Carrier 24ANB1 Product data

0 (0)
Carrier 24ANB1 Product data

24ANB1

Infinityr 21 2---Stage Air Conditioner

with Puronr Refrigerant

2 to 5 Nominal Tons

Product Data

Carrier’s Air Conditioners with Puronr refrigerant provide a collection of features unmatched by any other family of equipment. The 24ANB1 has been designed utilizing Carrier’s Puron refrigerant. The environmentally sound refrigerant allows you to make a responsible decision in the protection of the earth’s ozone layer.

This product has been designed and manufactured to meet Energy Starr criteria for energy efficiency when matched with appropriate coil components. Refer to the combination ratings in the Product Data for system combinations that meet Energy Starr guidelines.

NOTE: Ratings contained in this document are subject to change at any time. Always refer to the AHRI directory (www.ahridirectory.org) for the most up-to-date ratings information.

INDUSTRY LEADING FEATURES / BENEFITS

Efficiency

S 14.5 - 21 SEER / 11.7 - 15 EER

S Microtube Technologyt refrigeration system

S Indoor air quality accessories available

Sound

S Sound level as low as 65 dBA

S Quiet mount split post compressor grommets

SElectronic ECM ball bearing outdoor condenser fan motor

S Forward-swept condenser fan blade S Compressor sound hood

S Laminated steel compressor mounting plate

Comfort

SSystem supports Infinityt Control or standard 2-stage thermostat controls

Reliability

SPuronr refrigerant - environmentally sound, won’t deplete the ozone layer and low lifetime service cost.

S Front-seating service valves S 2-stage scroll compressor S Internal pressure relief valve S Internal thermal overload

S Low pressure switch S High pressure switch S Filter drier

S Crankcase heater standard

S Balanced refrigeration system for maximum reliability

Controls and Diagnostics

S Infinityt control or 2-stage thermostat

STwo control wires to outdoor unit with Infinity Control (serial numbers 1213E and newer)

S Utility Interface Connection

S Enhanced diagnostics capability with Infinity Control

Durability

WeatherArmor Ultrat protection package:

S Solid, Durable sheet metal construction S Steel louver coil guard

S Baked-on, complete outer coverage, powder paint

Applications

SLong-line - up to 250 feet (76.2 m) total equivalent length, up to 200 feet (60.96 m) condenser above evaporator, or up to 80 ft. (24.38 m) evaporator above condenser (See Longline Guide for more information.)

SLow ambient (down to 0_F) with complete Infinity system.

MODEL NUMBER NOMENCLATURE

1

2

3

4

5

6

7

8

9

10

11

12

13

N

N

A

A

A/N

N

N

N

A/N

A/N

A/N

N

N

2

4

A

N

B

1

3

6

A

0

0

3

0

Product

Product

Tier

Major

SEER

Cooling

Variations

Open

Open

Voltage

Minor

Series

Family

 

Series

 

Capacity

 

 

 

 

Series

24=AC

A=RES AC

N =

B=Puron

1=21

 

 

A=Standard

0=Not

0=Not 3=208---230---1

0, 1, 2...

 

 

 

Infinity

 

SEER

 

 

 

Defined

Defined

 

 

 

 

 

 

 

Nominal

 

 

 

 

 

 

 

24ANB1

the environmentally sound refrigerant

Use of the AHRI Certified

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TM Mark indicates a

 

 

 

 

 

 

 

 

 

 

 

manufacturer’s

 

 

 

 

 

 

 

 

 

This product has been designed and manufactured to

 

participation in the

 

 

 

 

 

 

 

 

 

 

program For verification

 

 

 

 

 

 

 

 

 

meet Energy Star criteria for energy efficiency when

 

 

 

 

 

 

 

 

 

 

matched with appropriate coil components. However,

 

of certification for individual

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

proper refrigerant charge and proper air flow are critical

 

products, go to

 

 

 

 

 

 

 

 

 

to achieve rated capacity and efficiency. Installation of

 

 

 

 

 

 

 

 

 

 

 

www.ahridirectory.org.

 

 

 

 

 

 

 

 

 

this product should follow all manufacturing refrigerant

 

 

 

 

 

 

 

 

 

 

charging and air flow instructions. Failure to confirm

 

 

 

 

 

 

 

 

 

 

 

proper charge and air flow may reduce energy

 

 

 

 

 

 

 

 

 

 

 

efficiency and shorten equipment life.

STANDARD FEATURES

FEATURES

 

Unit Size --- Voltage, Series

 

 

 

 

 

24---31

36---31

48---31

60---31

 

 

 

 

 

 

Puron Refrigerant

X

X

X

X

 

 

 

 

 

Maximum SEER Rating*

21.0

20.0

18.0

16.7

 

 

 

 

 

2---Stage Scroll Compressor

X

X

X

X

 

 

 

 

 

2 control wires to outdoor unit with Infinity Control

X

X

X

X

(serial numbers 1213E and newer)

 

 

 

 

 

 

 

 

 

Crankcase Heater

X

X

X

X

 

 

 

 

 

Low Ambient Capability to 0_F (---17.8_C) w/Infinity Control

X

X

X

X

 

 

 

 

 

Enhanced Diagnostics w/Infinity Control

X

X

X

X

 

 

 

 

 

Utility Interface Connection

X

X

X

X

 

 

 

 

 

Louvered Coil Guard

X

X

X

X

 

 

 

 

 

Field Installed Filter Drier

X

X

X

X

 

 

 

 

 

Front Seating Service Valves

X

X

X

X

 

 

 

 

 

Internal Pressure Relief Valve

X

X

X

X

 

 

 

 

 

Internal Thermal Overload

X

X

X

X

 

 

 

 

 

Long Line Capability

X

X

X

X

 

 

 

 

 

Low Pressure Switch

X

X

X

X

 

 

 

 

 

High Pressure Switch

X

X

X

X

 

 

 

 

 

Sound Blanket

X

X

X

X

 

 

 

 

 

X = Standard

* With approved combinations

2

REFRIGERANT PIPING LENGTH LIMITATIONS

Liquid Line Sizing and Maximum Total Equivalent Lengths{ for Cooling Only Systems with Puronr Refrigerant:

The maximum allowable length of a residential split system depends on the liquid line diameter and vertical separation between indoor and outdoor units.

See Table below for liquid line sizing and maximum lengths :

Maximum Total Equivalent Length

Outdoor Unit BELOW Indoor Unit

 

 

Liquid

 

 

AC with Puron Refrigerant Maximum Total Equivalent Length{: Outdoor unit BELOW Indoor

 

 

Size

Liquid Line

Line

 

 

 

 

 

 

 

Vertical Separation ft (m)

 

 

 

 

 

 

Connection

Diam.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

5

6

10

11

20

21

30

31

40

41

50

51

60

61

70

71

80

 

 

 

w/TXV

(0---

1.5)

(1.8---

3.0)

(3.4---

6.1)

(6.4---

9.1)

(9.4---

12.2)

(12.5---

15.2)

(15.5---

18.3)

(18.6---

21.3)

(21.6---

24.4)

024

 

1/4

75

75

75

50

50

--- ---

 

--- ---

--- ---

--- ---

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AC with

3/8

5/16

250*

250*

250*

250*

250*

225*

175

125

100

Puron

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3/8

250*

250*

250*

250*

250*

250*

250*

250*

250*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

036

 

5/16

175

150

150

100

100

100

75

 

 

--- ---

AC with

3/8

--- ---

 

3/8

250*

250*

250*

250*

250*

250*

250*

250*

250*

Puron

 

048

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AC with

3/8

3/8

250*

250*

250*

250*

250*

250*

230

160

--- ---

 

Puron

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

060

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AC with

3/8

3/8

250*

250*

250*

225*

190

150

110

--- ---

 

--- ---

Puron

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

* Maximum actual length not to exceed 200 ft (61 m)

{Total equivalent length accounts for losses due to elbows or fitting. See the Long Line Guideline for details.

------ = outside acceptable range

Maximum Total Equivalent Length

Outdoor Unit ABOVE Indoor Unit

 

 

Liquid

 

AC with Puron Refrigerant Maximum Total Equivalent Length{: Outdoor unit ABOVE Indoor

Size

Liquid Line

Line

 

 

 

Vertical Separation ft (m)

 

 

 

Connection

Diam.

 

 

 

 

 

 

 

 

25

26---50

51---75

76---100

101---125

126---150

151---175

176---200

 

 

 

w/TXV

(7.6)

(7.9---15.2)

(15.5---22.9)

(23.2---30.5)

(30.8---38.1)

(38.4---45.7)

(46.0---53.3)

(53.6---61.0)

024

 

1/4

100

125

175

200

225*

250*

250*

250*

AC with

3/8

5/16

250*

250*

250*

250*

250*

250*

250*

250*

Puron

 

 

 

 

 

 

 

 

 

 

 

3/8

250*

250*

250*

250*

250*

250*

250*

250*

036

 

5/16

225*

250*

250*

250*

250*

250*

250*

250*

AC with

3/8

 

 

 

 

 

 

 

 

 

3/8

250*

250*

250*

250*

250*

250*

250*

250*

Puron

 

048

 

 

 

 

 

 

 

 

 

 

AC with

3/8

3/8

250*

250*

250*

250*

250*

250*

250*

250*

Puron

 

 

 

 

 

 

 

 

 

 

060

 

 

 

 

 

 

 

 

 

 

AC with

3/8

3/8

250*

250*

250*

250*

250*

250*

250*

250*

Puron

 

 

 

 

 

 

 

 

 

 

* Maximum actual length not to exceed 200 ft (61 m)

{ Total equivalent length accounts for losses due to elbows or fitting. See the Long Line Guideline for details.

REFRIGERANT CHARGE ADJUSTMENTS

Liquid Line Size

Puron Charge oz/ft (g/m)

3/8

0.60 (17.74)

(Factory charge for lineset = 9 oz / 266.16 g)

 

 

 

5/16

0.40 (11.83)

 

 

1/4

0.27 (7.98)

 

 

Units are factory charged for 15 ft (4.6 m) of 3/8” liquid line. The factory charge for 3/8” lineset 9 oz.(266.16 g). When using other length or diameter liquid lines, charge adjustments are required per the chart above.

Charging Formula:

[(Lineset oz/ft x total length) – (factory charge for lineset)] = charge adjustment

Example 1: System has 15 ft of line set using existing 1/4“ liquid line. What charge adjustment is required? Formula: (.27 oz/ft x 15ft) – (9 oz) = (-4.95) oz.

Net result is to remove 4.95 oz of refrigerant from the system

Example 2: System has 45 ft of existing 5/16” liquid line. What is the charge adjustment? Formula: (.40 oz/ft. x 45ft) – (9 oz.) = 9 oz.

Net result is to add 9 oz of refrigerant to the system

3

24ANB1

24ANB1

LONG LINE APPLICATIONS

An application is considered Long Line, when the refrigerant level in the system requires the use of accessories to maintain acceptable refrigerant management for systems reliability. See Accessory Usage Guideline table for required accessories. Defining a system as long line depends on the liquid line diameter, actual length of the tubing, and vertical separation between the indoor and outdoor units.

For Air Conditioner systems, the chart below shows when an application is considered Long Line.

AC WITH PURONr REFRIGERANT LONG LINE DESCRIPTION ft (m)

Beyond these lengths, long line accessories are required

Liquid Line Size

Units On Same Level

Outdoor Below Indoor

Outdoor Above Indoor

1/4

No accessories needed within allowed

No accessories needed within allowed

175 (53.3)

lengths

lengths

 

 

5/16

120 (36.6)

50 (15.2) vertical or 120 (36.6) total

120 (36.6)

3/8

80 (24.4)

35 (10.7) vertical or 80 24.4) total

80 (24.4)

Note: See Long Line Guideline for details

VAPOR LINE SIZING AND COOLING CAPACITY LOSS

Acceptable vapor line diameters provide adequate oil return to the compressor while avoiding excessive capacity loss. The suction line diameters shown in the chart below are acceptable for AC systems with Puron refrigerant:

Vapor Line Sizing and Cooling Capacity Losses — Puronr Refrigerant 2-Stage Air Conditioner Applications

 

Unit

Maximum

Vapor Line

 

 

 

Cooling Capacity Loss (%)

 

 

 

 

Liquid

 

 

 

Total Equivalent Line Length ft. (m)

 

 

 

 

Nominal

Line

Diameters

 

 

 

 

 

 

 

 

 

 

Size (Btuh)

Diameters

(In.) OD

26---50

51---80

81---100

101---125

126---150

151---175

176---200

201---225

226---250

 

 

(In. OD)

 

(7.9---15.2)

(15.5---24.4)

(24.7---30.5)

(30.8---38.1)

(38.4---45.7)

(46.0---50.3)

(53.6---60.0)

(61.3---68.6)

(68.9---76.2)

 

024

 

5/8

0

1

1

2

3

3

4

4

5

 

2---Stage

 

 

3/8

 

 

 

 

 

 

 

 

 

 

 

Puron

3/4

0

0

0

0

1

1

1

1

1

 

 

 

AC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

036

 

5/8

1

2

4

5

6

7

9

10

11

 

2---Stage

3/8

3/4

0

0

1

1

2

2

3

3

4

 

Puron

 

AC

 

7/8

0

0

0

0

1

1

1

1

2

 

048

 

3/4

1

2

2

3

4

5

6

7

7

 

2---Stage

 

 

 

 

 

 

 

 

 

 

 

 

3/8

7/8

0

1

1

2

2

2

3

3

3

 

Puron

 

AC

 

1---1/8

0

0

 

060

 

3/4

1

2

4

5

6

7

9

10

11

 

2---Stage

 

 

 

 

 

 

 

 

 

 

 

 

3/8

7/8

0

1

2

2

3

4

4

5

5

 

Puron

 

AC

 

1---1/8

0

0

0

1

1

1

1

1

1

 

Applications in

this area may

be long line and may have height restrictions. See the Residential Piping and Long Line Guideline.

 

 

 

— Applications in this area are not recommended due to insufficient oil return

 

 

 

 

 

 

PHYSICAL DATA

UNIT SIZE --- VOLTAGE, SERIES

24---31

36---31

 

48---31

60---31

Operating Weight lb (kg)

282 (127.9)

312 (141.5)

 

335 (152.0)

336 (152.4)

Shipping Weight lb (kg)

324 (147.0)

357 (161.9)

 

381 (172.8)

381 (172.8)

Compressor Type

 

2---Stage Scroll

 

REFRIGERANT

 

Puron (R---410A)

 

Control

 

TXV (Puron Hard Shutoff)

 

Charge lb. (kg)

13.34 (6.05)

13.66 (6.20)

 

13.53 (6.14)

14.33 (6.50)

COND FAN

 

Forward Swept Propeller Type, Direct Drive

 

Air Discharge

 

 

Vertical

 

Air Qty (CFM)

3040 / 3637

3124 / 3700

 

3703 / 4309

4209 / 4668

Motor HP

1/5

1/5

 

1/5

1/5

Motor RPM

628 / 752

582 / 689

 

659 / 765

742 / 828

COND COIL

 

 

 

 

 

Face Area (sq. ft.)

25.12

30.15

 

30.15

30.15

Fins per In.

20

20

 

20

20

Rows

2

2

 

2

2

Circuits

8

8

 

8

8

VALVE CONNECT. (In. ID)

 

 

 

 

 

Vapor

7/8

7/8

 

7/8

7/8

Liquid

 

 

3/8

 

REFRIGERANT TUBES* (In. OD)

 

 

 

 

 

Vapor (0---80 Ft Tube Length)

7/8

7/8

 

1---1/8

1---1/8

Liquid (0---80 Ft Tube Length)

 

 

3/8

 

*Units are rated with 25 ft (7.6 m) of lineset length. See Vapor Line Sizing and Cooling Capacity Loss table when using other sizes and lengths of lineset.

4

ELECTRICAL DATA

Unit Size ---

 

 

 

 

 

 

 

MIN

MIN

MAX

MAX

MAX

V/PH

OPER VOLTS*

COMPR

FAN

MCA

WIRE

WIRE

LENGTH

LENGTH

FUSE** or

Voltage,

 

 

 

 

 

SIZE{

SIZE{

ft. (m)}

ft. (m)}

CKT BRK

Series

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AMPS

 

MIN

MAX

LRA

RLA

FLA

 

60 C

75 C

60 C

75 C

 

 

 

 

 

 

 

24---31

 

 

 

58.3

11.1

1.8

15.7

14

14

50 (15.2)

48 (14.6)

25

36---31

208---230/1

253

197

83.0

15.3

2.0

21.1

12

12

59 (18.0)

56 (17.1)

30

48---31

104.0

21.2

2.7

29.2

10

10

68 (20.7)

65 (19.8)

40

 

 

 

60---31

 

 

 

152.9

28.8

2.7

38.7

8

8

80 (24.4)

76 (23.2)

60

* Permissible limits of the voltage range at which the unit will operate satisfactorily

{If wire is applied at ambient greater than 30_C, consult table 310---16 of the NEC (NFPA 70). The ampacity of non---metallic---sheathed cable (NM), trade name ROMEX, shall be that of 60_C conditions, per the NEC (NFPA 70) Article 336---26. If other than uncoated (no---plated), 60 or 75_C insulation, copper

wire (solid wire for 10 AWG or smaller, stranded wire for larger than 10 AWG) is used, consult applicable tables of the NEC (NFPA 70).

}Length shown is as measured one way along wire path between unit and service panel for voltage drop not to exceed 2%.

**Time---Delay fuse.

FLA --- Full Load Amps LRA --- Locked Rotor Amps

MCA --- Minimum Circuit Amps RLA --- Rated Load Amps

NOTE: Control circuit is 24---V on all units and requires external power source. Copper wire must be used from service disconnect to unit. All motors/compressors contain internal overload protection.

Complies with 2010 requirements of ASHRAE Standards 90.1

A-WEIGHTED SOUND POWER (dBA)

Unit Size ---

Standard Rating

 

Typical Octave Band Spectrum (dBA, without tone adjustment)

 

Voltage, Series

 

(dBA)

125

250

500

1000

2000

4000

8000

 

 

 

 

 

 

 

 

 

 

24---31

71

--- High Stage

49.5

56.0

60.5

67.5

58.0

53.5

53.0

65

--- Low Stage

47.0

52.0

56.5

60.5

55.0

50.0

49.0

 

36---31

68

--- High Stage

47.5

53.0

60.0

60.0

56.0

52.0

51.0

66

--- Low Stage

46.5

54.5

56.0

56.5

53.0

50.0

48.0

 

48---31

69

--- High Stage

49.0

61.5

62.0

62.0

59.5

54.5

49.5

66

--- Low Stage

48.5

59.5

59.0

59.5

56.5

51.5

48.5

 

60---31

69

--- High Stage

50.8

57.5

60.5

63.0

59.5

57.5

54.5

68

--- Low Stage

48.0

56.0

59.0

62.0

57.5

55.5

52.0

 

NOTE: Tested in accordance with AHRI Standard 270---08. (Not listed with AHRI).

CHARGING SUBCOOLING (TXV-TYPE EXPANSION DEVICE)

UNIT SIZE---VOLTAGE, SERIES

REQUIRED SUBCOOLING _F (_C)

24---31

10 (5.6)

36---31

11 (6.1)

48---31

12 (6.7)

60---31

14 (7.8)

ACCESSORY CONTROLS

PART NUMBER

DESCRIPTION

 

 

SYSTXCCITN01

Infinity Touch Control (non---Wi---Fi)

 

 

SYSTXCCITW01

Infinity Touch Control with Wi---Fi & Wireless Access Point

 

 

SYSTXCC4ZC01

Infinity 4---Zone Damper Control Module (Wall---mounted control for a four---zone system.)

 

 

SYSTXCCSMS01

Infinity Smart Sensor (Optional wall control used to monitor temperature and/or fan control in an individual zone.)

SYSTXCCRRS01

Infinity Remote Room Sensor (Monitors temperature in an individual zone.)

SYSTXCCRCT01 or

Infinity System Remote Access Module (Hardware for wireless access and control via internet.)

SYSTXCCRWF01

 

 

 

SYSTXCCNIM01

Infinity Network Interface Module (Connects Heat Recovery and Energy Recovery Ventilators on non---zoning applications.)

 

 

5

24ANB1

ACCESSORIES

 

 

ORDER NUMBER

 

 

DESCRIPTION

24---31

 

36---31

48---31

 

60---31

 

 

KAALS0201LLS

LIQUID LINE SOLENOID VALVE KIT

X

 

X

 

X

 

X

 

 

KSAHS2501AAA*

HARD START KIT

X

 

X

 

 

 

 

 

 

KSAHS2801AAA*

HARD START KIT

 

 

 

 

X

 

X

 

 

KSASF0101AAA

SUPPORT FEET

X

 

X

 

X

 

X

 

 

x = Accessory

 

 

 

 

 

 

 

 

 

 

 

 

 

* Not backward compatible to previous series

 

 

 

 

 

 

 

 

 

 

 

ACCESSORY USAGE GUIDELINE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

REQUIRED FOR

 

 

 

 

 

REQUIRED FOR SEA COAST

 

 

 

 

 

LOW---AMBIENT COOLING

 

REQUIRED FOR LONG LINE

 

 

 

ACCESSORY

 

 

 

 

APPLICATIONS

 

 

 

 

APPLICATIONS

 

APPLICATIONS*

 

 

 

 

 

 

 

 

(Within 2 miles/3.22 km)

 

 

 

 

 

(Below 55 F/12.8_C)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor Start Assist Kit

 

 

No

 

No

 

 

 

No

 

 

Crankcase Heater

 

 

Yes

 

Yes

 

 

 

No

 

 

 

 

(standard on some units)

 

(standard on some units)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Evaporator Freeze Protection

 

 

Standard with Infinity Control

 

No

 

 

 

No

 

 

Liquid---Line Solenoid Valve

 

 

No

 

No

 

 

 

No

24ANB1

Low---Ambient Control

 

 

Standard with Infinity Control

 

No

 

 

 

No

 

 

Puron Refrigerant Balance Port Hard---

 

Yes{

 

Yes{

 

 

 

Yes{

 

 

ShutOff TXV

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Support Feet

 

 

Recommended

 

No

 

 

Recommended

 

 

Winter Start Control

 

 

Standard with Infinity Control

 

No

 

 

 

No

*For tubing set lengths between 80 and 200 ft. (24.38 and 60.96 m) horizontal or 35 ft. (10.7 m) vertical differential (total equivalent length), refer to the Long Line Guideline—Air Conditioners and Heat Pumps using Puron® Refrigerant.

{Required on all indoor units. Standard on all new Puron refrigerant fan coils and furnace coils.

Accessory Description and Usage (Listed Alphabetically)

1. Compressor Start Assist - Capacitor and Relay

3. Support Feet

Start capacitor and relay gives a ”hard” boost to compressor motor at each start up.

Usage Guideline:

Not required on this unit since compressor always starts unloaded.

Available if required by local codes.

2. Crankcase Heater

An electric resistance heater which mounts to the base of the compressor to keep the lubricant warm during off cycles. Improves compressor lubrication on restart and minimizes the chance of liquid slugging.

Usage Guideline:

Required in low ambient cooling applications. Required in long line applications.

Suggested in all commercial applications.

Four stick-on plastic feet that raise the unit 4 in. (101.6 mm) above the mounting pad. This allows sand, dirt, and other debris to be flushed from the unit base, minimizing corrosion.

Usage Guideline:

Suggested in the following applications: Coastal installations.

Windy areas or where debris is normally circulating. Rooftop installations.

For improved sound ratings.

4. Thermostatic Expansion Valve (TXV)

A modulating flow-control valve which meters refrigerant liquid flow rate into the evaporator in response to the superheat of the refrigerant gas leaving the evaporator.

Kit includes valve, adapter tubes, and external equalizer tube. Hard shut off types are available.

NOTE: When using a hard shut off TXV with single phase reciprocating compressors, a Compressor Start Assist Capacitor and Relay is required.

Usage Guideline:

Required to achieve AHRI ratings in certain equipment combinations. Refer to combination ratings.

Hard shut off TXV or LLS required in air conditioner long line applications.

6