24ANB1
Infinityr 21 2---Stage Air Conditioner
with Puronr Refrigerant
2 to 5 Nominal Tons
Product Data
Carrier’s Air Conditioners with Puronr refrigerant provide a collection of features unmatched by any other family of equipment. The 24ANB1 has been designed utilizing Carrier’s Puron refrigerant. The environmentally sound refrigerant allows you to make a responsible decision in the protection of the earth’s ozone layer.
This product has been designed and manufactured to meet Energy Starr criteria for energy efficiency when matched with appropriate coil components. Refer to the combination ratings in the Product Data for system combinations that meet Energy Starr guidelines.
NOTE: Ratings contained in this document are subject to change at any time. Always refer to the AHRI directory (www.ahridirectory.org) for the most up-to-date ratings information.
INDUSTRY LEADING FEATURES / BENEFITS
Efficiency
S 14.5 - 21 SEER / 11.7 - 15 EER
S Microtube Technologyt refrigeration system
S Indoor air quality accessories available
Sound
S Sound level as low as 65 dBA
S Quiet mount split post compressor grommets
SElectronic ECM ball bearing outdoor condenser fan motor
S Forward-swept condenser fan blade S Compressor sound hood
S Laminated steel compressor mounting plate
Comfort
SSystem supports Infinityt Control or standard 2-stage thermostat controls
Reliability
SPuronr refrigerant - environmentally sound, won’t deplete the ozone layer and low lifetime service cost.
S Front-seating service valves S 2-stage scroll compressor S Internal pressure relief valve S Internal thermal overload
S Low pressure switch S High pressure switch S Filter drier
S Crankcase heater standard
S Balanced refrigeration system for maximum reliability
Controls and Diagnostics
S Infinityt control or 2-stage thermostat
STwo control wires to outdoor unit with Infinity Control (serial numbers 1213E and newer)
S Utility Interface Connection
S Enhanced diagnostics capability with Infinity Control
Durability
WeatherArmor Ultrat protection package:
S Solid, Durable sheet metal construction S Steel louver coil guard
S Baked-on, complete outer coverage, powder paint
Applications
SLong-line - up to 250 feet (76.2 m) total equivalent length, up to 200 feet (60.96 m) condenser above evaporator, or up to 80 ft. (24.38 m) evaporator above condenser (See Longline Guide for more information.)
SLow ambient (down to 0_F) with complete Infinity system.
MODEL NUMBER NOMENCLATURE
1 |
2 |
3 |
4 |
5 |
6 |
7 |
8 |
9 |
10 |
11 |
12 |
13 |
N |
N |
A |
A |
A/N |
N |
N |
N |
A/N |
A/N |
A/N |
N |
N |
2 |
4 |
A |
N |
B |
1 |
3 |
6 |
A |
0 |
0 |
3 |
0 |
Product |
Product |
Tier |
Major |
SEER |
Cooling |
Variations |
Open |
Open |
Voltage |
Minor |
||
Series |
Family |
|
Series |
|
Capacity |
|
|
|
|
Series |
||
24=AC |
A=RES AC |
N = |
B=Puron |
1=21 |
|
|
A=Standard |
0=Not |
0=Not 3=208---230---1 |
0, 1, 2... |
||
|
|
|
Infinity |
|
SEER |
|
|
|
Defined |
Defined |
|
|
|
|
|
|
|
Nominal |
|
|
|
|
|
|
|
24ANB1
the environmentally sound refrigerant |
Use of the AHRI Certified |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
TM Mark indicates a |
|
|
|
|
|
|
|
|
|
|
|
manufacturer’s |
|
|
|
|
|
|
|
|
|
This product has been designed and manufactured to |
|
participation in the |
|
|
|
|
|
|
|
|
|
|
|
program For verification |
|
|
|
|
|
|
|
|
|
meet Energy Star criteria for energy efficiency when |
|
|
|
|
|
|
|
|
|
|
matched with appropriate coil components. However, |
|
|
of certification for individual |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
proper refrigerant charge and proper air flow are critical |
|
|
products, go to |
|
|
|
|
|
|
|
|
|
to achieve rated capacity and efficiency. Installation of |
|
|
|
|
|
|
|
|
|
|
||
|
www.ahridirectory.org. |
|
|
|
|
|
|
|
|
|
this product should follow all manufacturing refrigerant |
|
|
|
|
|
|
|
|
|
|
charging and air flow instructions. Failure to confirm |
|
|
|
|
|
|
|
|
|
|
|
|
proper charge and air flow may reduce energy |
|
|
|
|
|
|
|
|
|
|
|
efficiency and shorten equipment life. |
STANDARD FEATURES
FEATURES |
|
Unit Size --- Voltage, Series |
|
||
|
|
|
|
||
24---31 |
36---31 |
48---31 |
60---31 |
||
|
|||||
|
|
|
|
|
|
Puron Refrigerant |
X |
X |
X |
X |
|
|
|
|
|
|
|
Maximum SEER Rating* |
21.0 |
20.0 |
18.0 |
16.7 |
|
|
|
|
|
|
|
2---Stage Scroll Compressor |
X |
X |
X |
X |
|
|
|
|
|
|
|
2 control wires to outdoor unit with Infinity Control |
X |
X |
X |
X |
|
(serial numbers 1213E and newer) |
|||||
|
|
|
|
||
|
|
|
|
|
|
Crankcase Heater |
X |
X |
X |
X |
|
|
|
|
|
|
|
Low Ambient Capability to 0_F (---17.8_C) w/Infinity Control |
X |
X |
X |
X |
|
|
|
|
|
|
|
Enhanced Diagnostics w/Infinity Control |
X |
X |
X |
X |
|
|
|
|
|
|
|
Utility Interface Connection |
X |
X |
X |
X |
|
|
|
|
|
|
|
Louvered Coil Guard |
X |
X |
X |
X |
|
|
|
|
|
|
|
Field Installed Filter Drier |
X |
X |
X |
X |
|
|
|
|
|
|
|
Front Seating Service Valves |
X |
X |
X |
X |
|
|
|
|
|
|
|
Internal Pressure Relief Valve |
X |
X |
X |
X |
|
|
|
|
|
|
|
Internal Thermal Overload |
X |
X |
X |
X |
|
|
|
|
|
|
|
Long Line Capability |
X |
X |
X |
X |
|
|
|
|
|
|
|
Low Pressure Switch |
X |
X |
X |
X |
|
|
|
|
|
|
|
High Pressure Switch |
X |
X |
X |
X |
|
|
|
|
|
|
|
Sound Blanket |
X |
X |
X |
X |
|
|
|
|
|
|
X = Standard
* With approved combinations
2
REFRIGERANT PIPING LENGTH LIMITATIONS
Liquid Line Sizing and Maximum Total Equivalent Lengths{ for Cooling Only Systems with Puronr Refrigerant:
The maximum allowable length of a residential split system depends on the liquid line diameter and vertical separation between indoor and outdoor units.
See Table below for liquid line sizing and maximum lengths :
Maximum Total Equivalent Length
Outdoor Unit BELOW Indoor Unit
|
|
Liquid |
|
|
AC with Puron Refrigerant Maximum Total Equivalent Length{: Outdoor unit BELOW Indoor |
|
|
||||||||||||||
Size |
Liquid Line |
Line |
|
|
|
|
|
|
|
Vertical Separation ft (m) |
|
|
|
|
|
|
|||||
Connection |
Diam. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
0 |
5 |
6 |
10 |
11 |
20 |
21 |
30 |
31 |
40 |
41 |
50 |
51 |
60 |
61 |
70 |
71 |
80 |
||||
|
|||||||||||||||||||||
|
|
w/TXV |
(0--- |
1.5) |
(1.8--- |
3.0) |
(3.4--- |
6.1) |
(6.4--- |
9.1) |
(9.4--- |
12.2) |
(12.5--- |
15.2) |
(15.5--- |
18.3) |
(18.6--- |
21.3) |
(21.6--- |
24.4) |
|
024 |
|
1/4 |
75 |
75 |
75 |
50 |
50 |
--- --- |
|
--- --- |
--- --- |
--- --- |
|||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
AC with |
3/8 |
5/16 |
250* |
250* |
250* |
250* |
250* |
225* |
175 |
125 |
100 |
||||||||||
Puron |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
3/8 |
250* |
250* |
250* |
250* |
250* |
250* |
250* |
250* |
250* |
|||||||||||
|
|
||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
036 |
|
5/16 |
175 |
150 |
150 |
100 |
100 |
100 |
75 |
|
|
--- --- |
|||||||||
AC with |
3/8 |
--- --- |
|
||||||||||||||||||
3/8 |
250* |
250* |
250* |
250* |
250* |
250* |
250* |
250* |
250* |
||||||||||||
Puron |
|
||||||||||||||||||||
048 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
AC with |
3/8 |
3/8 |
250* |
250* |
250* |
250* |
250* |
250* |
230 |
160 |
--- --- |
|
|||||||||
Puron |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
060 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
AC with |
3/8 |
3/8 |
250* |
250* |
250* |
225* |
190 |
150 |
110 |
--- --- |
|
--- --- |
|||||||||
Puron |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
* Maximum actual length not to exceed 200 ft (61 m)
{Total equivalent length accounts for losses due to elbows or fitting. See the Long Line Guideline for details.
------ = outside acceptable range
Maximum Total Equivalent Length
Outdoor Unit ABOVE Indoor Unit
|
|
Liquid |
|
AC with Puron Refrigerant Maximum Total Equivalent Length{: Outdoor unit ABOVE Indoor |
|||||||
Size |
Liquid Line |
Line |
|
|
|
Vertical Separation ft (m) |
|
|
|
||
Connection |
Diam. |
|
|
|
|
|
|
|
|
||
25 |
26---50 |
51---75 |
76---100 |
101---125 |
126---150 |
151---175 |
176---200 |
||||
|
|||||||||||
|
|
w/TXV |
(7.6) |
(7.9---15.2) |
(15.5---22.9) |
(23.2---30.5) |
(30.8---38.1) |
(38.4---45.7) |
(46.0---53.3) |
(53.6---61.0) |
|
024 |
|
1/4 |
100 |
125 |
175 |
200 |
225* |
250* |
250* |
250* |
|
AC with |
3/8 |
5/16 |
250* |
250* |
250* |
250* |
250* |
250* |
250* |
250* |
|
Puron |
|
|
|
|
|
|
|
|
|
|
|
|
3/8 |
250* |
250* |
250* |
250* |
250* |
250* |
250* |
250* |
||
036 |
|
5/16 |
225* |
250* |
250* |
250* |
250* |
250* |
250* |
250* |
|
AC with |
3/8 |
||||||||||
|
|
|
|
|
|
|
|
|
|||
3/8 |
250* |
250* |
250* |
250* |
250* |
250* |
250* |
250* |
|||
Puron |
|
||||||||||
048 |
|
|
|
|
|
|
|
|
|
|
|
AC with |
3/8 |
3/8 |
250* |
250* |
250* |
250* |
250* |
250* |
250* |
250* |
|
Puron |
|
|
|
|
|
|
|
|
|
|
|
060 |
|
|
|
|
|
|
|
|
|
|
|
AC with |
3/8 |
3/8 |
250* |
250* |
250* |
250* |
250* |
250* |
250* |
250* |
|
Puron |
|
|
|
|
|
|
|
|
|
|
* Maximum actual length not to exceed 200 ft (61 m)
{ Total equivalent length accounts for losses due to elbows or fitting. See the Long Line Guideline for details.
REFRIGERANT CHARGE ADJUSTMENTS
Liquid Line Size |
Puron Charge oz/ft (g/m) |
|
3/8 |
0.60 (17.74) |
|
(Factory charge for lineset = 9 oz / 266.16 g) |
||
|
||
|
|
|
5/16 |
0.40 (11.83) |
|
|
|
|
1/4 |
0.27 (7.98) |
|
|
|
Units are factory charged for 15 ft (4.6 m) of 3/8” liquid line. The factory charge for 3/8” lineset 9 oz.(266.16 g). When using other length or diameter liquid lines, charge adjustments are required per the chart above.
Charging Formula:
[(Lineset oz/ft x total length) – (factory charge for lineset)] = charge adjustment
Example 1: System has 15 ft of line set using existing 1/4“ liquid line. What charge adjustment is required? Formula: (.27 oz/ft x 15ft) – (9 oz) = (-4.95) oz.
Net result is to remove 4.95 oz of refrigerant from the system
Example 2: System has 45 ft of existing 5/16” liquid line. What is the charge adjustment? Formula: (.40 oz/ft. x 45ft) – (9 oz.) = 9 oz.
Net result is to add 9 oz of refrigerant to the system
3
24ANB1
24ANB1
LONG LINE APPLICATIONS
An application is considered Long Line, when the refrigerant level in the system requires the use of accessories to maintain acceptable refrigerant management for systems reliability. See Accessory Usage Guideline table for required accessories. Defining a system as long line depends on the liquid line diameter, actual length of the tubing, and vertical separation between the indoor and outdoor units.
For Air Conditioner systems, the chart below shows when an application is considered Long Line.
AC WITH PURONr REFRIGERANT LONG LINE DESCRIPTION ft (m)
Beyond these lengths, long line accessories are required
Liquid Line Size |
Units On Same Level |
Outdoor Below Indoor |
Outdoor Above Indoor |
|
1/4 |
No accessories needed within allowed |
No accessories needed within allowed |
175 (53.3) |
|
lengths |
lengths |
|||
|
|
|||
5/16 |
120 (36.6) |
50 (15.2) vertical or 120 (36.6) total |
120 (36.6) |
|
3/8 |
80 (24.4) |
35 (10.7) vertical or 80 24.4) total |
80 (24.4) |
Note: See Long Line Guideline for details
VAPOR LINE SIZING AND COOLING CAPACITY LOSS
Acceptable vapor line diameters provide adequate oil return to the compressor while avoiding excessive capacity loss. The suction line diameters shown in the chart below are acceptable for AC systems with Puron refrigerant:
Vapor Line Sizing and Cooling Capacity Losses — Puronr Refrigerant 2-Stage Air Conditioner Applications
|
Unit |
Maximum |
Vapor Line |
|
|
|
Cooling Capacity Loss (%) |
|
|
|
||
|
Liquid |
|
|
|
Total Equivalent Line Length ft. (m) |
|
|
|
||||
|
Nominal |
Line |
Diameters |
|
|
|
|
|
|
|
|
|
|
Size (Btuh) |
Diameters |
(In.) OD |
26---50 |
51---80 |
81---100 |
101---125 |
126---150 |
151---175 |
176---200 |
201---225 |
226---250 |
|
|
(In. OD) |
|
(7.9---15.2) |
(15.5---24.4) |
(24.7---30.5) |
(30.8---38.1) |
(38.4---45.7) |
(46.0---50.3) |
(53.6---60.0) |
(61.3---68.6) |
(68.9---76.2) |
|
024 |
|
5/8 |
0 |
1 |
1 |
2 |
3 |
3 |
4 |
4 |
5 |
|
2---Stage |
|
||||||||||
|
3/8 |
|
|
|
|
|
|
|
|
|
|
|
|
Puron |
3/4 |
0 |
0 |
0 |
0 |
1 |
1 |
1 |
1 |
1 |
|
|
|
|||||||||||
|
AC |
|
||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
036 |
|
5/8 |
1 |
2 |
4 |
5 |
6 |
7 |
9 |
10 |
11 |
|
2---Stage |
3/8 |
3/4 |
0 |
0 |
1 |
1 |
2 |
2 |
3 |
3 |
4 |
|
Puron |
|||||||||||
|
AC |
|
7/8 |
0 |
0 |
0 |
0 |
1 |
1 |
1 |
1 |
2 |
|
048 |
|
3/4 |
1 |
2 |
2 |
3 |
4 |
5 |
6 |
7 |
7 |
|
2---Stage |
|
|
|
|
|
|
|
|
|
|
|
|
3/8 |
7/8 |
0 |
1 |
1 |
2 |
2 |
2 |
3 |
3 |
3 |
|
|
Puron |
|||||||||||
|
AC |
|
1---1/8 |
0 |
0 |
— |
— |
— |
— |
— |
— |
— |
|
060 |
|
3/4 |
1 |
2 |
4 |
5 |
6 |
7 |
9 |
10 |
11 |
|
2---Stage |
|
|
|
|
|
|
|
|
|
|
|
|
3/8 |
7/8 |
0 |
1 |
2 |
2 |
3 |
4 |
4 |
5 |
5 |
|
|
Puron |
|||||||||||
|
AC |
|
1---1/8 |
0 |
0 |
0 |
1 |
1 |
1 |
1 |
1 |
1 |
|
Applications in |
this area may |
be long line and may have height restrictions. See the Residential Piping and Long Line Guideline. |
|
|
|||||||
|
— Applications in this area are not recommended due to insufficient oil return |
|
|
|
|
|
|
PHYSICAL DATA
UNIT SIZE --- VOLTAGE, SERIES |
24---31 |
36---31 |
|
48---31 |
60---31 |
Operating Weight lb (kg) |
282 (127.9) |
312 (141.5) |
|
335 (152.0) |
336 (152.4) |
Shipping Weight lb (kg) |
324 (147.0) |
357 (161.9) |
|
381 (172.8) |
381 (172.8) |
Compressor Type |
|
2---Stage Scroll |
|
||
REFRIGERANT |
|
Puron (R---410A) |
|
||
Control |
|
TXV (Puron Hard Shutoff) |
|
||
Charge lb. (kg) |
13.34 (6.05) |
13.66 (6.20) |
|
13.53 (6.14) |
14.33 (6.50) |
COND FAN |
|
Forward Swept Propeller Type, Direct Drive |
|
||
Air Discharge |
|
|
Vertical |
|
|
Air Qty (CFM) |
3040 / 3637 |
3124 / 3700 |
|
3703 / 4309 |
4209 / 4668 |
Motor HP |
1/5 |
1/5 |
|
1/5 |
1/5 |
Motor RPM |
628 / 752 |
582 / 689 |
|
659 / 765 |
742 / 828 |
COND COIL |
|
|
|
|
|
Face Area (sq. ft.) |
25.12 |
30.15 |
|
30.15 |
30.15 |
Fins per In. |
20 |
20 |
|
20 |
20 |
Rows |
2 |
2 |
|
2 |
2 |
Circuits |
8 |
8 |
|
8 |
8 |
VALVE CONNECT. (In. ID) |
|
|
|
|
|
Vapor |
7/8 |
7/8 |
|
7/8 |
7/8 |
Liquid |
|
|
3/8 |
|
|
REFRIGERANT TUBES* (In. OD) |
|
|
|
|
|
Vapor (0---80 Ft Tube Length) |
7/8 |
7/8 |
|
1---1/8 |
1---1/8 |
Liquid (0---80 Ft Tube Length) |
|
|
3/8 |
|
*Units are rated with 25 ft (7.6 m) of lineset length. See Vapor Line Sizing and Cooling Capacity Loss table when using other sizes and lengths of lineset.
4
ELECTRICAL DATA
Unit Size --- |
|
|
|
|
|
|
|
MIN |
MIN |
MAX |
MAX |
MAX |
|
V/PH |
OPER VOLTS* |
COMPR |
FAN |
MCA |
WIRE |
WIRE |
LENGTH |
LENGTH |
FUSE** or |
||||
Voltage, |
|
|
|
|
|
SIZE{ |
SIZE{ |
ft. (m)} |
ft. (m)} |
CKT BRK |
|||
Series |
|
|
|
|
|
|
|
||||||
|
|
|
|
|
|
|
|
|
|
|
AMPS |
||
|
MIN |
MAX |
LRA |
RLA |
FLA |
|
60 C |
75 C |
60 C |
75 C |
|||
|
|
|
|||||||||||
|
|
|
|
||||||||||
24---31 |
|
|
|
58.3 |
11.1 |
1.8 |
15.7 |
14 |
14 |
50 (15.2) |
48 (14.6) |
25 |
|
36---31 |
208---230/1 |
253 |
197 |
83.0 |
15.3 |
2.0 |
21.1 |
12 |
12 |
59 (18.0) |
56 (17.1) |
30 |
|
48---31 |
104.0 |
21.2 |
2.7 |
29.2 |
10 |
10 |
68 (20.7) |
65 (19.8) |
40 |
||||
|
|
|
|||||||||||
60---31 |
|
|
|
152.9 |
28.8 |
2.7 |
38.7 |
8 |
8 |
80 (24.4) |
76 (23.2) |
60 |
* Permissible limits of the voltage range at which the unit will operate satisfactorily
{If wire is applied at ambient greater than 30_C, consult table 310---16 of the NEC (NFPA 70). The ampacity of non---metallic---sheathed cable (NM), trade name ROMEX, shall be that of 60_C conditions, per the NEC (NFPA 70) Article 336---26. If other than uncoated (no---plated), 60 or 75_C insulation, copper
wire (solid wire for 10 AWG or smaller, stranded wire for larger than 10 AWG) is used, consult applicable tables of the NEC (NFPA 70).
}Length shown is as measured one way along wire path between unit and service panel for voltage drop not to exceed 2%.
**Time---Delay fuse.
FLA --- Full Load Amps LRA --- Locked Rotor Amps
MCA --- Minimum Circuit Amps RLA --- Rated Load Amps
NOTE: Control circuit is 24---V on all units and requires external power source. Copper wire must be used from service disconnect to unit. All motors/compressors contain internal overload protection.
Complies with 2010 requirements of ASHRAE Standards 90.1
A-WEIGHTED SOUND POWER (dBA)
Unit Size --- |
Standard Rating |
|
Typical Octave Band Spectrum (dBA, without tone adjustment) |
|
||||||
Voltage, Series |
|
(dBA) |
125 |
250 |
500 |
1000 |
2000 |
4000 |
8000 |
|
|
|
|
|
|
|
|
|
|
|
|
24---31 |
71 |
--- High Stage |
49.5 |
56.0 |
60.5 |
67.5 |
58.0 |
53.5 |
53.0 |
|
65 |
--- Low Stage |
47.0 |
52.0 |
56.5 |
60.5 |
55.0 |
50.0 |
49.0 |
||
|
||||||||||
36---31 |
68 |
--- High Stage |
47.5 |
53.0 |
60.0 |
60.0 |
56.0 |
52.0 |
51.0 |
|
66 |
--- Low Stage |
46.5 |
54.5 |
56.0 |
56.5 |
53.0 |
50.0 |
48.0 |
||
|
||||||||||
48---31 |
69 |
--- High Stage |
49.0 |
61.5 |
62.0 |
62.0 |
59.5 |
54.5 |
49.5 |
|
66 |
--- Low Stage |
48.5 |
59.5 |
59.0 |
59.5 |
56.5 |
51.5 |
48.5 |
||
|
||||||||||
60---31 |
69 |
--- High Stage |
50.8 |
57.5 |
60.5 |
63.0 |
59.5 |
57.5 |
54.5 |
|
68 |
--- Low Stage |
48.0 |
56.0 |
59.0 |
62.0 |
57.5 |
55.5 |
52.0 |
||
|
NOTE: Tested in accordance with AHRI Standard 270---08. (Not listed with AHRI).
CHARGING SUBCOOLING (TXV-TYPE EXPANSION DEVICE)
UNIT SIZE---VOLTAGE, SERIES |
REQUIRED SUBCOOLING _F (_C) |
24---31 |
10 (5.6) |
36---31 |
11 (6.1) |
48---31 |
12 (6.7) |
60---31 |
14 (7.8) |
ACCESSORY CONTROLS
PART NUMBER |
DESCRIPTION |
|
|
|
|
SYSTXCCITN01 |
Infinity Touch Control (non---Wi---Fi) |
|
|
|
|
SYSTXCCITW01 |
Infinity Touch Control with Wi---Fi & Wireless Access Point |
|
|
|
|
SYSTXCC4ZC01 |
Infinity 4---Zone Damper Control Module (Wall---mounted control for a four---zone system.) |
|
|
|
|
SYSTXCCSMS01 |
Infinity Smart Sensor (Optional wall control used to monitor temperature and/or fan control in an individual zone.) |
|
SYSTXCCRRS01 |
Infinity Remote Room Sensor (Monitors temperature in an individual zone.) |
|
SYSTXCCRCT01 or |
Infinity System Remote Access Module (Hardware for wireless access and control via internet.) |
|
SYSTXCCRWF01 |
||
|
||
|
|
|
SYSTXCCNIM01 |
Infinity Network Interface Module (Connects Heat Recovery and Energy Recovery Ventilators on non---zoning applications.) |
|
|
|
5
24ANB1
ACCESSORIES
|
|
ORDER NUMBER |
|
|
DESCRIPTION |
24---31 |
|
36---31 |
48---31 |
|
60---31 |
||
|
|
KAALS0201LLS |
LIQUID LINE SOLENOID VALVE KIT |
X |
|
X |
|
X |
|
X |
|||
|
|
KSAHS2501AAA* |
HARD START KIT |
X |
|
X |
|
|
|
|
|||
|
|
KSAHS2801AAA* |
HARD START KIT |
|
|
|
|
X |
|
X |
|||
|
|
KSASF0101AAA |
SUPPORT FEET |
X |
|
X |
|
X |
|
X |
|||
|
|
x = Accessory |
|
|
|
|
|
|
|
|
|
|
|
|
|
* Not backward compatible to previous series |
|
|
|
|
|
|
|
|
|
||
|
|
ACCESSORY USAGE GUIDELINE |
|
|
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
REQUIRED FOR |
|
|
|
|
|
REQUIRED FOR SEA COAST |
||
|
|
|
|
|
LOW---AMBIENT COOLING |
|
REQUIRED FOR LONG LINE |
|
|||||
|
|
ACCESSORY |
|
|
|
|
APPLICATIONS |
||||||
|
|
|
|
APPLICATIONS |
|
APPLICATIONS* |
|
||||||
|
|
|
|
|
|
|
(Within 2 miles/3.22 km) |
||||||
|
|
|
|
|
(Below 55 F/12.8_C) |
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Compressor Start Assist Kit |
|
|
No |
|
No |
|
|
|
No |
||
|
|
Crankcase Heater |
|
|
Yes |
|
Yes |
|
|
|
No |
||
|
|
|
|
(standard on some units) |
|
(standard on some units) |
|
|
|||||
|
|
|
|
|
|
|
|
|
|
||||
|
|
Evaporator Freeze Protection |
|
|
Standard with Infinity Control |
|
No |
|
|
|
No |
||
|
|
Liquid---Line Solenoid Valve |
|
|
No |
|
No |
|
|
|
No |
||
24ANB1 |
Low---Ambient Control |
|
|
Standard with Infinity Control |
|
No |
|
|
|
No |
|||
|
|
Puron Refrigerant Balance Port Hard--- |
|
Yes{ |
|
Yes{ |
|
|
|
Yes{ |
|||
|
|
ShutOff TXV |
|
|
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Support Feet |
|
|
Recommended |
|
No |
|
|
Recommended |
|||
|
|
Winter Start Control |
|
|
Standard with Infinity Control |
|
No |
|
|
|
No |
*For tubing set lengths between 80 and 200 ft. (24.38 and 60.96 m) horizontal or 35 ft. (10.7 m) vertical differential (total equivalent length), refer to the Long Line Guideline—Air Conditioners and Heat Pumps using Puron® Refrigerant.
{Required on all indoor units. Standard on all new Puron refrigerant fan coils and furnace coils.
Accessory Description and Usage (Listed Alphabetically)
1. Compressor Start Assist - Capacitor and Relay |
3. Support Feet |
Start capacitor and relay gives a ”hard” boost to compressor motor at each start up.
Usage Guideline:
Not required on this unit since compressor always starts unloaded.
Available if required by local codes.
2. Crankcase Heater
An electric resistance heater which mounts to the base of the compressor to keep the lubricant warm during off cycles. Improves compressor lubrication on restart and minimizes the chance of liquid slugging.
Usage Guideline:
Required in low ambient cooling applications. Required in long line applications.
Suggested in all commercial applications.
Four stick-on plastic feet that raise the unit 4 in. (101.6 mm) above the mounting pad. This allows sand, dirt, and other debris to be flushed from the unit base, minimizing corrosion.
Usage Guideline:
Suggested in the following applications: Coastal installations.
Windy areas or where debris is normally circulating. Rooftop installations.
For improved sound ratings.
4. Thermostatic Expansion Valve (TXV)
A modulating flow-control valve which meters refrigerant liquid flow rate into the evaporator in response to the superheat of the refrigerant gas leaving the evaporator.
Kit includes valve, adapter tubes, and external equalizer tube. Hard shut off types are available.
NOTE: When using a hard shut off TXV with single phase reciprocating compressors, a Compressor Start Assist Capacitor and Relay is required.
Usage Guideline:
Required to achieve AHRI ratings in certain equipment combinations. Refer to combination ratings.
Hard shut off TXV or LLS required in air conditioner long line applications.
6