNING TIMES
The control displays the accumulated running time of the boiler in the VIEW menu.
Resetting the Running Time
To reset the running time for the boiler, select the running time in the VIEW menu. Next press the and buttons simultaneously
until CLR is displayed.
FACTORY D EFAULTS
The control comes preset with several factory defaults. These are based on the terminal unit selection. To fine-tune building
requirements, these defaults may be changed.
To reload the factory default, power down the control and wait for 10 seconds. Power up the control while simultaneously
holding the Menu and buttons. An E01 error occurs forcing the installer to go through the ADJUST menu to ensure the
settings are correct.
Section B: Boiler Operation
BOILER TARGET TEMPERATURE
The boiler target temperature is determined by the type of demand received by the control. A boiler demand calculates a boiler
target based on the characterized heating curve settings and the outdoor air temperature. A DHW demand has a temperature
setting to which the boiler is operated to meet.
The control displays the temperature that it is currently trying to maintain as the boiler supply temperature. If the control does not
presently have a requirement for heat, it does not show a boiler target temperature. Instead, “– – –” is displayed in the LCD.
BOILER MINIMUM
The boiler minimum is the lowest temperature that the control is
allowed to use as a boiler target temperature. During mild conditions,
if the control calculates a boiler target temperature that is below the
Boiler Minimum setting, the boiler target temperature is adjusted to at
least the Boiler Minimum setting. During this condition, if the boiler is
operating, the minimum segment is turned on in the display when viewing
either the boiler supply temperature or the boiler target temperature. Set
the Boiler Minimum setting to the boiler manufacturer’s recommended
temperature.
BOILER MAXIMUM
The boiler maximum is the highest temperature that the control is
allowed to use as a boiler target temperature. If the control does target
the Boiler Maximum setting, and the boiler temperature is near the boiler
maximum temperature, the maximum segment will be displayed in the
LCD while either the boiler target temperature or the boiler temperature
is being viewed. At no time does the control operate the boiler above
248°F (120°C).
MIN Segment On
MAX Segment
On
Boiler
Contact Closes
Boiler
Fires
MAX Segment
On
FIRE DELAY
The Fire Delay is the time delay that occurs between the time that the control
closes a stage contact to fire a stage and the burner fires for that stage.
The Boiler Control 270 provides a modulating output signal to operate a single modulating boiler. The control first closes the boiler
contact on to ignite the ignition sequence. The boiler is then modulated from the minimum modulation using Proportional, Integral
and Derivative (PID) logic in order to satisfy the boiler target temperature.
MOTOR SPEED
The Motor Speed is the amount of time the boiler requires to go from 0%
modulation to 100% modulation.
Gas valve actuating motors have a design time from fully closed to
fully open which can be found in the manufacturer’s manual. The
Motor Speed should be set to this time.
The Motor Speed setting for a Variable Frequency Drive (VFD) is the
amount of time required to go from a stopped position to 100% fan
speed. Since a VFD has a very quick response rate, it may be necessary
to increase the Motor Speed setting in order to increase the stability of
the boiler modulation.
MODULATION RANGE (0 to 10 V (dc), 2 to 10 V (dc), 0 to 20 mA, 4 to 20 mA)
The modulation output can be adjusted from a 0 to 10 V (dc) or to a 2 to 10 V (dc) output range using the Boil Modulation setting.
If a 0 to 20 mA range is required, set the Boil Modulation item to 0 to 10 V (dc) and cut the jumper wire located next to the modulation
output.
If a 4 to 20 mA range is required, set the Boil Modulation item to 2 to 10 V (dc) and cut the jumper wired located next to the
modulation output.
MINIMUM MODULATION
The minimum modulation defines the minimum output signal from the control to the boiler
burner. It is based on a percentage of the control’s output signal range.
The Minimum Modulation setting for boilers with power burners is typically set to
0%.
For boilers with electronic operators, the boiler’s input signal range may not match the
output signal range of the 270 control. The Minimum Modulation setting limits the control
output range in order to match the boiler’s input range.
To calculate the Minimum Modulation, use the following formula:
For 0 to 10 V (dc):
Minimum Modulation =
0 V (dc) – Boiler’s Minimum Input Signal
0 – 10 V (dc)
x 100%
For 2 to 10 V (dc):
Minimum Modulation =
2 V (dc) – Boiler’s Minimum Input Signal
2 – 10 V (dc)
x 100%
MINIMUM MODULATION
Control's
Output
Signal
Range
Minimum
Modulation
100%10 V (dc)10 V (dc)
Boiler's
Input
Signal
Range
18%
0%0 V (dc)
1.8 V (dc)
Boiler's Minimum
Input Signal
Example:
A boiler requires a 1.8 V (dc) signal to fire the boiler at low fire. The boiler can be modulated to 10 V (dc) where it reaches high fire. This
means the boiler’s input signal range is 1.8 to 10 V (dc). The 270 control has an output signal range of 0 to 20 mA.
To make the two signal ranges the same, the Minimum Modulation required is:
0 V – 1.8 V
Minimum Modulation
=
0 V – 10 V
x 100% = 18%
MAXIMUM MODULATION
The maximum modulation defines the maximum output signal from the control
to the boiler burner. It is based on a percentage of the control’s output signal
range.
The Maximum Modulation setting for boilers with power burners is
typically set to 100%.
For boilers with electronic operators, the boiler’s input signal range may not
match the output signal range of the 270 control. The Maximum Modulation
setting limits the control output range in order to match the boiler’s input
range.
To calculate the Maximum Modulation, use the following formula:
For 0 to 10 V (dc):
Maximum Modulation =
0 V (dc) – Boiler’s Maximum Input Signal
0 – 10 V (dc)
x 100%
For 2 to 10 V (dc):
Maximum Modulation =
2 V (dc) – Boiler’s Maximum Input Signal
2 – 10 V (dc)
x 100%
Example:
A boiler’s input signal range is 2 to 9 V (dc). The 270 control has an output signal range of 2 to 10 V (dc).
To make the two signal ranges the same, the Maximum Modulation required is:
Maximum Modulation =
2 V – 9 V
2 V – 10 V
x 100% = 88%
BOILER MASS
The Boiler Mass setting allows the installer to adjust the control to the thermal mass of the type of heat sources used in the
application. The modulation of the boiler can become unstable if the incorrect Boiler Mass setting is chosen. A key sign of the boiler
modulation being unstable is the flame will continue to increase and then decrease in short periods of time. By choosing a lower
Boiler Mass setting, the boiler response will become more stable.
Lo (1)
The Lo setting is selected if the boiler that is used has a low thermal mass. This means that the boiler has a very small water
content and has very little metal in the heat exchanger. A boiler that has a low thermal mass comes up to temperature quite rapidly
when fired. This is typical of many copper fin-tube boilers. The Lo Mass setting provides a fast response to the heating system.
Med (2)
The Med setting is selected if the boiler that is used has a medium thermal mass. This means that the boiler either has a large
water content and a low metal content or a low water content and a high metal content. This is typical of many modern residential
cast iron boilers or steel tube boilers. The Med Mass setting provides a moderate response to the heating system.
Hi (3)
The Hi setting is selected if the boiler that is used has a high thermal mass. This means that the boiler has both a large water
content and a large metal content. A boiler that has a high thermal mass is relatively slow in coming up to temperature. This is
typical of many commercial cast iron and steel tube boilers. The Hi Mass setting provides a slow response to the heating system.
DIFFERENTIAL
A modulating boiler must be operated with a differential while operating in low fire. The boiler differential is divided around the boiler
target temperature. The boiler burner ignites at low fire when the supply water temperature is ½ of the Boiler Differential setting
below the boiler target temperature. The boiler is shut off in low fire as the supply temperature reaches at least ½ of the differential
above the boiler target temperature. With the control, either a fixed or an auto differential may be selected.
When the boiler is modulating above low fire, the differential does not apply. Instead, the modulation output signal is determined
using Proportional, Integral and Derivative (PID) logic in order to satisfy the boiler target temperature.
Desired temperature
Fixed Differential
If the user desires to have a fixed differential, this is set using the
Boiler Differential setting in the ADJUST menu.
160°F (71°C)
Boiler Off
Boiler On
165°F (74°C)
a
r
e
p
m
e
T
e
s
i
r
e
r
u
t
155°F (68°C)
T
e
m
p
e
r
a
t
u
Differential
10°F (6°C)
r
e
f
a
l
l
Time
Auto Differential
If the Auto Differential is selected, the control automatically determines
the best differential as the load changes. This reduces potential short
cycling during light load conditions.
The primary pump operates under the following conditions:
• A boiler demand is present and the control is not in Warm Weather
Shut Down (WWSD).
• A DHW demand is present and DHW MODE is set to 3 or 4.
Primary
Primary Pump Purge
Pump
After a demand is removed, the control continues to operate the primary
pump for a period of time. The maximum length of time that the primary
pump continues to run is adjustable using the Primary Pump Purge
setting. The primary pump continues to run until either the purging
time has elapsed or the boiler supply temperature drops more than a
differential below the Boiler Minimum setting.
BOILER PUMP OPERATION
The boiler pump turns on prior to the boiler firing (pre-purge) and continues to run after the boiler is turned off (post-purge). The
boiler pump pre-purge time is determined by the Boiler Mass setting. As the Boiler Mass setting is increased, the boiler pump pre-
purge time of the boiler also increases.
Boiler Pump Purge
The amount of time that the boiler pump continues to run after the boiler turns off is adjustable using the Boiler Pump Purge setting.
DHW
Pump
Boiler
Sensor
Boiler
Pump
Section D: Boiler Reset Operation
BOILER DEMAND
A boiler demand is required in order for the control to provide heat to
the heating system. A boiler demand is generated by applying a voltage
between 24 and 230 V (ac) across the Boiler Demand terminals (1 and
2). Once voltage is applied, the Boiler Demand pointer is displayed in
the LCD. If the control is not in Warm Weather Shut Down (WWSD), the
control closes the primary pump contact. The control calculates a boiler
target supply temperature based on the outdoor air temperature and the
characterized heating curve settings. The control then fires the boiler, if
24 to 230 V (ac)
L
N
required, to maintain the target supply temperature.
OUTDOOR DESIGN TEMPERATURE
The outdoor design temperature is the outdoor air temperature that is the typical coldest temperature of the year where the building
is located. This temperature is used when doing the heat loss calculations for the building. If a cold outdoor design temperature is
selected, the boiler supply temperature rises gradually as the outdoor temperature drops. If a warm outdoor design temperature is
selected, the boiler supply temperature rises rapidly as the outdoor temperature drops.