Flowserve LY User Manual

USER INSTRUCTIONS
Limitorque LY Series: LY 1001, LY 2001 and LY 3001
FCD LMENIM1501-00 – 11/11
50
100
0
L i m i t o r q u e
Installation
Maintenance
Experience In Motion
Limitorque LY Series: LY 1001, LY 2001 and LY 3001 FCD LMENIM1501-00 – 11/11
2
Limitorque LY Series: LY 1001, LY 2001 and LY 3001 FCD LMENIM1501-00 – 11/11
Contents
1 Introduction 5
1.1 Purpose 5
1.2 User Safety 5 2 Product Capabilities and Features 6 3 Initial Inspection and Storage Instructions 7
3.1 Product Identification 7
3.2 Inspection and Recording 8
3.3 Storage Procedures 8
3.3.1 Short-Term Storage (less than 1 year) 8
3.3.2 Long-Term Storage (1 to 5 years) 8 4 Actuator Weights 10 5 Installation Instructions 11
5.1 Safety Precautions 11
5.2 Safety Practices 12
5.3 Initial Actuator Preparation 12
5.4 Installation Overview 14
5.5 Torques Switch Settings 18
5.6 Rewiring the Torque Switch for Non-Standard Drive Sleeve Rotation 18
5.7 Limit Switch and Mechanical Stop Settings 19
5.8 Setting the Limit Switches 19
5.8.1 Setting the CLOSED Limit Switch 19
5.8.2 Setting the OPEN Limit Switch 21
5.9 Mechanical Stops 22
5.9.1 Setting the CLOSED Mechanical Stop on the LY 1001 22
5.9.2 Setting the CLOSED Mechanical Stop on the LY 2001/3001 23
5.9.3 Setting the OPEN Mechanical Stop on the LY 1001 24
5.9.4 Setting the OPEN Mechanical Stop on the LY 2001/3001 24
5.10 Setting the MDPI (Mechanical Dial Position Indicator) 24
5.10.1 Setting the Potentiometer 25 6 Operation 27
6.1 Typical LY 1001 Operation 27
6.2 Verify Correct Motor Rotation (Phasing) and OPEN/CLOSE Pushbutton Operation 27
6.2.1 Three-Phase Motor 28
6.2.2 Single-Phase Motor 32
6.2.3 DC Motor 36
6.3 Electrical Startup 36
6.4 Manual Operation 37
6.5 Motor Operation 37
7 Maintenance 45
7.1 Lubrication 45
7.1.1 Lubrication Inspection 45
7.1.2 Factory Lubricant 46
7.2 Minimum Lubricant Qualities Required 46
7.3 Disassembly and Reassembly 46
7.3.1 LY 1001 Disassembly 46
7.3.2 LY 1001 Reassembly 48
7.3.3 LY 2001/3001 Disassembly 50
7.3.4 LY 2001/3001 Reassembly 52
7.4 Troubleshooting 55 8 Parts List 58 9 How to Order Parts 61 10 Regulatory Information 62
3
flowserve.com
Limitorque LY Series: LY1001, LY 2001 and LY 3001 FCD LMENIM1501-00 – 11/11
Figures
Figure 2.1 – LY Actuator 6 Figure 3.1 – LY Nameplate 7 Figure 5.1 – Torque Nut and Retaining Drive Ring Removal from an LY 1001 12 Figure 5.2 – LY Keyway Locations 13 Figure 5.3 – LY 1001, 2001, and 3001 Torque Drive Nut Orientation 15 Figure 5.4 – Removing Control Cover and Conduit Pipe Plugs 16 Figure 5.5 – Grounding Lug Location 17 Figure 5.6 – Reversing Torque Switch Wiring 18 Figure 5.7 – Limit Switch Setting Nut 20 Figure 5.8 – Setting CLOSE Limit Cam 20 Figure 5.9 – Setting OPEN Limit Cam 21 Figure 5.10 – Mechanical Stop Set Screw Adjusted to Torque Nut Contact Point on LY 1001 22 Figure 5.11 – Mechanical Stop Set Screw Adjusted to Torque Nut Contact Point on LY 2001 and 3001 23 Figure 5.12 – Aligning MDPI with Dial Window Retaining Plate 25 Figure 5.13 – Potentiometer Calibration Components 26 Figure 6.1 – Standard Actuator/Three-Phase 29 Figure 6.2 – Three-Phase with Control Package 30 Figure 6.3 – Standard Actuator/Single-Phase 33 Figure 6.4 – Single-Phase with Control Package 34 Figure 6.5 – LY 1001 Cover and Associated Parts 38 Figure 6.6 – LY 1001 Top Plate and Associated Parts 39 Figure 6.7 – LY 1001 Housing and Associated Parts 40 Figure 6.8 – LY 2001/3001 Cover and Associated Parts 41 Figure 6.9 – LY 2001/3001 Top Plate and Associated Parts 42 Figure 6.10 – LY 2001/3001 Housing and Associated Parts 43 Figure 6.11 – LY 3001 Handwheel Assembly 44 Figure 7.1 – LY 1001 Declutch Return Spring Installation Position 48 Figure 7.2– LY 2001/3001 Declutch Return Spring Installation Position 52
Tables
Table 4.1 – Actuator Weights 10 Table 5.1 – Mounting Base Dimensions 13 Table 5.2 – LY Actuator/Mounting Base Tap Sizes 16 Table 5.3 – Control Cover and Conduit Pipe Plug Hardware 16 Table 5.4 – LY Control Cover and Integral Control Cover Bolt Sizes and Torques 17 Table 5.5 – Mechanical Stop Set Screws 22 Table 5.6 – Mechanical Stop and Locknut Screw Sizes 23 Table 8.1 – LY 1001 Parts List 58 Table 8.2 – LY 2001/3001 Parts List 59
4
1
Limitorque LY Series: LY 1001, LY 2001 and LY 3001 FCD LMENIM1501-00 – 11/11
Introduction
1.1 Purpose
This Installation and Maintenance Manual explains how to install and maintain LY actuators. Information on installation, disassembly, lubrication, and parts is provided.
1.2 User Safety
Safety notices in this manual detail precautions the user must take to reduce the risk of personal injury and damage to the equipment. The user must read and be familiar with these instructions before attempting installation, operation, or maintenance. Failure to observe these precautions could result in serious bodily injury, damage to the equipment, warranty void, or operational difficulty.
Safety notices are presented in this manual in three forms:
c WARNING: Refers to personal safety. Alerts the user to potential danger. Failure to follow
warning notices could result in personal injury or death.
a CAUTION: Directs the user’s attention to general precautions that, if not followed, could result in
personal injury and/or equipment damage.
NOTE: Highlights information critical to the user’s understanding of the actuator’s installation and operation.
flowserve.com
5
2
Limitorque LY Series: LY 1001, LY 2001 and LY 3001 FCD LMENIM1501-00 – 11/11
Product Capabilities and Features
The LY actuator controls the opening and closing travel of the valve and limits torque through the torque switches provided. As a result, all valve-operating parts are protected from overload, improper seating, and foreign obstructions.
LY actuators may be mounted on any size valve in almost any position or location.
Microprocessor-based control and monitoring devices are available for installation on your actuator. Contact your local Limitorque distributor or Limitorque sales office for further information.
Figure 2.1 – LY Actuator (LY 1001 shown)
50
100
0
L i m i t o r q u e
Position Indication Window
Control Cover
Housing
Conduit Adapter
6
Handwheel typically clockwise turn to CLOSE and counterclockwise turn to OPEN
Declutch Lever
Limitorque LY Series: LY 1001, LY 2001 and LY 3001 FCD LMENIM1501-00 – 11/11
Initial Inspection and Storage Instructions
3
c WARNING: Read this Installation and Maintenance Manual carefully and completely before
attempting to store the actuator. Be aware of electrical hazards within the actuator and high­pressure hazards of the attached valve or other actuated device when installing or performing maintenance on your LY actuator.
3.1 Product Identification
The actuator unit nameplate is located on the side of the unit opposite the conduit entry. The nameplate contains the following information:
• Limitorque name
• Point of Manufacture
• Unit Size
• Serial Number
• Order Number
• Electrical Power Supply
• Operating Time (seconds)
• Motor Full Load Amperage
• Connection diagram
Figure 3.1 – LY Nameplate (Reference Drawing 61-682-0108)
LETTERS TO BE LASER ETCHED (SILVER)
LUBE
TAGGING
LY­ORDER SERIAL VOLT OP. TIME
R
Limitorque
Lynchburg, VA. USA
PH FLA
7
flowserve.com
Limitorque LY Series: LY 1001, LY 2001 and LY 3001 FCD LMENIM1501-00 – 11/11
3.2 Inspection and Recording
Upon receipt of the actuator, inspect the condition of the equipment and record nameplate information as follows:
1. Carefully remove actuator from shipping carton or skid. Thoroughly examine the equipment for any physical damage that may have occurred during shipment. If damaged, immediately report the damage to the transport company.
2. Record the unit nameplate information for future reference, i.e., ordering parts, and obtaining further information.
3.3 Storage Procedures
NOTE: The following are Flowserve’s recommended storage procedures to retain maximum product integrity during short-term and long-term storage. Failure to comply with recommended procedures will void the warranty.
3.3.1 Short-Term Storage (less than 1 year)
Actuators should be stored in a clean, dry, protected warehouse, free from excessive vibration and rapid temperature changes.
Preparation
1. Connect internal heaters, if supplied.
2. Replace all plastic caps or plugs with metal pipe plugs.
3. Ensure all covers are tight.
Outdoor Storage
If actuators must be stored outdoors, they must be stored off the ground, high enough to prevent being immersed in water or buried in snow.
LY Storage Orientation
• Store with the Control Compartment Cover (Limit Switch compartment) facing upward.
• Do not store units on their side.
3.3.2 Long-Term Storage (1 to 5 years)
Actuators should be stored in a clean, dry, protected warehouse, free from excessive vibration and rapid temperature changes.
NOTE: During long-term storage, the maximum source of equipment deterioration anticipated is from possible condensation within the actuator enclosure. This condensation may occur with rapid temperature changes in the storage environment. If reliable means are not available to prevent rapid temperature changes, a heat source should be added in the electrical enclosure during storage. Consult the Limitorque Customer Service Department for further information.
8
Limitorque LY Series: LY 1001, LY 2001 and LY 3001 FCD LMENIM1501-00 – 11/11
Preparation
1. Connect internal heaters, if supplied.
2. Replace all plastic caps or plugs with metal pipe plugs.
3. Ensure all covers are tight.
LY Storage Orientation
1. Store with the Control Compartment Cover (Limit Switch compartment) facing upward. Do not store units on their side.
2. Store off the floor on suitable skids and cover with an unsealed dust cover leaving the bottom open and air holes in the side.
Storage Inspection and Correction
1. Perform a semi-annual visual inspection. A minimum inspection should include checking the following:
•Packaging •Plugs
•Covers •Dryness
•Cleanliness  •Heatsource(ifused)forproperfunctioning
2. Record and correct deficiencies noted during inspection.
flowserve.com
9
4
Limitorque LY Series: LY 1001, LY 2001 and LY 3001 FCD LMENIM1501-00 – 11/11
Actuator Weights
The approximate LY actuator weights are provided below.
Table 4.1 – Unit Weights
Unit Size Control Types
NCU 40 20
LY 1001
LY 2001
LY 3001
BIC 75 34 UEC 90 41 NCU 100 45
BIC 110 50 UEC 144 65 NCU 105 48
BIC 130 59 UEC 149 68
Weight
lb. kg
10
5
Limitorque LY Series: LY 1001, LY 2001 and LY 3001 FCD LMENIM1501-00 – 11/11
Installation Instructions
5.1 Safety Precautions
c WARNING: Read this Installation and Maintenance Manual carefully and completely before
attempting to install, operate, or troubleshoot the Limitorque actuator.
c WARNING: Be aware of electrical hazards. Turn off incoming power before working on the
actuator and before opening the switch compartment.
c WARNING: Potential HIGH PRESSURE vessel — be aware of high-pressure hazards associated
with the attached valve or other actuated device when installing or performing maintenance on the actuator. Do not remove the actuator mounting bolts from the valve or actuated device unless the valve or device stem is secured or there is no pressure in the line.
c WARNING: For maintenance and/or disassembly of the actuator while installed on the valve,
ensure that the actuator is not under thrust or torque load. If the valve must be left in service, the valve stem must be locked in such a way as to prevent any movement of the valve stem.
c WARNING: Do not manually operate the actuator with devices other than the installed hand-
wheel and declutch lever. Using force beyond the ratings of the actuator and/or using additive force devices such as cheater bars, wheel wrenches, pipe wrenches, or other devices on the actuator handwheel or declutch lever may cause serious personal injury and/or damage to the actuator and valve.
c WARNING: Do not exceed any design limitations or make modifications to this equipment
without first consulting Limitorque.
c WARNING: Actuators equipped with electrical devices (motors, controls) requiring field wiring
must be wired and checked for proper operation by a qualified tradesman.
c WARNING: Use of the product must be suspended any time it fails to operate properly.
11
flowserve.com
Limitorque LY Series: LY 1001, LY 2001 and LY 3001 FCD LMENIM1501-00 – 11/11
a CAUTION: Do not operate the valve under motor operation without first setting or checking the
limit switch setting and motor direction.
a CAUTION: Do not force the declutch lever into the motor operation position. The lever returns to
this position automatically when the motor is energized.
a CAUTION: Do not depress the declutch lever during motor operation to stop valve travel.
a CAUTION: Do not use replacement parts that are not genuine Flowserve Limitorque parts, as
serious personal injury and/or damage to the actuator and valve may result.
a CAUTION: Do not lift the actuator by handwheel.
5.2 Safety Practices
The following check points should be performed to maintain safe operation of the LY actuator:
• Keep the switch compartment clean and dry.
• Keep the valve stem clean and lubricated.
• Set up a periodic operating schedule for infrequently used valves.
• Verify all actuator wiring is in accordance with the applicable wiring diagram.
• Carefully check for correct motor rotation direction. If the valve closes when open button is pushed,
the motor leads may have to be reversed.
12
5.3 Initial Actuator Preparation
Piece numbers refer to Figure 5.1.
1. Remove the Retaining Drive Ring (piece #165 or #109) and Torque Nut (piece #32) from actuator.
Figure 5.1 – Torque Nut and Retaining Drive Ring Removal from an LY 1001
L i m i t o r q u e
#32 Torque Nut
#165 (LY 1001) #109 (LY 2001/3001) Torque Nut Retaining Drive Ring
Limitorque LY Series: LY 1001, LY 2001 and LY 3001 FCD LMENIM1501-00 – 11/11
2. If Torque Nut has been bored and keywayed by Limitorque, verify dimensions and keyway location for proper compatibility with the valve stem.
3. If Torque Nut has not been bored and keywayed by Limitorque, it is provided solid (blank) to allow customer to custom key and bore up to the maximum permissible sizes as listed in Table 5.1.
Table 5.1 – Mounting Base Dimensions
Unit Type and Size
LY 1001 1-1/8, dia (28 dia) 1/4 x 1/8, (6 x 3)
LY 2001/3001 2-3/8, dia (60 dia) 5/8 x 1/16 (15 x 7.5)
NOTE: Before keywaying, match the Torque Nut with the Valve Stem to ensure proper keyway location. Use the Keyway Index Mark (LY 1001 only) for locating appropriate keyway location.
Maximum Bore
inch (mm)
Maximum Keyway
inch (mm)
Figure 5.2 – LY Keyway Locations
LY 2001/3001 Keyway Location Positions
B
A
LY 1001 Keyway
A
Location Marks
D
B
C
To rque Nut
C
D
Stop Lug
flowserve.com
13
Limitorque LY Series: LY 1001, LY 2001 and LY 3001 FCD LMENIM1501-00 – 11/11
5.4 Installation Overview
a CAUTION: Be sure to complete each step of the installation overview before electrically
operating your actuator. If the actuator is already mounted to a valve from the manufacturer, verify that the actuator is mounted according to the following overview. Failure to follow the installation procedures could result in personal injury and/or improper operation and could cause damage to the equipment.
1. Mount Torque Nut (piece #32) in the actuator as shown in Figure 5.3 with the following alignment:
A. For LY 1001 – Stop Lugs facing the Actuator Mounting Adapter with index lines positioned to
face the Mechanical Stop Screws.
B. For LY 2001/3001 – Torque Nut axially aligned on the Drive Sleeve so that the bottom of the nut
is positioned inside the Actuator Mounting Base.
2. Insert the Retaining Drive Ring (piece #165 for LY 1001, piece #109 for LY 2001/3001) on the Torque Nut (piece #32) to hold the Torque Nut in place in the actuator.
3. Mount the LY actuator on the mounting flange of the valve or other actuated equipment. High­strength (minimum SAE-Grade 5 120,000 psi tensile strength) hex head or socket head cap screws with lockwashers are recommended. The actuator mounting tap quantities and thread sizes are detailed in Table 5.2.
14
Limitorque LY Series: LY 1001, LY 2001 and LY 3001 FCD LMENIM1501-00 – 11/11
Figure 5.3 – LY 1001, 2001, and 3001 Torque Drive Nut Orientation
#32 Torque Nut
CCW to
Open
Torque Nut Stop Lugs
Actuator Mounting Base
Valve Stem
Actuator Mounting
LY 1001
Adapter
Mechanical Stop
Setscrews
Closed
Open
B
A
D
C
Stop Lug index lines facing Mechanical Stop Screws
Top view of LY 1001 Mechanical Stops
CCW to
Open
LY 2001/3001
Actuator Mounting Base
#32 Torque
Nut
Valve Stem
Actuator Mounting Adapter
Top view of LY
2001/3001 Mechanical Stops
Stop Pins located within actuator housing on the Drive Sleeve Gear
Mechanical Stop Screws
Closed
D
A
C
B
Open
15
flowserve.com
Limitorque LY Series: LY 1001, LY 2001 and LY 3001 FCD LMENIM1501-00 – 11/11
Table 5.2 – LY Actuator/Mounting Base Tap Sizes
Unit Type
and Size
LY 1001 8
LY 2001/3001 8
Qty
English Metric
3/8-16 x
0.71 deep
5/8-11 x
1.26 deep
Tap Size
M10 x 1.5 mm x 25 mm deep
(Complies with F10 ISO
mounting flange criteria)
M16 x 2 mm x 35 mm deep
(Complies with F10 ISO
mounting flange criteria)
NOTE: Flowserve has supplied eight taps for the LY 1001, LY 2001, and LY 3001 in English/Metric units to provide flexibility in mounting arrangements. A minimum of four securing bolts is required to properly secure and retain torque reaction on these units.
c WARNING: HAZARDOUS VOLTAGE. No electrical power should be connected until all wiring
and limit switch adjustments have been completed. Once power is supplied to unit, exercise caution if cover is not installed.
4. Remove the Control Cover (piece #3) and Conduit Pipe Plugs (piece #144).
Figure 5.4 – Removing Control Cover and Conduit Pipe Plugs
L i mi to r q u e
#3 Control Cover
16
#144 Conduit Pipe Plugs
Table 5.3 – Control Cover and Conduit Pipe Plug Hardware
Unit Type
LY 1001
(WP & XP)
LY 2001/3001 8
Control Cover Conduit Pipe Plug
Quantity Size Quantity Size
6 M8 x 40 mm 2
M12 x 50 mm (WP)
M12 x 55 mm (XP)
1" NPT Socket
Hex Head
2
1" NPT Socket
Hex Head
Limitorque LY Series: LY 1001, LY 2001 and LY 3001 FCD LMENIM1501-00 – 11/11
5. Adjust the Limit Switches, Mechanical Stops, and Position Indication Dial following the procedures detailed in Section 5.7, Limit Switch and Mechanical Stop Settings.
6. Connect the wiring to the terminal strips provided on the actuator. Refer to the wiring diagram supplied with the actuator. “Fork-type” terminal connections are recommended.
7. Insert a Conduit Pipe Plug in the unused conduit entrance if the wiring that enters the actuator uses only one conduit entrance.
NOTE:
a. Explosionproof actuators require approved “sealing fittings” installed in accordance with the
National Electric Code.
b. Submersible actuators require an approved “sealing fitting” in order to keep water from entering
the actuator.
8. Attach grounding wire to Grounding Lug (piece #141).
9. Verify motor rotation direction to ensure that the limit switch is wired properly for intended operation. (See Section 6.2, Verify Correct Motor Rotation (Phasing) and OPEN/CLOSE Pushbutton Operation.)
Figure 5.5 – Grounding Lug Location
#141 Grounding Lug
To earth ground
10. Reinstall Control Cover (piece #3).
NOTE: Submersible actuators require tightening the Control Cover Bolts and Integral Control Cover Bolts to a specified torque in order to maintain submersibility. (See Table 5.4 for specific torque settings.)
Table 5.4 – LY Control Cover and Integral Control Cover Bolt Sizes and Torques
Unit Type Control Cover Integral Compartment
LY 1001 M8 - 10 to 15 ft-lb M10 - 15 to 20 ft-lb
LY 2001/3001 M12 - 20 to 25 ft-lb M10 - 15 to 20 ft-lb
Unit is now ready for electrical operation.
17
flowserve.com
Limitorque LY Series: LY 1001, LY 2001 and LY 3001 FCD LMENIM1501-00 – 11/11
5.5 Torque Switch Settings
c WARNING: HAZARDOUS VOLTAGE. Turn power OFF before opening the Electrical Compartment
Cover or making any adjustments to the Torque Switch.
a CAUTION: Installing or adjusting the Torque Switch with the actuator in a loaded condition will
result in loss of torque protection. Before adjusting or installing the Torque Switch, place the actuator in MANUAL mode and turn the Handwheel in the direction necessary to release the torque load on the Wormshaft Assembly.
NOTE: Removal or modification of the Torque Switch Limiter Plate will void the actuator warranty. Do not exceed the torque setting indicated by the Torque Switch Limiter Plate without contacting the Limitorque Service Department.
The LY unit is equipped with a do W to MEDIUM or HIGH by adjusting the Torque Switch Adjustment Screw unless it is limited by the Limiter Plate. (See Figure 5.6 for Torque Switch Adjustment Screw location.)
5.6 Rewiring the Torque Switch for Non-Standard Drive Sleeve Rotation
a CAUTION: Double-check the wiring diagram to verify that the Torque Switch is wired appro-
priately for the application. The Torque Switch will not protect the valve from over-torque if the Torque Switch is not wired properly for the application.
LY series actuators are typically supplied with a CCW Drive Sleeve rotation to open a valve. The Torque Switch is marked OPEN (CCW) and CLOSE (CW) based upon CW Drive Sleeve rotation to close the valve. The Mechanical Dial Position Indicator (MDPI) is typically mounted for CW rotation to indicate the CLOSED position. If opposite Drive Sleeve rotation is required (CCW to close a valve), the following Torque Switch modifications are required.
1. Turn all power to the actuator OFF.
2. Reverse the ID Limiter Plate.
3. Interchange OPEN Torque Switch wires 18 and 18C with CLOSED wires 17 and 17C. (Refer to the wiring diagram for other Torque Switch wiring configurations.)
Figure 5.6 – Reversing Torque Switch Wiring
18
Typical CLOSE-circuit microswitch (17 &17C)
Typical OPEN-circuit microswitch (18 &18C)
CLOSE
LY-1
H
M
L
OPEN
H M L
ID-Limiter Plate
Torque Switch Adjustment Screws
Limitorque LY Series: LY 1001, LY 2001 and LY 3001 FCD LMENIM1501-00 – 11/11
4. Remove the MDPI Plate and flip over for indication of CCW rotation to the valve’s closed position. (See Figure 5.12 for MDPI Dial Plate.)
5.7 Limit Switch and Mechanical Stop Settings
The Limit Switch and Mechanical Stops are not preset at the factory, but must be set after mounting on the associated equipment. If the actuator has been shipped already installed on a valve, the actuator should have the Limit Switch and Mechanical Stops set for your application. If the actuator is not already installed on a valve or needs resetting, use the following instructions to make the appropriate settings.
The following instructions for setting the Limit Switches and Mechanical Stops are based on the typical orientation for most actuator applications. Consult the applicable wiring diagram located in the Control Compartment for the specific Limit Switch development.
NOTE: While making Limit Switch settings, remember that the Limit Cams rotate in the same direction as the valve stem.
5.8 Setting the Limit Switches
c WARNING: Do not manually operate actuator with devices other than installed Handwheel and
Declutch Lever. Using additive force devices (cheater bars, wheel wrenches, pipe wrenches or other devices of this nature) on the actuator Handwheel or Declutch Lever may cause serious personal injury and/or damage to the actuator or valve.
c WARNING: HAZARDOUS VOLTAGE. Make sure all power is disconnected before making the
following settings.
5.8.1 Setting the CLOSED Limit Switch
1. Put the actuator in MANUAL operation: move the Declutch Lever in the direction of the arrow on the lever until the Declutch Lever locks in place. If Declutch Lever is difficult to move, see Section 6.4, Manual Operation for instructions to release the Declutch Lever.
2. Turn the Handwheel CW to move the valve to the full CLOSE position.
NOTE: Most applications require turning the Handwheel CW to obtain the full CLOSE position and
CCW to obtain full OPEN position. The Drive Sleeves and Limit Cams also rotate in CW rotation to the CLOSE position and CCW to the OPEN position. If the application is configured differently, the descriptions in this manual will describe rotation directions opposite your application.
3. Loosen Setting Nut (piece #7-10) located at the top of the switch bracket approximately ¾ turn.
NOTE: When setting the Limit Cams by rotating to the trip point as described in Step 4, be careful
not to move more than one cam at a time. Limit Cams that have already been set are not secure until Setting Nut (piece #7-10) is retightened.
19
flowserve.com
Limitorque LY Series: LY 1001, LY 2001 and LY 3001 FCD LMENIM1501-00 – 11/11
CLOSE
Figure 5.7 – Limit Switch Setting Nut
100
50
0
OPEN
PERCENT
Limitorque
7-10
Standard OPEN Microswitch location
Standard CLOSE Microswitch location
4. Rotate the CLOSE Limit Cam CW through the high side to the trip point until the Switch Plunger is released. This causes the N.O. (normally open) contact to open.
NOTE: There will be no electrical continuity at the trip point when measuring with an ohmmeter
between the common lead and the N.O. lead. You may also hear a faint “click” at the trip point.
NOTE: During actuator operation, when the Switch Plunger trips, the N.O. contact is released,
causing the Limit Switch to stop the actuator in the CLOSED position.
Figure 5.8 – Setting CLOSE Limit Cam
Tr ip Point position (“click”)
CLOSE Limit Cam
Switch Plunger
COM
NO
NC
CLOSE microswitch position when valve has reached the CLOSED position and microswitch has tripped
CLOSE Limit Cam
High Side
Rotate CW to reach CLOSE Tr ip Point
COM
NO
NC
CLOSE microswitch position while valve is traveling from OPEN toward the CLOSED position
Switch Plunger
High Side
20
5. Retighten Setting Nut (piece #7-10).
Loading...
+ 44 hidden pages