This document is meant for use with MX Installation and Operation Manual for MX-05 through MX-40. Information
in this document is also applicable to MX-85 through MX-150. No part of this book shall be reproduced, stored in a
retrieval system, or transmitted by any means, electronic, mechanical, photocopying, recording, or otherwise without
the written permission of Limitorque. While every precaution has been taken in the preparation of this book, the
publisher assumes no responsibility for errors or omissions. Neither is any liability assumed for damages resulting
from the use of the information contained herein.
This document is the proprietary information of Limitorque, furnished for customer use ONLY. No other uses are
authorized without written permission from Limitorque.
Limitorque reserves the right to make changes, without notice, to this document and the product it describes.
Limitorque shall not be liable for technical or editorial errors or omissions made herein; nor for incidental and
consequential damages resulting from the furnishing, performance or use of this document.
The choice of system components is the responsibility of the buyer, and how they are used cannot be the liability of
Limitorque. However, Limitorque’s sales team and application engineers are always available to assist you in making
your decision.
This manual contains information that is correct to the best of Limitorque’s knowledge. It is intended to be a guide
and should not be considered as a sole source of technical instruction, replacing good technical judgment, since all
possible situations cannot be anticipated. If there is any doubt as to exact installation, configuration, and/or use, call
Limitorque at (434) 528-4400. The latest revisions to this document are available at www.flowserve.com.
2
MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/11
Contents
1 Introduction 5
1.1 Purpose 5
1.2 How to Use this Manual 5
1.3 User Safety 5
1.4 User Knowledge 6
1.5 DDC-100 System Capabilities and Features 6
1.6 General Specifications 7
2 System Components 8
2.1 Introduction 8
2.2 Hardware 8
2.2.1 MX Actuator 9
2.2.2 DDC–100 Field Unit 9
2.2.3 Host Controller 10
2.2.4 Master Station II 11
2.2.5 Network Cable 12
2.3 Software 13
2.3.1 Modbus Protocol 13
2.3.2 Modbus Function Codes 14
2.3.3 Modbus Function Code 01 (Read Coil Status) 14
2.3.4 Modbus Function Code 02 (Read Input Status) 15
2.3.5 Modbus Function Code 03 (Read Holding Register) 17
2.3.6 Modbus Function Code 04 (Read Input Register) 21
2.3.8 Modbus Function Code 06 (Preset Single Register) 23
2.3.9 Modbus Function Code 08 (Diagnostics) 26
2.3.10 Modbus Function Code 15 (Force Multiple Coils) 27
2.3.11 Modbus Function Code 16 (Preset Multiple Registers) 28
3 Installation and Configuration 30
3.1 Site and Network Cable Preparation 30
3.1.1 Site Preparation 30
3.1.2 Network Cable Preparation 30
3.2 Installation Verification 38
3.2.1 Network Cabling Installation Verification 38
3.2.2 Field Unit Installation Verification 38
3.3 Field Unit Configuration 39
3.3.1 Configuring Field Unit Parameters 39
3.4 Configuration Confirmation 44
3.4.1 Checking Connections 44
3.4.2 View Settings 44
3.4.3 Checking the Normal Display 44
4 Associated Documents 46
5 Troubleshooting 48
6 How to Order Parts 50
Appendix – Wiring Diagram 52
Appendix – MX/DDC Register Definitions 56
Appendix – Typical DDC-100 Network Installation Assignments 62
3
flowserve.com
MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/11
Figures
Figure 1.1 – Typical DDC-100 system with or without a Master Station II 6
Figure 2.1 – MX-05 actuator 8
Figure 2.2 – DDC-100 field unit 9
Figure 2.3 – Typical direct-to-host arrangement 10
Figure 2.4 – Typical Master Station II (rear view) 11
Figure 2.5 – Redundant connection operation in redundant host loop topology 12
Figure 3.1 – Network connections 30
Figure 3.2 – Removing outer plastic jacket 31
Figure 3.3 – Separating cable parts 32
Figure 3.4 – Stripping conductors 32
Figure 3.5 – Applying heat shrink tubing 33
Figure 3.6 – Ring tongue connectors 33
Figure 3.7 – Connecting network cable to MX terminal block 34
Figure 3.8 – Redundant bi-directional loop topology 36
Figure 3.9 – Daisy chain topology 37
Figure 3.10 – Error Messages 44
Figure A.1 (1 of 2) – Typical MX/DDC-100 wiring diagram 52
Figure A.1 (2 of 2) – Typical MX/DDC-100 wiring diagram 53
Figure A.2 - MX Terminal block 54
Tables
Table 2.1 – Modbus function codes supported 14
Table 2.2 – DDC-100 coil assignments, Modbus 05 command usage for digital outputs 14
Table 2.3 – Status Bit Definitions 15
Table 2.3 – Status Bit Definitions (continued) 16
Table 2.4 – Register definitions 18
Table 2.4 – Register definitions (continued) 19
Table 2.4 – Register definitions (continued) 20
Table 2.5 – DDC-100 coil assignments, Modbus 05 command usage for digital outputs 22
Table 2.6 – Modbus 06 command and field unit holding register 40001 24
Table 2.7 – Diagnostic Codes Supported by the DDC-100 Field Unit 27
Table 3.3 – Network cable terminations 34
Table 3.4 – MX/DDC digital input configurations (only one selection per row is permitted) 42
Table 3.5 – MX/DDC digital inputs (cross-reference of various inputs) 42
Table 3.6 – Digital input voltages 43
Table 3.7 – MX/DDC digital outputs S1-2 and R1-8 43
4
1
MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/11
Introduction
1.1 Purpose
This manual explains how to install and operate the Flowserve Limitorque MX™/DDC-100 field unit and is to be used
as an addendum to Bulletin FCD LMENIM2306, MX Electronic Actuator Installation and Operation Manual. Up to 250
actuators, each containing a DDC-100 field unit, may be connected by a single twisted-pair cable to form a DDC-100
network. This network permits the actuators to be operated by various control room devices such as a distributed
control system (DCS), a programmable logic controller (PLC), or a personal computer (PC). The DDC-100 system
communicates status and alarm data from each MX and valve.
1.2 How to Use this Manual
Each section provides the MX user with information on installing and operating the MX field unit.
Section 1 - Introduction
Details user safety and knowledge requirements, system capabilities, and features.
Section 2 - System Components
Focuses on the description of the DDC-100 system hardware and software components.
Section 3 - Installation and Configuration
Provides details for installing and configuring a field unit.
Section 4 - Associated Documents
Provides a list of documents on related subjects for additional MX and DDC-100 system information.
Section 5 - Troubleshooting
Section 6 - How to Order Parts
Appendix A - Wiring Diagram
Details wiring connections.
Appendix B - MX/DDC Register Definitions
Appendix C - Typicl DDC-100 Network Installation Assignments
1.3 User Safety
Safety notices in this manual detail precautions the user must take to reduce the risk of personal injury and damage
to the equipment. The user must read and be familiar with these instructions before attempting installation, operation,
or maintenance. Failure to observe these precautions could result in serious bodily injury, damage to the equipment,
warranty void, or operational difficulty. User must follow local and state safety regulations.
Safety notices are presented in this manual in three forms:
WARNING: c Refers to personal safety. Alerts the user to potential danger. Failure to follow warning notices could
result in personal injury or death.
CAUTION:a Directs the user’s attention to general precautions that, if not followed, could result in personal injury
and/or equipment damage.
NOTE: Highlights information critical to the user’s understanding of the actuator’s installation and operation.
flowserve.com
5
MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/11
1
2
34
5
250
.
.
.
Host controller
Optional
Master
Station
Network
RS-485
MX field
units
(up to 250)
1.4 User Knowledge
It is recommended that the user read this manual in its entirety before the DDC-100 equipped actuator is installed and
operated.
The user needs to have a fundamental knowledge of electronics and microprocessor concepts. An understanding of
valve actuators and digital control systems is beneficial to the field unit user.
1.5 DDC-100 System Capabilities and Features
Limitorque’s distributed digital control (DDC) valve control network supports up to 250 actuators over a single
twisted-pair cable using Modbus™ protocol. MX actuators and other devices can be accessed from a control room
for integration with a plant asset management (PAM) system, distributed control system (DCS), programmable
logic controller (PLC), or personal computer (PC) based network. The DDC-100 system consists of a host system,
controller, network, and field units. A typical DDC-100 system is shown in Figure 1.1.
Figure 1.1 – Typical DDC-100 system with or without a Master Station II
6
MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/11
1.6 General Specifications
Direct-to-Host Specifications:
Direct connection to host controller•
Communicates using the Modbus protocol and the RS-485 electrical standards•
Configurable bitmap•
High-level surge protection on network•
Network Specifications:
Redundant bi-directional loop or daisy chain topology•
Modbus protocol and the RS-485 electrical standards•
High speed—up to 19.2 kbaud communications•
MX Field Unit Specifications:
“• OPEN,” “STOP,” and “CLOSE” commands
“• ESD” and “MOVE–TO” position commands
Actuator status and alarm messages•
Six digital inputs and two analog inputs for user (see •Table 2.2, Register Definitions)
Two surge-protected and mutually isolated communication channels•
MX local control panel configuration•
Torque output (for reference only) and position feedback•
User’s analog input feedback•
Nine digital outputs maximum (three standard/six optional)•
Master Station II (Optional) Specifications:
Supports all Limitorque DDC-100 field units: MX, L120, LY•
Controls up to 250 MOVs•
User-friendly touch panel operator interface:•
Permits configuration and control of DDC-100 network•
Configures communication to host or DCS (Distribution Control System)•
Password protected•
Optional Hot Standby Configuration: Automatically assumes control on Primary Master Failure or on command •
from the DCS or touch panel
Provides realtime status of field units through continuous cyclical polling•
Modbus RTU and TCP/IP:•
Addressable•
RS-232/485/422•
10/100 baseT•
Built-in Web server for ease of actuator and network diagnostics•
7
flowserve.com
PieceDescription
1Handwheel
2Declutch Lever
3 Oil Fills (dotted arrow depicts fill on declutch side)
4Controls Compartment (field unit location)
5 LCD Display
6Control Knobs
7 Ground Lug
8 Thrust/Torque Base
9Conduit Entries
10Terminal Compartment
11 Motor
12 Nameplate
1
2
3
7
8
4
5
11
12
10
6
9
2
MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/11
System Components
2.1 Introduction
This section gives an overview of the components used in the DDC-100 system. The field unit is installed in each MX
actuator. The network cable connects the field unit to the network via the actuator terminal block. The network cable is
connected to a host controller or Master Station II.
2.2 Hardware
NOTE: Recommended storage procedures are detailed in Bulletin FCD LMENIM2314, MX Maintenance and Spare
Parts Manual. Failure to comply with recommended procedures will void the warranty. For longer-term storage,
contact Flowserve for procedures and recommendations.
Figure 2.1 – MX-05 actuator
8
MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/11
2.2.1 MX Actuator
The MX is a multi-turn valve actuator designed for operation of ON-OFF and modulating valve applications. This
actuator controls the opening and closing of valves. See Figure 2.1.
Features of the MX include:
Non-intrusive setup•
Separately sealed terminal chamber•
Absolute encoder for valve position sensing (no battery required) •
32-character graphical LCD display with 180° rotation •
Sophisticated electronic control, monitoring, and diagnostic capabilities with LimiGard™ technology •
2.2.2 DDC–100 Field Unit
The DDC-100 field unit is installed in the MX controls compartment. This unit permits the actuator to be controlled by
a host controller or Master Station II via the DDC-100 network. The field unit includes two high-level, surge-protected,
and isolated network communication channels, configurable digital I/O, and configuration via LCD screen. The
following commands and information may be transmitted over the DDC-100 network:
“• OPEN,” “STOP,” and “CLOSE” commands
“• ESD” and “MOVE–TO” position commands
Actuator status and alarm messages•
Six digital inputs and two analog inputs for user (see •Table 2.2, Register Definitions)
Two surge-protected and mutually isolated communication channels•
MX local control panel configuration•
Torque output (for reference only) and position feedback•
User’s analog input feedback•
Nine digital outputs maximum (three standard/six optional)•
Figure 2.2 – DDC-100 field unit
flowserve.com
9
MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/11
DCSPC/PAMPLC
1250
52
34
RS-485
2.2.3 Host Controller
In the DDC-100 system, the network can be connected directly to a host controller without an interposing Master
Station II.
In this configuration, the host sends commands and messages to, and gathers responses from, the field units. The
commands and messages are sent via RS-485 data signals. The gathered responses are stored in a data table in the
host and are periodically updated by sequential polling of the field units. The host controls up to 250 field units. See Section 3.1.2.3, Network Cable Connection to Host System or Master Station II.
When a host controller is used to directly communicate with the field units, i.e., direct-to-host communications, it
communicates using the Modbus protocol and the RS-485 electrical standard. This host controller can be one of the
following:
Distributed control system (DCS)•
Programmable logic controller (PLC) •
Personal computer (PC)•
Plant Asset Management (PAM) system•
Figure 2.3 – Typical direct-to-host arrangement
10
MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-00 – 2/08
o
l
FUSES
FUSES
l
o
ETHERNET
DO NOT USE
SINGLE
--
+
24VDC
PROPER OPERATION
INSIDE OF UNIT FOR
INPUT ONLY
EXTERNAL 24VDC
MOVE JUMPERS ON
250 V
INPUT
POWER
~1.5A
100-240VAC
ON
OFF
FUSES
2 AMP
DCS
DATA *
GND
CHANNEL B
PRINTER / DEBUG
WITH 110-240VAC
OPTIONAL
DO NOT USE
HOT STANDBY
GND
DATA *
DATA
DCS
PRINTER / DEBUG
ON
OFF
~1.5A
INPUT
100-240VAC
250 V
POWER
2 AMP
FUSES
--
+
24VDC
PROPER OPERATION
INSIDE OF UNIT FOR
INPUT ONLY
EXTERNAL 24VDC
MOVE JUMPERS ON
WITH 110-240VAC
CHANNEL A
DATA
NO SERVICEABLE PARTS INSIDE
1
2
3
5
4
6
9
7
8
10
2.2.4 Master Station II
A Master Station II may be used in the DDC-100 system. Master Station II’s are normally located in the control room,
and serve as the interface between the field units and the host controller. The following functions are provided:
Continuous polling of actuator network•
Message routing to/from field units •
Data concentration •
Data logging •
In this configuration, the Master Station II receives commands from a host controller. The Master Station II communicates with the host controller using the Modbus Protocol and the RS-232 or RS-485 electrical standard. See Bulletin FCD LMENIM5001, DDC-100 Master Station II Installation and Operation Manual for details.
The Master Station II sends commands and messages to, and gathers responses from, the field units. The
commands and messages are sent via RS-485 data signals. The gathered responses are stored in a poll table in the
Master Station II and are periodically updated by sequential polling of the field units. The Master Station II controls up
to 250 field units. See Section 3.1.2.3, Network Cable Connection to Host System or Master Station II.
Figure 2.4 – Typical Master Station II (rear view)
1. Ethernet ports
2. Printer/Debug port
3. DCS port
4. Auxiliary 24 VDC power connection
5. Main power switch and connector for 120-240 VAC
6. Electrostatic ground
7. Hot Standby unit main power switch and connector for 120-240 VAC
8. Hot Standby auxiliary 24 VDC power connection
9. Hot Standby DCS Port
10. Hot Standby Printer/Debug Port
11
flowserve.com
MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/11
Signal initiated from host fails to reach
field unit which is located after fault...
Instead, signal routes to field unit using
other side of the loop cable and
completes connection.
2.2.5 Network Cable
The network consists of a shielded, twisted-pair cable that connects all field units and the host/Master Station II. The
cable is normally connected in a loop fashion so that any single break or short will not disable communication.
The network cable connects the field units to the host controller or Master Station II. Belden 3074F, 3105A, or 9841
shielded, twisted-pair cable should be used. The use of other cables may result in a reduction of internodal distances
or increased error rate, and is the user’s responsibility.
Belden 3074F Specifications
Key Specifications
Total cable length between repeaters or nodes with repeaters, up to 19.2 kbps: 5000 ft (1.52 km) For loop •
mode, this is the total length between operating field units. If a field unit loses power, then the relays internal
to the field unit connect the A1 Channel to the A2 Channel, which effectively doubles the length of the cable
(assuming a single field unit fails). To ensure operation within specifications in the event of power failure to
field units, this consideration must be added. Example: To ensure operation within specification when any two
consecutive field units lose power, the maximum length of cable, up to 19.2 kbps, should not exceed 5000 ft
(1.52 km) per every four field units. See Section 3.1.2.3, Network Cable Connection to Host Controller or Master Station II.
Resistance/1000 ft = 18 AWG (7 x 26) 6.92 ohms each conductor (13.84 ohms for the pair)•
Capacitance/ft = 14 pF (conductor-to-conductor)•
Capacitance/ft = 14 pF (conductor-to-shield)•
MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/11
Belden 3105A Specifications
Total cable length between repeaters or nodes with repeaters, up to 19.2 kbps: 4500 ft (1.37 km) For loop •
mode, this is the total length between operating field units. If a field unit loses power, then the relays internal
to the field unit connect the A1 Channel to the A2 Channel, which effectively doubles the length of the cable
(assuming a single field unit fails). To ensure operation within specifications in the event of power failure to
field units, this consideration must be added. Example: To ensure operation within specification when any two
consecutive field units lose power, the maximum length of cable, up to 19.2 kbps, should not exceed 4500 ft
(1.37 km) per every four field units. See Section 3.1.2.3, Network Cable Connection to Host Controller or
Master Station II.
Key Specifications
Resistance/1000 ft = 22 AWG (7 x 30) 14.7 ohms each conductor (29.4 ohms for the pair)•
Total cable length between repeaters or nodes with repeaters: up to 19.2 kbps: 3500 ft (1 km) For loop mode, •
this is the total length between operating field units. If a field unit loses power, then the relays internal to the
field unit connect the A1 Channel to the A2 Channel, which effectively doubles the length of the cable (assuming
a single field unit fails). To ensure operation within specifications in the event of power failure to field units, this
consideration must be added. Example: To ensure operation within specification when any two consecutive
field units lose power, the maximum length of cable, up to 19.2 kbps, should not exceed 3500 ft (1 km) per
every four field units. See Section 3.1.2.3, Network Cable Connection to Host Controller or Master Station II.
Key Specifications
Resistance/1000 ft = 24 AWG (7 x 32) 24 ohms each conductor (48 ohms for the pair)•
The Modbus protocol was developed by AEG Modicon® for communicating to various networked devices. The
relationship between these devices and a central controller is called a master-slave relationship in which the master
(host device) initiates all communication. The slave devices (DDC-100 field units in the actuators) respond to the
queries from the master.
Modbus only permits one device to communicate at any given time (simultaneous communication is prohibited) to
ensure process control integrity.
flowserve.com
13
MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/11
2.3.2 Modbus Function Codes
The controlling device (master) must conform to the Modbus protocol as defined in the Modbus-IDA Modbus
Application Protocol Specification V1.1a (http://www.Modbus-IDA.org) and support Modbus function codes 01
through 06, 08, 15, and 16. These function codes are a subset of the complete protocol and are defined in Table 2.1.
Table 2.1 – Modbus function codes supported
Extended
Function Bit/Register Addressing
Code Name Addressing Range
01 Read Coil Status Bit 0,000 - 9,999
02 Read Discrete Inputs Bit 10.000 - 19,999
03 Read Holding Register Register 40,000 - 49,999
04 Read Input Register Register 30,000 - 39,999
05 Force Single Coil Bit 0,000 - 9,999
06 Preset Single Register Register 40,000 - 49,999
08 Diagnostics N/A N/A
15 Force Multiple Coils Bit 0,000 - 9,999
16 Preset Multiple Registers Register 40,000 - 49,999
See Table 2.2 for a complete listing of MX/DDC holding registers.
2.3.3 Modbus Function Code 01 (Read Coil Status)
This function code is used to read the coil status in the DDC-100 Field Unit. There are nine coils available to be read
on DDC-100 Field Units as shown in Table 2.2. For the MX/DDC, Coil 1 indicates CLOSE contactor and is interlocked
with Coil 2, Coil 2 indicates OPEN contactor and is interlocked with Coil 1. When the I/O Module is used in non-MOV
(motor-operated valve) mode, relays 1 through 6 or coils 3 through 8 are available for user configuration.
Table 2.2 – DDC-100 coil assignments, Modbus 05 command usage for digital outputs
Note 1: 18h equals 00011000 or coils 4 and 5 are ON.
1
Data (Coils 8 - 1)
2.3.4 Modbus Function Code 02 (Read Input Status)
This function code is used to read the discrete input status bits in the DDC-100 Field Unit. The use of this function
code will provide the user with the input status bits that are used to develop holding registers 9 through 13. The
status bit inputs are contained in locations 10129-10208 for each DDC-100 Field Unit and are defined in Table 2.3.
Table 2.3 – Status Bit Definitions
Bit Number
129128Opened
130129Closed
131130Stopped in mid-travel
132131Opening
133132Closing
134133Valve jammed
135134Not in remote
136135Combined fault
137136Over-temperature fault
138137Actuator failing to de-energize
139138Channel A fault
140139Channel B fault
141140Open torque switch fault
142141Close torque switch fault
143142Valve operated manually fault
144143Phase error
145144Open inhibit active
146145Close inhibit active
147146Not used
148147Not used
149148One or more phases is missing
150149Reverse phase sequence is occurring
151150ESD conflict
152151Inhibit conflict
153152Use in local/stop (input must be set for CSE and enabled)
154153Not used
155154Network emergency shutdown (ESD) is active
156155Local emergency shutdown is active
Modbus
Bit
Address
MX/DDC
15
flowserve.com
16
MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/11
Table 2.3 – Status Bit Definitions (continued)
Bit Number
157156Field unit microprocessor has reset since the last poll
158157MX in stop move
159158Opening in local mode
160159Closing in local mode
161160Close contactor (interlocked)
162161Open contactor (interlocked)
163162S1 or R1 (opt)
164163S2 or R2 (opt)
165164R3 (opt)
166165R4 (opt)
167166R5 (opt)
168167R6 (opt)
169168R7 (opt)
170169Network relay
171170R8 (opt)
172171Not used
173-176172-175Mov series (0=1, A=9)
177176Remote switch
178177Thermal overload
179178Open torque switch
180179Open limit switch
181180Close torque switch
182181Close limit switch
183182Not used
184183Not used
185184User Input 0
186185User Input 1
187186User Input 2
188187Remote stop input
189188Remote open input
190189Remote close input
191190Not used
192191Not used
193192Analog board 1 present
194193Analog board 2 present
195194Analog Input #1 lost
196195Analog Input #2 lost
197196Network Channels A/B timed out
198197Relay board R5-R8 present
199198DDC board present
200199Relay board R1-R4 and RM present
201200FF board present
202201PB PA board present
203202CLE assigned for input 2
204203DNET board present
Modbus
Bit
Address
MX/DDC
MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/11
Table 2.3 – Status Bit Definitions (continued)
Bit Number
205204Lost Phase Input
206205Phase Reverse Input
207206Not used
208207PB DP board present
Example
Poll field unit number 22 for 16 inputs starting at input 129 with the actuator opening.
Note 1: 01h equals 0000 0001 (actuator open input bit is ON).
Modbus
Bit
Address
MX/DDC
1
Data (Inputs 10136 - 10129)
2
Data (Inputs 10144 - 10137)
Note 2: 08h equals 0000 1000 (actuator Channel B Fail bit is ON).
2.3.5 Modbus Function Code 03 (Read Holding Register)
This function code is used to read the binary contents of holding registers in the DDC-100 Field Unit. This function
code is typically used during the network polling cycle. A network poll should consist of field unit registers 9 (Status)
and 10 (Fault) as a minimum. Holding register 8 should also be polled when the actuator is configured for the analog
feedback option or position control. See Table 2.4 for a complete listing of the holding registers.
17
flowserve.com
MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/11
Table 2.4 – Register definitions
Register # Description Meaning
1 Command Registers 1 and 2 are write-only registers used for Modbus
Function Code 06
2 Argument Registers 1 and 2 are write-only registers used for Modbus
Function Code 06
3 Analog Output 1 Analog Output 1 Value (Default 0-100)
4 Analog Output 2 Analog Output 2 Value (Default 0-100)
5 Analog Input Main Power (Volts)
6 Analog Input Analog Input 1 (Default 0-100)
7 Analog Input Analog Input 2 (Default 0-100)
8 Position Valve Position, Scaled Value (Default 0-100)
9 Status Register 16 Bits of field unit status:
Bit 0 Opened
Bit 1 Closed
Bit 2 Stopped in Mid-Travel
Bit 3 Opening
Bit 4 Closing
Bit 5 Valve jammed
Bit 6 Not in Remote
Bit 7 Combined fault
2
3
Bit 8 Over temperature fault
Bit 9 Future Implementation
Bit 10 Network Channel A fault
Bit 11 Network Channel B fault
Bit 12 Open torque switch fault
Bit 13 Close torque switch fault
Bit 14 Valve-operated manually fault
Bit 15 Phase error
NOTE 1: Default value is scaled 0-100 of span. Changes made to “Analog Scale” affect analog registers (3, 4, 6, 7, 8)
and “move-to” commands. (0-100, 0-255, 0-4095)
1
1
1
User 4-20 mA / 0-20 mA Input
1
User 4-20 mA / 0-20 mA Input
4
(Terminals 5 and 4)
4
(Terminals 13 and 14)
1
18
NOTE 2: MX/DDC actuators shipped after 2nd QTR, 1999, have the following definition of Register 9 Bit 6. When this
bit has a value of 1 or true, the actuator is in LOCAL or STOP (unavailable for network control). The actuator
selector switch in REMOTE (available for network control) is indicated by Register 12 Bit 0 having a value of 1
or true.
IMPORTANT: Verify host program when installing an MX/DDC actuator shipped after 2nd QTR, 1999, on a network
commissioned before 2nd QTR, 1999, for proper indication of selector switch values. Failure to verify proper selector
switch indication at the host may cause unsafe conditions at the facility.
MX/DDC actuators shipped prior to 2nd QTR, 1999, have the following definition for Register 9 Bit 6. When this bit has
a value of 1 or true, the actuator selector switch is in LOCAL mode. This bit does not indicate STOP or REMOTE. The
actuator selector switch in REMOTE (available for network control) is indicated by Register 12 Bit 0 having a value of 1
or true. Register 9 Bit 6 value 0 (zero) or false AND Register 12 Bit 0 value 0 (zero) or false indicates selector switch is
in the STOP position.
NOTE 3: Combined Fault bit is high when Bit 5 or 8 or 9 or 15 or (Bits 10 and 11) is high.
NOTE 4: Channel A is physical connection A1. Channel B is physical connection A2. (See Appendix A.)
MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/11
Table 2.4 – Register definitions (continued)
Register # Description Meaning
10 Fault Register 16 Bits of field status
Bit 0 Open inhibit active
Bit 1 Close inhibit active
Bit 2 Not Used
Bit 3 Not Used
Bit 4 One or more phases are missing
Bit 5 Reverse phase sequence is occurring
Bit 6 ESD conflict
Bit 7 Inhibit conflict
Bit 8 CSE in local/stop (input must be set for CSE and enabled)
Bit 9 Not Used
Bit 10 Network emergency shutdown is active
Bit 11 Local PB emergency shutdown is active
Bit 12 Field unit microprocessor has reset since the last poll
Bit 13 MX in stop mode
Bit 14 Opening in local mode
Bit 15 Closing in local mode
11 Digital Outputs Value of 16 Digital Outputs
Bit 0 Close contactor (Interlocked)
Bit 1 Open contactor (Interlocked)
Bit 2 S1 or R1 (Opt)
Bit 3 S2 or R2 (Opt)
Bit 4 R3 (Opt)
Bit 5 R4 (Opt)
Bit 6 R5 (Opt)
Bit 7 R6 (Opt)
Bit 8 R7 (Opt)
Bit 9 Network Relay
Bit 10 R8 (Opt)
Bit 11 Not Used
BIT 12-15 MOV Series (0 = 1, A = 9)
12 Digital Inputs 1 Value of 16 Digital Inputs
Bit 0 Remote Switch
Bit 1 Thermal Overload
Bit 2 Open Torque Switch
Bit 3 Open Limit Switch
Bit 4 Close Torque Switch
Bit 5 Close Limit Switch
Bit 6 Not Used
Bit 7 Not Used
Bit 8 User Input 0 (Default=ESD), Terminal 30
Bit 9 User Input 1 (Default=Open Inhibit), Terminal 34
Bit 10 User Input 2 (Default=Close Inhibit), Terminal 35
Bit 11 Remote Stop Input, Terminal 26
Bit 12 Remote Open Input, Terminal 25
Bit 13 Remote Close Input, Terminal 27
Bits 14-15 Not Used
flowserve.com
19
MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/11
Table 2.4 – Register definitions (continued)
Register # Description Meaning
13 Digital Inputs 2 Value of 16 Digital Inputs
Bit 0 Analog board 1 present
Bit 1 Analog board 2 present
Bit 2 Analog Input 1 lost
Bit 3 Analog Input 2 lost
Bit 4 Network Channels A/B timed out
Bit 5 Relay board R5-R8 present
Bit 6 DDC board present
Bit 7 Relay board R1-R4 and RM present
Bit 8 Foundation Fieldbus board present
Bit 9 Profibus PA board present
Bit 10 CSE chosen for input 2
Bit 11 DeviceNet board present
Bit 12 Phase lost
Bit 13 Phase reverse
Bit 14 Not Used
Bit 15 Profibus DP board present
14 Timers and Analog Channels Internal compartment temperature
15 User Faults Bits 0-15 Not Used
16 Current State Bits 0-15 Not Used
17 Field Unit Holding Register Special Applications Only
18 Field Unit Holding Register Special Applications Only
19 Field Unit Holding Register Special Applications Only
20 Field Unit Holding Register Special Applications Only
21 Field Unit Holding Register Special Applications Only
22 Field Unit Holding Register Special Applications Only
23 Field Unit Holding Register Special Applications Only
24-44 Reserved Special Applications Only
45-47 Not Named Special Applications Only
48 TP_START_POSITION Special Applications Only
49 TP_STOP_POSITION Special Applications Only
50 TP_SAMPLE Special Applications Only
51 TP_MID_T_HIGH Special Torque Applications Only
52 TP_MID_T_POS Special Applications Only
53 TP_MID_T_AV_VAL Special Torque Applications Only
54 TP_STOP_VAL Special Applications Only
55 TP_BEFORE_ MID_T_HIGH Special Torque Applications Only
56 TP_AFTER_ MID_T_HIGH Special Torque Applications Only
Note 1: Range is +90°C to -55°C. High byte 00 indicates positive (+) and 01 indicates negative (-). Low byte indicates temperature
value.
Example: 0x0019 = +25°C
0x011E = -30°C
1
20
Example
Poll field unit number 125 for 3 registers starting at register 8 with the actuator stopped between the limits and in
local mode.
Query: 7D0300070003BFF6
Response: 7D0306003D084400003E07
Loading...
+ 46 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.