- Data Brochure
R
D 269
One Stage Steam Control 269
The tekmar One Stage Steam Control 269 is a microprocessor-based control which regulates the
firing time of a steam boiler based on user settings, outdoor air temperature, condensate return
temperature, and optionally, the indoor air temperature(s). The steam boiler can be operated in
the outdoor reset mode, or in Manual Override mode based on dial settings. The control has builtin diagnostics for sensor checking with a Warning output for error reporting. Other control
operation features include Auxiliary relay output, Steam Established and Lockout Differential
temperatures, and Early Start with setback limit when using the Unoccupied input.
70°F
70°F
(21°C)
(21°C)
40
40
100
(4)
(4)
(38)
Occupied
Unoccupied
One Stage Steam Control 259
with Early Start
Steam
Power
established
Heating
WWSD
cycle
Early Start
UnOcc.
Auxiliary
Warning
100
(38)
Boiler
R
R
LR 58233
E150539
Outdoor Reset Strategy . . pg. 2
Sequence of Operation . . . pg. 3
Installation . . . . . . . . . . . . . pg. 6
Settings . . . . . . . . . . . . . . . pg. 8
Early Start
into or
out of UnOcc.
System is in
Warm Weather
Shut Down
System is in
Unoccupied
mode
Sensor Fault
warning
Occupied
temperature
setting
Unoccupied
temperature
setting
Boiler is on
120Vac power
supply is on
70°F
(21°C)
40
100
(4)
(38)
Occupied
One Stage Steam Control 269
with Early Start
Use Nº 20 AWG or larger copper conductors rated for at least 75°C and 300V.
Heating Cycle
is in progress
70°F
(21°C)
40
100
(4)
(38)
Unoccupied
1234 5
Power
Warn.
NL
Aux.
Condensate
temperature is
established
6
Power
WWSD
UnOcc.
Warning
LR 58223
78
Boiler
Auxiliary relay
output is on
Steam
Established
Heating
Cycle
Early Start
Auxiliary
Boiler
Listed
R
5T62
R
E150539
Testing . . . . . . . . . . pg. 9
Error Messages . . . pg. 11
Technical Data . . . . pg. 12
Limited Warranty . . pg. 12
Operating Mode
selector switches
Indoor Sensor S1
Indoor Sensor S2
Early Start
45%
0
Auto
100
Man. Override
Test
Manufactured
in Canada by
Power: 120V 50/60Hz 3VA
Relays: 120Vac 10A 1/4 hp 240VA, 2A pilot duty
Enclosed Energy Management Equipment
9
10K
S1
Condensate Return Sensor
123 4
Off
0 °F
10
180 °F
Steam
11 12
UnO
Sw
1
40
Cycle Length
5
Off2550
Min. On Time (%)
Lockout Diff'l (°F)
13 14 15
Com
10K
Sen
S2
2093
1234567
Cnd Out
Sen
-40
Design Out
130 230
Established
Do not apply power here
10
Com
Sen
50 min
R
06/00
Manual
override setting
System design
outdoor
temperature
setting
Heating cycle
length setting
Steam
established
100
(condensate
temperature)
setting
Minimum on
time/lockout
differential
Date
S/N
setting
Test button and
LED to test main
control functions
H1099
Sen
Terminal Plugs:
Power and out-
put connections
120 Vac
power supply
Warning Relay
Output:
Output:
Auxiliary Relay
Output:
Turn on boiler
Input: Indoor
Sensor 074
Optional
Input:
Unoccupied
signal
Optional
Input: Outdoor
Sensor 070. Included
Input: Condensate
Return Sensor 071.
Included
Input: Indoor
Sensor 074
Copyright © D 269 - 06/001 of 12
Optional
Outdoor Reset Strategy
Boiler
off
15 minutes
off time
15 minutes
off
on time
Boiler Operation
Boiler
on
30 minute cycle
Figure 1. 50% on time with a 30 minute heating cycle
Boiler on
off
Boiler Operation
30 minutes
on time
60 minute cycle
Figure 2. 50% on time with a 60 minute heating cycle
Boiler is turned off
WWSD
Point
90
70
(32)
(21)
Boiler is cycled on/off
Design
Outdoor
Temperature
50
(10)
Outdoor air temperature
30
(-1)10(-12)
-10°F
(-23)°C
Figure 3. Outdoor Reset of boiler % on time
on
15 minutes
on time
30 minute cycle 30 minute cycle 30 minute cycle
off
15 minutes
off time
on
15 minutes
on time
off
15 minutes
off time
on
15 minutes
on time
Boiler off
30 minutes
off time
on
30 minutes
on time
off
30 minutes
60 minute cycle
100%
90%
80%
70%
60%
50%
40%
30%
Boiler is turned on 100%
20%
10%
0%
on time
-30°F
(-34)°C
Most residential and small commercial steam systems can only produce
heat at a fixed rate and are either on (100% output), or off (0% output). When
100% output is not required (warmer weather), the boiler must be cycled on
and off in order to prevent overheating. Figures 1 and 2 illustrate the
operation of two heating systems with different heating cycle times.
Cycle times are selected based on the operating characteristics of each
individual heating system. Figure 1 shows a system where a 30 minute cycle
is required, and Figure 2 shows a system where a 60 minute cycle is required.
In both examples the heating plant output is exactly the same at 50%.
As the outdoor temperature changes, the % on time of the boiler should
be changed to match the changing heat losses of the building. Figure 3
illustrates how Outdoor Reset of a steam boiler changes the % on time from
Percentage of boiler on time per cycle
0% at the Warm Weather Shut Down point, to 100% at design outdoor
conditions (coldest day of the year). Applying this chart to the system
represented in Figure 1, we see that the outdoor temperature would be at
30°F with the 50% on time that is illustrated, and if the outdoor temperature
warmed up to 50°F, the system would operate with a 25% on time as
illustrated in Figure 4. Using outdoor temperature to reset the % on time in
this manner can help minimize the overheating and wide temperature swings
found in many systems that use only room temperature control.
off time
off
15 minutes
off time
on
on
Boiler
off
45 minutes off time
60 minute cycle
on
15 minutes
on time
off
45 minutes off time
60 minute cycle
on
15 minutes
off
on time
Boiler Operation
Boiler
on
Figure 4. 25% on time with a 60 minute cycle time
Before adding this control to a steam system, it is very important that the installer examine the
complete
system and how
it works. In order to properly install and setup this control, the installer must know: the optimum cycle length and minimum on
time of the system, the outdoor temperature at which 100% boiler on time will be required, and the best locations to install
sensors. In addition to examining the boiler operation,
all other
system components such as steam traps, air vents, radiators,
piping, etc. should be examined for correct operation to ensure that the system is working at its peak efficiency. If there are
existing faults that degrade the operation of the system, it is quite likely that the addition of this control could allow those faults
to have an even greater effect, making it important to correct such faults or at least point them out to the end user.
Copyright © D 269 - 06/00 2 of 12
Sequence of Operation
Start-up
When the One Stage Steam Control 269 is powered-up, the "Power" light and all of the red
lights will come on. After 5 seconds the red lights will go out and the control will enter the
operating mode. If there is a sensor error detected, the control will display an error message
(see "Error Messages", page 11).
Power
WWSD
UnOcc.
Warning
Manual Override function
If the "Man. Override" dial is turned up from the "Auto" position, the WWSD, Heating Cycle, Early
Start and UnOcc. lights will cycle on and off in a clockwise, circular sequence and the control
will continually operate the system at the % on time setting of the "Man. Override" dial position.
Power
WWSD
UnOcc.
In this mode, the only two dial adjustments that will have any influence on the control's operation
will be the "Man. Override" and the "Cycle Length" dials, and the control will cycle the boiler on
Warning
and off as illustrated in Figures 1, 2 and 4 on page 2. Outdoor or room temperatures will have
no effect on the operation of the control when it is in "Man. Override" mode.
Auto (reset) function
If the "Man. Override" dial is set to the "Auto" (Outdoor Reset) operating mode, the control uses the Outdoor Sensor 070 to
continually monitor the outdoor temperature. As options, a Condensate Return Sensor 071 can continually monitor the temperature
of the condensate return line and one or two Indoor Sensors 074 can continually monitor the indoor air temperature. DIP switches
for Condensate Return Sensor and Indoor sensors must be switched on when these sensors are connected.
An Error Message
will be displayed if these switches are in the on position without sensors installed.
While monitoring all of these temperatures, the control recognizes the following inputs and will respond as described. During
operation, the lights of the control will indicate operational status as illustrated.
Outdoor Sensor 070 only
When an Outdoor Sensor 070 is connected to the control and the
"Design Out" dial set to the correct setting, the control will cycle
the boiler on and off based on the outdoor temperature and the
settings on the "Cycle Length" and "Min. On Time (%)" dials as
shown in Figure 5.
The "Min. on time (%)" dial must be set to at
least the minimum time required for the boiler to produce steam
and add heat to the building.
As soon as the outdoor temperature
drops below the setting of the "Occupied" dial (WWSD point), the
"WWSD" light will go out and the "Heating Cycle" and "Auxiliary"
lights will come on. The "Boiler" light will come on and the
123 4
Off
Power
WWSD
UnOcc.
Warning
Indoor Sensor S1
Indoor Sensor S2
Condensate Return Sensor
Steam
established
Heating
cycle
Early Start
Auxiliary
Boiler
123 4
Off
Power
WWSD
UnOcc.
Warning
Indoor Sensor S1
Indoor Sensor S2
Condensate Return Sensor
Steam
established
Heating
cycle
Early Start
Auxiliary
Boiler
Condensate return sensor,
+ Indoor sensors S1 & S2
DIP switches = off
boiler will fire for at least the time set on the "Min. On Time (%)" dial, and then shut off for the remainder of the time set on the "Cycle
length" dial. This cycle will be repeated until the outdoor temperature becomes warmer than the "Occupied" dial setting, putting the
control back into WWSD. Adjusting the "Occupied" dial shifts the WWSD point and heating curve up or down as shown in Figure
6, and the indoor air temperature will be affected accordingly. The "UnOccupied" dial works the same way as the "Occupied" dial
when the control has been put into the UnOccupied mode, except the design outdoor temperature is also shifted down.
Indoor Sensor 074 function
When Indoor Sensor 074s are connected to this control, the control will still operate the boilers based on
outdoor temperature, but will also use one 074 sensor input, or the lower reading of two 074s to prevent
overheating. With these sensors, the "Occupied" and "UnOccupied" dial settings become the desired
indoor air temperatures.
The control will not allow the curve to be shifted up,
if windows or doors are left
open. Figure 7 shows how an Indoor Sensor will shift the heating curve and the WWSD point down to
prevent overheating, especially in milder weather when a Minimum On Time may cause overheating.
Boiler is cycled on/off
Boiler is turned off
Boiler is turned on 100%
-10°F
-30°F
(-23)°C
(-34)°C
90
(32)
WWSD
Point
70
(21)
(10)30(-1)10(-12)
20% minimum on time
50
Design
Outdoor
Temperature
Outdoor air temperature
Figure 5. Outdoor Reset with a
20% Minimum On Time setting
100%
90%
80%
70%
60%
50%
40%
30%
20%
20% Min. on time selected
10%
Percentage of boiler on time per cycle
0%
on time
Boiler is turned off
WWSD
Point
90
(32)
(21)
Figure 6. Shifting the heating curve
Boiler is cycled on/off
20% minimum on time
Design
Outdoor
70
Temperature
50
(10)30(-1)10(-12)
Outdoor air temperature
-10°F
(-23)°C
with the Occupied dial
100%
90%
80%
70%
60%
50%
40%
30%
Boiler is turned on 100%
20%
20% Min. on time selected
10%
Percentage of boiler on time per cycle
0%
on time
-30°F
(-34)°C
WWSD
90
(32)
Figure 7. Temporary shift to UnOc-
cupied mode or by Indoor Sensor
If the indoor temp. becomes
too warm, the Heating
Curve shifts down.
After the Heating
Cycle, the boiler is
kept off until the
indoor cools off
to the desired
room temp.
Boiler is turned off
Point
70
(21)
Early Start
123 4
Early Start
123 4
Indoor sensors S1 or
S1 & S2 DIP switches = on
Boiler is cycled on/off
20% minimum on time
Design
Outdoor
Temperature
50
(10)30(-1)10(-12)
Outdoor air temperature
Off
Off
-10°F
(-23)°C
074 room temperature feedback
Copyright © D 269 - 06/003 of 12
Steam
established
Heating
cycle
Early Start
Auxiliary
Boiler
Steam
established
Heating
cycle
Early Start
Auxiliary
Boiler
Power
WWSD
UnOcc.
Warning
Indoor Sensor S1
Indoor Sensor S2
Condensate Return Sensor
Indoor Sensor S1
Indoor Sensor S2
Condensate Return Sensor
Boiler is turned on 100%
-30°F
(-34)°C
Steam
established
Heating
cycle
Early Start
Auxiliary
Boiler
100%
90%
80%
70%
60%
50%
40%
30%
20%
20% Min. on time selected
10%
Percentage of boiler on time per cycle
0%
on time
Condensate Return Sensor 071 function
Setting a Minimum On Time for a steam system can
become problematic because a system takes more time to
reach operating temperature from a cold start than when it
is hot from a previous cycle. Use of the Condensate Return
Sensor included with the control is highly recommended
since the "Steam Established" dial can then be set to match
the operating characteristics of the system. The control will
turn on its "Boiler" light and fire the boiler for a warm-up
period, modifying the cycle to operate as in Figure 8.
Early Start
Establishing Steam
(Warm up)
Power
WWSD
UnOcc.
Warning
Steam
established
Heating
cycle
Early Start
Auxiliary
Boiler
123 4
Off
oor Sensor
Condensate Return Sensor
Heating Cycle
(on time)
Steam
Power
established
Heating
WWSD
cycle
Early Start
UnOcc.
Auxiliary
Warning
Boiler
Condensate return sensor
DIP switch = on
Steam
Power
established
Heating
WWSD
cycle
Early Start
UnOcc.
Auxiliary
Warning
Boiler
Heating Cycle
(off time)
Steam
Power
established
Heating
WWSD
cycle
Early Start
UnOcc.
Auxiliary
Warning
Boiler
Boiler on
off
Boiler Operation
15 minutes
on time
Boiler off
Steam established - start cycle
45 minutes off time
60 minute cycle
Boiler on
15 minutes
on time
Steam established - start cycle
45 minutes off time
60 minute cycle
Boiler off
220°F
210°F
200°F
190°F
180°F
(Warm-up period)
Establishing Steam
170°F
temperature
160°F
Condensate return
150°F
est.
off
Steam established
temperature setting
(Warm-up period)
Establishing Steam
est.
on
off
140°F
on
Figure 8. 25% on time with Condensate Return Sensor and "Steam Established" dial set to 170°F
The control will not start to time out the Heating Cycle until the Condensate Return Sensor reaches the temperature set on the "Steam
Established" dial. When this occurs, the "Steam Established" light will come on and the control will operate the boiler until the on time of the
Heating Cycle has elapsed. This function ensures that steam has been established throughout the system before the Heating Cycle is started.
In a two pipe system, most installers will place the Condensate Sensor on the condensate return line of the radiator furthest from the boiler.
In one pipe systems the best location is usually on the pipe just before it enters the last radiator. These locations are usually good, but in
some larger systems with long runs it may be necessary to place the sensor closer to the boiler so that the first rooms in the system do not
overheat. Again, it is important to ensure that the system components are all working properly, since in a properly vented and drained system,
steam is established quickly throughout the system during each cycle, and sensor placement is not as critical as in some "problem" systems.
Boiler on
15 minutes
on time
Boiler off
Steam established - start cycle
45 minutes off time
Boiler on
15 minutes
on time
Steam established - start cycle
45 minutes off time
Boiler off
Boiler
Operation
60 minute cycle
220°F
210°F
200°F
190°F
180°F
170°F
160°F
temperature
150°F
Condensate return
140°F
Figure 9. 25% on time with Condensate Return Sensor, "Steam Established" dial set to 170°F and "Lockout Diff'l" set to 30°F
Copyright © D 269 - 06/00 4 of 12
off
Steam established
temperature setting
30°F Lockout differential setting
Lockout period
(Warm-up period)
Establishing Steam
est.
on
60 minute cycle
off
Lockout period
on
(Warm-up period)
Establishing Steam