Panasonic S-26PU1U6, U-26PE1U6 service manual

0 (0)
Panasonic S-26PU1U6, U-26PE1U6 service manual

Order No. SM830203-11CE

TECHNICAL DATA & SERVICE MANUAL

Indoor Unit

Outdoor Unit

 

Model No.

Shows S-26PU1U6

 

 

 

Shows U-26PE1U6

 

 

 

 

 

 

 

 

 

Outdoor Units

 

Nominal Capacity

 

 

 

Type

 

Outdoor Units

26

 

36

42

Remarks

 

 

 

 

 

 

U-26PE1U6

 

U-36PE1U6

U-42PE1U6

Cooling/Heating

 

 

U

 

Single

 

 

 

 

 

 

 

 

 

 

U-26PS1U6

 

U-36PS1U6

U-42PS1U6

Cooling

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor Units

 

 

Nominal Capacity

 

 

 

Type

 

Indoor Units Type

26

 

36

42

Remarks

 

 

U1

 

4-Way Cassette

 

S-26PU1U6

 

S-36PU1U6

S-42PU1U6

with Wired Remote Controller: CZ-RTC2

 

 

 

 

 

 

 

 

 

 

 

 

 

K1

 

Wall Mounted

 

S-26PK1U6

 

 

 

with Wireless Remote Controller: CZ-RWSK1U

 

 

 

 

 

 

 

 

 

 

 

 

 

T1

 

Ceiling

 

S-26PT1U6

 

S-36PT1U6

S-42PT1U6

with Wired Remote Controller: CZ-RTC2

 

 

 

 

 

 

 

 

 

 

 

 

F1

 

Low Silhouette Ducted

S-26PF1U6

 

S-36PF1U6

 

with Wired Remote Controller: CZ-RTC2

 

 

 

 

 

 

 

 

 

 

 

 

 

F2

 

Concealed Duct

 

S-26PF2U6

 

S-36PF2U6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

U2

 

4-Way Cassette 36” × 36”

S-26PU2U6

 

S-36PU2U6

S-42PU2U6

 

 

 

 

(CZ-36KPU3U)*

(CZ-36KPU3U)*

(CZ-36KPU3U)*

 

 

 

K2

 

Wall Mounted

 

S-26PK2U6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T2

 

Ceiling

 

S-26PT2U6

 

S-36PT2U6

S-42PT2U6

 

 

 

 

 

 

 

 

 

 

 

 

* Panel (optional parts)

 

 

 

 

 

 

 

85464849303004

 

 

 

 

 

REFERENCE NO. SM830203-04

IMPORTANT!

Please Read Before Starting

This air conditioning system meets strict safety and operating standards. As the installer or service person, it is an important part of your job to install or service the system so it operates safely and efficiently.

For safe installation and trouble-free operation, you must:

Carefully read this instruction booklet before beginning.

Follow each installation or repair step exactly as shown.

This air conditioner shall be installed in accordance with National Wiring Regulations.

Pay close attention to all warning and caution notices given in this manual.

This symbol refers to a hazard or WARNING unsafe practice which can result in severe personal injury or death.

This symbol refers to a hazard or

CAUTION

unsafe practice which can result in personal injury or product or property damage.

If Necessary, Get Help

These instructions are all you need for most installation sites and maintenance conditions. If you require help for a special problem, contact our sales/service outlet or your certified dealer for additional instructions.

In Case of Improper Installation

The manufacturer shall in no way be responsible for improper installation or maintenance service, including failure to follow the instructions in this document.

SPECIAL PRECAUTIONS

WARNING When Wiring

ELECTRICAL SHOCK CAN CAUSE

SEVERE PERSONAL INJURY OR DEATH.

ONLY A QUALIFIED, EXPERIENCED

ELECTRICIAN SHOULD ATTEMPT TO

WIRE THIS SYSTEM.

= Do not supply power to the unit until all wiring and tubing are completed or reconnected and checked.

= Highly dangerous electrical voltages are used in this system. Carefully refer to the wiring diagram and these instructions when wiring. Improper connections and inadequate grounding can cause accidental injury or death.

= Ground the unit following local electrical codes.

= Connect all wiring tightly. Loose wiring may cause overheating at connection points and a possible fire hazard.

= To prevent possible hazards from insulation failure, the unit must be grounded. = This equipment is strongly recommended to be installed with Earth Leakage Circuit Breaker (ELCB) or Residual Current Device (RCD). Otherwise, it may cause electrical

shock and fire in case of equipment breakdown or insulation breakdown.

When Transporting

Be careful when picking up and moving the indoor and outdoor units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin aluminum fins on the air conditioner can cut your fingers.

When Installing…

Select an installation location which is rigid and strong enough to support or hold the unit, and select a location for easy maintenance.

…In a Room

Properly insulate any tubing run inside a room to prevent “sweating” that can cause dripping and water damage to walls and fl oors.

Keep the fire alarm and the air

CAUTION outlet at least 5 feet (1.5 m) away from the unit.

…In Moist or Uneven Locations

Use a raised concrete pad or concrete blocks to provide a solid, level foundation for the outdoor unit. This prevents water damage and abnormal vibration.

…In an Area with High Winds

Securely anchor the outdoor unit down with bolts and a metal frame. Provide a suitable air baffl e.

…In a Snowy Area (for Heat Pump-type Systems)

Install the outdoor unit on a raised platform that is higher than drifting snow. Provide snow vents.

When Connecting Refrigerant Tubing

= 8 / 13("4+ 1 33$-3(.- 3. 1$%1(&$1 -3 +$ * &$2.

= Ventilate the room immediately, in the event that is refrigerant gas leaks during the installation. Be careful not to allow contact of the refrigerant gas with a fl ame as this will cause the generation of toxic gas.

= Keep all tubing runs as short as possible.

= Apply refrigerant lubricant to the matching surfaces of the fl are and union tubes before connecting them, then tighten the nut with a torque wrench for a leak-free connection.

= Check carefully for leaks before starting the test run.

WARNING

=When performing piping work, do not mix air except for specified refrigerant (R410A) in refrigeration cycle. It causes capacity down, and risk of explosion and injury due to high tension inside the refrigerant cycle.

=If the refrigerant comes in contact with a flame, it produces a toxic gas.

=Do not add or replace refrigerant other than specified type. It may cause product damage, burst and injury etc.

i

8 Do not leak refrigerant while piping work for an installation or re-installation, and while repairing refrigeration parts.

Handle liquid refrigerant carefully as it may cause frostbite.

#'

8 Turn the power OFF at the main power bo4)%*/ before opening the unit to check or repair electrical

parts and wiring.

8 Keep your fi ngers and clothing away from any moving parts.

8 (!* 1, 0$!/%0!"0!.5ou fi nish, remembering to check that no metal scraps or bits of wiring have been left inside the unit.

W

8 This product must not be modifi ed or disassembled under any circumstances. Modifi ed or disassembled unit may cause fi re, electric shock or injury.

8 Do not clean inside the indoor and outdoor units by users. Engage authorized dealer or specialist for cleaning.

8 In case of malfunction of this appliance, do not repair by yourself. +*0 0 0+0$!/ (!/ !(!. +. service dealer for a repair.

CAUTION

8 Do not touch the air inlet or the sharp aluminum fi ns of the outdoor unit.You may get injured.

8 entilate any enclosed areas when installing or testing the refrigeration system. Leaked refrigerant gas, on contact with fi re or heat, can produce dangerously to4%#/.

8 +*fi rm after installation that no refrigerant gas is leaking. If the gas comes in contact with a burning stove, gas water heater, electric room heater or other heat source, it can cause the

#!*!.0%+* +"0+4%#s.

% #$

W

8 Do not sit or step on the unit, you may fall down accidentally.

CAUTION

8 Do not touch the air inlet or the sharp aluminum fi ns of the outdoor unit. You may get injured.

8 Do not stick any object into the FAN

You may be injured and the unit may be damaged.

NOTICE *$' !$( % ! #% % &$

Operation is subject to the following two conditions:

(1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.

*$"& ! %$%$% & % ! ) ( % % %$ #$$% ' !$& % % ! #% % &$

These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:

8!+.%!*0+. .!(+0! 0$!.! !%2%*#*0!** 8 * .!/! 0$!/!,.0%+*!03!!*0$! !-1%,)!*0* .! !%2!.

8 +**! 0 0$! !-1%,)!*0%*0+ * +10(!0+* %. 1%0 %""!.!*0".+) 0$0 0+ 3$% $0$!.! !%2!. %/ +**! 0! 8 +*/1(0 0$! !(!. +. *!4,!.%!*! . %+0!$*% % * "+. $!(,

8 10%+* + //1.!+*0%*1! +),(% *!"+((+30$! 00$! %*/0((0%+* %*/0.10%+*/*5$ *#!/ +.)+ %"%0%+*/ *+0 !4,.!//(5 ,,.+2! 5 0$! ,.05.!/,+*/% (!"+. +),(% *!+1( void the user’s authority to operate this equipment.

ii

Check of Density Limit

The room in which the air conditioner is to be installed requires a design that in the event of refrigerant gas leaking out, its density will not exceed a set limit.

The refrigerant (R410A), which is used in the air conditioner, is safe, without the toxicity or combustibility of ammonia, and is not restricted by laws imposed to protect the ozone layer. However, since it contains more than air, it poses the risk of suffocation if its density should rise excessively. Suffocation from leakage of refrigerant is almost non-existent. With the recent increase in the number of high density buildings, however, the installation of multi air conditioner systems is on the increase because of the need for effective use of floor space, individual control, energy conservation by curtailing heat and carrying power, etc.

Most importantly, the multi air conditioner system is able to replenish a large amount of refrigerant compared to conventional individual air conditioners. If a single unit of

the multi air conditioner system is to be installed in a small room, select a suitable model and installation procedure so that if the refrigerant accidentally leaks out, its density does not reach the limit (and in the event of an emergency, measures can be made before injury can occur).

ASHRAE and the International Mechanical Code of the ICC as well as CSA provide guidance and define safeguards related to the use of refrigerants, all of which define a Refrigerant Concentration Level (RCL) of 25 pounds per 1,000 cubic feet for R410A refrigerant.

For additional guidance and precautions related to refrigerant safety, please refer to the following documents:

International Mechanical Code 2012 (IMC-2012) (or more recently revised)

ASHRAE 15

ASHRAE 34

Precautions for Installation Using New Refrigerant

1. Care regarding tubing

1-1. Process tubing

Material: Use C1220 phosphorous deoxidized copper specified in JIS H3300 “Copper and Copper Alloy Seamless Pipes and Tubes.”

Tubing size: Be sure to use the sizes indicated in the table below.

Use a tube cutter when cutting the tubing, and be sure to remove any flash. This also applies to distribution joints (optional).

When bending tubing ø5/8" or smaller, use a bending radius that is 4 times the outer diameter of the tubing or larger.

Use sufficient care in handling the tubing. Seal the tubing ends with CAUTION caps or tape to prevent dirt, moisture, or other foreign substances

from entering. These substances can result in system malfunction.

 

 

 

 

 

 

Unit: inch

Material

 

 

O

 

Copper tube

Outer diameter

1/4

3/8

 

1/2

5/8

Wall thickness

t0.032

t0.032

 

t0.032

t0.04

 

 

1-2. Prevent impurities including water, dust and oxide from entering the tubing. Impurities can cause R410A refrigerant deterioration and compressor defects. Due to the features of the refrigerant and refrigerating machine oil, the prevention of water and other impurities becomes more important than ever.

2. Be sure to recharge the refrigerant only in liquid form.

2-1. Since R410A is a non-azeotrope, recharging the refrigerant in gas form can lower performance and cause defects of the unit.

2-2. Since refrigerant composition changes and performance decreases when gas leaks, collect the remaining refrigerant and recharge the required total amount of new refrigerant after fixing the leak.

iii

3. Different tools required

3-1. Tool specifications have been changed due to the characteristics of R410A. Some tools for R22and R407C-type refrigerant systems cannot be used.

 

New

R407C tools

 

Item

tool?

compatible

Remarks

 

 

with R410A?

 

Manifold gauge

Yes

No

Types of refrigerant, refrigerating machine oil, and

 

 

 

pressure gauge are different.

Charge hose

Yes

No

To resist higher pressure, material must be changed.

Vacuum pump

Yes

Yes

Use a conventional vacuum pump if it is equipped

 

 

 

with a check valve. If it has no check valve,

 

 

 

purchase and attach a vacuum pump adapter.

Leak detector

Yes

No

Leak detectors for CFC and HCFC that

 

 

 

react to chlorine do not function because

 

 

 

R410A contains no chlorine. Leak detector

 

 

 

for HFC134a can be used for R410A.

Flaring oil

Yes

No

For systems that use R22, apply mineral oil (Suniso oil)

 

 

 

to the flare nuts on the tubing to prevent refrigerant

 

 

 

leakage. For machines that use R407C or R410A, apply

 

 

 

synthetic oil (ether oil) to the flare nuts.

* Using tools for R22 and R407C and new tools for R410A together can cause defects.

3-2. Use R410A exclusive cylinder only.

Manifold gauge

Vacuum pump

Outlet

Inlet

When charging with a refrigerant cylinder, use an electronic scale for charging refrigerant.

In this case, if the volume of refrigerant in the cylinder becomes less than 20% of the fully-charged amount, the composition of the refrigerant starts to change.

Thus, do not use the refrigerant if the amount in the charging cylinder is less than 20%.

Also, charge the minimum necessary amount to the charging cylinder before using it to charge the air conditioning unit.

Configuration and characteristics of cylinders

Valve

Valve

 

Liquid

Liquid

 

Single valve

 

 

Charge liquid refrigerant with

 

Single valve (with siphon tube)

cylinder in up-side-down position.

Fig. 1

Charge with cylinder in normal position. Fig. 2

iv

Contents

Section 1: SPECIFICATIONS.....................................................................................................

1-1

1-1. Unit Specifications ..............................................................................................

1-2

1-2. Major Component Specifications ......................................................................

1-29

1-3. Other Component Specifications ......................................................................

1-53

1-4. Dimensional Data..............................................................................................

1-56

1-5. Refrigerant Flow Diagram .................................................................................

1-70

1-6.

Operating Range...............................................................................................

1-71

1-7.

Capacity Correction Graph According to Temperature Condition .....................

1-72

1-8.

Noise Criterion Curves......................................................................................

1-73

1-9.

Increasing the Fan Speed .................................................................................

1-82

1-10. External Static Pressure Setting......................................................................

1-83

1-11. Air Throw Distance Chart ................................................................................

1-89

1-12. ELECTRICAL WIRING ....................................................................................

1-97

1-13. Installation Instructions ..................................................................................

1-100

Section 2: PROCESSES AND FUNCTIONS..............................................................................

2-1

2-1. Room Temperature Control.................................................................................

2-2

2-2. Cold Draft Prevention (Heating Cycle) ................................................................

2-4

2-3.

Automatic Fan Speed (Indoor Unit).....................................................................

2-5

2-4.

Control Functions................................................................................................

2-6

2-5.

Outdoor Unit Control PCB...................................................................................

2-9

2-6.

Outdoor Unit Control PCB (CR-CH4272R) .......................................................

2-10

Section 3: ELECTRICAL DATA..................................................................................................

3-1

 

3-1. Indoor Units ........................................................................................................

3-2

 

3-2. Outdoor Units....................................................................................................

3-14

Section 4: SERVICE PROCEDURES.........................................................................................

4-1

 

4-1. Meaning of Alarm Messages ..............................................................................

4-2

 

4-2. Symptoms and Parts to Inspect ..........................................................................

4-5

 

4-3. Details of Alarm Messages .................................................................................

4-8

 

4-4. Table of Thermistor Characteristics ..................................................................

4-16

Section 5: OUTDOOR UNIT MAINTENANCE REMOTE CONTROL ........................................

5-1

 

 

 

 

 

In the case of CZ-RTC2

 

5-1. Overview .............................................................................................................

5-2

5-2. Functions ............................................................................................................

5-2

5-3. Normal Display Operations and Functions .........................................................

5-3

 

5-4. Monitoring Operations: Display of Indoor Unit and Outdoor Unit Sensor

 

 

Temperatures ......................................................................................................

5-6

 

5-5. Monitoring the Outdoor Unit Alarm History: Display of Outdoor Unit

 

 

Alarm History ......................................................................................................

5-7

 

5-6. Setting Modes: Setting the Outdoor Unit EEPROM ............................................

5-7

 

 

 

 

 

In the case of CZ-RTC4

 

5-7. Overview ...........................................................................................................

5-11

5-8. Functions ..........................................................................................................

5-12

5-9. Normal Display Operations and Functions .......................................................

5-13

 

5-10. Monitoring Operations: Display of Indoor Unit and Outdoor Unit Sensor

 

 

Temperatures...................................................................................................

5-18

 

5-11. Monitoring the Outdoor Unit Alarm History: Display of Outdoor Unit

 

 

Alarm History...................................................................................................

5-20

 

5-12. Setting Modes: Setting the Outdoor Unit EEPROM.........................................

5-21

v

Section 6: TEST RUN.................................................................................................................

6-1

6-1. Preparing for Test Run ........................................................................................

6-2

6-2. Caution ...............................................................................................................

6-3

6-3. Test Run Procedure ............................................................................................

6-3

6-4. Items to Check Before the Test Run....................................................................

6-4

6-5.

Test Run Using the Remote Controller ...............................................................

6-4

6-6.

Precautions .........................................................................................................

6-5

6-7.

Table of Self-Diagnostic Functions and Corrections

 

 

(Type F2, U2, T2, K2, U1, K1, T1 and F1)...............................................................

6-6

6-8.

Examples of Wiring Diagrams.............................................................................

6-7

vi

— MEMO —

vii

1. SPECIFICATIONS

1-1.

Unit Specifications....................................................................................................

1-2

 

1-2.

Major Component Specifications ..........................................................................

1-29

 

1-3.

Other Component Specifications ..........................................................................

1-53

 

1-4.

Dimensional Data ....................................................................................................

1-56

 

1-5.

Refrigerant Flow Diagram ......................................................................................

1-70

 

1-6.

Operating Range .....................................................................................................

1-71

 

1-7.

Capacity Correction Graph According to Temperature Condition .....................

1-72

 

1-8.

Noise Criterion Curves ...........................................................................................

1-73

 

1-9.

Increasing the Fan Speed .......................................................................................

1-82

 

1-10.

External Static Pressure Setting

1-83

 

 

1-11.

Air Throw Distance Chart .........................................................................................

1-89

 

1-12.

ELECTRICAL WIRING .............................................................................................

1-97

1

1-13.

Installation Instructions ........................................................................................

1-100

 

 

 

 

Outdoor Unit

 

 

 

 

 

 

 

 

1.

Tubing Size .....................................................................................................................................

1-100

 

 

2.

Check of density limit ......................................................................................................................

1-101

 

 

3.

SELECTING THE INSTALLATION SITE .......................................................................................

1-102

 

 

4.

HOW TO INSTALL THE OUTDOOR UNIT .....................................................................................

1-111

 

 

 

 

Indoor Unit

 

 

 

 

 

 

 

 

5.

SELECTING THE INSTALLATION SITE .......................................................................................

1-119

 

 

6.

HOW TO INSTALL THE INDOOR UNIT .........................................................................................

1-120

 

 

7.

HOW TO INSTALL THE WIRELESS REMOTE CONTROLLER ....................................................

1-176

 

 

8.

HOW TO INSTALL THE TIMER WIRED REMOTE CONTROLLER ..............................................

1-198

 

1-1

1. Specifications

1-1. Unit Specifications

Concealed Duct (Type F2)

 

 

 

 

 

 

 

 

INDOOR

 

MODEL

 

 

S-26PF2U6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PANEL

 

MODEL

 

-

 

 

 

 

-

 

 

 

 

 

 

 

 

 

 

 

 

OUTDOOR

 

MODEL

 

 

 

 

 

 

 

 

U-26PE1U6

 

 

 

 

 

 

 

 

 

 

Branch pipe

 

MODEL

 

 

 

 

 

 

 

-

 

 

 

 

 

 

 

 

 

 

 

 

PERFORMANCE TEST CONDITION

 

 

 

 

 

 

ARI Standard 210/240

 

 

 

 

 

 

 

 

 

 

POWER SUPPLY

 

PH, Hz

 

 

1PH, 60Hz

 

 

 

 

1PH, 60Hz

 

 

 

 

 

 

 

 

 

 

 

V

208

 

230

 

-

 

208

 

230

 

-

Min

Max

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CAPACITY *1

 

kW

7.0

 

7.0

 

-

 

 

 

 

 

 

-

-

 

 

 

 

 

 

 

 

 

BTU/h

24000

 

24000

 

-

 

 

 

 

 

 

9500

24000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C

CURRENT *1 *4

 

A

0.95

 

0.89

 

-

 

15.6

 

14.2

 

-

-

-

 

 

 

 

 

W

120

 

120

 

-

 

2600

 

2600

 

-

-

-

 

 

O

INPUT POWER *1

 

 

 

 

 

 

 

 

 

TOTAL W

 

-

 

 

 

2720

 

2720

 

-

650

2720

 

 

O

 

 

 

 

 

 

 

 

 

 

 

L

 

EER

 

 

-

 

-

 

-

 

-

 

8.8

 

8.8

 

-

14.6

8.8

 

 

 

SEER

 

 

-

 

-

 

-

 

-

 

16.2

 

16.2

 

-

 

 

 

 

I

 

 

 

 

 

 

 

 

 

 

 

 

 

POWER FACTOR

 

%

 

-

 

-

 

-

 

80

 

80

 

-

 

 

 

 

N

 

 

 

 

 

 

 

 

 

 

 

NOISE INDOOR

 

dB-A (H/M/L)

 

35/32/26

 

 

 

 

 

 

 

 

 

 

 

 

G

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power Level dB

 

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOISE OUTDOOR

 

dB-A (H)

 

 

 

 

 

 

 

49

 

 

 

 

 

 

 

 

 

 

 

 

Power Level dB

 

 

 

 

 

 

 

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CAPACITY *2

 

kW

8.4

 

8.4

 

-

 

 

 

 

 

 

-

-

 

 

 

 

 

 

 

 

 

BTU/h

28600

 

28600

 

-

 

 

 

 

 

 

8000

28600

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CURRENT *2 *4

 

A

0.95

 

0.89

 

-

 

14.8

 

13.4

 

-

-

-

 

 

H

INPUT POWER *2

 

W

120

 

120

 

-

 

2460

 

2460

 

-

-

-

 

 

 

TOTAL W

 

-

 

 

 

2580

 

2580

 

-

470

2580

 

 

 

 

 

 

 

 

 

 

 

 

 

E

 

 

(COP)

 

 

-

 

-

 

-

 

-

 

(11.1)

 

(11.1)

 

-

17.0

11.1

1

 

A

 

 

HSPF

 

 

-

 

-

 

-

 

-

 

9.8

 

9.8

 

-

 

 

 

T

 

(HSPF (CANADA REGIONS))

 

-

 

-

 

-

 

-

 

(8.1)

 

(8.1)

 

-

 

 

 

I

 

H32 *3

CAPACITY

 

BTU/h

-

 

-

 

-

 

16000

 

16000

 

-

 

 

 

 

N

(17°F)

INPUT POWER

 

TOTAL W

-

 

-

 

-

 

2000

 

2000

 

-

 

 

 

 

G

 

POWER FACTOR

 

%

 

-

 

-

 

-

 

80

 

80

 

-

 

 

 

 

 

 

 

 

 

NOISE INDOOR

 

dB-A (H/M/L)

 

 

35/32/26

 

 

 

 

-

 

 

 

 

 

 

 

 

 

 

 

 

Power Level dB

 

-

 

 

 

 

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOISE OUTDOOR

 

dB-A (H)

 

-

 

 

 

 

49

 

 

 

 

 

 

 

 

 

 

 

 

Power Level dB

 

-

 

 

 

 

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MAX CURRENT (A)/MAX

INPUT POWER (W)

1.32/160

 

1.20/160

 

-

 

16.5/2.75k

 

16.5/3.04k

 

-

 

 

 

 

 

 

 

 

 

 

1(7:25. ,03('$1&( ȍ0$;

 

 

-

 

 

 

 

 

-

 

 

 

 

 

 

 

 

 

 

 

 

MINIMUM CIRCUIT AMPACITY (A)

 

15

 

 

 

 

17

 

 

 

 

 

 

 

 

 

 

 

MAXIMUM OVERCURRENT PROTECTION (A)

 

15

 

 

 

 

30

 

 

 

 

 

 

 

 

 

 

 

 

DISCONNECT SWITCH CAPACITY (A)

 

15

 

 

 

 

-

 

 

 

 

 

 

OUTDOOR FAN MOTOR

AMPERES (A)

 

COOL/HEAT

 

-

 

 

 

0.9 / 0.9

 

0.9 / 0.9

 

-

 

 

 

 

 

 

 

 

 

COMPRESSOR AMPERES (A)

 

COOL/HEAT

 

-

 

 

 

10.1 / 12.9

 

10.2 / 11.4

 

-

 

 

 

 

 

 

 

 

 

COMPRESSOR LOCKED-ROTOR AMPERES (A)

 

-

 

 

 

 

 

17.5

 

 

 

 

 

 

 

 

 

 

 

COMPRESSOR RATED LOAD AMPERES (A)

 

-

 

 

 

 

12.9

 

 

 

 

 

 

 

 

 

 

 

 

OUTDOOR

 

HIGH SIDE

 

MPa , psi.

 

-

 

 

 

 

(3.4) , 487

 

 

 

 

 

 

 

 

 

 

 

DESIGN PRESSURE

 

LOW SIDE

 

MPa , psi.

 

-

 

 

 

 

(1.63) , 236

 

 

 

 

 

 

 

 

 

 

 

 

FM OUTPUT

(ID/OD) W

 

 

 

124

 

 

 

 

90

 

 

 

 

 

 

 

 

 

 

 

MOISTURE REMOVAL VOLUME

 

L/h, Pints/h

 

2.2, 4.6

 

 

 

 

-

 

 

 

 

 

 

 

 

 

 

 

 

Extarnal static pressure

 

Pa, in.WC

70(min10 ~ max150), 0.28(min0.04 ~ max0.60)

 

 

 

 

 

 

 

 

 

I/D AIR

COOL (H/M/L)

 

m3/min, ft3/min (CFM)

21/19/15, 742/671/530

 

 

 

 

 

 

 

 

 

 

 

FLOW

HEAT (H/M/L)

 

m3/min, ft3/min (CFM)

21/19/15, 742/671/530

 

 

 

 

 

 

 

 

 

 

 

O/D AIR

COOL

 

m3/min, ft3/min (CFM)

 

 

 

 

 

 

 

50, 1766

 

 

 

 

 

 

FLOW

HEAT

 

m3/min, ft3/min (CFM)

 

 

 

 

 

 

 

50, 1766

 

 

 

 

 

 

 

 

 

 

 

 

REFRIGERANT TYPE,

AMOUNT g, lb, (oz)

 

 

R410A, -

 

 

R410A, 1.90k, 4.2, (67.0)

 

 

 

 

P

D

HEIGHT : H mm (inch)

 

290 (11-7/16)

 

 

 

780 (30-23/32)

 

 

 

 

 

R

I

WIDTH : W mm (inch)

 

1000 (39-3/8)

 

 

 

940 (37)

 

 

 

 

 

 

O

M

DEPTH : D mm (inch)

 

700 (27-9/16)

 

 

 

340 (13-3/8)

 

 

 

 

 

 

P

D

HEIGHT : H mm (inch)

 

355 (13-31/32)

 

 

 

888 (34-31/32)

 

 

 

 

 

A

I

WIDTH : W mm (inch)

 

1214 (47-13/16)

 

 

1015 (39-31/32)

 

 

 

 

 

C

M

DEPTH : D mm (inch)

 

850 (33-15/32)

 

 

 

409 (16-3/32)

 

 

 

 

 

MASS

 

(NET) kg (lb)

 

 

 

33 (73)

 

 

 

 

58 (128)

 

 

 

 

 

 

(GROSS) kg (lb)

 

 

 

40 (89)

 

 

 

 

67 (148)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LAYERS LIMIT ID/OD (actually)

 

 

 

9 (10)

 

 

 

 

3 (4)

 

 

 

 

 

 

 

 

 

 

 

 

Operation

 

 

 

Cool (DBT)

18°C ~ 32°C (64°F ~ 90°F)

 

-10°C ~ 46°C (14°F ~ 115°F)

 

 

 

 

 

 

 

 

 

 

Condition

 

 

 

Heat (DBT)

16°C ~ 30°C (61°F ~ 86°F)

 

-20°C ~ 24°C (-4°F ~ 75°F)

 

 

 

 

P

 

PIPE DIAMETER mm (inch)

 

 

(Liquid) ø9.52 (3/8) (Gas) ø15.88 (5/8)

(Liquid) ø9.52 (3/8) (Gas) ø15.88 (5/8)

 

 

 

 

 

CONNECT METHOD

 

 

 

 

ÀDUHG W\SH

 

 

 

 

ÀDUHG W\SH

 

 

 

 

 

I

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

STD LENGTH m (ft)

 

 

 

 

 

 

 

7.6 (25)

 

 

 

 

 

 

 

 

P

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PIPE LENGTH RANGE m (ft)

 

3 ~ 50 (10 ~ 165)

 

 

 

 

 

 

 

 

I

 

 

 

 

 

 

 

 

 

 

 

I/D&O/D HEIGHT DIFFERENCE

m (ft)

 

15 (OD located lower) /30 (OD located higher) (50/100)

 

 

 

 

 

N

 

 

 

 

 

 

 

 

ADD GAS AMOUNT g/m (oz/ft)

 

 

 

 

 

40 (0.43)

 

 

 

 

 

 

 

 

G

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PIPE LENGTH FOR ADDITIONAL GAS m (ft)

 

 

 

 

 

30 (100)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DATA SUBJECT TO CHANGE WITHOUT NOTICE.

*1:Rating conditions : Room temperature 80 °F DB / 67 °F WB (26.7°C DB / 19.4°C WB), Ambient temperature 95 °F DB / 75 °F WB (35.0°C DB / 23.9°C WB).

*2:Rating conditions : Room temperature 70 °F DB / 60 °F WB (21.1°C DB / 15.6°C WB), Ambient temperature 47 °F DB / 43 °F WB (8.3°C DB / 6.1°C WB).

*3:Low temp conditions : Room temperature 70 °F DB / 60 °F WB (21.1°C DB / 15.6°C WB), Ambient temperature 17 °F DB / 15 °F WB (-8.3°C DB / -9.4°C WB).

*4:INDOOR CURRENT="INDOOR FAN MOTOR LOAD"

1-2

1. Specifications

1-1. Unit Specifications

Concealed Duct (Type F2)

 

 

 

 

 

INDOOR

 

MODEL

 

 

S-36PF2U6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PANEL

 

MODEL

 

-

 

 

 

 

-

 

 

 

 

 

 

 

 

 

 

 

OUTDOOR

 

MODEL

 

 

 

 

 

 

 

 

U-36PE1U6

 

 

 

 

 

 

 

 

 

Branch pipe

 

MODEL

 

 

 

 

 

 

 

-

 

 

 

 

 

 

 

 

 

 

 

PERFORMANCE TEST CONDITION

 

 

 

 

 

 

ARI Standard 210/240

 

 

 

 

 

 

 

 

 

POWER SUPPLY

 

PH, Hz

 

 

1PH, 60Hz

 

 

 

 

1PH, 60Hz

 

 

 

 

 

 

 

 

 

 

V

208

 

230

 

-

 

208

 

230

 

-

Min

Max

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CAPACITY *1

 

kW

9.1

 

9.1

 

-

 

 

 

 

 

 

-

-

 

 

 

 

 

 

 

 

BTU/h

31200

 

31200

 

-

 

 

 

 

 

 

9500

31200

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C

CURRENT *1 *4

 

A

1.53

 

1.42

 

-

 

17.8

 

16.2

 

-

-

-

 

 

 

 

 

W

220

 

220

 

-

 

3380

 

3380

 

-

-

-

 

 

O

INPUT POWER *1

 

 

 

 

 

 

 

 

 

TOTAL W

 

-

 

 

 

3600

 

3600

 

-

640

3600

 

 

O

 

 

 

 

 

 

 

 

 

 

 

L

 

EER

 

 

-

 

-

 

-

 

-

 

8.6

 

8.6

 

-

14.8

8.6

 

 

 

SEER

 

 

-

 

-

 

-

 

-

 

15.5

 

15.5

 

-

 

 

 

 

I

 

 

 

 

 

 

 

 

 

 

 

 

 

POWER FACTOR

 

%

 

-

 

-

 

-

 

91

 

91

 

-

 

 

 

 

N

 

 

 

 

 

 

 

 

 

 

 

NOISE INDOOR

 

dB-A (H/M/L)

 

39/35/31

 

 

 

 

 

 

 

 

 

 

 

 

G

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power Level dB

 

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOISE OUTDOOR

 

dB-A (H)

 

 

 

 

 

 

 

52

 

 

 

 

 

 

 

 

 

 

 

Power Level dB

 

 

 

 

 

 

 

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CAPACITY *2

 

kW

10.6

 

10.6

 

-

 

 

 

 

 

 

-

-

 

 

 

 

 

 

 

 

BTU/h

36200

 

36200

 

-

 

 

 

 

 

 

8000

36200

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CURRENT *2 *4

 

A

1.53

 

1.42

 

-

 

16.0

 

14.5

 

-

-

-

 

 

H

INPUT POWER *2

 

W

220

 

220

 

-

 

3030

 

3030

 

-

-

-

 

 

 

TOTAL W

 

-

 

 

 

3250

 

3250

 

-

480

3250

 

 

 

 

 

 

 

 

 

 

 

 

 

E

 

(COP)

 

 

-

 

-

 

-

 

-

 

(11.1)

 

(11.1)

 

-

16.7

11.1

 

 

A

 

HSPF

 

 

-

 

-

 

-

 

-

 

9.0

 

9.0

 

-

 

 

 

1

T

 

(HSPF (CANADA REGIONS))

 

-

 

-

 

-

 

-

 

(7.1)

 

(7.1)

 

-

 

 

 

I

 

H32 *3

CAPACITY

 

BTU/h

-

 

-

 

-

 

18000

 

18000

 

-

 

 

 

N

(17°F)

INPUT POWER

 

TOTAL W

-

 

-

 

-

 

2450

 

2450

 

-

 

 

 

 

G

 

POWER FACTOR

 

%

 

-

 

-

 

-

 

91

 

91

 

-

 

 

 

 

 

 

 

 

NOISE INDOOR

 

dB-A (H/M/L)

 

 

39/35/31

 

 

 

 

-

 

 

 

 

 

 

 

 

 

 

 

Power Level dB

 

-

 

 

 

 

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOISE OUTDOOR

 

dB-A (H)

 

-

 

 

 

 

52

 

 

 

 

 

 

 

 

 

 

 

Power Level dB

 

-

 

 

 

 

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MAX CURRENT (A)/MAX

INPUT POWER (W)

1.88/265

 

1.75/265

 

-

 

19.0/3.60k

 

19.0/3.98k

 

-

 

 

 

 

 

 

 

 

 

1(7:25. ,03('$1&( ȍ0$;

 

 

-

 

 

 

 

 

-

 

 

 

 

 

 

 

 

 

 

 

MINIMUM CIRCUIT AMPACITY (A)

 

15

 

 

 

 

21

 

 

 

 

 

 

 

 

 

 

MAXIMUM OVERCURRENT PROTECTION (A)

 

15

 

 

 

 

35

 

 

 

 

 

 

 

 

 

 

 

DISCONNECT SWITCH CAPACITY (A)

 

15

 

 

 

 

-

 

 

 

 

 

 

OUTDOOR FAN MOTOR

AMPERES (A)

 

COOL/HEAT

 

-

 

 

 

1.0 / 1.0

 

0.9 / 0.9

 

-

 

 

 

 

 

 

 

 

COMPRESSOR AMPERES (A)

 

COOL/HEAT

 

-

 

 

 

12.8 / 15.7

 

12.9 / 16.4

 

-

 

 

 

 

 

 

 

 

COMPRESSOR LOCKED-ROTOR AMPERES (A)

 

-

 

 

 

 

 

17.5

 

 

 

 

 

 

 

 

 

 

COMPRESSOR RATED LOAD AMPERES (A)

 

-

 

 

 

 

15.7

 

 

 

 

 

 

 

 

 

 

 

OUTDOOR

 

HIGH SIDE

 

MPa , psi.

 

-

 

 

 

 

(3.4) , 487

 

 

 

 

 

 

 

 

 

 

DESIGN PRESSURE

 

LOW SIDE

 

MPa , psi.

 

-

 

 

 

 

(1.63) , 236

 

 

 

 

 

 

 

 

 

 

 

FM OUTPUT

(ID/OD) W

 

 

 

235

 

 

 

 

90

 

 

 

 

 

 

 

 

 

 

MOISTURE REMOVAL VOLUME

 

L/h, Pints/h

 

1.4, 2.9

 

 

 

 

-

 

 

 

 

 

 

 

 

 

 

 

Extarnal static pressure

 

Pa, in.WC

100(min10 ~ max150), 0.40(min0.04 ~ max0.60)

 

 

 

 

 

 

 

 

 

I/D AIR

COOL (H/M/L)

 

m3/min, ft3/min (CFM)

34/28/23, 1201/989/812

 

 

 

 

 

 

 

 

 

 

 

FLOW

HEAT (H/M/L)

 

m3/min, ft3/min (CFM)

34/28/23, 1201/989/812

 

 

 

 

 

 

 

 

 

 

 

O/D AIR

COOL

 

m3/min, ft3/min (CFM)

 

 

 

 

 

 

 

55, 1942

 

 

 

 

 

 

FLOW

HEAT

 

m3/min, ft3/min (CFM)

 

 

 

 

 

 

 

55, 1942

 

 

 

 

 

 

 

 

 

 

 

REFRIGERANT TYPE,

AMOUNT g, lb, (oz)

 

 

R410A, -

 

 

R410A, 2.80k, 6.2, (98.8)

 

 

 

 

P

D

HEIGHT : H mm (inch)

 

290 (11-7/16)

 

 

 

780 (30-23/32)

 

 

 

 

 

R

I

WIDTH : W mm (inch)

 

1400 (55-1/8)

 

 

 

940 (37)

 

 

 

 

 

 

O

M

DEPTH : D mm (inch)

 

700 (27-9/16)

 

 

 

340 (13-3/8)

 

 

 

 

 

 

P

D

HEIGHT : H mm (inch)

 

355 (13-31/32)

 

 

 

888 (34-31/32)

 

 

 

 

 

A

I

WIDTH : W mm (inch)

 

1614 (63-9/16)

 

 

1015 (39-31/32)

 

 

 

 

 

C

M

DEPTH : D mm (inch)

 

850 (33-15/32)

 

 

 

409 (16-3/32)

 

 

 

 

 

MASS

 

(NET) kg (lb)

 

 

 

44 (97)

 

 

 

 

65 (143)

 

 

 

 

 

 

(GROSS) kg (lb)

 

 

 

52 (115)

 

 

 

 

73 (161)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LAYERS LIMIT ID/OD (actually)

 

 

 

9 (10)

 

 

 

 

3 (4)

 

 

 

 

 

 

 

 

 

 

 

Operation

 

 

 

Cool (DBT)

18°C ~ 32°C (64°F ~ 90°F)

 

-10°C ~ 46°C (14°F ~ 115°F)

 

 

 

 

 

 

 

 

 

Condition

 

 

 

Heat (DBT)

16°C ~ 30°C (61°F ~ 86°F)

 

-20°C ~ 24°C (-4°F ~ 75°F)

 

 

 

 

P

 

PIPE DIAMETER mm (inch)

 

 

(Liquid) ø9.52 (3/8) (Gas) ø15.88 (5/8)

(Liquid) ø9.52 (3/8) (Gas) ø15.88 (5/8)

 

 

 

 

 

CONNECT METHOD

 

 

 

 

ÀDUHG W\SH

 

 

 

 

ÀDUHG W\SH

 

 

 

 

 

I

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

STD LENGTH m (ft)

 

 

 

 

 

 

 

7.6 (25)

 

 

 

 

 

 

 

 

P

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PIPE LENGTH RANGE m (ft)

 

3 ~ 50 (10 ~ 165)

 

 

 

 

 

 

 

 

I

 

 

 

 

 

 

 

 

 

 

 

I/D&O/D HEIGHT DIFFERENCE

m (ft)

 

15 (OD located lower) /30 (OD located higher) (50/100)

 

 

 

 

 

N

 

 

 

 

 

 

 

 

ADD GAS AMOUNT g/m (oz/ft)

 

 

 

 

 

40 (0.43)

 

 

 

 

 

 

 

 

G

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PIPE LENGTH FOR ADDITIONAL GAS m (ft)

 

 

 

 

 

30 (100)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DATA SUBJECT TO CHANGE WITHOUT NOTICE.

*1:Rating conditions : Room temperature 80 °F DB / 67 °F WB (26.7°C DB / 19.4°C WB), Ambient temperature 95 °F DB / 75 °F WB (35.0°C DB / 23.9°C WB).

*2:Rating conditions : Room temperature 70 °F DB / 60 °F WB (21.1°C DB / 15.6°C WB), Ambient temperature 47 °F DB / 43 °F WB (8.3°C DB / 6.1°C WB).

*3:Low temp conditions : Room temperature 70 °F DB / 60 °F WB (21.1°C DB / 15.6°C WB), Ambient temperature 17 °F DB / 15 °F WB (-8.3°C DB / -9.4°C WB).

*4:INDOOR CURRENT="INDOOR FAN MOTOR LOAD"

1-3

1. Specifications

1-1. Unit Specifications

4-Way Cassette (Type U1)

 

 

 

MODEL No.

 

Indoor Unit

 

 

 

 

 

 

 

 

 

S-26PU1U6

 

 

 

 

 

 

 

 

 

Outdoor Unit

 

 

 

 

 

 

 

 

 

U-26PE1U6

 

 

 

 

 

 

 

 

POWER SOURCE

 

 

 

230 - 208V / 1 Phase / 60Hz

 

 

 

PERFORMANCE

 

Cooling

 

 

 

 

 

Heating

 

 

 

Capacity * [minimum~muximum]

 

BTU / h

24,800 [9,500~24,800]

 

29,800 [8,000~29,800]

 

 

 

 

 

(17˚F)**

 

BTU / h

 

 

 

 

 

 

 

 

 

 

 

 

 

 

18,300

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Moisture removal (High)

 

 

Pints / h

8.1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air circulation (H / M / L) 230 V

 

CFM

 

 

 

 

 

 

 

710 / 530 / 450

 

 

 

 

 

 

 

External Static Pressure

 

 

in. WG

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S.E.E.R. / H.S.P.F. (Region 4)

 

BTU / Wh

14.1

 

 

 

 

 

 

 

9.6

 

 

 

ELECTRICAL RATINGS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Voltage rating

 

 

V

230

 

 

 

 

 

 

208

 

230

 

208

 

 

 

Available voltage range

 

 

V

VAC 187 - 253

 

 

 

 

VAC 187 - 253

 

 

 

Max.Running amperes*

 

 

A

15.6

 

 

 

 

 

 

17.3

 

14.8

 

16.4

 

 

 

Power input

 

 

W

2,920

 

 

 

 

 

 

2,920

 

2,790

 

2,790

 

 

 

 

 

(17˚F)**

 

W

 

 

 

 

 

 

 

 

 

 

2,200

 

2,200

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Back-up Heater

 

 

kW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

Maximum overcurrent protection (Indoor/Outdoor)

 

A

 

 

 

 

 

 

 

15 / 30

 

 

 

 

 

 

FEATURES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Controls

 

 

 

 

 

 

 

 

 

 

 

Microprocessor

 

 

 

 

 

 

 

Low ambient control

 

 

 

 

 

 

 

 

 

 

 

Built-in 0˚F

 

 

 

 

 

 

 

Fan speeds Indoor / Outdoor

 

3 and Automatic control / Variable

 

 

 

Wired Remote Controller

 

 

 

 

 

 

 

 

 

 

 

CZ-RTC2

 

 

 

 

 

 

 

Optional Wireless Remote Controller

 

 

 

 

 

 

 

 

 

CZ-RWSU2U

 

 

 

 

 

 

 

Air deflection (Horizontal / Vertical )

 

 

 

 

 

 

 

 

 

/ Automatic (Vertical )

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air filter

 

 

 

 

 

Washable, long life (2,500 hr)

 

 

 

Drain pump (Drain connection)

 

Max.head 2-33/64 in. above drain connection (25A , OD32mm)

 

 

 

Compressor

 

 

 

 

 

 

 

 

 

 

 

Rotary

 

 

 

 

 

 

 

Operation sound

Indoor - Hi/Me/Lo

 

dB - A

 

 

 

 

 

 

 

38 / 35 / 31

 

 

 

 

 

 

 

 

 

Outdoor - Hi

 

dB - A

 

 

 

 

 

 

 

 

 

49

 

 

 

 

 

 

 

Refrigerant control

 

 

 

Electronic Expansion Valve (MOV)

 

 

 

REFRIGERANT TUBING

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Limit of tubing length

 

 

ft. (m)

 

 

 

 

 

 

 

165 (50)

 

 

 

 

 

 

 

Limit of tubing length at shipment

 

ft. (m)

 

 

 

 

 

 

 

10~100 (3~30)

 

 

 

 

 

 

 

Limit of elevation difference

 

ft. (m)

Outdoor unit is higher than indoor unit : 100 (30)

 

 

 

between the two units

 

 

ft. (m)

Outdoor unit is lower than indoor unit : 50 (15)

 

 

 

Refrigerant tube

Narrow tube

 

in. (mm)

 

 

 

 

 

 

 

3 / 8 (9.52)

 

 

 

 

 

 

 

outer diameter

Wide tube

 

in. (mm)

 

 

 

 

 

 

 

5 / 8 (15.88)

 

 

 

 

 

 

 

Refrigerant amount at shipment

 

lbs. (kg)

 

 

 

 

 

 

 

4.2 (1.9) - R410A

 

 

 

 

 

 

 

DIMENSIONS & WEIGHT

 

 

 

Indoor unit (Include panel)

Outdoor unit

 

 

 

Unit dimensions

Height

 

in. (mm)

13-5/16 (338)

 

 

 

 

 

3023/32 (780)

 

 

 

 

 

Width

 

in. (mm)

33-55/64 (860)

 

 

 

 

 

37 (940)

 

 

 

 

 

Depth

 

in. (mm)

33-55/64 (860)

 

 

 

 

 

13- 3/8 (340)

 

 

 

Package dimensions

 

 

 

Body

 

Panel

Outdoor unit

 

 

 

 

 

Height

 

in. (mm)

13-5/16 (338)

 

4-3/32 (104)

3431/32 (888)

 

 

 

 

 

Width

 

in. (mm)

32-7/8 (835)

 

37-61/64 (964)

3931/32 (1,015)

 

 

 

 

 

Depth

 

in. (mm)

33-9/32 (845)

 

39-21/64 (999)

16- 3/32 (409)

 

 

 

Net weight

 

 

lbs. (kg)

49 (22)

 

 

 

 

 

11 (5)

128 (58)

 

 

 

Shipping weight

 

 

lbs. (kg)

57 (26)

 

 

 

 

 

18 (8)

148 (67)

 

 

 

Shipping volume

 

 

cu.ft. (m3 )

8.4 (0.238)

 

 

3.6 (0.100)

13.0 (0.369)

 

 

 

 

 

 

 

 

DATA SUBJECT

TO CHANGE

WITHOUT NOTICE.

Cooling:

Rating conditions (*) : Room temperature 80 °F DB / 67 °F WB, Ambient temperature 95 °F DB / 75 °F WB

Heating:

Rating conditions (*) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 47 °F DB / 43 °F WB Low temp conditions (**) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 17 °F DB / 15 °F WB

1-4

1. Specifications

1-1. Unit Specifications

4-Way Cassette (Type U1)

 

MODEL No.

 

Indoor Unit

 

 

 

 

 

 

 

 

 

 

S-36PU1U6

 

 

 

 

 

 

 

 

 

Outdoor Unit

 

 

 

 

 

 

 

 

 

 

U-36PE1U6

 

 

 

 

 

 

 

 

POWER SOURCE

 

 

 

 

230 - 208V / 1 Phase / 60Hz

 

 

 

PERFORMANCE

 

 

Cooling

 

 

 

 

 

 

 

Heating

 

 

 

Capacity * [minimum~muximum]

 

BTU / h

32,600 [9,500~32,600]

 

 

37,600 [8,000~37,600]

 

 

 

 

 

(17˚F)**

 

BTU / h

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20,000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Moisture removal (High)

 

 

Pints / h

 

10.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air circulation (H / M / L) 230 V

 

CFM

 

 

 

 

 

 

 

 

1050 / 840 / 720

 

 

 

 

 

 

 

External Static Pressure

 

 

in. WG

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S.E.E.R. / H.S.P.F. (Region 4)

 

BTU / Wh

 

14.6

 

 

 

 

 

 

 

 

8.4

 

 

 

ELECTRICAL RATINGS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Voltage rating

 

 

V

230

 

 

 

 

 

 

 

208

 

 

230

 

 

208

 

 

 

Available voltage range

 

 

V

VAC 187 - 253

 

 

 

VAC 187 - 253

 

 

 

Max. Running amperes*

 

 

A

18.7

 

 

 

 

 

 

 

20.7

 

 

15.9

 

 

17.6

 

 

 

Power input

 

 

W

3,950

 

 

 

3,950

 

 

3,350

 

 

3,350

 

 

 

 

 

(17˚F)**

 

W

 

 

 

 

 

 

 

 

 

 

 

 

2,450

 

 

2,450

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Back-up Heater

 

 

kW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Maximum overcurrent protection (Indoor/Outdoor)

 

A

 

 

 

 

 

 

 

 

15 / 35

 

 

 

 

 

1

 

FEATURES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Controls

 

 

 

 

 

 

 

 

 

 

 

 

Microprocessor

 

 

 

 

 

 

 

Low ambient control

 

 

 

 

 

 

 

 

 

 

 

 

Built-in 0˚F

 

 

 

 

 

 

 

Fan speeds Indoor / Outdoor

 

 

3 and Automatic control / Variable

 

 

 

Wired Remote Controller

 

 

 

 

 

 

 

 

 

 

 

 

CZ-RTC2

 

 

 

 

 

 

 

Optional Wireless Remote Controller

 

 

 

 

 

 

 

 

 

 

CZ-RWSU2U

 

 

 

 

 

 

 

Air deflection (Horizontal / Vertical )

 

 

 

 

 

 

 

 

 

 

/ Automatic (Vertical )

 

 

 

 

 

 

 

 

 

 

 

 

 

Air filter

 

 

 

 

 

 

Washable, long life (2,500 hr)

 

 

 

Drain pump (Drain connection)

 

Max.head 2-33/64 in. above drain connection (25A , OD32mm)

 

 

 

Compressor

 

 

 

 

 

 

 

 

 

 

 

 

Rotary

 

 

 

 

 

 

 

Operation sound

Indoor - Hi/Me/Lo

 

dB - A

 

 

 

 

 

 

 

 

44 / 37 / 33

 

 

 

 

 

 

 

 

 

Outdoor - Hi

 

dB - A

 

 

 

 

 

 

 

 

 

 

 

52

 

 

 

 

 

 

 

Refrigerant control

 

 

 

 

Electronic Expansion Valve (MOV)

 

 

 

REFRIGERANT TUBING

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Limit of tubing length

 

 

ft. (m)

 

 

 

 

 

 

 

 

165 (50)

 

 

 

 

 

 

 

Limit of tubing length at shipment

 

ft. (m)

 

 

 

 

 

 

 

 

10~100 (3~30)

 

 

 

 

 

 

 

Limit of elevation difference

 

ft. (m)

Outdoor unit is higher than indoor unit : 100 (30)

 

 

 

between the two units

 

 

ft. (m)

Outdoor unit is lower than indoor unit : 50 (15)

 

 

 

Refrigerant tube

Narrow tube

 

in. (mm)

 

 

 

 

 

 

 

 

3 / 8 (9.52)

 

 

 

 

 

 

 

outer diameter

Wide tube

 

in. (mm)

 

 

 

 

 

 

 

 

5 / 8 (15.88)

 

 

 

 

 

 

 

Refrigerant amount at shipment

 

lbs. (kg)

 

 

 

 

 

 

 

 

6.2 (2.8) - R410A

 

 

 

 

 

 

 

DIMENSIONS & WEIGHT

 

 

 

Indoor unit (Include panel)

Outdoor unit

 

 

 

Unit dimensions

Height

 

in. (mm)

 

14-31/64 (368)

 

 

 

 

 

3023/32 (780)

 

 

 

 

 

Width

 

in. (mm)

 

45-9/32 (1,150)

 

 

 

 

37 (940)

 

 

 

 

 

Depth

 

in. (mm)

 

33-55/64 (860)

 

 

 

 

 

13- 3/8 (340)

 

 

 

Package dimensions

 

 

 

Body

 

Panel

Outdoor unit

 

 

 

 

 

Height

 

in. (mm)

14-31/64 (368)

 

 

4-3/32 (104)

3431/32 (888)

 

 

 

 

 

Width

 

in. (mm)

44-19/64 (1,125)

 

49-31/64 (1,257)

3931/32 (1,015)

 

 

 

 

 

Depth

 

in. (mm)

33-9/32 (845)

 

 

39-21/64 (999)

16- 3/32 (409)

 

 

 

Net weight

 

 

lbs. (kg)

60 (27)

 

 

 

 

 

16 (7)

143 (65)

 

 

 

Shipping weight

 

 

lbs. (kg)

71 (32)

 

 

 

 

 

22 (10)

161 (73)

 

 

 

Shipping volume

 

 

cu.ft. (m3 )

12.4 (0.350)

 

 

4.6 (0.131)

13.0 (0.369)

 

 

 

 

 

 

 

 

DATA SUBJECT

TO CHANGE

WITHOUT NOTICE.

 

 

Cooling:

Rating conditions (*) : Room temperature 80 °F DB / 67 °F WB, Ambient temperature 95 °F DB / 75 °F WB

Heating:

Rating conditions (*) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 47 °F DB / 43 °F WB Low temp conditions (**) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 17 °F DB / 15 °F WB

1-5

1. Specifications

1-1. Unit Specifications

4-Way Cassette (Type U1)

 

 

 

MODEL No.

 

Indoor Unit

 

 

 

 

 

 

 

 

 

 

S-42PU1U6

 

 

 

 

 

 

 

 

 

Outdoor Unit

 

 

 

 

 

 

 

 

 

 

U-42PE1U6

 

 

 

 

 

 

 

 

POWER SOURCE

 

 

 

 

230 - 208V / 1 Phase / 60Hz

 

 

 

PERFORMANCE

 

 

Cooling

 

 

 

 

 

 

 

Heating

 

 

 

Capacity * [minimum~muximum]

 

BTU / h

39,500 [9,500~39,500]

 

 

48,000 [8,000~48,000]

 

 

 

 

 

(17˚F)**

 

BTU / h

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

31,800

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Moisture removal (High)

 

 

Pints / h

 

12.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air circulation (H / M / L) 230 V

 

CFM

 

 

 

 

 

 

 

 

1050 / 840 / 720

 

 

 

 

 

 

 

External Static Pressure

 

 

in. WG

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S.E.E.R. / H.S.P.F. (Region 4)

 

BTU / Wh

 

14.6

 

 

 

 

 

 

 

 

9.7

 

 

 

ELECTRICAL RATINGS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Voltage rating

 

 

V

230

 

 

 

 

 

 

 

208

 

 

230

 

 

208

 

 

 

Available voltage range

 

 

V

VAC 187 - 253

 

 

 

VAC 187 - 253

 

 

 

Max. Running amperes*

 

 

A

23.0

 

 

 

 

 

 

 

25.4

 

 

22.4

 

 

24.8

 

 

 

Power input

 

 

W

4,520

 

 

 

4,520

 

 

4,360

 

 

4,360

 

 

 

 

 

(17˚F)**

 

W

 

 

 

 

 

 

 

 

 

 

 

 

3,540

 

 

3,540

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Back-up Heater

 

 

kW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

Maximum overcurrent protection (Indoor/Outdoor)

 

A

 

 

 

 

 

 

 

 

15 / 40

 

 

 

 

 

 

FEATURES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Controls

 

 

 

 

 

 

 

 

 

 

 

 

Microprocessor

 

 

 

 

 

 

 

Low ambient control

 

 

 

 

 

 

 

 

 

 

 

 

Built-in 0˚F

 

 

 

 

 

 

 

Fan speeds Indoor / Outdoor

 

 

3 and Automatic control / Variable

 

 

 

Wired Remote Controller

 

 

 

 

 

 

 

 

 

 

 

 

CZ-RTC2

 

 

 

 

 

 

 

Optional Wireless Remote Controller

 

 

 

 

 

 

 

 

 

 

CZ-RWSU2U

 

 

 

 

 

 

 

Air deflection (Horizontal / Vertical )

 

 

 

 

 

 

 

 

 

 

/ Automatic (Vertical )

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air filter

 

 

 

 

 

 

Washable, long life (2,500 hr)

 

 

 

Drain pump (Drain connection)

 

Max.head 2-33/64 in. above drain connection (25A , OD32mm)

 

 

 

Compressor

 

 

 

 

 

 

 

 

 

 

 

 

Rotary

 

 

 

 

 

 

 

Operation sound

Indoor - Hi/Me/Lo

 

dB - A

 

 

 

 

 

 

 

 

45 / 38 / 34

 

 

 

 

 

 

 

 

 

Outdoor - Hi

 

dB - A

 

 

 

 

 

 

 

 

 

 

 

53

 

 

 

 

 

 

 

Refrigerant control

 

 

 

 

Electronic Expansion Valve (MOV)

 

 

 

REFRIGERANT TUBING

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Limit of tubing length

 

 

ft. (m)

 

 

 

 

 

 

 

 

165 (50)

 

 

 

 

 

 

 

Limit of tubing length at shipment

 

ft. (m)

 

 

 

 

 

 

 

 

10~100 (3~30)

 

 

 

 

 

 

 

Limit of elevation difference

 

ft. (m)

Outdoor unit is higher than indoor unit : 100 (30)

 

 

 

between the two units

 

 

ft. (m)

Outdoor unit is lower than indoor unit : 50 (15)

 

 

 

Refrigerant tube

Narrow tube

 

in. (mm)

 

 

 

 

 

 

 

 

3 / 8 (9.52)

 

 

 

 

 

 

 

outer diameter

Wide tube

 

in. (mm)

 

 

 

 

 

 

 

 

5 / 8 (15.88)

 

 

 

 

 

 

 

Refrigerant amount at shipment

 

lbs. (kg)

 

 

 

 

 

 

 

 

7.9 (3.6) - R410A

 

 

 

 

 

 

 

DIMENSIONS & WEIGHT

 

 

 

Indoor unit (Include panel)

Outdoor unit

 

 

 

Unit dimensions

Height

 

in. (mm)

 

14-31/64 (368)

 

 

 

 

 

48-7/16 (1,230 )

 

 

 

 

 

Width

 

in. (mm)

 

45-9/32 (1,150)

 

 

 

 

37 (940)

 

 

 

 

 

Depth

 

in. (mm)

 

33-55/64 (860)

 

 

 

 

 

13- 3/8 (340)

 

 

 

Package dimensions

 

 

 

Body

 

Panel

Outdoor unit

 

 

 

 

 

Height

 

in. (mm)

14-31/64 (368)

 

 

4-3/32 (104)

52-3/8 (1,330 )

 

 

 

 

 

Width

 

in. (mm)

44-19/64 (1,125)

 

49-31/64 (1,257)

3931/32 (1,015)

 

 

 

 

 

Depth

 

in. (mm)

33-9/32 (845)

 

 

39-21/64 (999)

16- 3/32 (409)

 

 

 

Net weight

 

 

lbs. (kg)

60 (27)

 

 

 

 

 

16 (7)

220 (100)

 

 

 

Shipping weight

 

 

lbs. (kg)

71 (32)

 

 

 

 

 

22 (10)

240 (109 )

 

 

 

Shipping volume

 

 

cu.ft. (m3 )

12.4 (0.350)

 

 

4.6 (0.131)

19.5 (0.552 )

 

 

 

 

 

 

 

 

DATA SUBJECT

TO CHANGE

WITHOUT NOTICE.

Cooling:

Rating conditions (*) : Room temperature 80 °F DB / 67 °F WB, Ambient temperature 95 °F DB / 75 °F WB

Heating:

Rating conditions (*) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 47 °F DB / 43 °F WB Low temp conditions (**) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 17 °F DB / 15 °F WB

1-6

1. Specifications

1-1. Unit Specifications

4-Way Cassette (Type U1)

 

MODEL No.

 

Indoor Unit

 

 

 

 

S-26PU1U6

 

 

 

 

 

 

Outdoor Unit

 

 

 

 

U-26PS1U6

 

 

 

 

 

POWER SOURCE

 

230 - 208V / 1 Phase / 60Hz

 

 

 

PERFORMANCE

 

 

 

 

Cooling

 

 

 

 

Capacity * [minimum~muximum]

 

BTU / h

24,800 [9,500~24,800]

 

 

 

 

 

(17˚F)**

 

BTU / h

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Moisture removal (High)

 

 

Pints / h

 

 

8.1

 

 

 

 

Air circulation (H / M / L) 230 V

 

CFM

 

 

710 / 530 / 450

 

 

 

 

External Static Pressure

 

 

in. WG

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S.E.E.R. / H.S.P.F. (Region 4)

 

BTU / Wh

 

 

14.1

 

 

 

 

ELECTRICAL RATINGS

 

 

 

 

 

 

 

 

 

 

 

 

 

Voltage rating

 

 

V

230

 

 

 

 

 

208

 

 

 

Available voltage range

 

 

V

 

 

 

VAC 187 - 253

 

 

 

 

Max. Running amperes*

 

 

A

15.6

 

 

 

 

 

17.3

 

 

 

Power input

 

 

W

2,920

 

 

 

 

 

2,920

 

 

 

 

 

(17˚F)**

 

W

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Back-up Heater

 

 

kW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Maximum overcurrent protection (Indoor/Outdoor)

 

A

 

 

15 / 30

 

 

1

 

FEATURES

 

 

 

 

 

 

 

 

 

 

 

 

 

Controls

 

 

 

 

 

 

Microprocessor

 

 

 

 

Low ambient control

 

 

 

 

 

 

Built-in 0˚F

 

 

 

 

Fan speeds Indoor / Outdoor

 

3 and Automatic control / Variable

 

 

 

Wired Remote Controller

 

 

 

 

 

 

CZ-RTC2

 

 

 

 

Optional Wireless Remote Controller

 

 

 

 

CZ-RWSU2U

 

 

 

 

Air deflection (Horizontal / Vertical )

 

 

 

 

/ Automatic (Vertical )

 

 

 

 

 

 

 

Air filter

 

 

 

Washable, long life (2,500 hr)

 

 

 

Drain pump (Drain connection)

 

Max.head 2-33/64 in. above drain connection (25A , OD32mm)

 

 

 

Compressor

 

 

 

 

 

 

Rotary

 

 

 

 

Operation sound

Indoor - Hi/Me/Lo

 

dB - A

 

 

38 / 35 / 31

 

 

 

 

 

 

Outdoor - Hi

 

dB - A

 

 

49

 

 

 

 

Refrigerant control

 

 

 

Electronic Expansion Valve (MOV)

 

 

 

REFRIGERANT TUBING

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Limit of tubing length

 

 

ft. (m)

 

 

165 (50)

 

 

 

 

Limit of tubing length at shipment

 

ft. (m)

 

 

10~100 (3~30)

 

 

 

 

Limit of elevation difference

 

ft. (m)

Outdoor unit is higher than indoor unit : 100 (30)

 

 

 

between the two units

 

 

ft. (m)

Outdoor unit is lower than indoor unit : 50 (15)

 

 

 

Refrigerant tube

Narrow tube

 

in. (mm)

 

 

3 / 8 (9.52)

 

 

 

 

outer diameter

Wide tube

 

in. (mm)

 

 

5 / 8 (15.88)

 

 

 

 

Refrigerant amount at shipment

 

lbs. (kg)

 

 

4.2 (1.9) - R410A

 

 

 

 

DIMENSIONS & WEIGHT

 

 

 

Indoor unit (Include panel)

Outdoor unit

 

 

 

Unit dimensions

Height

 

in. (mm)

13-5/16 (338)

 

 

 

3023/32 (780)

 

 

 

 

 

Width

 

in. (mm)

33-55/64 (860)

 

 

 

37 (940)

 

 

 

 

 

Depth

 

in. (mm)

33-55/64 (860)

 

 

 

13- 3/8 (340)

 

 

 

Package dimensions

 

 

 

Body

 

Panel

Outdoor unit

 

 

 

 

 

Height

 

in. (mm)

13-5/16 (338)

 

4-3/32 (104)

3431/32 (888)

 

 

 

 

 

Width

 

in. (mm)

32-7/8 (835)

 

37-61/64 (964)

3931/32 (1,015)

 

 

 

 

 

Depth

 

in. (mm)

33-9/32 (845)

 

39-21/64 (999)

16- 3/32 (409)

 

 

 

Net weight

 

 

lbs. (kg)

49 (22)

 

 

11 (5)

128 (58)

 

 

 

Shipping weight

 

 

lbs. (kg)

57 (26)

 

 

18 (8)

148 (67)

 

 

 

Shipping volume

 

 

cu.ft. (m3 )

8.4 (0.238)

 

 

3.6 (0.100)

13.0 (0.369)

 

 

 

 

 

 

 

 

DATA SUBJECT

TO CHANGE

WITHOUT NOTICE.

 

 

Cooling:

Rating conditions (*) : Room temperature 80 °F DB / 67 °F WB, Ambient temperature 95 °F DB / 75 °F WB

Heating:

Rating conditions (*) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 47 °F DB / 43 °F WB Low temp conditions (**) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 17 °F DB / 15 °F WB

1-7

1. Specifications

1-1. Unit Specifications

4-Way Cassette (Type U1)

 

 

 

MODEL No.

 

Indoor Unit

 

 

 

 

 

S-36PU1U6

 

 

 

 

 

 

Outdoor Unit

 

 

 

 

 

U-36PS1U6

 

 

 

 

 

POWER SOURCE

 

230 - 208V / 1 Phase / 60Hz

 

 

 

PERFORMANCE

 

 

 

 

 

Cooling

 

 

 

 

Capacity * [minimum~muximum]

 

BTU / h

32,600 [9,500~32,600]

 

 

 

 

 

(17˚F)**

 

BTU / h

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Moisture removal (High)

 

 

Pints / h

 

 

 

10.6

 

 

 

 

Air circulation (H / M / L) 230 V

 

CFM

 

 

 

1050 / 840 / 720

 

 

 

 

External Static Pressure

 

 

in. WG

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S.E.E.R. / H.S.P.F. (Region 4)

 

BTU / Wh

 

 

 

14.6

 

 

 

 

ELECTRICAL RATINGS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Voltage rating

 

 

V

230

 

 

 

 

 

 

208

 

 

 

Available voltage range

 

 

V

 

 

 

 

VAC 187 - 253

 

 

 

 

Max. Running amperes*

 

 

A

18.7

 

 

 

 

 

 

20.7

 

 

 

Power input

 

 

W

3,950

 

 

 

 

 

 

3,950

 

 

 

 

 

(17˚F)**

 

W

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Back-up Heater

 

 

kW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

Maximum overcurrent protection (Indoor/Outdoor)

 

A

 

 

 

15 / 30

 

 

 

FEATURES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Controls

 

 

 

 

 

 

 

Microprocessor

 

 

 

 

Low ambient control

 

 

 

 

 

 

 

Built-in 0˚F

 

 

 

 

Fan speeds Indoor / Outdoor

 

3 and Automatic control / Variable

 

 

 

Wired Remote Controller

 

 

 

 

 

 

 

CZ-RTC2

 

 

 

 

Optional Wireless Remote Controller

 

 

 

 

 

CZ-RWSU2U

 

 

 

 

Air deflection (Horizontal / Vertical )

 

 

 

 

 

/ Automatic (Vertical )

 

 

 

 

 

 

 

 

 

 

Air filter

 

 

 

Washable, long life (2,500 hr)

 

 

 

Drain pump (Drain connection)

 

Max.head 2-33/64 in. above drain connection (25A , OD32mm)

 

 

 

Compressor

 

 

 

 

 

 

 

Rotary

 

 

 

 

Operation sound

Indoor - Hi/Me/Lo

 

dB - A

 

 

 

44 / 37 / 33

 

 

 

 

 

 

Outdoor - Hi

 

dB - A

 

 

 

52

 

 

 

 

Refrigerant control

 

 

 

Electronic Expansion Valve (MOV)

 

 

 

REFRIGERANT TUBING

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Limit of tubing length

 

 

ft. (m)

 

 

 

165 (50)

 

 

 

 

Limit of tubing length at shipment

 

ft. (m)

 

 

 

10~100 (3~30)

 

 

 

 

Limit of elevation difference

 

ft. (m)

Outdoor unit is higher than indoor unit : 100 (30)

 

 

 

between the two units

 

 

ft. (m)

Outdoor unit is lower than indoor unit : 50 (15)

 

 

 

Refrigerant tube

Narrow tube

 

in. (mm)

 

 

 

3 / 8 (9.52)

 

 

 

 

outer diameter

Wide tube

 

in. (mm)

 

 

 

5 / 8 (15.88)

 

 

 

 

Refrigerant amount at shipment

 

lbs. (kg)

 

 

 

6.2 (2.8) - R410A

 

 

 

 

DIMENSIONS & WEIGHT

 

 

 

Indoor unit (Include panel)

Outdoor unit

 

 

 

Unit dimensions

Height

 

in. (mm)

14-31/64 (368)

 

 

 

3023/32 (780)

 

 

 

 

 

Width

 

in. (mm)

45-9/32 (1,150)

 

 

 

37 (940)

 

 

 

 

 

Depth

 

in. (mm)

33-55/64 (860)

 

 

 

13- 3/8 (340)

 

 

 

Package dimensions

 

 

 

Body

 

Panel

Outdoor unit

 

 

 

 

 

Height

 

in. (mm)

14-31/64 (368)

 

 

4-3/32 (104)

3431/32 (888)

 

 

 

 

 

Width

 

in. (mm)

44-19/64 (1,125)

 

49-31/64 (1,257)

3931/32 (1,015)

 

 

 

 

 

Depth

 

in. (mm)

33-9/32 (845)

 

 

39-21/64 (999)

16- 3/32 (409)

 

 

 

Net weight

 

 

lbs. (kg)

60 (27)

 

 

 

16 (7)

143 (65)

 

 

 

Shipping weight

 

 

lbs. (kg)

71 (32)

 

 

 

22 (10)

161 (73)

 

 

 

Shipping volume

 

 

cu.ft. (m3 )

12.4 (0.350)

 

 

4.6 (0.131)

13.0 (0.369)

 

 

 

 

 

 

 

 

DATA SUBJECT

TO CHANGE

WITHOUT NOTICE.

Cooling:

Rating conditions (*) : Room temperature 80 °F DB / 67 °F WB, Ambient temperature 95 °F DB / 75 °F WB

Heating:

Rating conditions (*) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 47 °F DB / 43 °F WB Low temp conditions (**) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 17 °F DB / 15 °F WB

1-8

1. Specifications

1-1. Unit Specifications

4-Way Cassette (Type U1)

 

MODEL No.

 

Indoor Unit

 

 

 

 

 

S-42PU1U6

 

 

 

 

 

 

Outdoor Unit

 

 

 

 

 

U-42PS1U6

 

 

 

 

 

POWER SOURCE

 

230 - 208V / 1 Phase / 60Hz

 

 

 

PERFORMANCE

 

 

 

 

 

Cooling

 

 

 

 

Capacity * [minimum~muximum]

 

BTU / h

39,500 [9,500~39,500]

 

 

 

 

 

(17˚F)**

 

BTU / h

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Moisture removal (High)

 

 

Pints / h

 

 

 

12.6

 

 

 

 

Air circulation (H / M / L) 230 V

 

CFM

 

 

 

1050 / 840 / 720

 

 

 

 

External Static Pressure

 

 

in. WG

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S.E.E.R. / H.S.P.F. (Region 4)

 

BTU / Wh

 

 

 

14.6

 

 

 

 

ELECTRICAL RATINGS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Voltage rating

 

 

V

230

 

 

 

 

 

 

208

 

 

 

Available voltage range

 

 

V

 

 

 

 

VAC 187 - 253

 

 

 

 

Max. Running amperes*

 

 

A

23.0

 

 

 

 

 

 

25.4

 

 

 

Power input

 

 

W

4,520

 

 

 

 

 

 

4,520

 

 

 

 

 

(17˚F)**

 

W

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Back-up Heater

 

 

kW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Maximum overcurrent protection (Indoor/Outdoor)

 

A

 

 

 

15 / 35

 

 

1

 

FEATURES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Controls

 

 

 

 

 

 

 

Microprocessor

 

 

 

 

Low ambient control

 

 

 

 

 

 

 

Built-in 0˚F

 

 

 

 

Fan speeds Indoor / Outdoor

 

3 and Automatic control / Variable

 

 

 

Wired Remote Controller

 

 

 

 

 

 

 

CZ-RTC2

 

 

 

 

Optional Wireless Remote Controller

 

 

 

 

 

CZ-RWSU2U

 

 

 

 

Air deflection (Horizontal / Vertical )

 

 

 

 

 

/ Automatic (Vertical )

 

 

 

 

 

 

 

 

Air filter

 

 

 

Washable, long life (2,500 hr)

 

 

 

Drain pump (Drain connection)

 

Max.head 2-33/64 in. above drain connection (25A , OD32mm)

 

 

 

Compressor

 

 

 

 

 

 

 

Rotary

 

 

 

 

Operation sound

Indoor - Hi/Me/Lo

 

dB - A

 

 

 

45 / 38 / 34

 

 

 

 

 

 

Outdoor - Hi

 

dB - A

 

 

 

53

 

 

 

 

Refrigerant control

 

 

 

Electronic Expansion Valve (MOV)

 

 

 

REFRIGERANT TUBING

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Limit of tubing length

 

 

ft. (m)

 

 

 

165 (50)

 

 

 

 

Limit of tubing length at shipment

 

ft. (m)

 

 

 

10~100 (3~30)

 

 

 

 

Limit of elevation difference

 

ft. (m)

Outdoor unit is higher than indoor unit : 100 (30)

 

 

 

between the two units

 

 

ft. (m)

Outdoor unit is lower than indoor unit : 50 (15)

 

 

 

Refrigerant tube

Narrow tube

 

in. (mm)

 

 

 

3 / 8 (9.52)

 

 

 

 

outer diameter

Wide tube

 

in. (mm)

 

 

 

5 / 8 (15.88)

 

 

 

 

Refrigerant amount at shipment

 

lbs. (kg)

 

 

 

7.9 (3.6) - R410A

 

 

 

 

DIMENSIONS & WEIGHT

 

 

 

Indoor unit (Include panel)

Outdoor unit

 

 

 

Unit dimensions

Height

 

in. (mm)

14-31/64 (368)

 

 

 

48-7/16 (1,230 )

 

 

 

 

 

Width

 

in. (mm)

45-9/32 (1,150)

 

 

 

37 (940)

 

 

 

 

 

Depth

 

in. (mm)

33-55/64 (860)

 

 

 

13- 3/8 (340)

 

 

 

Package dimensions

 

 

 

Body

 

Panel

Outdoor unit

 

 

 

 

 

Height

 

in. (mm)

14-31/64 (368)

 

 

4-3/32 (104)

52-3/8 (1,330 )

 

 

 

 

 

Width

 

in. (mm)

44-19/64 (1,125)

 

49-31/64 (1,257)

3931/32 (1,015)

 

 

 

 

 

Depth

 

in. (mm)

33-9/32 (845)

 

 

39-21/64 (999)

16- 3/32 (409)

 

 

 

Net weight

 

 

lbs. (kg)

60 (27)

 

 

 

16 (7)

220 (100)

 

 

 

Shipping weight

 

 

lbs. (kg)

71 (32)

 

 

 

22 (10)

240 (109 )

 

 

 

Shipping volume

 

 

cu.ft. (m3 )

12.4 (0.350)

 

 

4.6 (0.131)

19.5 (0.552 )

 

 

 

 

 

 

 

 

DATA SUBJECT

TO CHANGE

WITHOUT NOTICE.

 

 

Cooling:

Rating conditions (*) : Room temperature 80 °F DB / 67 °F WB, Ambient temperature 95 °F DB / 75 °F WB

Heating:

Rating conditions (*) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 47 °F DB / 43 °F WB Low temp conditions (**) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 17 °F DB / 15 °F WB

1-9

1. Specifications

1-1. Unit Specifications

Wall Mounted (Type K1)

 

 

 

MODEL No.

 

Indoor Unit

 

 

 

 

 

 

 

 

 

S-26PK1U6

 

 

 

 

 

 

Outdoor Unit

 

 

 

 

 

 

 

 

 

U-26PE1U6

 

 

 

 

 

POWER SOURCE

 

 

 

230 - 208V / 1 Phase / 60Hz

 

 

 

 

PERFORMANCE

 

 

Cooling

 

 

 

 

Heating

 

 

 

Capacity * [minimum~muximum]

 

BTU / h

25,200 [9,500~25,200]

 

29,200 [8,000~29,200]

 

 

 

 

 

(17˚F)**

 

BTU / h

 

 

 

 

 

 

 

 

 

 

17,200

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Moisture removal (High)

 

 

Pints / h

 

8.1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air circulation (H / M / L) 230 V

 

CFM

 

559 / 475 / 390

 

 

 

 

 

 

 

External Static Pressure

 

 

in. WG

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S.E.E.R. / H.S.P.F. (Region 4)

 

BTU / Wh

 

14.9

 

 

 

 

10.2

 

 

 

 

ELECTRICAL RATINGS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Voltage rating

 

 

V

230

 

 

208

 

230

 

 

 

208

 

 

 

Available voltage range

 

 

V

VAC 187 - 253

 

 

 

 

VAC 187 - 253

 

 

 

Max. Running amperes*

 

 

A

15.3

 

 

16.9

 

14.0

 

 

 

15.5

 

 

 

Power input

 

 

W

2,840

 

 

2,840

 

2,620

 

 

 

2,620

 

 

 

 

 

(17˚F)**

 

W

 

 

 

 

 

 

 

 

 

 

2,030

 

 

 

2,030

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Back-up Heater

 

 

kW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

Maximum overcurrent protection (Indoor/Outdoor)

 

A

 

15 / 30

 

 

 

 

 

 

FEATURES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Controls

 

 

 

 

 

 

 

 

 

 

 

Microprocessor

 

 

 

 

Low ambient control

 

 

 

 

 

 

 

 

 

 

 

Built-in 0˚F

 

 

 

 

Fan speeds Indoor / Outdoor

 

 

3 and Automatic control / Variable

 

 

 

 

Optional Wired Remote Controller

 

 

 

 

 

 

 

 

 

CZ-RTC2

 

 

 

 

Wireless Remote Controller

 

 

 

 

 

 

 

 

 

CZ-RWSK1U

 

 

 

 

Air deflection (Horizontal / Vertical )

 

 

 

 

 

 

 

 

/ Automatic (Vertical )

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air filter

 

 

 

 

 

 

 

 

 

 

 

Washable

 

 

 

 

Drain pump (Drain connection)

 

 

 

 

 

 

 

 

 

(20A , OD26mm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor

 

 

 

 

 

 

 

 

 

 

 

Rotary

 

 

 

 

Operation sound

Indoor - Hi/Me/Lo

 

dB - A

 

48 / 42 / 38

 

 

 

 

 

 

 

 

 

Outdoor - Hi

 

dB - A

 

 

 

 

 

 

 

 

 

49

 

 

 

 

 

 

 

Refrigerant control

 

 

 

 

Electronic Expansion Valve (MOV)

 

 

 

 

REFRIGERANT TUBING

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Limit of tubing length

 

 

ft. (m)

 

165 (50)

 

 

 

 

 

 

 

Limit of tubing length at shipment

 

ft. (m)

 

10~100 (3~30)

 

 

 

 

 

 

 

Limit of elevation difference

 

ft. (m)

Outdoor unit is higher than indoor unit : 100 (30)

 

 

 

between the two units

 

 

ft. (m)

Outdoor unit is lower than indoor unit : 50 (15)

 

 

 

Refrigerant tube

Narrow tube

 

in. (mm)

 

3 / 8 (9.52)

 

 

 

 

 

 

 

outer diameter

Wide tube

 

in. (mm)

 

5 / 8 (15.88)

 

 

 

 

 

 

 

Refrigerant amount at shipment

 

lbs. (kg)

 

 

 

 

 

 

 

4.2 (1.9) - R410A

 

 

 

 

DIMENSIONS & WEIGHT

 

 

 

Indoor unit

 

 

 

 

Outdoor unit

 

 

 

Unit dimensions

Height

 

in. (mm)

1263/64 (330)

 

3023/32 (780)

 

 

 

 

 

Width

 

in. (mm)

44- 7/8 (1,140)

 

37 (940)

 

 

 

 

 

Depth

 

in. (mm)

8- 31/32 (228)

 

13- 3/8 (340)

 

 

 

Package dimensions

 

 

 

Indoor unit

 

 

 

 

Outdoor unit

 

 

 

 

 

Height

 

in. (mm)

1511/32 (390)

 

3431/32 (888)

 

 

 

 

 

Width

 

in. (mm)

4727/32 (1,215)

 

3931/32 (1,015)

 

 

 

 

 

Depth

 

in. (mm)

1117/32 (293)

 

16- 3/32 (409)

 

 

 

Net weight

 

 

lbs. (kg)

 

40 (18)

 

 

 

128 (58)

 

 

 

Shipping weight

 

 

lbs. (kg)

 

44 (20)

 

 

 

148 (67)

 

 

 

Shipping volume

 

 

cu.ft. (m3 )

4.9 (0.139)

 

 

13.0 (0.369)

DATA SUBJECT TO CHANGE WITHOUT NOTICE.

Cooling:

Rating conditions (*) : Room temperature 80 °F DB / 67 °F WB, Ambient temperature 95 °F DB / 75 °F WB

Heating:

Rating conditions (*) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 47 °F DB / 43 °F WB Low temp conditions (**) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 17 °F DB / 15 °F WB

1-10

1. Specifications

1-1. Unit Specifications

Wall Mounted (Type K1)

 

MODEL No.

 

Indoor Unit

 

 

 

 

 

S-26PK1U6

 

 

 

 

 

Outdoor Unit

 

 

 

 

 

U-26PS1U6

 

 

 

 

POWER SOURCE

 

230 - 208V / 1 Phase / 60Hz

 

 

 

PERFORMANCE

 

 

 

 

 

Cooling

 

 

 

 

Capacity * [minimum~muximum]

 

BTU / h

25,200 [9,500~25,200]

 

 

 

 

 

(17˚F)**

 

BTU / h

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Moisture removal (High)

 

 

Pints / h

8.1

 

 

 

 

Air circulation (H / M / L) 230 V

 

CFM

559 / 475 / 390

 

 

 

External Static Pressure

 

 

in. WG

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S.E.E.R. / H.S.P.F. (Region 4)

 

BTU / Wh

14.9

 

 

 

 

ELECTRICAL RATINGS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Voltage rating

 

 

V

230

 

 

 

 

 

 

208

 

 

 

Available voltage range

 

 

V

 

 

 

 

VAC 187 - 253

 

 

 

Max. Running amperes*

 

 

A

15.3

 

 

 

 

 

 

16.9

 

 

 

Power input

 

 

W

2,840

 

 

 

 

 

 

2,840

 

 

 

 

 

(17˚F)**

 

W

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Back-up Heater

 

 

kW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Maximum overcurrent protection (Indoor/Outdoor)

 

A

15 / 30

 

 

1

 

FEATURES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Controls

 

 

 

 

 

 

 

Microprocessor

 

 

 

Low ambient control

 

 

 

 

 

 

 

Built-in 0˚F

 

 

 

Fan speeds Indoor / Outdoor

 

3 and Automatic control / Variable

 

 

 

Optional Wired Remote Controller

 

 

 

 

 

CZ-RTC2

 

 

 

 

Wireless Remote Controller

 

 

 

 

 

CZ-RWSK1U

 

 

 

Air deflection (Horizontal / Vertical )

 

 

 

 

/ Automatic (Vertical )

 

 

 

 

 

 

 

 

Air filter

 

 

 

 

 

 

 

Washable

 

 

 

Drain pump (Drain connection)

 

 

 

 

 

(20A , OD26mm)

 

 

 

 

 

 

 

 

 

Compressor

 

 

 

 

 

 

 

Rotary

 

 

 

 

Operation sound

Indoor - Hi/Me/Lo

 

dB - A

48 / 42 / 38

 

 

 

 

 

Outdoor - Hi

 

dB - A

49

 

 

 

 

Refrigerant control

 

 

 

Electronic Expansion Valve (MOV)

 

 

 

REFRIGERANT TUBING

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Limit of tubing length

 

 

ft. (m)

165 (50)

 

 

 

 

Limit of tubing length at shipment

 

ft. (m)

10~100 (3~30)

 

 

 

Limit of elevation difference

 

ft. (m)

Outdoor unit is higher than indoor unit : 100 (30)

 

 

 

between the two units

 

 

ft. (m)

Outdoor unit is lower than indoor unit : 50 (15)

 

 

 

Refrigerant tube

Narrow tube

 

in. (mm)

3 / 8 (9.52)

 

 

 

outer diameter

Wide tube

 

in. (mm)

5 / 8 (15.88)

 

 

 

Refrigerant amount at shipment

 

lbs. (kg)

 

 

 

4.2 (1.9) - R410A

 

 

 

DIMENSIONS & WEIGHT

 

 

 

Indoor unit

 

Outdoor unit

 

 

 

Unit dimensions

Height

 

in. (mm)

1263/64 (330)

 

 

 

3023/32 (780)

 

 

 

 

 

Width

 

in. (mm)

44- 7/8 (1,140)

 

 

 

37 (940)

 

 

 

 

 

Depth

 

in. (mm)

8- 31/32 (228)

 

 

 

13- 3/8 (340)

 

 

 

Package dimensions

 

 

 

Indoor unit

 

Outdoor unit

 

 

 

 

 

Height

 

in. (mm)

1511/32 (390)

 

 

 

3431/32 (888)

 

 

 

 

 

Width

 

in. (mm)

4727/32 (1,215)

 

 

 

3931/32 (1,015)

 

 

 

 

 

Depth

 

in. (mm)

1117/32 (293)

 

 

 

16- 3/32 (409)

 

 

 

Net weight

 

 

lbs. (kg)

40 (18)

 

 

 

 

128 (58)

 

 

 

Shipping weight

 

 

lbs. (kg)

44 (20)

 

 

 

 

 

148 (67)

 

 

 

Shipping volume

 

 

cu.ft. (m3 )

4.9 (0.139)

 

 

 

 

13.0 (0.369)

 

 

 

 

 

 

 

 

DATA SUBJECT TO CHANGE WITHOUT NOTICE.

 

 

Cooling:

Rating conditions (*) : Room temperature 80 °F DB / 67 °F WB, Ambient temperature 95 °F DB / 75 °F WB

Heating:

Rating conditions (*) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 47 °F DB / 43 °F WB Low temp conditions (**) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 17 °F DB / 15 °F WB

1-11

1. Specifications

1-1. Unit Specifications

Ceiling (Type T1)

 

 

 

MODEL No.

 

Indoor Unit

 

 

 

 

 

 

 

 

 

 

S-26PT1U6

 

 

 

 

 

 

Outdoor Unit

 

 

 

 

 

 

 

 

 

 

U-26PE1U6

 

 

 

 

 

POWER SOURCE

 

 

 

 

230 - 208V / 1 Phase / 60Hz

 

 

 

 

PERFORMANCE

 

 

Cooling

 

 

 

 

Heating

 

 

 

Capacity * [minimum~muximum]

 

BTU / h

24,400 [9,500~24,400]

 

30,800 [8,000~30,800]

 

 

 

 

 

(17˚F)**

 

BTU / h

 

 

 

 

 

 

 

 

 

 

 

17,900

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Moisture removal (High)

 

 

Pints / h

 

7.7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air circulation (H / M / L) 230 V

 

CFM

 

550 / 490 / 460

 

 

 

 

 

 

 

External Static Pressure

 

 

in. WG

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S.E.E.R. / H.S.P.F. (Region 4)

 

BTU / Wh

 

14.5

 

 

 

 

9.4

 

 

 

 

ELECTRICAL RATINGS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Voltage rating

 

 

V

230

 

208

 

230

 

 

 

208

 

 

 

Available voltage range

 

 

V

VAC 187 - 253

 

 

 

 

VAC 187 - 253

 

 

 

Max. Running amperes* (Without Back-up Heater)

 

A

15.6

 

17.3

 

16.4

 

 

 

18.1

 

 

 

Power input

 

 

W

2,880

 

2,880

 

3,000

 

 

 

3,000

 

 

 

 

 

(17˚F)**

 

W

 

 

 

 

 

 

 

 

 

 

 

2,190

 

 

 

2,190

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Back-up Heater

 

 

kW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

Maximum overcurrent protection (Indoor/Outdoor)

 

A

 

15 / 30

 

 

 

 

 

 

FEATURES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Controls

 

 

 

 

 

 

 

 

 

 

 

Microprocessor

 

 

 

 

Low ambient control

 

 

 

 

 

 

 

 

 

 

 

 

Built-in 0˚F

 

 

 

 

Fan speeds Indoor / Outdoor

 

 

3 and Automatic control / Variable

 

 

 

 

Wired Remote Controller

 

 

 

 

 

 

 

 

 

 

 

 

CZ-RTC2

 

 

 

 

Optional Wireless Remote Controller

 

 

 

 

 

 

 

 

 

 

CZ-RWSU2U

 

 

 

 

Air deflection (Horizontal / Vertical )

 

 

 

 

 

 

 

 

 

/ Automatic (Vertical )

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air filter

 

 

 

 

 

Washable, long life (2,500 hr)

 

 

 

 

Drain pump (Drain connection)

 

 

 

 

 

 

 

 

 

 

(20A , OD26mm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor

 

 

 

 

 

 

 

 

 

 

 

 

Rotary

 

 

 

 

Operation sound

Indoor - Hi/Me/Lo

 

dB - A

 

39 / 37 / 33

 

 

 

 

 

 

 

 

 

Outdoor - Hi

 

dB - A

 

 

 

 

 

 

 

 

 

 

49

 

 

 

 

 

 

 

Refrigerant control

 

 

 

 

Electronic Expansion Valve (MOV)

 

 

 

 

REFRIGERANT TUBING

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Limit of tubing length

 

 

ft. (m)

 

165 (50)

 

 

 

 

 

 

 

Limit of tubing length at shipment

 

ft. (m)

 

10~100 (3~30)

 

 

 

 

 

 

 

Limit of elevation difference

 

ft. (m)

Outdoor unit is higher than indoor unit : 100 (30)

 

 

 

between the two units

 

 

ft. (m)

Outdoor unit is lower than indoor unit : 50 (15)

 

 

 

Refrigerant tube

Narrow tube

 

in. (mm)

 

3 / 8 (9.52)

 

 

 

 

 

 

 

outer diameter

Wide tube

 

in. (mm)

 

5 / 8 (15.88)

 

 

 

 

 

 

 

Refrigerant amount at shipment

 

lbs. (kg)

 

 

 

 

 

 

 

 

4.2 (1.9) - R410A

 

 

 

 

DIMENSIONS & WEIGHT

 

 

 

Indoor unit

 

 

 

 

Outdoor unit

 

 

 

Unit dimensions

Height

 

in. (mm)

7-17/32 (190)

 

3023/32 (780)

 

 

 

 

 

Width

 

in. (mm)

51-3/16 (1,300)

 

37 (940)

 

 

 

 

 

Depth

 

in. (mm)

26-3/8 (670)

 

13- 3/8 (340)

 

 

 

Package dimensions

 

 

 

Indoor unit

 

 

 

 

Outdoor unit

 

 

 

 

 

Height

 

in. (mm)

9-7/16 (240)

 

3431/32 (888)

 

 

 

 

 

Width

 

in. (mm)

54-19/32 (1,387)

 

3931/32 (1,015)

 

 

 

 

 

Depth

 

in. (mm)

31-1/16 (789)

 

16- 3/32 (409)

 

 

 

Net weight

 

 

lbs. (kg)

 

57 (26)

 

 

 

 

128 (58)

 

 

 

Shipping weight

 

 

lbs. (kg)

 

68 (31)

 

 

 

 

148 (67)

 

 

 

Shipping volume

 

 

cu.ft. (m3 )

8.9 (0.253)

 

 

13.0 (0.369)

DATA SUBJECT TO CHANGE WITHOUT NOTICE.

Cooling:

Rating conditions (*) : Room temperature 80 °F DB / 67 °F WB, Ambient temperature 95 °F DB / 75 °F WB

Heating:

Rating conditions (*) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 47 °F DB / 43 °F WB Low temp conditions (**) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 17 °F DB / 15 °F WB

1-12

1. Specifications

1-1. Unit Specifications

Ceiling (Type T1)

 

MODEL No.

 

Indoor Unit

 

 

 

 

 

 

 

 

 

 

S-36PT1U6

 

 

 

 

 

 

Outdoor Unit

 

 

 

 

 

 

 

 

 

 

U-36PE1U6

 

 

 

 

 

POWER SOURCE

 

 

 

 

230 - 208V / 1 Phase / 60Hz

 

 

 

 

PERFORMANCE

 

 

Cooling

 

 

 

 

Heating

 

 

 

Capacity * [minimum~muximum]

 

BTU / h

31,200 [9,500~31,200]

 

37,400 [8,000~37,400]

 

 

 

 

 

(17˚F)**

 

BTU / h

 

 

 

 

 

 

 

 

 

 

 

21,000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Moisture removal (High)

 

 

Pints / h

 

10.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air circulation (H / M / L) 230 V

 

CFM

 

1100 / 930 / 750

 

 

 

 

 

 

 

External Static Pressure

 

 

in. WG

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S.E.E.R. / H.S.P.F. (Region 4)

 

BTU / Wh

 

15.1

 

 

 

 

8.8

 

 

 

 

ELECTRICAL RATINGS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Voltage rating

 

 

V

230

 

 

 

208

 

230

 

 

 

208

 

 

 

Available voltage range

 

 

V

VAC 187 - 253

 

 

 

 

VAC 187 - 253

 

 

 

Max. Running amperes*

 

 

A

18.2

 

 

 

20.1

 

15.6

 

 

 

17.3

 

 

 

Power input

 

 

W

3,840

 

 

 

3,840

 

3,250

 

 

 

3,250

 

 

 

 

 

(17˚F)**

 

W

 

 

 

 

 

 

 

 

 

 

 

2,470

 

 

 

2,470

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Back-up Heater

 

 

kW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Maximum overcurrent protection (Indoor/Outdoor)

 

A

 

15 / 35

 

 

 

 

 

1

 

FEATURES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Controls

 

 

 

 

 

 

 

 

 

 

 

Microprocessor

 

 

 

 

Low ambient control

 

 

 

 

 

 

 

 

 

 

 

 

Built-in 0˚F

 

 

 

 

Fan speeds Indoor / Outdoor

 

 

3 and Automatic control / Variable

 

 

 

 

Wired Remote Controller

 

 

 

 

 

 

 

 

 

 

 

 

CZ-RTC2

 

 

 

 

Optional Wireless Remote Controller

 

 

 

 

 

 

 

 

 

 

CZ-RWSU2U

 

 

 

 

Air deflection (Horizontal / Vertical )

 

 

 

 

 

 

 

 

 

/ Automatic (Vertical )

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air filter

 

 

 

 

 

Washable, long life (2,500 hr)

 

 

 

 

Drain pump (Drain connection)

 

 

 

 

 

 

 

 

 

 

(20A , OD26mm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor

 

 

 

 

 

 

 

 

 

 

 

 

Rotary

 

 

 

 

Operation sound

Indoor - Hi/Me/Lo

 

dB - A

 

42 / 40 / 35

 

 

 

 

 

 

 

 

 

Outdoor - Hi

 

dB - A

 

 

 

 

 

 

 

 

 

 

52

 

 

 

 

 

 

 

Refrigerant control

 

 

 

 

Electronic Expansion Valve (MOV)

 

 

 

 

REFRIGERANT TUBING

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Limit of tubing length

 

 

ft. (m)

 

165 (50)

 

 

 

 

 

 

 

Limit of tubing length at shipment

 

ft. (m)

 

10~100 (3~30)

 

 

 

 

 

 

 

Limit of elevation difference

 

ft. (m)

Outdoor unit is higher than indoor unit : 100 (30)

 

 

 

between the two units

 

 

ft. (m)

Outdoor unit is lower than indoor unit : 50 (15)

 

 

 

Refrigerant tube

Narrow tube

 

in. (mm)

 

3 / 8 (9.52)

 

 

 

 

 

 

 

outer diameter

Wide tube

 

in. (mm)

 

5 / 8 (15.88)

 

 

 

 

 

 

 

Refrigerant amount at shipment

 

lbs. (kg)

 

 

 

 

 

 

 

 

6.2 (2.8) - R410A

 

 

 

 

DIMENSIONS & WEIGHT

 

 

 

Indoor unit

 

 

 

 

Outdoor unit

 

 

 

Unit dimensions

Height

 

in. (mm)

9-7/16 (240)

 

3023/32 (780)

 

 

 

 

 

Width

 

in. (mm)

62-1/32 (1,575)

 

37 (940)

 

 

 

 

 

Depth

 

in. (mm)

26-3/8 (670)

 

13- 3/8 (340)

 

 

 

Package dimensions

 

 

 

Indoor unit

 

 

 

 

Outdoor unit

 

 

 

 

 

Height

 

in. (mm)

12-15/32 (317)

 

3431/32 (888)

 

 

 

 

 

Width

 

in. (mm)

66-1/16 (1,678)

 

3931/32 (1,015)

 

 

 

 

 

Depth

 

in. (mm)

31-1/16 (789)

 

16- 3/32 (409)

 

 

 

Net weight

 

 

lbs. (kg)

 

84 (38)

 

 

 

 

143 (65)

 

 

 

Shipping weight

 

 

lbs. (kg)

 

97 (44)

 

 

 

 

161 (73)

 

 

 

Shipping volume

 

 

cu.ft. (m3 )

14.8 (0.420)

 

13.0 (0.369)

 

 

 

 

 

 

 

 

DATA SUBJECT TO CHANGE WITHOUT NOTICE.

 

 

Cooling:

Rating conditions (*) : Room temperature 80 °F DB / 67 °F WB, Ambient temperature 95 °F DB / 75 °F WB

Heating:

Rating conditions (*) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 47 °F DB / 43 °F WB Low temp conditions (**) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 17 °F DB / 15 °F WB

1-13

1. Specifications

1-1. Unit Specifications

Ceiling (Type T1)

 

 

 

MODEL No.

 

Indoor Unit

 

 

 

 

 

 

 

 

 

 

S-42PT1U6

 

 

 

 

 

 

Outdoor Unit

 

 

 

 

 

 

 

 

 

 

U-42PE1U6

 

 

 

 

 

POWER SOURCE

 

 

 

 

230 - 208V / 1 Phase / 60Hz

 

 

 

 

PERFORMANCE

 

 

Cooling

 

 

 

 

Heating

 

 

 

Capacity * [minimum~muximum]

 

BTU / h

39,000 [9,500~39,000]

 

44,500 [8,000~44,500]

 

 

 

 

 

(17˚F)**

 

BTU / h

 

 

 

 

 

 

 

 

 

 

 

28,800

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Moisture removal (High)

 

 

Pints / h

 

12.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air circulation (H / M / L) 230 V

 

CFM

 

1130 / 950 / 775

 

 

 

 

 

 

 

External Static Pressure

 

 

in. WG

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S.E.E.R. / H.S.P.F. (Region 4)

 

BTU / Wh

 

15.6

 

 

 

 

9.5

 

 

 

 

ELECTRICAL RATINGS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Voltage rating

 

 

V

230

 

 

 

208

 

230

 

 

 

208

 

 

 

Available voltage range

 

 

V

VAC 187 - 253

 

 

 

 

VAC 187 - 253

 

 

 

Max. Running amperes*

 

 

A

21.1

 

 

 

23.3

 

18.6

 

 

 

20.6

 

 

 

Power input

 

 

W

4,140

 

 

 

4,140

 

3,630

 

 

 

3,630

 

 

 

 

 

(17˚F)**

 

W

 

 

 

 

 

 

 

 

 

 

 

3,110

 

 

 

3,110

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Back-up Heater

 

 

kW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

Maximum overcurrent protection (Indoor/Outdoor)

 

A

 

15 / 40

 

 

 

 

 

 

FEATURES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Controls

 

 

 

 

 

 

 

 

 

 

 

Microprocessor

 

 

 

 

Low ambient control

 

 

 

 

 

 

 

 

 

 

 

 

Built-in 0˚F

 

 

 

 

Fan speeds Indoor / Outdoor

 

 

3 and Automatic control / Variable

 

 

 

 

Wired Remote Controller

 

 

 

 

 

 

 

 

 

 

 

 

CZ-RTC2

 

 

 

 

Optional Wireless Remote Controller

 

 

 

 

 

 

 

 

 

 

CZ-RWSU2U

 

 

 

 

Air deflection (Horizontal / Vertical )

 

 

 

 

 

 

 

 

 

/ Automatic (Vertical )

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air filter

 

 

 

 

 

Washable, long life (2,500 hr)

 

 

 

 

Drain pump (Drain connection)

 

 

 

 

 

 

 

 

 

 

(20A , OD26mm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor

 

 

 

 

 

 

 

 

 

 

 

 

Rotary

 

 

 

 

Operation sound

Indoor - Hi/Me/Lo

 

dB - A

 

44 / 41 / 37

 

 

 

 

 

 

 

 

 

Outdoor - Hi

 

dB - A

 

 

 

 

 

 

 

 

 

 

53

 

 

 

 

 

 

 

Refrigerant control

 

 

 

 

Electronic Expansion Valve (MOV)

 

 

 

 

REFRIGERANT TUBING

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Limit of tubing length

 

 

ft. (m)

 

165 (50)

 

 

 

 

 

 

 

Limit of tubing length at shipment

 

ft. (m)

 

10~100 (3~30)

 

 

 

 

 

 

 

Limit of elevation difference

 

ft. (m)

Outdoor unit is higher than indoor unit : 100 (30)

 

 

 

between the two units

 

 

ft. (m)

Outdoor unit is lower than indoor unit : 50 (15)

 

 

 

Refrigerant tube

Narrow tube

 

in. (mm)

 

3 / 8 (9.52)

 

 

 

 

 

 

 

outer diameter

Wide tube

 

in. (mm)

 

5 / 8 (15.88)

 

 

 

 

 

 

 

Refrigerant amount at shipment

 

lbs. (kg)

 

 

 

 

 

 

 

 

7.9 (3.6) - R410A

 

 

 

 

DIMENSIONS & WEIGHT

 

 

 

Indoor unit

 

 

 

 

Outdoor unit

 

 

 

Unit dimensions

Height

 

in. (mm)

9-7/16 (240)

 

48-7/16 (1,230 )

 

 

 

 

 

Width

 

in. (mm)

62-1/32 (1,575)

 

37 (940)

 

 

 

 

 

Depth

 

in. (mm)

26-3/8 (670)

 

13- 3/8 (340)

 

 

 

Package dimensions

 

 

 

Indoor unit

 

 

 

 

Outdoor unit

 

 

 

 

 

Height

 

in. (mm)

12-15/32 (317)

 

52-3/8 (1,330 )

 

 

 

 

 

Width

 

in. (mm)

66-1/16 (1,678)

 

3931/32 (1,015)

 

 

 

 

 

Depth

 

in. (mm)

31-1/16 (789)

 

16- 3/32 (409)

 

 

 

Net weight

 

 

lbs. (kg)

 

84 (38)

 

 

 

 

220 (100)

 

 

 

Shipping weight

 

 

lbs. (kg)

 

97 (44)

 

 

 

 

240 (109 )

 

 

 

Shipping volume

 

 

cu.ft. (m3 )

14.8 (0.420)

 

19.5 (0.552 )

DATA SUBJECT TO CHANGE WITHOUT NOTICE.

Cooling:

Rating conditions (*) : Room temperature 80 °F DB / 67 °F WB, Ambient temperature 95 °F DB / 75 °F WB

Heating:

Rating conditions (*) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 47 °F DB / 43 °F WB Low temp conditions (**) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 17 °F DB / 15 °F WB

1-14

1. Specifications

1-1. Unit Specifications

Ceiling (Type T1)

 

MODEL No.

 

Indoor Unit

 

 

 

 

 

S-26PT1U6

 

 

 

 

 

 

Outdoor Unit

 

 

 

 

 

U-26PS1U6

 

 

 

 

 

POWER SOURCE

 

230 - 208V / 1 Phase / 60Hz

 

 

 

PERFORMANCE

 

 

 

 

 

Cooling

 

 

 

 

Capacity * [minimum~muximum]

 

BTU / h

24,400 [9,500~24,400]

 

 

 

 

 

(17˚F)**

 

BTU / h

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Moisture removal (High)

 

 

Pints / h

7.7

 

 

 

 

Air circulation (H / M / L) 230 V

 

CFM

550 / 490 / 460

 

 

 

External Static Pressure

 

 

in. WG

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S.E.E.R. / H.S.P.F. (Region 4)

 

BTU / Wh

14.5

 

 

 

 

ELECTRICAL RATINGS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Voltage rating

 

 

V

230

 

 

 

 

 

 

208

 

 

 

Available voltage range

 

 

V

 

 

 

VAC 187 - 253

 

 

 

Max. Running amperes* (Without Back-up Heater)

 

A

15.6

 

 

 

 

 

 

17.3

 

 

 

Power input

 

 

W

2,880

 

 

 

 

 

 

2,880

 

 

 

 

 

(17˚F)**

 

W

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Back-up Heater

 

 

kW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Maximum overcurrent protection (Indoor/Outdoor)

 

A

15 / 30

 

 

1

 

FEATURES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Controls

 

 

 

 

 

 

Microprocessor

 

 

 

Low ambient control

 

 

 

 

 

 

 

Built-in 0˚F

 

 

 

Fan speeds Indoor / Outdoor

 

3 and Automatic control / Variable

 

 

 

Wired Remote Controller

 

 

 

 

 

 

 

CZ-RTC2

 

 

 

 

Optional Wireless Remote Controller

 

 

 

 

 

CZ-RWSU2U

 

 

 

Air deflection (Horizontal / Vertical )

 

 

 

 

/ Automatic (Vertical )

 

 

 

 

 

 

 

 

Air filter

 

 

 

Washable, long life (2,500 hr)

 

 

 

Drain pump (Drain connection)

 

 

 

 

 

(20A , OD26mm)

 

 

 

 

 

 

 

 

 

Compressor

 

 

 

 

 

 

 

Rotary

 

 

 

 

Operation sound

Indoor - Hi/Me/Lo

 

dB - A

39 / 37 / 33

 

 

 

 

 

Outdoor - Hi

 

dB - A

49

 

 

 

 

Refrigerant control

 

 

 

Electronic Expansion Valve (MOV)

 

 

 

REFRIGERANT TUBING

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Limit of tubing length

 

 

ft. (m)

165 (50)

 

 

 

 

Limit of tubing length at shipment

 

ft. (m)

10~100 (3~30)

 

 

 

Limit of elevation difference

 

ft. (m)

Outdoor unit is higher than indoor unit : 100 (30)

 

 

 

between the two units

 

 

ft. (m)

Outdoor unit is lower than indoor unit : 50 (15)

 

 

 

Refrigerant tube

Narrow tube

 

in. (mm)

3 / 8 (9.52)

 

 

 

outer diameter

Wide tube

 

in. (mm)

5 / 8 (15.88)

 

 

 

Refrigerant amount at shipment

 

lbs. (kg)

 

 

4.2 (1.9) - R410A

 

 

 

DIMENSIONS & WEIGHT

 

 

 

Indoor unit

 

Outdoor unit

 

 

 

Unit dimensions

Height

 

in. (mm)

7-17/32 (190)

 

 

 

3023/32 (780)

 

 

 

 

 

Width

 

in. (mm)

51-3/16 (1,300)

 

 

 

37 (940)

 

 

 

 

 

Depth

 

in. (mm)

26-3/8 (670)

 

 

 

 

13- 3/8 (340)

 

 

 

Package dimensions

 

 

 

Indoor unit

 

Outdoor unit

 

 

 

 

 

Height

 

in. (mm)

9-7/16 (240)

 

 

 

 

3431/32 (888)

 

 

 

 

 

Width

 

in. (mm)

54-19/32 (1,387)

 

 

 

3931/32 (1,015)

 

 

 

 

 

Depth

 

in. (mm)

31-1/16 (789)

 

 

 

16- 3/32 (409)

 

 

 

Net weight

 

 

lbs. (kg)

57 (26)

 

 

 

 

 

 

128 (58)

 

 

 

Shipping weight

 

 

lbs. (kg)

68 (31)

 

 

 

 

 

 

148 (67)

 

 

 

Shipping volume

 

 

cu.ft. (m3 )

8.9 (0.253)

 

 

 

 

13.0 (0.369)

 

 

 

 

 

 

 

 

DATA SUBJECT TO CHANGE WITHOUT NOTICE.

 

 

Cooling:

Rating conditions (*) : Room temperature 80 °F DB / 67 °F WB, Ambient temperature 95 °F DB / 75 °F WB

Heating:

Rating conditions (*) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 47 °F DB / 43 °F WB Low temp conditions (**) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 17 °F DB / 15 °F WB

1-15

1. Specifications

1-1. Unit Specifications

Ceiling (Type T1)

 

 

 

MODEL No.

 

Indoor Unit

 

 

 

 

 

S-36PT1U6

 

 

 

 

 

Outdoor Unit

 

 

 

 

 

U-36PS1U6

 

 

 

 

POWER SOURCE

 

230 - 208V / 1 Phase / 60Hz

 

 

 

PERFORMANCE

 

 

 

 

 

 

Cooling

 

 

 

Capacity * [minimum~muximum]

 

BTU / h

31,200 [9,500~31,200]

 

 

 

 

 

(17˚F)**

 

BTU / h

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Moisture removal (High)

 

 

Pints / h

 

 

 

 

 

10.0

 

 

 

Air circulation (H / M / L) 230 V

 

CFM

1100 / 930 / 750

 

 

 

External Static Pressure

 

 

in. WG

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S.E.E.R. / H.S.P.F. (Region 4)

 

BTU / Wh

 

 

 

 

 

15.1

 

 

 

ELECTRICAL RATINGS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Voltage rating

 

 

V

230

 

 

 

 

208

 

 

 

Available voltage range

 

 

V

 

 

 

VAC 187 - 253

 

 

 

Max. Running amperes*

 

 

A

18.2

 

 

 

 

20.1

 

 

 

Power input

 

 

W

3,840

 

 

 

 

3,840

 

 

 

 

 

(17˚F)**

 

W

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Back-up Heater

 

 

kW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

Maximum overcurrent protection (Indoor/Outdoor)

 

A

 

 

 

 

 

15 / 35

 

 

FEATURES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Controls

 

 

 

 

 

 

Microprocessor

 

 

 

Low ambient control

 

 

 

 

 

 

 

 

Built-in 0˚F

 

 

 

Fan speeds Indoor / Outdoor

 

3 and Automatic control / Variable

 

 

 

Wired Remote Controller

 

 

 

 

 

 

 

 

CZ-RTC2

 

 

 

Optional Wireless Remote Controller

 

 

 

 

 

CZ-RWSU2U

 

 

 

Air deflection (Horizontal / Vertical )

 

 

 

 

/ Automatic (Vertical )

 

 

 

 

 

 

 

 

 

Air filter

 

 

 

Washable, long life (2,500 hr)

 

 

 

Drain pump (Drain connection)

 

 

 

 

 

(20A , OD26mm)

 

 

 

 

 

 

 

 

 

 

 

Compressor

 

 

 

 

 

 

 

 

Rotary

 

 

 

Operation sound

Indoor - Hi/Me/Lo

 

dB - A

 

 

 

 

 

42 / 40 / 35

 

 

 

 

 

Outdoor - Hi

 

dB - A

 

 

 

 

 

52

 

 

 

Refrigerant control

 

 

 

Electronic Expansion Valve (MOV)

 

 

 

REFRIGERANT TUBING

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Limit of tubing length

 

 

ft. (m)

 

 

 

 

 

165 (50)

 

 

 

Limit of tubing length at shipment

 

ft. (m)

10~100 (3~30)

 

 

 

Limit of elevation difference

 

ft. (m)

Outdoor unit is higher than indoor unit : 100 (30)

 

 

 

between the two units

 

 

ft. (m)

Outdoor unit is lower than indoor unit : 50 (15)

 

 

 

Refrigerant tube

Narrow tube

 

in. (mm)

 

 

 

 

 

3 / 8 (9.52)

 

 

 

outer diameter

Wide tube

 

in. (mm)

 

 

 

 

 

5 / 8 (15.88)

 

 

 

Refrigerant amount at shipment

 

lbs. (kg)

 

 

6.2(2.8) - R410A

 

 

 

DIMENSIONS & WEIGHT

 

 

 

Indoor unit

 

 

 

Outdoor unit

 

 

 

Unit dimensions

Height

 

in. (mm)

9-7/16 (240)

 

 

3023/32 (780)

 

 

 

 

 

Width

 

in. (mm)

62-1/32 (1,575)

 

37 (940)

 

 

 

 

 

Depth

 

in. (mm)

26-3/8 (670)

 

 

13- 3/8 (340)

 

 

 

Package dimensions

 

 

 

Indoor unit

 

 

 

Outdoor unit

 

 

 

 

 

Height

 

in. (mm)

12-15/32 (317)

 

3431/32 (888)

 

 

 

 

 

Width

 

in. (mm)

66-1/16 (1,678)

 

3931/32 (1,015)

 

 

 

 

 

Depth

 

in. (mm)

31-1/16 (789)

 

16- 3/32 (409)

 

 

 

Net weight

 

 

lbs. (kg)

84 (38)

 

 

 

 

143 (65)

 

 

 

Shipping weight

 

 

lbs. (kg)

97 (44)

 

 

 

 

161 (73)

 

 

 

Shipping volume

 

 

cu.ft. (m3 )

14.8 (0.420)

 

 

13.0 (0.369)

DATA SUBJECT TO CHANGE WITHOUT NOTICE.

Cooling:

Rating conditions (*) : Room temperature 80 °F DB / 67 °F WB, Ambient temperature 95 °F DB / 75 °F WB

Heating:

Rating conditions (*) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 47 °F DB / 43 °F WB Low temp conditions (**) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 17 °F DB / 15 °F WB

1-16

1. Specifications

1-1. Unit Specifications

Ceiling (Type T1)

 

MODEL No.

 

Indoor Unit

 

 

 

 

 

S-42PT1U6

 

 

 

 

 

Outdoor Unit

 

 

 

 

 

U-42PS1U6

 

 

 

 

POWER SOURCE

 

230 - 208V / 1 Phase / 60Hz

 

 

 

PERFORMANCE

 

 

 

 

 

 

Cooling

 

 

 

Capacity * [minimum~muximum]

 

BTU / h

39,000 [9,500~39,000]

 

 

 

 

 

(17˚F)**

 

BTU / h

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Moisture removal (High)

 

 

Pints / h

 

 

 

 

 

12.6

 

 

 

Air circulation (H / M / L) 230 V

 

CFM

1130 / 950 / 775

 

 

 

External Static Pressure

 

 

in. WG

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S.E.E.R. / H.S.P.F. (Region 4)

 

BTU / Wh

 

 

 

 

 

15.6

 

 

 

ELECTRICAL RATINGS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Voltage rating

 

 

V

230

 

 

 

 

208

 

 

 

Available voltage range

 

 

V

 

 

 

VAC 187 - 253

 

 

 

Max. Running amperes*

 

 

A

21.1

 

 

 

 

23.3

 

 

 

Power input

 

 

W

4,140

 

 

 

 

4,140

 

 

 

 

 

(17˚F)**

 

W

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Back-up Heater

 

 

kW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Maximum overcurrent protection (Indoor/Outdoor)

 

A

 

 

 

 

 

15 / 40

 

1

 

FEATURES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Controls

 

 

 

 

 

 

Microprocessor

 

 

 

Low ambient control

 

 

 

 

 

 

 

 

Built-in 0˚F

 

 

 

Fan speeds Indoor / Outdoor

 

3 and Automatic control / Variable

 

 

 

Wired Remote Controller

 

 

 

 

 

 

 

 

CZ-RTC2

 

 

 

Optional Wireless Remote Controller

 

 

 

 

 

CZ-RWSU2U

 

 

 

Air deflection (Horizontal / Vertical )

 

 

 

 

/ Automatic (Vertical )

 

 

 

 

 

 

 

 

 

Air filter

 

 

 

Washable, long life (2,500 hr)

 

 

 

Drain pump (Drain connection)

 

 

 

 

 

(20A , OD26mm)

 

 

 

 

 

 

 

 

 

 

 

Compressor

 

 

 

 

 

 

 

 

Rotary

 

 

 

Operation sound

Indoor - Hi/Me/Lo

 

dB - A

 

 

 

 

 

44 / 41 / 37

 

 

 

 

 

Outdoor - Hi

 

dB - A

 

 

 

 

 

53

 

 

 

Refrigerant control

 

 

 

Electronic Expansion Valve (MOV)

 

 

 

REFRIGERANT TUBING

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Limit of tubing length

 

 

ft. (m)

 

 

 

 

 

165 (50)

 

 

 

Limit of tubing length at shipment

 

ft. (m)

10~100 (3~30)

 

 

 

Limit of elevation difference

 

ft. (m)

Outdoor unit is higher than indoor unit : 100 (30)

 

 

 

between the two units

 

 

ft. (m)

Outdoor unit is lower than indoor unit : 50 (15)

 

 

 

Refrigerant tube

Narrow tube

 

in. (mm)

 

 

 

 

 

3 / 8 (9.52)

 

 

 

outer diameter

Wide tube

 

in. (mm)

 

 

 

 

 

5 / 8 (15.88)

 

 

 

Refrigerant amount at shipment

 

lbs. (kg)

 

 

7.9 (3.6) - R410A

 

 

 

DIMENSIONS & WEIGHT

 

 

 

Indoor unit

 

 

 

Outdoor unit

 

 

 

Unit dimensions

Height

 

in. (mm)

9-7/16 (240)

 

 

48-7/16 (1,230 )

 

 

 

 

 

Width

 

in. (mm)

62-1/32 (1,575)

 

37 (940)

 

 

 

 

 

Depth

 

in. (mm)

26-3/8 (670)

 

 

13- 3/8 (340)

 

 

 

Package dimensions

 

 

 

Indoor unit

 

 

 

Outdoor unit

 

 

 

 

 

Height

 

in. (mm)

12-15/32 (317)

 

52-3/8 (1,330 )

 

 

 

 

 

Width

 

in. (mm)

66-1/16 (1,678)

 

3931/32 (1,015)

 

 

 

 

 

Depth

 

in. (mm)

31-1/16 (789)

 

16- 3/32 (409)

 

 

 

Net weight

 

 

lbs. (kg)

84 (38)

 

 

 

 

220 (100)

 

 

 

Shipping weight

 

 

lbs. (kg)

97 (44)

 

 

 

 

240 (109 )

 

 

 

Shipping volume

 

 

cu.ft. (m3 )

14.8 (0.420)

 

 

19.5 (0.552 )

 

 

 

 

 

 

 

 

DATA SUBJECT TO CHANGE WITHOUT NOTICE.

 

 

Cooling:

Rating conditions (*) : Room temperature 80 °F DB / 67 °F WB, Ambient temperature 95 °F DB / 75 °F WB

Heating:

Rating conditions (*) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 47 °F DB / 43 °F WB Low temp conditions (**) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 17 °F DB / 15 °F WB

1-17

1. Specifications

1-1. Unit Specifications

Low Silhouette Ducted (Type F1)

 

 

 

MODEL No.

 

Indoor Unit

 

 

 

 

 

S-26PF1U6

 

 

 

 

 

 

 

 

 

Outdoor Unit

 

 

 

 

 

U-26PE1U6

 

 

 

 

 

 

 

 

POWER SOURCE

 

 

 

230 - 208V / 1 Phase / 60Hz

 

 

 

PERFORMANCE

 

 

Cooling

 

 

 

 

Heating

 

 

 

Capacity * [minimum~muximum]

 

BTU / h

24,000 [9,500~24,000]

 

28,600 [8,000~28,600]

 

 

 

 

 

(17˚F)**

 

BTU / h

 

 

 

 

 

 

 

 

 

17,100

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Moisture removal (High)

 

 

Pints / h

 

7.7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air circulation (H / M / L) 230 V

 

CFM

 

670 / 530 / 460

 

 

 

 

 

 

 

External Static Pressure

 

 

in.WG

0.2:at shipment / 0.4:using jumper cable

 

 

 

S.E.E.R. / H.S.P.F. (Region 4)

 

BTU / Wh

 

14.0

 

 

 

 

9.0

 

 

 

ELECTRICAL RATINGS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Voltage rating

 

 

V

230

 

208

 

230

 

208

 

 

 

Available voltage range

 

 

V

VAC 187 - 253

 

 

 

VAC 187 - 253

 

 

 

Max. Running amperes*

 

 

A

13.6

 

15.0

 

12.5

 

13.8

 

 

 

Power input

 

 

W

2,600

 

2,600

 

2,400

 

2,400

 

 

 

 

 

(17˚F)**

 

W

 

 

 

 

 

 

1,980

 

1,980

 

 

 

 

 

 

 

 

 

 

 

 

 

Back-up Heater

 

 

kW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

Maximum overcurrent protection (Indoor/Outdoor)

 

A

 

15 / 30

 

 

 

 

 

 

FEATURES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Controls

 

 

 

 

 

 

 

Microprocessor

 

 

 

 

 

 

 

Low ambient control

 

 

 

 

 

 

 

Built-in 0˚F

 

 

 

 

 

 

 

Fan speeds Indoor / Outdoor

 

 

3 and Automatic control / Variable

 

 

 

Wired Remote Controller

 

 

 

 

 

 

 

CZ-RTC2

 

 

 

 

 

 

 

Optional Wireless Remote Controller

 

 

 

 

 

CZ-RWSC1U

 

 

 

 

 

 

 

Air deflection (Horizontal / Vertical )

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air filter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Drain pump (Drain connection)

 

Max.head 2-33/64 in. above drain connection (25A , OD32mm)

 

 

 

Compressor

 

 

 

 

 

 

 

Rotary

 

 

 

 

 

 

 

Operation sound

Indoor - Hi/Me/Lo

 

dB - A

 

34 / 30 / 27

 

 

 

 

 

 

 

 

 

Outdoor - Hi

 

dB - A

 

 

 

 

 

49

 

 

 

 

 

 

 

Refrigerant control

 

 

 

 

Electronic Expansion Valve (MOV)

 

 

 

REFRIGERANT TUBING

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Limit of tubing length

 

 

ft. (m)

 

165 (50)

 

 

 

 

 

 

 

Limit of tubing length at shipment

 

ft. (m)

 

10~100 (3~30)

 

 

 

 

 

 

 

Limit of elevation difference

 

ft. (m)

Outdoor unit is higher than indoor unit : 100 (30)

 

 

 

between the two units

 

 

ft. (m)

Outdoor unit is lower than indoor unit : 50 (15)

 

 

 

Refrigerant tube

Narrow tube

 

in. (mm)

 

3 / 8 (9.52)

 

 

 

 

 

 

 

outer diameter

Wide tube

 

in. (mm)

 

5 / 8 (15.88)

 

 

 

 

 

 

 

Refrigerant amount at shipment

 

lbs. (kg)

 

 

 

 

4.2 (1.9) - R410A

 

 

 

 

 

 

 

DIMENSIONS & WEIGHT

 

 

 

Indoor unit

 

 

 

Outdoor unit

 

 

 

Unit dimensions

Height

 

in. (mm)

12-7/32 (310)

 

3023/32 (780)

 

 

 

 

 

Width

 

in. (mm)

39-3/8 (1,000)

 

 

 

 

37 (940)

 

 

 

 

 

Depth

 

in. (mm)

24-13/16 (630)

 

13- 3/8 (340)

 

 

 

Package dimensions

 

 

 

Indoor unit

 

 

 

Outdoor unit

 

 

 

 

 

Height

 

in. (mm)

14-3/32 (358)

 

3431/32 (888)

 

 

 

 

 

Width

 

in. (mm)

46-7/8 (1,191)

 

3931/32 (1,015)

 

 

 

 

 

Depth

 

in. (mm)

30-13/16 (783)

 

16- 3/32 (409)

 

 

 

Net weight

 

 

lbs. (kg)

 

71 (32)

 

 

 

 

128 (58)

 

 

 

Shipping weight

 

 

lbs. (kg)

 

82 (37)

 

 

 

 

148 (67)

 

 

 

Shipping volume

 

 

cu.ft. (m3 )

11.8 (0.334)

 

13.0 (0.369)

 

 

 

 

 

 

 

 

DATA SUBJECT TO CHANGE WITHOUT NOTICE.

Cooling:

Rating conditions (*) : Room temperature 80 °F DB / 67 °F WB, Ambient temperature 95 °F DB / 75 °F WB

Heating:

Rating conditions (*) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 47 °F DB / 43 °F WB Low temp conditions (**) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 17 °F DB / 15 °F WB

1-18

1. Specifications

1-1. Unit Specifications

Low Silhouette Ducted (Type F1)

 

MODEL No.

 

Indoor Unit

 

 

 

 

 

S-36PF1U6

 

 

 

 

 

 

 

 

 

Outdoor Unit

 

 

 

 

 

U-36PE1U6

 

 

 

 

 

 

 

 

POWER SOURCE

 

 

 

230 - 208V / 1 Phase / 60Hz

 

 

 

PERFORMANCE

 

 

Cooling

 

 

 

 

Heating

 

 

 

Capacity * [minimum~muximum]

 

BTU / h

31,200 [9,500~31,200]

 

36,200 [8,000~36,200]

 

 

 

 

 

(17˚F)**

 

BTU / h

 

 

 

 

 

 

 

 

 

20,200

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Moisture removal (High)

 

 

Pints / h

 

10.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air circulation (H / M / L) 230 V

 

CFM

 

1060 / 920 / 750

 

 

 

 

 

 

 

External Static Pressure

 

 

in. WG

0.24:at shipment / 0.4:using jumper cable

 

 

 

S.E.E.R. / H.S.P.F. (Region 4)

 

BTU / Wh

 

13.9

 

 

 

 

8.5

 

 

 

ELECTRICAL RATINGS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Voltage rating

 

 

V

230

 

208

 

230

 

208

 

 

 

Available voltage range

 

 

V

VAC 187 - 253

 

 

 

VAC 187 - 253

 

 

 

Max. Running amperes*

 

 

A

18.6

 

20.6

 

15.9

 

17.6

 

 

 

Power input

 

 

W

3,920

 

3,920

 

3,340

 

3,340

 

 

 

 

 

(17˚F)**

 

W

 

 

 

 

 

 

2,570

 

2,570

 

 

 

 

 

 

 

 

 

 

 

 

 

Back-up Heater

 

 

kW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Maximum overcurrent protection (Indoor/Outdoor)

 

A

 

15 / 35

 

 

 

 

 

1

 

FEATURES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Controls

 

 

 

 

 

 

 

Microprocessor

 

 

 

 

 

 

 

Low ambient control

 

 

 

 

 

 

 

Built-in 0˚F

 

 

 

 

 

 

 

Fan speeds Indoor / Outdoor

 

 

3 and Automatic control / Variable

 

 

 

Wired Remote Controller

 

 

 

 

 

 

 

CZ-RTC2

 

 

 

 

 

 

 

Optional Wireless Remote Controller

 

 

 

 

 

CZ-RWSC1U

 

 

 

 

 

 

 

Air deflection (Horizontal / Vertical )

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air filter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Drain pump (Drain connection)

 

Max.head 2-33/64 in. above drain connection (25A , OD32mm)

 

 

 

Compressor

 

 

 

 

 

 

 

Rotary

 

 

 

 

 

 

 

Operation sound

Indoor - Hi/Me/Lo

 

dB - A

 

38 / 33 / 31

 

 

 

 

 

 

 

 

 

Outdoor - Hi

 

dB - A

 

 

 

 

 

52

 

 

 

 

 

 

 

Refrigerant control

 

 

 

 

Electronic Expansion Valve (MOV)

 

 

 

REFRIGERANT TUBING

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Limit of tubing length

 

 

ft. (m)

 

165 (50)

 

 

 

 

 

 

 

Limit of tubing length at shipment

 

ft. (m)

 

10~100 (3~30)

 

 

 

 

 

 

 

Limit of elevation difference

 

ft. (m)

Outdoor unit is higher than indoor unit : 100 (30)

 

 

 

between the two units

 

 

ft. (m)

Outdoor unit is lower than indoor unit : 50 (15)

 

 

 

Refrigerant tube

Narrow tube

 

in. (mm)

 

3 / 8 (9.52)

 

 

 

 

 

 

 

outer diameter

Wide tube

 

in. (mm)

 

5 / 8 (15.88)

 

 

 

 

 

 

 

Refrigerant amount at shipment

 

lbs. (kg)

 

 

 

 

6.2 (2.8) - R410A

 

 

 

 

 

 

 

DIMENSIONS & WEIGHT

 

 

 

Indoor unit

 

 

 

Outdoor unit

 

 

 

Unit dimensions

Height

 

in. (mm)

12-7/32 (310)

 

3023/32 (780)

 

 

 

 

 

Width

 

in. (mm)

58-9/32 (1,480)

 

 

 

 

37 (940)

 

 

 

 

 

Depth

 

in. (mm)

24-13/16 (630)

 

13- 3/8 (340)

 

 

 

Package dimensions

 

 

 

Indoor unit

 

 

 

Outdoor unit

 

 

 

 

 

Height

 

in. (mm)

14-3/32 (358)

 

3431/32 (888)

 

 

 

 

 

Width

 

in. (mm)

65-25/32 (1,671)

 

3931/32 (1,015)

 

 

 

 

 

Depth

 

in. (mm)

30-13/16 (783)

 

16- 3/32 (409)

 

 

 

Net weight

 

 

lbs. (kg)

 

104 (47)

 

 

 

 

143 (65)

 

 

 

Shipping weight

 

 

lbs. (kg)

 

115 (52)

 

 

 

 

161 (73)

 

 

 

Shipping volume

 

 

cu.ft. (m3 )

16.5 (0.468)

 

13.0 (0.369)

 

 

 

 

 

 

 

 

DATA SUBJECT TO CHANGE WITHOUT NOTICE.

 

 

Cooling:

Rating conditions (*) : Room temperature 80 °F DB / 67 °F WB, Ambient temperature 95 °F DB / 75 °F WB

Heating:

Rating conditions (*) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 47 °F DB / 43 °F WB Low temp conditions (**) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 17 °F DB / 15 °F WB

1-19

1. Specifications

1-1. Unit Specifications

Low Silhouette Ducted (Type F1)

 

 

 

MODEL No.

 

Indoor Unit

 

S-26PF1U6

 

 

 

 

 

Outdoor Unit

 

U-26PS1U6

 

 

 

 

POWER SOURCE

 

230 - 208V / 1 Phase / 60Hz

 

 

 

PERFORMANCE

 

 

Cooling

 

 

 

Capacity * [minimum~muximum]

 

BTU / h

24,000 [9,500~24,000]

 

 

 

 

 

(17˚F)**

 

BTU / h

 

 

 

 

Moisture removal (High)

 

 

Pints / h

 

7.7

 

 

 

Air circulation (H / M / L) 230 V

 

CFM

670 / 530 / 460

 

 

 

External Static Pressure

 

 

in. WG

0.2:at shipment / 0.4:using jumper cable

 

 

 

S.E.E.R. / H.S.P.F. (Region 4)

 

BTU / Wh

 

14.0

 

 

 

ELECTRICAL RATINGS

 

 

 

 

 

 

 

 

Voltage rating

 

 

V

230

 

208

 

 

 

Available voltage range

 

 

V

VAC 187 - 253

 

 

 

Max. Running amperes*

 

 

A

13.6

 

15.0

 

 

 

Power input

 

 

W

2,600

 

2,600

 

 

 

 

 

(17˚F)**

 

W

 

 

 

 

Back-up Heater

 

 

kW

 

1

 

 

Maximum overcurrent protection (Indoor/Outdoor)

 

A

 

15 / 30

 

 

FEATURES

 

 

 

 

 

 

 

 

 

Controls

 

 

 

Microprocessor

 

 

 

Low ambient control

 

 

 

 

Built-in 0˚F

 

 

 

Fan speeds Indoor / Outdoor

 

3 and Automatic control / Variable

 

 

 

Wired Remote Controller

 

 

 

 

RCZ-RTC2

 

 

 

Optional Wireless Remote Controller

 

CZ-RWSC1U

 

 

 

Air deflection (Horizontal / Vertical )

 

 

 

 

 

Air filter

 

 

 

 

 

 

 

Drain pump (Drain connection)

 

Max.head 2-33/64 in. above drain connection (25A , OD32mm)

 

 

 

Compressor

 

 

 

 

Rotary

 

 

 

Operation sound

Indoor - Hi/Me/Lo

 

dB - A

 

34 / 30 / 27

 

 

 

 

 

Outdoor - Hi

 

dB - A

 

49

 

 

 

Refrigerant control

 

 

 

Electronic Expansion Valve (MOV)

 

 

 

REFRIGERANT TUBING

 

 

 

 

 

 

 

 

 

Limit of tubing length

 

 

ft. (m)

 

165 (50)

 

 

 

Limit of tubing length at shipment

 

ft. (m)

10~100 (3~30)

 

 

 

Limit of elevation difference

 

ft. (m)

Outdoor unit is higher than indoor unit : 100 (30)

 

 

 

between the two units

 

 

ft. (m)

Outdoor unit is lower than indoor unit : 50 (15)

 

 

 

Refrigerant tube

Narrow tube

 

in. (mm)

 

3 / 8 (9.52)

 

 

 

outer diameter

Wide tube

 

in. (mm)

 

5 / 8 (15.88)

 

 

 

Refrigerant amount at shipment

 

lbs. (kg)

4.2 (1.9) - R410A

 

 

 

DIMENSIONS & WEIGHT

 

 

 

Indoor unit

 

Outdoor unit

 

 

 

Unit dimensions

Height

 

in. (mm)

12-7/32 (310)

 

3023/32 (780)

 

 

 

 

 

Width

 

in. (mm)

39-3/8 (1,000)

 

37 (940)

 

 

 

 

 

Depth

 

in. (mm)

24-13/16 (630)

 

13- 3/8 (340)

 

 

 

Package dimensions

 

 

 

Indoor unit

 

Outdoor unit

 

 

 

 

 

Height

 

in. (mm)

14-3/32 (358)

 

3431/32 (888)

 

 

 

 

 

Width

 

in. (mm)

46-7/8 (1,191)

 

3931/32 (1,015)

 

 

 

 

 

Depth

 

in. (mm)

30-13/16 (783)

 

16- 3/32 (409)

 

 

 

Net weight

 

 

lbs. (kg)

71 (32)

 

128 (58)

 

 

 

Shipping weight

 

 

lbs. (kg)

82 (37)

 

148 (67)

 

 

 

Shipping volume

 

 

cu.ft. (m3 )

11.8 (0.334)

 

13.0 (0.369)

 

 

 

 

 

 

 

 

DATA SUBJECT TO CHANGE WITHOUT NOTICE.

Cooling:

Rating conditions (*) : Room temperature 80 °F DB / 67 °F WB, Ambient temperature 95 °F DB / 75 °F WB

Heating:

Rating conditions (*) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 47 °F DB / 43 °F WB Low temp conditions (**) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 17 °F DB / 15 °F WB

1-20

1. Specifications

1-1. Unit Specifications

Low Silhouette Ducted (Type F1)

 

MODEL No.

 

Indoor Unit

 

S-36PF1U6

 

 

 

 

 

 

Outdoor Unit

 

U-36PS1U6

 

 

 

 

 

POWER SOURCE

 

230 - 208V / 1 Phase / 60Hz

 

 

 

PERFORMANCE

 

Cooling

 

 

 

 

Capacity * [minimum~muximum]

 

BTU / h

31,200 [9,500~31,200]

 

 

 

 

 

(17˚F)**

 

BTU / h

 

 

 

 

Moisture removal (High)

 

 

Pints / h

10.0

 

 

 

 

Air circulation (H / M / L) 230 V

 

CFM

1060 / 920/ 750

 

 

 

External Static Pressure

 

 

in. WG

0.24:at shipment / 0.4:using jumper cable

 

 

 

S.E.E.R. / H.S.P.F. (Region 4)

 

BTU / Wh

13.9

 

 

 

 

ELECTRICAL RATINGS

 

 

 

 

 

 

 

 

Voltage rating

 

 

V

230

 

208

 

 

 

Available voltage range

 

 

V

VAC 187 - 253

 

 

 

Max. Running amperes*

 

 

A

18.6

 

20.6

 

 

 

Power input

 

 

W

3,920

 

3,920

 

 

 

 

 

(17˚F)**

 

W

 

 

 

 

Back-up Heater

 

 

kW

 

 

 

 

Maximum overcurrent protection (Indoor/Outdoor)

 

A

15 / 35

 

 

1

 

FEATURES

 

 

 

 

 

 

 

 

Controls

 

 

 

Microprocessor

 

 

 

Low ambient control

 

 

 

Built-in 0˚F

 

 

 

Fan speeds Indoor / Outdoor

 

3 and Automatic control / Variable

 

 

 

Wired Remote Controller

 

 

 

CZ-RTC2

 

 

 

 

Optional Wireless Remote Controller

 

CZ-RWSC1U

 

 

 

Air deflection (Horizontal / Vertical )

 

 

 

 

 

Air filter

 

 

 

 

 

 

 

Drain pump (Drain connection)

 

Max.head 2-33/64 in. above drain connection (25A , OD32mm)

 

 

 

Compressor

 

 

 

Rotary

 

 

 

 

Operation sound

Indoor - Hi/Me/Lo

 

dB - A

38 / 33 / 31

 

 

 

 

 

Outdoor - Hi

 

dB - A

52

 

 

 

 

Refrigerant control

 

 

 

Electronic Expansion Valve (MOV)

 

 

 

REFRIGERANT TUBING

 

 

 

 

 

 

 

 

 

Limit of tubing length

 

 

ft. (m)

165 (50)

 

 

 

 

Limit of tubing length at shipment

 

ft. (m)

10~100 (3~30)

 

 

 

Limit of elevation difference

 

ft. (m)

Outdoor unit is higher than indoor unit : 100 (30)

 

 

 

between the two units

 

 

ft. (m)

Outdoor unit is lower than indoor unit : 50 (15)

 

 

 

Refrigerant tube

Narrow tube

 

in. (mm)

3 / 8 (9.52)

 

 

 

outer diameter

Wide tube

 

in. (mm)

5 / 8 (15.88)

 

 

 

Refrigerant amount at shipment

 

lbs. (kg)

6.2 (2.8) - R410A

 

 

 

DIMENSIONS & WEIGHT

 

 

 

Indoor unit

 

Outdoor unit

 

 

 

Unit dimensions

Height

 

in. (mm)

12-7/32 (310)

 

3023/32 (780)

 

 

 

 

 

Width

 

in. (mm)

58-9/32 (1,480)

 

37 (940)

 

 

 

 

 

Depth

 

in. (mm)

24-13/16 (630)

 

13- 3/8 (340)

 

 

 

Package dimensions

 

 

 

Indoor unit

 

Outdoor unit

 

 

 

 

 

Height

 

in. (mm)

14-3/32 (358)

 

3431/32 (888)

 

 

 

 

 

Width

 

in. (mm)

65-25/32 (1,671)

 

3931/32 (1,015)

 

 

 

 

 

Depth

 

in. (mm)

30-13/16 (783)

 

16- 3/32 (409)

 

 

 

Net weight

 

 

lbs. (kg)

104 (47)

 

143 (65)

 

 

 

Shipping weight

 

 

lbs. (kg)

115 (52)

 

161 (73)

 

 

 

Shipping volume

 

 

cu.ft. (m3 )

16.5 (0.468)

 

13.0 (0.369)

 

 

 

 

 

 

 

 

DATA SUBJECT TO CHANGE WITHOUT NOTICE.

 

 

Cooling:

Rating conditions (*) : Room temperature 80 °F DB / 67 °F WB, Ambient temperature 95 °F DB / 75 °F WB

Heating:

Rating conditions (*) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 47 °F DB / 43 °F WB Low temp conditions (**) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 17 °F DB / 15 °F WB

1-21

1. Specifications

1-1. Unit Specifications

4-Way Cassette 36” × 36” (Type U2)

 

 

 

 

 

 

 

 

INDOOR

 

MODEL

 

 

S-26PU2U6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PANEL

 

MODEL

 

CZ-36KPU3U

 

 

 

-

 

 

 

 

 

 

 

 

 

 

 

 

OUTDOOR

 

MODEL

 

 

 

 

 

 

 

 

U-26PE1U6

 

 

 

 

 

 

 

 

 

 

Branch pipe

 

MODEL

 

 

 

 

 

 

 

-

 

 

 

 

 

 

 

 

 

 

 

 

PERFORMANCE TEST CONDITION

 

 

 

 

 

 

ARI Standard 210/240

 

 

 

 

 

 

 

 

 

 

POWER SUPPLY

 

PH, Hz

 

 

1PH, 60Hz

 

 

 

 

1PH, 60Hz

 

 

 

 

 

 

 

 

 

 

 

V

208

 

230

 

-

 

208

 

230

 

-

Min

Max

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CAPACITY *1

 

kW

7.3

 

7.3

 

-

 

 

 

 

 

 

-

-

 

 

 

 

 

 

 

 

 

BTU/h

24800

 

24800

 

-

 

 

 

 

 

 

9500

24800

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C

CURRENT *1 *4

 

A

0.37

 

0.33

 

-

 

16.1

 

14.6

 

-

-

-

 

 

 

 

 

W

40

 

40

 

-

 

2690

 

2690

 

-

-

-

 

 

O

INPUT POWER *1

 

 

 

 

 

 

 

 

 

TOTAL W

 

-

 

 

 

2730

 

2730

 

-

580

2730

 

 

O

 

 

 

 

 

 

 

 

 

 

 

L

 

EER

 

 

-

 

-

 

-

 

-

 

9.1

 

9.1

 

-

16.4

9.1

 

 

 

SEER

 

 

-

 

-

 

-

 

-

 

17.2

 

17.2

 

-

 

 

 

 

I

 

 

 

 

 

 

 

 

 

 

 

 

 

POWER FACTOR

 

%

 

-

 

-

 

-

 

80

 

80

 

-

 

 

 

 

N

 

 

 

 

 

 

 

 

 

 

 

NOISE INDOOR

 

dB-A (H/M/L)

 

37/31/28

 

 

 

 

 

 

 

 

 

 

 

 

G

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power Level dB

 

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOISE OUTDOOR

 

dB-A (H)

 

-

 

 

 

 

49

 

 

 

 

 

 

 

 

 

 

 

 

Power Level dB

 

-

 

 

 

 

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CAPACITY *2

 

kW

8.4

 

8.4

 

-

 

 

 

 

 

 

-

-

 

 

 

 

 

 

 

 

 

BTU/h

28600

 

28600

 

-

 

 

 

 

 

 

8000

28600

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CURRENT *2 *4

 

A

0.36

 

0.32

 

-

 

15.2

 

13.8

 

-

-

-

 

 

H

INPUT POWER *2

 

W

40

 

40

 

-

 

2540

 

2540

 

-

-

-

 

 

 

TOTAL W

 

-

 

 

 

2580

 

2580

 

-

420

2580

 

 

 

 

 

 

 

 

 

 

 

 

 

E

 

 

(COP)

 

 

-

 

-

 

-

 

-

 

(11.1)

 

(11.1)

 

-

19.0

11.1

1

 

A

 

 

HSPF

 

 

-

 

-

 

-

 

-

 

10.3

 

10.3

 

-

 

 

 

T

 

(HSPF (CANADA REGIONS))

 

-

 

-

 

-

 

-

 

(8.4)

 

(8.4)

 

-

 

 

 

I

 

H32 *3

CAPACITY

 

BTU/h

-

 

-

 

-

 

16200

 

16200

 

-

 

 

 

 

N

(17°F)

INPUT POWER

 

TOTAL W

-

 

-

 

-

 

1880

 

1880

 

-

 

 

 

 

G

 

POWER FACTOR

 

%

 

-

 

-

 

-

 

80

 

80

 

-

 

 

 

 

 

 

 

 

 

NOISE INDOOR

 

dB-A (H/M/L)

 

 

37/31/28

 

 

 

 

-

 

 

 

 

 

 

 

 

 

 

 

 

Power Level dB

 

-

 

 

 

 

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOISE OUTDOOR

 

dB-A (H)

 

-

 

 

 

 

49

 

 

 

 

 

 

 

 

 

 

 

 

Power Level dB

 

-

 

 

 

 

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MAX CURRENT (A)/MAX

INPUT POWER (W)

0.37/40

 

0.33/40

 

-

 

16.5/2.75k

 

16.5/3.04k

 

-

 

 

 

 

 

 

 

 

 

 

1(7:25. ,03('$1&( ȍ0$;

 

 

-

 

 

 

 

 

-

 

 

 

 

 

 

 

 

 

 

 

 

MINIMUM CIRCUIT AMPACITY (A)

 

15

 

 

 

 

17

 

 

 

 

 

 

 

 

 

 

 

MAXIMUM OVERCURRENT PROTECTION (A)

 

15

 

 

 

 

30

 

 

 

 

 

 

 

 

 

 

 

 

DISCONNECT SWITCH CAPACITY (A)

 

15

 

 

 

 

-

 

 

 

 

 

 

OUTDOOR FAN MOTOR

AMPERES (A)

 

COOL/HEAT

 

-

 

 

 

0.9 / 0.9

 

0.9 / 0.9

 

-

 

 

 

 

 

 

 

 

 

COMPRESSOR AMPERES (A)

 

COOL/HEAT

 

-

 

 

 

10.1 / 12.9

 

10.2 / 11.4

 

-

 

 

 

 

 

 

 

 

 

COMPRESSOR LOCKED-ROTOR AMPERES (A)

 

-

 

 

 

 

 

17.5

 

 

 

 

 

 

 

 

 

 

 

COMPRESSOR RATED LOAD AMPERES (A)

 

-

 

 

 

 

12.9

 

 

 

 

 

 

 

 

 

 

 

 

OUTDOOR

 

HIGH SIDE

 

MPa , psi.

 

-

 

 

 

 

(3.36) , 487

 

 

 

 

 

 

 

 

 

 

 

DESIGN PRESSURE

 

LOW SIDE

 

MPa , psi.

 

-

 

 

 

 

(1.63) , 236

 

 

 

 

 

 

 

 

 

 

 

 

FM OUTPUT

(ID/OD) W

 

 

 

60

 

 

 

 

90

 

 

 

 

 

 

 

 

 

 

 

MOISTURE REMOVAL VOLUME

 

L/h, Pints/h

 

2.2, 4.6

 

 

 

 

-

 

 

 

 

 

 

 

 

 

 

 

 

Extarnal static pressure

 

Pa, in.WC

 

-

 

 

 

 

 

 

 

 

 

 

 

 

I/D AIR

COOL (H/M/L)

 

m3/min, ft3/min (CFM)

22/17/14, 777/600/494

 

 

 

 

 

 

 

 

 

 

 

FLOW

HEAT (H/M/L)

 

m3/min, ft3/min (CFM)

22/17/14, 777/600/494

 

 

 

 

 

 

 

 

 

 

 

O/D AIR

COOL

 

m3/min, ft3/min (CFM)

 

 

 

 

 

 

 

50, 1766

 

 

 

 

 

 

FLOW

HEAT

 

m3/min, ft3/min (CFM)

 

 

 

 

 

 

 

50, 1766

 

 

 

 

 

 

 

 

 

 

 

 

REFRIGERANT TYPE,

AMOUNT g, lb, (oz)

 

 

R410A, -

 

 

R410A, 1.90k, 4.2, (67.0)

 

 

 

 

P

D

HEIGHT : H mm (inch)

 

256 (10-5/64)

 

 

 

780 (30-23/32)

 

 

 

 

 

R

I

WIDTH : W mm (inch)

 

840 (33-5/64)

 

 

 

940 (37)

 

 

 

 

 

 

O

M

DEPTH : D mm (inch)

 

840 (33-5/64)

 

 

 

340 (13-3/8)

 

 

 

 

 

 

P

D

HEIGHT : H mm (inch)

 

298 (11-47/64)

 

 

 

888 (34-31/32)

 

 

 

 

 

A

I

WIDTH : W mm (inch)

 

929 (36-37/64)

 

 

1015 (39-31/32)

 

 

 

 

 

C

M

DEPTH : D mm (inch)

 

929 (36-37/64)

 

 

 

409 (16-3/32)

 

 

 

 

 

MASS

 

(NET) kg (lb)

 

 

 

24 (53)

 

 

 

 

58 (128)

 

 

 

 

 

 

(GROSS) kg (lb)

 

 

 

30 (67)

 

 

 

 

67 (148)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LAYERS LIMIT ID/OD (actually)

 

 

 

11 (12)

 

 

 

 

3 (4)

 

 

 

 

 

 

 

 

 

 

 

 

Operation

 

 

 

Cool (DBT)

18°C ~ 32°C (64°F ~ 90°F)

 

-10°C ~ 46°C (14°F ~ 115°F)

 

 

 

 

 

 

 

 

 

 

Condition

 

 

 

Heat (DBT)

16°C ~ 30°C (61°F ~ 86°F)

 

-20°C ~ 24°C (-4°F ~ 75°F)

 

 

 

 

P

 

PIPE DIAMETER mm (inch)

 

 

(Liquid) ø9.52 (3/8) (Gas) ø15.88 (5/8)

(Liquid) ø9.52 (3/8) (Gas) ø15.88 (5/8)

 

 

 

 

 

CONNECT METHOD

 

 

 

 

ÀDUHG W\SH

 

 

 

 

ÀDUHG W\SH

 

 

 

 

 

I

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

STD LENGTH m (ft)

 

 

 

 

 

 

 

7.6 (25)

 

 

 

 

 

 

 

 

P

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PIPE LENGTH RANGE m (ft)

 

3 ~ 50 (10 ~ 165)

 

 

 

 

 

 

 

 

I

 

 

 

 

 

 

 

 

 

 

 

I/D&O/D HEIGHT DIFFERENCE

m (ft)

 

15 (OD located lower) /30 (OD located higher) (50/100)

 

 

 

 

 

N

 

 

 

 

 

 

 

 

ADD GAS AMOUNT g/m (oz/ft)

 

 

 

 

 

40 (0.43)

 

 

 

 

 

 

 

 

G

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PIPE LENGTH FOR ADDITIONAL GAS m (ft)

 

 

 

 

 

30 (100)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DATA SUBJECT TO CHANGE WITHOUT NOTICE.

*1:Rating conditions : Room temperature 80 °F DB / 67 °F WB (26.7°C DB / 19.4°C WB), Ambient temperature 95 °F DB / 75 °F WB (35.0°C DB / 23.9°C WB).

*2:Rating conditions : Room temperature 70 °F DB / 60 °F WB (21.1°C DB / 15.6°C WB), Ambient temperature 47 °F DB / 43 °F WB (8.3°C DB / 6.1°C WB).

*3:Low temp conditions : Room temperature 70 °F DB / 60 °F WB (21.1°C DB / 15.6°C WB), Ambient temperature 17 °F DB / 15 °F WB (-8.3°C DB / -9.4°C WB).

*4:INDOOR CURRENT="INDOOR FAN MOTOR LOAD"

1-22