Rockwell Automation 1768-L43 User Manual

1768 CompactLogix System
Catalog Numbers Quick Start
1768-L43 and 1768-L45 CompactLogix Controllers
Important User Information
WARNING
IMPORTANT
ATTENTION
SHOCK HAZARD
BURN HAZARD
Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1 Automation sales office or online at http://www.rockwellautomation.com/literature/ between solid state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
available from your local Rockwell
) describes some important differences
Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
Identifies information that is critical for successful application and understanding of the product.
Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence
Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be present.
Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach dangerous temperatures.
Allen-Bradley, Rockwell Automation, Rockwell Software, Inc., CompactLogix, ControlLogix, FactoryTalk ME, Kinetix, Logix5000, Point I/O, Panelview Plus, PowerFlex, RSLinx, RSLinx Classic, RSLinx Enterprise, RSLogix, RSLogix 5000, RSLogix 5000 with PhaseManager, RSView Machine Edition, RSView ME, RSView SE, RSView Studio, RSView Enterprise, and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Follow the path that matches your hardware and network configuration.
Chapter 12
Create a PanelView Plus
Application
Chapter
13
Create a Kinetix 6000
Application
Chapter 11
CCreate a PowerFlex 70
Application
Chapter 1
Prepare the CompactLogix
Hardware
Chapter 2
Prepare the Computer and Load
Controller Firmware
Chapter 3
Prepare the Distributed
POINT I/O Hardware
Chapter 6
Prepare the Kinetix 6000
Multi-axis Servo Drive
System
Chapter 5
Prepare the PanelView
Plus Terminal
Chapter 7
Configure the
EtherNet/IP Network
Chapter 8
Configure the
DeviceNet Network
Chapter 9
Create a Project in RSLogix 5000
Chapter 10
Add Distributed Point
I/O Modules to the
Required
Optional
depending on your system
Optional
depending on your network
Required
Optional
depending on your system
Required
Chapter 4
Prepare the
PowerFlex 70 Drive
Where to Start
3Publication IASIMP-QS003B-EN-P - October 2009 3
Where to Start
1768-L43 CompactLogix Controller with
1768-ENBT EtherNet/IP and 1768-M04SE SERCOS Modules
Computer with Ethernet Port
Distributed POINT I/O
with 1734-AENT Adapter
PowerFlex 70 Drive with
20-COMM-E Adapter
2711P PanelView Plus Terminal
with Built-in EtherNet/IP Port
Ethernet Switch
1756-CP3
EtherNet/IP
SERCOS
2094 Kinetix 6000
Multi-axis Servo Drive System
Serial

How Hardware Is Connected

This quick start demonstrates CompactLogix L43 and L45 control systems using a single EtherNet/IP or DeviceNet network for cost-effectiveness and simplified setup. You may choose to use a multiple network system requiring a combination of EtherNet/IP and DeviceNet procedures shown in this quick start.
Rockwell Automation also offers many devices other than those in the examples. See your local Rockwell Automation representative for other device options.
Option 1: 1768-L43 and 1768-L45 Systems with EtherNet/IP Network
4 Publication IASIMP-QS003B-EN-P - October 2009
Option 2: 1768-L43 and L45 Systems with DeviceNet Network
1768-L43 CompactLogix Controller with
1768-M04SE SERCOS and 1769-SDN DeviceNet Modules
Distributed POINT I/O
with 1734-ADN Adapter
PowerFlex 70 Drive with
20-COMM-D Adapter
DeviceNet Power Supply
1606-XLDNET8
2711P PanelView Plus Terminal
Computer
Serial
DeviceNet
SERCOS
DeviceNet with KwikLink
flat cable and micro connectors
2094 Kinetix 6000
Multi-axis Servo Drive System
2706-NC13
1756-CP3
Where to Start
Publication IASIMP-QS003B-EN-P - October 2009 5
Where to Start
PanelView Plus
AC Line
Filter
Line Interface
Module
PowerFlex 70
Kinetix 6000 Drive Modules
DeviceNet Power Supply
Distributed POINT I/O
Ethernet Switch
1768-L43 CompactLogix System
DeviceNet KwikLink System
E-Stop
Through-the-door
Disconnect
1794-PS3

Sample System Panel Layout

The sample panel layout shows the general orientation of 1768-L43 and 1768-L45 system components for both EtherNet/IP and DeviceNet networks used in this quick start.
For additional panel layout assistance, the Kinetix Accelerator Toolkit CD in Appendix provides CAD enclosure, component, and wiring diagrams, in DXF format, for most Rockwell Automation motion components. Refer to the System Design for Control of Electrical Noise Reference Manual, publication GMC-RM001
For panel layout instructions specific to the Kinetix 6000 drives, refer to the Kinetix 6000 Installation Manual, publication 2094-IN001
B
, for best practice techniques.
.
6 Publication IASIMP-QS003B-EN-P - October 2009
Prepare the CompactLogix Hardware

Table of Contents

Preface
About This Publication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Audience. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Required Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Parts List: Option 1, 1768-L43 System with EtherNet/IP . . . . . . . . . 15
Parts List: Option 2, 1768-L43 System with DeviceNet . . . . . . . . . . . 17
Conventions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Chapter 1
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Before You Begin. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
What You Need . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Follow These Steps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
About the 1768 CompactLogix Controller. . . . . . . . . . . . . . . . . . . . . . 23
Mount and Wire the Line Interface Module. . . . . . . . . . . . . . . . . . . . . 24
Assemble the 1768 CompactLogix System. . . . . . . . . . . . . . . . . . . . . . 25
Make EtherNet/IP Network Connection. . . . . . . . . . . . . . . . . . . . . . . 28
Make DeviceNet Network Connections. . . . . . . . . . . . . . . . . . . . . . . . 29
Wire the 1768-PA3 Power Supply. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Prepare the Computer and Load Controller Firmware
Prepare the Distributed POINT I/O Hardware
Chapter 2
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Before You Begin. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
What You Need . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Follow These Steps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Terminology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Make Network Connections for Personal Computer. . . . . . . . . . . . . . 38
Install RSLogix Programming Software . . . . . . . . . . . . . . . . . . . . . . . . 39
Configure a Serial Driver . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Set the IP Address for the Computer . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Configure the EtherNet/IP Driver in RSLinx Software . . . . . . . . . . . 48
Load the Controller Firmware. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Install Additional Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Chapter 3
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Before You Begin. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
What You Need . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Follow These Steps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Mount and Connect the Network Adapter. . . . . . . . . . . . . . . . . . . . . . 55
Mount the POINT I/O Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Mount and Wire the POINT I/O Power Supply. . . . . . . . . . . . . . . . . 58
Wire the Adapter and I/O Modules to the Power Supply. . . . . . . . . . 59
Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
7 Publication IASIMP-QS003B-EN-P - October 2009
Table of Contents
Prepare the PowerFlex 70 Drive
Prepare the PanelView Plus Terminal
Chapter 4
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Before You Begin. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
What You Need . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Follow These Steps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Mount and Wire the PowerFlex 70 Drive. . . . . . . . . . . . . . . . . . . . . . . 63
Configure the Communication Adapter . . . . . . . . . . . . . . . . . . . . . . . . 65
Connect Communication Adapter to the PowerFlex 70 Drive . . . . . . 66
Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Chapter 5
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Before You Begin. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
What You Need . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Follow These Steps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Mount and Wire the PanelView Plus Terminal . . . . . . . . . . . . . . . . . . 71
Make Network Connections for PanelView Plus. . . . . . . . . . . . . . . . . 72
Assign IP Address for PanelView Plus . . . . . . . . . . . . . . . . . . . . . . . . . 73
Upgrade Terminal Firmware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Prepare the Kinetix 6000 Multi-axis Servo Drive System
Configure the EtherNet/IP Network
Chapter 6
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Before You Begin. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
What You Need . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Follow These Steps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Mount and Bond the Power Rail. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Mount the Integrated Axis and Axis Module . . . . . . . . . . . . . . . . . . . . 80
Wire Power to the Integrated Axis Module . . . . . . . . . . . . . . . . . . . . . 82
Wire Servo Motors to Integrated Axis and Axis Modules . . . . . . . . . . 83
Connect the SERCOS Fiber Optic Cables . . . . . . . . . . . . . . . . . . . . . . 84
Set the SERCOS Node Address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Chapter 7
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Before You Begin. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
What You Need . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Follow These Steps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Terminology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Assign IP Addresses. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Browse the EtherNet/IP Network in RSLinx Classic Software . . . . . 91
Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
8 Publication IASIMP-QS003B-EN-P - October 2009
Configure the DeviceNet Network
Create a Project in RSLogix 5000 Programming Software
Table of Contents
Chapter 8
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Before You Begin. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
What You Need . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Follow These Steps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Apply Power to the DeviceNet Network . . . . . . . . . . . . . . . . . . . . . . . 94
Set the Node Address of the DeviceNet Scanner . . . . . . . . . . . . . . . . 95
Create a DeviceNet Configuration File. . . . . . . . . . . . . . . . . . . . . . . . . 97
Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Chapter 9
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Before You Begin. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
What You Need . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Follow These Steps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
Create a Project . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
Configure 1768-ENBT Ethernet Module. . . . . . . . . . . . . . . . . . . . . . 104
Configure 1769-SDN DeviceNet Module . . . . . . . . . . . . . . . . . . . . . 105
Configure 1769 Local I/O Modules . . . . . . . . . . . . . . . . . . . . . . . . . . 107
Verify I/O Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
Add Ladder Logic to Test Local 1769 Compact I/O Modules. . . . . 109
Set the Project Path and Download to the Controller . . . . . . . . . . . . 112
Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114
Add Distributed Point I/O Modules to the Project
Chapter 10
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
Before You Begin. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
What You Need . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
Follow These Steps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
Add Distributed I/O Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
Configure the DeviceNet Subnet . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
Configure the 1734-ADN Properties . . . . . . . . . . . . . . . . . . . . . . . . . 123
Create a DeviceNet Scanlist. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126
Add Ladder Logic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128
Create DeviceNet Tags and Add Ladder Logic . . . . . . . . . . . . . . . . . 130
Download the Project . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135
Test the Distributed I/O Light . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136
Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136
Publication IASIMP-QS003B-EN-P - October 2009 9
Table of Contents
Create a PowerFlex 70 Application
Create a PanelView Plus Application
Chapter 11
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137
Before You Begin. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137
What You Need . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137
Follow These Steps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138
Add the Drive to Your RSLogix 5000 Project . . . . . . . . . . . . . . . . . . 139
Edit the Drive Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 143
Create a DeviceNet Scanlist. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 145
Create DeviceNet Tags . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 149
Download the Project . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 152
Test the PowerFlex 70 Tags . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 153
Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 159
Chapter 12
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 161
Before You Begin. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 161
What You Need . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 161
Follow These Steps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 162
Create a New Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 163
Create an RSLinx Enterprise Configuration in
FactoryTalkView ME . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 164
Create Device Shortcuts to the Controller . . . . . . . . . . . . . . . . . . . . . 166
Create the OB16_Light Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . 170
Create a Push Button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 173
Test the Indicator and Push Button . . . . . . . . . . . . . . . . . . . . . . . . . . 175
Add a Goto Configuration Mode Button . . . . . . . . . . . . . . . . . . . . . . 176
Assign Keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 177
Assign an Initial Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 178
Transfer the Application to the PanelView Plus Terminal. . . . . . . . . 179
Test the Application on the PanelView Plus Terminal . . . . . . . . . . . 181
Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 182
Chapter 13
Create a Kinetix 6000 Application
10 Publication IASIMP-QS003B-EN-P - October 2009
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 183
Before You Begin. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 183
What You Need . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 183
Follow These Steps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 184
Enable Coordinated System Time Master . . . . . . . . . . . . . . . . . . . . . 185
Create the Motion Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 186
Configure Your Logix SERCOS Module . . . . . . . . . . . . . . . . . . . . . . 187
Configure Your Kinetix IAM and AM Modules . . . . . . . . . . . . . . . . 189
Configure Axis Properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 192
Save and Download Your Program. . . . . . . . . . . . . . . . . . . . . . . . . . . 193
Test the Kinetix Application File . . . . . . . . . . . . . . . . . . . . . . . . . . . . 195
Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 196
Network Information
Kinetix Accelerator Toolkit
Motion Anaylzer
Table of Contents
Appendix A
Network Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 197
Appendix B
Sample Panel Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 199
Simplified Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 199
Preconfigured HMI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 199
Preconfigured Logic. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 199
Diagnostic Tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 200
Kinetix Accelerator Toolkit CD . . . . . . . . . . . . . . . . . . . . . . . . . . 200
Appendix C
Motion Analyzer. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 201
Publication IASIMP-QS003B-EN-P - October 2009 11
Table of Contents
12 Publication IASIMP-QS003B-EN-P - October 2009
Preface

About This Publication

This quick start provides examples and procedures for 1768-L43 and 1768-L45 CompactLogix systems. It includes version 18 release updates for RSLogix 5000 programming software. These procedures cover many common user tasks, such as:
connecting the controller to multiple devices including local and distributed I/O, drives,
Kinetix 6000 servo drives, and a PanelView Plus terminal.
connecting and configuring EtherNet/IP, DeviceNet, and serial networks using
CompactLogix systems.
creating and monitoring controller programs.
The examples are designed to get devices installed and communicating with each other in the simplest way possible. The programming examples are not complex, and offer easy solutions to verify that devices are communicating properly.
The beginning of each chapter contains the following information. Read these sections carefully before beginning work in each chapter.
Before You Begin - This section lists the steps that must be completed and decisions
that must be made before starting that chapter. Because the chapters in this quick start do not have to be completed in the order in which they appear, this section defines the minimum amount of preparation required before completing the current chapter.
What You Need - This section lists the tools that are required to complete the steps in
the current chapter. This includes, but is not limited to, hardware and software.
Follow These Steps - This section illustrates the steps in the current chapter and
identifies which steps are required to complete the examples using specific networks.
Also note that the electronic version of this publication contains links to pages within publications for easier navigation. Click on any chapter title, chapter number, topic title, or page number to follow a link to the item.
13Publication IASIMP-QS003B-EN-P - October 2009 13

Audience

This quick start was created to assist experienced or new industrial control users not familiar with the CompactLogix controllers or Integrated Architecture products of Rockwell Automation.

Required Software

The table lists software required to complete the examples in this quick start. Some software is required regardless of the 1768 CompactLogix system you use and other software is dependent on the network and devices in the system.
Rockwell Automation Version Required for
RSLogix 5000 programming software 18
RSNetWorx for DeviceNet software 7.0 DeviceNet network FactoryTalkView Machine Edition software
Includes:
Factory Talk Services
RSLinx Enterprise
RSLinx Lite (Classic)
All 1768-L43 and 1768-L45 systems
PanelView Plus terminals
14 Publication IASIMP-QS003B-EN-P - October 2009

Parts List: Option 1, 1768-L43 and 1768-L45 Systems with EtherNet/IP

The table lists the parts for the 1768-L43 and 1768-L45 systems with an EtherNet/IP network and a 200/230V Kinetix 6000 Multi-axis Servo Drive System.
Parts List: Option 1, 1768-L43 and 1768-L45 Systems with EtherNet/IP Network
General Configuration
Quantity Catalog Number Description
1 1768-L43 and 1768-L45 CompactLogix Controller 1 1768-PA3 CompactLogix Power Supply 1 1769-ECR Compact I/O Right End Cap/Terminator 1 1769-IF4 Compact 4 Channel Analog Current/Voltage Input Module 1 1769-IQ16 Compact 16 Point 24V dc Sinking/Sourcing Input Module 1 1769-IF4XOF2 Compact 8 Bit Resolution, High Speed 4 In/2 Out Analog Combination Module 1 1769-OF2 Compact 2 Channel Analog Current/Voltage Output Module 1
1
1
1
1 1734-TB Wiring Base w/ Removable IEC Screw Terminals (Quantity of 10) 1 1794-PS13 FLEX I/O 85-264V ac to 24V dc 1.3A Power Supply 1 20AB4P2A3AYNNNNN PowerFlex 70 Drive. 1 2711P-B10C4D1 PanelView Plus 10 inch color keypad/touch terminal with EtherNet/IP and RS-232 1 1747-CP3 or 1756-CP3 RS-232 cable for connection between the 1768-L43 controller and personal computer 1 64-134 DIN rail (steel not aluminum), 1 m
EtherNet/IP Configuration
1 1768-ENBT CompactLogix EtherNet/IP Communication Module 1 1734-AENT POINT I/O Ethernet Adapter 1 20-COMM-E PowerFlex 70 EtherNet/IP Adapter 1 Ethernet Switch 6 Non Rockwell Automation Ethernet CAT5 Straight-through cables
1769-OB16
1734-IB4
1734-OB4E
1734-OE2C
(2)
(1)
(2) (3)
(2)
Compact 16 Point 24V dc Sourcing Output Module
POINT I/O 4 Sink Input Module
POINT I/O 4 Protected Output Module
POINT I/O 2 Current Output Analog Module
Publication IASIMP-QS003B-EN-P - October 2009 15
Parts List: Option 1, 1768-L43 and 1768-L45 Systems with EtherNet/IP Network
Quantity Catalog Number Description
Kinetix 6000 Servo Drive System - 200/230V (The quantity, size, and cat. nos. for the Kinetix equipment will vary by application motion requirements.)
1
1
1768-M04SE
2094-AL75S
(4)
SERCOS interface module installs in 1768 CompactLogix controller and connects to Integrated Axis modules or Axis modules.
Line Interface Module (LIM), 230V, 75 A
1 140U-H-RVM12R Through-the-door Disconnect for LIM 1 2090-XXLF-X330B Line Filter, 3-phase, 30 A ac 1 2094-PRS2 Power Rail, 2-slot, Slim 1 2094-AC09-M02 Integrated Axis Module (IAM), 6 kW Converter and 19 A Inverter Output 1 2094-AM01 Axis Module (AM), 9 A Inverter Output 1 MPL-A310P-MK22AA MP-Series Low Inertia Motor, 0.73 kW Output with Absolute, Multi-turn Feedback 2 2090-XXNPMP-16S03 Motor Power Cable: 3 m (9.8 ft) 2 2090-UXNFBMP-S03 Motor Feedback Cable, 3 m (9.8 ft) 2 2090-SCEP0-9 SERCOS Fiber Optic Cable, 0.9 m (2.9 ft) 1 2090-SCEP0-1 SERCOS Fiber Optic Cable, 0.1 m (5.1 in.)
(1)
The 1769-OB16 is the only Compact I/O module used in this quick start. The other modules are added as examples only and are not required.
(2)
Use POINT I/O modules at series C or later to complete examples in this quick start.
(3)
The 1734-OB4E module is the only POINT I/O module used in this quick start. The other modules are added as examples only and are not required.
(4)
The 2094-AL75S line interface module (LIM) is optional. Individual components can be purchased separately instead of the LIM.
16 Publication IASIMP-QS003B-EN-P - October 2009

Parts List: Option 2, 1768-L43 and 1768-L45 Systems with DeviceNet

The table lists the parts for a 1768-L43 and 1768-L45 Systems with DeviceNet I/O, serial connections, and a 200/230V Kinetix 6000 Multi-axis Servo Drive System.
Parts List: Option 2, 1768-L43 and 1768-L45 Systems with DeviceNet Network
General Configuration
Quantity Catalog Number Description
1 1768-L43 and 1768-L45 CompactLogix Controller 1 1768-PA3 CompactLogix Power Supply 1 1769-ECR Compact I/O Right End Cap/Terminator 1 1769-IF4 Compact 4 Channel Analog Current/Voltage Input Module 1 1769-IQ16 Compact 16 Point 24V dc Sinking/Sourcing Input Module 1 1769-IF4XOF2 Compact 8 Bit Resolution, High Speed 4 In/2 Out Analog Combination Module 1 1769-OF2 Compact 2 Channel Analog Current/Voltage Output Module 1
1
1
1
1 1734-TB Wiring Base w/ Removable IEC Screw Terminals (Quantity of 10) 1 1794-PS13 FLEX I/O 85-264V ac to 24V dc 1.3A Power Supply 1 20AB4P2A3AYNNNNN PowerFlex 70 Drive 1 2711P-B10C4D1 PanelView Plus 10 inch color keypad/touch terminal with EtherNet/IP and RS-232 1 1747-CP3 or 1756-CP3 RS-232 cable for connection between the 1768-L43 controller and personal computer 1 2711-NC13 RS-232 cable for connection between the PanelView Plus terminal and the 1768-L43
1 64-134 DIN rail (steel not aluminum), 1 m
DeviceNet Configuration
1 1769-SDN Compact DeviceNet Scanner 1 1734-ADN POINT I/O DeviceNet Adapter 1 20-COMM-D PowerFlex 70 DeviceNet Adapter 1 1606-XLDNET8 DeviceNet Power Supply 1 1485C-P1E75 KwikLink Flat Cable, 75 m 2 1485A-T1E4 KwikLink Terminator/Resistor 3 1485P-P1E4-R5 KwikLink Sealed Micro Connector 3 1485K-P1F5-C KwikLink QD Cordset Micro Right-Angle Male 1 1485T-P1E4-B1 KwikLink Power Tap Module
1769-OB16
1734-IB4
1734-OB4E
1734-OE2C
(2)
(1)
(2) (3)
(2)
Compact 16 Point 24V dc Sourcing Output Module
POINT I/O 4 Sink Input Module
POINT I/O 4 Protected Output Module
POINT I/O 2 Current Output Analog Module
controller or personal computer
Publication IASIMP-QS003B-EN-P - October 2009 17
Parts List: Option 2, 1768-L43 and 1768-L45 Systems with DeviceNet Network
Quantity Catalog Number Description
Kinetix 6000 Servo Drive System - 200/230V (The quantity, size, and cat. nos. for the Kinetix equipment will vary by application motion requirements.)
1
1
1768-M04SE
2094-AL75S
(4)
SERCOS interface module installs in 1768 CompactLogix controller and connects to Integrated Axis modules or Axis modules.
Line Interface Module (LIM), 230V, 75 A
1 140U-H-RVM12R Through-the-door Disconnect for LIM 1 2090-XXLF-X330B Line Filter, 3-phase, 30 A ac 1 2094-PRS2 Power Rail, 2-slot, Slim 1 2094-AC09-M02 Integrated Axis Module (IAM), 6 kW Converter and 19 A Inverter Output 1 2094-AM01 Axis Module (AM), 9 A Inverter Output 1 MPL-A310P-MK22AA MP-Series Low Inertia Motor, 0.73 kW Output with Absolute, Multi-turn Feedback 2 2090-XXNPMP-16S03 Motor Power Cable: 3 m (9.8 ft) 2 2090-UXNFBMP-S03 Motor Feedback Cable, 3 m (9.8 ft) 2 2090-SCEP0-9 SERCOS Fiber Optic Cable, 0.9 m (2.9 ft) 1 2090-SCEP0-1 SERCOS Fiber Optic Cable, 0.1 m (5.1 in.)
(1)
The 1769-OB16 module is the only Compact I/O module used in this quick start. The other modules are added as examples only and are not required.
(2)
Use POINT I/O modules at series C or later to complete examples in this quick start.
(3)
The 1734-OB4E module is the only POINT I/O module used in this quick start. The other modules are added as examples only and are not required.
(4)
The 2094-AL75S line interface module (LIM) is optional. Individual components can be purchased separately instead of the LIM.
18 Publication IASIMP-QS003B-EN-P - October 2009

Conventions

This manual uses the following conventions.
Convention Meaning Example
Courier font
Check or uncheck Click to activate or deactivate a checkbox. Check the Disable Keying checkbox.
Click
Double-click
Type or enter text exactly as shown. Type cmd.
Click the left mouse button once while the cursor is positioned on object or selection.
Click the left mouse button twice in quick succession while the cursor is positioned on object or selection.
Click Browse.
Double-click the application icon.
Expand
Right-click
Select Click to highlight a menu item or list choice. Select New Module from the pull-down list. > Shows nested menu selections as menu name followed by menu
Click the + to the left of a given item /folder to show its contents.
Click the right mouse button once while the cursor is positioned on object or selection.
selection.
Expand 1768 Bus under I/O Configuration.
Right-click the 1768 Bus icon.
Select File
>Menu.
Publication IASIMP-QS003B-EN-P - October 2009 19
Notes:
20 Publication IASIMP-QS003B-EN-P - October 2009
Chapter
1
Prepare the CompactLogix Hardware

Introduction

In this chapter, you install your CompactLogix hardware including the controller, power supply, 1768 SERCOS module, and the 2094 line interface module. The line interface module will power the 1768 CompactLogix and Kinetix 6000 system components. Depending on your configuration, you also install the 1768 EtherNet/IP module, 1769 DeviceNet module, and local 1769 I/O modules.

Before You Begin

Determine which network and appropriate hardware to use.
For an EtherNet/IP network (option 1), use the 1768-ENBT module with the
controller.
For a DeviceNet (option 2), use the 1769-SDN module with the controller.
For a motion application (option 1 or 2), use a 1768-M04SE SERCOS module with the
controller.

What You Need

2094-AL75S line interface module (optional)
1768-L43 or 1768-L45 CompactLogix controller
1768-PA3 CompactLogix power supply
1769-ECR end cap
1768-ENBT EtherNet/IP module for an EtherNet/IP network (option 1)
Ethernet switch and standard CAT5 Ethernet cable for EtherNet/IP network
1768-M04SE SERCOS module for motion on either network (option 1 or 2)
1769-SDN DeviceNet module for a DeviceNet network (option 2)
– 1606-XLDNET8 power supply and KwikLink Power Tap module for DeviceNet
network
– KwikLink right-angle male cables with sealed microconnectors, connected to a flat
cable with terminator/resistor on each end for a DeviceNet network
1769 Compact I/O modules
Serial 1756-CP3 cable for EtherNet/IP and DeviceNet networks
21Publication IASIMP-QS003B-EN-P - October 2009 21
Chapter 1 Prepare the CompactLogix Hardware
page 25
Assemble the 1768
CompactLogix
System
Make EtherNet/IP
Network
Connection
Wire the
1768-PA3 Power
Supply
page 28
page 32
page 24
Mount and Wire
the Line Interface
Module
Make DeviceNet
Network
Connections
page 29
1768
CompactLogix
System
Line Interface
Module
Ethernet
Switch
DeviceNet Network
Through-the-door Disconnect for LIM Module

Follow These Steps

Complete the appropriate steps to assemble your 1768-L43/L45 CompactLogix hardware.
22 Publication IASIMP-QS003B-EN-P - October 2009
Prepare the CompactLogix Hardware Chapter 1
Slot 0
Slot 1
Slot 2
Slot 2
Slot 1
Slot 0
Slot 3
1768
1769

About the 1768 CompactLogix Controller

The 1768-L43 and 1768-L45 CompactLogix controllers combine a 1768 backplane and a 1769 backplane. The 1768 backplane supports the 1768 controller, the 1768 power supply, and a maximum of two 1768 modules, such as the EtherNet/IP module and the SERCOS interface module. The 1769 backplane supports 1769 modules, such as the 1769 DeviceNet module and 1769 I/O modules.
Publication IASIMP-QS003B-EN-P - October 2009 23
Chapter 1 Prepare the CompactLogix Hardware
WARNING

Mount and Wire the Line Interface Module

2094-AL75S or Equivalent Hardware, Required for EtherNet/IP and DeviceNet Systems
The line interface module (LIM) serves as the power connection and the generation point for the complete power needs of most control panels. The LIM module provides the control of three-phase power and the drive logic power, and also serves as the source and circuit protection of power for the controller, I/O, and other panel devices. A single LIM module can replace nine individual components, eliminating up to 100 interconnecting wire terminations. The 2094-AL75S line interface module (LIM) is optional. Individual components can be purchased separately instead of purchasing the LIM.
Verify that all incoming power is turned off before wiring power to the LIM module or any other devices in this chapter.
1. Lay out the position of the LIM module in the enclosure.
2. Attach the LIM module to the cabinet by using M6 (1/4 in.) bolts.
3. Tighten all mounting fasteners.
4. Mount the through-the-door disconnect switch for the LIM module.
5. Wire 230V 3-phase incoming power to the LIM module and
6. Bond the ground terminal to the panel.
L3 L2 L1
MAIN VAC
L3
L2
L1
195-265 VAC LINE, 50/60 Hz
L3'
L2'
L1'
195-265 VAC LOAD, 50/60 Hz
1 2 3 4
1 2 3 4
CONTROL VAC
CTRL2
1 2
CTRL1
230 VAC SUPPLY
AUX2
AUX2
AUX1
AUX1
1 2 3 4
I/O_COM
24 VDC SUPPLY
I/O_PWR I/O_COM I/O_PWR I/O_COM I/O_PWR
1 2 3 4 5 6
24 Publication IASIMP-QS003B-EN-P - October 2009
Prepare the CompactLogix Hardware Chapter 1
a
b
2
b
c
d

Assemble the 1768 CompactLogix System

1768-L43 Controller, 1768-L45 Controller, 1768-PA3 Power Supply, 1768-ENBT, 1768-M04SE, 1769-SDN, 1769 Local I/O Modules, 1769-ECR End Cap Terminator
1. Mount the 1768-L43 or 1768-L45 controller on the DIN rail.
a. Pull locking tabs out. b. Slide controller into
position and push locking tabs in.
2. If you have an EtherNet/IP module:
a. locate the Ethernet
(MAC) address on the side of module and record address in
Appendix A. b. pull locking tabs out. c. align module to the left
of controller on DIN
rail and slide the mating
connector into the
1768-L43 or 1768-L45
controller. d. push locking tabs in.
Publication IASIMP-QS003B-EN-P - October 2009 25
Chapter 1 Prepare the CompactLogix Hardware
b
a
c
a
b
c
3. Mount the SERCOS 1768-M04SE module.
a. Pull locking tabs out. b. Align SERCOS module
to the left of EtherNet/IP module or controller and slide into place.
c. Push locking tabs in.
4. Mount the power supply on the DIN rail.
a. Pull locking tabs out. b. Align supply to the left
of the SERCOS module and slide into place.
c. Push locking tabs in.
5. If you have a 1769-SDN DeviceNet module, locate the series letter and firmware revision on the side of the module and record in Appendix A.
26 Publication IASIMP-QS003B-EN-P - October 2009
6. Mount the 1769-SDN
b
c
d
b
c
a
and 1769 I/O modules to the right of the controller on DIN rail.
In this quick start, the 1769-SDN module is directly to the right of the controller in slot 1.
a. Pull locking tabs out. b. Slide module along
tongue-and-groove slots on the side of the controller or modules.
c. Push locking tabs in.
Prepare the CompactLogix Hardware Chapter 1
d. Slide white locking tab
to the left.
A maximum of three modules can be mounted between the 1769-SDN and the power supply.
7. Mount the 1769-ECR end cap terminator.
a. Pull locking tab to the
right. b. Slide end cap on rail. c. Pull locking tab to the
left.
Publication IASIMP-QS003B-EN-P - October 2009 27
Chapter 1 Prepare the CompactLogix Hardware
IO_PWR1 IO_COM1 IO_PWR1 IO_COM1 IO_PWR1 IO_COM1 COIL_E1 COIL_E2 ALRM_M SHIELD ALRM_B ALRM_COM CONSTAT_11 CONSTAT_12 CONSTAT_21 CONSTAT_22 CONSTAT_31 CONSTAT_32 CONSTAT_53 CONSTAT_54 SHIELD
1
3
5
7
9
11
13
15
17
19
21
2
4
6
8
10
12
14
16
18
20
IOL
3
4
24VDC (+) DC NEUT (-) CHS GND
Line Interface Module
I/O Power
Front View
8
1
Computer POINT I/O
connection
PowerFlex 70 connection
PanelView Plus connection
Ethernet CAT5 Cable

Make EtherNet/IP Network Connection

1. Mount the Ethernet switch to the DIN rail.
2. Connect the Ethernet switch power terminals to the I/O power terminals on the front of the line interface module.
3. Connect a CAT5 Ethernet cable between the Ethernet port on the bottom of 1768-ENBT module and the Ethernet switch.
4. Do not turn on incoming power.
28 Publication IASIMP-QS003B-EN-P - October 2009

Make DeviceNet Network Connections

Input
AC 100-120/200-240V
N L
Isolate power before disconnecting
1606-XL
POWER SUPPLY
DC ok
Output
200W Limited Power DC 24V / 8A
+ –
DC ok
AC 120V
AC 240V
1. Attach and lock the 1606-XLDNET8 DeviceNet power supply to a DIN rail by pressing the tab at the top of the supply.
Prepare the CompactLogix Hardware Chapter 1
Publication IASIMP-QS003B-EN-P - October 2009 29
Chapter 1 Prepare the CompactLogix Hardware
PowerFlex 70 Drive
with
20-COMM-D
Distributed
POINT I/O
Connection with
1734-ADN Adapter
1606-XLDNET8
DeviceNet Power Supply
KwikLink Sealed
Terminator
KwikLink Sealed
Terminator
KwikLink Sealed Micro Connector
2. Assemble the DeviceNet network cable system using the KwikLink flat cable, terminators, and sealed micro connectors for each device.
See instructions included with devices.
3. Wire a KwikLink QD Micro Cordset to the 1769-SDN connector.
Connect To
Red V+ White CAN High Bare Shield Blue CAN Low Black V-
4. Connect the QD Micro
5. Connect the DeviceNet
6. Connect the DeviceNet
Cordset to a KwikLink sealed microconnector on the network.
KwikLink power tap to the power supply Output connector.
Connect To
Red + White Not Used Shield Not Used Blue Not Used Black
power tap to the DeviceNet network.
AC 120V
AC 240V
Input
AC 100-120/200-240V
N L
Isolate power before disconnecting
DC ok
1606-XL
POWER SUPPLY
Output
200W Limited Power DC 24V / 8A
+ –
DC ok
30 Publication IASIMP-QS003B-EN-P - October 2009
WARNING
Verify that all incoming power is turned off before wiring power.
Input
AC 100-120/200-240V
N L
Isolate power before disconnecting
1606-XL
POWER SUPPLY
DC ok
Output
200W Limited Power DC 24V / 8A
+ –
DC ok
AC 120V
AC 240V
Line Interface Module
230V AC AUX Power
Top View
L (line)
N (neutral)
7. Wire the DeviceNet power supply to the 230V AC Aux Power Output connector on the line interface module.
8. Place the switch in the position that matches your supply voltage.
Prepare the CompactLogix Hardware Chapter 1
9. Do not turn on incoming power.
Publication IASIMP-QS003B-EN-P - October 2009 31
Chapter 1 Prepare the CompactLogix Hardware
L1
L2/N
Protective Earth Ground
Line Interface Module
230V AC AUX Power
Top View

Wire the 1768-PA3 Power Supply

Required for EtherNet/IP and DeviceNet Systems
1. Wire the 1768-PA3 power supply to the 230V AC Aux Power Output Connector on the line interface module.
2. Do not turn on incoming power.
32 Publication IASIMP-QS003B-EN-P - October 2009

Additional Resources

Resource Description
Prepare the CompactLogix Hardware Chapter 1
CompactLogix Controller Installation Instructions, publication 1768-IN004
CompactLogix EtherNet/IP Communication Module Installation Instructions, publication
1768-IN002
Compact I/O DeviceNet Scanner Module Installation Instructions, publication
1769-IN060
Compact Logix SERCOS Interface Module Installation Instructions, publication
1768-IN005
1768 CompactLogix Power Supply, publication
1768-IN001
KwikLink General Purpose DeviceNet Media Installation Instructions, publication
1485-IN001
1769 CompactLogix Selection Guide, publication 1769-SG001
Provides details on how to install controller firmware, configure the serial and EtherNet/IP driver, and troubleshoot system power and controller operation.
Provides details on how to install, configure and troubleshoot the module.
Provides details on how to install, configure and troubleshoot the module.
Provides information on available fiber optic cables, and details on how to install, configure and troubleshoot the module.
Provides details on power considerations, master control relay, safety circuits, grounding, power dissipation, input power requirements, and how to interpret the status indicators.
Provides details on how to install a DeviceNet network cable system.
Provides details on selecting 1769 CompactLogix system components.
Publication IASIMP-QS003B-EN-P - October 2009 33
Chapter 1 Prepare the CompactLogix Hardware
Notes:
34 Publication IASIMP-QS003B-EN-P - October 2009
Chapter
2
Prepare the Computer and Load Controller Firmware

Introduction

In this chapter, you configure network communication on your computer and install the necessary programming and configuration software.

Before You Begin

Assemble the CompactLogix hardware (Chapter 1).
Verify that your computer meets the software’s system requirements for your edition of
RSLogix 5000 software.
Refer to Required Software on page 14
for your system requirements.

What You Need

Personal computer
1756-CP3 serial cable to configure serial driver and update controller firmware
Ethernet CAT5 cable to configure EtherNet/IP driver (option 1)
RSLogix 5000 programming software (see page 14
RSLinx Classic software, version 2.54 or later (packaged with RSLogix 5000
programming software).
RSNetWorx for DeviceNet software for the DeviceNet network (option 2)
BOOTP/DHCP server utility (packaged with RSLogix 5000 programming software)
A Network Interface Card (NIC) and its associated Windows driver installed (the NIC
and driver are standard on most computers)
An Ethernet Address (MAC) for each device.
A planned IP Address for each device. If you are using an isolated network, determine a
numbering convention for your IP addresses.
for edition and version information)
ControlFlash software (packaged with RSLogix 5000 programming software)
35Publication IASIMP-QS003B-EN-P - October 2009 35
Chapter 2 Prepare the Computer and Load Controller Firmware
page 52
page 49
page 48
page 46
page 38
Set the IP
Address for
the Computer
Make Network
Connections for
Personal
Terminology
Configure the
EtherNet/IP
Driver in RSLinx
Software
Load the Controller
Firmware
Install Additional
Software
page 37
Install RSLogix Programming
Configure a Serial Driver
page 39
page 44

Follow These Steps

Complete the appropriate steps.
36 Publication IASIMP-QS003B-EN-P - October 2009
Prepare the Computer and Load Controller Firmware Chapter 2

Terminology

Ethernet networks use these types of addresses.
Term Definition
Ethernet Address Each Ethernet device has a unique Ethernet address (sometimes called a MAC address). The
address appears as twelve digits separated by colons (for example, xx:xx:xx:xx:xx:xx). It is usually on a label on the device itself.
Each digit is a number in hexadecimal (0 to 9 or A through F). No other device in the world will have the same address, and it can not be changed.
You use the Ethernet address to identify a device so you can assign it an IP address.
IP Address In addition to the Ethernet address, an IP address identifies a node on an Ethernet network.
The IP address can be manually set. or you can use special software to automatically assign it.
An IP Address consists of four decimal integers separated by periods (xxx.xxx.xxx.xxx). Each xxx is a decimal value from 0…255. For example, an IP Address could be 192.168.1.092 The selection of IP Addresses is beyond the scope of this quick start, so please contact your network administrator or use the ones provided in the examples.
Once you set an IP address for a device, you generally reference the device by its IP address. The examples in this quick start use IP Addresses to define communication paths to the devices.
Publication IASIMP-QS003B-EN-P - October 2009 37
Chapter 2 Prepare the Computer and Load Controller Firmware
1756-CP3
EtherNet/IP
Serial
Ethernet CAT 5
Serial
1756-CP3

Make Network Connections for Personal Computer

Network Connections Required for EtherNet/IP System
1. Connect a CAT5 Ethernet cable between the Ethernet port on the computer and the Ethernet switch.
This connection is used to configure the EtherNet/IP driver in RSLinx software.
2. Connect the 1756-CP3 cable between the CH0 serial port on the controller and a computer COM port.
This connection is used to configure the serial driver and load controller firmware.
Network Connections Required for DeviceNet System
Connect the 1756-CP3 cable between the CH0 serial port on the controller and the COM port on the computer.
This connection is used to configure the serial driver and load controller firmware.
38 Publication IASIMP-QS003B-EN-P - October 2009
Prepare the Computer and Load Controller Firmware Chapter 2
3. Accept the default software products for installation and click Next.
Throughout the installation, click Next to use default RSLogix 5000 installation settings except when indicated in the steps below.
1. Begin the RSLogix 5000 software installation.
2. Choose your language and click Continue.
4. Enter your user name, organization, and software serial number, then click Next.

Install RSLogix Programming Software

Required for all controllers
Publication IASIMP-QS003B-EN-P - October 2009 39
Chapter 2 Prepare the Computer and Load Controller Firmware
7. Select your activation type and click Next.
This quick start uses FactoryTalk Activation software to activate RSLogix 5000 software. For more information, see the FactoryTalk Activation FAQ, publication
Ftalk-FA017.
5. Accept the license agreement and click Next.
8. Click Next to install only the latest version of RSLogix 5000 software (version
18).
9. Verify that RSLogix 5000 Tools and Files is checked and click
Next.
6. Click Next to install the program
files to the default directory.
40 Publication IASIMP-QS003B-EN-P - October 2009
10. Click Next to install the typical firmware kits.
11. Click Next to install typical RSLogix Architect tools.
12. Click Next to install the typical set of EDS files and RSLinx software.
Prepare the Computer and Load Controller Firmware Chapter 2
Publication IASIMP-QS003B-EN-P - October 2009 41
Chapter 2 Prepare the Computer and Load Controller Firmware
13. Click Install to complete the installation.
The installation dialog box displays progress while the software installs.
TIP
As the installation progresses, you may be prompted to complete additional set-up tasks depending on your system configuration. Follow those prompts and enter information as indicated in the dialog boxes to complete your installation.
After a few moments, the FactoryTalk Installation Wizard starts.
14. Click Next.
15. Enter the Serial number and Product key from the
certification letter packaged with your software.
16. Click Next.
42 Publication IASIMP-QS003B-EN-P - October 2009
17. Select your host ID and click Next.
The activation completes if the computer is connected to the Internet.
If Internet access is not available, call Rockwell Automation Technical Support to complete your activation.
18. Click Finish to close the Activation Wizard.
Prepare the Computer and Load Controller Firmware Chapter 2
Publication IASIMP-QS003B-EN-P - October 2009 43
Chapter 2 Prepare the Computer and Load Controller Firmware
1. Launch RSLinx software.
2. Under Communications, select Configure Drivers.
3. Select RS-232 DF1 devices.
4. Click Add New.
5. Click OK to keep the default
name.

Configure a Serial Driver

Required for all controllers
44 Publication IASIMP-QS003B-EN-P - October 2009
The Serial driver is added to the Configured Drivers list.
10. Verify that the Status of the driver is Running, and click Close.
11. Click the RSWho icon to view the driver.
All of the configured, active drivers display.
6. Select the Comm Port to which you
connected the 1756-CP3 cable.
7. For Device, select
Logix5550/CompactLogix.
8. Click Auto Configure.
9. Click OK.
Expand the serial driver to see connected devices.
Prepare the Computer and Load Controller Firmware Chapter 2
Publication IASIMP-QS003B-EN-P - October 2009 45
Chapter 2 Prepare the Computer and Load Controller Firmware
1. On your desktop, right-click My Network Places and select Properties.
2. Double-click the Local Area
Connection.
3. Click Properties.
4. On the General tab, select Internet Protocol (TCP/IP) and click Properties.
5. Select Use the following IP address
and enter an IP address and Subnet mask for your computer using the example shown or enter your own address.
For more information about selecting an IP Address, see page 7-81
.
6. Click OK.
7. Record the IP address and subnet mask in the Network Worksheet on the back cover.
8. Click OK.

Set the IP Address for the Computer

Required for all controllers, regardless of network choice
46 Publication IASIMP-QS003B-EN-P - October 2009
9. Click the Support tab.
10. Verify that the IP Address and Subnet
Mask match what you entered on the
Appendix A.
If these numbers do not match what you entered, contact your network administrator to verify that your IP address is correct.
11. Close the Local Area Connection Status dialog box.
Prepare the Computer and Load Controller Firmware Chapter 2
Publication IASIMP-QS003B-EN-P - October 2009 47
Chapter 2 Prepare the Computer and Load Controller Firmware
1. If RSLinx software is not open, launch RSLinx software.
2. From the Communications
menu, choose Configure Drivers.
3. From the Available
Driver Types, select
Ethernet/IP Driver.
4. Click Add New.
5. Click OK to keep the default
name.
6. Click OK to Browse Local Subnet.

Configure the EtherNet/IP Driver in RSLinx Software

Required for 1768-L43, 1768-L45, and PanelView Plus
48 Publication IASIMP-QS003B-EN-P - October 2009

Load the Controller Firmware

TIP
The EtherNet/IP driver is added to the Configured Drivers list.
7. Verify that the driver’s
Status is Running, and click Close.
Prepare the Computer and Load Controller Firmware Chapter 2
Required for All Systems
This procedure shows how to load firmware in the controller using a serial connection. It is faster to load the firmware using an EtherNet/IP connection. For details, see the controller installation instructions.
1. Turn on incoming power to the CompactLogix power supply.
2. Launch the ControlFlash software.
Publication IASIMP-QS003B-EN-P - October 2009 49
Chapter 2 Prepare the Computer and Load Controller Firmware
18.0
3. Click Next when the Welcome screen appears.
4. Select the controller catalog number and click Next.
5. Move the keyswitch on controller to Program.
6. If the Current Revision matches the firmware revision you want, click Cancel, then skip to the next section.
Otherwise, select the revision level to which you want to update the controller and click Next.
If you are not sure what revision to use, select the latest.
50 Publication IASIMP-QS003B-EN-P - October 2009
7. Click Finish, then click
18.0
ATTENTION
Yes to start the firmware update.
When the controller is updated, the status box displays Update complete.
8. Close ControlFlash by clicking Cancel, then Yes.
Prepare the Computer and Load Controller Firmware Chapter 2
The 1768-L43 and 1768-L45 controllers are compatible with firmware version 16.23, or later. If you encounter errors, contact Technical Support.
Publication IASIMP-QS003B-EN-P - October 2009 51
Chapter 2 Prepare the Computer and Load Controller Firmware

Install Additional Software

If your network configuration includes a PanelView Plus terminal, install FactoryTalk
Machine Edition software and RSLinx Enterprise software from the FactoryTalk View Machine Edition package.
If you are using a DeviceNet network, install RSNetWorx for DeviceNet software. Also
install the DeviceNet Tag Generator Tool under optional steps of the RSNetWorx for DeviceNet install.

Additional Resources

Resource Description
CompactLogix Controller Installation Instructions 1768-IN004
Provides other methods for loading firmware in the controller.
FactoryTalk Activation FAQ, publication
FTalk-FA017
ControlFlash Firmware Upgrade Kit, publication
1756-QS105
Provides answers to FactoryTalk Activation questions, including how the FactoryTalk Activation differs from master disk activation.
Provides details regarding the installation of ControlFlash software and execution of firmware upgrades.
52 Publication IASIMP-QS003B-EN-P - October 2009
Chapter
Prepare the Distributed POINT I/O Hardware

Introduction

In this chapter, you install the 1734 POINT network adapter and the 1734 POINT I/O modules.

Before You Begin

Assemble your CompactLogix hardware (Chapter 1).
3
Determine which of these network adapters to use:
For an EtherNet/IP network (option 1), use the 1734-AENT adapter.For an DeviceNet network (option 2), use the 1734-ADN adapter.
Select the appropriate mounting base for the I/O modules:
For the 1734-IT2I module, use the 1734-TBCJC mounting baseFor all other modules, use the 1734-TB or 1734-TBS mounting base.

What You Need

POINT I/O adapter: 1734-AENT or 1734-ADN
POINT I/O mounting bases: 1734-TB or 1734-TBS, and 1734-TBCJC
A digital POINT I/O module. This example uses 1734-OB4E, however, other POINT
I/O modules can also be used but are not required.
1794-PS3 or 1794-PS13 power supply
DIN rail
Standard CAT5 Ethernet cable for EtherNet/IP system (option 1)
53Publication IASIMP-QS003B-EN-P - October 2009 53
Chapter 3 Prepare the Distributed POINT I/O Hardware
page 59
page 58
page 57
page 56
page 59
page 58
page 57
Mount and
Connect the
Network Adapter
Mount the POINT
I/O Modules
Mount and Wire
the POINT I/O Power Supply
Wire the Adapter
and I/O Modules to
the Power Supply
page 55
Mount and
Connect the
Network Adapter
Mount the POINT
I/O Modules
Mount and Wire
the POINT I/O Power Supply
Wire the Adapter
and I/O Modules to
the Power Supply
EtherNet/IP
DeviceNet
Distributed POINT I/O
Power Supply

Follow These Steps

If you have POINT I/O, complete the steps for your network.
DIRTY
L1 L2 L3 E
LINE
DIRTY
LOAD
L1 L2 L3 E
DIRTY
DIRTY
CLEAN
CLEAN
CLEAN
CD V4
2
rewoP
O
YLPPU
W
S RE
P
971
3SP-4
MOC
V42
CLEAN
54 Publication IASIMP-QS003B-EN-P - October 2009
Prepare the Distributed POINT I/O Hardware Chapter 3
00:00:BC:21:44:8A
Ethernet Address
p
E
t
h
e
r
n
e
t
A
d
d
r
e
s
s
Example Address

Mount and Connect the Network Adapter

1734-AENT EtherNet/IP Adapter for EtherNet/IP System
1. Locate the Ethernet Address (MAC) and the major revision on the POINT Adapter and record both in Appendix A. The address is used to set the IP address.
2. Set the address to a value greater than or equal to
256. This example uses 999.
3. Remove the protective cover from the right side of the adapter.
4. Press the adapter onto the DIN rail.
5. Connect an Ethernet cable between the Ethernet connector on the adapter and the Ethernet switch.
For EtherNet/IP systems, skip to page 57 Mount the Point I/O Modules.
,
Publication IASIMP-QS003B-EN-P - October 2009 55
Chapter 3 Prepare the Distributed POINT I/O Hardware
retpad
A
suta
t
S
teNeciveD
sutat
S
suBtnioP s
utat
S
NDA-4371
dleiF
rewoP
m e tsyS
rewoP
PowerFlex 70 Drive
with
20-COMM-D
KwikLink Sealed
Terminator
KwikLink Sealed
Terminator
KwikLink Sealed Micro Connector
1769-SDN
DeviceNet Module
1606-XLDNET8
Power Supply
1734-ADN DeviceNet Adapter for DeviceNet System
1. Remove the protective cover from the right side of the adapter.
2. Press the adapter onto the DIN rail.
3. Set the node address to 02 for this example.
4. Wire the KwikLink QD Micro Cordset to the 1734-ADN connector.
Connect To
Red V+ White CAN High Bare Shield Blue CAN Low Black V-
5. Connect the QD Micro Cordset to a KwikLink sealed micro connector on the DeviceNet network.
56 Publication IASIMP-QS003B-EN-P - October 2009

Mount the POINT I/O Modules

IMPORTANT
Wiring Base
Tongue-and-groove slots
Handle
Module
Required for EtherNet/IP and DeviceNet Systems
The 1734-IT21 must be mounted in the 1734-TBCJC wiring base. All other modules can be mounted in either the 1734-TB or 1734-TBS wiring bases.
1. Using a small, flathead screwdriver, rotate the keyswitch on the wiring base to 1.
Prepare the Distributed POINT I/O Hardware Chapter 3
This quick start uses the 1734-OB4E output module.
2. Press the module into the wiring base.
3. Snap the handle up.
4. Complete steps 1-3 with
all POINT I/O modules.
5. Slide the first module and wiring base assembly along the side of the adapter and press it onto DIN rail.
6. Repeat with all of the I/O assemblies.
2
3
1
4
8
7
1
5
6
Publication IASIMP-QS003B-EN-P - October 2009 57
Chapter 3 Prepare the Distributed POINT I/O Hardware
WARNING
Upper-lip of DIN rail latch
GR L2/N
L1
L2
L1
Optional LIM 230V AC
AUX Power Output Connector
Top View

Mount and Wire the POINT I/O Power Supply

1794-PS3 or 1794-PS13 Power Supply for EtherNet/IP and DeviceNet Systems
Verify that all incoming power is turned off before wiring power.
1. Hook the upper-lip of the power module onto the DIN rail.
2. Press the module onto the DIN rail.
3. Wire the POINT I/O power supply to the 230V AC Aux Power Output connector on the line interface module.
58 Publication IASIMP-QS003B-EN-P - October 2009
Prepare the Distributed POINT I/O Hardware Chapter 3
COM
24V

Wire the Adapter and I/O Modules to the Power Supply

Required for EtherNet/IP and DeviceNet Systems
1. Connect the 12/24V dc common and power wires from the power supply to the adapter.
Refer to the installation instructions for the 1734-AENT or 1734-ADN adapters.
2. Refer to the individual POINT I/O installation instructions for wiring the I/O modules.
3. Turn on incoming power.
Publication IASIMP-QS003B-EN-P - October 2009 59
Chapter 3 Prepare the Distributed POINT I/O Hardware

Additional Resources

Resource Description
POINT I/O EtherNet/IP Adapter Installation Instructions, publication 1734-IN590
POINT I/O DeviceNet Adapter Installation Instructions, publication 1734-IN026
POINT I/O Wiring Base Assembly Installation Instructions, publication 1734-IN511
POINT I/O Cold Junction Compensation Wiring Base Assembly Installation Instructions, publication 1734-IN583
POINT I/O Protected Output Module Installation Instructions, publication 1734-IN056
FLEX I/O DC Power Supply Module Installation Instructions, publication 1794-IN069
Point I/O Selection Guide, publication
1734-SG001
Provides details regarding installation of the adapter and technical specifications.
Provides details regarding installation of the adapter and technical specifications.
Provides details on how to install and remove the wiring base, and terminal block.
Provides details regarding installation of the Cold Junction Compensated Terminal Block wiring base.
Provides details on how to install, wire, communicate with, and troubleshoot the protected output module.
Provides details on how to mount and wire the power supply.
Provides details on selecting 1734 POINT I/O components.
60 Publication IASIMP-QS003B-EN-P - October 2009
Chapter
4
Prepare the PowerFlex 70 Drive

Introduction

In this chapter, you mount and wire power to a PowerFlex 70 drive. You also configure the communication adapter and make network connections.

Before You Begin

Assemble your CompactLogix hardware (Chapter 1).
Determine which network adapter to use on the PowerFlex 70 drive:
For an EtherNet/IP network (option 1), use the 20-COMM-E adapter.For a DeviceNet network (option 2), use the 20-COMM-D adapter.

What You Need

PowerFlex 70 drive
PowerFlex 70 communication adapter
20-COMM-E for an EtherNet/IP network (option 1)20-COMM-D for a DeviceNet network (option 2)
Standard CAT5 Ethernet cable for EtherNet/IP system (option 1)
61Publication IASIMP-QS003B-EN-P - October 2009 61
Chapter 4 Prepare the PowerFlex 70 Drive
page 65
page 65
DIRTY
DIRTY
CLEAN
CLEAN
CLEAN
DIRTY
CLEAN
DIRTY
L1 L2 L3 E
L1 L2 L3 E
LINE
LOAD
rewoP
CD V4
2
YLPPU
S RE
W
O
P
3SP-4
971
V42
MOC
page 67
page 63
Connect
Communication
Adapter to the
PowerFlex 70 Drive
Configure the
Communication
Adapter
Mount and Wire
the PowerFlex 70
Drive
page 66
page 63
Connect
Communication
Adapter to the
PowerFlex 70 Drive
Configure the
Communication
Adapter
Mount and Wire
the PowerFlex 70
Drive
EtherNet/IP
DeviceNet

Follow These Steps

If you have a PowerFlex 70 Drive, complete the steps for your network.
62 Publication IASIMP-QS003B-EN-P - October 2009

Mount and Wire the PowerFlex 70 Drive

WARNING
Required for EtherNet/IP and DeviceNet Systems
Verify that all incoming power is turned off before wiring power.
1. Mount the PowerFlex 70 drive to the control enclosure subpanel using the four mounting slots provided.
Prepare the PowerFlex 70 Drive Chapter 4
For mounting instructions, refer to the PowerFlex 70 User Manual, publication 20A-UM001.
2. Loosen the screw and remove the cover.
Publication IASIMP-QS003B-EN-P - October 2009 63
Chapter 4 Prepare the PowerFlex 70 Drive
L1RL2SL3TBR1
+DC
BR2
BRKT1UT2VT3W
PE PE
Optional LIM 240V AC
3-Phase Load Connector
Motor
fuse fuse fuse
Top View
3. Remove a knockout from the bottom plate on the drive for routing the power line conductors.
4. Wire the PowerFlex 70 240V AC, 3-phase line power terminals to the 240V AC, 3-phase Load connector on the line interface module. Fuse according to PowerFlex power rating.
5. Wire the PE Chassis ground terminal on the PowerFlex 70 to earth ground.
6. Connect the 240V 3-phase motor to the PowerFlex T1, T2, T3, PE terminals.
64 Publication IASIMP-QS003B-EN-P - October 2009

Configure the Communication Adapter

2
1
0
9
8
3
4
5
6
7
2
1
0
9
8
3
4
5
6
7
Tens Digit
Ones Digit
PGM
500K
250K
125K
AUTO
HW Address 00:00:BC:32:00:35
For example:
20-COMM-D DeviceNet Adapter for DeviceNet System
1. Set the node address on the adapter to 13 for this quick start.
2. Set the adapter to AUTO for autobaud.
Prepare the PowerFlex 70 Drive Chapter 4
20-COMM-E EtherNet/IP Adapter for EtherNet/IP System
Locate the Ethernet Address (MAC) on the label of the adapter and record this address in Appendix A
This address is used to set the IP address.
.
Publication IASIMP-QS003B-EN-P - October 2009 65
Chapter 4 Prepare the PowerFlex 70 Drive
POINT I/O with
1734-ADN Adapter
KwikLink Sealed
Terminator
KwikLink Sealed
Terminator
KwikLink Sealed Micro Connector
1606-XLDNET8
Power Supply
1769-SDN
DeviceNet Module

Connect Communication Adapter to the PowerFlex 70 Drive

20-COMM-D DeviceNet Adapter for DeviceNet System
1. Connect the flat-ribbon cable between the adapter and the PowerFlex 70 drive.
2. Fold the cable under adapter without creasing and secure adapter on drive using the captive screws.
3. Remove a knockout from
4. Wire the KwikLink QD
5. Connect the QD Micro
the bottom plate on the drive and route the DeviceNet network cable through the hole.
Micro Cordset to the 20-COMM-D connector.
Connect To
Red V+ White CAN High Bare Shield Blue CAN Low Black V-
Cordset to a KwikLink sealed micro connector on the DeviceNet network.
6. Replace drive cover.
66 Publication IASIMP-QS003B-EN-P - October 2009
20-COMM-E EtherNet/IP Adapter for EtherNet/IP System
1. Connect the flat-ribbon cable between the adapter and the PowerFlex 70 drive.
2. Fold the cable under the adapter without creasing and secure the adapter on the drive using the captive screws.
Prepare the PowerFlex 70 Drive Chapter 4
3. Remove a knockout from the bottom plate on the drive route the Ethernet cable through the hole.
4. Connect a CAT5 Ethernet cable between the Ethernet adapter and the Ethernet switch.
5. Replace drive cover.
Publication IASIMP-QS003B-EN-P - October 2009 67
Chapter 4 Prepare the PowerFlex 70 Drive

Additional Resources

Resource Description
PowerFlex 70 User Manual, publication
20A-UM001
PowerFlex 70 EtherNet/IP Adapter User Manual, publication 20COMM-UM010
PowerFlex 70 DeviceNet Adapter User Manual, publication 20COMM-UM002
Provides details on how to mount and wire power to the PowerFlex 70 drive. Also provides information on how to set drive parameters and troubleshoot the drive.
Provides details on how to install, configure, and use the adapter.
Provides details on how to install, configure, and use the adapter.
68 Publication IASIMP-QS003B-EN-P - October 2009
Chapter
5
Prepare the PanelView Plus Terminal

Introduction

In this chapter, you mount and wire the PanelView Plus terminal. You also configure network communication and make network connections.

Before You Begin

Assemble your CompactLogix hardware (Chapter 1).
Determine which network to use.
EtherNet/IP network (option 1) using Ethernet connectionDeviceNet network (option 2) using serial connection

What You Need

PanelView Plus terminal
Standard CAT5 Ethernet cable for Ethernet connection (option 1)
2711-NC13 cable for a serial connection
69Publication IASIMP-QS003B-EN-P - October 2009 69
Chapter 5 Prepare the PanelView Plus Terminal
page 72
page 71
page 73
page 72
page 71
Mount and Wire
the PanelView
Plus Terminal
Make Network
Connections for
PanelView Plus
Assign IP Address
for PanelView Plus
EtherNet/IP
Mount and Wire
the PanelView
Plus Terminal
Make Network
Connections for
PanelView Plus
DeviceNet

Follow These Steps

If you have a PanelView Plus terminal, complete the appropriate steps.
70 Publication IASIMP-QS003B-EN-P - October 2009
Prepare the PanelView Plus Terminal Chapter 5
WARNING
24V (+)
COM (-)
Line Interface Module I/O Power
Front View

Mount and Wire the PanelView Plus Terminal

Required for EtherNet/IP and DeviceNet Systems
For the purpose of this quick start, the PanelView Plus terminal can be propped on a desktop.
For complete mounting instructions, refer to the PanelView Plus Terminal user manual, publication 2711P-UM001
Verify that all incoming power is turned off before wiring power.
.
1. Mount the PanelView Plus to the control enclosure door using the mounting clips shipped with terminal.
2. Remove the terminal block from the PanelView Plus.
3. Connect the PanelView Plus power terminal block to the I/O power terminals on the front of the line interface module.
4. Re-attach the terminal block to the PanelView Plus terminal.
2
4
6
8
10
12
14
16
18
20
IO_PWR1
1
IO_COM1 IO_PWR1
3
IO_COM1 IO_PWR1
5
IO_COM1 COIL_E1
7
COIL_E2 ALRM_M
9
SHIELD ALRM_B
11
ALRM_COM CONSTAT_11
13
CONSTAT_12 CONSTAT_21
15
CONSTAT_22 CONSTAT_31
17
CONSTAT_32 CONSTAT_53
19
CONSTAT_54 SHIELD
21
-
IOL
+
1
2
Publication IASIMP-QS003B-EN-P - October 2009 71
Chapter 5 Prepare the PanelView Plus Terminal
CAT5 Ethernet Cable
2711-NC13

Make Network Connections for PanelView Plus

Network Connections Required for EtherNet/IP System
Connect a CAT5 Ethernet cable between the Ethernet port on the PanelView Plus terminal and the Ethernet switch.
Network Connections Required for DeviceNet System
Connect the 2711-NC13 cable between the serial port on the PanelView Plus terminal and the CH0 serial port of the L43 controller.
72 Publication IASIMP-QS003B-EN-P - October 2009

Assign IP Address for PanelView Plus

Networks and Communications
Network Connections
Network Adapters
Built-in Ethernet Controller
Diagnostics Setup Display File Management Font Linking Input Devices
Networks and Communications
Print Setup Startup Options System Event Log System Information Time/Date/Regional Settings
Required for EtherNet/IP System
1. Apply power to the PanelView terminal.
2. On the initial PanelView configuration screen, select Terminal Settings [F4].
3. Navigate to Built-in Ethernet Controller by selecting
Prepare the PanelView Plus Terminal Chapter 5
the path shown.
4. Select IP Address [F2].
Publication IASIMP-QS003B-EN-P - October 2009 73
Chapter 5 Prepare the PanelView Plus Terminal
5. Select Use DHCP [F4] to select No.
6. Select IP Address [F1]. a. Enter an IP address in
the input panel. b. Press Enter. c. Record IP address in
Appendix A. For information on IP
addresses, see page 89
.
7. Select Subnet Mask [F2].
a. Enter the subnet mask
for your computer,
recorded in Appendix
A.
b. Press Enter.
8. Select OK [F7] to save settings, then OK [F7] again to acknowledge reset message.
74 Publication IASIMP-QS003B-EN-P - October 2009
9. Select Close [F8] until you return to the initial configuration screen.
10. Select Reset [F8] to reset the terminal, then Yes [F7] to confirm.
Prepare the PanelView Plus Terminal Chapter 5

Upgrade Terminal Firmware

Required for Terminals with Firmware Earlier than 4.00.09
If the firmware in your PanelView Plus terminal is earlier than 4.00.09, you need to upgrade the terminal firmware. You can download the firmware from this website:
http://support.rockwellautomation.com/ControlFlash/FUW.asp
To update the terminal firmware, launch FactoryTalkView Machine Edition software and select Tools>Firmware Upgrade Wizard. Upgrade the firmware in the terminal by using the RSLinx Enterprise network connection.
Publication IASIMP-QS003B-EN-P - October 2009 75
Chapter 5 Prepare the PanelView Plus Terminal

Additional Resources

Resource Description
PanelView Plus Terminal User Manual, publication 2711P-UM001
PanelView Plus Grounding and Wiring Applications Technical Data, publication
2711P-TD001
Provides details on how to install communication modules, mount the PanelView Plus terminals, wire power to the terminals, make network connections, and configure terminal settings.
Provides comprehensive guidelines on how to properly ground and wire PanelView Plus terminals.
76 Publication IASIMP-QS003B-EN-P - October 2009
Chapter
6
Prepare the Kinetix 6000 Multi-axis Servo Drive System

Introduction

In this chapter, you prepare your Kinetix 6000 Multi-axis Servo Drive system.

Before You Begin

Assemble your CompactLogix Hardware (Chapter 1)
Review Basic System Components (Preface
)

What You Need

Input Power: Line Interface Module (optional), line filter
Kinetix 6000 Multi-axis Servo Drive System: power rail, Axis and Integrated Axis
Modules
Motors
Cables: motor power, motor feedback, SERCOS fiber optic cables, connector kit
77Publication IASIMP-QS003B-EN-P - October 2009 77
Chapter 6 Prepare the Kinetix 6000 Multi-axis Servo Drive System
page 80
page 83
page 82
page 79
Mount and Bond
the Power Rail
page 80
Mount the
Integrated Axis and
Axis Module
Wire Power to the
Integrated Axis
Module
Wire Servo Motors
to Integrated Axis and Axis Modules
page 84
Connect the
SERCOS Fiber
Optic Cables
Set the SERCOS
Node Address
page 85
Line Interface
Module
AC Line
Filter

Follow These Steps

If you have a Kinetix 6000 Multi-axis Servo Drive System, complete these steps.
DIRTY
L1 L2 L3 E
LINE
CLEAN
LOAD
L1 L2 L3 E
DIRTY
CLEAN
DIRTY
DIRTY
CLEAN
CD V4
2
rewoP
O
YLPPU
W
S RE
P
971
3SP-4
MOC
V42
CLEAN
78 Publication IASIMP-QS003B-EN-P - October 2009
Prepare the Kinetix 6000 Multi-axis Servo Drive System Chapter 6
Boot
Ground Stud with Braided Ground Strap
Bonded Cabinet Ground

Mount and Bond the Power Rail

2094-PRS1 through 2094-PRS8
The Kinetix power rails support one integrated axis module (IAM), and up to seven axis modules (AM), or shunt modules (SM). The connector pins for each slot on the power rail are covered by a protective boot. Do not remove the protective boot until you install the modules.
1. Layout the position for your power rail in the enclosure.
2. Attach the power rail to the cabinet using M6 (1/4 in.) bolts, making sure the power rail is properly bonded to the cabinet.
3. Bond the power rail to the enclosure subpanel using the ground strap provided.
4. Tighten all mounting fasteners.
Publication IASIMP-QS003B-EN-P - October 2009 79
Chapter 6 Prepare the Kinetix 6000 Multi-axis Servo Drive System
Guide Pin
Guide Pin Holes
Power Rail
Typical Rear View of IAM or AM Module

Mount the Integrated Axis and Axis Module

2094-AC09-M02, 2094-AM01
The integrated axis module (IAM) mounts in the two leftmost slots of the power rail. The axis modules (AM) mount to the right of the IAM module in left-to-right order, ranging from highest-to-lowest power rating. This quick start uses one integrated axis module and one axis module. Slot filler modules fill the remaining empty slots on the power rail. If your application includes a shunt module, it would mount to the right of the axis modules.
1. Remove the protective boot covering the two leftmost slots on the power rail.
2. Remove the label from the IAM module (2094-AC09-M02) that is covering the power connector pins.
3. Hang the mounting bracket from the slots on the power rail.
4. Pivot the IAM module downward, aligning the guide pins on the power rail with the guide pin holes on the back of the module.
5. Gently push the module against the power rail.
80 Publication IASIMP-QS003B-EN-P - October 2009
6. Use 2.26 Nm (20 lb•in)
Mounting Screws on IAM and AM modules.
torque to tighten the mounting screws.
7. Remove the protective boot from the power rail slot to the right of the IAM module.
Prepare the Kinetix 6000 Multi-axis Servo Drive System Chapter 6
8. Repeat steps 2 through 6 to mount the AM module in the power rail slot to the right of the IAM module.
9. Repeat steps 2 through 6 to mount slot filler modules in all remaining, empty power slots.
Publication IASIMP-QS003B-EN-P - October 2009 81
Chapter 6 Prepare the Kinetix 6000 Multi-axis Servo Drive System
Line Interface Module
AC RFI Line Filter
E-Stop
Top View
Integrated Axis Module
Front View
Top View
5
1
2
5
4
3
Incoming Power

Wire Power to the Integrated Axis Module

This procedure shows power connections to the integrated axis module (IAM) when using the line interface module (LIM). The AC conductor sizes are based on the motor load requirements.
2094-AC09-M02
1. Wire the LIM module
2. Wire the AC line filter
3. Wire the 230V control
load terminals to the AC line filter, line terminals.
load terminals to the IAM line terminals.
power from the LIM to the IAM module.
L3 L2 L1
L3
L2
L1
195-265 VAC LINE, 50/60 Hz
L3'
L2'
L1'
195-265 VAC LOAD, 50/60 Hz
1 2 3 4
1 2 3 4
CL2 CL1
IOL
IO_PWR1
1
2
IO_COM1
CONTROL VAC
IO_PWR1
CTRL2
1 2
CTRL1
AUX2
AUX2
AUX1
AUX1
1 2 3 4
I/O_COM I/O_PWR I/O_COM I/O_PWR I/O_COM I/O_PWR
1 2 3 4 5 6
3
4
IO_COM1 IO_PWR1
5
6
IO_COM1
230 VAC SUPPLY
COIL_E1
7
8
COIL_E2 ALRM_M
9
10
SHIELD ALRM_B
11
12
ALRM_COM
24 VDC SUPPLY
CONSTAT_11
13
14
CONSTAT_12 CONSTAT_21
15
16
CONSTAT_22 CONSTAT_31
17
18
CONSTAT_32 CONSTAT_53
19
20
CONSTAT_54 SHIELD
21
6 8
1
7
4. Wire the E1 safety coil on the LIM module to the E-stop button.
5. Wire the E2 safety coil on LIM module to the CONT EN contacts on the IAM module.
L1 L2 L3 E
LINE
LOAD
L1 L2 L3 E
1 2
CTRL 2 CTRL 1
1 2 3 4 5 6
DC­DC+
L3 L2 L1
1 2
CONT EN­CONT EN+
1 2 3 4 5 6 7 8 9
RX
DPI
MBRK ­MBRK +
DBRK ­DBRK +
W
V
1 2 3 4
U
COM PWR
1 2 3 4 5 6
TX
BAUD RATE
82 Publication IASIMP-QS003B-EN-P - October 2009
Prepare the Kinetix 6000 Multi-axis Servo Drive System Chapter 6
U-Brown
V-Black
W-Blue
Green/Yellow
BAUD RATE
TX
RX
DPI
DC­DC+
L3 L2 L1
CONT EN­CONT EN+
CTRL 2 CTRL 1
W V U
MBRK -
MBRK +
COM
PWR
DBRK -
DBRK +
1 2 3 4
MP
MF
Top View
Front View
Integrated Axis Module or Axis Module
MPL Motor
Motor Feedback Cable 2090-UXNFBMP-S03
Motor Power Cable
2090-XXNPMP-16S03
1
2
3

Wire Servo Motors to Integrated Axis and Axis Modules

2094-AC09-M02, 2094-AM01, MPL-A310P-MK22AA, 2090-XXNPMP-16S03, 2090-UXNFBMP-S03
1. Attach motor power cable to shield clamp.
a. Use a small flatblade
screwdriver to depress the spring loaded clamp plate.
Cable
Tie Wrap
b. Position the exposed
braid of the motor power cable in line with the clamp.
c. Release the spring,
making sure the cable and braid are secured by clamp.
d. Attach the tie wrap
around cable and clamp if you need more strain relief.
2. Connect the motor power cable between the Motor Power (MP) Connector on the IAM or AM module and the power
Cable Clamp
Exposed Braid under Clamp
connector on the motor.
3. Connect the feedback cable between the Motor Feedback (MF) connector on the IAM or AM module and the feedback connector on the motor.
4. Repeat steps 1 through 3 for all servo motors and AM modules.
Publication IASIMP-QS003B-EN-P - October 2009 83
Chapter 6 Prepare the Kinetix 6000 Multi-axis Servo Drive System
SERCOS Interface Module
SERCOS Interface Module, 1768-M04SE

Connect the SERCOS Fiber Optic Cables

2090-SCEP0-1, 2090-SCEP0-9
1. Connect the 2090-SCEP0-9 fiber optic cable between the TX port on the bottom of the SERCOS module and the RX port on the IAM module, making sure to tighten the fiber optic ring on each end.
2. Connect the 2090-SCEP0-9 fiber optic cable between the RX port on the bottom of the SERCOS module and the TX port on the AM module, making sure to tighten the fiber optic ring on each end.
3. Connect the 2090-SCEP0-1 fiber optic cable between the TX port on the IAM module
SERVO
Interface
b
a
c
2090-SCEP0-9
31604-M
TX
RX
SERCOS FIBER-OPTIC RING
2090-SCEP0-1
2090-SCEP0-9
TXRXTXRX
and the RX port on the AM module, making sure to tighten the fiber optic ring on each end.
84 Publication IASIMP-QS003B-EN-P - October 2009
AXIS 0 AXIS 1
KINETIX 2 AXIS MOTION
NODE 03NODE 01

Set the SERCOS Node Address

1
0
1. Set the SERCOS node address on the front of the Integrated Axis Module to 01.
Prepare the Kinetix 6000 Multi-axis Servo Drive System Chapter 6
2. Record this address in
Appendix A
.
Publication IASIMP-QS003B-EN-P - October 2009 85
Chapter 6 Prepare the Kinetix 6000 Multi-axis Servo Drive System

Additional Resources

Resource Description
Kinetix Motion Control Selection Guide, publication GMC-SG001
Kinetix 6000 Multi-Axis Servo Drive Installation Manual, publication 2094-IN001
Kinetix 6000 Multi-Axis Servo Drive User Manual, publication 2094-UM001
Line Interface Module installation Instructions, publication 2094-IN005
System Design for Control of Electrical Noise, publication GMC-RM001
Kinetix Accelerator Toolkit Quick Start, publication IASIMP-QS002
Logix5000 Motion Modules User Manual, publication LOGIX-UM002
System Design for Control of Electrical Noise Video, publication GMC-SP004
Kinetix Accelerator Toolkit CD, IASIMP-SP004
Provides details on motor and drive performance specifications.
Provides details on panel layout, and how to install and wire Kinetix 6000 drives and components.
Provides details on how to integrate your Kinetix 6000 system with a CompactLogix 2094-M04SE SERCOS module, including how to start up, configure, and troubleshoot the system.
Provides details on how to install, wire, and troubleshoot the line interface module.
Provides best practices on how to minimize noise in control panel while complying with noise regulations.
Provides complete details and tools to help you quickly integrate a Kinetix Motion system into your ControlLogix system.
Provides details on how to setup and configure motion control using your 1768 SERCOS module.
Contact your local distributor for details on how obtain publication.
Contact your local distributor for details on how to obtain CD. See appendix B for more information.
86 Publication IASIMP-QS003B-EN-P - October 2009
Configure the EtherNet/IP Network
TIP

Introduction

In this chapter, you assign IP addresses to devices on the EtherNet/IP network.

Before You Begin

Assemble your CompactLogix hardware (Chapter 1).
Chapter
7
Prepare your computer (Chapter 2
Devices on the EtherNet/IP network broadcast requests for IP addresses until the IP addresses have been assigned.
The procedure in this chapter uses the BOOTP Server packaged with RSLogix 5000 software to assign IP addresses, however, any industry-standard BOOTP server will work.
Install all your hardware (Chapter 4
– If you connect all devices, including the computer through an Ethernet switch, you
can create an isolated network. This chapter assumes you are using an isolated network.
– If using a non-isolated network, contact your network administrator to obtain IP
addresses.
Verify that power is applied to all devices.
).
through 6).

What You Need

Network Interface Card (NIC) and its associated Windows driver installed on your
computer. The NIC and driver are standard on most computers.
BOOTP/DHCP utility from the RSLogix 5000 software CD.
Ethernet Address (MAC) for each device that you recorded in Appendix A
IP Address for each device, except the PanelView Plus terminal.
– For an isolated network, determine a numbering convention for your IP addresses.
Record these addresses in the Ethernet Addresses table in Appendix A
– For a non-isolated network, obtain IP addresses from your network administrator.
87Publication IASIMP-QS003B-EN-P - October 2009 87
.
.
Chapter 7 Configure the EtherNet/IP Network
page 89
Browse the EtherNet/IP
Network in RSLinx
Classic Software
Assign IP
Addresses
page 91

Follow These Steps

If you have an EtherNet/IP network, complete these steps.

Terminology

Ethernet networks use these types of addresses.
Term Definition
Ethernet address
Each Ethernet device has a unique Ethernet address, sometimes called a MAC address. The address is usually on a label on the device itself. You use the Ethernet address to identify a device so you can assign it an IP address.
The address has twelve digits separated by colons, xx:xx:xx:xx:xx:xx. Each digit in the address is a hexadecimal number from 0 to 9, or A to F. No other device will have the same address, and it can not be changed by the user.
IP address
The IP address identifies a node on an Ethernet network. You can manually set the IP address or you can use special software to automatically assign it.
An IP address consists of four decimal integers separated by periods, xxx.xxx.xxx.xxx. Each xxx is a decimal value from 0…255. An example IP address is 192.168.0.1. The selection of IP addresses is beyond the scope of this quick start. Contact your network administrator or use the ones provided in the examples.
Once you set an IP address for a device, you generally reference the device by its IP address. The examples in this quick start use IP addresses to define communication paths to the devices.
88 Publication IASIMP-QS003B-EN-P - October 2009
Configure the EtherNet/IP Network Chapter 7

Assign IP Addresses

The BOOTP/DHCP Server utility is used to assign IP addresses to most devices in this quick start, except the PanelView Plus terminal. The IP address for the PanelView Plus device was assigned during installation in Chapter 5 BOOTP/DHCP utility is installed during the RSLogix 5000 programming software installation.
1. Launch BOOTP/DHCP Server utility.
If running this utility for the first time, you will get a Network Setup Error message. Click OK. You
, Prepare the PanelView Plus terminal. The
are then asked to enter the subnet mask in step 3.
2. Otherwise, select Tools>Network Settings.
3. Enter the Subnet Mask recorded in Appendix A for your computer.
4. Click OK.
Publication IASIMP-QS003B-EN-P - October 2009 89
Chapter 7 Configure the EtherNet/IP Network
The Request History displays all devices in your network that need IP addresses.
The Ethernet (MAC) addresses correspond to the addresses entered in
Appendix A
.
5. Double-click a request from one of the devices.
6. Enter the IP address that you recorded in
Appendix A
and click
OK. If you are not on an
isolated network, obtain IP addresses from your network administrator.
7. Repeat steps 5 - 6 for each device, except the PanelView Plus terminal.
If a device is power cycled, it will not retain its IP address unless you disable BOOTP/DHCP.
8. Select the first device in the Relation List and click Disable BOOTP/DHCP.
90 Publication IASIMP-QS003B-EN-P - October 2009
Configure the EtherNet/IP Network Chapter 7
9. Repeat step 8 for all devices except the PanelView Plus terminal.
10. Close the BOOTP/DHCP utility.
If prompted to save changes, click No.

Browse the EtherNet/IP Network in RSLinx Classic Software

Click the RSWho button to view the EtherNet/IP driver and devices.
Publication IASIMP-QS003B-EN-P - October 2009 91
Chapter 7 Configure the EtherNet/IP Network

Additional Resources

Resource Description
EtherNet/IP Modules in Logix 5000 Control Systems User Manual, publication ENET-UM001
Tech Note # E47839422 available at:
Provides details on how to configure and use EtherNet/IP modules in Logix 5000 systems including how to assign IP addresses to devices and browse the EtherNet/IP
network in RSLinx software.
(1)
Provides a description of the common Comms error dialog box and its solution.
http://rockwellautomation.com/knowledgebase
(1)
If you are connecting to the AB_ETHIP driver using a VPN connection with a firewall, refer to the Knowledgebase tech note E47839422.
92 Publication IASIMP-QS003B-EN-P - October 2009
Chapter
8
Configure the DeviceNet Network

Introduction

In this chapter, you configure the DeviceNet node address for the 1769-SDN module. You also create the RSNetWorx for DeviceNet file that stores the network configuration.

Before You Begin

Install all hardware, including the DeviceNet Scanner (Chapter 1 through 6).
Prepare the computer (Chapter 2
Connect devices to the DeviceNet network (option 1).
POINT I/O 1734-ADN DeviceNet adapter (Chapter 3PowerFlex 70 drive with 20-COMM-D adapter (Chapter 4
Verify that power is applied to all devices.
).

What You Need

RSNetWorx for DeviceNet software
)
)
93Publication IASIMP-QS003B-EN-P - October 2009 93
Chapter 8 Configure the DeviceNet Network
page 97
page 94
Set the Node
Address of the
DeviceNet Scanner
Apply Power to
the DeviceNet
Network
Create a
DeviceNet
Configuration File
page 95

Follow These Steps

If you have a DeviceNet network, complete these steps.

Apply Power to the DeviceNet Network

Turn on incoming power to the DeviceNet network.
94 Publication IASIMP-QS003B-EN-P - October 2009

Set the Node Address of the DeviceNet Scanner

1. Launch RSNetWorx for DeviceNet software.
2. Select Tools>Node Commissioning.
3. Click Browse.
Configure the DeviceNet Network Chapter 8
4. Under AB_DF1-1, expand the CompactLogix Backplane and the 1769 CompactBus.
5. Expand the 1769-SDN Scanner Module and the DeviceNet Port, then select 1769-SDN Scanner Module.
6. Click OK.
Publication IASIMP-QS003B-EN-P - October 2009 95
Chapter 8 Configure the DeviceNet Network
7. If you receive a linking device warning, click Yes.
The Node Commissioning dialog box is populated with the current settings for the 1769-SDN module.
8. Select an available node Address for the 1769-SDN module and click Apply.
This example uses node address 1.
The node address is applied and a confirmation is given in the Messages box.
9. Record the address in
Appendix A
.
10. Click Close.
96 Publication IASIMP-QS003B-EN-P - October 2009

Create a DeviceNet Configuration File

node 1
slot1
1. Select File>New.
2. Click the Who Active
button to go online.
3. Under AB_DF-1, expand the 1768-L43 Backplane and the 1769 CompactBus.
Configure the DeviceNet Network Chapter 8
4. Expand the 1769-SDN Scanner Module and select the DeviceNet port, then click OK.
5. Record the slot number of the 1769-SDN module in Appendix A
.
In this example, the 1769-SDN is in slot 1 of the 1769 Bus and node 1 of the DeviceNet network.
Publication IASIMP-QS003B-EN-P - October 2009 97
Chapter 8 Configure the DeviceNet Network
6. Click OK. RSNetWorx begins
browsing the network.
When all of the devices on your DeviceNet network have appeared on the screen, click Cancel.
If your PowerFlex drive does not display, see Uploading an EDS File From a Drive, Knowledgebase ID
20539.
7. Right-click the 1769-SDN and select Properties.
8. Select the Module tab.
9. Click Download.
This clears the configuration from the 1769-SDN module, synching the software with the device.
98 Publication IASIMP-QS003B-EN-P - October 2009
10. In the Platform field, select CompactLogix.
11. Select the Slot number, recorded in Appendix A and click OK.
Configure the DeviceNet Network Chapter 8
12. Save the DeviceNet configuration file.
13. Record the .dnt file name and path in Appendix A
.
14. Close the RSNetWorx for DeviceNet software.
Publication IASIMP-QS003B-EN-P - October 2009 99
Chapter 8 Configure the DeviceNet Network

Additional Resources

Resource Description
DeviceNet Modules in Logix5000 Control Systems User Manual, publication DNET-UM004
Uploading an EDS File From a Drive, Knowledgebase ID 20539,
http://rockwellautomation.com/knowledgebase
Provides details on the installation, configuration, and operation of DeviceNet modules.
Provides an explanation about uploading EDS files from drives.
100 Publication IASIMP-QS003B-EN-P - October 2009
Loading...