Rockwell Automation 1769-IQ16F User Manual

Installation Instructions
Compact 16-point 24V dc Sink/Source High-speed Input Module
Catalog Number 1769-IQ16F
Use this document as a guide when installing a Compact™ 16-point 24V dc sink/source high-speed input module.
Topic Page
Spare/Replacement Module Parts 12
Specifications 13
Hazardous Location Considerations 15
For More Information 16
Publication 1769-IN064A-EN-P - April 2003
2 Compact 16-point 24V dc Sink/Source High-speed Input Module
Important User Information
Because of the variety of uses for the products described in this publication, those responsible for the application and use of these products must satisfy themselves that all necessary steps have been taken to assure that each application and use meets all performance and safety requirements, including any applicable laws, regulations, codes and standards. In no event will Rockwell Automation be responsible or liable for indirect or consequential damage resulting from the use or application of these products.
Any illustrations, charts, sample programs, and layout examples shown in this publication are intended solely for purposes of example. Since there are many variables and requirements associated with any particular installation, Rockwell Automation does not assume responsibility or liability (to include intellectual property liability) for actual use based upon the examples shown in this publication.
Allen-Bradley publication SGI-1.1, Safety Guidelines for the Application, Installation and Maintenance of Solid-State Control (available from your local Rockwell Automation office), describes some important differences between solid-state equipment and electromechanical devices that should be taken into consideration when applying products such as those described in this publication.
Reproduction of the contents of this copyrighted publication, in whole or part, without written permission of Rockwell Automation, is prohibited.
Throughout this publication, notes may be used to make you aware of safety considerations. The following annotations and their accompanying statements help you to identify a potential hazard, avoid a potential hazard, and recognize the consequences of a potential hazard:
WARNING
Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
!
ATTENTION
Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss.
!
IMPORTANT
Publication 1769-IN064A-EN-P - April 2003
Identifies information that is critical for successful application and understanding of the product.
Compact 16-point 24V dc Sink/Source High-speed Input Module 3
5
b

Module Description

1
10a
10
10b
8a
7a
a
9
7a
2a
DANGER
Do Not Remove RTB Under Power
Unless Area is Non-Hazardous
IN 0
IN 1
IN 2
IN 3
IN 4
IN 5
IN 6
IN 7
DC
COM1
IN 9
IN 8
IN 11
IN 10
IN 13
IN 12
IN 15
IN 14
DC
COM 2
Ensure Adjacent Bus Lever is Unlatched/Latched Before/After Removing/Inserting Module
1769-IQ16F
1769-IQ16
2b
Item Description
1 bus lever
(with locking function)
2a upper panel mounting tab
2b lower panel mounting tab
3
3 I/O diagnostic LEDs
4 module door with terminal
identification label
5a movable bus connector
with female pins
5b stationary bus connector
4
with male pins
6 nameplate label
7a upper
tongue-and-groove slots
7b lower
tongue-and-groove slots
8a upper DIN rail latch
8b lower DIN rail latch
5
9 write-on label (user ID tag)
10 removable terminal block (RTB)
with finger-safe cover
10a RTB upper retaining screw
6
10b RTB lower retaining screw
7b
7b
8b
Publication 1769-IN064A-EN-P - April 2003
4 Compact 16-point 24V dc Sink/Source High-speed Input Module

Module Installation

Compact I/O is suitable for use in an industrial environment when installed in accordance with these instructions. Specifically, this equipment is intended for use
in clean, dry environments (Pollution degree 2 Over Voltage Category II
(2)
(IEC 60664-1).

Prevent Electrostatic Discharge

(1)
) and to circuits not exceeding
(3)
ATTENTION
!

Remove Power

ATTENTION
!
Electrostatic discharge can damage integrated circuits or semiconductors if you touch bus connector pins. Follow these guidelines when you handle the module:
Touch a grounded object to discharge static potential.
Wear an approved wrist-strap grounding device.
Do not touch the bus connector or connector pins.
Do not touch circuit components inside the module.
If available, use a static-safe work station.
When not in use, keep the module in its static-shield box.
Remove power before removing or inserting this module. When you remove or insert a module with power applied, an electrical arc may occur. An electrical arc can cause personal injury or property damage by:
– sending an erroneous signal to your system’s field
devices, causing unintended machine motion
– causing an explosion in a hazardous environment
Electrical arcing causes excessive wear to contacts on both the module and its mating connector. Worn contacts may create electrical resistance.
(1)
Pollution Degree 2 is an environment where, normally, only non-conductive pollution occurs except that occasionally a temporary conductivity caused by condensation shall be expected.
(2)
Over Voltage Category II is the load level section of the electrical distribution system. At this level transient voltages are controlled and do not exceed the impulse voltage capability of the product’s insulation.
(3)
Pollution Degree 2 and Over Voltage Category II are International Electrotechnical Commission (IEC) designations.
Publication 1769-IN064A-EN-P - April 2003
Compact 16-point 24V dc Sink/Source High-speed Input Module 5
2

System Assembly

The module can be attached to the controller or an adjacent I/O module before or after mounting. For mounting instructions, see
Rail Mounting on page 8. To work with a system that is already mounted, see Replacing a Single Module within a System on page 8.
The following procedure shows you how to assemble the Compact I/O system.
1
Panel Mounting on page 6, or DIN
3
4
1
5
1. Disconnect power.
2. Check that the bus lever of the module to be installed is in the unlocked
(fully right) position.
3. Use the upper and lower tongue-and-groove slots (1) to secure the modules
together (or to a controller).
4. Move the module back along the tongue-and-groove slots until the bus
connectors (2) line up with each other.
5. Push the bus lever back slightly to clear the positioning tab (3). Use your
fingers or a small screw driver.
6. To allow communication between the controller and module, move the bus
lever fully to the left (4) until it clicks. Ensure it is locked firmly in place.
ATTENTION
When attaching I/O modules, it is very important that the bus connectors are securely locked together to ensure proper electrical connection.
6
!
Publication 1769-IN064A-EN-P - April 2003
6 Compact 16-point 24V dc Sink/Source High-speed Input Module
7. Attach an end cap terminator (5) to the last module in the system by using
the tongue-and-groove slots as before.
8. Lock the end cap bus terminator (6).
IMPORTANT
A 1769-ECR or 1769-ECL right or left end cap must be used to terminate the end of the serial communication bus.

Mounting Expansion I/O

ATTENTION
During panel or DIN rail mounting of all devices, be sure that all debris (metal chips, wire strands, etc.) is kept from falling into the module. Debris that falls into the module could cause damage on power up.
!

Minimum Spacing

Maintain spacing from enclosure walls, wireways, adjacent equipment, etc. Allow
mm (2 in.) of space on
50 all sides for adequate ventilation, as shown:
Side Side
Controller
Top
Compact I/O
Compact I/O
Bottom
Compact I/O
Compact I/O
End Cap
Compact I/O

Panel Mounting

Mount the module to a panel using two screws per module. Use M4 or #8 panhead screws. Mounting screws are required on every module.
Publication 1769-IN064A-EN-P - April 2003
Compact 16-point 24V dc Sink/Source High-speed Input Module 7

Panel Mounting Using the Dimensional Template

For more than 2 modules: (number of modules - 1) X 35 mm (1.38 in.)
Refer to host controller documentation for this dimension.
132
(5.197)
122.6±0.2
(4.826±0.008)
Host Controller
35
(1.38)
Compact I/O
28.5
(1.12)
Compact I/O
Compact I/O
Right End Cap
NOTE: All dimensions are in mm (inches). Hole spacing tolerance: ±0.4 mm (0.016 in.)

Panel Mounting Procedure Using Modules as a Template

The following procedure allows you to use the assembled modules as a template for drilling holes in the panel. If you have sophisticated panel mounting equipment, you can use the dimensional template provided on mounting hole tolerance, it is important to follow these procedures:
1. On a clean work surface, assemble no more than three modules.
2. Using the assembled modules as a template, carefully mark the center of all
module-mounting holes on the panel.
3. Return the assembled modules to the clean work surface, including any
previously mounted modules.
4. Drill and tap the mounting holes for the recommended M4 or #8 screw.
page 7. Due to module
5. Place the modules back on the panel, and check for proper hole alignment.
6. Attach the modules to the panel using the mounting screws.
TIP
If mounting more modules, mount only the last one of this group and put the others aside. This reduces remounting time during drilling and tapping of the next group.
7. Repeat steps 1 to 6 for any remaining modules.
Publication 1769-IN064A-EN-P - April 2003
8 Compact 16-point 24V dc Sink/Source High-speed Input Module

DIN Rail Mounting

The module can be mounted using the following DIN rails: 35 x 7.5 mm (EN 50 022
- 35 x 7.5) or 35 x 15 mm (EN 50 022 - 35 x 15).
Before mounting the module on a DIN rail, close the DIN rail latches. Press the DIN rail mounting area of the module against the DIN rail. The latches will momentarily open and lock into place.

Replacing a Single Module within a System

The module can be replaced while the system is mounted to a panel (or DIN rail).
1. Remove power. See important note on page 4.
2. On the module to be removed, remove the upper and lower mounting
screws from the module (or open the DIN latches using a flat-blade or phillips style screw driver).
3. Move the bus lever to the right to disconnect (unlock) the bus.
4. On the right-side adjacent module, move its bus lever to the right (unlock)
to disconnect it from the module to be removed.
5. Gently slide the disconnected module forward. If you feel excessive
resistance, check that the module has been disconnected from the bus, and that both mounting screws have been removed (or DIN latches opened).
TIP
6. Before installing the replacement module, be sure that the bus lever on the
module to be installed, and on the right-side adjacent module are in the unlocked (fully right) position.
7. Slide the replacement module into the open slot.
8. Connect the modules together by locking (fully left) the bus levers on the
replacement module and the right-side adjacent module.
9. Replace the mounting screws (or snap the module onto the DIN rail).
Publication 1769-IN064A-EN-P - April 2003
It may be necessary to rock the module slightly from front to back to remove it, or, in a panel-mounted system, to loosen the screws of adjacent modules.
Compact 16-point 24V dc Sink/Source High-speed Input Module 9
+
-
-
+
)
g)
)
g)

Field Wiring Connections

Grounding the Module

This product is intended to be mounted to a well-grounded mounting surface such as a metal panel. Additional grounding connections from the module’s mounting tabs or DIN rail (if used), are not required unless the mounting surface cannot be grounded. Refer to Industrial Automation Wiring and Grounding Guidelines, Allen-Bradley publication 1770-4.1, for additional information.

Input Wiring

Basic wiring of input devices
(1)
to the 1769-IQ16F is shown below.
ATTENTION
Miswiring of the module to an AC power source will damage the module.
Be careful when stripping wires. Wire fragments that fall into a
!
(1)
Sinking/Sourcing Inputs - Sourcing/sinking describes the current flow between the I/O module and the field device. Sourcing I/O circuits supply (source) current to sinking field devices. Sinking I/O circuits are driven by a current sourcing field device. Field devices connected to the negative side (DC Common) of the field power supply are sinking field devices. Field devices connected to the positive side (+V) of the field supply are sourcing field devices. Europe: DC sinking input and sourcing output module circuits are the commonly used options.
module could cause damage at power up. Once wiring is complete, ensure the module is free of all metal fragments.
+DC (sinking
-DC (sourcin
IN 0
IN 1
DC (sinking)
DC (sourcing)
24V dc
DC (sinking)
DC (sourcing)
IN 3
IN 5
IN 7
IN 9
IN 11
IN 13
IN 15
DC
COM 2
IN 2
IN 4
IN 6
DC
COM 1
IN 8
IN 10
IN 12
IN 14
24V dc
-DC (sinking
+DC (sourcin
Publication 1769-IN064A-EN-P - April 2003
10 Compact 16-point 24V dc Sink/Source High-speed Input Module
A removable, write-on label is provided with the module. Remove the label from the door, mark the identification of each terminal with permanent ink, and slide the label back into the door. Your markings (ID tag) will be visible when the module door is closed.
upper retaining
wiring the finger-safe terminal
lower retaining

Removing the Finger-Safe Terminal Block

To remove the terminal block, loosen the upper and lower retaining screws. The terminal block will back away from the module as you remove the screws. When replacing the terminal block, torque the retaining screws to 0.46 Nm (4.1 in-lbs).

Wiring the Finger-Safe Terminal Block

When wiring the terminal block, keep the finger-safe cover in place.
1. Loosen the terminal screws to be wired.
2. Route the wire under the terminal pressure plate. You can use the bare wire
or a spade lug. The terminals will accept a 6.35 mm (0.25 in.) spade lug.
TIP
Publication 1769-IN064A-EN-P - April 2003
The terminal screws are non-captive. Therefore, it is possible to use a ring lug [max. 1/4” o.d. with a 0.139” minimum i.d. (M3.5)] with the module.
Compact 16-point 24V dc Sink/Source High-speed Input Module 11
3. Tighten the terminal screw making sure the pressure plate secures the wire.
Recommended torque when tightening terminal screws is 0.68 Nm (6 in-lbs).
TIP
If you need to remove the finger-safe cover, insert a screw driver into one of the square, wiring holes and gently pry the cover off. If you wire the terminal block with the finger-safe cover removed, you will not be able to put it back on the terminal block because the wires will be in the way.

Wire Size and Terminal Screw Torque

Each terminal accepts up to two wires with the following restrictions:
Wire Type Wire Size Terminal Screw
Torque
Solid Cu-90°C (194°F) #14 to #22 AWG 0.68 Nm (6 in-lbs) 0.46 Nm (4.1 in-lbs)
Stranded Cu-90°C (194°F) #16 to #22 AWG 0.68 Nm (6 in-lbs) 0.46 Nm (4.1 in-lbs)
Retaining Screw
Tor qu e

I/O Memory Mapping

Input Data File

For each input module, slot x, word 0 in the input data file contains the current state of the field input points.
Bit Position
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Word
0 r r r r r r r r r r r r r r r r
r= read
Publication 1769-IN064A-EN-P - April 2003
12 Compact 16-point 24V dc Sink/Source High-speed Input Module

1769-IQ16F Configuration File

The read/writable configuration data file allows the setup of the digital filter settings for each of the two input groups. Group 0 is inputs 0 - 7, Group 1 is inputs 8 - 15.
The manipulation of the bits from this file is normally done with programming software (e.g., RSLogix 500, RSNetworx for DeviceNet, etc.) during initial configuration of the system. In that case, graphical screens are provided via the programmer to simplify configuration. However, some systems (e.g., 1769-ADN DeviceNet Adapter) also allow the bits to be altered as part of the control program using communication rungs. In that case, it is necessary to understand the bit arrangement.
Bit Position
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Word
0 Filter Time On to Off
Group 1
1 0000000000000000
2 0000000000000000
3 0000000000000000
Filter Time Off to On
Group 1
Filter Time On to Off
Group 0
Filter Time Off to On
Group 0
Filter Time
(1)
Filter Time: Word 0, the Filter Time configures
the ON to OFF and OFF to ON hardware delay times for each input group.
(1)
2.0 msec 0010
1.0 msec 0011
0.5 msec 0100
0.1 msec 0101
0.0 msec 0110

Spare/Replacement Module Parts

Terminal Block: 1769-RTBN18 (1 per kit)
Door Label: 1769-RL1 (2 per kit)
Door: 1769-RD (2 per kit)
Publication 1769-IN064A-EN-P - April 2003
Bit Setting
Compact 16-point 24V dc Sink/Source High-speed Input Module 13

Specifications

General Specifications

Specification Valu e
Dimensions 118 mm (height) x 87 mm (depth) x 35 mm (width)
Approximate Shipping Weight (with carton)
Storage Temperature -40°C to +85°C (-40°F to +185°F)
Operating Temperature 0°C to +60°C (32°F to +140°F)
Operating Humidity 5% to 95% non-condensing
Operating Altitude 2000 meters (6561 feet)
Vibration Operating: 10 to 500 Hz, 5G, 0.030 inches maximum
Shock Operating: 30G panel mounted (20G DIN rail mounted)
Agency Certification C-UL certified (under CSA C22.2 No. 142)
Hazardous Environment Class Class I, Division 2, Hazardous Location, Groups A, B, C, D (UL
Radiated and Conducted Emissions EN50081-2 Class A
Electrical /EMC: The module has passed testing at the following levels:
ESD Immunity (IEC1000-4-2) 4kV contact, 8 kV air, 4 kV indirect
Radiated Immunity (IEC1000-4-3) 10 V/m, 80 to 1000 MHz, 80% amplitude modulation, +900
Fast Transient Burst (IEC1000-4-4) 2 kV, 5 kHz
Surge Immunity (IEC1000-4-5) 2 kV common mode, 1 kV differential mode
Conducted Immunity (IEC1000-4-6)
(1)
Conducted Immunity frequency range may be 150 kHz to 30 MHz if the Radiated Immunity frequency range is 30 MHz to 1000 MHz.
height including mounting tabs is 138 mm
4.65 in. (height) x 3.43 in (depth) x 1.38 in (width) height including mounting tabs is 5.43 in.
270g (0.6 lbs.)
peak-to-peak Relay Operation: 2G
Relay Operation: 7.5G panel mounted (5G DIN rail mounted) Non-Operating: 40G panel mounted (30G DIN rail mounted)
UL 508 listed CE compliant for all applicable directives
1604, C-UL under CSA C22.2 No. 213)
MHz keyed carrier
10V, 0.15 to 80 MHz
(1)
Publication 1769-IN064A-EN-P - April 2003
14 Compact 16-point 24V dc Sink/Source High-speed Input Module
Input Specifications
Specification 1769-IQ16F
Voltage Category
24V dc (sink/source
Operating Voltage Range 10 to 30V dc at 30°C (86°F)
10 to 26.4V dc at 60°C (140°F)
Number of Inputs 16
Bus Current Draw (max.) 110 mA at 5V dc (0.55W)
Heat Dissipation 3.55 Total Watts (The Watts per point, plus the minimum Watts, with
all points energized.)
Digital Filter OFF to ON 0s, 100µs, 500µs, 1ms, 2ms
ON to OFF 0s, 100µs, 500µs, 1ms, 2ms
Hardware Delay OFF to ON 100µs (typical)
ON to OFF 250µs (typical)
Off-State Voltage (max.) 5V dc
Off-State Current (max.) 1.5 mA
On-State Voltage (min.) 10V dc
On-State Current (min.) 2.0 mA
Inrush Current (max.) 250 mA
Nominal Impedance 3K
IEC Input Compatibility Type 1+
Power Supply Distance Rating 8 (The module may not be more than 8 modules away from the power
supply or controller.)
Input Point to Bus (Compact Bus) Isolation
Verified by one of the following dielectric tests: 1200V ac for 1 sec. or 1697V dc for 1 sec. 75V dc working voltage (IEC Class 2 reinforced insulation)
Isolated Groups Group 1: inputs 0 to 7
Group 2: inputs 8 to 15 Isolated groups operate in either sink or source configurations.
Input Group to Input Group Isolation Verified by one of the following dielectric tests: 1200V ac for 1 sec. or
1697V dc for 1 sec. 75V dc working voltage (IEC Class 2 reinforced insulation)
Vendor I.D. Code 1
Product Type Code 7
Product Code 69
(1)
Sinking/Sourcing Inputs - Sourcing/sinking describes the current flow between the I/O module and the field device. Sourcing I/O circuits supply (source) current to sinking field devices. Sinking I/O circuits are driven by a current sourcing field device. Field devices connected to the negative side (DC Common) of the field power supply are sinking field devices. Field devices connected to the positive side (+V) of the field supply are sourcing field devices. Europe: DC sinking input and sourcing output module circuits are the commonly used options.
(1)
)
300µs (maximum)
1ms (maximum)
Publication 1769-IN064A-EN-P - April 2003
Compact 16-point 24V dc Sink/Source High-speed Input Module 15

Hazardous Location Considerations

This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D or non-hazardous locations only. The following ATTENTION statement applies to use in hazardous locations.
ATTENTION
!
EXPLOSION HAZARD
– Substitution of components may impair suitability for Class I,
Division 2.
– Do not replace components or disconnect equipment unless
power has been switched off or the area is known to be non-hazardous.
– Do not connect or disconnect components unless power has
been switched off or the area is known to be non-hazardous.
This product must be installed in an enclosure.All wiring must comply with N.E.C. article 501-4(b).

Environnements dangereux

Cet équipement est conçu pour être utilisé dans des environnements de Classe 1, Division 2, Groupes A, B, C, D ou non dangereux. La mise en garde suivante s’applique à une utilisation dans des environnements dangereux.
ATTENTION
!
DANGER D’EXPLOSION
– La substitution de composants peut rendre cet équipement
impropre à une utilisation en environnement de Classe 1, Division 2.
– Ne pas remplacer de composants ou déconnecter
l'équipement sans s'être assuré que l'alimentation est coupée et que l'environnement est classé non dangereux.
– Ne pas connecter ou déconnecter des composants sans
s'être assuré que l'alimentation est coupée ou que l'environnement est classé non dangereux.
– Ce produit doit être installé dans une armoire.
Publication 1769-IN064A-EN-P - April 2003

For More Information

For Refer to this Document Pub. No.
a more detailed description of how to install and
use your Compact I/O with MicroLogix
1200 & 1500 programmable controller
a more detailed description of how to install
use your Compact I/O with the
and 1769-ADN DeviceNet Adapter
a more detailed description of how to install and use you programmable controllers
more information on proper wiring and grou
r Compact I/O with CompactLogix
nding techniq
ues
If you would like a manual, you can:
download a free electronic version from the internet: w.ab.com/micrologix or www.theautomationbookstore.com
ww
purchase a printed manual by:
contacting your local distributor or Rockwell Automation representativevisiting www.theautomationbookstore.com and placing your ordercalling 1.800.9NEWLIT(800.963.9548) (USA/Canada)
01.330.725.1574 (Outside USA/Canada)
or 0
MicroLogix 1200 and MicroLogix
00 Programmable Controllers User
15 Manual
1769-ADN DeviceNet Adapter User
l
Manua
CompactLogix System User Manual 1769-UM007C-EN-P
Industrial Automation Wiring and Grounding Guidelines
1764-RM001B-US-P
1769-UM001A-US-P
1770-4.1
Compact and MicroLogix are trademarks of Rockwell Automation.
Publication 1769-IN064A-EN-P - April 2003 PN 40071-151-01(1)
Copyright © 2003 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.
´H'+S!¶1z¨
Loading...