tekmar 270 User Manual

Page 1
- Data Brochure
Boiler Control 270
D 270
08/10
The tekmar Boiler Control 270 can control the supply water temperature from a single modulating boiler based on outdoor temperature or domestic hot water requirements. A large easy to read display provides current system temperatures and operating status.
Additional functions include:
• Outdoor Reset
• Installer and Advanced access levels
• Primary pump output
• Pump exercising
• Pump purging
• DHW demand for domestic hot water loads
• Optional indoor sensor for room air temperature control
• Test sequence to ensure proper component operation
• Setback input for energy savings
• CSA C US certified
• Boiler demand for space heating loads
Boiler
Demand
Menu Item
Boiler Control 270
One Modulating Boiler & DHW
1
2
3
4 5NL6
DHW Dem
Prim
P1
Boil
Com
Dem
Dem
Boiler Demand
DHW Demand
Modulation
DHW Priority Override
7 8 9 10 11
DHW
Power
Pmp/Vlv
Boiler
Pmp P2
Advanced Off
Installer Exercise
Test
off not testing red red
For maximum heat press & hold Test button for 3 second
Made in Canada by tekmar Control Systems Ltd. tektra 969-03
Power 115 V ±10% 50/60 Hz 600 VA Relays 230 V (ac) 5 A 1/3 hp, pilot duty 240 VA Demands 20 to 260 V (ac) 2 VA
Signal wiring must be rated at least 300 V.
Do not apply power
12 13 14 15 16 17 18
Mod V(dc) Out Com Indr
UnO Boil
Com
+--
Sw
testing testing paused
Meets Class B: Canadian ICES FCC Part 15
s.
Date Code
H2039A
Indoor Sensor
Optional
DHW
Demand
Outdoor Sensor
Included
Output
Primary
Pump
Input
115 V (ac)
Power Supply
OR
Output
DHW Pump or
DHW Valve
M
Output
Pump
Output
Boiler
tekmar
Timer
Universal Sensor
Included
1 of 24 © 2010 D 270 - 08/10
Page 2
How To Use The Data Brochure
This brochure is organized into four main sections. They are: 1) Sequence of Operation, 2) Installation, 3) Control Settings, and
4) Testing and Troubleshooting. The Sequence of Operation section has six sub-sections. We recommend reading Section A: General of the Sequence of Operation, as this contains important information on the overall operation of the control. Then read the sub sections that apply to your installation.
The Control Settings section (starting at DIP Switch Settings) of this brochure describes the various items that are adjusted and displayed by the control. The control functions of each adjustable item are described in the Sequence of Operation.
Table of Contents
User Interface ..................................................Pg 2
Display ............................................................. Pg 3
Sequence of Operation ..................................Pg 4
Section A: General Operation .............. Pg 4
Section B: Boiler Operation.................. Pg 5
Section C: Pump Operation .................. Pg 8
Section D: Boiler Reset Operation ......Pg 8
Section E: DHW Operation ...................Pg 10
DIP Switch Settings ........................................Pg 17
Control Settings ..............................................Pg 18
View Menu ..............................................Pg 18
Adjust Menu ...........................................Pg 19
Testing the Control ......................................... Pg 21
Error Messages ...............................................Pg 23
Technical Data .................................................Pg 24
Limited Warranty ............................................Pg 24
Installa tion ....................................................... Pg 13
User Interface
The control uses a Liquid Crystal Display (LCD) as the method of supplying information. You use the LCD in order to setup and monitor the operation of your system. The control has four push buttons (Menu, Item, , ) for selecting and adjusting settings. As you program your control, record your settings in the ADJUST menu table, which is found in the second half of this brochure.
Menu
All of the items displayed by the control are organized into two menus (View and Adjust). These menus are listed on the top left hand side of the display (Menu Field). To select a menu, use the Menu button. By pressing and releasing the Menu button, the display sequences between the two menus. Once a menu is selected, there will be a group of items that can be viewed within the menu.
Item
The abbreviated name of the selected item will be displayed in the item field of the display. To view the next available item, press and release the Item button. Once you have reached the last available item in a menu, pressing and releasing the Item button will return the display to the first item in the selected menu.
The items can be quickly scrolled through by holding the Item button and then pressing
button. To rapidly scroll through the items in the reverse order, hold the Item
the button and press the button.
Adjust
To make an adjustment to a setting in the control, begin by selecting the ADJUST menu using the Menu button. Then select the desired item using the Item button. Finally, use the , and / or button to make the adjustment.
Additional information can be gained by observing the Status field of the LCD. The status field will indicate which of the control’s outputs are currently active. Most symbols in the status field are only visible when the VIEW menu is selected.
© 2010 D 270 - 08/10 2 of 24
Page 3
Display
Menu Field
Displays the current menu
Item Field
Displays an abbreviated name of the selected item
Status Field
Displays the current status of the control's inputs, outputs and operation
Number Field
Displays the current value of the selected item
Boiler Demand DHW Demand Modulation DHW Priority Override
Buttons
Selects Menus, Items and adjust settings
Symbol Description
Burner
Displays when Relay 1 is turned on.
Pump
Displays when the primary or boiler pump is operating.
DHW
Displays when the DHW pump is on.
Occupied Schedule
Displays when the control is in occupied mode.
UnOccupied Schedule
Displays when the control is in unoccupied mode.
Warning
Displays when an error exists or when a limit has been reached.
Lock / Unlock
Displays when the Advanced / Installer DIP switch is set to Installer.
°F, °C, min, hr, %
Units of measurement.
Pointer
Displays the control operation as indicated by the text.
Modulating Output Scale
Displays the total modulation output level of the boiler.
3 of 24 © 2010 D 270 - 08/10
Page 4
Definitions
The following defined terms and symbols are used throughout this manual to bring attention to the presence of hazards of various risk levels, or to important information concerning the life of the product.
- Warning Symbol: Indicates presence of hazards which can cause severe personal injury, death or substantial property damage if ignored.
INSTALLATION
CATEGORY II
- Double insulated
- Local level, appliances
Sequence of Operation
Section A
General
Operation
Page 4 - 5
Section B
Boiler Operation Page 5 - 7
Section C
Pump
Operation
Page 8
Section D
Boiler Reset
Operation
Page 8 - 10
Section E
DHW
Operation
Page 10 - 13
Section A: General Operation
POWERING UP THE CONTROL
When the control is powered up, all segments in the LCD are turned on for 2 seconds. Next, the control displays the control type number in the LCD for 2 seconds. Next, the software version is displayed for 2 seconds. Finally, the control enters into the normal operating mode.
OPERATION
The control stages or modulates the boiler to control supply water temperature to a hydronic system. The supply water temperature is based on outdoor reset or a fixed temperature for DHW.
Outdoor Reset
When a boiler demand signal from the heating system is present, the control operates the boiler(s) to maintain the supply temperature based on the outdoor air temperature and the Characterized Heating Curve settings. Refer to section D.
DHW
When a DHW demand is present, the control operates the boiler to maintain the supply water temperature at least as hot as the DHW exchange setting or high enough to satisfy tank temperature. Refer to section E.
SETBACK (Occ and UnOcc)
14
To provide greater energy savings, the control has a setback feature. With setback, the supply water temperature in the system is reduced when the building is unoccupied. By reducing the supply water temperature, the air temperature in the space may be reduced even when thermostat(s) are not turned down. Any time the UnO Sw (18) and the Com (17) are shorted together, the control operates in the unoccupied mode.
When in the unoccupied mode, the UNOCC segment is displayed in the LCD. The control adjusts the supply water temperature based on the UNOCC settings made in the control.
13
UnO
Com
Sw
UnOccupied
Switch
© 2010 D 270 - 08/10 4 of 24
Page 5
EXERCISING
The control has a built-in exercising feature that is selected through the Exercise / Off DIP switch. To enable the exercising feature set the Exercise / Off DIP switch to Exercise. If exercising is enabled, the control ensures that each pump is operated at least once every 3 days. If a pump has not been operated at least once every 3 days, the control turns on the output for 10 seconds. This minimizes the possibility of the pump seizing during a long period of inactivity. While the control is exercising, the Test LED flashes quickly.
Note: The exercising function does not work if power to the control or pumps is disconnected.
RUNNING TIMES
The control displays the accumulated running time of the boiler in the VIEW menu.
Resetting the Running Time
To reset the running time for the boiler, select the running time in the VIEW menu. Next press the and buttons simultaneously until CLR is displayed.
FACTORY D EFAULTS
The control comes preset with several factory defaults. These are based on the terminal unit selection. To fine-tune building requirements, these defaults may be changed.
To reload the factory default, power down the control and wait for 10 seconds. Power up the control while simultaneously holding the Menu and buttons. An E01 error occurs forcing the installer to go through the ADJUST menu to ensure the settings are correct.
Section B: Boiler Operation
BOILER TARGET TEMPERATURE
The boiler target temperature is determined by the type of demand received by the control. A boiler demand calculates a boiler target based on the characterized heating curve settings and the outdoor air temperature. A DHW demand has a temperature setting to which the boiler is operated to meet.
The control displays the temperature that it is currently trying to maintain as the boiler supply temperature. If the control does not presently have a requirement for heat, it does not show a boiler target temperature. Instead, “– – –” is displayed in the LCD.
BOILER MINIMUM
The boiler minimum is the lowest temperature that the control is allowed to use as a boiler target temperature. During mild conditions, if the control calculates a boiler target temperature that is below the Boiler Minimum setting, the boiler target temperature is adjusted to at least the Boiler Minimum setting. During this condition, if the boiler is operating, the minimum segment is turned on in the display when viewing either the boiler supply temperature or the boiler target temperature. Set the Boiler Minimum setting to the boiler manufacturer’s recommended temperature.
BOILER MAXIMUM
The boiler maximum is the highest temperature that the control is allowed to use as a boiler target temperature. If the control does target the Boiler Maximum setting, and the boiler temperature is near the boiler maximum temperature, the maximum segment will be displayed in the LCD while either the boiler target temperature or the boiler temperature is being viewed. At no time does the control operate the boiler above 248°F (120°C).
MIN Segment On
MAX Segment
On
Boiler Contact Closes
Boiler Fires
MAX Segment
On
FIRE DELAY
The Fire Delay is the time delay that occurs between the time that the control closes a stage contact to fire a stage and the burner fires for that stage.
5 of 24 © 2010 D 270 - 08/10
Fire
Delay
Time
Page 6
MODULATION
The Boiler Control 270 provides a modulating output signal to operate a single modulating boiler. The control first closes the boiler contact on to ignite the ignition sequence. The boiler is then modulated from the minimum modulation using Proportional, Integral and Derivative (PID) logic in order to satisfy the boiler target temperature.
MOTOR SPEED
The Motor Speed is the amount of time the boiler requires to go from 0% modulation to 100% modulation.
Gas valve actuating motors have a design time from fully closed to fully open which can be found in the manufacturer’s manual. The Motor Speed should be set to this time.
The Motor Speed setting for a Variable Frequency Drive (VFD) is the amount of time required to go from a stopped position to 100% fan speed. Since a VFD has a very quick response rate, it may be necessary to increase the Motor Speed setting in order to increase the stability of the boiler modulation.
MODULATION RANGE (0 to 10 V (dc), 2 to 10 V (dc), 0 to 20 mA, 4 to 20 mA)
The modulation output can be adjusted from a 0 to 10 V (dc) or to a 2 to 10 V (dc) output range using the Boil Modulation setting. If a 0 to 20 mA range is required, set the Boil Modulation item to 0 to 10 V (dc) and cut the jumper wire located next to the modulation
output. If a 4 to 20 mA range is required, set the Boil Modulation item to 2 to 10 V (dc) and cut the jumper wired located next to the
modulation output.
MINIMUM MODULATION
The minimum modulation defines the minimum output signal from the control to the boiler burner. It is based on a percentage of the control’s output signal range.
The Minimum Modulation setting for boilers with power burners is typically set to 0%.
For boilers with electronic operators, the boiler’s input signal range may not match the output signal range of the 270 control. The Minimum Modulation setting limits the control output range in order to match the boiler’s input range.
To calculate the Minimum Modulation, use the following formula:
For 0 to 10 V (dc):
Minimum Modulation =
0 V (dc) – Boiler’s Minimum Input Signal
0 – 10 V (dc)
x 100%
For 2 to 10 V (dc):
Minimum Modulation =
2 V (dc) – Boiler’s Minimum Input Signal
2 – 10 V (dc)
x 100%
MINIMUM MODULATION
Control's
Output Signal Range
Minimum Modulation
100%10 V (dc) 10 V (dc)
Boiler's Input Signal Range
18%
0%0 V (dc)
1.8 V (dc)
Boiler's Minimum
Input Signal
Example:
A boiler requires a 1.8 V (dc) signal to fire the boiler at low fire. The boiler can be modulated to 10 V (dc) where it reaches high fire. This means the boiler’s input signal range is 1.8 to 10 V (dc). The 270 control has an output signal range of 0 to 20 mA.
To make the two signal ranges the same, the Minimum Modulation required is:
0 V – 1.8 V
Minimum Modulation
=
0 V – 10 V
x 100% = 18%
MAXIMUM MODULATION
The maximum modulation defines the maximum output signal from the control to the boiler burner. It is based on a percentage of the control’s output signal range.
The Maximum Modulation setting for boilers with power burners is typically set to 100%.
For boilers with electronic operators, the boiler’s input signal range may not match the output signal range of the 270 control. The Maximum Modulation setting limits the control output range in order to match the boiler’s input range.
© 2010 D 270 - 08/10 6 of 24
Maximum
Modulation
MAXIMUM MODULATION
Control's
Output
Signal
Range
100%10 V (dc)
88%
9 V (dc)
Boiler's Input Signal Range
0%2 V (dc)
2 V (dc)
Boiler's
Maximum
Input Signal
Page 7
To calculate the Maximum Modulation, use the following formula:
For 0 to 10 V (dc): Maximum Modulation =
0 V (dc) – Boiler’s Maximum Input Signal
0 – 10 V (dc)
x 100%
For 2 to 10 V (dc):
Maximum Modulation =
2 V (dc) – Boiler’s Maximum Input Signal
2 – 10 V (dc)
x 100%
Example:
A boiler’s input signal range is 2 to 9 V (dc). The 270 control has an output signal range of 2 to 10 V (dc).
To make the two signal ranges the same, the Maximum Modulation required is:
Maximum Modulation =
2 V – 9 V
2 V – 10 V
x 100% = 88%
BOILER MASS
The Boiler Mass setting allows the installer to adjust the control to the thermal mass of the type of heat sources used in the application. The modulation of the boiler can become unstable if the incorrect Boiler Mass setting is chosen. A key sign of the boiler modulation being unstable is the flame will continue to increase and then decrease in short periods of time. By choosing a lower Boiler Mass setting, the boiler response will become more stable.
Lo (1)
The Lo setting is selected if the boiler that is used has a low thermal mass. This means that the boiler has a very small water content and has very little metal in the heat exchanger. A boiler that has a low thermal mass comes up to temperature quite rapidly when fired. This is typical of many copper fin-tube boilers. The Lo Mass setting provides a fast response to the heating system.
Med (2)
The Med setting is selected if the boiler that is used has a medium thermal mass. This means that the boiler either has a large water content and a low metal content or a low water content and a high metal content. This is typical of many modern residential cast iron boilers or steel tube boilers. The Med Mass setting provides a moderate response to the heating system.
Hi (3)
The Hi setting is selected if the boiler that is used has a high thermal mass. This means that the boiler has both a large water content and a large metal content. A boiler that has a high thermal mass is relatively slow in coming up to temperature. This is typical of many commercial cast iron and steel tube boilers. The Hi Mass setting provides a slow response to the heating system.
DIFFERENTIAL
A modulating boiler must be operated with a differential while operating in low fire. The boiler differential is divided around the boiler target temperature. The boiler burner ignites at low fire when the supply water temperature is ½ of the Boiler Differential setting below the boiler target temperature. The boiler is shut off in low fire as the supply temperature reaches at least ½ of the differential above the boiler target temperature. With the control, either a fixed or an auto differential may be selected.
When the boiler is modulating above low fire, the differential does not apply. Instead, the modulation output signal is determined using Proportional, Integral and Derivative (PID) logic in order to satisfy the boiler target temperature.
Desired temperature
Fixed Differential
If the user desires to have a fixed differential, this is set using the Boiler Differential setting in the ADJUST menu.
160°F (71°C)
Boiler Off
Boiler On
165°F (74°C)
a
r
e
p
m
e
T
e
s
i
r
e
r
u
t
155°F (68°C)
T
e
m
p
e
r
a
t
u
Differential 10°F (6°C)
r
e
f
a
l
l
Time
Auto Differential
If the Auto Differential is selected, the control automatically determines the best differential as the load changes. This reduces potential short cycling during light load conditions.
Off
Differential
On
Increasing Load
Time
7 of 24 © 2010 D 270 - 08/10
Page 8
Section C: Pump Operation
PRIMARY PUMP OPERATION
The primary pump operates under the following conditions:
• A boiler demand is present and the control is not in Warm Weather Shut Down (WWSD).
• A DHW demand is present and DHW MODE is set to 3 or 4.
Primary
Primary Pump Purge
Pump
After a demand is removed, the control continues to operate the primary pump for a period of time. The maximum length of time that the primary pump continues to run is adjustable using the Primary Pump Purge setting. The primary pump continues to run until either the purging time has elapsed or the boiler supply temperature drops more than a differential below the Boiler Minimum setting.
BOILER PUMP OPERATION
The boiler pump turns on prior to the boiler firing (pre-purge) and continues to run after the boiler is turned off (post-purge). The boiler pump pre-purge time is determined by the Boiler Mass setting. As the Boiler Mass setting is increased, the boiler pump pre- purge time of the boiler also increases.
Boiler Pump Purge
The amount of time that the boiler pump continues to run after the boiler turns off is adjustable using the Boiler Pump Purge setting.
DHW
Pump
Boiler
Sensor
Boiler Pump
Section D: Boiler Reset Operation
BOILER DEMAND
A boiler demand is required in order for the control to provide heat to the heating system. A boiler demand is generated by applying a voltage between 24 and 230 V (ac) across the Boiler Demand terminals (1 and
2). Once voltage is applied, the Boiler Demand pointer is displayed in the LCD. If the control is not in Warm Weather Shut Down (WWSD), the control closes the primary pump contact. The control calculates a boiler target supply temperature based on the outdoor air temperature and the characterized heating curve settings. The control then fires the boiler, if
24 to 230 V (ac)
L
N
required, to maintain the target supply temperature.
OUTDOOR DESIGN TEMPERATURE
The outdoor design temperature is the outdoor air temperature that is the typical coldest temperature of the year where the building is located. This temperature is used when doing the heat loss calculations for the building. If a cold outdoor design temperature is selected, the boiler supply temperature rises gradually as the outdoor temperature drops. If a warm outdoor design temperature is selected, the boiler supply temperature rises rapidly as the outdoor temperature drops.
© 2010 D 270 - 08/10 8 of 24
Boil
Dem
2
1
Com
Dem
Page 9
-20
(-29)
210 (99)
190 (88)
170 (77)
150 (66)
130 (54)
110 (43)
90 (32)
70 (2
50°F (10°C)
CHARACTERIZED HEATING CURVE
The control varies the supply water temperature based on the outdoor air temperature. The control takes into account the type of terminal unit that the system is using. Since different types of terminal units transfer heat to a space using different proportions of radiation, natural convection and forced convection, the supply water temperature must be controlled differently. Once a terminal unit is selected, the control varies the supply water temperature according to the type of terminal unit. This improves the control of the air temperature in the building.
BOILER DESIGN TEMPERATURE
The boiler design supply temperature is the supply water temperature required to heat the building when the outdoor air temperature is as cold as the outdoor design temperature.
BOILER INDOOR DESIGN TEMPERATURE
The indoor design temperature is the room temperature that was used in the original heat loss calculations for the building. This setting establishes the beginning of the characterized heating curve.
Boiler Characterized
Boiler Characterized
Heating Curve
Heating Curve
BOIL MIN
BOIL INDR
80
(27)
60
(16)
Outdoor Air Temperature
OUT DSGN
WWSD OCC
WWSD UNOCC
ROOM OCC
ROOM UNOCC
40 (5)
BOIL DSGN
20
(-7)
BOIL MAX
0
(-18)
ROOM
The Room setting is the desired room temperature for the building and provides a parallel shift of the heating curve. The room temperature desired by the occupants is often different from the design indoor temperature. If the room temperature is not correct, adjusting the Room setting increases or decreases the amount of heat available to the building. A Room setting is available for both the occupied (day) and unoccupied (night) periods.
Supply Water Temperature
INDOOR SENSOR
With the indoor sensor connected, the control is able to sense the actual room temperature. Indoor temperature feedback fine­tunes the supply water temperature in the heating system to maintain room temperature. To adjust the room temperature, use the Room Occ or Room UnOcc setting in the ADJUST menu at the control.
The indoor sensor is connected to the Indr and Com terminals (17 and 18). In addition, power must be applied to the Boiler Demand terminals (1 and 2) as described in the Boiler Demand section.
If a multiple zone system is used with an indoor sensor, proper placement of the indoor sensor is essential. The indoor sensor should be located in an area which best represents the average air temperature of the zones.
TERMINAL UNITS
The control provides for a selection between six different terminal unit types: two types of radiant floor heat, fancoil, fin-tube convector, radiator and baseboard. When a terminal unit is selected, the control automatically loads the design supply temperature, maximum supply temperature, and minimum supply temperature. The factory defaults are listed below. These factory defaults can be changed to better match the installed system.
Terminal Unit High Mass
Radiant (1)
Low Mass
Radiant (2)
Fancoil
(3)
Fin-Tube
Convector (4)
Radiator
(5)
Baseboard
(6)
BOIL DSGN 120°F (49°C) 140°F (60°C) 190°F (88°C) 180°F (82°C) 160°F (71°C) 150°F (66°C)
BOIL MAX 140°F (60°C) 160°F (71°C) 210°F (99°C) 200°F (93°C) 180°F (82°C) 170°F (77°C)
BOIL MIN OFF OFF 140°F (60°C) 140°F (60°C) 140°F (60°C) 140°F (60°C)
High Mass Radiant (1)
This type of a hydronic radiant floor is embedded in either a thick concrete or gypsum pour. This heating system has a large thermal mass and is slow acting.
Low Mass Radiant (2)
This type of radiant heating system is either attached to the bottom of a wood sub-floor, suspended in the joist space, or sandwiched between the sub-floor and the surface. This type of radiant system has a relatively low thermal mass and responds faster than a high mass system.
9 of 24 © 2010 D 270 - 08/10
Page 10
Fancoil (3)
A fancoil terminal unit or Air Handling Unit (AHU) consists of a hydronic heating coil and either a fan or blower. Air is forced across the coil at a constant velocity by the fan or blower, and is then delivered into the building space.
Fin-Tube Convector (4)
A convector terminal unit is made up of a heating element with fins on it. This type of terminal unit relies on the natural convection of air across the heating element to deliver heated air into the space. The amount of natural convection to the space is dependent on the supply water temperature to the heating element and the room air temperature.
Radiator (5)
A radiator terminal unit has a large heated surface that is exposed to the room. A radiator provides heat to the room through radiant heat transfer and natural convection.
Baseboard (6)
A baseboard terminal unit is similar to a radiator, but has a low profile and is installed at the base of the wall. The proportion of heat transferred by radiation from a baseboard is greater than that from a fin-tube convector.
WARM WEATHER SHUT DOWN (OCC AND UNOCC)
The warm weather shut down (WWSD) disables the space heating system during warm outdoor weather. There is a separate WWSD for both the occupied and the unoccupied periods. When the outdoor air temperature rises above the WWSD setting, the control turns on the WWSD pointer in the display. When the control is in WWSD, the Boiler Demand pointer is displayed if there is a boiler demand. However, the control does not operate the heating system to satisfy this demand. The control does respond to a DHW demand and operates as described in section E.
Section E1: Domestic Hot Water Operation
DHW DEMAND
A DHW Demand is required in order for the control to provide heat to the DHW system. A DHW aquastat or setpoint control is used as a switch in the DHW demand circuit. Once the control detects a DHW demand, the DHW Demand pointer turns on in the LCD and the control operates the boiler to provide a sufficient boiler supply water temperature to the DHW tank. The control operates the pumps as described below.
The control registers a DHW Demand when a voltage between 24 and 230 V (ac) is applied across the DHW Demand terminals (2 and 3).
24 to 230 V (ac)
L
N
BOILER TARGET DURING DHW GENERATION
The DHW demand overrides the reset water temperature, except when the reset water temperature requirement is higher than that of the DHW tank. When the control receives a DHW demand through an aquastat, the boiler target temperature is at least as hot as the DHW heat exchange setting (DHW XCHG).
Com
Dem
3
2
DHW Dem
DHW MODE AND PRIORITY OPERATION
The control has four different modes of DHW operation, which depends on the piping arrangement of the DHW tank. It is often desirable to limit or even stop the flow of heat to the heating system when the DHW tank calls for heat. This allows for a faster recovery of the DHW tank.
© 2010 D 270 - 08/10 10 of 24
Page 11
DHW
Pump
DHW Mode 1 - DHW in Parallel no Priority
When a DHW Demand is present, the DHW Pmp / Vlv contact (terminals 7 and 8) closes. The primary pump contact does not turn on, but may operate based on a boiler demand.
DHW Mode 2 - DHW in Parallel with Priority
When a DHW Demand is present, the DHW Pmp / Vlv contact (terminals 7 and 8) closes and the primary pump contact is opened.
DHW Mode 3 - DHW in Primary / Secondary no Priority
When a DHW Demand is present, the DHW Pmp / Vlv contact (terminals 7 and 8) is closed and the primary pump contact is closed. This mode can be used if DHW tank is piped in direct return and a DHW valve is installed.
DHW Mode 4 - DHW in Primary / Secondary with Priority
When a DHW Demand is present, the DHW Pmp / Vlv contact (terminals 7 and 8) is closed and the primary pump contact is closed. Priority can only be obtained using external wiring. During a priority override, the DHW Pmp / Vlv contact is opened until the heating system has recovered before returning to DHW operation.
Th is mo d e can b e used if a DHW t ank is piped i n dir e c t retur n and a DHW valve is installed.
Primary
Pump
Primary
Pump
Disable
Using External
Wiring
Power from
DHW Pump / Vlv
Contact
Primary
Primary
L
DHW
Pump
Pump
DHW
Pump
Pump
DHW
Pump
Boiler Pump
Boiler Pump
Boiler Pump
Boiler Pump
L
COIL
N
N.C.
Power to External
Boiler Zones
N
N.O.
DHW Pump
DHW MODE 4 External Priority
Interlock
DHW PRIORITY OVERRIDE
The DHW Priority Override applies to DHW modes 2 and 4. To prevent the building from cooling off too much or the possibility of a potential freeze up during DHW priority, the control limits the amount of time for DHW priority. As the outdoor air temperature becomes colder, the length of time that the control provides DHW priority is reduced. Once the allowed time for priority has elapsed, the control overrides the DHW priority and resumes space heating.
To provide external DHW priority, the space heating zones must be interlocked with the DHW Pmp / Vlv contact. During demands, the DHW Pmp / Vlv contact must remove any power to all space heating zone valves or zone pumps.
11 of 24 © 2010 D 270 - 08/10
DHW Priority OverrideDHW Priority Override
Increasing Air Temperature
Outdoor Air Temperature
DHW priority demand time limit
Increasing Time
Page 12
CONDITIONAL DHW PRIORITY
The Conditional DHW Priority Override applies to DHW MODE 2 and Boiler Minimum is not set to OFF. If the boiler supply temperature is maintained at or above the required temperature during DHW generation, this indicates that the boiler has enough capacity for DHW and possibly heating as well. As long as the boiler supply temperature is maintained near its target, DHW and heating occurs simultaneously.
DHW POST PURGE
After the DHW Demand is removed, the control performs a purge on the boiler. The control shuts off the boiler and continues to operate either the DHW pump or the DHW valve and the system and boiler pump if applicable. This purges the residual heat from the boiler into the DHW tank. The control continues this purge for a maximum of four minutes or until the boiler supply water temperature drops 20°F (11°C) below the boiler target temperature during the DHW operation. The control also stops the purge if the boiler supply temperature drops below the current boiler target temperature.
DHW MIXING PURGE
After DHW operation, the boiler is extremely hot. At the same time, the heating zones may have cooled off considerably after being off for a period of time. To avoid thermally shocking the boiler after DHW in parallel with priority (DHW MODE 2), the control shuts off the boiler, but continues to operate the DHW pump while restarting the heating system. This allows some of the DHW return water to mix with the cool return water from the zones and temper the boiler return water.
Primary
Pump
DHW Pump
Boiler
Pump
DHW DURING UNOCCUPIED
When an external DHW Demand is present, the control can either continue operation of the DHW system as it would during the occupied period or the control can ignore a call for DHW as long as the control is in an unoccupied mode.
Section E2: DHW with Low Temperature Boilers
If DHW is to be incorporated into a low temperature system such as a radiant heating system, a mixing device is often installed to isolate the high DHW supply temperature from the lower system temperature. If a mixing device is not installed, high temperature water could be supplied to the low temperature system while trying to satisfy the DHW demand. This may result in damage to the low temperature heating system. The control is capable of providing DHW in such a system while maximizing the chance that the temperature in the heating system does not exceed its allowed Boiler Maximum setting.
Primary
Pump
To prevent high temperature water from being introduced into the heating system, the primary pump (Prim P1) must be turned off during a call for DHW. To do this, the control must be set to DHW MODE 2 or DHW MODE 4 and Boil MIN must be set to OFF.
DHW MODE 2 OPERATION
On a call for DHW, the control provides DHW priority by shutting off the primary pump (Prim P1) for a period of time. This time is based on the outdoor air temperature as described in the DHW Priority Override section. However, if the DHW Demand is not satisfied within the allotted time, the boiler shuts off and the heat of the boiler is purged into the DHW tank.
Once the boiler supply temperature is sufficiently reduced, the DHW Pmp / Vlv contact shuts off. The heating system is turned on for a period of time to prevent the building from cooling off. After a period of heating, and if the DHW Demand is still present, the control shuts off the heating system and provides heat to the DHW tank once again.
For correct operation, close attention must be paid to the mechanical layout of the system. When the control turns off the primary pump (Prim P1), flow to the heating system must stop. If flow is not stopped, the temperature in the heating system can exceed the maximum desired temperature and can result in damage to the heating system.
DHW
Pump
Boiler Pump
© 2010 D 270 - 08/10 12 of 24
Page 13
DHW MODE 4 OPERATION
In DHW MODE 4, the space heating zones must be prevented from coming on during DHW demands using external wiring. This can be done using an external relay to remove power from zone pumps or zone valves while a DHW Demand is present. This external relay is interlocked with the DHW Pmp / Vlv contact.
During a DHW Demand, the control closes the primary pump (Prim P1) contact and the DHW Pmp / Vlv contact. Once the DHW Demand is removed, or during a DHW priority override, the DHW Pmp / Vlv contact is opened, and the external wiring should allow the space heating zones to operate.
There is no mixing purge available in DHW MODE 4. After DHW priority, the boiler supply water temperature may exceed the design water temperature of the space heating system and can result in damage to the heating system.
Installation
CAUTION
Improper installation and operation of this control could result in damage to the equipment and possibly even personal injury. It is your responsibility to ensure that this control is safely installed according to all applicable codes and standards. This electronic control is not intended for uses as a primary limit control. Other controls that are intended and certified as safety limits must be placed into the control circuit. Do not open the control. Refer to qualified personnel for servicing. Opening voids warranty and could result in damage to the equipment and possibly even personal injury.
STEP ONE
Check the c ontents of this package. If any of the contents listed are missing or damaged, please contact your wholesaler or tekmar sales representative for assistance.
Type 270 includes: One Boiler Control 270, One Outdoor Sensor 070, One Universal Sensor 082, Data Brochures D 270, D 070, D 001, Application Brochure A 270.
Note: Carefully read the details of the Sequence of Operation to ensure that you have chosen the proper control for your application.
STEP TWO
Remove the control from its base by pressing down on the release clip in the wiring chamber and sliding the control away from it. The base is then mounted in accordance with the instructions in the Data Brochure D 001.
STEP THREE
All electrical wiring terminates in the control base wiring chamber. The base has standard common wiring hardware and conduit fittings. Before removing the knockouts, check the wiring diagram and select those sections of the chamber with common voltages. Do not allow the wiring to cross between sections, as the wires will interfere with safety dividers which should be installed at a later time.
Power must not be applied to any of the wires during the rough-in wiring stage.
All wires are to be stripped to a length of
Install the Outdoor Sensor 070 according to the installation instructions in the Data Brochure D 070 and run the wiring back to
the control.
Install the Boiler Supply Sensor 082 according to the installation instructions in the Data Brochure D 070 and run the wiring
back to the control.
GETTING READY
MOUNTING THE BASE
ROUGH-IN WIRING
3
in (9 mm) to ensure proper connection to the control.
8
7
in (22 mm) knockouts, which accept
8
If an Indoor Sensor 076 or 077 is used, install the indoor sensor according to the instructions in the Data Brochure D 074 and
run the wiring back to the control.
Run wire from other system components (pumps, boiler, etc.) to the control.
Run wires from the 115 V (ac) power to the control. Use a clean power source with a 15 A circuit to ensure proper operation. Multi-strand 16 AWG wire is recommended for all 115 V (ac) wiring due to its superior flexibility and ease of installation into the terminals.
13 of 24 © 2010 D 270 - 08/10
Page 14
STEP FOUR
ELECTRICAL CONNECTIONS TO THE CONTROL
General
The installer should test to confirm that no voltage is present at any of the wires. Push the control into the base and slide it down until it snaps firmly into place.
5
Powered Input Connections
115 V (ac) Power
Connect the 115 V (ac) power supply to the Power L and Power N terminals (5 and 6). This connection provides power to the microprocessor and display of the control. As well, this connection provides power to the Prim P1 terminal (4) from the Power L terminal (5).
Boiler Demand
To gener a t e a Boiler Demand, a voltage between 24 V (ac) and 230 V (ac) must be applied across the Boil Dem and Com Dem terminals (1 and 2).
115 V (ac)
L
N
24 to 230 V (ac)
L
N
L
Boil
Dem
Power
1
N
Com
Dem
6
2
DHW Demand
To gener a t e a DHW Demand, a voltage between 24 V (ac) and 230 V (ac) must be applied across the Com Dem and DHW Dem terminals (2 and 3).
Caution: The same power supply must be used to power both the DHW Demand and the Boiler Demand circuits since they both share the Com Dem terminal.
Output Connections
Primary Pump Contact (Prim P1)
The Prim P1 output terminal (4) is a powered output. When the relay in the control closes, 115 V (ac) is provided to the Prim P1 terminal (4) from the Power L terminal (5). To operate the primary pump, connect one side of the primary pump circuit to terminal 4 and the second side of the pump circuit to the neutral (Power N) side of the 115 V (ac) power supply.
DHW Pmp / Vlv Contact
The DHW Pmp / Vlv terminals (7 and 8) are an isolated output. There is no power available on these terminals from the control. These terminals are to be used as a switch to either make or break power to the DHW pump or the DHW valve. Since this is an isolated contact, it may switch a voltage between 24 V (ac) and 230 V (ac).
24 to 230 V (ac)
L
N
115 V (ac)
N
L
24 to 230 V (ac)
L
N
M
3
2
DHW
Com
Dem
Dem
6
5
4
Power
Prim
or
N
L
P1
8
7
DHW
Pmp/Vlv
Boiler Pmp P2 Contact
The Boiler Pmp P2 terminals (9 and 10) are isolated output in the control. There is no power available on these terminals from the control. These terminals are to be used as a switch to either make or break power to a boiler pump. Since this is an isolated contact, it may switch a voltage between 24 V (ac) and 230 V (ac).
© 2010 D 270 - 08/10 14 of 24
24 to 230 V (ac)
L
N
9
Boiler
Pmp P2
10
Page 15
Modulation Output
1
C
The Modulation Output terminals (11 and 12) provide a 0 to 10 V (dc) or a 2 to 10 V (dc) output to the boiler. If a 0 to 20 mA or a 4 to 20 mA output is required, cu t the jumper wire located next to the modulation output.
The modulating outputs replace any mechanical operator such as a T991. Observe polarity when connecting the control to the boiler.
SENSOR AND UNPOWERED INPUT CONNECTIONS
Do not apply power to these terminals as this will damage the control.
Outdoor Sensor
Connect the two wires from the Outdoor Sensor 070 to the Com and Out terminals (17 and
16). The outdoor sensor is used by the control to measure the outdoor air temperature.
Boiler Supply Sensor
Connect the two wires from the Boiler Supply Sensor 082 to the Com and Boil terminals (13 and 15). The boiler supply sensor is used by the control to measure the boiler supply water temperature.
11
Mod V(dc)
+--
Cut jumper
*
for 0-20 mA
or 4-20 mA
12
12
11
Mod V (dc)
+
+
V (dc)
Connection to Operate
Modulating Boiler
17
16
Com
Out
15
14
13
Boil
UnO
Com
Sw
UnOccupied Switch
If an external timer (tekmar Timer 032) or switch is used, connect the two wires from the external switch to the Com and UnO Sw terminals (13 and 14). When these two terminals are shorted together, the control registers an unoccupied (UNOCC) signal.
STEP FIVE
——————
TESTING THE WIRING
General
Each terminal block must be unplugged from its header on the control before power is applied for testing. To remove the terminal block, pull straight down from the control.
The following tests are to be performed using standard testing practices and procedures and should only be carried out by properly trained and experienced persons.
A good quality electrical test meter, capable of reading from at least 0 to 300 V (ac) and at least 0 to 2,000,000 Ω, is essential to properly test the wiring and sensors.
Test The Sensors
In order to test the sensors, the actual temperature at each sensor location must be measured. A good quality digital thermometer with a surface temperature probe is recommended for ease of use and accuracy. Where a digital thermometer is not available, a spare sensor can be strapped alongside the one to be tested and the readings compared. Test the sensors according to the instructions in the Data Brochure D 070.
16
Out
17
Com
14
13
UnO
Com
Sw
Timer Switch
15 of 24 © 2010 D 270 - 08/10
Page 16
Test The Power Supply
Make sure exposed wires and bare terminals are not in contact with other wires or grounded surfaces. Turn on the power and measure the voltage between the Power L and Power N terminals (5 and 6) using an AC voltmeter, the reading should be between 103.5 and
126.5 V (ac).
Test the Powered Inputs
Boiler Demand
If a boiler demand is used, measure the voltage between the Boil Demand terminals (1 and 2). When the boiler demand device calls for heat, between 20 and 260 V (ac) shoul d be measur e d at th e terminals. When the boiler demand device is off, less than 5 V (ac) should be measured.
V
5
Power
L
Dem
Boil
2
103.5 to 126.5 V (ac)
20 to 260 V (ac)
6
N
1
Com
Dem
DHW Demand
If a DHW demand is used, measure the voltage between the DHW Dem and the Com Dem terminals (2 and 3). When the DHW
Com
Dem
3
2
DHW Dem
20 to 260 V (ac)
demand device calls for heat, between 20 and 260 V (ac) should b e measured at the terminals. When the DHW demand device is off, less than 5 V (ac) should be measured.
TEST THE OUTPUTS
Primary Pump (Prim P1)
If a primary pump is connected to the Prim P1 terminal (4), make sure that power to the terminal block is off and install a jumper between the Power L and Prim P1 terminals (5 and 4). When power is applied to the Power L and Power N terminals (5 and 6), the primary pump should start. If the pump does not turn on, check the wiring between the terminal block and pump and refer to any installation or troubleshooting information supplied with the pump. If the pump operates properly, disconnect the power and remove the jumper.
Boiler Pmp P2
If a b o i ler pump is connected t o t he Boiler Pmp P2 terminals (9 and 10), make sure that power to the terminal block is off and install a jumper between the terminals. When power is applied to circuit, the boiler pump should start. If the pump does not turn on, check the wiring between the terminal block and pump and refer to any installation or troubleshooting information supplied with the pump. If the pump oper­ates properly, disconnect the power and remove the jumper.
24 to 230 V (ac)
L
N
9
Boiler
Pmp P2
10
DHW Pump Or Valve (DHW Pmp / Vlv)
If a DHW pump or DHW valve is connected to the DHW Pmp / Vlv terminals (7 and 8), make sure the power to the pump or valve circuit is off and install a jumper between those terminals. When the DHW circuit is powered up, the DHW pump should turn on or the DHW valve should open completely. If the DHW pump or valve fails to operate, check the wiring between the terminals and the pump or valve and refer to any installation or troubleshooting information supplied with these devices. If the DHW pump or valve operates correctly, disconnect the power and remove the jumper.
© 2010 D 270 - 08/10 16 of 24
24 to 230 V (ac)
L
N
7
DHW
Pmp/Vlv
8
Page 17
CONNECTING THE CONTROL
Test
Make sure all power to the devices and terminal blocks is off, and remove any remaining jumpers from the terminals.
Reconnect the terminal blocks to the control by carefully aligning them with their respective headers on the control, and then pushing the terminal blocks into the headers. The terminal blocks should snap firmly into place.
Install the supplied safety dividers between the unpowered sensor inputs and the powered or 115 V (ac) wiring chambers.
Apply power to the control. The operation of the control on power up is described in the Sequence of Operation section of the brochure.
TEST THE MODULATING OUTPUT
If a modulating device is used, connect an ammeter to the modulating output Mod V (dc) terminals (11 and 12) and observe the current reading during operation. For example, when using a 0 to 10 V (dc) output, the initial percentage output is zero and the meter should read 0 V (dc). As the Boiler Modulation in the VIEW menu increases, the meter reading should increase until the Boiler Modulation reaches 100% at which point the meter should read 10 V (dc). When the 0 to 10 V (dc) modulation decreases, the meter should start at 10 V (dc) and eventually reach 0 V (dc) when the display shows 0% Boiler Modulation.
V
Prim
P1
4
L
Power
Pmp/Vlv
N
11
ModV(dc)
+
DHW
12
-
8
7
6
5
Cleaning the Control
The control’s exterior can be cleaned using a damp cloth. Moisten the cloth with water and wring out prior to wiping control. Do not use solvents or cleaning solutions.
DIP Switch Settings
GENERAL
The DIP switch settings on the control are very important and should be set to the appropriate settings prior to making any adjustments to the control through the User Interface. The DIP switch settings change the items that are available to be viewed and / or adjusted in the User Interface.
If a DIP switch is c hanged while the cont rol is powered up, the control respond s to the change in setting by returning the display to the VIEW menu.
Advanced / Installer
The Advanced / Installer DIP switch selects the access level of the control. In the Installer access level, a limited number of items may be viewed and / or adjusted. In the Advanced access level, all items may be viewed and / or adjusted.
DIP Switches
Boiler Demand
DHW Demand
Modulation
DHW Priority Override
Menu Item
Boiler Control 270
One Modulating Boiler & DHW
Advanced Off
Installer Exercise
Advanced Off
Installer Exercise
Test
ting
s
te
t
o
n
o
ting
s
te
d
e
r
d
e
s
u
a
p ting
s
e
t
d
e
r
t
a
e
h
m
u
im
x
a
m
r
o
F
t
s
e
T
d
l
o
h
&
s
s
e
r
p
.
s
d
n
o
c
e
s
3
r
o
f
n
o
tt
u
b
:
B
s
s
la
C
ts
e
e
M
S
E
C
I
n
ia
d
a
n
a
C
Made in Canada by tekmar Control Systems Ltd.
Power 115 V ±10% 50/60 Hz 600 VA Relays 230 V (ac) 5 A 1/3 hp, pilot duty 240 VA Demands 20 to 260 V (ac) 2 VA
Signal wiring must be rated at least 300 V.
5
1
t
r
a
P
C
C
F
e d o C e t a D
Off / Exercise
The Off / Exercise DIP switch selects whether or not the control is to exercise the primary
Advanced Off
pump and boiler pumps. If the DIP switch is set to Exercise, the pumps are operated for 10 seconds after every three days of inactivity.
Installer Exercise
17 of 24 © 2010 D 270 - 08/10
Page 18
View Menu (1 of 1)
Display
B3
Section
Installer
Description
Advanced
Outdoor Current outdoor air temperature as measured by the outdoor sensor.
Room Current room air temperature as measured by the indoor sensor.
This item is only available when an indoor sensor is connected to the control.
Boiler Supply Current boiler supply water temperature as measured by the boiler supply sensor.
Boiler Target Boiler target temperature is the temperature the control is currently trying to maintain at the boiler supply sensor +/- ½ of the differential.
Boiler Modulation Current percent modulation of the boiler’s burner.
Range
-76 to 149°F (-60 to 65°C)
23 to 113°F (-5 to 45°C)
-22 to 266°F (-30 to 130°C)
– – –, 35 to 230°F (– – –, 2 to 110°C)
0 to 100%
Boiler Hours The total running time of the boiler since this item was last cleared. To clear this item, press the and button simultaneously while viewing this item.
0 to 1999 hr
© 2010 D 270 - 08/10 18 of 24
Page 19
Adjust Menu (1 of 2)
Display
D1
D1
D1
D1
Section
Installer
Description
Advanced
Room Occupied The desired room air temperature during the occupied period.
Room Unoccupied The desired room air temperature during the unoccupied period.
Outdoor Design The design outdoor air temperature used in the heat loss calculations for the heating system.
Term i n al Unit The type of terminal units that are being used in the heating system.
Boiler Indoor The design indoor air temperature used in the heat loss calculation for the heating system.
Range
35 to 100°F (2 to 38°C) Default = 70°F (21°C)
35 to 100°F (2 to 38°C, OFF) Default = 65°F (18°C)
-60 to 45°F (-51 to 7°C) Default = 10°F (-12°C)
1 (HRF1), 2 (HRF2), 3 (COIL), 4 (CONV), 5 (RAD), 6 (BASE)
Default = 4
35 to 100°F (2 to 38°C) Default = 70°F (21°C)
Actual
Setting
D1
B1
B1
B1
B2 B3
B2 B3
Boiler Design The design supply water temperature used
in the heat loss calculations for the heating system.
Boiler Minimum The minimum allowed boiler target temperature. Check the boiler manufacturer’s manual for a recommended setting.
Boiler Maximum The maximum allowed boiler target temperature.
Fire Delay The time delay the control can expect between the time that the relay contact closes to fire the boiler and when the burner actually fires.
Boiler Mass The thermal mass characteristics of the boiler that is being used.
Boiler Differential The temperature differential that the control is to use when it is operating the boiler.
70 to 220°F (21 to 104°C) Default = 180°F (82°C)
OFF, 80 to 180°F (OFF, 27 to 82°C) Default = 140°F (60°C)
120 to 225°F, OFF (49 to 107°C, OFF) Default = 200°F (93°C)
0:00 to 4:00 minutes (1 sec increment)
Default = 0:10 minutes
1 (Lo) 2 (Med) 3 (Hi)
Default = 2 (Med)
Au, 2 to 42°F (Au, 1 to 23°C) Default = Au
Motor Speed The amount of time required for the modulat-
B3
19 of 24 © 2010 D 270 - 08/10
ing actuating motor to fully open the gas valve or operate the fan speed from a stopped position to full speed.
10 to 230 seconds Default = 30
Page 20
Adjust Menu (2 of 2)
Display
B3
B3
B3
E1 E2
Installer
Section
Description
Advanced
Boiler Modulation Selects either a 2 to 10 V (dc) or a 0 to 10 V (dc) output signal.
Minimum Modulation The minimum percent modulation of the burner.
Maximum Modulation The maximum percent modulation of the burner.
DHW Mode Selects the DHW mode of operation.
DHW Exchange Occupied The minimum boiler supply
temperature to the DHW heat exchanger during the Occupied period.
Range
2:10, 0:10 Default = 0:10
0 to 50% Default = 0%
50 to 100% Default = 100%
1 (parallel, no priority), 2 (parallel, priority), 3 (pri-sec, no priority),
4 (pri-sec, priority)
Default = 1
OFF, 100 to 220°F (OFF, 38 to 104°C) Default = 180°F (82°C)
Actual
Setting
C1
C1
DHW Exchange Unoccupied Selects whether or not a
D HW de ma n d w il l b e re s po n de d to du ri n g t he Un O cc u pi ed period.
WWSD Occupied The system’s warm weather shut down temperature during the Occupied period.
WWSD Unoccupied The system’s warm weather shut down temperature during the Unoccupied period.
Primary Pump Purge The maximum length of time that the primary pump will continue to operate after the boiler demand has been removed.
Boiler Pump Purge The length of time that the boiler pump will continue to run after the boiler demand is removed.
The units of measure that all of the temperatures are to be displayed in by the control.
OFF, On Default = OFF
35 to 100°F, OFF (2 to 38°C, OFF) Default = 70°F (21°C)
35 to 100°F, OFF (2 to 38°C, OFF) Default = 60°F (16°C)
OFF, 0:10 to 19:55 min. (5 second increments)
Default = 0:20 min
OFF, 0:10 to 19:55 min. (5 second increments)
Default = 0:20 min
°F,°C Default = °F
© 2010 D 270 - 08/10 20 of 24
Page 21
Testing the Control
The control has a built-in test routine that is used to test the main control functions. The control continually monitors the sensors and displays an error message whenever a fault is found. See the following pages for a list of the control’s error messages and possible causes. When the Test button is pressed, the Test light is turned on. The individual outputs and relays are tested in the following test sequence.
TEST SEQUENCE
Each step in the test sequence lasts 10 seconds.
During the test routine, if a demand from the system is present, the test sequence may be paused by pressing the Test button. If the Test button is not pressed again for 5 minutes while the test sequence is paused, the control exits the entire test routine. If the test sequence is paused, the Te st button can be pressed again to advance to the next step. This can also be used to rapidly advance through the test sequence. To reach the desired step, repeatedly press and release the Tes t button until the appropriate device and segment in the display turn on.
Step 1 – The primary pump contact is closed.
Step 2 – The boiler pump contact is closed.
Step 3 – The Boiler contact is closed and the modulation output is set to the Minimum Modulation setting.
Step 4 –
Step 5 –
Step 6 – The Boiler and boiler pump contacts are opened. – If DHW MODE is set to 1 or 2, the DHW Pmp / Vlv contact is closed and the primary pump contact is opened. – If DHW MODE is set to 3 or 4, the DHW Pmp / Vlv contact is closed and the primary pump contact remains closed.
Step 7 – After the test sequence is completed, the control resumes its normal operation.
If there is a demand present, the modulation output increases to Maximum Modulation according to the Motor Speed setting.
If there is a demand present, the modulation output decreases to Minimum Modulation according to the Motor Speed setting.
21 of 24 © 2010 D 270 - 08/10
Page 22
MAX HEAT
The control has a function called Max Heat. In this mode, the control turns on and operates the system up to the maximum set temperatures as long as there is a demand for heat. The control continues to operate in this mode for up to 24 hours or until the Item, Menu or Tes t button is pressed. This mode may be used for running all circulators during system start-up in order to purge air from the piping. To enable the Max Heat feature, use the following procedure.
1) Press and hold the Test button for more than 3 seconds. At this point, the control flashes the MAX segment and displays the word OFF
2) Using the
or buttons, select the word On. After 3 seconds, the control turns on all
outputs. However, the max heat mode is still limited by the BOIL MAX setting.
3) To cancel the Max Heat mode, press the Item, Menu, or Test button.
4) Once the Max Heat mode has either ended or is cancelled, the control resumes normal operation.
Menu Item
Menu Item
© 2010 D 270 - 08/10 22 of 24
Page 23
Error Messages (1 of 1)
E01
The control was unable to read a piece of information stored in its memory. Because of this, the control was required to reload the factory settings into all of the items in the ADJUST menu. The control will stop operation until all of the items in the ADJUST menu of the control have been checked by the user or installer. Note: The Advanced / Installer DIP switch must be set to Advanced in order to clear the error.
Boil Supply Sensor Short
The control is no longer able to read the boiler supply sensor due to a short circuit. The control will not operate the boiler until the sensor is repaired. Locate and repair the problem as described in the Data Brochure D 070. To clear the error message from the control after the sensor has been repaired, press either the Menu or Item button.
Boil Supply Sensor Open
The control is no longer able to read the boiler supply sensor due to an open circuit. The control will not operate the boiler until the sensor is repaired. Locate and repair the problem as described in the Data Brochure D 070. To clear the error message from the control after the sensor has been repaired, press either the Menu or Item button.
Outdoor Sensor Short
The control is no longer able to read the outdoor sensor due to a short circuit. In this case the control assumes an outdoor temperature of 32°F (0°C) and continues operation. Locate and repair the problem as described in the Data Brochure D 070. To clear the error message from the control after the sensor has been repaired, press either the Menu or Item button.
Outdoor Sensor Open
The control is no longer able to read the outdoor sensor due to an open circuit. In this case the control assumes an outdoor temperature of 32°F (0°C) and continues operation. Locate and repair the problem as described in the Data Brochure D 070. To clear the error message from the control after the sensor has been repaired, press either the Menu or Item button.
Indoor Sensor Short
The control is no longer able to read the indoor sensor due to a short circuit. The control will operate the system as if an indoor sensor where not installed until the indoor sensor is repaired. Locate and repair the problem as described in the Data Brochure D 074. To clear the error message from the control after the sensor has been repaired, press either the Menu or Item button.
Indoor Sensor Open
The control is n o lon ger a ble to read t he indoor sens or du e to an o p en circui t. T he control wil l operate the system as if an indoor sensor where not installed until the indoor sensor is repaired. Locate and repair the problem as described in the Data Brochure D 074. To clear the error message from the control after the sensor has been repaired, press either the Menu or Item button.
23 of 24 © 2010 D 270 - 08/10
Page 24
Techn ical Dat a
Boiler Control 270 One Modulating Boiler & DHW
Literature — D 270, A 270, D 001, D 070. Control — Microprocessor PID control; This is not a safety (limit) control. Packaged weight — 3.3 lb. (1500 g), Enclosure A , blue modified PVC plastic Dimensions — 6-5/8” H x 7-9/16” W x 2-13/16” D (170 x 193 x 72 mm) Approvals — CSA C US, meets ICES & FCC regulations for EMI/RFI. Ambi ent conditions — Indoor use only, 32 to 104°F (0 to 40°C), < 90% RH non-condensing. Power supply — 115 V (ac) ±10% 50/60 Hz 600 VA Relay capacit y — 230 V (ac) 5 A 1/3 hp pilot duty 240 VA Modulation Output — 0 – 10 V (dc) Demands — 20 to 260 V (ac) 2 VA
Boiler Demand
DHW Demand
Modulation
DHW Priority Override
Sensors included — NTC thermistor, 10 k @ 77°F (25°C ±0.2°C) ß=3892 Outdoor Sensor 070 and Universal Sensor 082
Optional devices — Indoor Sensor 076/077
Menu Item
Boiler Control 270
One Modulating Boiler & DHW
1
2
3
4 5NL6
7 8 9 10 11
Boil
Com
DHW
Dem
Dem
Dem
DHW
Prim
Power
P1
Pmp/Vlv
Pmp P2
Boiler
The installer must ensure that this control and its wiring are isolated and/or shielded from strong sources of electromagnetic noise. Conversely, this Class B digital apparatus complies with Part 15 of the FCC Rules and meets all requirements of the Canadian Interference-Causing Equipment Regulations. However, if this control does cause harmful interference to radio or television reception, which is determined by turning the control off and on, the user is encouraged to try to correct the interference by re-orientating or relocating the receiving antenna, relocating the receiver with respect to this control, and/or connecting the control to a different circuit from that to which the receiver is connected.
Cet appareil numérique de la classe B respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada.
Caution The nonmetallic enclosure does not provide grounding between conduit connec tions. Use grounding type bushings and jumper wires.
Attention Un boîtier nonmétallique n´assure pas la continuité électrique des conduits. Utiliser des manchons ou des fils de ac cord spécialement conçus pour la mise
á la terre.
Advanced Off
Installer Exercise
Tes t
o
te
d
re
te
d
re
or m
F
s
s
pre
to
ut
b
Made in Canada by tekmar Control Systems Ltd. tektra 969-03
Power 115 V ±10% 50/60 Hz 600 VA Relays 230 V (ac) 5 A 1/3 hp, pilot duty 240 VA Demands 20 to 260 V (ac) 2 VA
Signal wiring must be rated at least 300 V.
Do not apply power
12 13 14 15 16 17 18
Mod V(dc) Out Com Indr
UnO Boil
Com
+--
Sw
g
testin
t
o
n
ting
s
d
e
s
u
a
p
ting
s
at
e
h
um
im
x
a
t
s
e
hold T
&
ds.
n
o
ec
for 3 s
n
:
B
s
las
ts C
ee
M
S
E
IC
n
ia
d
a
an
C
5
rt 1
a
P
C
C
F
e d o
C e
t a D
H2039A
Limited Warranty and Product Return Procedure
Limited Warranty The liability of tekmar under this warranty is limited. The
Purchaser, by taking receipt of any tekmar product (“Product ”), acknowl­edges the terms of the Limited Warranty in effect at the time of such Product sale and acknowledges that it has read and understands same.
The tekmar Limited Warranty to the Purchaser on the Products sold hereunder is a manufacturer’s pass-through warranty which the Purchaser is authorized to pass through to its customers. Under the Limited Warranty, each tekmar Product is warranted against defects in workmanship and materials if the Prod­uct is installed and used in compliance with tekmar’s instructions, ordinary wear and tear excepted. The pass-through warranty period is for a period of twenty-four (24) months from the production date if the Product is not installed during that period, or twelve (12) months from the documented date of installa­tion if installed within twenty-four (24) months from the production date.
The liability of tekmar under the Limited Warranty shall be limited to, at tekmar’s sole discretion: the cost of parts and labor provided by tekmar to repair defects in materials and/or workmanship of the defective product; or to the exchange of the defective product for a warranty replacement product; or to the granting of credit limited to the original c ost of the defective product, and such repair, exchange or credit shall be the sole remedy available from tekmar, and, without limiting the foregoing in any way, tekmar is not responsible, in contract, tort or strict prod­uct liabilit y, for any other losses, costs, expenses, inconveniences, or damages, whether direct, indirect, special, secondar y, incidental or consequential, arising fro m ownership or u se of t he produc t, or f ro m defe cts i n workmanship o r materials, including any liability for fundamental breach of contract.
The pass-through Limited Warranty applies only to those defective Pro ducts returned to tekmar during the warrant y period. This Limited Warranty does not cover the cost of the parts or labor to remove or transport the defective Product, or to reinstall the repaired or replacement Product, all such costs and expenses being subject to Purchaser’s agreement and warranty with its customers.
Any representations or warranties about the Products made by Purchaser to its customers which are different from or in excess of the tekmar Limited Warranty are
the Purchaser’s sole responsibility and obligation. Purchaser shall indemnify and hold tekmar harmless from and against any and all claims, liabilities and damages of any kind or nature which arise out of or are related to any such representations or warranties by Purchaser to its customers.
The pass-through Limited Warranty does not ap ply if the returned Product has been damaged by negligence by persons other than tekmar, accident, fire, Act of God, abuse or misuse; or has been damaged by modifications, alterations or attachments made subsequent to purchase which have not been authorized by tekmar; or if the Product was not installed in compliance with tekmar’s instructions and/or the local codes and ordinanc es; or if due to defec tive installation of the
Product; or if the Product was not used in compliance with tekmar’s instructions.
THIS WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, WHICH THE GOVERNING LAW ALLOWS PARTIES TO CONTRACTU­ALLY EXCLUDE, INCLUDING, WITHOUT LIMITATION, IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, DURA­BILITY OR DESCRIPTION OF THE PRODUCT, ITS NON-INFRINGEMENT OF ANY RELEVANT PATENTS OR TRADEMARKS, AND ITS COMPLIANCE WITH OR NON-VIOLATION OF ANY APPLICABLE ENVIRONMENTAL, HEALTH OR SAFETY LEGISL ATION; THE TERM OF ANY OTHER WARRANTY NOT HEREBY CONTRACTUALLY EXCLUDED IS LIMITED SUCH THAT IT SHALL NOT EXTEND BEYOND TWENTY-FOUR (24) MONTHS FROM THE PRODUCTION DATE, TO THE EXTENT THAT SUCH LIMITATION IS ALLOWED BY THE GOVERNING LAW.
Product Warranty Return Procedure All Products that are believed to have defects in workmanship or materials must be returned, together with a written description of the defect, to the tekmar Representative assigned to the territor y in which such Product is located. If tekmar receives an inquiry from someone other than a tekmar Representative, including an inquiry from Purchaser (if not a tekmar Representative) or Purchaser’s customers, regarding a potential warranty claim, tekmar’s sole obligation shall be to provide the address and other contact informa­tion regarding the appropriate Representative.
tekmar Control Systems Ltd., Canada
Control Systems
tekmar Control Systems, Inc., U.S.A.
Head Office: 5100 Silver Star Road Vernon, B.C. Canada V1B 3K4 (250) 545 -7749 Fax. (250) 545-0650 Web Site: www.tekmarcontrols.com
Product design, software and literature are Copyright © 2010 by:
24 of 24
tekmar Control Systems Ltd. and tekmar Control Systems, Inc.
All specifications are subject to change without notice.
Printed in Canada. D 270 - 08/10.
Loading...