Olson Technology HML-C, HMLV-C User Manual

20. MAINTENANCE AND SERVICE
Routine Maintenance By Home Owner
Other than remembering to arrange for the annual professional servicing of the furnace by the service or installation contractor, the most important routine service performed by the homeowner is to maintain the air filter or filters. A dirty filter can cause the furnace to over-heat, fail to maintain indoor temperature during cold weather, increase fuel consumption and cause component failure.
The furnace filter(s) should be inspected, cleaned or replaced monthly. The furnace is factory equipped with a semi-permanent type filter. If the filter is damaged, replace with filters of the same size and type. (See Appendix A, Table A-8).
During the routine service, inspect the general condition of the furnace watching for signs of oil leaks in the vicinity of the oil burner, soot forming on any external part of the furnace, soot forming around the joints in the vent pipe, etc. If any of these conditions are present, please advise your service or installation contractor.
Annual Service By Contractor
THE COMBUSTION CHAMBER (FIREPOT) IS FRAGILE. USE CARE WHEN INSPECTING AND CLEANING THIS AREA.
The heat exchanger should be inspected periodically and
cleaned if necessary. If cleaning is necessary, SHUT OFF POWER TO THE FURNACE and remove the
burner. Using a stiff brush with a wire handle, brush off scale and soot from inside the drum and flue pipe. To clean the radiator, remove the clean-out caps screws, and remove the caps carefully to avoid tearing the gaskets. A wire brush can be used to loosen dirt and debris on the inside surfaces of the radiator. Clean out all accumulated dirt, soot and debris with a wire handled brush and an industrial vacuum cleaner. Before replacing the clean-out caps, inspect the gaskets. If the gaskets are broken, remove the remnants and replace with new gaskets.
The blower motor is factory oiled and permanently
sealed. DO NOT LUBRICATE. Excess oil causes
premature electric motor failure.
Inspect the blower fan. Clean if necessary.
Oil Burner Maintenance: Follow the instructions of the oil burner manufacturer. (See oil burner manufacturer's instructions supplied with furnace or burner). It is advisable to change the oil burner nozzle and oil filter on an annual basis.
The venting system should be cleaned and inspected for signs of deterioration. Replace pitted or perforated vent
pipe and fittings. The barometric damper should open and close freely.
All electrical connections should be checked to ensure tight connections. Safety controls such as the high limit controls should be tested for functionality. The fan control should be checked to ensure that the fan on and off delay function continues to start and stop the blower fan at the optimal settings.
21. OPERATING INSTRUCTIONS (HML-C)
Before Lighting
Open all supply and return air registers and grilles.
Open all valves in oil pipes.
Turn on electric power supply
To Light Unit
Set the thermostat above room temperature to call for heat. The burner should start. NOTE: It may be necessary to press the RESET button on the primary combustion control relay.
There will be a fan on time delay before the
circulating fan is energized. The United Technologies 1158-120 has an adjustable fan on
time that is set by selecting the dipswitch combination displayed in Chart 1. This fan on delay can be set at 1, 2, 4 or 6 minutes.
Set the thermostat below room temperature. The oil burner should stop.
The air circulation blower will continue to run until the time off setting selected on the electronic fan
timer control times out. The United Technologies 1158-120 has an adjustable fan off time of 30, 60,
90 or 120 seconds. The fan timer control adjustments may be altered if the air at the room registers is uncomfortably high upon blower start up or shutdown.
The necessary adjustments to the fan control settings should be determined by measuring the temperature of the air in the supply air take-off, or within the first few inches of the supply air trunk. The side mid point of the transition is usually ideal, providing that the thermometer probe is beyond the "line of sight" wherein false readings from radiant heat could be observed. System temperature rise is
the difference in temperature between the supply air and return air.
To check the operation of the limit switch, shut off power to the furnace. Temporarily remove the neutral wire from the direct drive blower motor. Restore the electrical power to the furnace and set the thermostat above room temperature.
8
30173 Rev B 4/29/2008
After three or four minutes of burner operation, the limit control should turn the burner off. When the limit function test is complete, shut off electrical power to the furnace, replace the neutral wire to the blower fan motor, and then restore power. The blower fan will start up immediately. Once the temperature has dropped and the limit control has reset, the fan will operate until the fan off time is achieved. The oil burner will then resume operation and continue until the thermostat is satisfied. Restore the thermostat setting to a comfortable temperature.
To Shut Down Unit
Set the thermostat to the lowest possible setting.
Set the manual switch (if installed) in the Electrical Power Supply Line to "OFF".
21. OPERATING INSTRUCTIONS (HMLV-C)
Before Lighting
Open all supply and return air registers and grilles.
operation and continue until the thermostat is satisfied. Restore the thermostat setting to a comfortable temperature.
NOTE: IF THE FURNACE IS TO BE SHUT DOWN FOR AN EXTENDED PERIOD OF TIME, CLOSE THE OIL SUPPLY VALVE TO THE BURNER.
DO NOT ATTEMPT TO START THE BURNER WHEN EXCESS OIL HAS ACCUMULATED, WHEN THE FURNACE IS FULL OF VAPOUR, OR WHEN THE COMBUSTION CHAMBER IS VERY HOT. NEVER BURN GARBAGE OR PAPER IN THE FURNACE, AND NEVER LEAVE PAPER OR RAGS AROUND THE UNIT.
Open all valves in oil pipes.
Turn on electric power supply
To Light Unit
Set the thermostat above room temperature to call for heat. The burner should start. NOTE: It may be necessary to press the RESET button on the primary combustion control relay.
There will be a fan on time delay before the circulating
fan is energized. The United Technologies 1168-1 has
an adjustable fan on/off time delay that is programmed into the ECM motor, and is set by selecting the SW4 DIP switch combination displayed in Table A-10 page 15.
Fan on/off delay must be adjusted according to input (nozzle size).
1. Set the thermostat below room temperature. The oil burner should stop.
The air circulation blower will continue to run until the blower off delay setting programmed into the ECM motor times out.
To check the operation of the limit switch, shut off power to the furnace. Temporarily remove the 5 pin power
connector plug from the ECM blower motor. NOTE:
Isolate the AC Line pins on the 5 pin power connector with electrical tape to prevent electric shock hazard. Restore the electrical power to the
furnace and set the thermostat above room temperature.
After three or four minutes of burner operation, the limit control should turn the burner off. When the limit function
test is complete, shut off electrical power to the furnace,
replace the 5 pin power plug to the blower fan motor, and then restore power. The blower fan will start up immediately. Once the temperature has dropped and the limit control has reset, the fan will operate until the fan off time is achieved. The oil burner will then resume
22. ECM BLOWER MOTOR OPERATION (HMLV-C)
Setting Blower “ON” and “OFF” Timings
Blower on/off time delays are handled by ECM motor programming. Features of this ECM variable speed motor are that it will deliver a constant airflow within a wide range of external static pressures, and also includes:
Soft Start: This ECM variable speed motor will
slowly ramp up to the required operating speed. This feature in the heating cycle allows the heat exchanger to reach operating temperature before the set heat speed, which minimizes noise and increases comfort.
Soft Stop: At the end of the heating cycle, the ECM
variable speed motor will slowly ramp down. This feature allows for increased energy efficiency and reduced noise levels.
Dehumidification: A dehumidification feature has
been programmed into the variable speed motor. At the start of each cooling cycle, the variable speed motor will run at 82% of the rated airflow for 7.5 minutes. After 7.5 minutes has elapsed, the motor will increase to 100% of the rated airflow. This profile is used to provide dehumidification and improve system efficiency.
Continuous Fan Operation: When the thermostat
continuous fan (G) switch is on without a call for heating or cooling, the indoor fan is immediately energized up to 50% of the cooling speed. This feature allows continuous circulation of air between calls for heating or cooling.
If a call for heat (W) or cool (Y) occurs during continuous fan, the blower will remain energized
9
30173 Rev B 4/29/2008
Loading...