Ge HOME GENERATOR 10000 Manual

0 (0)

GE Home Generator Systems

10,000 Watt

Home Generator System

Installation and

Reproduction

Start-Up Manual

Not

for

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Thank you for purchasing this quality-built GE home generator. We’re pleased that you’ve placed your confidence in the GE brand. When operated and maintained according to the instructions in the operator’s manual, your home generator will provide many years of dependable service.

This manual contains safety information to make you aware of the hazards and risks associated with residential generator systems and how to avoid them. This generator system is designed and intended only for use as an optional home standby system that provides an alternate source of electric power and to serve loads such as heating, refrigeration systems, and communication systems that, when stopped during any power outage, could cause discomfort or inconvenience. Save these instructions for future reference.

This generator requires professional installation before use. The installer should follow the instructions completely.

Where to Find Us

You never have to look far to find support and service for your generator. For quick service when you need it most fill out the information below and keep your original receipt with this manual. You may contact Customer Service at (888) 575-8226, or click on SERVICE & SUPPORT at www.homestandbygeneratorsystems.com, which provides a list of authorized dealers.

For Future Reference

Please fill out the information below andReproductionkeep with your receipt to assist in unit identification for future purchase issues. for

Date of PurchaseNot

Generator

Model Numb

Model evision

Serial Number

Engine

Model Number

2

Table of Contents

Important Safety Instructions . . . . . . . . . . . . . . . . 4 Installation . . . . . . . . . . . . . . . . .             7

Home Owner Responsibilities . . . . . . . .

. . . .

.

.

. .

.

 

    7

Installing Dealer/Contractor Responsibilities . . . . .

.

.

. .

.

.

. . . 7

Unpacking Precautions . . . . . . . . . . .

. . . .

.

.

 

 

 

    7

Shipment Contents . . . . . . . . . . . . .

. . . .

 

 

   

 

 

    8

Generator Location . . . . . . . . . . . . .

. . .

.

 

   

 

 

      8

Electrical and Fuel Inlet Locations . . . . . .

. . . .

.

.

. .

.

.

. 10

The Gaseous Fuel System . . . . . . . . . .

. . . .

.

.

.         12

Reproduction

Fuel Consumption . . . . . . . . . . . . . .

. . .

              14

Initial Start-up (No Load) . . . . . . . . . . .

for. . . . .

.

        20

System Connectors . . . . . . . . . . . . .

. . . .

 

 

            15

Grounding the Generator . . . . . . . . . .

. . . .

.

.

.         16

Final Installation Considerations . . . . . . .

. . .

. .

.

. .

.

.

19

Not

. . . .

              21

Engine Adjustment . . . . . . . . . . . . .

Test Shutdown(s) Procedure . . . . . . . . .

. . . .

.

.

. .

      22

Fuel Conversion . . . . . . . . . . . . . . .

. .

 

 

   

        23

Schematic Diagram . . . . . . . . . . . . .

. . .

.

 

   

        24

Wiring Diagram . . . . . . . . . . . . . . .

. .

 

 

   

        25

Operation . . . . . . . . . . . . . .

. . .

            26

Automatic Operation Sequence . . . . . . .

. . . .

.

.

. .

.

.

  26

Setting Exercise Timer . . . . . . . . . . . .

. . .

. .

 

 

 

 

    26

Installation Inspection . . . . . . . . . . . .

. . .

. .

 

 

 

 

    27

3

Safety Rules
Important Safety Instructions

SAVE THESE INSTRUCTIONS - This manual contains

 

The manufacturer cannot possibly anticipate every possible

important instructions that should be followed during

 

circumstance that might involve a hazard. The warnings

installation and maintenance of the generator and batteries.

 

in this manual, and the tags and decals affixed to the unit

Safety Symbols and Meanings

 

 

 

 

 

are, therefore, not all-inclusive. If you use a procedure, work

 

 

 

 

 

 

 

 

 

 

 

method or operating technique that the manufacturer does

 

 

 

 

 

 

 

 

 

 

 

not specifically recommend, you must satisfy yourself that it

 

 

 

 

 

 

 

 

 

 

 

is safe for you and others. You must also make sure that the

 

 

 

 

 

 

 

 

 

 

 

procedure, work method or operating technique that you

Explosion

Fire

 

Electrical Shock

 

choose does not render the generator system unsafe.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WARNING Running engine gives off carbon monoxide, an

 

 

 

 

 

 

 

 

 

 

 

 

 

odorless, colorless, poison gas.

 

 

 

 

 

 

 

 

 

 

 

 

 

Breathing carbon mo

oxide can cause headache, fatigue,

Toxic Fumes

Rotating Parts

 

 

 

Hot Surface

 

 

 

dizz ness, v

m t g, co

fusion, seizures, nausea, fainting

 

 

 

 

 

 

or dea h.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operate genera

r ONLY utdoors.

 

 

 

 

 

 

 

 

 

 

 

Install a ba ery operated carbon monoxide alarm near

 

 

 

 

 

 

 

 

 

 

 

 

the bedrooms.

 

 

 

 

 

 

 

 

 

 

 

 

for

 

 

 

Auto Start

Explosive Pressure

 

 

Chemical Burn

 

Keep exha st gas from entering a confined area through

 

 

 

 

win ows, doors, ventilation intakes, or other openings.

 

 

 

 

 

 

 

 

 

Not

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WARNING The engine exhaust from this product contains

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

chemicals known to the State of California to cause cancer, birth

Lift Hazard

 

 

 

 

 

 

 

defects, or other reproductive harm.

Read Manual

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The safety alert symbol indicates a potential rsonal

 

 

WARNING Certain components in this product and related

 

accessories contain chemicals known to the State of California

injury hazard. A signal word (DANGER, WA

NING, or

 

to cause cancer, birth defects, or other reproductive harm. Wash

CAUTION) is used with the alert symbol to designate a degree

hands after handling.

 

or level of hazard seriousness. A safety symbol may be used

 

 

 

 

 

 

 

 

 

 

 

 

Reproduction

to represent the type of hazard. The signal word NOTICE is

 

 

 

 

 

 

used to address practices not related to personal injury.

 

 

 

 

 

 

DANGER indicates a hazard which, if not avoided, will result in death or serious injury.

WARNING indicates a hazard which, if not avoided, could result in death or serious injury.

CAUTION indicates a hazard which, if not avoided, could result in minor or moderate injury.

NOTICE addresses practices not related to personal injury.

4

WARNING Storage batteries give off explosive hydrogen gas

 

WARNING Hazardous Voltage - Contact with power lines can

during recharging.

 

 

 

cause electric shock or burn.

Slightest spark will ignite hydrogen and

 

 

 

Lifting Hazard / Heavy Object - Can cause muscle

 

 

 

cause explosion.

 

 

 

strain or back injury.

Battery electrolyte fluid contains acid and is

If lifting or hoisting equipment is used, DO NOT contact any

extremely caustic.

 

power lines.

Contact with battery contents will cause severe chemical burns.

DO NOT lift or move generator without assistance.

A battery presents a risk of electrical shock and high short

DO NOT lift unit by roof as damage to generator will occur.

circuit current.

 

 

 

 

• DO NOT dispose of battery in a fire. Recycle battery.

DO NOT allow any open flame, spark, heat, or lit cigarette during

 

 

WARNING Generator produces hazardous voltage.

 

and for several minutes after charging a battery.

 

 

 

 

Failure to properly ground generator can result in

DO NOT open or mutilate the battery.

 

 

 

 

 

electrocution.

Wear protective goggles, rubber apron, rubber boots and

 

 

 

 

Failure to isolate ge erator from power utility can result in

 

 

 

 

death r injury to electric utility workers due to backfeed of

 

rubber gloves.

 

 

 

 

 

 

 

 

 

 

 

electr cal energy.

Remove watches, rings, or other metal objects.

 

 

 

 

 

 

When using generat r f r backup power, notify utility company.

Use tools having insulated handles.

 

 

 

 

 

 

DO NOT

ou h bare wires or bare receptacles.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DO NOT

se generator with electrical cords which are worn,

 

WARNING Propane and Natural Gas are extremely flammable

for

 

 

 

 

 

frayed, bare or otherwise damaged.

 

and explosive.

 

 

 

DO NOT handle generator or electrical cords while standing in

 

Fire or explosion can cause severe burns or death.

 

 

water, while barefoot, or while hands or feet are wet.

Install the fuel supply system according to FPA 37 and other

 

 

If you must work around a unit while it is operating, stand on an

 

applicable fuel-gas codes.

 

 

 

 

insulated dry surface to reduce the risk of a shock hazard.

Before placing the generator into service, the fuelNotsystem lines

 

 

DO NOT allow unqualified persons or children to operate or

 

must be properly purged and leak tested.

 

 

 

service generator.

After the generator is installed, you should insp the fu l

 

 

In case of an accident caused by electrical shock, immediately

 

system periodically.

 

 

 

 

shut down the source of electrical power and contact the local

NO leakage is permitted.

 

 

 

 

authorities. Avoid direct contact with the victim.

DO NOT operate engine if smell of fuel is present or other

 

 

Despite the safe design of the residential generator, operating

 

explosive conditions exist.

 

 

 

 

this equipment imprudently, neglecting its maintenance or being

DO NOT smoke around the generator. Wipe up any oil spills

 

 

 

careless can cause possible injury or death.

 

 

Reproduction

 

immediately. Ensure that no combustible materials are left in the

 

Remain alert at all times while working on this equipment.

 

generator compartment. Keep the area near the generator clean

 

 

Never work on the equipment when you are physically or

 

and free of debris.

 

 

 

 

mentally fatigued.

 

 

 

 

 

Before performing any maintenance on the generator, disconnect

 

 

 

 

 

 

 

 

 

 

 

the battery cable indicated by a NEGATIVE, NEG or (-) first. When

 

 

 

 

 

 

finished, reconnect that cable last.

 

 

 

 

 

After your system is installed, the generator may crank and start

 

 

 

 

 

 

without warning any time there is a power failure. To prevent

 

 

 

 

 

 

possible injury, always set the generator’s system switch to OFF,

 

 

 

 

 

 

remove the service disconnect from the disconnect box AND

 

 

 

 

 

 

remove the 15 Amp fuse BEFORE working on the equipment.

 

 

 

 

 

 

 

 

 

5

• Observe that the 15 Amp fuse has been removed from the control panel for shipping.
• DO NOT install this fuse until all plumbing and wiring has been completed and inspected.

 

WARNING Contact with muffler area can result in

 

 

 

CAUTION Excessively high operating speeds increase risk of

 

serious burns.

 

 

 

injury and damage to generator.

 

Exhaust heat/gases can ignite combustibles or

 

 

Excessively low speeds impose a heavy load on generator.

 

structures causing a fire.

 

 

 

DO NOT tamper with governed speed. Generator supplies correct

DO NOT touch hot parts and AVOID hot exhaust gases.

 

 

 

rated frequency and voltage when running at governed speed.

Allow equipment to cool before touching.

 

 

 

DO NOT modify generator in any way.

DO NOT install the generator closer than 5 feet (1.5m) from any

 

 

 

 

 

 

 

 

 

 

 

combustibles or structures with combustible walls having a fire

 

 

NOTICE Exceeding generators wattage/amperage capacity can

 

resistance rating of less than 1 hour.

 

 

 

 

 

 

 

damage generator and/or electrical devices connected to it.

Keep at least minimum distances shown in General Location

 

 

 

 

Start generator and let engine stabilize before connecting

 

Guidelines to insure for proper generator cooling and

 

 

 

 

 

 

electrical loads.

 

maintenance clearances.

 

 

 

 

 

 

 

 

 

 

 

It is a violation of California Public Resource Code, Section 4442,

 

NOTICE Improper treatme t of generator can damage it and

 

to use or operate the engine on any forest-covered, brush-

 

 

 

 

 

sh ten its life.

 

covered, or grass-covered land unless the exhaust system is

 

 

 

 

 

Use genera

r nly f r intended uses.

 

equipped with a spark arrester, as defined in Section 4442,

 

 

 

 

 

If you have ques ns ab ut intended use, contact your

 

maintained in effective working order. Other states or federal

 

 

 

jurisdictions may have similar laws.

 

 

 

 

authorized dealer.

 

Contact the original equipment manufacturer, retailer, r dealer

 

 

Operate generator only on level surfaces.

 

 

 

for

 

 

obtain a spark arrester designed for the exhaust system installed

 

Adeq ate,

nobstructed flow of cooling and ventilating air is

 

on this engine.

 

 

 

 

 

 

 

 

critical to correct generator operation.

Replacement parts must be the same and installed in the same

 

 

 

 

 

The access panels/door must be installed whenever the unit

 

position as the original parts.

 

 

 

 

 

 

 

 

is running.

 

 

 

 

 

 

 

 

 

 

Not

 

 

DO NOT expose generator to excessive moisture, dust, dirt, or

 

WARNING Starter and other rotating parts can entangle hands,

 

 

corrosive vapors.

 

hair, clothing, or accessories.

 

 

 

Remain alert at all times while working on this equipment.

 

 

 

 

 

 

Never work on the equipment when you are physically or

 

 

 

 

 

 

mentally fatigued.

NEVER operate generator without protective housings, cov rs, or

 

DO NOT start engine with air cleaner or air cleaner cover removed.

 

guards in place.

 

 

 

DO NOT insert any objects through cooling slots.

DO NOT wear loose clothing, jewelry or anything that may be

 

 

DO NOT use the generator or any of its parts as a step. Stepping

 

caught in the starter or other rotating parts.

 

 

 

the unit can cause stress and break parts. This may result in

Tie up long hair and remove jewelry.

Reproduction

 

 

 

 

dangerous operating conditions from leaking exhaust gases, fuel

Before servicing, remove 15 Amp fuse from control panel and

 

 

 

leakage, oil leakage, etc.

 

disconnect Negative (NEG or -) battery cable.

 

 

If connected devices overheat, turn them off and disconnect them

 

 

 

 

 

 

from generator.

 

 

 

 

 

 

 

 

 

 

 

Shut off generator if:

 

CAUTION Installing the 15A fuse could cause the engine

 

 

 

 

 

-electrical output is lost;

 

to start.

 

 

 

 

 

 

 

 

 

-equipment sparks, smokes, or emits flames;

 

 

 

 

 

 

 

 

 

 

 

 

-unit vibrates excessively.

 

 

 

 

 

 

 

 

6

Installation

This product is intended for use as an optional home generator system which provides an alternate source of electric power and to serve loads such as heating, refrigeration systems, and communication systems that, when stopped during any power outage, could cause

discomfort or inconvenience. This product does not qualify for emergency standby as defined by NFPA 70 (NEC).

Every effort has been made to ensure that information in this manual is accurate and current. However, we reserve the right to change, alter, or otherwise improve the product and this document at any time without prior notice.

Only current licensed electrical and plumbing professionals should attempt home generator system installations. Installations must strictly comply with all applicable codes, industry standards and regulations.

 

Reproduction

• Read and follow the instructions given in the

for

operator’s manual.

 

 

• Follow a regular schedule in maintaining, caring for

 

and using your home generator, as specified in the

 

operator’s manual.

Not

 

Installing Dealer/Contractor

 

esponsibilities

 

 

 

• Read and observe the safety rules.

 

If operating the generator below 40°F (5°C), it is HIGHLY

 

 

RECOMMENDED that a battery warmer be installed. This item

• Install only an UL approved transfer switch that is

 

Home Owner Responsibilities

 

compatible with the generator.

is available at your local servicing dealer.

 

• Read and follow the instructions given in this

If you need more information on this matter, please call

(888) 575-8226, between 8:00 AM and 5:00 PM CT.

installation and start-up manual.

 

Unpacking Precautions

The unit is shipped bolted to its mounting pad, ready for installation. Avoid damage from dropping, bumping, collision, etc. Store and unpack carton with the proper side up, as noted on the shipping carton.

7

Delivery Inspection

After removing the carton, carefully inspect the generator for any damage that may have occurred during shipment.

If loss or damage is noted at time of delivery, have the person(s) making delivery note all damage on the freight bill and affix his signature under the consignor’s memo of loss or damage. If loss or damage is noted after delivery, separate the damaged materials and contact the carrier for claim procedures. Missing or damaged parts are not warranted.

Shipment Contents

The home generator system is supplied with:

Oil drain tray

 

Pre-attached mounting pad

Reproduction

 

 

Touch up pai

t

Fully-serviced oil/lubricating system

 

Roof hardware

• Flexible fuel hook-up hose

 

 

Remote LED

dicat r kit (LED/plate/screws)

• Installation and start-up manual

 

 

N supplied:

 

Operator’s manual

 

 

Star ing ba ery (see page 19)

Engine operator’s manual

 

Not

for•

Conne ting wire and conduit

Installation checklist

 

F el s pply valves/plumbing

Access door keys

 

Crane, lifting straps, chains or cables

• Spare 15 Amp ATO-type fuse

 

Hole punches for 16ga steel

Two-pole control panel connector

Torque screwdriver, 5 to 50 inch-pound range

• Ten-pole control panel connector

 

Voltage/frequency meter

Generator Location

Before installing the generator, consult with the homeowner and convey the following guidelines, which may affect the desired installation location.

WARNING Exhaust heat/gases can ignite combustibles or structures causing a fire.

DO NOT install the generator closer than 5 feet (1.5m) from any combustibles or structures with combustible walls having a fire resistance rating of less than 1 hour.

WARNING Running engine gives off carbon monoxide, an odorless, colorless, poison gas.

Breathing carbon monoxide can cause headache, fatigue, dizziness, vomiting, confusion, seizures, nausea, fainting or death.

Operate generator ONLY outdoors.

Install a battery operated carbon monoxide alarm near the bedrooms.

Keep exhaust gas from entering a confined area through windows, doors, ventilation intakes, or other openings.

8

Install generator outdoors in an area which will not accumulate deadly exhaust gas. DO NOT install generator where exhaust gas could accumulate and enter inside or be drawn into a potentially occupied building. Ensure exhaust gas is kept away from windows, doors, ventilation intakes or other openings that can allow exhaust gas to collect in a confined area. Prevailing winds and air currents should be taken into consideration when positioning generator.

General Location Guidelines

Install the unit outdoors ONLY.

Place the unit in a prepared location that is flat and has provisions for water drainage.

Install the unit in a location where sump pump discharge, rain gutter down spouts, roof run-off, landscape irrigation, or water sprinklers will not flood the unit or spray the enclosure and enter any air inlet or outlet openings.

 

 

 

 

 

 

 

 

5’ (1.5 m)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3’ (1 m)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3’ (1 m)

 

 

 

 

 

 

 

3’ (1 m)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B

 

 

 

 

 

5’ (1.5 m)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5’ (1.5 m)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D A

C

5’ (1.5 m)

• Install the unit where it will not affect or obstruct

 

E

 

E

 

Reproduction

 

any services (including covered, concealed and

for

 

 

 

underground), such as telephone, electric, fuel,

 

A Non-Combust ble material with Fire Resistant Rating of

irrigation, air conditioning, and so forth.

 

 

• Install the unit where air inlet and outlet openings

 

1 hour

r greater

 

will not become obstructed by leaves, grass, snow,

 

B Home S andby Generator

 

 

Not

 

 

 

 

etc. If prevailing winds will cause blowing

r drif ing,

 

C Engine Exhaust

 

you may need to construct a windbreak to pr ect

 

D Comb

stible Material or Structure with a Fire

 

the unit.

 

 

 

Resistance Rating of less than 1 hour.

 

• Install the generator as close as possible to the

 

E Any structure or material. DO NOT connect (A) and/or

transfer switch and fuel supply to reduce the length

f

(D) to (E).

 

wiring, conduit, and piping.

 

 

 

 

 

 

 

 

 

 

Laws or local codes may regulate the distance to the

 

 

 

 

fuel supply.

 

 

 

 

 

 

The minimum clearances from aerial view of g

rator (B) to

 

 

 

 

combustible (D), and non-combustible (A) mat rials is shown at right:

• These distances are provided to give generator location guidance relative ONLY to combustibles, generator cooling, and maintenance.

• The minimum distances in the figure are as shown.

All four sides of the generator cannot be enclosed or restricted, even if the minimum distances are maintained. DO NOT connect (A) and/or (D) to (E)

• A roof cannot be used.

• Exhaust (C) must not be allowed to accumulate.

9

Electrical and Fuel Inlet Locations

The 3/4 inch N.P.T. fuel inlet connector (A) and electrical inlet location (B) is shown at right.

The home generator is shipped already attached to its mounting pad. Unless mandated by local code, a concrete slab is not required.

If mandated by local code, construct a concrete slab at least 3 inches thick and 6 inches longer and wider than the unit. Attach unit to slab with 1/4” diameter (minimum) masonry anchor bolts long enough to retain the unit.

B

A

Lifting the Generator

 

for

 

 

 

 

 

 

The generator weighs more than 350 pounds (159 kg). Pr per

tools, equipment and qualified personnel should be used in

 

 

all phases of handling and moving the generator.

 

 

 

 

 

 

 

 

 

WARNING Hazardous Voltage - Contact with power lines can

 

 

 

 

 

 

cause electric shock or burn.

Not

 

 

 

 

 

 

 

 

 

 

 

 

 

Lifting Hazard / Heavy Object - Can cause muscle

 

 

 

 

 

 

strain or back injury.

 

 

 

If lifting or hoisting equipment is used, DO NOT contact any

 

 

 

power lines.

 

 

 

 

DO NOT lift or move generator without assistance.

 

 

DO NOT lift unit by roof as damage to generator will occur.

 

 

 

 

 

 

 

Reproduction

Lifting pockets are provided at each corner between the base of the generator and its mounting pad. Retouch any chipped paint with supplied touch-up paint.

10

Access Ports

The home generator is equipped with several access openings and a removable roof to permit simple oil and filter servicing.

To remove roof:

Remove the four screws and lift off. Replace roof in reverse order.

To remove access cover:

Remove the two screws, tilt cover out, and lift cover off panel. Replace cover in reverse order.

To remove side panel (if necessary):

1.Remove roof.

2.Remove screw(s) attaching side panel.

Each home generator is suppied with a set of identical keys. These keys fit the locks that secure the access door.

To open access door:

1.Insert key into lock of access door and turn key one quarter turn counterclockwise.

2.Grasp door’s handle and turn one quarter turn counterclockwise to open. Remove key.

To close access door:

1.Close door and turn doors handle one quarter of a turn clockwise.

2.Insert key into lock of access door and turn key one quarter turn clockwise. Remove key.

 

WARNING Contact with muffler and engine parts can result in

 

 

 

serious burns.

Reproduction

DO NOT touch hot parts and AVOID hot exhaust gases.

for

Allow equipment to cool before touching.

 

 

 

 

 

3.

 

 

Not

 

 

 

Pull panel outward (away) from unit while pulling

 

 

 

 

panel upward and out of base.

 

 

 

 

To install side panel:

 

 

 

 

 

1.

Guide bottom of side into base.

 

 

 

 

 

2.

Push panel until it is flush with sides.

 

 

 

 

3.

Replace panel screw(s).

 

 

 

 

 

4.

Replace roof and screws.

 

 

 

 

11

The generator has been factory set to run on natural gas. If you need to change from natural gas to LP gas, the unit will need to be reconfigured, as described in Fuel Conversion.

The Gaseous Fuel System

The information below is provided to assist gaseous fuel

 

 

 

• Piping must be of the correct size to maintain the

system technicians in planning installations. In no way

 

 

 

required supply pressures and volume flow under

should this information be interpreted to conflict with

 

 

 

varying generator load conditions with all gas

applicable fuel gas codes. Consult with your local fuel

 

 

 

appliances connected to the fuel system turned on

supplier or Fire Marshall if questions or problems arise.

 

 

 

and operating.

 

 

 

 

 

 

WARNING Propane and Natural Gas are extremely flammable

 

 

 

 

 

 

WARNING Propane and Natural Gas are extremely flammable

 

and explosive.

 

 

 

 

 

 

 

 

 

 

 

and explosive.

 

Fire or explosion can cause severe burns or death.

 

 

 

 

 

Fire or explosion can cause severe burns or death.

 

 

 

 

 

 

 

LP gas is heavier than air and will settle in low areas.

 

 

 

Before placing the generator into service, the fuel system lines

Natural gas is lighter than air and will collect in high areas.

 

 

 

must be properly purged and leak tested.

The slightest spark can ignite these fuels and cause an explosion.

 

No leakage is permitted.

DO NOT light a cigarette or smoke.

 

 

 

 

 

 

 

 

 

 

 

• Use a pipe sealant or joint compound approved for

 

 

 

 

 

 

 

TO THE INSTALLER: Consult with the home generator

 

 

 

 

 

 

use with NG/LPG on all threaded fittings to reduce the

owner(s) and convey any technical considerations that

 

 

 

possibility of leakage.

might affect their installation plans before applying these

 

 

 

• Installed piping must be properly purged and

general guidelines.

 

 

 

 

 

 

 

 

 

 

leak tested, in accordance with applicable codes

The following general rules apply to gaseous fuel

 

 

 

 

 

 

 

 

and standards.

system piping:

 

 

 

 

C

nsider the f ll w g factors when planning the fuel

 

• The piping should be of a material that conforms

 

 

 

 

 

supply sys em ns allat n:

 

to federal and local codes, rigidly mounted and

 

 

 

• Air dens y s less at high altitudes, resulting in

 

protected against vibration.

 

 

 

 

 

 

 

 

 

 

 

less available engine power. See Power Decrease

 

 

 

 

 

 

 

 

• Piping should be protected from physical damage

for at High Altitude or High Temperature in the

 

where it passes through flower beds, shrub beds, and

 

 

operator’s manual.

 

other cultivated areas where damage c uld

ccur.

 

 

 

• The generator engine is fitted with a fuel mixer system

 

 

 

 

 

 

 

 

 

 

 

 

 

 

that meets the specifications of the California Air

 

CAUTION The supplied flexible gaseous pipe is not to be

 

 

 

 

 

 

 

Resources Board for “tamper-proof” fuel systems.

installed underground or in contact with the ground.

 

 

 

 

 

 

Not

 

 

 

• A minimum of one accessible, approved manual

• The entire flexible gaseous pipe must be visible for eriodic

 

 

 

 

inspection and must not be concealed within nor contact nor

un

 

 

shutoff valve shall be installed in the fuel supply line

 

through any wall, floor, or partition.

 

 

 

 

 

within 6 ft (1.8 m) of the generator. A union or flanged

 

• Install the flexible, gaseous hose (suppli d) b

tw

 

 

 

connection shall be provided downstream from this

 

 

 

 

valve to permit removal of controls.

 

the generator Fuel Inlet port and rigid piping to

 

 

 

 

 

 

 

 

prevent thermal expansion or contraction from

• Natural gas fuel supply pressure at the generator’s

fuel inlet port should be between 5 to 7 inches of

causing excessive stress on the piping material.

water (in. W.C.) at full load with all gas appliances

 

Reproduction

Where local conditions include earthquake, tornado,

turned on and operating.

unstable ground, or flood hazards, special consideration

• LP gas fuel supply pressure should be 11 to 14 inches

shall be given to increase strength and flexibility of piping

of water (in. W.C.) at full load with all gas appliances

supports and connections.

turned on and operating.

 

12

It is recommended that the fuel connection incorporate the following components:

A manual fuel shut-off valve located in the interior of the building.

A manual fuel shut-off valve located outside the building, just before the generator unit.

Where the formation of hydrates or ice is known to occur, piping should be protected against freezing. The termination of hard piping should include

a sediment trap where condensate is not likely to freeze.

A manometer port should be provided.

The manometer port permits temporary installation of a manometer to ensure that the engine receives the correct fuel pressure to operate efficiently throughout its operating range.

When the initial test runs are completed, the manometer is removed and the port is plugged. A typical final fuel connection assembly is shown here, where (A) is the fuel supply and (B) goes to the home generator.

A B

Reproduction

 

Fuel Pipe Sizing

 

for

 

The

a e numerous on-li e or otherwise-published

 

efe ences for fuel pipe sizi g. For example, NFPA 54 -

 

Nati

nal Fuel Gas C de, 2006 (Item #: 320-6031-06) is a

Not

mmon resource.

 

The installer should consider the specific gravity of gas

 

and

ompensate for a nominal amount of restriction from

bends, fittings, etc. If an unusual number of fittings, bends, or other restrictions are used, refer to federal and local codes

f r gui ance.

13

Fuel Consumption

Estimated fuel supply requirements at half and full load for natural gas and LP vapor fuels are shown here.

Natural Gas

 

LP Vapor

1/2 Load

Full Load

1/2 Load

 

Full Load

 

 

 

 

 

84 C

162 C

35 C

 

65 C

 

 

 

 

 

84,000 B

162,000 B

86,375 B

 

163,625 B

 

 

 

 

 

C = Cubic feet per hour

 

 

 

B = BTU’s per hour

 

 

 

Physical

LP Vapor

Natural

 

 

Properties

 

Gas

 

 

Normal Atmospheric

Gas

Gas

 

 

State

 

 

 

 

 

 

 

 

 

† Weight is given in “Pounds per

Gallon of Liquid”.

Reproduction

Boiling Point (in °F):

 

 

for

Initial

-44

-259

 

 

End

-44

-259

 

 

Heating Value:

 

Not

 

 

BTU per gallon (Net

 

 

 

 

LHV*)

83,340

63,310

 

 

BTU per gallon (gross**)

91,547

 

 

 

Cubic feet (gas)

2,500

1,000

 

 

Density***

36.39

57.75

 

 

Weight†

4.24

2.65

 

 

Octane Number:

 

 

 

 

Research

110+

110+

 

 

Motor

97

 

 

 

* LHV (Low Heat Value) is the more realistic rating.

 

 

 

** Gross heat value does not consider heat lost in the form of water during

 

 

combustion.

 

 

 

 

*** Density is given in “Cubic Feet of Gas per Gallon of Liquid”.

 

 

 

 

 

 

 

14

System Connectors

Low Voltage connections to signal fault contacts, transfer switch communication, remote LED and auxiliary 12VDC power are made via a removable ten-pole connector plug. Compare this illustration with your generator to familiarize yourself with the location of these connections. Count down to the proper pin location on the control board since visual alignment with the decal can be misleading:

 

Reproduction

 

 

 

 

for

 

 

 

 

B

 

D

 

 

 

 

A

C

E

F

G

A - Fault Contacts — Use NO, COM and C to hook up a

 

D - +12 Volt DC, .5 Amp Output — Internal power supply.

siren, light, etc. to alert you in case of a fault. Contacts

 

E - 240 Volt Utility — Use to hook up the 240V utility leads

reverse state (NO goes to NC and vice versa) upon a fault

 

from the transfer switch to the generator.

condition.

Not

 

 

 

 

F – Ten-pole Connector Plug

 

B - Transfer Switch Communication — Conn

to transfer

 

 

 

G – Two-pole Connector Plug

 

switch control board for communication int

rface using

 

 

 

 

 

 

18AWG copper twisted pair wire.

C - Remote LED Output — Use this to hook up the remote

LED supplied with the generator. The remote LED will turn on and off in a series of blinks if certain faults are detected in the generator.

For power output connection, use #8 AWG minimum 300 volt 75°C-90°C copper wire, (ref. NEC Table 310.16, 100 ft.

Use National Electric Code for correction factors and wire size calculations.)

For Utility Circuit connection use #14 AWG minimum 300 volt 75°C-90°C copper wire

For transfer switch communication use #18 AWG twisted pair conductors, no greater than 200 ft in length, 300 volt 75°C 90°C copper wire

When connecting to the connector plugs, fasten only one wire to each connector screw.

Torque connector plug screws to 7 in-lb (7.9 Newton meter).

15

Generator AC Connection System

A single-phase, three-wire AC connection system is used in

33

the home generator. The stator assembly consists of a pair

22

of stationary windings with two leads brought out of each

winding. The junction of leads 22 and 33 forms the neutral

 

lead, as shown schematically and as a wiring diagram. A

 

complete schematic and wiring diagram can be found later

 

in this manual.

Winding

Neutral is not bonded to ground at generator.

 

Power

 

Circuit

 

Breaker

 

11

 

44

Reproduction

 

 

Not

for

22

33

44

 

11

 

 

 

 

 

Circuit

 

 

 

 

 

 

Breaker

 

 

 

Neutral

Line 2

 

Line 1

 

 

 

 

To Transfer Switch

 

Grounding the Generator

Ground the home generator per applicable codes, standards, and regulations. The generator GND lug is located inside the control panel box.

Neutral

120V

120V

240V

0

Ground

16

Utility Circuit Connection

“240V Utility” leads must be routed in conduit. The “240V Utility” leads deliver power to the generator’s circuit board, optional battery warmer and optional oil warmer. This power also charges the battery. When power on these leads is lost, the generator will start.

Using provided 2 pole connector plug and installer-supplied minimum 300V, 14 AWG copper wire, connect each control circuit terminal in the generator to the two-amp fuse terminals in the automatic transfer switch.

When making connections, obey wire type and torque specifications printed on the circuit breaker and neutral/ ground connector.

Transfer Switch Communication

(Units with ACCM II or later transfer switch only)

 

 

 

Using #18 AWG twisted pair conductors, no greater than

 

 

 

200 ft in length, connect Tx Rx and Tx Rx GND from the

for

 

 

generator control panel (A) to T/R and GND on the transfer

 

 

switch control board (B).

 

A

 

 

 

 

 

Not

 

 

 

 

 

B

Fault Detection System

 

 

 

 

The generator may have to run for long periods of time with

T install the remote LED indicator:

 

 

Reproduction

 

no operator present. For that reason, the system is equipped

 

1. Push the LED through the mounting plate from

with sensors that automatically shut down the generator

 

the front until it snaps in place. The LED is

in the event of potentially damaging conditions, such as

 

polarity sensitive.

 

low oil pressure, high temperature, over speed, and other

2. Using provided 10 pole connector and installer-

conditions. Refer to Fault Detection System in the operator’s

supplied minimum 18AWG wire, connect the remote

manual for more detailed information.

LED to the generator control board +LED and GND

The owner will use the remote LED indicator to observe

connection. Use wire nuts to attach wire to LED leads.

the status of the home generator system. The remote LED

3. Attach mounting plate to installer-supplied

will turn on and off in a series of blinks if certain faults are

electrical box.

detected in the generator system. Consult with the owner

 

for a convenient location. Locate the electrical box in an

 

area visible by the home owner such as near a garage door

 

opener or security control panel.

 

17

System Control Panel

The home generator control panel, located inside the generator housing, is shown below.

C D E F

B

A

Brief descriptions of the controls used during installation are:

A - Set Exercise — Used to set the exercise cycle.

B - Circuit Breaker — Must be ON to supply power to the transfer switch.

C - 15 Amp Fuse — Protects DC control circuits.

D - System Switch — Switches modes to OFF or AUTO.

E – MANUAL OVER-RIDE — Used to manually start and stop the generator.

F - Digital Display — Displays running time in hours or fault codes.

More information may be found in Controls in the operator’s manual.

 

System Switch

 

 

This two-position switch is the most important control on the

 

home generator and is used as follows:

Reproduction

 

for

• “AUTO” position is the ormal operating position. If a

 

 

utility wer

utage is sensed, the system will start

 

 

the generat

r. When utility power is restored, lets the

 

 

engine s ab l ze internal temperatures, shuts off the

Not

 

genera or, and waits for the next utility power outage.

 

• “OFF” position turns off running generator, prevents

 

nit from starting and resets any detected faults.

15 Amp F se

 

Pr tects the home generator DC control circuits. If the fuse

has ‘blown’ (melted open) or was removed, the engine cannot

crank or start. Replace the fuse using only an identical

ATO 15A fuse. One spare fuse is supplied with the unit. If fuse was blown or removed, you will need to reset the exercise timer (see Setting Exercise Timer).

18

Final Installation Considerations

Engine Oil

 

Battery

 

NOTICE Any attempt to crank or start the engine before it has

 

The installer must supply and install a valve-regulated

been properly serviced with the recommended oil will result in

 

rechargeable 12 volt starting battery. The starting battery

equipment failure.

 

MUST conform to the specifications shown in this chart.

Refer to Maintenance in the operator’s manual and engine

 

 

 

 

 

Battery Specifications

 

manual for oil fill information.

 

Damage to equipment resulting from failure to follow this

 

Volts

 

12 Volt DC

 

instruction will void engine and generator warranty.

 

 

 

 

 

 

Amps (MIN)

 

350 CCA (cold cranking amps)

 

 

 

 

This engine is shipped from the factory pre-run and filled with

Type

 

AGM (Absorbent glass mat)

 

 

 

Terminal Hardware

 

M8

synthetic oil (SAE 5W-30). This allows for system operation in

 

 

 

 

 

 

 

Dimensions (MAX):

 

 

a wide range of temperature and climate conditions. Before

 

 

 

 

Width

 

5.325 inches (135mm)

starting the engine, check oil level and ensure that engine is

 

 

serviced as described in the engine operator’s manual.

 

Length

 

7.875 inches (200mm)

 

 

 

 

The use of synthetic oil does not alter the required oil change

Height

 

6.875 inches (175mm)

intervals described in the engine operator’s manual.

 

Install the battery as described in Servicing the Battery in

 

 

 

 

 

 

the Maintenance section of the operator’s manual. Always

 

 

 

make sure the NEGATIVE cable is connected last and that

 

 

 

the ed POSITIVE term

al sulator is fully in place.

 

 

 

 

 

 

 

 

WARNING Ba ery p

sts, terminals and related accessories

 

 

 

contain lead and lead compounds, chemicals known to the State

 

 

 

of California to ause cancer and reproductive harm. Wash hands

 

Not

for

 

 

 

after handling.

 

 

 

 

 

 

Fuel Supply System

Ensure that all fuel pipe connections areReproductiontight, secure and without leaks.

Ensure that all gas line shutoff valves are OPEN and that adequate fuel pressure is available whenever automatic operation is desired.

19

7. Listen for unusual noises, vibration or other indications of abnormal operation. Check for oil leaks while engine runs.

Initial Start-up (No Load)

Unit has been set-up for NG operation at the factory. Fuel conversion, if needed, must be completed prior to performing these steps. See Fuel Conversion later in this section.

5. Set generator’s system switch to AUTO.

 

 

 

Reproduction

6. Push and hold MANUAL OVER-RIDE button on control

DO NOT proceed until you are certain that generator AC

 

 

voltage and freque cy are correct and within the stated

panel for about six seconds. Engine will start.

for

 

When the generator is started for the very first time, it will

limits. To obtain the pr per ge erator frequency, see

Engine Adjustment.

Before operating the home generator or placing it into

8. Let engine warm up for about five minutes to allow

service, inspect the entire installation carefully. Then begin

internal temperatures to stabilize.

testing the system without any electrical loads connected,

9. Check generator output at load side of circuit breaker.

as follows:

 

Voltage should be 239   262 Volts, frequency should

1. Remove four screws that secure control panel to

be 62.0   62.5 Hz.

enclosure to expose unit’s circuit breaker.

If either parameter is outside these ranges, perform Engine

2. Connect an accurate frequency meter to line side of

Adjustment described later in this section.

generator’s main circuit breaker.

 

10. Check generator output between one generator

3. Set generator’s main circuit breaker to ON

connection lug and neutral lug, then between

(closed) position.

 

other generator connection lug and neutral lug.

4. Install 15 Amp fuse in control panel.

In both cases, voltage reading should be between

 

 

119 and 131 Volts.

require that air in the gaseous fuel lines be purged. This may

11.

Push and h ld MANUAL OVER-RIDE button on

take a few minutes.

Not

 

rol panel until engine stops.

 

12.

Reinstall ontrol panel into enclosure.

 

 

 

20

Engine Adjustment

There are regional variances in the composition of natural

 

8. Turn service disconnect to transfer switch OFF.

gas. Each home generator unit leaves the factory set for

 

After a short time delay, transfer switch will connect

NG operation. If the generator output voltage or frequency

 

to generator.

 

measured during Initial Start-Up is outside the listed ranges,

 

9. Load generator to full load.

the combustibility of the gas supplied at the installtion

 

 

10. After load stabilizes, frequency should be

site may be substantially different from the fuel used at

 

 

above 57.0 Hz.

 

the factory.

 

 

 

 

 

11. If frequency is below 57.0 Hz, slowly adjust the

To adjust the engine for this difference, proceed as follows.

 

 

governor until frequency is above 57.0 Hz.

1. Remove four screws that secure control panel to

 

 

12. Turn service disconnect to transfer switch ON.

enclosure to expose unit’s circuit breaker.

 

 

Transfer switch will connect to utility power after

2. Connect an accurate frequency meter to line side of

 

 

five minutes.

 

generator’s main circuit breaker.

 

 

 

 

 

13. Push and hold MANUAL OVER-RIDE button on

3. Ensure that the 15 Amp fuse is installed.

 

 

control panel until engine stops.

4. Set the generator’s main circuit breaker ON.

 

 

14. After the engine has stopped:

5. Set the generator’s system switch to AUTO.

 

 

• If an adjustment was made in step 11, repeat steps

6. Push MANUAL OVER-RIDE button control panel.

 

 

2 through 7.

 

When the engine starts, allow it to warm up for

 

• If an adjustme

t was ot made in step 11, proceed

five minutes.

 

 

 

 

to step 15.

 

7. Normal no load frequency is 62.0 to 62.5 Hz. If

 

 

If no load frequency falls

ut of the no load range shown

adjustment is needed at no load, slowly rota he

in step 7 af er full load adjustment is made, contact an

governor adjustment knob (A) clockwise and/or

authorized servi e center.

counterclockwise until frequency is 62.0 to 62.5 Hz.

for

15. Reinstall control panel into enclosure.

 

Not

 

 

 

 

Reproduction

A

21

Test Shutdown(s) Procedure

The installer will test the system to verify that diagnostic messages are correctly shown on the system control panel digital display, as follows:

three seconds the generator will shut down and FC_5 will be displayed on the system control panel. Turn the system switch to OFF for 30 seconds to clear the fault.

FC_1 - Low Battery

No test procedure required for this fault.

FC_2 - Low Oil Pressure:

Locate wire #85 connected to the oil pressure switch (A):

A

FC_6 - Engine Overspeed

With the system switch in AUTO position, push and hold MANUAL OVER-RIDE to start the generator. Locate the governor lever and SLOWLY raise engine speed. Do NOT change engine speed using the governor adjustment. When the generator output frequency is 65-70 Hz after three seconds the generator will shut down and FC_6 will be displayed on the system control panel. If the generator output frequency is greater than 70 Hz the generator will shut down immediately. Turn the system switch to OFF for 30 seconds to clear the fault.

FC_7 - High Temperature

Connect an installer-supplied jumper wire to wire #85.

 

Locate wire #95 connected to the temperature switch (B):

With the system switch in AUTO position, push the manual

for

 

 

 

over-ride switch to start the generator. With the generator

 

 

 

running, connect other end of jumper to a good ground

 

 

 

location such as the engine block. The generator will shut

 

 

 

down and FC_2 will be displayed on the system con rol

 

 

 

panel. Remove the jumper wire. Turn the system swi ch

B

 

 

OFF for 30 seconds to clear the fault.

 

 

 

 

 

 

 

 

 

 

 

 

 

FC_3 - Low Voltage

 

 

 

 

 

 

With the system switch in AUTO position, push and hold

 

 

 

 

 

MANUAL OVER-RIDE to start the generator. With the

 

 

 

 

 

 

Not

 

 

 

 

generator running at no load, turn the generator circuit

 

C nnect an installer-supplied jumper wire to wire #95. With

breaker to OFF. The generator should shut down and FC 3

 

 

the system switch in AUTO position, push and hold MANUAL

will be displayed on the system control panel. Turn the

 

 

OVER-RIDE to start the generator. With the generator

system switch to OFF for 30 seconds to clear the fault. Turn

 

 

running, connect other end of jumper to a good ground

the circuit breaker to ON position.

 

 

 

 

location such as the engine block. The generator should

FC_4 - Engine Does Not Start

 

 

 

 

shut down and display FC 7 on the system control panel.

With the generator not running, turn the installer supplied

 

Remove the jumper wire. Turn the system switch to OFF for

manual fuel valve to the OFF position. With the system

 

30 seconds to clear the fault.

 

Reproduction

switch in AUTO, turn off utility power. The engine will crank,

 

FC_8 - Transfer Switch Fault

attempting to start. After approximately a two-minute

Verify that utility power is present at the Automatic Transfer

start attempt (10 seconds of crank, 10 seconds of rest) the

Switch. With the system switch in AUTO position, remove

generator should terminate the start attempt and FC_4 will

one of the fuses from the transfer switch. FC_8 will display

be displayed on the system control panel. Turn the system

on the system control panel. Carefully reinstall the fuse in

switch to OFF for 30 seconds to clear the fault. Turn the

the transfer switch, then turn the system switch to OFF for

installer supplied fuel valve to the ON position.

30 seconds to clear the fault

FC_5 - Low Frequency

Analyze Test Results

With the system switch in AUTO position, push and hold

If any test procedure above does not cause the generator

MANUAL OVER-RIDE to start the generator. Locate the

to shut down and display the indicated fault, repair the fault

governor lever and SLOWLY lower engine speed. Do NOT

condition before putting the unit into service.

change engine speed using the governor adjustment.

 

When the generator reaches a speed slower than 55 Hz for

 

22

Fuel Conversion

The engine of your home generator system is factory calibrated to run on natural gas (NG). It may also be operated on liquefied petroleum (LP) vapor. There is no additional hardware/equipment required to switch between either

fuel. However, LP fuel inlet pressure must be between 11 and 14 inches water column at full load with all gas appliances turned on and operating.

To configure the fuel system for LP use:

1.Set generator’s system switch to OFF.

2.Remove 15 Amp fuse from control panel.

3.Open oil fill access panel.

4.Connect the fuel select solenoid by joining the two-pin electrical connector (C).

 

 

 

Reproduction

 

 

C

 

for

 

 

 

Not

 

5.

Reinstall 15 Amp fuse in control panel.

 

6.

Set generator’s system switch to AUTO.

 

7.

Close access panels.

 

 

 

The system is now ready to operate automatically using

LP vapor fuel.

23

Ge HOME GENERATOR 10000 Manual

Schematic Diagram

Not

for

 

Reproduction

24