Carrier 30HH User Manual

4.3 (3)

in ¡n \r.

B

■as

<a

0

30HH,HJ

Carrier r-

Installation and

Maintenance Instructions

(o

30

4111111 y I

Jiy nil|FilJ

HERMETIC RECIPROCATING

LiaUIO CHILLING PACKAGE

Carrier Corporation 1964

Tab

IS

LItbo m L’«S.A.

12-62

Carrier

INSTALLATION

CONTENTS

 

 

PAGE

STALLATION SECTION

 

Dimension Drawings

3-5

Preliminary Survey

6

Moving and Placing Unit

6-7

Unit Specifications

7-10

Compressor Physical Data

7

Condenser Physical Data

8

Cooler Physical Data

9

Refrigerant Circuits

10

Refrigerant Charge

10

Compressor Mounting

10

Condenser Water Piping

11-13

Cooler Water Piping

14

Refrigerant Piping

15-16

Leak Testing

17

Dehydrate the System

17-18

Start-up Procedures

18-20

Charge with Refrigerant

20-21

Oil Charge

21

Check the Controls

21-23

Starters and Overloads

23

Circuit Breakers

23-24

Water Regulating Valve

24

Temperature Controller Adjustment

24-26

Wiring Diagrams

27-32

Electrical Data

33-34

Capacity Controls

34-35

Sequence of Operation

35-36

Moisture and Liquid Indicator

37

AINTENANCE SECTION

 

Condenser Maintenance

38-39

Trouble Diagnosis Chart

40-42

Compressor Maintenance

42

Cause and Prevention of Freeze-up

42

INSTALLATION 30HH,HJ

NOTES;

1.CONDENSER AND ATTACHED PIPING AS SHOWN ARE FOR 30HH MODEL ONLY.

2.REMOVABLE PANELS FURNISHED ON UN IT AS FOLLOWS'. ONE PANEL EACH SIDE, PANELS FRONT AND BACK OF COOLER SECTION, PANELS OVER FRONT OF COMPR., STEP CONT

AND CONTROL CENTER SECTIONS.

3.SIDE PANELS PROVIDED WITH HOLES FOR CHILLED WATER PIPING.

. TWO HOLES PROVIDED IN REAR PANEL OF CONTROL BOX FOR CONTROL AND AUXILIARY WIRE ACCESS.

CONTROL BULB OF TEMPERATURE CONTROLLER TO BE FIELD INSTALLED IN INLET CHILLED WATER LINE.

STANDARD CON T ROL VOLTAGE IS 230 VOLTS FOR 208, 230 aAOOVOLT UNITS FOR 460 a 575 VOLT UNITS STANDARD CONTROL VOLTAGE IS 115 VOLTS.

LEFT SiDE VIEW

FRONT VIEW

Fig. 1 - 30HH,HJ015 Dimensiona! Data

NOTES;

I.CONDENSER AND ATTACHED PIPING AS SHOWN ARE FOR 30HH MODEL ONLY.

2 REMOVABLE PANELS FURN ISHED ON UNIT AS FOLLOWSlONE

PANEL EACH SI DE, PANELS FRONT AND BACK OF COOLER

. TWO HOLES PROVIDED IN REAR PANEL OF CONTROL BOX FOR CONTROL AND AUXILIARY WIRE ACCESS.

. CONTROL BULB OF TEMPERATURE CONTROLLER TO BE FIELD INSTALLED IN INLET CHILLED WATER LINE.

I.I

LEFT SIDE VIEW

FRONT VIEW

Fig. 2 - 30HH,HJ020 Dimensional Data

Carrier 30HH User Manual

30HH,HJ INSTALLATION Carrier

SEE NOTE !

2”FPT WATER OUTLET -

CONDENSERS FOR 30HH030 -------------------

CONDENSERS FOR 30HH025

I 2 FPT WATER

INLET—-.,

I2 FPT WATER

OUTLET—

FPT WATER

INLET

NOTES;

I CONDENSER ANDATTACHED PIPING AS SHOWN ARE FOR 30 HH MODEL ONLY.

2.REMOVABLE PANELS FURNfSHEO ON UNITAS FOLLOWS. ONE PANEL EACHSIDE, PANELS FRONT AND BACK OF COOLER SECTION, PANELS OVER FRONTOF COM PR., STEP CONT AND CONTROL CENTER SECTIONS.

SIDE PANELS PROVIDED WITH HOLES FOR CHILLED

WATER PIPING.,,,

COND.

CONDENSER

(SEE NOTE I )

V..y V

CONTROL

BOX

CIRCUIT

BREAKERS' y •

COMPR. OVERLOAD

RESET BUTTON -

MPT WATER

INLET

4 TWO HOLES PROVIDED IN REAR PANEL OF CONTROL BOX FOR CONTROL AND AUXILIARY WIRE ACCESS.

5.CONTROLSULB OF TEMPERATURE CONTROLLER TO BE FIELD INSTALLED IN INLET CHILLEDWATER LINE.

6.STANDARD CONTROL VOLTAGE IS23OV0LTS F0R208. 230 9 400V0LT UNITS. FOR 460 S 575 VOLT UNITS STANDARD CONTROL VOLTAGE IS 115 VOLTS.

STEP CONTROLLER

DISCH CONN.iHJ ONLY)

HJ025- I OD

HJ030IffOD____________

SAFETY

THERMOSTAT

RESET BUTTON

 

2 DIA. HOLE ELECTRIC CONN.

IDE VIEW

FRONT VIEW

Fig. 3 - 30HH,HJ025,030 Dimensional Data

NOTES:

1CONDENSER AND ATTACHED PIPING AS SHOWN ARE FOR 30HH MODEL ONLY.

2REMOVABLE PANELS FURNISHED ON UNIT AS FOLLOWS: ONE PANEL EACH SIDE, PANELS FRONT AND BACKOF COOLER SECTION, PANELS OVER FRONT OF COMPR, STEP CONT. AND CONTROL CENTER SECTIONS.

3SIDE PANELS PROVIDED WITH HOLES FOR CHILLED WATER PIPING.

TWO HOLES PROVIDED IN REAR PANEL OF CONTROL BOX FOR CONTROL AND AUXILIARY WIRE ACCESS.

. CONTROL BULB OF TEMPERATURE CONTROLLER TO

BE FIELD INSTALLED IN INLET CHILLED WATER LINE.

STANDARD CONTROL VOLTAGE IS 230 VOLTS FOR 208,230 5 400 VOLT UNITS FOR 460 5 575 VOLT UNITS STANDARD CONTROL VOLTAGE IS 115 VOLTS.

h 5''— 2 ^

I' o.D. LIQUID LINE

Fig, 4 - 30HH,HJ045 Dimensional Data

Carrier INSTALLATION 30HH,HJ

N O T E S:

1.CONDENSER AND ATTACHED PIPING AS SHOWN ARE FOR 30HH MODEL ONLY.

2.REMOVABLE PANELS FURNISHED ON UNIT AS FOLLOWS. ONE PANEL EACH SIDE, PANELS FRONT AND BACK OF COOLER SECTION, PANELS OVER FRONT OF COMPR., STEP CONT. AND CONTROL CENTER SECTIONS.

3.SIDE PANELS PROVIDED WITH HOLES FOR CHILLED WATER PIPING.

Fig. 5 - 30HH055 Dimensional Data

4.TWO HOLES PROVIDED IN REAR PANEL OF CONTROL BOX FOR CONTROL AND AUXILIARY WIRE ACCESS

5.CONTROL BULB OF TEMPERATURE CONTROLLER TO BE FIELD INSTALLED IN INLET CHILLED WATER LINE.

6.STANDARD CONTROL VOLTAGE IS 230 VOLTS FOR 208, 230 8 400 VOLT UNITS FOR 460 8575 VOLT UNITS STANDARD CONTROL VOLTAGE IS 115 VOLTS.

-3’’DIA.H0LE FOR ELECTRICAL CONN LOCATED IN REAR OF CIRCUIT BREAKER CABINET

Fig. 6 - 30HH,HJ055 Dimensional Data

30HH,HJ INSTALLATION

PRELIMINARY SURVEY

Before

installation is

started, a

survey

should

be made to

establish

the procedures and

ma­

terials

required

by

installation

personnel.

See

cover picture for typical unit.

 

 

Storage

Because of the sensitive control mechanisms and electrical devices incorporated in the 30HH,HJ units, they should not be exposed to the weather.

Location

Always

locate the

unit

 

indoors.

In

order

to

pre­

vent freezing, the unit must be located

in

a

space

where the temperature is at least 40 degrees.

 

 

 

 

Space Requirements and Clearance

 

 

 

 

 

Dimensions

for

the

units

are

given

in

Table

1.

These dimensions are useful in checking

door

clearances for moving the unit in and

for deter­

mining

space

requirements.

A

clearance

of

2

to

3 feet should

be

left on

each

side and on

the

ends

for

piping

 

and

electrical

connections

and

 

also

to

facilitate

service

 

operations.

Clearance

 

at

one

end

of

the

unit,

equal to

the

length

of

the

unit,

for

servicing

and

removal

of

chiller

tubes

must be provided.

 

 

 

 

 

 

 

 

 

 

 

 

Adequate Floor Strength

 

 

 

 

 

 

 

 

Approximate weights of units are given in Table

 

 

 

1.

Make

certain

that

 

the

floor

is

strong

enough

to support this weight. If necessary,

add

sup­

porting

structure

to

the

floor

for

transferring

weight

to the nearest beams. This

can

be

done

with steel beams or reinforced concrete slabs.

 

 

Vibration Isolation

 

 

 

 

 

 

 

Rubber-in-shear

vibration

insulators

and

muf­

flers

are installed on, or furnished with,

the

compressors of

all

units

beginning

with

early

1961

production.

The

inter-connecting

piping

must

be sufficiently flexible to prevent vibra­

tion

transmission,

if

vibration

still

exists,

vi­

bration

isolators

may

be used

on the unit

itself.

The

field-purchased

 

vibration

mountings

should

be placed under each corner of the

package.

The

weight

distribution

of

all

packages

except

the

30HH015 and 30HJ015 is such that each corner

mounting

supports

one fourth

of

the

operating

weight.

The weight

distribution

of

the

30HH015

and 30HJ015 units is 55-45 side to side and sym­ metrical front to back.

All phases of vibration isolation

are

fully

de­

scribed in Section 5X-1 of

the

Product

Infor­

mation book. Consult same for best results.

 

 

For

additional

information

see

"Compressor

Mounting."

 

 

 

 

 

 

MOVING AND PLACING UNIT

 

 

Moving

 

 

 

 

 

The

skids on

which the unit

is

mounted

should

not

be removed

until the unit is at

the

final

loca­

tion. When handling the unit with a chain

hoist,

remove the panels so that they

will not

be

dam­

aged by the sling. Do not attach the sling to

 

 

Table 1 - Weight and Overall Dimensions - 30HH.HJ Liquid Chiller Package

 

Shipping

Operating

Uncrated Dimensions (Ins.)

Crated Dimensions (Ins.)

 

Unit

Wt. (lbs.)

Wt. (lbs.)

Length

Width

Height

Length

Width

Height

 

 

 

 

 

 

 

 

 

30HH015

1430

1625

72

22-1/2

54-3/4

76

30

63

30HH020

2200

2150

72

22-1/2

54-3/4

76

30

63

30HJ015

1270

1460

72

22-1/2

47

76

30

63

ЗОН] 020

1700

1800

72

25-1/2

47

76

30

63

30HH025

2200

1950

72

22-1/2

54-3/4

76

30

63

30HH030

2550

1950

72

22-1/2

54-3/4

76

30

63

30H]025

2100

1800

72

25-1/2

47

76

30

63

30HJ030

2150

1850

72

25-1/2

47

76

30

63

30HH045

3010

3391

79-1/4

29-1/4

79

83-1/2

33

84-7/8

30HJ045

2455

2835

•79-1/4

29-1/4

66

83-1/2

33

84-7/8

30HH055

4622

5158

105-1/4

29-1/4

80-3/8

109-3/4

33

86-3/4

30HH065

4700

5236

105-1/4

29-1/4

80-3/8

109-3/4

33

86-3/4

30HJ065

3700

4236

105-1/4

29-1/4

Ó6

109-3/4

33

86-3/4

 

 

 

 

 

 

 

 

 

Carrier

INSTALLATION 30HH,HJ

piping or equipment. Move the unit in an upright

position,

and

let

it down gently from the

truck

or

rollers.

On

30HH,HJ015-030 units the

sling

can

be

placed

under the frame channels at

the

main support (Fig. 7). On 30HH,HJ045 thru

065

units, the sling can be placed under the skids.

 

Placing

To anchor the equipment;

1.Locate the hold down bolts as shown in the

dimension

drawings.

The

areas

where

the

four corners will be located should be ap­

proximately level before the unit is placed.

 

2. Set the

unit in place

and

level

with a

spirit

level on the frame channels.

3.Bolt the unit to the floor. This is usually de­

sirable

for

basement or ground floor

instal­

lations

that

can

transmit

vibration

to the

ground

without

affecting

the building

struc­

ture.

 

 

 

 

 

Fig. 7 - Rig Sling to Hoist Unit

(015-030 Shown)

Table 2 - Compressor Motor Physical Data

Unit Size

 

30HH, H]

 

30HH, H]

 

30HH, HJ

30HH, HJ

30HH, HJ

 

30HH

30HH, HJ

 

0J5

 

020

 

025

030

045

 

055

065

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor Type

 

 

 

 

 

Hermetic Reciprocating

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Number

 

 

 

2

 

2

2

3

 

4

4

 

 

 

 

 

 

 

 

 

 

 

 

Sizes

 

1 - 6D73»

 

2 - 6D68

 

1 - 6D68

2 - 6D73*

3 - 6D73*

 

1 - 6D68

4 - 6D73*

 

 

 

 

 

1 - 6D73*

 

 

 

3 - 6D73

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cylinder (Total No.)

 

6

 

12

 

12

12

18

 

24

24

 

 

 

 

 

 

 

 

 

 

 

 

Speed - 60 Cycle (rpm)

 

1750

 

1750

 

1750

1750

1750

 

1750

1750

- 50 Cycle (rpm)

 

1460

 

1460

 

1460

1460

1460

 

1460

1460

 

 

 

 

 

 

 

 

 

 

 

 

Oil Charge (10 pt per compr) (pr)

 

10

 

20

 

20

20

30

 

40

40

 

 

 

 

 

 

 

 

 

 

 

 

Cylinder Unloading Devices (No.) t

 

2

 

 

 

1

1

1

 

 

1

 

 

 

 

 

 

 

 

 

 

 

*6D7 3 Compressors are used

on rhe 30HH models

t Each cylinder unloading device unloads two cylinders

 

 

only. 30HJ Models are supplied with 6D75 com­

 

of the compressor when it is energized.

 

 

pressors.

 

 

 

 

 

 

 

 

 

 

 

30HH/HJ INSTALLATION

Carrier

Table 3 - Condenser Physical Data

Unit Size

 

30HH015

30HH020

30HH025

30HH030

30HH045

30HH055

 

30HH065

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Condensers (No.)

 

1

2

 

2

2

3

2

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

Condenser Type

 

 

 

Shell-and-Coil

 

 

Sheil-anc -Tube

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Tubes or Coils, each

 

6

4

 

1 - 6

6

6

64

 

64

 

 

 

 

1 - 4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Effective External Surface, each (sq ft)

82.7

53.9

 

1 - 5 3 . 9

82.7

82.7

165.7

 

165.7

 

 

 

1 - 82.7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Water Side Volume, each (gal)

 

3.5

2.5

 

1 - 2.5

3.5

3.5

5.0

 

5.0

 

 

 

 

1 - 3.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Nominal Shell Diam (in.)

 

10-15/16

10-15/16

10-15/16

10-15/16

10-15/16

10-3/4

 

10-3/4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Shell Length (in.)

 

42-5/8

34-5/8

1

-

34-5/8

42-5/8

42-5/8

77

 

77

 

 

 

1 - 42-5/8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Water Connections (Total No.)

 

2

4

 

 

4

4

2

4

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Inlet

1 - 2"

2 - 1-1/2”

1

-

1-1/2”

2 - 2"

3 - 2"

2 - 2"

 

1 - 3"

 

 

Water Connection

 

1 - 2"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Size (each cond. )

 

Outlet

1 - 2"

2 - 1-1/2"

1

-

1-1/2"

2 - 2”

3 - 2"

2 - 1-1/2"

 

2 - 2”

 

 

 

 

 

1 - 2"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Г'

Coil or Tube Type

 

 

 

 

Trufin

 

 

 

 

 

 

 

 

 

 

 

 

Trufin

 

 

 

 

 

 

 

 

 

 

 

 

Coil or Tube OD (in.)

 

 

 

 

7/8

 

 

3/4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Nominal Shell Thickness (in.)

 

 

 

 

.278

 

 

.307

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Materials

 

Shell

 

 

 

Steel

 

 

Steel

 

of

 

Coil or Tubes

 

 

 

Copper

 

 

Copper

Construction

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Tube Sheet

 

 

 

Steel

 

 

Steel

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Max. Design

 

Water Side

 

 

 

100

 

 

100

 

 

 

Working Press, (psig)

 

Refrig. Side

 

 

 

385

 

 

385

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE: The 30HH065 unit is supplied with two subcooiers (one per circuit) to provide 15 F of subcooling.

INSTALLATION 30HH,HJ

m

Tabie 4 - Cooler Physical Data

Unit Size

 

30 HH, HJ

30HH, HJ

30HH, HJ

 

30HH. HJ

 

30HH. HJ

30 HH

30HH, HJ

 

015

020

025

 

030

 

045

055

065

 

 

 

 

 

 

 

 

 

 

 

Refrigerant Circuits (No.)

 

1

2

2

 

2

 

2

2

2

 

 

 

 

 

 

 

 

 

 

 

Tubes (No.)

 

136

136

136

 

136

 

188

186

186

 

 

 

 

 

 

 

 

 

 

Effective External Tube Surface (sq ft)

125

126

127

 

128

 

179

258

258

 

 

 

 

 

 

 

 

 

 

Length Between Tube Sheets (in.)

60-1/4

60-1/4

60-1/4

 

60-1/4

 

60-1/4

85-7/8

85-7/8

 

 

 

 

 

 

 

 

 

 

 

Shell Side Water Volume (gal)

 

20.4

20.6

20.8

 

21.0

 

26.6

38.2

38.2

 

 

 

 

 

 

 

 

 

 

 

Baffles (No.)

 

31

25

21

 

17

 

15

17

17

 

 

 

 

 

 

 

 

 

 

 

Baffle Spacing (in.)

 

1-7/16

1-27/32

2-7/32

 

2-3/4

 

3-1/4

4-1/2

4-1/2

 

 

 

 

 

 

 

 

 

 

 

Nominal Shell Diam. (in.)

 

14

14

14

 

14

 

16

16

16

 

 

 

 

 

 

 

 

 

 

Water Connection Size, IPS (in.)

2

2

2

 

2

 

2

3

3

 

 

 

 

 

 

 

 

 

 

 

Cooler Type

 

 

 

 

Direct Expansion

 

 

 

 

 

 

 

 

 

 

Construction

 

 

 

Shell-and-Tube, Fixed Tubesheet

 

 

 

 

 

 

 

 

 

 

Tube Type and Size (in.)

 

 

 

Prime Surface, 3/4 OD

 

 

 

 

 

 

 

 

 

 

 

 

 

Nominal Shell Thickness (in.)

 

 

 

 

1/4

 

 

 

 

 

 

 

 

 

 

 

 

 

Nominal Tube Sheet Thickness (in.)

 

 

 

 

1-3/8 Min.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Shell

 

 

 

 

Steel

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Materials

 

Tubes

 

 

 

 

Copper

 

 

 

of

 

Tube Sheet

 

 

 

 

Steel

 

 

 

Construction

 

 

 

 

 

 

 

 

 

 

 

 

Baffles

 

 

 

Polypropylene

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

insulation

 

 

Closed Cell Foam Plastic, Vapor Sealed

 

 

 

 

 

 

 

 

 

 

 

 

 

Maximum Design

 

Water Side

 

 

 

250

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Working Press.(psig)

 

Refrig. Side

 

 

 

150

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

30HH,HJ INSTALLATION

Carrier

 

 

 

 

 

Table 5 - Refrigerant Circuits

 

 

 

 

 

 

 

 

 

 

 

Unit Size

Circuits

 

 

Description of Refrigerant Circuit

 

Capacity (%)

 

 

 

 

 

 

 

 

зоны, HJ015

1

 

(i) 6D73 or 6D75 Compr, Full Cooler Surface

 

100

 

 

 

 

 

 

 

 

 

 

 

(1) 6D68 Compr, 1/2 Cooler Surface

 

50

 

30HH, HJ020

2

 

(1)

6D68 Compr, 1/2 Cooler Surface

 

50

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(1)

6D68 Compr, 1/2 Cooler Surface

 

40

 

зоны, HJ025

2

 

(1)

6D73 or 6D75 Compr, 1/2 Cooler Surface

 

60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(1)

6D73 or 6D75 Compr, 1/2 Cooler Surface

 

50

 

ЗОНЫ, HJ030

2

 

(1)

6D73 or 6D75 Compr, 1/2 Cooler Surface

 

50

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(1)

6D73 or 6D75 Compr, 1/3 Cooler Surface

 

33

 

ЗОНН, HJ045

2

 

(2)

6D73 or 6D7S Compr, 2/3 Cooler Surface

 

67

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(2)

6D73 Compr, 1/2 Cooler Surface

 

55

 

30НН055

2

 

(1)

6D73 & (1) 6D68 Compr, 1/2 Cooler Surface

 

45

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(2)

6D73 or 6D75 Compr, 1/2 Cooler Surface

 

50

 

ЗОНН, HJ065

2

 

(2) 6D73 or 6D75 Comipr, 1/2 Cooler Surface

 

50

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE: 6D73 Compressors arc used on ЗОНЫ models. 6D75 Compressors are used on 30HJ miodels.

Table 6 - Refrigerant Charge

Model ЗОНН, HJ

015

020

025

030

045

055

065

 

 

 

 

 

 

 

 

Refrigerant 22 (lb)

35

46

46

46

69

124

140

 

 

 

 

 

 

 

 

NOTES: 1. The refrigerant charges listed above do not include the additional charge required

for remote condensers and piping with ЗОН] models.

2. The 30HH015 and 30HH020 units are shipped fully charged with refrigerant. Other units are shipped with holding charges only.

COMPRESSOR MOUNTING

All 30HH,HJ chillers, as shipped,

have

the

com­

pressor rigidly mounted to

the

frame

with

bolts

and steel pipe spacers.

For

proper

operation,

the following procedure should be followed;

30HH,HJ020 to 030 units (Fig. 8):

1.Loosen the four (4) hold-down bolts on one compressor.

2.Remove one hold-down bolt, lock washer and nut on oil pump end of compressor. Lift

 

end of compressor and remove pipe spacer.

3.

Tighten hold-down bolt which is diagonally

 

opposite spacer which was removed.

 

4.

Install 3/8-16

X 1-1/2"

bolt, supplied in

bag

 

of fastenings,

between

compressor foot

and

bracket. Reinstall lock washer and nut.

5. Loosen hold-down bolt tightened in step No. 3.

6. Repeat steps 2 thru 5 for other oil pump end bolt.

10

INSTALLATION 30HH,HJ

FRONT

REAR

MOTOR END

PUMP END

Fig. 8 - 30HH,HJ015-030 Compressor

Fig. 9 - 30HH,HJ045-065 Compressor

Mounting

Mounting

7.

Remove

both compressor

motor

 

end

hold­

down

bolts, nuts,

lock

washers,

 

and

pipe

spacers, and replace with 3/8-16 x 1” bolts.

Reinstall lock washers and nuts

 

to

fasten

mounting brackets to resilient mounts.

 

 

 

30HH,HJ045 to 065 units (Fig. 9):

 

 

 

 

The

pairs of manifolded

compressors

are mount­

ed on common mounting brackets. Be sure all

 

 

 

pipe spacers are removed for proper operation.

 

 

The mounting of the single compressor on

 

 

 

30HH,HJ045 units is similar.

 

 

 

 

 

1.

Remove

one 3/8-16 x 3-1/2” hold-down

bolt,

nut,

lock

washer, and pipe spacer on

the

pump

end of the compressor.

 

 

 

 

 

 

2.

Install

a 3/8-16 x 1-3/4” bolt,

supplied in

bag

of

fastenings,

and

reinstall nut

and

lock

washer from hold-down bolt, to

fasten

com­

pressor to mounting bracket.

 

 

 

 

3. Repeat steps 1 and 2 for the other pump end fastenings of the compressors.

4. Remove

one 3/8-16

x 2-1/2” hold-down bolt,

nut, lock

washer and

pipe spacer on the motor

end of the compressor.

 

5.Install a 3/8-16 x 1” bolt, supplied in bag of

fastenings, and

reinstall

nut

and lock

washer

from

hold-down

bolt

to

fasten

mounting

bracket to resilient mount.

 

 

 

6.Repeat steps 5 and 6 for the other motor end fastenings of the compressor.

CONDENSER WATER PIPING

Water supply lines should be as short as condi­ tions will permit. The size of these lines is not necessarily the same as those of the water valve

connections.

All

piping must be sized in accord­

ance

with

tije

pressure

head

available.

This is

especially

 

true

on

cooling

tower

applications.

See

the

System

Design Manual, Part 3- "Piping

Design” for methods used in sizing pipe.

 

 

 

 

For

installations

using a waste water system, a

separate

water

regulating

valve

 

is

required

for

each

refrigerant

circuit.

Water

regulating valves

are not supplied by Carrier.

 

 

 

 

 

 

 

NOTE: Provide means for draining the

 

system

in

the

winter

and

 

for

repairs.

 

Figure 10 thru 16 show suggested piping

 

connections

for

each

model

when

used

 

with waste water or cooling towers.

 

 

 

 

Frangible Disc Safety Union

 

 

 

 

 

 

Each

condenser

is

provided

with

a

frangible

disc that will relieve at

385 psig to protect the

system from excessive pressure.

 

 

 

 

 

 

Some

local

codes

require

piping

from

the

relief

to the

outdoors.

The relief

outlet

size

on

both

models is 3/8” male flare.

 

 

 

 

 

 

 

11

1064

зонн^ш

Carrier

INSTALLATION

OUTLET

2" PIPE THD.

INLET

2" PIPE THD.

WATER REGULATING

VALUE-WASTE WATER

SYSTEMS ONLY

Fig. 10 - 30HH015 Condenser Piping Fig. 11 - 30HH020 Condenser Piping

Fig. 12 - 30HH025 Condenser Piping

Fig. 13 - 30HH030 Condenser Piping

1064

12

Carrier

INSTALLATION 30HH,HJ

Fig. 14 - 30HH045 Condenser Piping

Fig. 15 - 30HH055 Condenser Piping

Fig. 16 - 30HH065 Condenser Piping

13

1064

30HH,HJ

 

 

INSTALLATION

Drain Connection

 

 

 

 

 

 

Drain

connections

are

generally

governed

by

local

codes.

Water

leaving

the

condenser

is

under

pressure

and

should

not be

connected

directly

into

sewer

lines;

otherwise

 

water

may

back

up

into

other

fixtures.

Local

codes

nor­

mally

require

connections

similar

to

the

one

shown in Fig. 17.

 

 

 

 

 

 

 

 

COOLER WATER PIPING

 

 

Fig. 17 - Drain Connections

The cooler of each liquid chilling package is pro­ vided with stubouts for chilled water piping con­

nections. The

water outlet stubout

is provided

with a 90 degree elbow which contains

the

chilled

water safety

thermostat bulb. Holes

are

pro­

vided in both of the side panels for piping to the stubouts.

The

 

chilled

water

 

temperature

controller

is

mounted on the front of

the unit and has the con­

trol

bulb

and

capillary

tubing

wrapped

and

 

taped

before

shipping.

It

is

required

that

the

control

bulb

be

field

inserted

in

the

 

chilled

water

line.

It usually is inserted in

the return or inlet chilled

water piping. Figure 18

shows

a

typical

chilled

water

 

piping

arrangement

in the vicinity of the

cooler.

Details

of

the

 

required

remote

chilled

water

 

piping

are

outlined

in

the

Carrier

System

Design Manual, Part 3, "Piping Design."

 

 

 

 

Plan the piping so it has

a

minimum

number of

changes

 

in

elevation.

A

manual

or

automatic

vent-valve must

be

installed

at

the

high

points

in

the

line

to

permit venting

of

air

from the

chilled

water

circuit.

Standard

practice

for

in­

stalling

forced

water

systems

must

be

followed.

System

pressures

may

be maintained by using a

pressure

tank

or

a

combination

relief

 

valve

and

reducing valve.

 

 

 

 

 

 

 

 

 

 

It

is

recommended

that

thermometers

be

in­

stalled

in

entering

and

leaving

chilled

liquid

lines. Provide

drain connections

at

all

low

points

to

permit

complete

drainage of the system. A

chiller

drain

shut-off

valve

 

should

be

connected

to

the

chiller

drain

line before placing

the

unit

in operation (Fig. 18).

 

 

 

 

 

 

 

 

Insulate piping to prevent heat

loss

and

sweating.

Cover

the

insulation

with a moisture seal. Do

not

insulate

 

piping

before

all

leak

testing

has

been completed.

Fig. 18 - Cooler Water Piping, Front View

14

Carrier

INSTALLATION 30HH,HJ

REFRIGERANT PIPING

For

refrigerant piping

sizing

refer to Part

3

-

’’Piping Design” - of the System Design Manual.

 

 

 

The ЗОНЫ and HJ Packaged

Liquid

Chillers

 

are

leak tested at the factory and

provided

with

a

holding charge of Refrigerant 22.

 

 

 

 

 

 

 

NOTE: 30HH015,020 fully charged with

 

 

 

 

R 22 at factory.

 

 

 

 

 

 

 

 

If the holding charge is still

in

the

system

upon

arrival at

the

erection

site,

the

likelihood

of

leaks

is

slight.

If

the unit

is

not

under

pressure,

 

test

for leaks as outlined under Leak Testing.

 

 

 

 

 

NOTE: Be sure to open all stop valves when testing for leaks.

30HJ UNIT

This

section

also

applies

to the 30HJ unit which

is to

be connected

to a

remote

condenser

in the

field.

Figure

19

is

a

typical

refrigerant

piping

diagram showing

the 30HJ020 thru 030 unit and a

9H

Evaporative

Condenser. Simdlar connections

may be used for the 30Ш045 and 065 unit using

manifolded

compressors.

Figure

20-22

illus­

trate typical

refrigerant

piping for

30HJ020

thru

065

units and air-cooled

 

condensers.

Receivers

have

been

omitted,

but

it

must

be

recognized

that

with

this

arrangement

 

the

refrigerant

charge

is

critical.

 

An

overcharged

or

undercharged

system

can

cause a

loss of

capacity.

If

a

receiver

is

not

Included,

an accurate

refrigerant

charge

must be maintained to assure efficient operation.

 

 

Figure

20-22

are

shown

to

illustrate

a

typical

installation using 9A or 09DC016 air-cooled con­

densers.

These illustrations are

to be

used

as a

guide when designing a system and

are not

in­

tended

to be used as an actual

piping

layout.

Con­

sult the ’’System Design Manual” and condenser literature before designing the actual system.

Each 30HJ unit (except -015) consists of two independent refrigerant circuits. Each circuit must be isolated from the other.

Discharge

lines

and

liquid lines

are

shown mani­

folded at

the

units

on 30HJ045

and

065 units to

permit a minimum amount of piping. Individual

discharge

lines may

be run

from each

compres­

sor

to

the condenser if desirable. Liquid lines

must

be

manifolded

as shown

to enter the

30HJ065

unit to agree with the unit refrigerant circuit. In­ dividual liquid line connections are necessary on the 30HJ045 unit.

FROM TABLE - FOR VENTING AS SHOWN

UNI T

“X” DIM. *

30HU015

6 "

3ÛHJ020

15"

30HJ025

15"

30HJ030

15"

30HU0A5

15"

3 OHJO6 5

1 5"

"X" DIM. - THIS IS

THE MINIMUM, ELEVATION REQUIRED BETWEEN A CONDENSER COIL OUTLET AND A RECE!VER INLET FOR THE TOTAL LOAD WHEN RECE;VER 1S VENTED TO COI I. OUTLET HEADER (BASED ON 10'

OF HORIZONTAL PIPE,

1 VALVE AND 2 ELBOWS). APPLIES TO 9H TYPE

EVAP. CONDENSER

- REFRIG. GAS

-REFIG. LIQUID

M U F F L E R S S H O U L D I N S T A L L E D A S C L O S E T O T H E C O M P R E S S O ч

A S P O S S I S L E .

Fig. 19 - Typical Refrigerant Piping 30HJ020-030 Units

with 9H Evaporative Condenser

15

Loading...
+ 34 hidden pages