Flowserve MX HART Field Unit User Manual

USER INSTRUCTIONS
MX/QX HART Field Unit
FCD LMENIM2340-00 – 1/14
Installation
Operation
Maintenance
Experience In Motion
MX/QX HART Field Unit FCD LMENIM2340-00 – 1/14
Contents
1 Introduction 6
1.1 Purpose 6
1.2 How to Use This Manual 6
1.3 User Safety 7
1.4 User Knowledge 7
1.5 MX/QX HART System Capabilities and Features 7
1.5.1 General Network Specification 8
2 System Components and Installation 9
2.1 Introduction 9
2.2 Hardware 9
2.2.1 MX/QX Electronic Actuators 9
2.2.2 MX/QX HART Interface Board 11
2.2.3 Network Host 11
2.2.4 Network Cable 11
2.2.5 Typical HART Network Configuration 11
2.3 Network Cabling Topologies 12
2.4 Site and Network Cable Preparation 13
2.4.1 Site Preparation 13
2.4.2 Network Cable Preparation 13
2.4.2.1 Network Cable Connection to the MX/QX HART Unit 13
2.5 MX/QX HART Device Installation and Setup 14
2.5.1 MX/QX HART Device Installation 14
2.5.2 MX/QX HART Device Setup 14
2.6 Installation Verification 16
2.6.1 Network Cabling Installation Verification 16
2.6.2 MX/QX HART Device Installation Verification 16
2.7 Configuration Confirmation 17
2.7.1 Checking Connections 17
2.7.2 View Settings 17
2.7.3 Checking the Normal Display 18
2.8 MX/QX HART Device Description and Device Type Manager Files 18
3 Software 19
3.1 HART Protocol 19
3.2 HART Parameters 19
3.2.1 Analog Input Ratings 19
3.2.2 Field Device Status 20
3.3 Dynamic Variables 20
3.4 Device Variables 20
3.4.1 Supported Device Variables 20
3.4.2 Device Variable Mapping 21
3.4.3 Device Variable Units 21
3.5 Supported HART Commands 22
3.5.1 Universal Commands 22
3.5.1.1 Command 48 Data 24
3.5.2 Common Commands 29
3.5.3 Burst Messages 33
3.5.3.1 Update Periods 33
3.5.3.2 Commands Supported for Burst Message 34
3.5.3.3 Configuring a Device for Burst Mode Operation 34
3.5.3.4 Burst Message Trigger Mode 35
3.5.3.5 Burst Trigger Mode 35
MX/QX HART Field Unit FCD LMENIM2340-00 – 1/14
Contents (Continued)
3.5.4 Event Notification 35
3.5.4.1 Configuring Event Notification 36
3.5.4.2 Handling of Event Notifications 37
3.5.4.3 Update Periods 37
3.6 Device-Specific Commands 37
3.6.1 Remote Configuration Mode 37
3.6.2 Partial Stroke Test 39
3.6.3 Actuator Commands 41
3.7 Calibration 42
3.7.1 Loop Current Trim Procedure 42
3.7.2 Re-range Procedure 45
3.7.3 Analog Signal to Primary Variable Process Flow 47
4 Associated Documents 49 5 How to Order Parts 50 Appendix A – Wiring Diagrams 51 Appendix B – HART Data Formats 52 Appendix C – Enumeration and Bit Field Tables 52-55 Appendix D – Setting Data and Time 56 Appendix E – Command Response Codes 56-67
flowserve.com
MX/QX HART Field Unit FCD LMENIM2340-00 – 1/14
Figures
Figure 2.1a – MX-05 Actuator and Figure 2.1b – QX-05 Actuator 10 Figure 2.2 – Typical HART System With a DCS Host 11 Figure 2.3 – Point-to-Point Topology (Host Powered) 12 Figure 2.4 – Point-to-Point Topology (Loop Powered) 12 Figure 2.5 – Multi-drop Topology (Host Powered) 12 Figure 2.6 – Multi-drop Topology (Loop Powered) 13 Figure 2.7 – Connecting Network Cable to MX/QX Terminal Block 14 Figure 2.8 – MX/QX HART Setup Sequence 15 Figure 2.9 – MX/QX HART View Settings Sequence 17 Figure 2.10 – Normal Display 18 Figure 3.1 – Device Variable Mapping Setup 21 Figure 3.2 – Device Variable Units 22 Figure 3.3 – HART Diagnostics Data 28 Figure 3.4 – Burst Messages 34 Figure 3.5 – Trigger Mode 1 “Windowed” 35 Figure 3.6 – Event Notification 36 Figure 3.7 – Event Mask 36 Figure 3.8 – Remote Configuration Mode 37 Figure 3.9 – Analog Signal to Primary Variable Process Flow 48 Figure 5.1 – Device Variable Status Byte Format 53
MX/QX HART Field Unit FCD LMENIM2340-00 – 1/14
Tables
Table 2.1a – MX Actuator Components and Table 2.1b – QX Actuator Components 10 Table 3.1 – HART Parameters 19 Table 3.2 – Analog Input Ratings 19 Table 3.3 – Field Device Status 20 Table 3.4 – Supported Dynamic Variables 20 Table 3.5 – Supported Device Variables 20 Table 3.6 – Mapping of Device Variables to Dynamic Variables 21 Table 3.7 – HART Universal Commands 22 Table 3.8 – HART Defined Status Bits 25 Table 3.9 – MX/QX Defined Status Bits 26 Table 3.10 – Common Commands 29 Table 3.11 – Trigger Source for Burst Message Commands 35
flowserve.com
MX/QX HART Field Unit FCD LMENIM2340-00 – 1/14
Introduction
1
1.1 Purpose
This manual explains how to install and operate the MX/QX HART field unit. Actuators containing the HART field unit may be connected by a standard instrumentation twisted-pair cable to form a HART communication system network. The HART network employs a bi-directional communication protocol, operating at 1200 bits/sec, that provides data access between intelligent actuators and host control/monitoring systems. In addition to a digital signal, the network simultaneously provides a 4-20 mA analog signal that is proportional to the field unit’s primary measured value. This system allows a host system such as a distributed control system (DCS) to control and monitor the actuators, including the acquisition of status and alarm data from each MX/QX.
1.2 How to Use This Manual
Each section provides the MX/QX HART user with information on installing and operating the MX/QX HART field unit.
Section Title Description
1 Introduction
2 System Components
3 Installation and Configuration Provides details for installing and configuring a field unit.
4 Associated Documents
5 How to Order Parts
Appendix A Wiring Diagram Detail wiring connections to the MX/QX field unit.
Appendix B HART Data Formats Listing of HART parameters and descriptions.
Appendix C Enumeration and Bit Field Tables Explains field device bit masking information.
Appendix D Setting Date and Time Defines real-time clock configuration settings.
Appendix E Command Response Codes
Details user safety and knowledge requirements, system capabilities and features.
Focuses on the description of the HART system hardware and software components.
Provides a list of documents on related subjects for additional MX/QX and HART system information.
This section provides part numbers and ordering contact information.
Listing of response codes for all universal and common HART commands.
MX/QX HART Field Unit FCD LMENIM2340-00 – 1/14
1.3 User Safety
Safety notices in this manual detail precautions the user must take to reduce the risk of personal injury and damage to the equipment. The user must read and be familiar with these instructions before attempting installation, operation, or maintenance. Failure to observe these precautions could result in serious bodily injury, damage to the equipment, warranty void, or operational difficulty. User must follow local and state safety regulations.
Safety notices are presented in this manual in three forms:
c WARNING: Refers to personal safety. Alerts the user to potential danger. Failure to follow warning notices could
result in personal injury or death.
a CAUTION: Directs the user’s attention to general precautions that, if not followed, could result in personal injury
and/or equipment damage.
NOTE: Highlights information critical to the user’s understanding of the operator’s installation and operation.
1.4 User Knowledge
It is recommended that the user read this manual in its entirety before the MX/QX HART equipped actuator is installed and operated.
The user needs to have a fundamental knowledge of electronics and microprocessor concepts. An understanding of valve actuators and digital control systems is beneficial to the field unit user. Refer to the Glossary for terms used throughout this manual.
The following websites have documents on HART and electric actuators: www.hartcomm.org and www.flowserve.com
For HART technology and cabling information, refer to the following documents:
HART Communication Protocol Specification: HCF_SPEC-13 HART Communication FSK Physical Layer Specification: HCF_SPEC-54 HART Communication Command Summary Specification: HCF_SPEC-99 HART Communication Universal Command Specification: HCF_SPEC-127 HART Communication Common Practice Command Specification: HCF_SPEC-151 HART Communication Common Tables: HCF_SPEC-183
1.5 MX/QX HART System Capabilities and Features
Limitorque’s HART field unit conforms to the HART Communication Protocol Specification (Document HCF_SPEC-
13). The device is suitable for use on point-to-point and multi-drop network topologies. The communication system theoretically supports up to 26 actuators connected in a multi-drop network.
The MX/QX HART field unit fits in the actuator in the sealed electrical housing. Adjustments to the MX/QX HART settings must be made from the configuration SETUP menu.
The MX/QX HART field unit may command its actuator to:
Open Stop Close Move to a set position Perform an emergency shutdown operation Read and control relays Perform partial stroke test Monitor analog inputs and position Monitor modes and alarms
flowserve.com
MX/QX HART Field Unit FCD LMENIM2340-00 – 1/14
Commands to the unit come over the network from the host system, which may be:
• Personal Computer (PC)
• Distributed Control System (DCS)
• Programmable Logic Controller (PLC)
• Field Device Tool (FDT) w/Device Type Manager (DTM)
• Some other microprocessor-based device
A HART field device is an intelligent device within the actuator that can send multiple digital device variables to the control system over a 4-20 mADC analog signal loop. The device provides control and self-test capabilities, which allow abnormal conditions to be easily and immediately identified before an unplanned shutdown occurs.
Additional features and capabilities are:
• The system reduces the cost of wiring and installation – existing wiring and multi-drop connections can be used.
• The devices are interoperable – devices from different suppliers can communicate with one another on the same
network.
1.5.1 General Network Specification
System Specifications:
Communications using the HART Communication Foundation Protocol
Network Specificationss:
• Point-to-point and multi-drop topologies
• Master/slave communication
• Simultaneous 1200 bps digital communication without 4-20 mADC signal interruption
• Up to two masters per network (primary and secondary)
• Burst mode for continuous message broadcasting
MX/QX HART Unit Specification:
The field unit mounts in the actuator and is software-controlled in order to allow functionality of:
• Dynamic Variables PV, SV, QV and TV
• Device Variables: Position Setpoint, Measured Position, Torque, Motor Temperature and Compartment Temperature
• Network Communication
• Device-Specific Commands
System Host Specifications:
The HART master is the network system host, and can be a personal computer (PC), distributed control system (DCS), programmable logic controller (PLC), or another microprocessor-based device. The HART protocol allows for up to two masters (primary and secondary) per network loop. Secondary masters, such as handheld communicators, can be used without interrupting communications between the primary master and field devices.
MX/QX HART Field Unit FCD LMENIM2340-00 – 1/14
System Components
2
and Installation
2.1 Introduction
This section is an overview of the components used in the HART system and their installation. The MX/QX HART unit is installed in the MX or QX actuator, as shown in Figures 2.1 and 2.2. The network cable connects to the HART unit at the actuator terminal block. The network cable connects to the distributed control system, which usually acts as the host.
2.2 Hardware
2.2.1 MX/QX Electronic Actuators
The MX/QX actuators control the opening and closing of valves. The MX is a multi-turn valve, while the QX is a quarter­turn valve actuator. Both actuators are designed for operation of ON-OFF and modulating valve applications.
The MX/QX features include the following:
• Non-intrusive setup
• Separately sealed terminal compartment
• Patented absolute encoder for valve position sensing (no battery required)
• Graphical LCD for indication and calibration
• Sophisticated electronic control, monitoring, and diagnostic capabilities with patented LimiGard™ technology
NOTE: Recommended storage procedures for the MX are detailed in Bulletin LMENIM2306, MX Maintenance and Spare Parts Manual. QX procedures are detailed in Bulletin LMENIM3306, QX Maintenance and Spare Parts Manual. Failure to comply with recommended procedures will void the warranty. For longer-term storage, contact Limitorque for procedure and recommendations.
flowserve.com
MX/QX HART Field Unit FCD LMENIM2340-00 – 1/14
Figure 2.1a – MX-05 Actuator Figure 2.1b – QX-05 Actuator
1
10
3
11
13
5
12
2
9 OPTIONAL
15
1
9
7
4
9
3
14
8
6
3
3
11
10
9
12
4
8
7
2
2
5
6
10
Table 2.1a – MX Actuator Components Table 2.1b – QX Actuator Components
Item Description Item Description
1 Handwheel 1 Handwheel 2 Declutch lever 2 Declutch lever (QX-05) 3 Oil fills (dotted arrow depicts fill on declutch side) 3 Oil fill 4 Controls compartment (field unit location) 4 Controls cover 5 LCD display 5 LCD display 6 Control knobs 6 Control knob 7 Ground lug 7 Ground lug 8 Thrust/torque base 8 Baseplate
9 Conduit entries 9 Conduit entry 10 Terminal compartment 10 Terminal compartment 11 Electric motor 11 Motor 12 Nameplate 12 Certification nameplate
13 Tag nameplate 14 Oil plug 15 Stem nut stops
MX/QX HART Field Unit FCD LMENIM2340-00 – 1/14
2.2.2 MX/QX HART Interface Board
The MX/QX HART field unit interface board is installed in the actuator controls compartment (Figures 2.1 & 2.2 and Tables 2.1 & 2.2). This unit permits the actuator to be controlled by a DCS or other network host over the HART network.
The following commands and feedback information are transmitted through this unit:
• OPEN, CLOSE and STOP commands
• ESD (Emergency Shutdown) commands
• Partial Stroke Test commands
• Unit output torque (0-100% rating)
• Go-to-position commands
• Actuator status, alarm and diagnostic messages
• User analog input feedback
2.2.3 Network Host
The HART network is a master/slave communication protocol. Communication to each slave (MX/QX field device) is initiated by a master (system host device). Two masters can connect to each HART loop. Normally, the primary master is a DCS, PLC, or PC. If desired, a handheld communicator or PC can serve as the secondary master.
2.2.4 Network Cable
Network cabling should be in accordance with the HART Communication Foundation guidelines. In general, wiring for HART devices is the same as for conventional 4-20 mA instrumentation. It is recommended to use individually shielded twisted pair cable. The minimum conductor size is 0.51mm diameter (#24 AWG) for cable runs less than 1500 meters (5000 ft.), and 0.81mm diameter (#20 AWG) for distances up to the 3000 meter (10 000 ft.) theoretical limit for HART communication. Please note that the electrical characteristics of the cable, especially capacitance, and the number of network field devices can affect the maximum allowable cable length.
To prevent signal loop interference, tie all cable shields together and ground at only one point.
2.2.5 Typical HART Network Configuration
A typical MX/QX HART system is shown below:
Figure 2.2 – Typical HART System With a DCS Host
flowserve.com
11
MX/QX HART Field Unit FCD LMENIM2340-00 – 1/14
2.3 Network Cabling Topologies
There are two main topologies for MX/QX HART networks:
Point-to-point One field device connected to the bus (network)
Figure 2.3 – Point-to-Point Topology (Host Powered)
Figure 2.4 – Point-to-Point Topology (Loop Powered)
12
Multi-drop Multiple field devices connected to the bus (network)
Figure 2.5 – Multi-drop Topology (Host Powered)
Figure 2.6 – Multi-drop Topology (Loop Powered)
2.4 Site and Network Cable Preparation
MX/QX HART Field Unit FCD LMENIM2340-00 – 1/14
2.4.1 Site Preparation
Prepare the site and associated equipment for operation of the MX/QX HART actuators as follows:
1. Prepare a detailed site plan consisting of the following:
• Actuator locations and tag numbers
• Junction boxes, terminal strip locations and tag numbers
• Power supplies/conditioners
• Provide free access to the MX/QX control panel and terminal block for setup, configuration and troubleshooting.
2. Prepare the cable and label all wires.
3. Install power and control wires in separate conduits.
4. Install and verify earth grounds. The cable shields should be tied together and grounded at only one point. The single ground point is typically located at or near the system host device.
2.4.2 Network Cable Preparation
Care must be taken during cable preparation:
• When stripping the insulation, use wire strippers that do not nick the wire.
• Use crimp ferrules to prevent stranded wires from getting loose and shorting to other wires.
• Use vibration-resistant wiring terminals that hold the ferrule securely.
2.4.2.1 Network Cable Connection to the MX/QX HART Unit
The field device is connected to the network through the MX/QX terminal block. The network cable is connected to the terminal block shown in Figure 2.7.
13
flowserve.com
MX/QX HART Field Unit FCD LMENIM2340-00 – 1/14
Figure 2.7 – Connecting Network Cable to MX/QX Terminal Block
Shielded Wire Pair
HART
Interface
Field
Device
Field
Device
Connect Shield to Ground at one place only
Field
Device
Connect the network cables to the MX/QX terminal block as shown in Figures 2.3 – 2.6. Refer to Appendix A for unit wiring diagram.
Connect the cable shields to each other inside the unit. Do not connect them to the unit in any way. The network shield should be grounded at only one place in the network. If it is desired to ground the entire network shield at the actuator, then install a jumper cable from terminal 3 to earth ground or ground lug.
NOTE: The MX/QX HART device is sensitive to polarity. The cables should be labeled to indicate polarity, and polarity should be maintained through all connection points.
2.5 MX/QX HART Device Installation and Setup
2.5.1 MX/QX HART Device Installation
The MX/QX HART field unit is located in the controls compartment. It has four standoffs and mounts on top of the main processor board. Multiple Input/Output (I/O) option boards may also be present. If present, the I/O board will be on top of the MX/QX HART unit. For installation instructions, refer to the MX Maintenance and Spare Parts Manual, LMENIM2314 or the QX Maintenance and Spare Parts Manual, LMENIM3314.
14
2.5.2 MX/QX HART Device Setup
The MX/QX HART option enables the actuator to be controlled by a HART communications signal. If the option has been purchased, it is automatically enabled.
NOTE: If the HART option has not been purchased, the screens for changing HART will not be available. To add the HART option, please consult Limitorque service at (434) 528-4400.
Figure 2.8 illustrates the setup sequence. For proper operation, the correct mode must be selected.
To set up the MX or QX HART device, enter the Setup mode as detailed in Installation and Operation Manual Bulletins LMENIM2306 for the MX and LMENIM3306 for the QX;
Figure 2.8 – MX/QX HART Setup Sequence
ESD ACTION
(IGNORE)-OK?
(CLOSE)- OK?
(STOP)- OK? (OPEN)- OK?
(POSITION)- OK?
CHANGE
HART
STATUS
(ON)-OK?
(OFF)-OK? (ENABLED)-OK?
MOVE TO
XXX% OPEN
MULTI-DROP
(DISABLED)-OK?
If Hart Actuator & not Multidrop
FAIL POSITION (CLOSED)-OK?
If fail position is
“position”
If fail position is
not “position”
(OPEN)- OK? (STOP)- OK?
(POSITION)- OK?
XXX%-OPEN
MOVE TO
If Hart Actuator
& Multidrop
MX/QX HART Field Unit FCD LMENIM2340-00 – 1/14
POLLING ADDRESS
(0)-OK?
Address default is zero
Range is 0-63
SAVE
SETTINGS-OK?
CHANGE PROP/
DEADBAND?
YES
NO
PROP BAND
(5%)-OK?
DEADBAND
(2%)-OK?
NOTE: This menu is displayed after the actuator and HART board have been powered up together at least one time.
1. Proceed through Setup to the CHANGE HART? display. Select YES to get to the STATUS display.
2. STATUS enables the user to change from the default condition to turn on and off the network control capability of the actuator. Select NO to change the setting or YES to get to the next display. (Default = ON)
3. MULTI-DROP (ENABLED) or (DISABLED) allows the user to select the desired network topology. To change the setting, select NO until the required option is displayed. Select YES if the setting is correct to go to the next display.
NOTE: Changing the topology also requires that the network be wired correctly for the selected topology.
NOTE: If MULTI-DROP ENABLED was chosen, skip to step 5. Otherwise, FAIL POSITION display is shown. In multi-drop
mode the input is digital only (write PV over network), so there is no analog fail action.
4. FAIL POSITION allows the user to configure the action desired upon loss of the analog input signal. The selections are CLOSE, OPEN, STOP and POSITION. Select the desired setting and proceed to the next display.
NOTE: If POSITION is chosen as the action, a MOVE TO display will be shown where the user can select the desired position between 0 and 100% open, in one percent increments, by selecting NO until the desired position is selected. Select YES once the setting is correct to go to the next display.
5. POLLING ADDRESS allows the user to set the HART polling address of the unit. Point-to-Point units are typically set to address 0, and Multi-drop units are typically set from 1-63. HART 5 masters will always set Point-to-Point units to address 0.
6. SAVE SETTINGS allows the user to save the settings and make them active. This can result in a change in the hardware configuration on the HART board to support the change in configuration. Select NO to return to STATUS (step 2) and change settings. Select YES to save the HART configuration settings and go to additional network settings.
NOTE: The configuration set in steps 1-6 will not be saved if the user does not select YES for SAVE SETTINGS.
flowserve.com
15
MX/QX HART Field Unit FCD LMENIM2340-00 – 1/14
7. CHANGE PROP/DEADBAND allows for the setting of proportional band and deadband. Proportional band is the range of errors between the position and demand signal that will produce reduced speed (pulsing). The default value is 5%. To change from default, select NO until the required value is displayed. The value is adjustable between 1% and 100%, in 1% increments. The default deadband value is 2%. For error signals less than this, no motion occurs. The deadband should be wide enough to prevent “hunting” of the actuator but as low as possible to give adequate response to changes in the error signal. To change from the default, select NO to adjust the value between 1% and 50%, in 1% increments to suit the application.
8. ESD ACTION allows a network ESD function to be enabled after the ESD configuration has been established for the unit. This network ESD can be selected to do one of the following: ignore the command (NONE), CLOSE, OPEN, STOP or POSITION the actuator. To change from the default setting, select NO until the required option is displayed. Select YES if the setting is correct to go to the next display.
NOTE: If POSITION is chosen as the action, a MOVE TO display will be shown where the user can select the desired position between 0 and 100% open, in one percent increments, by selecting NO until the desired position is selected. Select YES once the setting is correct to go to the next display.
.2.6 Installation Verification
2.6.1 Network Cabling Installation Verification
After installation is complete and prior to operation, inspect the network cable and its connection to each field device. NOTE: Units should be disconnected from power. The network should be disconnected from the host device. Check for the following:
1. There should not be:
• Nicks in the insulation - this can cause a short to the grounded shield.
• Cut strands in a stranded conductor - this can cause a poor connection and eventually an open circuit.
2. The shield/drain wire should only be grounded at one point in the segment to avoid ground loop problems.
3. The ground/earth connection should be at true ground potential and effective at all times. See step No. 5 in Section
2.4.1, Site Preparation.
2.6.2 MX/QX HART Device Installation Verification
Verify the field device is installed as follows:
1. Enter the Setup mode as detailed in Installation and Operation Manual Bulletins LMENIM2306 for the MX or LMENIM3306 for the QX.
2. In the Setup mode, use the black control knob to select YES to the main menu selection. VIEW DIAGNOSTICS?
3. Select YES to the display VIEW HARDWARE STATUS?
4. Select YES to scroll through the menu selections. The LCD will read HART BOARD 1 (OK) - NEXT? if installed.
NOTE: If the HART BOARD 1 (OK)? does not appear, contact Limitorque for assistance.
5. To return to the normal display, use the black knob to select either LOCAL or REMOTE.
16
MX/QX HART Field Unit FCD LMENIM2340-00 – 1/14
2.7 Configuration Confirmation
Field device operation cannot be verified until the complete HART system is operational. However, routine checks can be performed to verify many functions.
2.7.1 Checking Connections
Verify that all connections, including data wires, shield ground, digital inputs (optional), digital outputs (optional), and analog inputs are in accordance with MX/QX wiring diagrams and MX/QX HART device diagrams in Appendix A.
2.7.2 View Settings
Refer to Installation and Operation Manual Bulletins LMENIM2306 for the MX and LMENIM3306 for the QX to access the view settings menu. Verify the settings as follows:
1. From the VIEW SETTINGS display, scan to the VIEW HART? display
2. From VIEW HART? display, select YES and check that the HART status is ON. This confirms that HART is enabled.
3. From HART STATUS display, select YES to go to next display, which is DEVICE ID. This is the Unique Device ID of the HART device.
4. If the MX/QX contacts are to be controlled via the network to control external equipment, from the VIEW HART? display, select NO and obtain the VIEW STATUS AND ALARM CONTROL? display. Verify that the digital outputs, S1a, S1b, S2a, S2b are set for “Network” controlled.
Figure 2.9 – MX/QX HART View Settings Sequence
VIEW
HART?
STATUS
(ON)-OK?
DEVICE ID
3295509-OK?
If Hart Actuator & not Multidrop
FAIL POSITION
(CLOSE)-OK?
If fail position is
“position”
HART-1 FIRMWARE
REV 25-OK?
MOVE TO
XXX% OPEN
If Hart Actuator
& Multidrop
If fail position is
not “position”
HART-1 HARDWARE
REV 25-OK?
POLLING ADDRESS
(0)-OK?
MULTI-DROP
(DISABLED)-OK?
PROP BAND
(5%)-OK?
DEADBAND
(2%)-OK?
ESD ACTION
(IGNORE)-OK?
MOVE TO
XXX% OPEN
flowserve.com
17
MX/QX HART Field Unit FCD LMENIM2340-00 – 1/14
2.7.3 Checking the Normal Display
Place the selector switch in LOCAL or REMOTE position. The valve position will be indicated at the top of the LCD. STATUS OK or HARDWARE FAILURE should be indicated at the bottom of the LCD display.
• If STATUS OK is displayed, then the HART board hardware is OK.
• If HARDWARE FAILURE and HART-1 FAILED or HART-1 NOT PRESENT is displayed, no communication is occurring.
This could be due to a number of factors. Check all local connections and configurations. If these are correct and the HARDWARE FAILURE is still displayed, then the solution to this problem must await full system commissioning.
Figure 2.10 – Normal Display
Remot e
or
Local
100% OPEN
STATUS OK
2.8 MX/QX HART Device Description and Device Type Manager Files
In the Host system, the configuration device can use Device Description (DD) files to configure a HART system without having the devices online. Please refer to your host system documentation for the files that are needed. The Device Type Manager (DTM) file provides an interface between the actuator’s specific application software and a Network Host Station’s Field Device Tool (FDT) frame. The DTM can be integrated into FDT frame applications to allow users to perform offline and online parameterization, configuration, and status and diagnostic retrieval. The DD files are downloaded from the HART Communication Foundation website (www.hcfcomm.org) into the DCS workstation or host device.
In addition, the DD and DTM files can be downloaded from the Flowserve Limitorque website: www.flowserve.com
18
MX/QX HART Field Unit FCD LMENIM2340-00 – 1/14
Software
3
3.1 HART Protocol
The system uses the HART protocol to communicate over the HART network with other HART devices. The HART protocol is a master/slave communication service for process control devices. HART digital signaling is an extension of conventional analog signaling allowing the network signal to ride on the 4-20 mADC analog process signal. It uses 1200 bps binary phase-continuous Frequency-Shift-Keying (FSK), where a high frequency current is superimposed on a low-frequency (typically 4-20 mADC) analog current.
3.2 HART Parameters
Table 3.1 – HART Parameters
Parameter Value
HART Version 7.3 Expanded Device Type = Manufactuer ID + Device Type 0x3008 Physical Layer Supported FSK Physical Device Catagory Actuator Maximum Number of Burst Messages 3 Maximum Number of Event Messages 1 Size of the Event Queue 6 Maximum Number of Trends 2 Size of the Trend Buffer 12 Default Number of Preambles1 5
3.2.1 Analog Input Ratings
Table 3.2 – Analog Input Ratings
Maximum current2 30.0 mA Maximum voltage 50 V
Current over-range
(Primary Variable Out of Limits)
Multi-drop current draw Approximately 2 mA
1. Field Device must have minimum 5 preambles, and maximum 20 preambles.
2. The analog input is automatically bypassed, if the maximum loop current is reached. The field device will continue to check the circuit for overload on a periodic basis, and will restore the connection if the overload clears.
Analog Input > 21 mA Analog Input < 3 mA
(HART communication may fail, if Analog Input <2 mA.)
19
flowserve.com
MX/QX HART Field Unit FCD LMENIM2340-00 – 1/14
3.2.2 Field Device Status
The Field Device Status is contained in the second data byte in a Slave-to-Master frame as a bit field table. It indicates the current operating status of the field device as a whole and is not associated with the completion of any command.
Table 3.3 – Field Device Status
Bit Mask Description
0x01 Primary Variable Out of Limits – The PV is beyond its operating limit. 0x02 Non-Primary Variable Out of Limits – A device variable not mapped to PV is beyond its operating limits.
0x04
0x08 Loop Current Fixed – The loop current is being held at a fixed value and is not responding to process variations. 0x10 More Status Available – More status information is available via Command 48, Read Additional Status Information. 0x20 Cold Start – A power failure or Device Reset has occurred. 0x40 Configuration Changed – An operation was performed that changed the device’s configuration. 0x80 Device Malfunction – The device detected a serious error or a failure that compromises device operation.
Loop Current Saturated – The loop current has reached its upper (or lower) endpoint limit and cannot increase (or decrease) any further.
3.3 Dynamic Variables
The Limitorque HART actuator device supports the following Dynamic Variables:
Table 3.4 – Supported Dynamic Variables
Variable Code Variable Direction Physical Interface
0 PV (Primary Variable) input Analog current input – Analog Channel 0 1 SV (Secondary Variable) output None 2 TV (Tertiary Variable) output None 4 QV (Quaternary Variable) output None
3.4 Device Variables
3.4.1 Supported Device Variables
The Limitorque HART actuator device supports the following Device Variables:
Table 3.5 – Supported Device Variables
Variable
Code
Variable Direction Unit Code
0 Position setpoint input % (57) Not Classified (0) Valve/Actuator (6) 0-100 1 Current position output % (57) Not Classified (0) Not Used (250) 0-100 2 Torque output % (57) Not Classified (0) Not Used (250) 0-100 3 Motor temperature output °C (32), °F (33) Temperature (64) Not Used (250) Not Limited
Compartment
4
temperature
output °C (32), °F (33) Temperature (64) Not Used (250) Not Limited
Device Variable Classification
Device Variable Family
Range
20
MX/QX HART Field Unit FCD LMENIM2340-00 – 1/14
3.4.2 Device Variable Mapping
Device Variables may be mapped to the Dynamic Variables according to the following table:
Table 3.6 – Mapping of Device Variables to Dynamic Variables
Variable
Code
0 PV input Position Setpoint Position Setpoint 1 SV output Current Position Current Position or Torque
2 TV output Motor Temperature
3 QV output Compartment Temperature
No single Device Variable may be mapped to more than one Dynamic Variable.
For Example:
Valid Mapping: Invalid Mapping:
PV = DV0 PV = DV0 SV = DV1 SV = DV1 TV = DV3 TV = DV1 QV = DV4 QV = DV4
Dynamic Variable
Direction Default Device Variable
Device Variables which may be mapped to the Dynamic Variable
Current Position, Torque, Motor Temperature or Compartment temperature
Current Position, Torque, Motor Temperature or Compartment temperature
If you try to map two Dynamic Variables to the same Device Variable, the command will return response code 2 “invalid selection”. The Device Variables may be mapped from the DD menu Device Setup->Wired HART Board->Configuration-> Device Variable Mapping as follows:
Figure 3.1 – Device Variable Mapping Setup
3.4.3 Device Variable Units
Device Variables 0, 1, and 2 have fixed units that may not be changed. Device Variables 3 and 4 have units that may be interchanged between °C and °F the default is °F. For Device Variables 3 and 4, the units may be changed from the DD menu Process Variables->Wired HART Board as follows:
flowserve.com
21
MX/QX HART Field Unit FCD LMENIM2340-00 – 1/14
Figure 3.2 – Device Variable Units
3.5 Supported HART Commands
The following Universal and Common HART commands are supported by the Limitorque MX/QX HART device. See Appendix B for more information on HART data formats such as: Packed, Latin-1, Date and Time. See Appendix C for more information on “Enum” or “Bits” formats. See Appendix E for more information on valid Response Codes for each command.
22
3.5.1 Universal Commands
Table 3.7 – HART Universal Commands
Command Request Data Bytes Response Data Bytes
No. Description Byte Format Description Byte Format Description
0 Read Unique
Identifier
1 Read Primary
Variable
2 Read Loop
Current And Percent Of Range
3 Read Dynamic
Variables And Loop Current
6 Write Polling
Address
7 Read Loop
Configuration
0
Unsigned-8
1
Enum
Polling Address of Device Loop Current Mode
0 1-2 3 4 5 6 7 7 8 9-11 12 13 14-15 16
17-18 19-20 21
0 1-4
0-3 4-7
0-3 4 5-8 9 10-13 14 15-18 19 20-23
0 1
0 1
Unsigned-8 Enum Unsigned-8 Unsigned-8 Unsigned-8 Unsigned-8 Unsigned-5 Enum Bits Unsigned-24 Unsigned-8 Unsigned-8 Unsigned-16 Bits
Enum Enum Enum
Enum Float
Float Float
Float Enum Float Enum Float Enum Float Enum Float
Unsigned-8 Enum
Unsigned-8 Enum
254” Expanded Device Type = 0x3008 Min. number of request preambles = 5 HART Protocol Major Rev. = 7 Device Rev. Level Software Rev. Level (5 MSB) Hardware Rev. Level (3 LSB) Physical Signaling Code=0 Device Flag Assignment = 1 Device ID (unique for given device type) Min. number of response preambles=5 Max. number of device variables = 5 Configuration Change Counter Extended Field Device Status: 0=OK, 1=Maintenance req’d, 2=Device Alert Manufacturer Identification Code = 0x0030 Private Label Distributor Code = 0x0030 Device Profile = 1
Primary Variable Units = 57 (%) Primary Variable
Primary Variable Loop Current (mA) Primary Variable % Of Range
Primary Variable Loop Current (mA) Primary Variable Unit Code Primary Variable Secondary Variable Unit Code Secondary Variable Tertiary Variable Units Code Tertiary Variable Quaternary Variable Unit Code Quaternary Variable
Polling Address of Device (0-63) Loop Current Mode
Polling Address of Device (0-63) Loop Current Mode
Loading...
+ 50 hidden pages