Carrier 30GX090, 30HXA086, 30GX105, 30GX106, 30GX115 Controls, Start-up, Operation, Service, And Troubleshooting

...
0 (0)
Controls, Start-Up, Operation,
Service, and Troubleshooting
SAFETY CONSIDERATIONS
Installing, starting up, and servicing this equipment can be hazardous due to system pressures, electrical compo­nents, and equipment location (roof, elevated structures, etc.). Only trained, qualified installers and servicemechanicsshould install, start up, and service this equipment.
Electrical shock can cause personal injury and death. Shut off all power to this equipment during installation and service. There may be more than one disconnect switch. Tag all disconnect locations to alert others not to restore power until work is completed.
This unit uses a microprocessor-based electronic con­trol system. Do not use jumpers or other tools to short out components, or to bypass or otherwise depart from recommended procedures. Any short-to-ground of the control board or accompanying wiring may destroy the electronic modules or electrical components.
To prevent potential damage to heat exchanger tubes al­ways run fluid through heat exchangers when adding or removing refrigerant charge.
DO NOT VENT refrigerant relief valves within a build­ing. Outlet from relief valves must be vented outdoors in accordance with the latest edition of ANSI/ASHRAE (American National Standards Institute/American Soci­ety of Heating, Refrigeration and Air Conditioning En­gineers) 15 (Safety Code for Mechanical Refrigeration). The accumulation of refrigerant in an enclosed space can displace oxygen and cause asphyxiation. Provide ad­equate ventilation in enclosed or low overhead areas. Inhalation of high concentrations of vapor is harmful and may cause heart irregularities, unconsciousness or death. Misuse can be fatal. Vapor is heavier than air and reduces the amount of oxygen available for breathing. Product causes eye and skin irritation. Decomposition products are hazardous.
DO NOT attempt to unbraze factory joints when ser­vicing this equipment. Compressor oil is flammable and there is no way to detect how much oil may be in any of the refrigerant lines. Cut lines with a tubing cutter as required when performing service. Use a pan to catch any oil that may come out of the lines and as a gage for how much oil to add to system. DO NOT re-use com­pressor oil.
CONTENTS
Page
SAFETY CONSIDERATIONS ...................1
GENERAL ...................................2
MAJOR SYSTEM COMPONENTS ..............3
Processor Module (PSIO-1) ...................3
DSIO-HV Relay Module .......................3
Electronic Expansion Device Module .........3
Compressor Protection Module (CPM) .........3
PSIO-2 (8052) Module ........................3
Keypad and Display Module
(Also Called HSIO-II) .......................3
Control (LOR) Switch .........................3
OPERATION DATA ..........................3-42
Electronic Expansion Device (EXD) ...........3
• EXV OPERATION
• ECONOMIZER OPERATION
Oil Pumps ...................................4
Motor Cooling ...............................4
Back Pressure Valve (30GX and 30HXA only) ..4
Sensors .....................................4
Compressor Protection Module (CPM) .........4
• OUTPUTS
• INPUTS
Wye-Delta vs Across-the-Line (XL)
Starting Option ............................5
Capacity Control .............................6
• MINUTES LEFT FOR START
• MINUTES OFF TIME
• LOADING SEQUENCE
• CLOSE CONTROL
• LEAD/LAG DETERMINATION
• CAPACITY SEQUENCE DETERMINATION
• MINIMUM LOAD VALVE
• CAPACITY CONTROL OVERRIDES
Head Pressure Control .......................8
• GENERAL
• AIR COOLED UNITS (30GX)
• WATER COOLED UNITS (30HX)
• ADJUSTING PID ROUTINES
Cooler and Condenser (30HXC)
Pump Control .............................10
30GX080-265
30HXA,HXC076-271
ECOLOGIC™ Air-Cooled and Fluid Cooled Chillers
50/60Hz
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 2 Tab 5c
PC 903 Catalog No. 533-062 Printed in U.S.A. Form 30G,H-3T Pg 1 1-98 Replaces: 30G,H-2T
Series 0,1,2
CONTENTS (cont)
Page
• COOLER PUMP CONTROL
• CONDENSER PUMP CONTROL
Cooler Heater Control .......................13
Keypad and Display Module
(Also Called HSIO-II) ......................13
• ACCESSING FUNCTIONS
AND SUBFUNCTIONS.......................13
• AUTOMATIC DEFAULT DISPLAY.............13
• STATUS FUNCTION .........................16
• TEST FUNCTION ...........................25
• HISTORY FUNCTION........................25
• SET POINT FUNCTION ......................25
• SERVICE FUNCTION ........................30
• SCHEDULE FUNCTION......................37
Temperature Reset ..........................39
• EXTERNAL TEMPERATURE RESET
• EXTERNALLY POWERED RESET
• RETURN FLUID TEMPERATURE RESET
Demand Limit ...............................39
• DEMAND LIMIT
• EXTERNALLY POWERED DEMAND LIMIT
• DEMAND LIMIT (CCN Loadshed Controlled)
TROUBLESHOOTING ......................43-52
Checking Display Codes ....................43
Unit Shutoff ................................43
Complete Unit Stoppage .....................43
Single Circuit Stoppage .....................43
Restart Procedure ...........................43
• POWER FAILURE EXTERNAL TO THE UNIT
Alarms and Alerts ...........................43
Compressor Alarm/Alert Circuit ..............43
EXD Troubleshooting Procedure .............50
• INSPECTING/OPENING ELECTRONIC EXPANSION VALVES
• INSPECTING/OPENING ECONOMIZERS
SERVICE ..................................52-66
Servicing Coolers and Condensers ..........52
• TUBE PLUGGING
• RETUBING
• TIGHTENING COOLER/CONDENSER HEAD BOLTS
Inspecting/Cleaning Heat Exchangers ........53
• COOLERS
• CONDENSERS (30HX Only)
Water Treatment ............................53
Condenser Coils (30GX Only) ................53
• COIL CLEANING
Condenser Fans (30GX Only) ................54
Refrigerant Charging/Adding Charge .........54
Oil Charging/Low Oil Recharging ............55
Oil Filter Maintenance .......................56
• REPLACING THE EXTERNAL OIL FILTER
• REPLACING THE INTERNAL OIL FILTER
Compressor Changeout Sequence ...........56
• BURNOUT CLEAN-UP PROCEDURE
Moisture-Liquid Indicator ....................58
Filter Drier ..................................58
Liquid Line Service Valve ....................58
Thermistors ................................58
• LOCATION
• THERMISTOR REPLACEMENT
Pressure Transducers .......................59
• PRESSURE TRANSDUCER CALIBRATION
• TROUBLESHOOTING
Safety Devices ..............................62
• COMPRESSOR PROTECTION
• OIL SEPARATOR HEATERS (30GX)
• COOLER PROTECTION
Relief Devices ..............................62
• PRESSURE RELIEF VALVES
Control Modules ............................64
• PROCESSOR MODULE (PSIO-1), HIGH VOLTAGE RELAY MODULE (DSIO-HV), AND EXV DRIVER MODULE (DSIO-EXV), 12/6 MODULE (PSIO-2)
• RED LED
• GREEN LED
Carrier Comfort Network (CCN) Interface .....64
• PROCESSOR MODULE (PSIO-1)
• HIGH VOLTAGE RELAY MODULE (DSIO-HV)
Replacing Defective Processor Module .......66
Winter Shutdown Preparation ................66
PRE-START-UP PROCEDURE ................67
START-UP AND OPERATION .................67
FIELD WIRING ............................68-73
APPENDIX A
(Compressor Must Trip Amps) ...........74-76
APPENDIX B
(Capacity Loading Sequence) ............77-79
APPENDIX C (Available Accessories) .........80
APPENDIX D (CPM Configurations) .........81-85
APPENDIX E (Cooler and
Condenser Pressure Drop) ...............86-88
APPENDIX F
(Typical System Components) ............89,90
INDEX ......................................91
START-UP CHECKLIST ..............CL-1 to CL-8
GENERAL
IMPORTANT: The 30GX/HX units use refrigerant R-134a. Compressor oil used with R-134a is Polyo­lester oil.
This publication contains Start-Up, Service, Controls, Operation and Troubleshooting data for the 30GX080-265 and 30HXA,C076-271 screw chillers.
Circuits are identified as circuits A and B, and compres­sors are identified as A1 or A2 in circuit A, and B1 in circuit B.
The 30GX/HX Series chillers feature microprocessor­based electronic controls and electronic expansion devices (EXD) in each refrigeration circuit.
The control system cycles compressor loaders and/or com­pressors to maintain the selected leaving fluid temperature set point. The system automatically positions the EXD to maintain the specified refrigerant level in the cooler.Thesys­tem also has capabilities to control a condenser water valve to maintain suitable leaving-water temperature for the30HXC unit. Safeties are continuously monitored to prevent the unit from operating under unsafe conditions. A scheduling func­tion can be programmed by the user to control the unit’s oc­cupied and unoccupied schedules. The control also operates a test function and a manual control function that allows the operator to check output signals and ensure components are operable.
The control system consists of a processor module (PSIO-1), an EXD driver module (DSIO-EXV), a high volt­age relay module on 30GX units (DSIO-HV), 2 six-pack re­lay boards, a keypad and display module (also called HSIO­II), 2 electronic expansion devices (EXDs), 1 compressor protection module (CPM) per compressor, a PSIO-2 mod­ule, 6 thermistors, and 8 transducers. Aremoteenhanceddis­play is available as an accessory.
2
MAJOR SYSTEM COMPONENTS
Processor Module (PSIO-1) —
This module is an upgrade to the original PSIO (8088) module, with superior electrical noise immunity capability. It contains the operat­ing software and controls the operation of the machine. It has 12 input channels and 6 output channels.
The PSIO-1 continuously monitors input/output channel information received from all the modules and controls all output signals for all output channels. It also controls the relays on the six-pack relay board. The processor module also controls the EXD driver module (as required), com­manding it to open or close each EXD in order to maintain the proper cooler level. Information is transmitted between the processor module, CPM modules, the EXD driver mod­ule, and the HSIO-II standarddisplaymodulethrougha3-wire communications bus called COMM3. The remote enhanced display (accessory) is connectedtothePSIO-1modulethrough a 3-wire communications bus, but uses a different commu­nication bus called COMM1. The COMM1 bus is also used to communicate to other CCN (Carrier Comfort Network) devices when the unit is installed in a network application.
DSIO-HV Relay Module — The DSIO-HV module has
4 inputs and 8 outputs and is installed on 30GX units only. The module communicates the status of the inputs with the PSIO-1 module and operates the oil heater, outdoor fan, and minimum load control outputs.
Electronic Expansion Device Module — The elec-
tronic expansion device module has 4 inputs and 2 outputs. It receives signals from the PSIO-1 module and operates the electronic expansion devices. The electronic expansion de­vice module also sends the PSIO-1 module the status of its 4 input channels.
CompressorProtectionModule(CPM)— The com-
pressor protection module monitors several of the compres­sor safeties and controls 4 of the outputs used to control each compressor. The CPM monitors compressor current, com­pressor voltage, high pressure switch status, and compressor motor temperature. The CPM controls the compressor con­tactors, oil solenoid, and motor cooling solenoid. Each CPM sends the PSIO-1 its circuit’s motor temperature, alarm sta­tus of the module, and the compressor relay status.
PSIO-2 (8052) Module — This module is used as an
input/output module only,as there is no unit software loaded in the module. This module has 12 input channels and 6 out­put channels.
Keypad and Display Module (Also Called HSIO-II) —
This device consists of a keypad with 8 func­tion keys, 4 operative keys, 12 numeric keys, and a 2-line 24-character alphanumeric LCD (liquid crystal display). Key usage is explained in the Accessing Functions and Subfunc­tions section on page 13.
Control (LOR) Switch — Control of the chiller is de-
fined by the position of the LOCAL/OFF/REMOTE (LOR) switch. This is a 3-position manual switch that allows the chiller to be put under the control of its own controls (LO­CAL), manually stopped (OFF), or controlled through a set of remote contacts (REMOTE). This switch is different than the switch that is used in the Flotronic™ II controls con­figuration. The CCN control is enabled through the HSIO-II. The switch allows unit operation as shown in Table 1.
In the LOCAL position, the chiller is allowed to operate and respond to the scheduling configuration, CCN configu­ration, and set point data. In the remote position, the unit operates similarly to the LOCAL position, except the remote contacts must be closed for the unit to operate.
Table 1 — Unit Mode from LOR Switch
and CCN State
SWITCH
POSITION
REMOTE
CONTACTS
CCN
CONFIGURATION
CCN
STATE
UNIT
MODE
OFF NR NR NR LOCAL OFF
LOCAL NR
DISABLE NR LOCAL ON
ENABLE
RUN CCN ON
STOP CCN OFF
REMOTE
OPEN NR NR LOCAL OFF
CLOSED
DISABLE NR LOCAL ON
ENABLE
RUN CCN ON
STOP CCN OFF
LEGEND
CCN — Carrier Comfort Network NR Input Not Read by Processor
NOTE: Iftheunit is configured for aclock,then the unit isunderclock control if it is in an ON mode.
OPERATION DATA
Electronic Expansion Device (EXD) —
The micro­processor controls the EXD through the EXD driver mod­ule. The EXD will either be an EXV (electronic expansion valve) or an economizer. Inside both these devices is a linear actuator stepper motor.
EXV OPERATION — High-pressure liquid refrigerant en­ters the valve through the bottom. Aseriesof calibrated slots are located inside the orifice assembly. As refrigerant passes through the orifice, the pressure drops and the refrigerant changes to a 2-phase condition (liquid and vapor). To con­trol refrigerant flow for different operating conditions, the sleeve moves up and down over the orifice, thereby chang­ing orifice size. The sleeve is moved by a linear stepper mo­tor.The stepper motor moves in increments and is controlled directly by the processor module. As the stepper motor ro­tates, motion is transferred into linear movement by the lead screw. Through the stepper motor and lead screw, 1500 dis­crete steps of motion are obtained. The large number of steps and long stroke result in very accurate control of refrigerant flow.
Each circuit has a liquid level sensor mounted vertically in the top of the cooler shell. The level sensor consists of a small electric resistance heater and 3 thermistors wired in series, positioned at different heights inside the body of the well. The heater is designed so that the thermistors read ap­proximately 200 F (93.3 C) in dry air.Astherefrigerantlevel rises (falls) in the cooler, the resistance of the closest ther­mistor(s) will increase (decrease) as it is cooled by the rising liquid refrigerant (heated by the heater). This large resis­tance difference allows the control to accurately maintain a specified level.
The level sensor monitors the refrigerant liquid level in the cooler and sends this information to the PSIO-1. At ini­tial start-up, the EXV position is at zero.After that, the micro­processor keeps accurate track of the valve position in order to use this information as input for the other control func­tions. The processor does this by initializing the EXVs at start-up. The processor sends out enough closing pulses to the valve to move it from fully open to fully closed, then resets the position counter to zero. From this point on, until the next initialization, the processor counts the total number of open and closed steps it has sent to each valve.
3
ECONOMIZER OPERATION — Economizers are factory installed on 30GX105-265 units and 30HXA,C161-271 units. All other sizes use standard EXVs. The economizer im­proves both the chiller capacity and efficiency as well as pro­viding compressor motor cooling. Inside the economizer are both a linear stepper motor (same as standard EXV motor) and a float valve. The stepper motor is controlled by the pro­cessor to maintain the desired liquid level in the cooler (as is done for chillers without economizers). The float valve maintains a liquid level in the bottom of the economizer.
Liquid refrigerant is supplied from the condenser through the end to the bottom of the economizer.Abubbler tube sup­plies a small amount of discharge gas to ensure that the float will be able to workproperly. As the refrigerantpassesthrough the EXD, its pressure is reduced to an intermediate level of about 75 psig (517 kPag). This pressure is maintained inside the economizer shell. Next, the refrigerant flows through the float valve where its pressure is further reduced to slightly above the pressure in the cooler.
The increase in performance is achieved when some of the refrigerant passing through the EXD flashes to vapor, further subcooling the liquid that is maintained at the bottom of the economizer. This increase in subcooling provides ad­ditional capacity. Also, since the additional power required to accomplish this is minimal, the efficiency of the machine improves. The vapor that flashes rises to the top of the econo­mizer where it passes to the compressor and is used to pro­vide motor cooling. After passing over the motor windings, the refrigerant reenters the cycle at an intermediate port in the compression cycle.
Oil Pumps — The 30GX/HX screw chillers use one ex-
ternally mounted prelubricating oil pump per circuit. This pump is operated as part of the start-up sequence. On 30GX units, the pumps are mounted to the base rails on the oil sepa­rator side of the unit. The pumps are mounted to a bracket on the condensers of 30HXC units and to the oil separator on 30HXA units.
When a circuit is required to start, the controls energize the oil pump first and read the oil pressure transducer read­ing. The pump is operated for a period of 20 seconds, after which the oil solenoid is energized to open the oil inlet valve at the compressor. The control again reads the pressure from the oil pressure transducer. If the pump has built up suffi­cient oil pressure, the compressor is allowed to start.
Once the compressor has started, the oil pump is turned off within 10 seconds and is not used again until the next start-up. If the pump is not able to build up enough oil pres­sure, the pump is turned off. Within 3 seconds, the pump is re-energized and makes one additional attempt to build oil pressure. The control generates an alarm if the second at­tempt fails.
Motor Cooling — Compressor motor winding tempera-
tures are controlled to a set point of 200 F (93.3 C). The control accomplishes this by cycling the motor cooling olenoid valve to allow liquid refrigerant to flow across the motor windings as needed. On units equipped with econo­mizers, flash gas leaves the top of the economizer and con­tinually flows to the motor windings. All refrigerant used for motor cooling re-enters the rotors through a port located mid­way along the compression cycle and is compressed to dis­charge pressure.
Back Pressure Valve (30GX and 30HXA only) —
This valve is located on the oil separator outlet on 30GX units and mounted on the oil separator shell of 30HXAunits. The valve’s function is to ensure that there is sufficient sys­tem differential pressure to allow for oil to be driven back to the compressor. A small copper line (economizer pressure) is connected to the top of the valve, which contains an in­ternal spring that closes a piston if the pressure in the oil separator is not at least 15 psig greater than the economizer pressure.
Sensors — The 30GX,HX control system (based on the
Flotronic™ II chiller control system)gathersinformationfrom sensors to control the operation of the chiller. The units use up to 9 standard pressure transducers, 7 standard thermistors (including 3 motor temperature thermistors), and 2liquidlevel thermistors to monitor and control system operation. The sen­sors are listed in Table 2.
Compressor Protection Module (CPM) — Each
compressor has its own CPM. The CPM provides the fol­lowing functions:
• compressor main contactor control
• Wye-Delta contactor transition
• compressor ground current protection
• motor temperature reading
• high-pressure protection
• reverse rotation protection
• voltage imbalance protection
• current imbalance protection
• compressor oil solenoid control
• motor cooling solenoid control
• sensor bus communications
• starting and running overcurrent protection
The CPM has the following 4 output relays and 4 inputs:
OUTPUTS:
• compressor contactor
• compressor oil solenoid
• compressor motor cooling solenoid
• Wye-Delta transition relay INPUTS:
• motor temperature
• three-phase voltage
• three-phase current
• high-pressure switch
Adiagram of the CPM board is shown in Fig. 1. There are line voltage inputs at L1, L2, and L3. Below these inputs are the current toroid inputs at Plug 1. Below Plug 1 are the 3 COMM3 communication terminals. In the lower left corner of the board are the inputs for motor winding temperature. The address DIP (dual-in-line package) switch and com­pressor must-trip amps header are factory set. For compres­sor A1, switches 2 and 4 should be set. For compressor A2 (30HXA,C206-271AND 30GX205-265), switches 2, 3, and 4 should be set. For compressor B1, switches 1 and 4 should be set.
T overifypropermusttripampsheaderconfiguration,press
and use the up arrow key on the HSIO to locate the
must trip amp values. Press the reset button on the HSIO/ fuse panel to update these values. See Appendix A. If the values do not match those in Appendix A, verify with Ap­pendix D that the configuration headers have been properly punched out.
4
Table 2 — Thermistor and Transducer Locations
THERMISTORS
Sensor Description Location Connection Terminals
T1 Cooler Leaving Fluid Temp Cooler Head Leaving Fluid Side PSIO-2, J7 pins 2,3 T2 Cooler Entering Fluid Temp Cooler Head Entering Fluid Side PSIO-2, J7 pins 5,6 Motor Temp A1 Motor Temperature A1 Compressor A1 Junction Box CPM-A1, T terminals Motor Temp A2* Motor Temperature A2 Compressor A2 Junction Box CPM-A2, T terminals Motor Temp B1 Motor Temperature B1 Compressor B1 Junction Box CPM-B1, T terminals T5 Discharge Gas TempA Top of Condenser Circuit A (30HXC Only) PSIO-2, J7 pins 8,9
Top of Oil Separator Circuit A (All Other Units)
T6 Discharge Gas Temp B Top of Condenser Circuit B (30HXC Only) PSIO-2, J7 pins 11,12
Top of Oil Separator Circuit B (All Other Units)
LL-A (T3) Liquid Level Circuit A Top of Cooler Circuit A PSIO-1, J7 pins 5,6 LL-B (T4) Liquid Level Circuit B Top of Cooler Circuit B PSIO-1, J7 pins 8,9 T7 (optional)† Outdoor Air Thermistor Outside Air Stream PSIO-2, J7 pins 20,21 STP (optional)† Space Temperature Conditioned Space PSIO-2, J7 pins 23,24 T8 (optional)† Condenser Entering Water Temp Condenser Entering Fluid Line PSIO-2, J7 pins 14,15 T9 (optional)† Condenser Leaving Water Temp Condenser Leaving Fluid Line PSIO-2, J7 pins 17,18
PRESSURE TRANSDUCERS
Sensor Description Location Connection Terminals DPT-A Discharge Pressure Circuit A Top of Condenser Circuit A (30HXC Only) PSIO-1, J7 pin 22
Top of Oil Separator Circuit A (All Other Units)
SPT-A Suction Pressure Circuit A Top of Cooler Circuit A PSIO-1, J7 pin 19 EPT-A Economizer Pressure Circuit A Economizer Line Entering Comp A PSIO-1, J7 pin 10 OPT-A1 Oil Pressure Compressor A1 Compressor A1 Oil Connection PSIO-1, J7 pin 25 OPT-A2* Oil Pressure Compressor A2 Compressor A2 Oil Connection PSIO-1, J7 Pin 1
DPT-B Discharge Pressure Circuit B Top of Condenser Circuit B (30HXC Only) PSIO-1, J7 pin 16
Top of Oil Separator Circuit B (All Other Units)
SPT-B Suction Pressure Circuit B Top of Cooler Circuit B PSIO-1, J7 pin 31 EPT-B Economizer Pressure Circuit B Economizer Line Entering Comp B PSIO-1, J7 pin 13 OPT-B Oil Pressure Compressor B Compressor B1 Oil Connection PSIO-1, J7 pin 28
*30HX206-271 only.
†Sensors are available as accessories for field installation.
The CPM communicates on the COMM3 communication bus to the PSIO-1 module. Proper operation of theCPMboard can be verified by observing the 3 LEDs (light-emitting di­odes) located on the board. The top LED is red and blinks at a rate of once every 1 to 2 seconds. This indicates that the module is powered and operating correctly.ThemiddleLED is yellow and blinks when there is an automatic reset alarm condition. The yellow LED remains on and does not blink for manual reset alarm conditions. The bottom LED is green and blinks when the module is satisfactorily communicating with the PSIO-1 module. The CPM communicates the status of its inputs and outputs, and reports 18 different alarm con­ditions to the PSIO-1. The alarms are listed in Table 3.
The CPM module has many features that are specifi­cally designed to protect the compressor, including re­verse rotation protection. Do not attempt to bypass or alter any of the factory wiring. Any compressor opera­tion in the reverse direction will result in a compressor failure that will require compressor replacement.
The PSIO-1 will generate an alert when it receives an alarm input from the CPM. The alert will be generated in a y.xx format, where ‘‘y’’ refers to the compressor and ‘‘xx’’ to the alarm value in Table 3 (decimal point removed). For ex­ample, the HSIO might displayAlarm 1.70 for a voltage phase reversal occurring on compressor A1. Similarly, the display would read 5.85 for a motor overtemperature condition on compressor B1.AlertsforcompressorsA2 and B2 (if present) would be generated as ‘‘2.xx’’and ‘‘6.xx,’’respectively. Alarm codes 3 and 4 would not be used. Ending zeros are not displayed.
The high-pressure switch is wired in series with the relay coils of the 4 relays on the CPM. If this switch opens during
operation, all relays on the CPM are deenergized and the compressor is stopped. The failure is reported to the PSIO-1 and the processor module locks off the compressor from re­starting until the alarm is manually reset.
Table 3 — Compressor Protection Module
Feedback Codes
ALARM CONDITION VALUE
High Pressure Switch Trip 1.0 No Motor Current 2.0 Current Imbalance Alarm 10% 2.5 Current Imbalance Warning 10% 2.7 Current Imbalance 18% 3.0 Single Phase Current Loss 3.5 High Motor Current 4.0 Ground Fault 5.0 Voltage Imbalance Alarm 3% 5.5 Voltage Imbalance Warning 3% 5.7 Voltage Imbalance 7% 6.0 Voltage Phase Reversal 7.0 Contactor Failure 7.5 Current Phase Reversal 8.0 Motor Overtemperature 8.5 Open Thermistor 9.0 Configuration Header Fault 9.5 Shorted Thermistor 10.0 No Error 0
Wye-Delta vs Across-the-line (XL) Starting Option —
All 30GX,HX chillers operating at voltages of 208/230-3-60 or 230-3-50 (5 or 8 at Position 12 in model number) are supplied with factory installed Wye-Deltastart­ers. All other voltage options can be ordered with either Wye-Delta or XL starting options. The XL starting method is the most cost effective and simply starts the compressor motor in a Delta configuration (the motors are designed for continuous operation in this configuration) using a single con­tactor. See Fig. 2. This is the simplest starting method to use and is ideal where starting current does not require limiting.
5
Where current limitations exist, the Wye-Deltaoptionmay be used. See Fig. 3. This option uses a factory-installed starter assembly for each compressor, which consists of 3 contac­tors labelled 1M, 2M, and S. As the compressor is started, the CPM module energizes contactors 1M and S, which con­nects and energizes the motor windings in a Wye configu­ration. The starting current required will be approximately 60% less than that required for an XL start due to the higher impedance of the motor windings when Wye connected. The compressor will attain about 100% of its normal operating speed (approximately 3 to 6 seconds) before the CPM mod­ule deenergizes the S contactor and energizes the 2M con­tactor, switching the compressor windings to a Delta wiring configuration. The S and 2M contactors in the starter assem­bly are both mechanically and electrically interlocked so that they will not both be energized at the same time.
Do not alter the factory-installed power wiring from the control box terminal block to the compressor junction block.
Doing so will cause permanent damage to the compressor and will require that the compressor be replaced.
Capacity Control — The control system cycles com-
pressors, loaders, and minimum load control valves to main­tain the user-configured leaving chilled fluid temperature set point. Entering fluid temperature is used by the microproces­sor to determine the temperature drop across the cooler and is used in determining the optimum time to add or subtract capacity stages. The chilled fluid temperature set point can be automatically reset by the return temperature reset or space and outdoor-air temperature reset features. It can also be re­set from an external 4 to 20 mA signal (requires field­supplied 500-ohm,1⁄2watt resistor), or from a network signal.
The capacity routine runs every 30 seconds. The routine attempts to maintain the Control Point at the desired set point. Each time it runs, the control reads the entering and leaving fluid temperatures. The control determines the rate at which conditions are changing and calculates 2 variables based on these conditions. Next, a capacity ratio (Load/Unload Fac-
tor under ) is calculated using the 2 variables to determine whether or not to make any changes to the current stages of capacity. This ratio value ranges from − 100 to + 100%. If the next stage of capacity is a compressor, the
control starts (stops) a compressor when the ratio reaches + 100% (− 100%). If the next stage of capacity is a loader, the control energizes (deenergizes) a loader when the ratio reaches + 60% (− 60%). Loaders are allowed to cycle faster than compressors, to minimize the number of starts and stops on each compressor.Adelay of 90 seconds occurs after each capacity step change.
MINUTES LEFT FOR START — This value is displayed in the Status subfunction and represents the amount of time to elapse before the unit is started. This value can be zero with­out the machine running in many situations. This can in­clude being unoccupied, LOR switch in the OFF position, CCN not allowing unit to start, Demand Limit in effect, no call for cooling due to no load, and alarm or alert conditions present. If the machine should be running and none of the above are true, a minimum off time may be in effect. The machine should start normally once the time limit has expired.
MINUTES OFF TIME ( ) — This user config­urable time period is used by the control to determine how
long unit operation is delayed after power is applied/ restored to the unit. It is also used to delay compressor re­starts after the unit has shut off its lowest stage of capacity. Typically, this time period is configured when multiple ma­chines are located on a single site. For example, this gives the user the ability to prevent all the units from restarting at once after a power failure. A value of zero for this variable does not mean that the unit should be running.
LOADING SEQUENCE — The 30GX,HX chiller effi­ciency is greatest at full load. Therefore, the following se­quence list applies to capacity control.
1. Thenextcompressor is not started until all others are run­ning at 100%.
2. The second unloading stage is only used during initial capacity staging of the unit at start-up.
3. Whenever a compressor is started in a circuit, the loaders in the circuit are deenergized for 15 seconds before the compressor is started. The loaders are energized 90 sec­onds after the compressor is started.
L1 L2
L3
CURRENT TOROID INPUT PLUG
1
2 3
T T
TEMPERATURE
ADDRESS DIP SWITCH
COMM3
24/115/230 VAC
INPUTS/OUTPUTS
COMPRESSOR PROTECTION MODULE (CPM)
COMPRESSOR MUST TRIP AMPS HEADER
1 2
RED LED
YELLOW LED
GREEN LED
MOTOR INPUT
PUSH THIS SIDE OF SWITCH DOWN TO SET ADDRESS
1234
ROCKER DOWN
1
0
2
3
4
5
Fig. 1 — Compressor Protection Module
LED — Light-Emitting Diode
NOTES:
1. The red LED blinks continuously when the module is operating properly.
2. The yellowLEDblinks during automaticreset alarm, and is continuously lit when the manual reset alarm is active.
3. The green LID blinks continuously when communi­cating properly with PSIO-1.
6
CLOSE CONTROL( ) — When configured for Close Control, the control is allowed to use any loading/capacity
control devices required to maintain better leaving fluid tem­perature regulation.Allstagesofunloadingareavailable.See Appendix B for an example.
LEAD/LAG DETERMINATION ( ) — This is a con­figurable choice and is factory set to be automatic. The value
can be changed to Circuit A or Circuit B leading, as desired. Set at automatic, the control will sum the current number of logged circuit starts and one-quarter (Version 3.0 and later) of the current operating hours for each circuit. The circuit with the lowest sum is started first. Changes to which circuit is the lead circuit and which is the lag are made when shut­ting off compressors.
On 30HX206-271 and 30GX205-265 units set for staged loading, the control fully loads the lead circuit before start­ing the lag circuit and unloads the lag circuit first. When these units are set for equal loading, the control maintains nearly equal capacities in each circuit when the chiller is loading and unloading.
CAPACITY SEQUENCE DETERMINATION ( ) — This is configurable as equal circuit loading or staged circuit
loading with the default set at staged. The control deter­mines the order in which the steps of capacity for each cir­cuit are changed. This control choice does NOT have any impact on machines with only 2 compressors.
MINIMUM LOAD VALVE ( ) — When this option is installed and configured, the first stage of capacity is ini­tiated by energizing the Minimum Load valve relay.The con­trol energizes loaders as needed thereafter. Similarly, the Minimum Load valve relay will be energized forthelaststage of capacity to be used before the circuit is shut down.
CAPACITY CONTROLOVERRIDES—The following over­rides will modify the normal operation of the routine.
Deadband Multiplier — The user configurableDeadbandMul­tiplier ( ) has a default value of 1.0. The range is from
1.0 to 4.0. When set to other than 1.0, this factor is applied to the capacity Load/Unload Factor. The larger this value is set, the longer the control will delay between adding or re­moving stages of capacity. Figure 4 shows how compressor starts can be reduced over time if the leaving water tempera­ture is allowed to drift a larger amount above and below the set point. This value should be set in the range of 3.0 to 4.0 for systems with small loop volumes.
First Stage Override — If the current capacity stage is zero, the control will modify the routine with a 1.2 factor on add­ing the first stage to reduce cycling. This factor is also ap­plied when the control is attempting to remove the last stage of capacity.
L1
L2
L3
T1
T1
T3
3
2
1
1
2
3
4
6
5
COMPRESSOR JUNCTION BOX
JUMPER BARS
COMPRESSOR CONTACTOR
1
2
3
21
22
23
TERMINAL BLOCK
Fig. 2 — Across-the-Line (XL) Compressor Wiring
1
2
3
4
5
6
1
2
3
T1
T1
T1
T2
T2
T2
T3
T3
T3
S
2M
1M
L3
L3
L3
L2
L2
L2
L1
L1
L1
1
2
3
22
21
23
TERMINAL BLOCK
COMPRESSOR STARTER ASSEMBLY
COMPRESSOR JUNCTION BOX
21
22
23
4
6
5
Fig.3—Wye-Delta Compressor Wiring
7
Slow Change Override —The control prevents the capacity stages from being changed when the leaving fluid tempera­ture is close to the set point (within an adjustable deadband) and moving towards the set point.
Ramp Loading ( ) —Limitstherate of change of leav­ing fluid temperature. If the unit is in a cooling mode and
configured for Ramp Loading, the control makes 2 compari­sons before deciding to change stages of capacity. The con­trol calculates a temperature difference between the control point and leaving fluid temperature. If the differenceisgreater than 4° F (2.2° C) and the rate of change (°F or °Cperminute) is less than the configured Cooling Ramp Loading value
( ), the control does not allow any changes to the current stage of capacity.
Low Entering Fluid Temperature Unloading — When the entering fluid temperature is below the control point, the con­trol will attempt to remove 25% of the current stages being used. If exactly 25% cannot be removed, the control re­moves an amount greater than 25%, but no more than nec­essary. The lowest stage will not be removed.
Low Discharge Superheat — If a circuit’s discharge super­heat is less than 15° F (8.3° C), the control does not increase the current capacity stage and the EXD is not opened any further. If the discharge superheat is less than 10° F (5.6° C) and decreasing, the EXD is closed 50 steps every 10 seconds. If the discharge superheat is less than 5° F (2.8° C) and decreasing, the circuit is unloaded every 30 seconds until the superheat is greater than 5° F (2.8° C). The final capacity stage is not unloaded unless an alarm condition exists. This override is ignored for the first 3 minutes after a compressor is started.
Low Saturated Suction Temperature — To avoid freezing the cooler,thecontrol will compare the circuit Saturated Suc­tion temperature with a predetermined freeze point. For wa­ter circuits, the freeze point is 28 F (−2.2 C). For brine cir­cuits, the freeze point is 8° F (4.4° C) below the cooling set point (lower of 2 cooling set points for dual configuration). If the saturated suction temperature is below the freeze point, the unit capacity is not allowed to increase. For brine cir-
cuits, the freeze point can be entered by pressing and scrolling 12 items down. The control will use the Brine
Freeze Point value less 6°F (3.3°C) as the freeze point to compare with the Saturated Suction temperature. The de­fault for the Brine Freeze Point is 34 F (1.1 C) which means the control will use 28 F (−2.2 C) as the freeze point. This value is adjustable from −15 F to 34 F (−26.1 to 1.1 C). For
water (brine) circuits, if the Saturated Suction temperature falls below 34 F (1.1 C) (the Brine Freeze Point), the unit capacity will not increase. If the Saturated Suction tempera­ture falls below 28 F (−2.2 C), the Brine Freeze Point minus 6° F (3.3° C), for 90 seconds, all loaders in the circuit are turned off. If this condition continues for a total of 3 min­utes, the circuit will shut down.
High Condensing Temperature Unloading — Every 10 sec­onds the control checks for the conditions below. Loaders will be cycled as needed to control the saturated condensing temperature below the configured maximum condensing tem­perature. Configured maximums are 154 F (67.8 C) for30GX, 152 F (66.7 C) for 30HXA, and 122 F (50 C) for 30HXC units. If a circuit’s saturated condensing temperature is more than 12° F (6.7 C) below the maximum condensing tem­perature, the circuit capacity is not allowed to increase. If the saturated condensing temperature is more than 2° F (1.1° C) above the maximum condensing temperature for 60 seconds, a loader is turned off. If the saturated condensing temperature rises to more than 5° F (2.8° C) above the maxi­mum condensing temperature during the 60 seconds, a loader is turned off immediately. If all the loaders were already off, the compressor is shut down and an alarm is generated.
MOP(Maximum Operating Pressure) Override —Thecon­trol monitors saturated condensing and suction temperature for each circuit as well as differential oil pressure. Based on a configurable maximum operating set point (saturated suction temperature), set maximum condensing tempera­ture, and minimum differential oil pressure, the control may reduce the number of capacity stages being used and/or may lower the EXD position when system pressures approach the set parameters.
Head Pressure Control
GENERAL — The microprocessor controls the condenser fans (30GX) or analog water valve (30HXC) to maintain the saturated condensing temperature to a configurable set point. The fans are staged or speed varied (30GX) or water valve controlled (30HX) based on each circuit’s saturated con­densing temperature and compressorstatus.Water cooled units (30HXC) operating at less than 70 F (21.1 C) for entering condenser water require the use of head pressure control.
The chiller must be field configured for the options shown
in Table 4. Fan stage settings are shown in Table 5. AIR COOLED UNITS (30GX) — See Fig. 5 for condenser
fan locations.
47 46 45 44
43 42 41
0 200 400 600 800 1000
TIME (SECONDS)
2 STARTS
3 STARTS
DEADBAND EXAMPLE
LWT (F)
MODIFIED DEADBAND
STANDARD DEADBAND
8
7
6
5
LWT (C)
LEGEND
LWT — Leaving Water
Temperature
Fig. 4 — Deadband Multiplier
8
No Motormastert Control — The fans are controlled based on Saturated Condensing Temperature. The first fan stage for each circuit is turnedonwheneverthecompressoristurned on.Afan stage is added when the Saturated Condensing Tem­perature (SCT) exceeds the Head Pressure Set Point. The Head Pressure Set Point is configurable in the Set Point sub­function. The default is 113 F (45 C). Once a fan stage has been added, the software temporarily modifies the head pres­sure set point by adding 15° F (8.3° C) for 35 seconds. A fan stage will be removed when the Saturated Condensing Temperature has been less than the Head Pressure Set Point minus 35 F (19.4 C) for 2 minutes.Thecontrolusesthehigher of the 2 Saturated Condensing Temperature values for 30GX080-150 and 160 units. For the 30GX151 and 161-265 units, each circuit’s fan stages are independently controlled based on the circuit Saturated Condensing Temperature. Refer to Table 6 for condenser fan control information. See Fig. 6A.
With Motormaster Control — For low-ambient operation, the lead fan in each circuit can be equipped with the optional or accessory Motormaster III head pressure controller. This controller can be used in one of 2 ways. If factory installed, the controller will be configured for 4 to 20 mA control. With the Motormaster III option enabled, the PSIO-1 module cal­culates the required output based on Saturated Condensing temperature, Head Pressure set point, and a PID (propor­tional integral derivative) loop calculation. This 4 to
20 mA output is driven through the PSIO-2 module. To ob­tain this accessory for field installation, order by part num­ber 30GX-900---012forasinglecontroller package (30GX080­150 and 160). Order part number 30GX-900---014 for a dual controller package (30GX151 and 161-265). These packages contain all the hardware required to install the accessory. See Fig. 6B.
The control will use the higher of the 2 Saturated Con­densing Temperature values for 30GX080-150 and 160 units. For the 30GX151 and 161-265 units, each circuit’s fan stages are independently controlled based on the circuit Saturated Condensing Temperature. Refer to Table6 for condenser fan staging information.
WATER-COOLED UNITS (30HX) — The 30HX chillers can be configured to control direct or reverse-acting water valves that are controlled bya4to20mAsignal. A 2 to 10 VDC signal can be used by installing a 500-ohm resistor across the 2 output terminals of the 4 to 20 mA signal. This control scheme reads the saturated condensing temperature and uses a PID (proportional integral deriative) loop to control the head pressure. Proportional, Integral and Deriva­tive gain parameters for both the water and air cooled con­trols are adjustable and can be found in the Service subfunc­tion. Checkout and adjustment of the PID loop should only be performed by certified Carrier Comfort Network technicians.
Table 4 — Field Configured Chiller Options
CONFIGURATION OPTION DESCRIPTION HSIO LOCATION FACTORY CONFIGURED?
Fan Staging Select Air cooled staging method
Yes. See Table 5
Motormaster Control Select Applies to air cooled units only
Yes. 0 = None
Set to 1 to enable (Motormaster only)
Water Valve Type Applies to water cooled unit only
Yes. 0 = None
Setto1=4−20mA,2=0−10V,
3=20−4mA,4=10−0V
Table 5 — Fan Staging Settings for Air Cooled (30GX) Units
UNIT 30GX DESCRIPTION OPTION NUMBER
080-105
1st stage compressor status 2nd stage common control based on highest SCT
12
106-125
1st stage compressor status 2nd and 3rd stage common control based on highest SCT
14
136, 150, 160
1st stage compressor status 2nd through 4th stage common control based on highest SCT
16
151, 161, 175,
205, 225
1st stage each circuit, compressor status 2nd stage Circuit B independent 2nd and 3rd stage Circuit A independent
7
176
1st stage each circuit, compressor status 2nd and 3rd stage each circuit independent
3
206, 226, 250
1st stage each circuit, compressor status 2nd stage Circuit B independent 2nd, 3rd and 4th stage Circuit A independent
9
251, 265
1st stage each circuit, compressor status 2nd, 3rd and 4th stage each circuit independent
5
LEGEND
SCT — Saturated Condensing Temperature
9
ADJUSTING PID ROUTINES — The 30GX and 30HXC head pressure control routines use PID (proportional inte­gral derivative) loops to maintain a user-configurable head pressure set point. Gain default values are located in the Serv­ice function. See page 30. The current values can be read
under from the HSIO. The control calculates a new fan speed (30GX) or water valve position (30HXC) every
5 seconds based on these gain values and an error term equal to saturated condensing temperature minus head pressure set point. If the control routine is not responding fast enough to large changes (circuit starting, for example), increase the pro­portional term.
When the routine is making too great a change to valve position or fan speed, decrease the proportional term.To mini­mize hunting, keep the integral term positive and as low as possible. The default for the derivative term is zero. This valve is used to control ‘‘droop,’’which is common in master/ submaster control schemes. The value should not need to be changed.
Cooler and Condenser (30HXC) Pump Control —
The 30GX and 30HX chillers can be configured forcooler and condenser (30HXC) pump control. Inputs for a cooler flow switch or interlock and condenser flow switch are also provided.
COOLER PUMP CONTROL ( ) — The factory de­fault setting for cooler pump control is ‘‘Not Controlled.’’
All chillers are enabled at the factory for cooler pump in­terlock. See page 71 of Field Wiring section for wiring of cooler flow switch and/or cooler pump interlock contacts. Whether cooler pump control is enabled or not, the control generates an alarm if this input does not close within one minute after the unit switches to an occupied mode or the cooler pump is turned on. See Alarms and Alerts section, page 43 for a description of Alarms 53-55. If cooler pump control is enabled, the control waits one minute and checks the interlock or switch input before starting to determine if cooling is needed. The cooler pump is turned on when the chiller is in the occupied mode and turned offotherwise.The cooler pump is turned on in either of two override condi­tions: If the cooler freeze protection alarm has been gener­ated, the cooler pump is turned on if not already running. If a cooler heater is being used and has been on for more than 15 minutes during saturated suction freeze protection, the cooler pump is turned on.
1
2
3
4
CONTROL BOX END
5
6
7
8
9
10
CONTROL BOX END
4
2
1
3
CONTROL BOX END
13 5 7
24 6 8
CONTROL BOX END
4
6
1
3
5
2
5
CONTROL BOX END
7911
12
6810
4
2
3
1
CONTROL BOX END
1
3
5
7
2
4
6
8
CONTROL BOX END
14
12
10
13
11
9
1
3
5
7
2
4
6
8
9
11
12
10
Fig. 5 — 30GX Condenser Fan Locations
30GX080-105 30GX106-125
30GX151, 161, 175, 205, 225 30GX176
30GX206, 226, 250
30GX136, 150, 160
30GX251, 265
10
Table 6 — 30GX080-265 Condenser Fan Staging (PSIO-1 Controlled)
30GX UNIT SIZE FAN TYPE FAN CONTACTOR FANS CONTROLLED FAN RELAY NO.*
080-105
Standard
FC-1 1, 2 5 FC-2 3, 4 1
High Static
FC-1, 1A 1, 2 5 FC-2, 2A 3, 4 1
106-125
Standard
FC-1 1, 2 5 FC-2 3, 4 1 FC-3 5, 6 2
High Static
FC-1, 1A 1, 2 5 FC-2, 2A 3, 4 1 FC-3, 3A 5, 6 2
136, 150,
160
Standard
FC-1 1, 2 5 FC-2 3, 4 1 FC-3 5, 6 2 FC-4 7, 8 2
High Static
FC-1, 1A 1, 2 5 FC-2, 2A 3, 4 1 FC-3, 3A 5, 6 2 FC-4, 4A 7, 8 2
151, 161, 175
205, 225
Standard
FC-1 1, 2 Comp. B1 contactor† FC-2 3, 4 3 FC-3 5, 6 2 FC-4 7, 8 Comp. A1/A2 contactor† FC-5 9, 10 1
High Static
FC-1, 1A 1, 2 Comp. B1 contactor† FC-2, 2A 3, 4 3 FC-3, 3A 5, 6 2 FC-4, 4A 7, 8 Comp. A1/A2 contactor† FC-5, 5A 9, 10 1
176
Standard
FC-1 1, 2 Comp. B1 contactor† FC-2 3, 4 3 FC-3 5, 6 4 FC-4 7, 8 Comp. A1 contactor† FC-5 9, 10 1 FC-6 11, 12 2
High Static
FC-1, 1A 1, 2 Comp. B1 contactor† FC-2, 2A 3, 4 3 FC-3, 3A 5, 6 4 FC-4, 4A 7, 8 Comp. A1 contactor† FC-5, 5A 9, 10 1 FC-6, 6A 11, 12 2
206, 226, 250
Standard
FC-1 1, 2 Comp. B1 contactor† FC-2 3, 4 3 FC-3 5, 6 1 FC-4 7, 8 Comp. A1/A2 contactor† FC-5 9, 10 2 FC-6 11, 12 2
High Static
FC-1, 1A 1, 2 Comp. B1 contactor† FC-2, 2A 3, 4 3 FC-3, 3A 5, 6 1 FC-4, 4A 7, 8 Comp. A1/A2 contactor† FC-5, 5A 9, 10 2 FC-6, 6A 11, 12 2
251, 265
Standard
FC-1 2, 4 1 FC-2 6, 8 2 FC-3 1 Comp B1 contactor† FC-4 3 3 FC-5 5, 7 4 FC-6 9, 10 Comp. A1/A2 contactor† FC-7 11, 12 2 FC-8 13, 14 2
High Static
FC-1, 1A 2, 4 1 FC-2, 2A 6, 8 2
FC-3 1 Comp. B1 contactor†
FC-4 3 3 FC-5, 5A 5, 7 4 FC-6, 6A 9, 10 Comp. A1/A2 contactor† FC-7, 7A 11, 12 2 FC-8, 8A 13, 14 2
LEGEND
Comp. — Compressor FC Fan Contactor
*Fan Relay number displayed when using to test fans.
†Proper rotationof these fans tobe checked whencompressor(s) is running.SeeFig. 5 forcondenser fan locationswhen viewing
from the control box end.
11
CONDENSER PUMP CONTROL ( ) — Factory de­faults for both condenser pump control and condenser flow
switch are set to ‘‘Not Controlled’’and ‘‘Disabled,’’ respec­tively. The condenser pump can be controlled in one of two ways: In the first method, the pump can be controlled like the cooler pump — it is turned on whenever the machine is in the on state and turned off otherwise (set to Type 1 using
the Service function). The second method of control is to turn the pump on when the first compressor is started and off when the last compressor is turned off (set to Type 2 using the Service function). With the flow switched enabled, the control checks the status of the input one minute after start­ing the pump. An alarm is generated if the flow switch input is not closed.
READ CIRCUIT SATURATED CONDENSING TEMPERATURE AND CURRENT FAN STAGE
IS SCT GREATER THAN HEAD PRESSURE SET POINT?
INCREASE CURRENT FAN STAGE BY ONE
ADD 15° F TO HEAD PRESSURE SET POINT FOR NEXT 35 SECONDS
DECREASE CURRENT FAN STAGE BY ONE
HAS SCT BEEN 35° F LESS THAN HEAD PRESSURE SET POINT 2 MINUTES?
NO
NO
YES
YES
LEGEND
SCT — Saturated Condensing Temperature
Fig. 6A — 30GX Head Pressure Control Without MotormasterT III Control
30GX UNITS — MOTORMASTER III CONTROL NOT INSTALLED
30GX UNITS — MOTORMASTER III CONTROL INSTALLED
DECREASE CURRENT FAN STAGE BY ONE
NO
NO
YES
IS SCT GREATER THAN HEAD PRESSURE SET POINT PLUS 15F?
INCREASE CURRENT FAN STAGE BY ONE
YES
READ CIRCUIT SATURATED CONDENSING TEMPERATURE AND CURRENT FAN STAGE
NO
INCREASE CURRENT FAN STAGE BY ONE
YES
CALCULATE NEW PID VALUE. DOSE OUTPUT REQUIRE MORE FANS?
OUTPUT NEW mA SIGNAL TO CONTROLLER
DOES PID OUTPUT REQUIRE LESS FANS?
LEGEND
PID — Proportional Integral Derivative SCT — Saturated Condensing Temperature
Fig. 6B — 30GX Head Pressure Control With Motormaster III Control
12
Cooler Heater Control — Accessory cooler heaters
can be ordered for the 30GX chillers. If installed and en­abled, these heaters are turned on only when the machine is in the off state and the chiller is in a saturated suction tem­perature freeze condition.
Keypad and Display Module (Also Called HSIO-II) —
This module allows the operator to commu­nicate with the processor. It is used to enter configurations and set points and to read data, perform tests, and set sched­ules. The device consists of a keypad with 7 function keys, 5 operative keys, 12 numeric keys (0 to 9, •, and -), and a 2-line, 24-character alphanumeric liquid crystal display. See Fig. 7.
ACCESSING FUNCTIONS AND SUBFUNCTIONS — Table 7 shows a brief description of the keypad buttons. Table 8A shows the 6 functions (identified by name) and the subfunctions (identified by number). Table 8B shows the 6 functions (identified by name) and the subfunctions (iden­tified by number) when using the optional LID-2B control­ler. Table 9 shows a brief example on how to access subfunctions.
NOTE: It is not necessary to use the through every item in a subfunction. For example, if you wanted to read
the oil pressure for the A1 compressor, press , then press to go directly to A1 Oil Pressure. Use a simi-
lar procedure to view an item near the bottom of a subfunc­tion. To view the Circuit A Oil Switch status, press and . Use a similar procedure to view an item near
the bottom of a subfunction. Toview Condenser Pump Flow Switch status, press , , and . This proce-
dure is available in all functions except the TEST function. AUTOMATIC DEFAULT DISPLAY — When the keypad
has not been used for 10 minutes, the display automatically switches to the rotating automatic default display. This dis­play contains the 5 parts shown below.
Entering Fluid Temp
xx.x° F
Leaving Fluid Temp
xx.x° F
Percent Total Capacity
xxx.x%
Total Number of Alarms
xx
MODES : MODE_TBL Current active modes
All functions are made up of a group of subfunctions. To enter a subfunction, first press the subfunction number de­sired. Then press the function key in which the subfunction resides. To move within that subfunction, press the up or down arrow keys. Another subfunction may be entered at any time by pressing the subfunction number, then the func­tion key. Depending on system type and configuration, all displays may not be shown.
Table 7 — Keypad and Display Module Usage
FUNCTION
KEYS
USE
STATUS — For displaying diagnostic codes and current operating information about the machine.
HISTORY — For displaying run time, cycles, and previous alarms.
SERVICE — For entering specific unit configuration information and enabling manual control function.
SCHEDULE — For entering occupied/unoccupied schedules for unit operation.
ALGORITHM — Not used. SET POINT — For entering operating set points
and day/time information. TEST — For testing operating of the analog and
discrete outputs.
OPERATIVE
KEYS
USE
EXPAND — For displaying a non-abbreviated expansion of the display.
CLEAR — For clearing the screen of all displays. UP ARROW — For returning to previous display
position. DOWN ARROW — For advancing to next display
position. ENTER — For entering data.
CLEAR
ENTER
1
2
3
4
5
6
7
8
9
0
.
-
STAT
SET
SCHD
EXPN EDIT
SRVC
HIST
ALGO
TEST ALRM
TWENTY-FOUR CHARACTER TWO-LINE LCD DISPLAY
LEGEND
LCD — Liquid Crystal Display
Fig. 7 — Keypad and Display Module
13
Table 8A — HSIO Functions and Subfunctions
SUBFUNCTION
NO.
FUNCTIONS
Status
Test Schedule Service History Set Point
1
Alarm Display
Circuit A Discrete Outputs
Ice Build Occupancy Schedule
Factory Configuration
Operating Hours Set Points
2
General Parameters Display
Circuit B Discrete Outputs
Local/Normal Occupancy Schedule
Options Configuration 1
Alarm History English/Metric
3
Circuit A Analog Values
Unit Discrete Outputs
Remote CCN Occupancy Schedule
Options Configuration 2
Bus Address
4
Circuit A Discrete Inputs/ Outputs Table
Valves and MotormasterT Control
Holiday 01 Configuration
Reset/Demand Limit Configuration
Time/Date
Configuration
5
Circuit B Analog Values
Holiday 02
Configuration
Machine Configuration Codes
CCN
Enable/Disable
6
Circuit B Discrete Inputs/ Outputs Table
Holiday 03
Configuration
———
7
Unit Analog Parameters
Holiday 04
Configuration
Transducer Calibration
——
8
Miscellaneous Inputs/Outputs
Holiday 05
Configuration
Manual Control
9
Operating Modes Holiday 06
Configuration
Master/Slave Configuration
——
10
Capacity Control Holiday 07
Configuration
———
11
Dual Chiller Holiday 08
Configuration*
———
*Subfunctions through are for configuring Holidays 09 through 30.
14
Table 8B — Functions and Subfunctions Cross-Reference for the Optional LID-2B Controller
The optional LID-2B controller cross reference table be­low can be used as a guide to access the same information outlined in the HSIO functions and subfunctions table (see Table 8A). For example, in Table 8A, the alarm history is accessed through the HSIO by pressing 2 and the History button on the keypad (see Table 7). The LID-2B cross
reference table lists the menu item from the LID-2B which contains the alarm history information. In another example, from Table 8A, pressing 3 and the Status button on the HSIO keypad will access the circuit A analog values. In the table below, the circuit A analog values are accessed by selecting STATUS CIRCA_AN from the appropriate LID-2B menu.
HSIO
SUBFUNCTION
NO.
HSIO FUNCTION KEY
Status
Test Schedule Service History Set Point
1
STATUS A_UNIT_1
SERVICE CONTROL TEST
SCHEDULE OCCPC012
SERVICE EQUIPMENT CONFIGURATION
SERVICE EQUIPMENT CONFIGURATION STRTHOUR
SETPOINT
2
STATUS A_UNIT_1
SERVICE CONTROL TEST
SCHEDULE OCCPC02S
SERVICE EQUIPMENT CONFIGURATION OPTIONS1
SERVICE ALARM HISTORY
SERVICE LID CONFIGURATION
3
STATUS CIRCA_AN
SERVICE CONTROL TEST
SCHEDULE OCCPC65S
SERVICE EQUIPMENT CONFIGURATION OPTIONS2
SERVICE CONTROLLER IDENTIFICATION
4
STATUS CIRA_DIO
SERVICE CONTROL TEST
SERVICE EQUIPMENT CONFIGURATION HOLIDAY,HOLDY_01
SERVICE EQUIPMENT CONFIGURATION RESETCON
SERVICE TIME AND DATE
5
STATUS CIRCB_AN
SERVICE EQUIPMENT CONFIGURATION HOLIDAY,HOLDY_02
SERVICE EQUIPMENT CONFIGURATION CONCODES
STATUS A_UNIT_1
6
STATUS CIRB_DIO
SERVICE EQUIPMENT CONFIGURATION HOLIDAY,HOLDY_03
———
7
STATUS UNIT_2
SERVICE EQUIPMENT CONFIGURATION HOLIDAY,HOLDY_04
SERVICE EQUIPMENT SERVICE CALIBRTE
——
8
STATUS UNIT_3
SERVICE EQUIPMENT CONFIGURATION HOLIDAY,HOLDY_05
SERVICE EQUIPMENT SERVICE MAN_CTRL
——
9
STATUS MODE_TBL
SERVICE EQUIPMENT CONFIGURATION HOLIDAY,HOLDY_06
SERVICE EQUIPMENT CONFIGURATION MSTR_SLV
——
10
SERVICE CONTROL ALGORITHM STATUS LOADFACT
SERVICE EQUIPMENT CONFIGURATION HOLIDAY,HOLDY_07
———
11
SERVICE CONTROL ALGORITHM STATUS LEADLAG
SERVICE EQUIPMENT CONFIGURATION HOLIDAY,HOLDY_08*
——
*Subfunctions through are for configuring Holidays 09 through 30, and are also found under Service, Equipment
Configuration.
NOTE: The optional LID-2B controller uses the same password (1111) as the HSIO.
15
Table 9 — Accessing Functions and Subfunctions
OPERATION KEYPAD ENTRY DISPLAY RESPONSE
To access a function, press subfunction no. and function name key. Display shows sub­function group.
Circuit A Discrete Outputs Loader A1
Relay is OFF
To move to other elements, scroll up or down using arrow keys.
Loader A2 Relay is OFF
Minimum Load Valve A Relay is OFF
Circuit A Oil Heater Relay is OFF
A1 Mtr. Cooling Solenoid Relay is OFF
A2 Mtr. Cooling Solenoid Relay is OFF
Circuit A Oil Pump Relay is OFF
Oil Solenoid A1 Relay is OFF
Oil Solenoid A2 Relay is OFF
When the last element in a subfunction has been displayed, the first element is repeated.
Loader A1 Relay is OFF
To move to next subfunction it is not necessary to use subfunction number. Press function name key to advance display through all subfunctions within a function and then back to the first.
Circuit B Discrete Outputs
Loader B1 Relay is OFF
Unit Discrete Outputs Valves and Motor Master
Circuit A Discrete Outputs
To move to another function, either depress function name key for desired function (display shows the first subfunction), or Access a specific sub­function by using the sub­function number and the function name key.
Alarms : xx Reset Alarms : 1 <ENTER>
CIR. A DISCRETE OUTPUTS
STATUS FUNCTION — This function shows the rotating display, current status of alarm and alert (diagnostic) codes, capacity stages, operating modes, chilled water set point, all measured system temperatures and pressures, analog inputs, and switch inputs. Refer to Table 10 for a complete descrip­tion of the function.
Alarms/Alerts — Alarms and alerts are messages that one or more faults have been detected. The alarms and alerts in­dicate failures that cause the unit to shut down, terminate an option (such as reset) or result in the use of a default value such as a set point. Refer to the Troubleshooting section for more information.
Up to 10 alarms/alerts can be stored at once. Toviewthem,
press . The control will display the current total number of alarms/alerts. Use the arrow keys to scroll through
the list. Press the key when needed to view the full description of an alarm or alert. Press to clear
all the alarms. See Table 11.
IMPORTANT: Do not clear the alarms without first reviewing the full list and investigating and correcting the cause of the alarms.
When an alarm or alert is stored in the display and the
machine automatically resets, the alarm/alert is deleted. Codes
for safeties which do not automatically reset are not deleted until the problem is corrected and the machine is reset. To clear manual reset alarms from the CPM modules, the reset button on the HSIO bracket must be pressed. Next, switch the LOR switch to OFF and back to Local or Remote position (default alarm clearing method). Press
and then to clear the alarm from the PSIO
if the default LOR reset function has been disabled. General Parameters — General operating parameters are
displayed including control mode, run status, CCN status, and the 5 most current alarms. Press to display these
and the other values as shown in Table 10. CircuitAand B Analog and Discrete Information —Circuit
A Analog Values can be viewed bypressing and scroll­ing down to see current system operating conditions such as
pressures and temperatures. Pressing will bring up Circuit A Discrete Inputs and Outputs. Scroll down to view
the On/Off status of the compressor(s), loaders, solenoids, and pumps. Oil switch and feedback inputs are also dis-
played. Press and to view the identical ana­log values and discrete inputs and outputs for Circuit B. See
Table 10 for a complete display.
16
Unit Analog Parameters and Temperature Reset — Press
and scroll down to display the unit entering and leav-
ing fluid temperatures as well as the temperature reset signal and calculated values.
Miscellaneous Inputs and Outputs — Pressing and scrolling down will reveal the On/Off status of the con-
denser fans (30GX only). Also found here are the Demand Limit settings, pump relay and switch status, and miscella­neous items such as Heat/Cool and Dual Set Point switch positions. See Table 10 for a complete list.
Modes —Theoperatingmodesaredisplayed to indicate the operating status of the unit at a given time. See Table 12 for a complete list of all modes.
To enter the MODES subfunction, press and use
the key to view all current modes of operation. See Table 13.
Capacity Control — Pressing , this subfunc­tion displays the load/unload factor, control point, and leav-
ing water temperature. Scrolling down will also reveal the liquid level sensor values in degrees format.
Dual Chiller — Pressing will access the dual chiller control status. This subfunction will display whether
or not the chiller is operating as a Master or Slave, any alarm conditions present for dual chiller control, and lead/lag in­formation for changeover. Dual chiller control is configured
under .
17
Table 10 — Status Function and Subfunction Directory
SUBFUNCTION KEYPAD ENTRY DISPLAY COMMENT
1 Alarms
Alarm : xx Reset Alarms: 1 <ENTER>
All current alarms are displayed Use as needed
2 General Parameters GENERAL PARAMETERS
Displays LOCAL ON/OFF or CCN ON/OFF
Force/clear value with HSIO or CCN device. Must be ON for CCN clock control.
Control Mode Run Status
Off/On Occupied ?
Yes/No CCN Enable
Off/On CCN Chiller Start/Stop
Start/Stop Alarm State
Normal/Alarm Current Alarm 1
x.xx Current Alarm 2
x.xx Current Alarm 3
x.xx Current Alarm 4
x.xx Current Alarm 5
x.xx Active Demand Limit
xxx.x% Percent Total Capacity
xxx.x% Water/Brine Setpoint
xx.x dF Control Point
xx.x dF Entering Fluid Temperature
xx.x dF Leaving Fluid Temperature
xx.x dF Emergency Stop
Emstop Minutes Left for Start
xx min Heat-Cool Status
Heat/Cool
3 Circuit A Analog Values
CIRCUIT A ANALOG VALUES
Percentage of total circuit capacity currently in use.
Percentage of Total Capacity value not in an alarm or fault condition.
Total Capacity xxx.x%
Available Capacity xxx.x%
Discharge Pressure xxx.x PSI
Suction Pressure xxx.x PSI
A1 Oil Pressure Diff. xxx.x PSI
A2 Oil Pressure Diff. xxx.x PSI
A1 Oil Pressure xxx.x PSI
A2 Oil Pressure xxx.x PSI
Discharge Gas Temperature xxx.x dF
A1 Motor Temperature xxx.x dF
A2 Motor Temperature xxx.x dF
See Legend on page 23.
18
Table 10 — Status Function and Subfunction Directory (cont)
SUBFUNCTION KEYPAD ENTRY DISPLAY COMMENT
3 Circuit A Analog Valves (cont)
SAT Condensing Temp xxx.x dF
Saturated Suction Temp xxx.x dF
EXV Percent Open xxx.x%
Motormaster Speed xxx.x%
Water Valve Position xxx.x%
Cooler Level Indicator x.xx
CPM A1 Feedback x.x Volts
See Table 3.
CPM A2 Feedback x.x Volts
See Table 3.
Circuit A Econ Pressure xxx.x PSI
4 Circuit A Discrete Inputs/Outputs
CIR. A DISCRETE OUTPUTS Compressor A1
Off/On Compressor A2
Off/On Loader A1
Off/On Loader A2
Off/On Minimum Load Valve A
Off/On Circuit A Oil Heater
Off/On A1 Mtr Cooling Solenoid
Off/On A2 Mtr Cooling Solenoid
Off/On Circuit A Oil Pump
Off/On Oil Solenoid A1
Off/On Oil Solenoid A2
Off/On CIR. A DISCRETE INPUTS
Circuit A Oil Switch Open/Close
Compressor A1 Feedback Off/On
Compressor A2 Feedback Off/On
5 Circuit B Analog Values
CIRCUIT B ANALOG VALUES
Percentage of total circuit capacity currently in use.
Percentage of Total Capacity value not in an alarm or fault condition.
Total Capacity xxx.x%
Available Capacity xxx.x%
Discharge Pressure xxx.x PSI
Suction Pressure xxx.x PSI
B1 Oil Pressure Diff. xxx.x PSI
B2 Oil Pressure Diff. xxx.x PSI
B1 Oil Pressure xxx.x PSI
B2 Oil Pressure xxx.x PSI
Discharge Gas Temperature xxx.x dF
19
Table 10 — Status Function and Subfunction Directory (cont)
SUBFUNCTION KEYPAD ENTRY DISPLAY COMMENT
5 Circut B Analog Valves (cont)
B1 Motor Temperature xxx.x dF
B2 Motor Temperature xxx.x dF
SAT Condensing Temp xxx.x dF
Saturated Suction Temp xxx.x dF
EXV Percent Open xxx.x%
Motormaster Speed xxx.x%
Water Valve Position xxx.x%
Cooler Level Indicator x.xx
CPM B1 Feedback x.x Volts
See Table 3.
CPM B2 Feedback x.x Volts
See Table 3.
Circuit B Econ Pressure xxx.x PSI
6 Circuit B Discrete Inputs/Outputs
CIR. B DISCRETE OUTPUTS Compressor B1
Off/On Compressor B2
Off/On Loader B1
Off/On Loader B2
Off/On Minimum Load Valve B
Off/On Circuit B Oil Heater
Off/On B1 Mtr Cooling Solenoid
Off/On B2 Mtr Cooling Solenoid
Off/On Circuit B Oil Pump
Off/On Oil Solenoid B1
Off/On Oil Solenoid B2
Off/On CIR. B DISCRETE INPUTS
Circuit B Oil Switch Open/Close
Compressor B1 Feedback Off/On
Compressor B2 Feedback Off/On
7 Unit Analog Parameters
UNIT ANALOG PARAMETERS Cooler Entering Fluid
xx.x dF Cooler Leaving Fluid
xx.x dF Condenser Entering Fluid
xx.x dF Condenser Leaving Fluid
xx.x dF Reclaim Entering Fluid
xx.x dF Reclaim Leaving Fluid
xx.x dF 5 Volt Supply
x.x Volts
See Legend on page 23.
20
Table 10 — Status Function and Subfunction Directory (cont)
SUBFUNCTION KEYPAD ENTRY DISPLAY COMMENT
7 Unit Analog Parameters (cont)
TEMPERATURE RESET 4-20 mA Reset Signal
xx.x mA Return Reset Signal
xx.x dF External Reset Signal
xx.x dF Outdoor Air Temp
xx.x dF Calculated Reset
xx.x dF
8 Misc. Inputs/Outputs
MISC INPUTS/OUTPUTS FAN_1
Off/On FAN_2
Off/On FAN_3
Off/On FAN_4
Off/On FAN_5
Off/On FAN_6
Off/On DEMAND LIMIT
4-20 mA Demand Signal xx.x mA
Demand Switch 1 Off/On
Demand Switch 2 Off/On
CCN Loadshed Signal Normal/Alarm
Max Allowable CAP xxx.x%
PUMPS Cooler Pump Relay
Off/On Cooler Pump Flow Switch
Off/On Condenser Pump Relay
Off/On Condenser Pump Flow Switch
Off/On MISCELLANEOUS
Ice Valve Off/On
Ice Build Complete Yes/No
Heat/Cool Switch Heat/Cool
Dual Set point Switch Off/On
Cooler Heater Off/On
Options Temperature 1 xx.x dF
Not Used
Options Temperature 2 xx.x dF
Not Used
9 Operating Modes
MODES :MODE_TBL mode name ON/OFF
Only active modes displayed LOCAL OFF Scroll with down arrow key to display CCN OFF
21
Table 10 — Status Function and Subfunction Directory (cont)
SUBFUNCTION KEYPAD ENTRY DISPLAY COMMENT
9 Operating Modes (cont)
CLOCK OFF LOCAL ON CCN ON CLOCK ON DUAL SP ACTIVE (1st SP) DUAL SP ACTIVE (2nd SP) TEMPERATURE RESET
ACTIVE DEMAND LIMIT ACTIVE
LOAD LIMIT ACTIVE LOW SOURCE TEMP PROTECT RAMP LOADING ACTIVE TIMED OVERRIDE ACTIVE LOW COOLER SUCTION TEMP WSM CONTROLLING SLOW CHANGE OVERRIDE OFF TO ON DELAYACTIVE FSM CONTROLLING 2 CHILLR LEAD LAG ACTIVE 2 CHILLR LL COMM FAILURE CIR A LOW DISCHG SUPERHT CIR B LOW DISCHG SUPERHT CIR A HIGH SDT CIR B HIGH SDT
10 Capacity Control
CAPACITY CONTROL Load/Unload Factor
xxx.x% Control Point
xx.x dF Leaving Water Temp
xx.x dF MISC. INDICATORS
Liquid Lvl Sensor Cir. A xx.x dF
Liquid Lvl Sensor Cir. B xx.x dF
22
Table 10 — Status Function and Subfunction Directory (cont)
SUBFUNCTION KEYPAD ENTRY DISPLAY COMMENT 11 Dual Chiller
DUAL CHILLER Unit Master / Slave
0/1/2
0 = Neither 1 = Slave 2 = Slave
Master / Slave Ctrl Active Yes/No
Lead Chiller 1/2
1 = Master 2 = Slave
Slave Chiller State 0/1/3/5/6
0 = Chiller OFF 1 = Valid Run State in CCN Mode 3 = Chiller in Local Mode 5 = Shutdown on Alarm 6 = Communications Failure
Slave Chiller Total Cap xxx.x%
Lead / Lag Changeover Yes if Lead / Lag Balance Enabled Master / Slave Error
1/2/3/4/5/6
1 = Master / Slave Have Same Address 2 = Master / Slave Communication Failure 3 = Chiller in Local Mode 4 = Slave Shutdown on Alarm(s) 5 = Master Configured for Heating 6 = No Slave Configured
LEGEND
CCN — Carrier Comfort Network CPM — Compressor Protection Module dF Degrees Fahrenheit EXV — Electronic Expansion Valve FSM — Flotronic™ System Manager LL Lead/Lag SAT — Saturated SDT — Saturated Discharge Temperature SP Set Point WSM — Water System Manager
Table 11 — Reading and Clearing Alarms
KEYPAD ENTRY DISPLAY COMMENT
Alarm: 02 Reset Alarms: 1 <ENTER>
Comp A1 Fail - 1.70 Volt Alarm : 15:12 04/15/96
Comp A1 Fail - 1.70 Volts Phase Reversal Alarm : 15:12 04/15/96
Compressor A1 Low Oil Pr Alarm : 10:34 04/15/96
Compressor A1 Low Oil Pressure Alarm : 10:34 04/15/96
Alarm: 02 Reset Alarms: 1 <ENTER>
Press Reset button first
Alarm: 00 Reset Alarms: 1 <ENTER>
Alarms reset and cleared
Entering Fluid Temp xx.x dF
Returns to rotating default display
Leaving Fluid Temp xx.x dF
Percent Total Capacity xxx.x%
Total Number of Alarms xx
MODES: MODE
TBL
List of All Current Modes
23
Table 12 — Operational and Mode Display Codes
CODE DESCRIPTION
LOCAL OFF Unit is off. LOCAL/OFF/REMOTE switch is
in OFF position or LOCAL/OFF/REMOTE switch is in REMOTE position and remote contacts are open.
CCN OFF Unit is off. LOCAL/OFF/REMOTE switch is
in LOCAL position and CCN control is enabled (Stop state) or CCN is enabled (Stop state) with LOR switch in REMOTE position and remote contacts closed.
CLOCK OFF Unit is off due to internal clock schedule.
LOR switch is in LOCAL position.
LOCAL ON Unit is on. LOR switch is in LOCAL position
and CCN is disabled or LOR switch is in REMOTE position with contacts closed and CCN is disabled.
CCN ON Unit is on due to CCN command. LOR
switch is in LOCAL position and CCN is enabled (Run state) or LOR switch is in REMOTE position with contacts closed and CCN is enabled (Run state)
CLOCK ON Unit is on due to internal clock schedule or
occupied override function. LOR switch is in LOCAL position.
DUAL SP ACTIVE (1st SP)
Dual set point is in effect. In this mode, unit continues to run in an occupied condition, and leaving fluid set point is automatically controlled to the CSP1 set point in the SET POINT function.
DUAL SP ACTIVE (2nd SP)
Dual set point is in effect. In this mode, unit continues to run in unoccupied condition, but leaving fluid set point is automatically increased to a higher level (CSP2 set point is in SET POINT function).
TEMPERATURE RESET ACTIVE
Temperature reset is in effect. In this mode, unit is using temperature reset to adjust leaving fluid set point upward, and unit is currently controlling to the modified set point. The set point can be modified based on return fluid, outdoor-air temperature, space temperature, or 4 to 20 mA signal.*
DEMAND LIMIT ACTIVE
Demand limit is in effect. This indicates that capacity of unit is being limited by demand limit control option. Because of this limitation, the unit may not be able to produce the desired leaving fluid temperature. Demand limit can be controlled by a switch or 4 to 20 mA signal.*
FSM CONTROLLING
Flotronic™ System Manager (FSM) is controlling the chiller.
RAMP LOADING ACTIVE
Ramp load (pulldown) limiting is in effect. In this mode, the rate at which leaving fluid temperature is dropped is limited to a predetermined value to prevent compressor overloading. See CRAMP set point in the SET function in (page 25). The pulldown limit can be modified, if desired, to any rate from
0.2° F to 2° F (0.1° to 1° C)/minute.
TIMED OVERRIDE ACTIVE
Timed override is in effect. This isa1to 4 hour temporary override of the pro­grammed schedule, forcing unit to occupied mode. Override can be implemented with unit under LOCAL/REMOTE or CCN control. Override expires after each use.
WSM CONTROLLING
Water System Manager is controlling the chiller.
SLOW CHANGE OVERRIDE
Slow change override is in effect. The leaving fluid temperature is close to and moving towards the control point.
CODE DESCRIPTION
OFF TO ON DELAY ACTIVE
Chiller is being held off by Minutes Off Time found by keying . Also, normal
operation of the chiller includes a minimum
1.5 minute delay after a capacity stage change has been made. This delay is adjustable from 1.5 to 6 minutes.
LOAD LIMIT ACTIVE
This function determines the maximum allowable capacity that can be running and is accomplished through the Flotronic System Manager. The unit may not be able to produce the desired leaving fluid temperature.
2 CHILLR LEAD LAG ACTIVE
Future Use.
2 CHILLR LL COMM FAILURE
Future Use.
CIRCUIT A LOW DISCHARGE SUPERHT
If the circuit discharge superheat is less than 15° F (8.3° C), the capacity control routine will not add any stages (to either circuit).
If the compressor has been running for at least 3 minutes, the EXV will not be opened any further. If the circuit discharge superheat is less than 10° F (5.6° C) and falling, the circuit EXV will be closed 50 steps every 10 seconds.
If the discharge superheat is less than 5° F (2.8° C) and falling, a circuit loader will be deenergized every 30 seconds. The final stage will not be unloaded unless an alarm condition is present.
CIRCUIT B LOW DISCHARGE SUPERHT
See description for Circuit A above.
CIRCUIT A HIGH SCT
If the circuit is running and the Saturated Condensing Temperature (SCT) is greater than the Maximum Condensing Temperature Set point (MCT_SP) minus 12° F (6.7° C), the control will not add any stages.
If the SCT is greater than the MCT_SP plus 5° F (2.8° C), the circuit will be unloaded and shut down if necessary. If the SCT is greater than the MCT_SP plus 2° F (1.1° C) for one minute, a loader will be deenergized.
If the SCT is greater than the MCT_SP minus 4° F (2.2° C), the control will compare the maximum operating pressure set point (MOP_SP) with the modified MOP_SP (MOP_CTRL).
If the MOP_CTRL is greater than the MOP_SP, the mode will be cleared. Otherwise the control will display the high SCT override mode. The capacity control routine will not add any stages. If the circuit is at its lowest capacity, this mode will be ignored.
CIRCUIT B HIGH SCT
See description for Circuit A above.
LEGEND
CCN Carrier Comfort Network CSP Cooling Set Point CRAMP — Cooling Ramp Loading EXV Electronic Expansion Valve LOR Local/Off/Remote SP Set Point WSM Water System Manager
*Afield-supplied500Ohm
1
⁄2W resistor must be installed across the
input terminals when usinga4to20mAsignal.
Table 13 — Reading Current Operating Modes
KEYPAD ENTRY DISPLAY
MODES :MODE_TBL CCN ON
DEMAND LIMIT ACTIVE
24
TEST FUNCTION — The test function operates the diag­nostic program. To initiate the test function, the LOCAL/ OFF/REMOTE switch must be in the OFF position.
To reach a particular test, press its subfunction number followed by the key then scroll to the desired test by pressing the down arrow key. Refer to Table 14 for a com-
plete description of the test function.
To start a test of discrete outputs, press . To end the test, simply press the key or press . Pressing the key after a test has started advances the system to
the next test, whether the current test is operating or has timed out. Circuit A discrete outputs can be tested in and
include loaders, minimum load valve, oil heater (if equipped), motor cooling solenoids, oil pump, and oil solenoids. Simi­larly, Circuit B discrete outputs can be tested in
.Additionaldiscrete outputs, including condenser fans,
cooler heater, water pumps, and remote alarms can be tested in .
Press to access Valves and Motormastert device analog outputs. Scroll down to display Circuit A EXV Valve
with a target percent of 0%. Press to step the EXV to 25%. Pressing three additional times will move
the EXV to 50%, 75%, and 100%. The EXV may be closed in 25% steps by pressing for each desired step. Wait
30 seconds between each step when opening and closing for the valve to stop moving. Pressing the down arrow will dis­play Circuit B EXV Valve and it is tested in the same man­ner as Circuit A. Also available for test are Circuit A water valve (if equipped) and the Circuit A and B Fan speed % (direct control Motormaster device) outputs for 30GX chill­ers. These are tested in the same manner as the EXV valves. Note that condenser fan motors are NOT started during fan speed quick tests. Measure 4 to 20 mA dc output using meter in series with violet wire to controller. See page 72 of Field Wiring section.
While the unit is in test, you can leave the test function and access another display or function by pressing the ap­propriate keys. However,a component that is operating when another function is accessed remains operating. You must
re-enter the test function and press to shut down the component. Components with a timed operating limit time
out normally even if another function is accessed.
Since the Test function checks only certain outputs, it is a good practice to also check all inputs and outputs acces­sible through the status function. These can be located by
pressing through . If keypad is not used for 10 minutes, the unit automatically leaves the test function
and resumes the normal rotating display. See Table 15. HISTORY FUNCTION — Pressing displays total
machine operating hours. Scroll down to display machine run time and starts, and total run time and starts for each compressor. Refer to Table 16 for a complete description of the function. When the PSIO-1 module is replaced or down­loaded with Version 4.0 or later software, the number of starts and run hours may be changed one time. Record the current values from the PSIO before removing the module or down­loading new software. The number of starts and hours may be changed by entering the desired value at the HSIO and
pressing the key.
Pressing displays the last 10 alarms along with a description and time and date of occurrence of each alarm.
SET POINT FUNCTION — Set points are entered through the keypad. Set points can be changed within the upper and lower limits, which are fixed. The ranges are listed below. Refer to Table 17 for a complete description of the function.
Cooling Set Point 1,2
Water:
Medium
Temperature Brine:
Low
Temperature Brine:
38 to 70 F
(3.3 to 21.1 C)
14 to 70 F
(−10 to 21.1 C)
−13 to 70 F
(−25 to 21.1 C)
Reset Set Points
Maximum
Reset Range:
−30 to 30 F
(−17 to 17 C)
External Temperature
Reset:
−40 to 240 F
(−40 to 118 C)
Chiller Fluid D:
0° to 15 F
(0° to 8 C)
External Signal Reset: 4 to 20 mA (2-10 vdc with
500 Ohm resistor) Demand Limit Set Points Switch Input: Step1—0to100% Capacity Reduction
Step2—0to100% Capacity Reduction
External Signal: Maximum Demand Limit 4 to 20 mA
(2-10 vdc with 500 Ohm resistor) Minimum Demand Limit 4 to 20 mA
(2-10 vdc with 500 Ohm resistor) Loadshed Demand Delta: 0 to 60% Maximum Loadshed Time: 0 to 120 min.
Head Pressure Set Points Air cooled chillers (30GX): 80 to 135 F (26.7 to 57.2 C) Water cooled chillers (30HX): 80 to 128 F (26.7 to 53.3 C) Set Point Table — The unit operating set points can be found
under . Use the down arrow key to scroll through the set points. The first set point is Cool Set Point 1. This is
the occupied chilled fluid set point. Scroll down to Cool Set Point 2 and then to the Cooling Ramp load multiplier which is configurable from 0.2 to 2.0° F/min. (0.11 to 1.1° C/min.). This value is the maximum rate at which the leaving fluid temperature is allowed to drop without adding a stage. Cool­ing Set Point 2 is used in conjunction with the dual set point switch function. This is used as the low temperature set point for ice duty or as the unoccupied set point. Press the down arrow key to display the Circuit A and B head pressure set points. The remaining set points in this subfunction include demand limit, LCW (leaving chilled water) delta alarm limit, minutes off time, and motor temperature set point.
Display Units — Press to display the units of mea­sure being used. Type 0 is for English and type 1 is for
Metric. Address — For CCN configurations, press and
scroll down to display the address and bus number of the chiller.
Time — Press and scroll down to read and change the unit day of week, time, day of month, month of year and
year of century. See the examples in Table 17 for making changes to these values.
CCN Enable/Disable — Press to disable the CCN control of the chiller. This function will override CCN con-
trol commands. The CCN Enable value under must be ON to activate this function. With CCN Enable set to ON
and Disable CCN Control set to ‘‘0,’’ the chiller will func­tion normally under CCN control. With Disable CCN Con­trol set to ‘‘1,’’ the chiller will operate in a local mode under its own control.
Reading and Changing Set Points — Table 18 shows how to read and change the chilled fluid set point. Other set points can be changed by following the same procedure. Refer to Table 17 for the sequence of display of set points in each subfunction.
25
Table 14 —Test Function and Subfunction Directory
SUBFUNCTION KEYPAD ENTRY DISPLAY COMMENT
1 Circuit A Discrete Output
Circuit A Discrete Output Loader A1 Relay is OFF
Loader A1 Relay is ON
Loader A2 Similarly, use to test remaining outputs. Press the
down arrow key or to turn an output off.
Minimum Load Valve A Circuit A Oil Heater A1 Mtr. Cooling Solenoid A2 Mtr. Cooling Solenoid Circuit A Oil Pump Oil Solenoid A1 Oil Solenoid A2
NOTE: Output will display Relay is ABSENT when not configured
2 Circuit B Discrete Outputs
Circuit B Discrete Outputs Loader B1 Relay is OFF
Loader B1 Relay is ON
Loader B2 Similarly, use to test remaining outputs. Press the
down arrow key or to turn the output off.
Minimum Load Valve B Circuit B Oil Heater B1 Mtr. Cooling Solenoid B2 Mtr. Cooling Solenoid Circuit B Oil Pump Oil Solenoid B1 Oil Solenoid B2
NOTE: Output will display Relay is ABSENT when not configured
3 Unit Discrete Output
Unit Discrete Output Fan 1 Relay is OFF
Fan 1 Relay is ON
Fan 2 Similarly use to test remaining outputs. Press the
down arrow key or to turn output off.
Fan 3 Fan 4 Fan 5 Energizes Circuit A fans for 30HXA units. Fan 6 Energizes Circuit B fans for 30HXA units. Cooler Pump Condenser Pump Cooler Heater Alarm Remote Alarm 1 Currently not supported.
26
Table 14 —Test Function and Subfunction Directory (cont)
SUBFUNCTION KEYPAD ENTRY DISPLAY COMMENT
3 Unit Discrete Output (cont)
Remote Alarm 2 Currently not supported. Remote Alarm 3 Currently not supported. Remote Alarm 4 Currently not supported. Remote Alarm 5 Currently not supported. Remote Alarm 6 Currently not supported. Remote Alarm 7 Currently not supported. Remote Alarm 8 Currently not supported. Remote Alarm 9 Currently not supported. Remote Alarm 10 Currently not supported. Remote Alarm 11 Currently not supported. Remote Alarm 12 Currently not supported. Remote Alarm 13 Currently not supported. Remote Alarm 14 Currently not supported. Remote Alarm 15 Currently not supported. Remote Alarm 16 Currently not supported.
4 Valves and Motormaster
Valves and Motor Master Circuit A EXV Valve Target Percent = 0%
Circuit A EXV Valve Target Percent = 25%
Step in 25% increments.
Circuit A EXV Valve Target Percent = 50%
Wait 30 seconds between each step for valve to stop moving.
Circuit A EXV Valve Target Percent = 75%
Valve may be closed in 25% increments by keying in . Wait 30 seconds between each step for valve to stop moving.
Circuit A EXV Valve Target Percent = 100%
Circuit B EXV Valve Target Percent = 0%
Test same method as for Circuit A
Circuit A Water Valve Target Percent = 0%
Test same method as for EXV valves Circuit A% Fan Speed Test same method as for EXV valves Circuit B% Fan Speed Test same method as for EXV valves
LEGEND
EXV — Electronic Expansion Valve
Table 15 — Using Test Function
KEYPAD ENTRY DISPLAY RESPONSE COMMENTS
Circuit A Discrete Output Loader A1 Relay is OFF
Appears on screen momentarily, then will switch to Loader A1.
Loader A1 Relay is ON
Compressor Loader A1 solenoid energized
Loader A1 Relay is OFF
Compressor Loader A1 solenoid deenergized
Valves and Motor Master Circuit A EXV Valve Target Percent = 0%
Circuit A EXV Valve Target Percent = 25%
Continue pressing to step to 50%, 75%, and 100%.
Circuit A EXV Valve Target Percent = 0
Continue pressing to step closed.
LEGEND
EXV — Electronic Expansion Valve
27
Table 16 — History Function and Subfunction Directory
SUBFUNCTION KEYPAD ENTRY DISPLAY COMMENT
1 Operating Hours
Machine Operating Hours xxx.x hours
Number of hours unit has at least 1 compressor running
Number of unit starts from zero capacity
These values may be changed once, when new software is down­loaded or when the PSIO-1 module is replaced (Version 4.0 and later).
Machine Starts xxx
Circuit A Operating Hours
xxx.x hours Compressor A1 Hours
xxx.x hours Compressor A2 Hours
xxx.x hours Starts
Compressor A1 Starts xxx
Compressor A2 Starts xxx
Circuit B Operating Hours
xxx.x hours Compressor B1 Hours
xxx.x hours Compressor B2 Hours
xxx.x hours Starts
Compressor B1 Starts xxx
Compressor B2 Starts xxx
2 Alarm History
Previous Alarm 1 - description Alarm description, time/day of occurrence
Lists 10 most recent alarms. Use key when necessary
Previous Alarm 2 - description Alarm description, time/day of occurrence
Previous Alarm 3 - description Alarm description, time/day of occurrence
Previous Alarm 4 - description Alarm description, time/day of occurrence
Previous Alarm 5 - description Alarm description, time/day of occurrence
Previous Alarm 6 - description Alarm description, time/day of occurrence
Previous Alarm 7 - description Alarm description, time/day of occurrence
Previous Alarm 8 - description Alarm description, time/day of occurrence
Previous Alarm 9 - description Alarm description, time/day of occurrence
Previous Alarm 10- description Alarm description, time/day of occurrence
28
Table 17 — Set Point Function and Subfunction Directory
SUBFUNCTION KEYPAD ENTRY DISPLAY COMMENT
1 Set Point Table
COOLING Cool Setpoint 1
xx.x dF
Default: 44.0
Cool Setpoint 2 xx.x dF
Default: 44.0
Cooling Ramp Loading xx.x dF
Default: 0.5 HEATING NOT SUPPORTED Heat Setpoint 1
xx.x dF
NOT SUPPORTED
Default: 98.0 Heat Setpoint 2
xx.x dF
NOT SUPPORTED
Default: 98.0 Heating Ramp Loading
xx.x dF
NOT SUPPORTED
Default: 0.5 HEAD PRESSURE
Head Pressure Setpoint A xxx.x dF
Default: 113.0 (GX)
100.0 (HXA) 85.0 (HXC)
Head Pressure Setpoint B xxx.x dF
Default: 113.0 (GX)
100.0 (HXA) 85.0 (HXC)
DEMAND LIMIT Demand Switch 1 Setpoint
xxx.x%
Default: 80.0% Demand Switch 2 Setpoint
xxx.x%
Default: 50.0% LCW Delta Alarm Limit
xxx.x dF
Default: 50.0 dF Minutes Off Time
xxx min
Default: 0 min Motor Temp Set Point
xxx.x dF
Default: 200.0 dF
2 Units
US IMPERIAL/METRIC 0
0 = English (Default)
1 = Metric
3 Address
TARGETADDRESS x
Default: 1 TARGET BUS NUMBER
x
Default: 0
4 Time
Day of Week Monday
Mon=1, Tues=2, etc. Day of Week
Wednsday
Day of week set TIME (HOUR:MIN)
00:00
Enter military format TIME (HOUR:MIN)
10:30
Time of day set DAY OF MONTH
xx DAY OF MONTH
20
Day of month set MONTH OF YEAR
xx MONTH OF YEAR
05
Month of year set YEAR OF CENTURY
xx YEAR OF CENTURY
96
Year of century set
5 CCN Disable
Disable CCN Control x
0=no, 1=yes
Default: 0
LEGEND
CCN — Carrier Comfort Network LCW — Leaving Chilled Water
NOTE: If metric option is selected under , temperatures are expressed in degrees Celsius and pressures are expressed in kPa.
29
Table 18 — Reading and Changing
Chilled Fluid Set Point
KEYPAD ENTRY DISPLAY RESPONSE COMMENTS
COOLING Change set point from
default to 48 F.
Cool Set point 1
44.0 F default Cool Set point 1
48.0 F
Set point change complete
SERVICE FUNCTION — This function allows the techni­cian to view and input configuration data. Factory configu­ration data, field configuration data, and service configura­tion data may be viewed or entered through the keypad and display module. See Table 19 for a complete listing of con­figurable items. Whenever a processor module is replaced in the field, the complete list of configuration codes should be checked for correct settings. The current software version can be displayed. See Table 20.
Scroll down in this function to display configuration in­formation including number of compressors, tonnage, and compressor must-trip amps.
Password Protection of HSIO Configurable Service Points — To modify configurations and values and to use the manual control subfunction, the password must be entered before the first change can be made. The default password is set to
. See Table 21 for an example of how to
enter the password to change the Lead/Lag configuration. Options Configuration Tables 1 and 2 — These subfunc-
tions can be accessed by pressing or and scroll­ing down to display the configuration options. See Table 19
for a complete list of these options. Temperature Reset, Demand Limit and Head Pressure PID
Configurations —Press andscrolldowntoview the configuration information. See Table 19 for a complete list.
Factory Configuration Codes — Pressing allows entry into the factory and service configuration codes
subfunction. Under this subfunction, there are 5 configura­tion codes that are downloaded at the factory. Each code is made up of 8 digits. If the processor module is replaced in the field, these 5 configuration codes should be checked us­ing the keypad and HSIO display module. See Table 22 for a descriptionofthefactory configuration codes (codes 1 through
3) and service configuration codes (codes 4 and 5).
The factory and service configuration codes are found by pressing . These are preset from the factory.They can
be verified by following the description in Table 22. These codes MUST be checked and corrected in the field if the PSIO-1 module is replaced.
NOTE: The LOCAL/OFF/REMOTE switch must be in the OFF position to change configuration codes.
A label is applied to a control box panel with a list of factory and service codes for particular units. Table23shows how to configure a new PSIO-1 module for use in a 30HXC­106---501CA water cooled chiller.
Transducer Calibration — Press and scroll down to view the transducer calibration information. See Table 19
for a complete list, and the Pressure Transducers section on page 59 for a description of this subfunction.
Manual Control Mode — This control allows the user to have full control over the compressors, loaders, and the mini­mum load valve (if installed) of the machine. Normal safe­ties such as high pressure, oil level and pressure, and CPM related alarms are NOT bypassed in this control mode. The capacity control function and overrides ARE bypassed when using the manual control mode. To enter this mode, switch
the LOR switch to OFF. Press at the HSIO. The dis­play will read Manual Control Enable - Disable. Press
and switch the LOR switch to Local. The display will change to Manual Control Enable - Enable. The Disable and Enable will appear on the second line of the display. See Table 19 for a complete list of this function.
Scroll down and press to start the desired com-
pressor.The control will start the compressor if the pre-lube cycle is passed, just as in normal operation. Press to add loaders as desired and press to turn off loaders
and compressors. The Minimum Load Valve can be ener­gized using the same procedure.
Dual Chiller Configuration — Press to enter the Dual Chiller control configuration. This method of control is for
a stand-alone Master/Slave combination of chillers and will NOT work with the Flotronic™ System Manager (FSM). The Minus One Pass Cooler option is required for this configuration.
The chillers should be piped for series flow through the coolers. The Master chiller must be downstream from the Slave chiller leaving water.BoththeMasterand Slave chiller must be connected to the same CCN Level II communica­tions bus with different addresses. To enable the dual chiller
configuration the CCN Enable function must be set to Enable for each chiller, otherwise each chiller will oper-
ate independently. This value can be activated through the HSIO or through a CCN device. Both chillers should be con-
figured for Close Control and require flow switches to be installed. For cooler pump control, wire both Master
and Slave chiller outputs to the cooler pump starter.All sys­tem inputs (temperature reset, demand limit, dual set point, etc.) should be connected to the Master chiller. If Lead/Lag Balance is disabled, the Master chiller will always be the lead chiller. If Lead/Lag Balance is enabled, the control will alternate between the Master and Slave chillers to keep their respective run hours balanced within the value configured for Lead/Lag Balance Delta. The desired leaving fluid set
point for the Duplex chiller must be configured in the Master chiller. CCN Control of the chillers can be dis-
abled locally through the HSIO by entering and en­abling the Disable CCN Control value. This value must be
disabled before the chiller will return to Duplex control.
30
Loading...
+ 70 hidden pages