Flowserve MX-100 User Manual

USER INSTRUCTIONS
MX/DDC-100 Field Unit
FCD LMENIM2329-0103/11
Installation
Operation
Maintenance
Experience In Motion
MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-0103/11
MX/DDC-100 Field Unit Installation and Operation Manual
©2011 Copyright Limitorque. All rights reserved. Printed in the United States of America.
Disclaimer
This document is meant for use with MX Installation and Operation Manual for MX-05 through MX-40. Information in this document is also applicable to MX-85 through MX-150. No part of this book shall be reproduced, stored in a retrieval system, or transmitted by any means, electronic, mechanical, photocopying, recording, or otherwise without the written permission of Limitorque. While every precaution has been taken in the preparation of this book, the publisher assumes no responsibility for errors or omissions. Neither is any liability assumed for damages resulting from the use of the information contained herein.
This document is the proprietary information of Limitorque, furnished for customer use ONLY. No other uses are authorized without written permission from Limitorque.
Limitorque reserves the right to make changes, without notice, to this document and the product it describes. Limitorque shall not be liable for technical or editorial errors or omissions made herein; nor for incidental and consequential damages resulting from the furnishing, performance or use of this document.
The choice of system components is the responsibility of the buyer, and how they are used cannot be the liability of Limitorque. However, Limitorque’s sales team and application engineers are always available to assist you in making your decision.
This manual contains information that is correct to the best of Limitorque’s knowledge. It is intended to be a guide and should not be considered as a sole source of technical instruction, replacing good technical judgment, since all possible situations cannot be anticipated. If there is any doubt as to exact installation, configuration, and/or use, call Limitorque at (434) 528-4400. The latest revisions to this document are available at www.flowserve.com.
MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/11
Contents
1 Introduction 5
1.1 Purpose 5
1.2 How to Use this Manual 5
1.3 User Safety 5
1.4 User Knowledge 6
1.5 DDC-100 System Capabilities and Features 6
1.6 General Specifications 7
2 System Components 8
2.1 Introduction 8
2.2 Hardware 8
2.2.1 MX Actuator 9
2.2.2 DDC–100 Field Unit 9
2.2.3 Host Controller 10
2.2.4 Master Station II 11
2.2.5 Network Cable 12
2.3 Software 13
2.3.1 Modbus Protocol 13
2.3.2 Modbus Function Codes 14
2.3.3 Modbus Function Code 01 (Read Coil Status) 14
2.3.4 Modbus Function Code 02 (Read Input Status) 15
2.3.5 Modbus Function Code 03 (Read Holding Register) 17
2.3.6 Modbus Function Code 04 (Read Input Register) 21
2.3.8 Modbus Function Code 06 (Preset Single Register) 23
2.3.9 Modbus Function Code 08 (Diagnostics) 26
2.3.10 Modbus Function Code 15 (Force Multiple Coils) 27
2.3.11 Modbus Function Code 16 (Preset Multiple Registers) 28
3 Installation and Configuration 30
3.1 Site and Network Cable Preparation 30
3.1.1 Site Preparation 30
3.1.2 Network Cable Preparation 30
3.2 Installation Verification 38
3.2.1 Network Cabling Installation Verification 38
3.2.2 Field Unit Installation Verification 38
3.3 Field Unit Configuration 39
3.3.1 Configuring Field Unit Parameters 39
3.4 Configuration Confirmation 44
3.4.1 Checking Connections 44
3.4.2 View Settings 44
3.4.3 Checking the Normal Display 44
4 Associated Documents 46 5 Troubleshooting 48 6 How to Order Parts 50 Appendix – Wiring Diagram 52 Appendix – MX/DDC Register Definitions 56 Appendix – Typical DDC-100 Network Installation Assignments 62
flowserve.com
MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/11
Figures
Figure 1.1 – Typical DDC-100 system with or without a Master Station II 6 Figure 2.1 – MX-05 actuator 8 Figure 2.2 – DDC-100 field unit 9 Figure 2.3 – Typical direct-to-host arrangement 10 Figure 2.4 – Typical Master Station II (rear view) 11 Figure 2.5 – Redundant connection operation in redundant host loop topology 12 Figure 3.1 – Network connections 30 Figure 3.2 – Removing outer plastic jacket 31 Figure 3.3 – Separating cable parts 32 Figure 3.4 – Stripping conductors 32 Figure 3.5 – Applying heat shrink tubing 33 Figure 3.6 – Ring tongue connectors 33 Figure 3.7 – Connecting network cable to MX terminal block 34 Figure 3.8 – Redundant bi-directional loop topology 36 Figure 3.9 – Daisy chain topology 37 Figure 3.10 – Error Messages 44 Figure A.1 (1 of 2) – Typical MX/DDC-100 wiring diagram 52 Figure A.1 (2 of 2) – Typical MX/DDC-100 wiring diagram 53 Figure A.2 - MX Terminal block 54
Tables
Table 2.1 – Modbus function codes supported 14 Table 2.2 – DDC-100 coil assignments, Modbus 05 command usage for digital outputs 14 Table 2.3 – Status Bit Definitions 15 Table 2.3 – Status Bit Definitions (continued) 16 Table 2.4 – Register definitions 18 Table 2.4 – Register definitions (continued) 19 Table 2.4 – Register definitions (continued) 20 Table 2.5 – DDC-100 coil assignments, Modbus 05 command usage for digital outputs 22 Table 2.6 – Modbus 06 command and field unit holding register 40001 24 Table 2.7 – Diagnostic Codes Supported by the DDC-100 Field Unit 27 Table 3.3 – Network cable terminations 34 Table 3.4 – MX/DDC digital input configurations (only one selection per row is permitted) 42 Table 3.5 – MX/DDC digital inputs (cross-reference of various inputs) 42 Table 3.6 – Digital input voltages 43 Table 3.7 – MX/DDC digital outputs S1-2 and R1-8 43
1
MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/11
Introduction
1.1 Purpose
This manual explains how to install and operate the Flowserve Limitorque MX™/DDC-100 field unit and is to be used as an addendum to Bulletin FCD LMENIM2306, MX Electronic Actuator Installation and Operation Manual. Up to 250 actuators, each containing a DDC-100 field unit, may be connected by a single twisted-pair cable to form a DDC-100 network. This network permits the actuators to be operated by various control room devices such as a distributed control system (DCS), a programmable logic controller (PLC), or a personal computer (PC). The DDC-100 system communicates status and alarm data from each MX and valve.
1.2 How to Use this Manual
Each section provides the MX user with information on installing and operating the MX field unit.
Section 1 - Introduction
Details user safety and knowledge requirements, system capabilities, and features.
Section 2 - System Components
Focuses on the description of the DDC-100 system hardware and software components.
Section 3 - Installation and Configuration
Provides details for installing and configuring a field unit.
Section 4 - Associated Documents
Provides a list of documents on related subjects for additional MX and DDC-100 system information.
Section 5 - Troubleshooting
Section 6 - How to Order Parts
Appendix A - Wiring Diagram
Details wiring connections.
Appendix B - MX/DDC Register Definitions
Appendix C - Typicl DDC-100 Network Installation Assignments
1.3 User Safety
Safety notices in this manual detail precautions the user must take to reduce the risk of personal injury and damage to the equipment. The user must read and be familiar with these instructions before attempting installation, operation, or maintenance. Failure to observe these precautions could result in serious bodily injury, damage to the equipment,
warranty void, or operational difficulty. User must follow local and state safety regulations.
Safety notices are presented in this manual in three forms:
WARNING: c Refers to personal safety. Alerts the user to potential danger. Failure to follow warning notices could
result in personal injury or death.
CAUTION: a Directs the user’s attention to general precautions that, if not followed, could result in personal injury and/or equipment damage.
NOTE: Highlights information critical to the user’s understanding of the actuator’s installation and operation.
flowserve.com
MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/11
1
2
34
5
250
.
.
.
Host controller
Optional Master Station
Network RS-485
MX field units (up to 250)
1.4 User Knowledge
It is recommended that the user read this manual in its entirety before the DDC-100 equipped actuator is installed and operated.
The user needs to have a fundamental knowledge of electronics and microprocessor concepts. An understanding of valve actuators and digital control systems is beneficial to the field unit user.
1.5 DDC-100 System Capabilities and Features
Limitorque’s distributed digital control (DDC) valve control network supports up to 250 actuators over a single twisted-pair cable using Modbus™ protocol. MX actuators and other devices can be accessed from a control room for integration with a plant asset management (PAM) system, distributed control system (DCS), programmable logic controller (PLC), or personal computer (PC) based network. The DDC-100 system consists of a host system, controller, network, and field units. A typical DDC-100 system is shown in Figure 1.1.
Figure 1.1 – Typical DDC-100 system with or without a Master Station II
MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/11
1.6 General Specifications
Direct-to-Host Specifications:
Direct connection to host controller•
Communicates using the Modbus protocol and the RS-485 electrical standards•
Configurable bitmap•
High-level surge protection on network•
Network Specifications:
Redundant bi-directional loop or daisy chain topology•
Modbus protocol and the RS-485 electrical standards•
High speed—up to 19.2 kbaud communications•
MX Field Unit Specifications:
• OPEN,” “STOP,” and “CLOSE” commands
• ESD” and “MOVE–TO” position commands
Actuator status and alarm messages•
Six digital inputs and two analog inputs for user (see • Table 2.2, Register Definitions)
Two surge-protected and mutually isolated communication channels•
MX local control panel configuration•
Torque output (for reference only) and position feedback•
User’s analog input feedback•
Nine digital outputs maximum (three standard/six optional)•
Master Station II (Optional) Specifications:
Supports all Limitorque DDC-100 field units: MX, L120, LY•
Controls up to 250 MOVs•
User-friendly touch panel operator interface:•
Permits configuration and control of DDC-100 network•
Configures communication to host or DCS (Distribution Control System)•
Password protected•
Optional Hot Standby Configuration: Automatically assumes control on Primary Master Failure or on command • from the DCS or touch panel
Provides realtime status of field units through continuous cyclical polling•
Modbus RTU and TCP/IP:•
Addressable•
RS-232/485/422•
10/100 baseT•
Built-in Web server for ease of actuator and network diagnostics•
flowserve.com
Piece Description
1 Handwheel 2 Declutch Lever 3 Oil Fills (dotted arrow depicts fill on declutch side) 4 Controls Compartment (field unit location) 5 LCD Display 6 Control Knobs 7 Ground Lug 8 Thrust/Torque Base 9 Conduit Entries 10 Terminal Compartment 11 Motor 12 Nameplate
1
2
3
7
8
4
5
11
12
10
6
9
2
MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/11
System Components
2.1 Introduction
This section gives an overview of the components used in the DDC-100 system. The field unit is installed in each MX actuator. The network cable connects the field unit to the network via the actuator terminal block. The network cable is connected to a host controller or Master Station II.
2.2 Hardware
NOTE: Recommended storage procedures are detailed in Bulletin FCD LMENIM2314, MX Maintenance and Spare Parts Manual. Failure to comply with recommended procedures will void the warranty. For longer-term storage,
contact Flowserve for procedures and recommendations.
Figure 2.1 – MX-05 actuator
MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/11
2.2.1 MX Actuator
The MX is a multi-turn valve actuator designed for operation of ON-OFF and modulating valve applications. This actuator controls the opening and closing of valves. See Figure 2.1.
Features of the MX include:
Non-intrusive setup•
Separately sealed terminal chamber•
Absolute encoder for valve position sensing (no battery required) •
32-character graphical LCD display with 180° rotation •
Sophisticated electronic control, monitoring, and diagnostic capabilities with LimiGard™ technology •
2.2.2 DDC–100 Field Unit
The DDC-100 field unit is installed in the MX controls compartment. This unit permits the actuator to be controlled by a host controller or Master Station II via the DDC-100 network. The field unit includes two high-level, surge-protected, and isolated network communication channels, configurable digital I/O, and configuration via LCD screen. The following commands and information may be transmitted over the DDC-100 network:
• OPEN,” “STOP,” and “CLOSE” commands
• ESD” and “MOVE–TO” position commands
Actuator status and alarm messages•
Six digital inputs and two analog inputs for user (see • Table 2.2, Register Definitions)
Two surge-protected and mutually isolated communication channels•
MX local control panel configuration•
Torque output (for reference only) and position feedback•
User’s analog input feedback•
Nine digital outputs maximum (three standard/six optional)•
Figure 2.2 – DDC-100 field unit
flowserve.com
MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/11
DCS PC/PAM PLC
1 250
52
3 4
RS-485
2.2.3 Host Controller
In the DDC-100 system, the network can be connected directly to a host controller without an interposing Master Station II.
In this configuration, the host sends commands and messages to, and gathers responses from, the field units. The commands and messages are sent via RS-485 data signals. The gathered responses are stored in a data table in the host and are periodically updated by sequential polling of the field units. The host controls up to 250 field units. See Section 3.1.2.3, Network Cable Connection to Host System or Master Station II.
When a host controller is used to directly communicate with the field units, i.e., direct-to-host communications, it communicates using the Modbus protocol and the RS-485 electrical standard. This host controller can be one of the following:
Distributed control system (DCS)•
Programmable logic controller (PLC) •
Personal computer (PC)•
Plant Asset Management (PAM) system•
Figure 2.3 – Typical direct-to-host arrangement
10
MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-00 – 2/08
o
l
FUSES
FUSES
l
o
ETHERNET
DO NOT USE
SINGLE
--
+
24VDC
PROPER OPERATION
INSIDE OF UNIT FOR
INPUT ONLY
EXTERNAL 24VDC
MOVE JUMPERS ON
250 V
INPUT
POWER
~1.5A
100-240VAC
ON
OFF
FUSES 2 AMP
DCS
DATA *
GND
CHANNEL B
PRINTER / DEBUG
WITH 110-240VAC
OPTIONAL
DO NOT USE
HOT STANDBY
GND
DATA *
DATA
DCS
PRINTER / DEBUG
ON
OFF
~1.5A
INPUT
100-240VAC
250 V
POWER
2 AMP
FUSES
--
+
24VDC
PROPER OPERATION
INSIDE OF UNIT FOR
INPUT ONLY
EXTERNAL 24VDC
MOVE JUMPERS ON
WITH 110-240VAC
CHANNEL A
DATA
NO SERVICEABLE PARTS INSIDE
1
2
3
5
4
6
9
7
8
10
2.2.4 Master Station II
A Master Station II may be used in the DDC-100 system. Master Station II’s are normally located in the control room, and serve as the interface between the field units and the host controller. The following functions are provided:
Continuous polling of actuator network•
Message routing to/from field units •
Data concentration •
Data logging •
In this configuration, the Master Station II receives commands from a host controller. The Master Station II communi­cates with the host controller using the Modbus Protocol and the RS-232 or RS-485 electrical standard. See Bulletin FCD LMENIM5001, DDC-100 Master Station II Installation and Operation Manual for details.
The Master Station II sends commands and messages to, and gathers responses from, the field units. The commands and messages are sent via RS-485 data signals. The gathered responses are stored in a poll table in the Master Station II and are periodically updated by sequential polling of the field units. The Master Station II controls up to 250 field units. See Section 3.1.2.3, Network Cable Connection to Host System or Master Station II.
Figure 2.4 – Typical Master Station II (rear view)
1. Ethernet ports
2. Printer/Debug port
3. DCS port
4. Auxiliary 24 VDC power connection
5. Main power switch and connector for 120-240 VAC
6. Electrostatic ground
7. Hot Standby unit main power switch and connector for 120-240 VAC
8. Hot Standby auxiliary 24 VDC power connection
9. Hot Standby DCS Port
10. Hot Standby Printer/Debug Port
11
flowserve.com
MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/11
Signal initiated from host fails to reach field unit which is located after fault...
Instead, signal routes to field unit using other side of the loop cable and completes connection.
2.2.5 Network Cable
The network consists of a shielded, twisted-pair cable that connects all field units and the host/Master Station II. The cable is normally connected in a loop fashion so that any single break or short will not disable communication.
Figure 2.5 – Redundant connection operation in redundant host loop topology
12
The network cable connects the field units to the host controller or Master Station II. Belden 3074F, 3105A, or 9841 shielded, twisted-pair cable should be used. The use of other cables may result in a reduction of internodal distances or increased error rate, and is the user’s responsibility.
Belden 3074F Specifications
Key Specifications
Total cable length between repeaters or nodes with repeaters, up to 19.2 kbps: 5000 ft (1.52 km) For loop • mode, this is the total length between operating field units. If a field unit loses power, then the relays internal to the field unit connect the A1 Channel to the A2 Channel, which effectively doubles the length of the cable (assuming a single field unit fails). To ensure operation within specifications in the event of power failure to field units, this consideration must be added. Example: To ensure operation within specification when any two consecutive field units lose power, the maximum length of cable, up to 19.2 kbps, should not exceed 5000 ft (1.52 km) per every four field units. See Section 3.1.2.3, Network Cable Connection to Host Controller or Master Station II.
Resistance/1000 ft = 18 AWG (7 x 26) 6.92 ohms each conductor (13.84 ohms for the pair)•
Capacitance/ft = 14 pF (conductor-to-conductor)•
Capacitance/ft = 14 pF (conductor-to-shield)•
MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/11
Belden 3105A Specifications
Total cable length between repeaters or nodes with repeaters, up to 19.2 kbps: 4500 ft (1.37 km) For loop • mode, this is the total length between operating field units. If a field unit loses power, then the relays internal to the field unit connect the A1 Channel to the A2 Channel, which effectively doubles the length of the cable (assuming a single field unit fails). To ensure operation within specifications in the event of power failure to field units, this consideration must be added. Example: To ensure operation within specification when any two consecutive field units lose power, the maximum length of cable, up to 19.2 kbps, should not exceed 4500 ft (1.37 km) per every four field units. See Section 3.1.2.3, Network Cable Connection to Host Controller or
Master Station II.
Key Specifications
Resistance/1000 ft = 22 AWG (7 x 30) 14.7 ohms each conductor (29.4 ohms for the pair)•
Capacitance/ft = 11.0 pF (conductor-to-conductor)•
Capacitance/ft = 20.0 pF (conductor-to-shield)•
Belden 9841 Specifications
Total cable length between repeaters or nodes with repeaters: up to 19.2 kbps: 3500 ft (1 km) For loop mode, • this is the total length between operating field units. If a field unit loses power, then the relays internal to the field unit connect the A1 Channel to the A2 Channel, which effectively doubles the length of the cable (assuming a single field unit fails). To ensure operation within specifications in the event of power failure to field units, this consideration must be added. Example: To ensure operation within specification when any two consecutive field units lose power, the maximum length of cable, up to 19.2 kbps, should not exceed 3500 ft (1 km) per every four field units. See Section 3.1.2.3, Network Cable Connection to Host Controller or Master Station II.
Key Specifications
Resistance/1000 ft = 24 AWG (7 x 32) 24 ohms each conductor (48 ohms for the pair)•
Capacitance/ft = 12.8 pF (conductor-to-conductor)•
Capacitance/ft = 23 pF (conductor-to-shield)•
2.3 Software
2.3.1 Modbus Protocol
The Modbus protocol was developed by AEG Modicon® for communicating to various networked devices. The relationship between these devices and a central controller is called a master-slave relationship in which the master (host device) initiates all communication. The slave devices (DDC-100 field units in the actuators) respond to the queries from the master.
Modbus only permits one device to communicate at any given time (simultaneous communication is prohibited) to ensure process control integrity.
flowserve.com
13
MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/11
2.3.2 Modbus Function Codes
The controlling device (master) must conform to the Modbus protocol as defined in the Modbus-IDA Modbus Application Protocol Specification V1.1a (http://www.Modbus-IDA.org) and support Modbus function codes 01 through 06, 08, 15, and 16. These function codes are a subset of the complete protocol and are defined in Table 2.1.
Table 2.1 – Modbus function codes supported
Extended Function Bit/Register Addressing Code Name Addressing Range
01 Read Coil Status Bit 0,000 - 9,999 02 Read Discrete Inputs Bit 10.000 - 19,999 03 Read Holding Register Register 40,000 - 49,999 04 Read Input Register Register 30,000 - 39,999 05 Force Single Coil Bit 0,000 - 9,999 06 Preset Single Register Register 40,000 - 49,999 08 Diagnostics N/A N/A 15 Force Multiple Coils Bit 0,000 - 9,999 16 Preset Multiple Registers Register 40,000 - 49,999
See Table 2.2 for a complete listing of MX/DDC holding registers.
2.3.3 Modbus Function Code 01 (Read Coil Status)
This function code is used to read the coil status in the DDC-100 Field Unit. There are nine coils available to be read on DDC-100 Field Units as shown in Table 2.2. For the MX/DDC, Coil 1 indicates CLOSE contactor and is interlocked with Coil 2, Coil 2 indicates OPEN contactor and is interlocked with Coil 1. When the I/O Module is used in non-MOV (motor-operated valve) mode, relays 1 through 6 or coils 3 through 8 are available for user configuration.
Table 2.2 – DDC-100 coil assignments, Modbus 05 command usage for digital outputs
Coil Number Bit Number Function
1 00 Close/Stop 2 01 Open/Stop 3 02 S1 or R1 (Opt) Latched 4 03 S2 or R2 (Opt) Latched 5 04 R3 (Opt) Latched 6 05 R4 (Opt) Latched 7 06 R5 (Opt) Latched 8 07 R6 (Opt) Latched 9 08 R7 (Opt) Latched 10 09 R8 (Opt) Latched
The normal response to the (05) command is an echo of the command.
Example
Poll field unit number 3 for 8 coils starting at coil 1.
Query: 0301000000083C2E
14
Response: 03010118503A
MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/11
Message Breakdown
Query Response
03 Slave (Field Unit) Address 03 Slave (Field Unit) Address
01 Function 01 Function
00 Starting Address Hi 01 Byte Count
00 Starting Address Lo 18
00 No. of Points Hi 503A Error Check (CRC)
08 No. of Points Lo
3C2E Error Check (CRC)
Note 1: 18h equals 00011000 or coils 4 and 5 are ON.
1
Data (Coils 8 - 1)
2.3.4 Modbus Function Code 02 (Read Input Status)
This function code is used to read the discrete input status bits in the DDC-100 Field Unit. The use of this function code will provide the user with the input status bits that are used to develop holding registers 9 through 13. The status bit inputs are contained in locations 10129-10208 for each DDC-100 Field Unit and are defined in Table 2.3.
Table 2.3 – Status Bit Definitions
Bit Number
129 128 Opened
130 129 Closed
131 130 Stopped in mid-travel
132 131 Opening
133 132 Closing
134 133 Valve jammed
135 134 Not in remote
136 135 Combined fault
137 136 Over-temperature fault
138 137 Actuator failing to de-energize
139 138 Channel A fault
140 139 Channel B fault
141 140 Open torque switch fault
142 141 Close torque switch fault
143 142 Valve operated manually fault
144 143 Phase error
145 144 Open inhibit active
146 145 Close inhibit active
147 146 Not used
148 147 Not used
149 148 One or more phases is missing
150 149 Reverse phase sequence is occurring
151 150 ESD conflict
152 151 Inhibit conflict
153 152 Use in local/stop (input must be set for CSE and enabled)
154 153 Not used
155 154 Network emergency shutdown (ESD) is active
156 155 Local emergency shutdown is active
Modbus
Bit
Address
MX/DDC
15
flowserve.com
16
MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/11
Table 2.3 – Status Bit Definitions (continued)
Bit Number
157 156 Field unit microprocessor has reset since the last poll
158 157 MX in stop move
159 158 Opening in local mode
160 159 Closing in local mode
161 160 Close contactor (interlocked)
162 161 Open contactor (interlocked)
163 162 S1 or R1 (opt)
164 163 S2 or R2 (opt)
165 164 R3 (opt)
166 165 R4 (opt)
167 166 R5 (opt)
168 167 R6 (opt)
169 168 R7 (opt)
170 169 Network relay
171 170 R8 (opt)
172 171 Not used
173-176 172-175 Mov series (0=1, A=9)
177 176 Remote switch
178 177 Thermal overload
179 178 Open torque switch
180 179 Open limit switch
181 180 Close torque switch
182 181 Close limit switch
183 182 Not used
184 183 Not used
185 184 User Input 0
186 185 User Input 1
187 186 User Input 2
188 187 Remote stop input
189 188 Remote open input
190 189 Remote close input
191 190 Not used
192 191 Not used
193 192 Analog board 1 present
194 193 Analog board 2 present
195 194 Analog Input #1 lost
196 195 Analog Input #2 lost
197 196 Network Channels A/B timed out
198 197 Relay board R5-R8 present
199 198 DDC board present
200 199 Relay board R1-R4 and RM present
201 200 FF board present
202 201 PB PA board present
203 202 CLE assigned for input 2
204 203 DNET board present
Modbus
Bit
Address
MX/DDC
MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/11
Table 2.3 – Status Bit Definitions (continued)
Bit Number
205 204 Lost Phase Input
206 205 Phase Reverse Input
207 206 Not used
208 207 PB DP board present
Example
Poll field unit number 22 for 16 inputs starting at input 129 with the actuator opening.
Query: 1602008000107B09
Response: 1602020108CDED
Message Breakdown
Query Response
16 Slave (Field Unit) Address 16 Slave (Field Unit) Address
02 Function 02 Function
00 Starting Address Hi 02 Byte Count
80 Starting Address Lo 01
00 No. of Points Hi 08
10 No. of Points Lo CDED Error Check (CRC)
7B09 Error Check (CRC)
Note 1: 01h equals 0000 0001 (actuator open input bit is ON).
Modbus
Bit
Address
MX/DDC
1
Data (Inputs 10136 - 10129)
2
Data (Inputs 10144 - 10137)
Note 2: 08h equals 0000 1000 (actuator Channel B Fail bit is ON).
2.3.5 Modbus Function Code 03 (Read Holding Register)
This function code is used to read the binary contents of holding registers in the DDC-100 Field Unit. This function code is typically used during the network polling cycle. A network poll should consist of field unit registers 9 (Status) and 10 (Fault) as a minimum. Holding register 8 should also be polled when the actuator is configured for the analog feedback option or position control. See Table 2.4 for a complete listing of the holding registers.
17
flowserve.com
MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/11
Table 2.4 – Register definitions
Register # Description Meaning
1 Command Registers 1 and 2 are write-only registers used for Modbus Function Code 06 2 Argument Registers 1 and 2 are write-only registers used for Modbus Function Code 06 3 Analog Output 1 Analog Output 1 Value (Default 0-100) 4 Analog Output 2 Analog Output 2 Value (Default 0-100) 5 Analog Input Main Power (Volts) 6 Analog Input Analog Input 1 (Default 0-100) 7 Analog Input Analog Input 2 (Default 0-100) 8 Position Valve Position, Scaled Value (Default 0-100) 9 Status Register 16 Bits of field unit status: Bit 0 Opened Bit 1 Closed Bit 2 Stopped in Mid-Travel Bit 3 Opening Bit 4 Closing Bit 5 Valve jammed Bit 6 Not in Remote Bit 7 Combined fault
2
3
Bit 8 Over temperature fault Bit 9 Future Implementation Bit 10 Network Channel A fault Bit 11 Network Channel B fault Bit 12 Open torque switch fault Bit 13 Close torque switch fault Bit 14 Valve-operated manually fault
Bit 15 Phase error
NOTE 1: Default value is scaled 0-100 of span. Changes made to “Analog Scale” affect analog registers (3, 4, 6, 7, 8)
and “move-to” commands. (0-100, 0-255, 0-4095)
1
1
1
User 4-20 mA / 0-20 mA Input
1
User 4-20 mA / 0-20 mA Input
4
(Terminals 5 and 4)
4
(Terminals 13 and 14)
1
18
NOTE 2: MX/DDC actuators shipped after 2nd QTR, 1999, have the following definition of Register 9 Bit 6. When this
bit has a value of 1 or true, the actuator is in LOCAL or STOP (unavailable for network control). The actuator selector switch in REMOTE (available for network control) is indicated by Register 12 Bit 0 having a value of 1 or true.
IMPORTANT: Verify host program when installing an MX/DDC actuator shipped after 2nd QTR, 1999, on a network commissioned before 2nd QTR, 1999, for proper indication of selector switch values. Failure to verify proper selector switch indication at the host may cause unsafe conditions at the facility.
MX/DDC actuators shipped prior to 2nd QTR, 1999, have the following definition for Register 9 Bit 6. When this bit has a value of 1 or true, the actuator selector switch is in LOCAL mode. This bit does not indicate STOP or REMOTE. The actuator selector switch in REMOTE (available for network control) is indicated by Register 12 Bit 0 having a value of 1 or true. Register 9 Bit 6 value 0 (zero) or false AND Register 12 Bit 0 value 0 (zero) or false indicates selector switch is in the STOP position.
NOTE 3: Combined Fault bit is high when Bit 5 or 8 or 9 or 15 or (Bits 10 and 11) is high.
NOTE 4: Channel A is physical connection A1. Channel B is physical connection A2. (See Appendix A.)
MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/11
Table 2.4 – Register definitions (continued)
Register # Description Meaning
10 Fault Register 16 Bits of field status Bit 0 Open inhibit active Bit 1 Close inhibit active Bit 2 Not Used Bit 3 Not Used Bit 4 One or more phases are missing Bit 5 Reverse phase sequence is occurring Bit 6 ESD conflict Bit 7 Inhibit conflict Bit 8 CSE in local/stop (input must be set for CSE and enabled) Bit 9 Not Used Bit 10 Network emergency shutdown is active Bit 11 Local PB emergency shutdown is active Bit 12 Field unit microprocessor has reset since the last poll Bit 13 MX in stop mode Bit 14 Opening in local mode Bit 15 Closing in local mode 11 Digital Outputs Value of 16 Digital Outputs Bit 0 Close contactor (Interlocked) Bit 1 Open contactor (Interlocked) Bit 2 S1 or R1 (Opt) Bit 3 S2 or R2 (Opt) Bit 4 R3 (Opt) Bit 5 R4 (Opt) Bit 6 R5 (Opt) Bit 7 R6 (Opt) Bit 8 R7 (Opt) Bit 9 Network Relay Bit 10 R8 (Opt) Bit 11 Not Used BIT 12-15 MOV Series (0 = 1, A = 9) 12 Digital Inputs 1 Value of 16 Digital Inputs Bit 0 Remote Switch Bit 1 Thermal Overload Bit 2 Open Torque Switch Bit 3 Open Limit Switch Bit 4 Close Torque Switch Bit 5 Close Limit Switch Bit 6 Not Used Bit 7 Not Used Bit 8 User Input 0 (Default=ESD), Terminal 30 Bit 9 User Input 1 (Default=Open Inhibit), Terminal 34 Bit 10 User Input 2 (Default=Close Inhibit), Terminal 35 Bit 11 Remote Stop Input, Terminal 26 Bit 12 Remote Open Input, Terminal 25 Bit 13 Remote Close Input, Terminal 27 Bits 14-15 Not Used
flowserve.com
19
MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/11
Table 2.4 – Register definitions (continued)
Register # Description Meaning
13 Digital Inputs 2 Value of 16 Digital Inputs Bit 0 Analog board 1 present Bit 1 Analog board 2 present Bit 2 Analog Input 1 lost Bit 3 Analog Input 2 lost Bit 4 Network Channels A/B timed out Bit 5 Relay board R5-R8 present Bit 6 DDC board present Bit 7 Relay board R1-R4 and RM present Bit 8 Foundation Fieldbus board present Bit 9 Profibus PA board present Bit 10 CSE chosen for input 2 Bit 11 DeviceNet board present Bit 12 Phase lost Bit 13 Phase reverse Bit 14 Not Used Bit 15 Profibus DP board present 14 Timers and Analog Channels Internal compartment temperature 15 User Faults Bits 0-15 Not Used 16 Current State Bits 0-15 Not Used 17 Field Unit Holding Register Special Applications Only 18 Field Unit Holding Register Special Applications Only 19 Field Unit Holding Register Special Applications Only 20 Field Unit Holding Register Special Applications Only 21 Field Unit Holding Register Special Applications Only 22 Field Unit Holding Register Special Applications Only 23 Field Unit Holding Register Special Applications Only 24-44 Reserved Special Applications Only 45-47 Not Named Special Applications Only 48 TP_START_POSITION Special Applications Only 49 TP_STOP_POSITION Special Applications Only 50 TP_SAMPLE Special Applications Only 51 TP_MID_T_HIGH Special Torque Applications Only 52 TP_MID_T_POS Special Applications Only 53 TP_MID_T_AV_VAL Special Torque Applications Only 54 TP_STOP_VAL Special Applications Only 55 TP_BEFORE_ MID_T_HIGH Special Torque Applications Only 56 TP_AFTER_ MID_T_HIGH Special Torque Applications Only
Note 1: Range is +90°C to -55°C. High byte 00 indicates positive (+) and 01 indicates negative (-). Low byte indicates temperature
value. Example: 0x0019 = +25°C
0x011E = -30°C
1
20
Example
Poll field unit number 125 for 3 registers starting at register 8 with the actuator stopped between the limits and in local mode.
Query: 7D0300070003BFF6
Response: 7D0306003D084400003E07
Loading...
+ 46 hidden pages