Toshiba Super MMU-AP0301H, Super MMU-AP0121H, Super MMU-AP0361H, Super MMU-AP0481H, Super MMU-AP0561H Service Manual

...
0 (0)
FILE NO. A03-009
PRINTED IN JAPAN, May.,2004 ToMo
Indoor Unit
<4-way Air Discharge Cassette Type>
MMU-AP0091H, AP0121H, AP0151H, MMU-AP0181H, AP0241H, AP0271H, MMU-AP0301H, AP0361H, AP0481H MMU-AP0561H
<2-way Air Discharge Cassette Type>
MMU-AP0481WH (CHINA market only)
<1-way Air Discharge Cassette Type>
MMU-AP0071YH, AP0091YH, AP0121YH, MMU-AP0151SH, AP0181SH, AP0241SH
<Concealed Duct Standard Type>
MMD-AP0071BH, AP0091BH, AP0121BH, MMD-AP0151BH, AP0181BH, AP0241BH, MMD-AP0271BH, AP0301BH, AP0361BH, MMD-AP0481BH, AP0561BH
<Concealed Duct High Static Pressure Type>
MMD-AP0181H, AP0241H, AP0271H, MMD-AP0361H, AP0481H, AP0721H, MMD-AP0961H
<Under Ceiling Type>
MMC-AP0151H, AP0181H, AP0241H, MMC-AP0271H, AP0361H, AP0481H
<High Wall Type>
MMK-AP0071H, AP0091H, AP0121H, MMK-AP0151H, AP0181H, AP0241H
<Floor Standing Cabinet Type>
MML-AP0071H, AP0091H, AP0121H, MML-AP0151H, AP0181H, AP0241H
<Floor Standing Concealed Type>
MML-AP0071BH, AP0091BH, AP0121BH, MML-AP0151BH, AP0181BH, AP0241BH
<Floor Standing Type>
MMF-AP0151H, AP0181H, AP0241H MMF-AP0271H, AP0361H, AP0481H MMF-AP0561H
Outdoor Unit
Cooling Only Model
<Inverter Unit>
MMY-MAP0501T8, MAP0601T8 MMY-MAP0801T8, MAP1001T8 MMY-MAP1201T8
Heat Pump Model
<Inverter Unit>
MMY-MAP0501HT8, MAP0601HT8 MMY-MAP0801HT8, MAP1001HT8 MMY-MAP1201HT8
Heat Pump Model
<Inverter Unit>
MMY-MAP0501HT7, MAP0601HT7 MMY-MAP0801HT7, MAP1001HT7 MMY-MAP1201HT7
SERVICE MANUAL
TENTATIVE
WARNINGS ON REFRIGERANT LEAKAGE
Outdoor unit
e.g., charged amount (15kg)
e.g., charged amount (10kg)
Indoor unit
Room A Room B Room C Room D Room E Room F
For the amount of charge in this example:
The possible amount of leaked refrigerant gas in rooms A, B and C is 10kg. The possible amount of leaked refrigerant gas in rooms D, E and F is 15kg.
NOTE : 2
The standards for minimum room volume are as follows.
(1) No partition (shaded portion)
Outdoor unit
Refrigerant piping
Indoor unit
(2) When there is an effective opening with the
adjacent room for ventilation of leaking refrigerant gas (opening without a door, or an opening 0.15% or larger than the respective floor spaces at the top or bottom of the door).
(3) If an indoor unit is installed in each partitioned
room and the refrigerant tubing is interconnected, the smallest room of course becomes the object. But when a mechanical ventilation is installed interlocked with a gas leakage detector in the smallest room where the density limit is exceeded, the volume of the next smallest room becomes the object.
Outdoor unit
Refrigerant piping
Indoor unit
Very small room
Small room
Medium room
Large room
Mechanical ventilation device - Gas leak detector
NOTE 3 : The minimum indoor floor area compared with the
amount of refrigerant is roughly as follows: (When the ceiling is 2.7m high)
0
5
10
10 20 30
15
20
25
30
35
40
Range below the density limit of 0.3 kg/m³ (countermeasures not needed)
Range above the density limit of 0.3 kg/m³ (countermeasures needed)
Total amount of refrigerant
kg
Min. indoor floor area
Check of Concentration Limit
The room in which the air conditioner is to be installed requires a design that in the event of refrigerant gas leaking out, its concentration will not exceed a set limit.
The refrigerant R410A which is used in the air conditioner is safe, without the toxicity or combustibility of ammonia, and is not restricted by laws to be imposed which protect the ozone layer. However, since it contains more than air, it poses the risk of suffocation if its concentration should rise excessively. Suffocation from leakage of R410A is almost non-existent. With the recent increase in the number of high concentration buildings, however, the installation of multi air conditioner systems is on the increase because of the need for effective use of floor space, individual control, energy conservation by curtailing heat and carrying power etc. Most importantly, the multi air conditioner system is able to replenish a large amount of refrigerant compared with conventional individual air conditioners. If a single unit of the multi conditioner system is to be installed in a small room, select a suitable model and installation procedure so that if the refrigerant accidentally leaks out, its concentration does not reach the limit (and in the event of an emergency, measures can be made before injury can occur). In a room where the concentration may exceed the limit, create an opening with adjacent rooms, or install mechanical ventilation combined with a gas leak detection device. The concentration is as given below.
Total amount of refrigerant (kg)
Min. volume of the indoor unit installed room (m³)
Concentration limit (kg/m³)
The concentration limit of R410A which is used in multi air conditioners is 0.3kg/m³.
NOTE 1 :
If there are 2 or more refrigerating systems in a single refrigerating device, the amounts of refrigerant should be as charged in each independent device.
Important
NOTE
A direct current motor is adopted for indoor fan motor in the Concealed Duct Standard Type air conditioner. Caused from its characteristics, a current limit works on the direct current motor. When replacing the high­performance filter or when opening the service board, be sure to stop the fan. If an above action is executed during the fan operation, the protective control works to stop the unit oper ation, and the check code “P12” may be issued. However it is not a trouble. When the desired operation has finished, be sure to reset the system to clear “P12” error code using the leak breaker of the indoor unit. Then push the operation stop button of the remote controller to return to the usual operation.
CONTENTS
SAFETY CAUTION ............................................................................................ 4
1. OUTLINE .................................................................................................. 10
2. WIRING DIAGRAM................................................................................... 13
3. PARTS RATING........................................................................................ 26
4. REFRIGERANT PIPING SYSTEMATIC DRAWING................................. 56
5. COMBINED REFRIGERANT PIPES SYSTEMATIC DRAWING.............. 59
6. CONTROL OUTLINE................................................................................ 64
7. APPLIED CONTROL................................................................................ 74
8. TEST OPERATION ................................................................................... 88
9. TROUBLESHOOTING............................................................................ 128
10. CONFIGURATION OF CONTROL CIRCUIT .......................................... 214
11. BACKUP OPERATIONS (EMERGENCY OPERATION) ........................ 228
12. OIL LEVEL JUDGMENT DISPLAY ........................................................ 233
13. REFRIGERANT RECOVERY
WHEN REPLACING THE COMPRESSOR ............................................ 234
14. LEAKAGE/CLOGGING OF OIL-EQUALIZATION CIRCUIT .................. 240
15. REPLACING COMPRESSOR................................................................ 242
16. REOLACING METHOD OF PARTS ....................................................... 249
17. P.C. BOARD EXCHANGE PROCEDURES ............................................ 259
4
SAFETY CAUTION
The important contents concerned to the safety are described on the product itself and on this Service Manual. Please read this Service Manual after understanding the described items thoroughly in the following contents
(Indications/Illustrated marks), and keep them.
[Explanation of indications]
Indication
DANGER
WARNING
CAUTION
Explanation
Indicates contents assumed that an imminent danger causing a death or serious injury of the repair engineers and the third parties when an incorrect work has been executed.
Indicates possibilities assumed that a danger causing a death or serious injury of the repair engineers, the third parties, and the users due to troubles of the product after work when an incorrect work has been executed.
Indicates contents assumed that an injury or property damage () may be caused on the repair engineers, the third parties, and the users due to troubles of the product after work when an incorrect work has been executed.
Property damage : Enlarged damage concerned to property, furniture, and domestic animal/pet
[Explanation of illustrated marks]
Mark Explanation
Indicates prohibited items (Forbidden items to do) The sentences near an illustrated mark describe the concrete prohibited contents.
Indicates mandatory items (Compulsory items to do) The sentences near an illustrated mark describe the concrete mandatory contents.
Indicates cautions (including danger/warning) The sentences or illustration near or in an illustrated mark describe the concrete cautious contents.
[Confirmation of warning label on the main unit]
Confirm that labels are indicated on the specified positions (Refer to the Parts disassembly diagram (Outdoor unit).)
If removing the label during parts replace, stick it as the original.
Turn “OFF” the breaker before removing the front panel and cabinet, otherwise an electric shock is caused by high voltage resulted in a death or injury.
During operation, a high voltage with 400V or higher of circuit () at secondary circuit of the high­voltage transfor mer is applied.
If touching a high voltage with the naked hands or body, an electr ic shock is caused even if using an electric insulator.
: For details, refer to the electric wiring diagram.
When removing the front panel or cabinet, execute short-circuit and discharge between high­voltage capacitor terminals.
If discharge is not executed, an electric shock is caused by high voltage resulted in a death or injury. After turning off the breaker, high voltage also keeps to apply to the high-voltage capacitor.
Do not turn on the breaker under condition that the front panel and cabinet are removed.
An electric shock is caused by high voltage resulted in a death or injury.
DANGER
Turn off breaker.
Execute discharge
between terminals.
Prohibition
5
Before troubleshooting or repair work, check the earth wire is connected to the earth terminals of the main unit, otherwise an electric shock is caused when a leak occur s.
If the earth wire is not correctly connected, contact an electric engineer for rework.
Do not modify the products.
Do not also disassemble or modify the parts. It may cause a fire, electric shock or injury.
For spare parts, use those specified (
∗∗
∗∗
∗).
If unspecified parts are used, a fire or electric shock may be caused. : For details, refer to the parts list.
Before troubleshooting or repair work, do not bring a third party (a child, etc.) except the repair engineers close to the equipment.
It causes an injury with tools or disassembled parts. Please inform the users so that the third party (a child, etc.) does not approach the equipment.
Connect the cut-off lead cables with crimp contact, etc, put the closed end side upward and then apply a water-cut method, otherwise a leak or production of fire is caused at the users’ side.
When repairing the refrigerating cycle, take the following measures.
1) Be attentive to fire around the cycle. When using a gas stove, etc, be sure to put out fire before work; otherwise the oil mixed with refrigerant gas may catch fire.
2) Do not use a welder in the closed room. When using it without ventilation, carbon monoxide poisoning may be caused.
3) Do not bring inflammables close to the refrigerant cycle, otherwise fire of the welder may catch the inflammables.
Check the used refrigerant name and use tools and materials of the parts which match with it.
For the products which use R410A refrigerant, the refrigerant name is indicated at a position on the outdoor unit where is easy to see. To prevent miss-charging, the route of the service por t is changed from one of the former R22.
For an air conditioner which uses R410A, never use other refrigerant than R410A. For an air conditioner which uses other refrigerant (R22, etc.), never use R410A.
If different types of refrigerant are mixed, abnormal high pressure generates in the refriger­ating cycle and an injury due to breakage may be caused.
Do not charge refrigerant additionally.
If charging refrigerant additionally when refrigerant gas leaks, the refrigerant composition in the refrigerating cycle changes resulted in change of air conditioner characteristics or refrigerant over the specified standard amount is charged and an abnormal high pressure is applied to the inside of the refrigerating cycle resulted in cause of breakage or injury. Therefore if the refrigerant gas leaks, recover the refrigerant in the air conditioner, execute vacuuming, and then newly recharge the specified amount of liquid refrigerant. In this time, never charge the refrigerant over the specified amount.
When recharging the refrigerant in the refrigerating cycle, do not mix the refrigerant or air other than R410A into the specified refrigerant.
If air or others is mixed with the refrigerant, abnormal high pressure generates in the refrigerating cycle resulted in cause of injury due to breakage.
After installation work, check the refrigerant gas does not leak.
If the refrigerant gas leaks in the room, poisonous gas generates when gas touches to fire such as fan heater, stove or cocking stove though the refrigerant gas itself is innocuous.
Never recover the refrigerant into the outdoor unit.
When the equipment is moved or repaired, be sure to recover the refrigerant with recover­ing device. The refrigerant cannot be recovered in the outdoor unit; otherwise a serious accident such as breakage or injury is caused.
After repair work, surely assemble the disassembled parts, and connect and lead the removed cables as before. Perform the work so that the cabinet or panel does not catch the inner cables.
If incorrect assembly or incorrect cable connection was done, a disaster such as a leak or fire is caused at user’s side.
WARNING
Check earth wires.
Prohibition of modification.
Use specified parts.
Do not bring a child
close to the equipment.
Insulating measures
No fire
Refrigerant
Assembly/Cabling
6
After the work has finished, be sure to use an insulation tester set (500V mugger) to check the resistance is 2M
ΩΩ
ΩΩ
or more between the charge section and the non-charge
metal section (Earth position).
If the resistance value is low, a disaster such as a leak or electric shock is caused at user’s side.
When the refrigerant gas leaks during work, execute ventilation.
If the refrigerant gas touches to a fire, poisonous gas generates. A case of leakage of the refrigerant and the closed room full with gas is dangerous because a shortage of oxygen occurs. Be sure to execute ventilation.
When checking the circuit inevitably under condition of the power-ON, use rubber gloves and others not to touch to the charging section.
If touching to the charging section, an electric shock may be caused.
When the refrigerant gas leaks, find up the leaked position and repair it surely.
If the leaked position cannot be found up and the repair work is interrupted, pump-down and tighten the service valve, otherwise the refrigerant gas may leak into the room. The poisonous gas generates when gas touches to fire such as fan heater, stove or cocking stove though the refrigerant gas itself is innocuous.
When installing equipment which includes a large amount of charged refrigerant such as a multi air conditioner in a sub-room, it is necessary that the density does not the limit even if the refrigerant leaks.
If the refrigerant leaks and exceeds the limit density, an accident of shortage of oxygen is caused.
For the installation/moving/reinstallation work, follow to the Installation Manual.
If an incorrect installation is done, a trouble of the refrigerating cycle, water leak, electric shock or fire is caused.
After repair work has finished, check there is no trouble.
If check is not executed, a fire, electric shock or injury may be caused. For a check, turn off the power breaker.
After repair work (installation of front panel and cabinet) has finished, execute a test run to check there is no generation of smoke or abnormal sound.
If check is not executed, a fire or an electric shock is caused. Before test run, install the front panel and cabinet.
Check the following items after reinstallation.
1) The earth wire is correctly connected.
2) The power cord is not caught in the product.
3) There is no inclination or unsteadiness and the installation is stable. If check is not executed, a fire, an electric shock or an injury is caused.
Be sure to put on gloves (
∗∗
∗∗
) during repair work.
If not putting on gloves, an injury may be caused with the parts, etc. () Heavy gloves such as work gloves
When the power was turned on, start to work after the equipment has been sufficiently cooled.
As temperature of the compressor pipes and others became high due to cooling/heating operation, a burn may be caused.
Insulator check
Ventilation
Be attentive to
electric shock
Compulsion
Check after rerair
Check after reinstallation
Put on gloves
Cooling check
WARNING
CAUTION
7
New Refrigerant (R410A)
This air conditioner adopts a new HFC type refrigerant (R410A) which does not deplete the ozone la yer.
1. Safety Caution Concerned to New Refrigerant
The pressure of R410A is high 1.6 times of that of the former refrigerant (R22). Accompanied with change of refrigerant, the refrigerating oil has been also changed. Therefore, be sure that water, dust, the former refriger­ant or the former refrigerating oil is not mixed into the refrigerating cycle of the air conditioner with new refriger­ant during installation work or service work. If an incorrect work or incorrect service is performed, there is a possibility to cause a serious accident. Use the tools and materials e xclusive to R410A to purpose a safe work.
2. Cautions on Installation/Service
(1) Do not mix the other refrigerant or refrigerating oil.
For the tools exclusive to R410A, shapes of all the joints including the service port differ from those of the former refrigerant in order to prevent mixture of them.
(2) As the use pressure of the new refrigerant is high, use material thickness of the pipe and tools which are
specified for R410A.
(3) In the installation time, use clean pipe materials and work with great attention so that water and others do
not mix in because pipes are affected by impurities such as water, oxide scales, oil, etc. Use the clean pipes.
Be sure to brazing with flowing nitrogen gas. (Never use gas other than nitrogen gas.) (4) For the earth protection, use a vacuum pump for air purge. (5) R410A refrigerant is azeotropic mixture type refrigerant. Therefore use liquid type to charge the refrigerant.
(If using gas for charging, composition of the refrigerant changes and then characteristics of the air condi-
tioner change.)
3. Pipe Materials
For the refrigerant pipes, copper pipe and joints are mainly used. It is necessary to select the most appropriate pipes to conform to the standard. Use clean material in which impurities adhere inside of pipe or joint to a minimum.
(1) Copper pipe
<Piping>
The pipe thickness, flare finishing size, flare n ut and others differ according to a refrigerant type. When using a long copper pipe for R410A, it is recommended to select “Copper or copper-base pipe without
seam and one with bonded oil amount 40mg/10m or less. Also do not use crushed, deformed, discolored (especially inside) pipes. (Impurities cause clogging of expansion valves and capillary tubes.)
<Flare nut>
Use the flare nuts which are attached to the air conditioner unit.
(2) Joint
The flare joint and socket joint are used for joints of the copper pipe. The joints are rarely used for installa-
tion of the air conditioner. However clear impurities when using them.
8
4. Tools
(1) Required T ools for R410A
Mixing of different types of oil ma y cause a trouble such as generation of sludge, clogging of capillary, etc.
Accordingly, the tools to be used are classified into the following three types.
1) Tools exclusive for R410A (Those which cannot be used f or conventional refrigerant (R22))
2) Tools exclusive for R410A, but can be also used for conventional refrigerant (R22)
3) Tools commonly used for R410A and for conventional refrigerant (R22)
The table below shows the tools exclusive for R410A and their interchangeability.
Tools exclusive for R410A (The following tools for R410A are required.)
Tools whose specifications are changed for R410A and their interchangeability
No.
Q
R
S
T
U
V
W
X
Y
Y
Used tool
Flare tool Copper pipe gauge for
adjusting projection margin
Torque wrench
Gauge manifold Charge hose
Vacuum pump adapter Electronic balance for
refrigerant charging Refrigerant cylinder Leakage detector Charging cylinder
Usage
Pipe flaring
Flaring by conventional flare tool
Connection of flare nut
Evacuating, refrigerant charge, run check, etc.
V acuum evacuating
Refrigerant charge Refrigerant charge
Gas leakage check Refrigerant charge
Conventional air
conditioner installation
Whether new equipment can be used with conventional refrigerant
Yes
*(Note 1)
No
No
Yes
Yes
No
Yes
No
Whether conven­tional equipment can be used
*(Note 1)
*(Note 1)
No
No
No
Yes
No No No
(1) V acuum pump
Use vacuum pump by
attaching vacuum pump adapter. (2) Torque wrench (3) Pipe cutter (4) Reamer (5) Pipe bender (6) Level vial
(7) Screwdriver (+, –) (8) Spanner or Monkey wrench (9) Hole core drill (10) Hexagon wrench (Opposite side 4mm) (11) Tape measure (12) Metal saw
Also prepare the following equipments for other installation method and run check. (1) Clamp meter (2) Thermometer
(3) IInsulation resistance tester (4) Electroscope
Existence of new equipment for R410A
Yes
Yes
Yes
Yes
Yes
Yes Yes
Yes
(Note 2)
R410A
air conditioner installation
(Note 1) When flaring is carried out for R410A using the conventional flare tools, adjustment of projection
margin is necessary. For this adjustment, a copper pipe gauge, etc. are necessary.
(Note 2) Charging cylinder for R410A is being currently developed.
General tools (Conventional tools can be used.)
In addition to the above exclusive tools, the following equipments which serve also for R22 are necessary as the general tools.
9
5. Recharge of Refrigerant
When recharge of the refrigerant is required, charge the new refrigerant with the specified amount in the procedure as described below.
Q
Never charge the refrigerant over the specified amount.
R
Do not charge the additional refrigerant. If charging refrigerant additionally when refrigerant gas leaks, the refrigerant composition in the refrigerating cycle changes resulted in change of air conditioner characteristics or refrigerant over the specified stan­dard amount is charged and an abnormal high pressure is applied to the inside of the refrigerating
cycle resulted in cause of breakage or injury .
Q
Set the equipment so that liquid refrigerant can be charged.
R
When using a cylinder with siphon pipe, liquid can be charged without inversing the cylinder.
Gauge manifold
[ Cylinder with siphon ] [ Cylinder without siphon ]
OUTDOOR unit
Gauge manifold
OUTDOOR unit
Electronic
balance
Refrigerant
cylinder
Electronic
balance
Siphon
Refrigerant
cylinder
6. Environment
Use Vacuum pump method for an air purge (Discharge of air in the connecting pipe) in installation time.
Do not discharge flon gas into the air to protect the earth environment.
Using the vacuum pump method, clear the remained air (Nitrogen, etc.) in the unit. If the air remains, the
pressure in the refrigerating cycle becomes abnormally high and an injury and others are caused due to burst.
VLV
H
Connected to indoor unit
Main pipe
Valve fully closed (gas side)
Center unit
Low-
pressure gauge
High-
pressure gauge
Gauge manifold
Brazed
Service port
Service port
Ø6.4
Copper pipe
Ø6.4 Copper pipe
Fully tightened
Fully tightened
Reducing valve
Nitrogen
gas
Valve fully closed (liquid side)
Valve fully closed (balance)
Connected to other terminal units
(Charge the refrigerant as below.)
Recover the refrigerant and check there is no refrigerant in the equipment.
Leave it as it is for 1 to 2 minutes and check the indicator of the compound gauge does not return.
Set the refrigerant tank on the electron balance, connect the connecting hose to connecting ports of the cylinder and the electron gauge, and then charge the liquid refrigerant from the service port at liquid side. (Shield with the gauge manifold so that refrigerant does not flow to gas side.)
Connect the charge hose to the packed valve service ports at gas side, liquid side, and balance side of the outdoor unit.
Open the packed valves of the balance pipe fully at liquid and gas sides, and then return the valve at gas side a little to the closed side.
Open fully PMV of the outdoor unit.
Turn on power of the outdoor unit.
Short CN30 on I/F P.C. board of the outdoor unit.
Turn off power of the outdoor unit within 2 minutes after short-circuiting.
Open fully the handle Low of the gauge manifold, and then turn on the power of vacuum pump for vacuuming.
When the pressure has lowered until indication of the compound gauge pointed -0.1MPa (-76cmHg), open fully the handle Low and turn off the power of vacuum pump.
Connect the charge hose to vacuum pump adaptor.
R410A refrigerant is consisted with HFC mixed refrigerant. Therefore if the refrigerant gas is charged, the composition of the charged refrigerant changes and characteristics of the equipment changes.
4mm-hexagonal wrench is required.
10
1. OUTLINE
1-1. Components Lineup in Super Modular Multi Using
High-efficiency Refrigerant R410A
n Outdoor units
Inverter unit
Corresponding HP
5 HP 6 HP 8 HP 10 HP 12 HP
Appearance
Heat pump
MMY- MAP0501HT8 MAP0601HT8 MAP0801HT8 MAP1001H8 MAP1201HT8
Heat pump
MMY- MAP0501HT7 MAP0601HT7 MAP0801HT7 MAP1001HT7 MAP1201HT7
Model name
Cooling only
MMY-
MAP0501T8 MAP0601T8 MAP0801T8 MAP1001T8 MAP1201T8 Cooling capacity (kW) 14.0 16.0 22.4 28.0 33.5 Heating capacity (kW) 16.0 18.0 25.0 31.5 37.5 No. of connectable indoor units 8 10 13 16 20
Correspondin g HP 14 HP 16 HP 18 HP 20 HP 22 HP 22 HP 24 HP 24 HP
MMY- AP1401HT8 AP1601HT8 AP1801HT8 AP2001HT8 AP2201HT8 AP2211HT8 AP2401HT8 AP2411HT8
MMY- AP1401HT7 AP1601HT7 AP1801HT7 AP2001HT7 AP2201HT7 AP2211HT7 AP2401HT7 AP2411HT7
Combine d Model
MMY- AP1401T8 AP1601T8 AP1801T8 AP2001T8 AP2201T8 AP2211T8 AP2401T8 AP2411T8
Cool i ng cap a ci t y ( kW ) 38.4 45.0 50.4 56.0 61.5 61.5 68.0 68.0 Heat i n g c apacity (kW) 43.0 50.0 56.5 63.0 69.0 69.0 76.5 76.5
8 HP 8 HP 10 HP 10 HP 8 HP 12 HP 8 HP 12 HP 6 HP 8 HP 8 HP 10 HP 8 HP 10 HP 8 HP 12 HP
————6 HP 8 HP
Combined ou tdoor units
————————
No. of connectable indoor units2327303337374040
Corresponding HP 26 HP 28 HP 30 HP 32 HP 32 HP 34 HP 34 HP 36 HP
MMY- AP2601HT8 AP2801HT8 AP3001HT8 AP3201HT8 AP3211HT8 AP3401HT8 AP3411HT8 AP3601HT8
MMY- AP2601HT7 AP2801HT7 AP3001HT7 AP3201HT7 AP3211HT7 AP3401HT7 AP3411HT7 AP3601HT7
Combine d Model
MMY- AP2601T8 AP2801T8 AP3001T8 AP3201T8 AP3211T8 AP3401T8 AP3411T8 AP3601T8
Cooling capacity (kW) 73.0 78.5 84.0 90.0 90.0 96.0 96.0 101.0 Heat i n g ca p a c i t y ( k W) 81.5 88.0 95.0 100.0 100.0 108.0 108.0 113.0
10 HP 10 HP 10 HP 8 HP 12 HP 10 HP 12 HP 10 HP 8 HP 10 HP 10 HP 8 HP 10 HP 8 HP 12 HP 10 HP 8 HP 8 HP 10 HP 8 HP 10 HP 8 HP 10 HP 8 HP
Combined ou tdoor units
———8 HP 8 HP 8 HP
No. of connectable indoor units4347484848484848
Corresponding HP 36 HP 38 HP 40 HP 42 HP 44 HP 46 HP 48 HP
MMY- AP3611HT8 AP3801HT8 AP4001HT8 AP4201HT8 AP4401HT8 AP4601HT8 AP4801HT8
MMY- AP3611HT7 AP3801HT7 AP4001HT7 AP4201HT7 AP4401HT7 AP4601HT7 AP4801HT7
Combine d Model
MMY- AP3611T8 AP3801T8 AP4001T8 AP4201T8 AP4401T8 AP4601T8 AP4801T8
Cool i ng c ap ac it y ( kW ) 101.0 106.5 112.0 118.0 123.5 130.0 135.0 Heat i n g ca p a city (kW) 113.0 119.5 126.5 132.0 138.0 145.0 150.0
12 HP 10 HP 10 HP 12 HP 12 HP 12 HP 12 HP 12 HP 10 HP 10 HP 10 HP 12 HP 12 HP 12 HP 12 HP 10 HP 10 HP 10 HP 10 HP 12 HP 12 HP
Combined ou tdoor units
8 HP 10 HP 10 HP 10 HP 10 HP 12 HP
No. of connectable indoor units48484848484848
n Combination of outdoor units
n Branching joints and headers
* In 1 line after header branch, the maximum total capacity codes 6.0 can be connected. * The capacity code is indicated as HP equivalent. For details, refer to Selection of refrigerant pipe
Y-branch joint
Branch header
T-branch joint
Model RBM-
BY53-E BY103-E BY203-E BY303-E HY1043-E HY2043-E HY1083-E HY2083-E
BT13-E
Usage
Total indoor unit capacity code Below 6.4 Total indoor unit capacity code Over 6.4, below 14.2 Total indoor unit capacity code Over 14.2, below 25.2 Total indoor unit capacity code Over 25.2
Max.
Total indoor unit capacity code Below 14.2
4 branches
Total indoor unit capacity code Over 14.2, below 25.2
Max.
Total indoor unit capacity code Below 14.2
8 branches
Total indoor unit capacity code Over 14.2, below 25.2
The following 3 types of T joint pipes are collected as 1 set.
Balance pipe (Ø9.5) ×1
Pipe at liquid side (Corresponded dia. Ø9.5 to Ø22.2) ×1
Pipe at gas side (Corresponded dia. Ø15.9 to Ø38.1) × 1
External view
11
n Indoor units
Type Appearance Model name Capacity rank Capacity code
Cooling
capacity (kW)
Heating
capacity (kW)
MMU-AP0091H
009 type 1 2.8
3.2
MMU-AP0121H
012 type 1.25 3.6
4.0
MMU-AP0151H,
015 type 1.7 4.5
5.0
MMU-AP0181H
018 type 2 5.6
6.3
MMU-AP0241H
024 type 2.5 7.1
8.0
MMU-AP0271H
027 type 3 8.0
9.0
MMU-AP0301H
030 type 3.2 9.0
10.0
MMU-AP0361H
036 type 4 11.2
12.5
MMU-AP0481H
048 type 5 14.0
16.0
4-way Air Discharge Cassette Type
MMU-AP0561H
056 type 6 16.0
18.0
MMU-AP0071WH
007 type 0.8 2.2
2.5
MMU-AP0091WH
009 type 1 2.8
3.2
MMU-AP0121WH
012 type 1.25 3.6
4.0
MMU-AP0151WH
015 type 1.7 4.5
5.0
MMU-AP0181WH
018 type 2 5.6
6.3
MMU-AP0241WH
024 type 2.5 7.1
8.0
MMU-AP0271WH
027 type 3 8.0
9.0
MMU-AP0301WH
030 type 3.2 9.0
10.0
2-way Air Discharge Cassette Type
MMU-AP0481WH
(CHINA only)
048 type 5 14.0
16.0
MMU-AP0071YH
007 type 0.8 2.2
2.5
MMU-AP0091YH
009 type 1 2.8
3.2
MMU-AP0121YH
012 type 1.25 3.6
4.0
MMU-AP0151SH
015 type 1.7 4.5
5.0
MMU-AP0181SH
018 type 2 5.6
6.3
1-way Air Discharge Cassette Type
MMU-AP0241SH
024 type 2.5 7.1
8.0
MMD-AP0071BH
007 type 0.8 2.2
2.5
MMD-AP0091BH
009 type 1 2.8
3.2
MMD-AP0121BH
012 type 1.25 3.6
4.0
MMD-AP0151BH
015 type 1.7 4.5
5.0
MMD-AP0181BH
018 type 2 5.6
6.3
MMD-AP0241BH
024 type 2.5 7.1
8.0
MMD-AP0271BH
027 type 3 8.0
9.0
MMD-AP0301BH
030 type 3.2 9.0
10.0
MMD-AP0361BH
036 type 4 11.2
12.5
MMD-AP0481BH
048 type 5 14.0
16.0
Conceal ed Duct Standard Type
MMD-AP0561BH
056 type 6 16.0
18.0
MMD-AP0181H,
018 type 2 5.6
6.3
MMD-AP0241H
024 type 2.5 7.1
8.0
MMD-AP0271H
027 type 3 8.0
9.0
MMD-AP0361H
036 type 4 11.2
12.5
MMD-AP0481H
048 type 5 14.0
16.0
MMD-AP0721H
072 type 8 22.4
25.0
Conceal ed Duct High Static Pressure Type
MMD-AP0961H
096 type 10 28.0
31.5
MMC-AP0151H
015 type 1.7 4.5
5.0
MMC-AP0181H
018 type 2 5.6
6.3
MMC-AP0241H
024 type 2.5 7.1
8.0
MMC-AP0271H
027 type 3 8.0
9.0
MMC-AP0361H
036 type 4 11.2
12.5
Under Ceiling Type
MMC-AP0481H
048 type 5 14.0
16.0
MMK-AP0071H
007 type 0.8 2.2
2.5
MMK-AP0091H
009 type 1 2.8
3.2
MMK-AP0121H
012 type 1.25 3.6
4.0
MMK-AP0151H
015 type 1.7 4.5
5.0
MMK-AP0181H
018 type 2 5.6
6.3
High Wall Type
MMK-AP0241H
024 type 2.5 7.1
8.0
MML-AP0071H
007 type 0.8 2.2
2.5
MML-AP0091H
009 type 1 2.8
3.2
MML-AP0121H
012 type 1.25 3.6
4.0
MML-AP0151H
015 type 1.7 4.5
5.0
MML-AP0181H
018 type 2 5.6
6.3
Floor Standing Cabinet Type
MML-AP0241H
024 type 2.5 7.1
8.0
MML-AP0071BH
007 type 0.8 2.2
2.5
MML-AP0091BH
009 type 1 2.8
3.2
MML-AP0121BH
012 type 1.25 3.6
4.0
MML-AP0151BH
015 type 1.7 4.5
5.0
MML-AP0181BH
018 type 2 5.6
6.3
Floor Standing Concealed Type
MML-AP0241BH
024 type 2.5 7.1
8.0
MMF-AP0151H
015 type 1.7 4.5
5.0
MMF-AP0181H
018 type 2 5.6
6.3
MMF-AP0241H
024 type 2.5 7.1
8.0
MMF-AP0271H
027 type 3 8.0
9.0
MMF-AP0361H
036 type 4 11.2
12.5
MMF-AP0481H
048 type 5 14.0
16.0
Floor Standing Ty pe
MMF-AP0561H
056 type 6 16.0
18.0
*1) Model built-in with heater will be delivered in Jan. ’04. *2) Concealed Duct High Static Pressure type models MMD-AP0241H and AP0271H will be delivered in April ’04.
12
n Remote controller switch
Name
Appearance
Model name
Type
Wired remote controller
RBC-AMT21E
Simple wired remote controller
RBC-AS21E
Weekly timer
RBC-EXW21E
Wireless remote controller kitName
Appearance
Model name
Type
RBC-AX22WU
Air Discharge Cassette type
4-way discharge type
RBC-AX22CE
Under Ceiling type
TCB-AX21E
Separate sensor type
Receiver section
UNIT
SET
CL
SETTING
UNIT No.
CODE No.
TEST
SET DATA
R.C. No.
˚C ˚F
TEST
SETTING
WEEKLY TIMER
ERROR
SuMoTuWeTh FrSa
PROGRAM1 PROGRAM2 PROGRAM3
ADR ADR ADR
Receiver section
Receiver section
laid separately
Name
Appearance
Model name
Type
Central remote controller
TCB-SC642TLE
64 system center controller
SELECT ZONE
CL
SET
GROUP
CODE
No.
UNIT No.
No.
R.C.
TEST
ZONE
ALL
ZONE GROUP
SETTING
1234
SET DATA
13
2. WIRING DIA GRAM
2-1. Indoor Unit
2-1-1. 4-way Air Discharge Cassette Type
Model: MMU-AP0091H, AP0121H, AP0151H, AP0181H, AP0241H,
MMU-AP0271H, AP0301H, AP0361H, AP0481H, AP0561H
CN104
(YEL)
CN102 (RED)
CN101
(BLK)
1 2 3 4 5 1 2 3 4 5
1 2 3 4 5 1 2 3 4 5
1 2 3 4 5 1 2 3 4 5
1 2 3 4 5 6 1 2 3 4 5
1 2 3 4 5 1 2 3 4 5 6
6 4 3 1 2 5 6 4 3 1 2 5
3 1 321
CN34
(RED)
FS
CN33 (WHI)
CN82 (BLU)
5 4 3 2 1 5 4 3 2 1
CN334 (BLU)
DC20V
CN333
(WHI)
CN68 (BLU)
CN304 (GRY)
CN66 (WHI)
CN44 (BLN)
CN67 (BLK)
LM1
PMV
Indoor control P.C. board
MCC-1402
121
2
TA
121
2
TCJ
121
2
TC2
CN100 (BRN)
121
2
33
CN80
(GRN)
PNL
EXCT
1 2
CN73
(RED)
1 2
Filter input
(Option)
(Fandrive)
CN70 (WHI)
CN20
(BLU)
1 2
3
TC1
1 2 3 4 5 1 2 3 4 5
LM2
1 2 3 4 5
CN81 (BLK)
CN60 (WHI)
CN32 (WHI)
CN61 (YEL)
CN50 (WHI)
CN40 (BLU)
T10
1 2 3 4 5
1 2
1 2
3 4 5 6
1 2 3 4 51 2 3
CN309
(YEL)
1 2 3 1 2 3
1 2 1 2
CN41 (BLU)
1 2 3 1 2 3
4 5 6
RY302
RY303
1
2
3
1
2
3
1
2
3
1
2
3
1
2
1 2
1 2
3
~
+
~
Fuse T6.3A 250V~
Fuse
T3.15A
250V~
DC15V DC12V DC7V
P301
BLK
RED
WHI
WHI
RED
S(N)R(L)
Power supply
Single phase 220-240V 50Hz 220V 60Hz
Indoor unit
Earth screw
DM
FM
Power supply circuit
Motor drive
circuit
Parts name
Fan motor Indoor temp sensor Temp sensor Temp sensor Temp sensor Lover motor Drain pump motor Float switch Drain control relay Pulse Motor Valve
Color identification
1. indicates the terminal block, letter at inside indicates the terminal number.
2. A dotted line and broken line indicate the wiring at site.
3. indicates the control P.C. board.
RED : RED WHI : WHITE YEL : YELLOW BLU : BLUE BRN : BROWN
BLK : BLACK GRY : GRAY PNK : PINK ORN : ORANGE GRN : GREEN
Closed end connector
CN01 (WHI)
CN02 (BLU)
Adaptor for wireless
remote controller
CN03
(RED)
Network adaptor (Option)
1 2 1 2
1 2 1 2
1 2 1 2
X Y
3 3 2 2 1 1
Wired remote
controller
1 2
BA
U
2
1 2
CN1
(WHI)
CN001 (WHI)
WHI
Outdoor unit
BLK WHI BLK
BLK
BLU
BLU
BLK
BLK
TR
WHI
U
1
U2U
1
Network adaptor P.C. board
MCC-1401
Symbol
FM
TA TC1 TCJ TC2
LM1, LM2
DM
FS
RY302
PMV
Flow selector
unit earth
screw
14
2-1-2. 2-way Air Discharge Cassette Type
Model: MMU-AP0071WH, AP0091WH, AP0121WH, AP0151WH, AP0181WH,
MMU-AP0241WH, AP0271WH, AP0301WH, AP0481WH
CN104
(YEL)
CN102
(RED)
CN101
(BLK)
5 4 3 2 1 5 4 3 2 1
9 8 7 6 9 8 7 6
FAN CN083
(WHI)
WHI
RED
DP
(BLU)
CN068
DM
CN304
(GRY)
CN066
(WHI)
CN067
(BLK)
CN044 (BRW)
Indoor control P.C. board
121
2
TA
121
2
TCJ
121
2
TC2
CN100
(BRW)
121
2
33
CN080
(GRN)
PNL
EXCT
1 2
CN073
(RED)
1 2
Filter
CN070
(WHI)
CN081
(BLK)
CN060
(WHI)
Option
CN032
(WHI)
CN075
(WHI)
CN074
(WHI)
TR
1 2
1 2 3 4 5
1 2
3
TC1
1 2 3 4 5 6
CN061
(YEL)
Fan drive
1 2 3 4 5 61 2 3 4 5 6
1 2 3
1 2 3 1 2 3
1 2 1 2
1 2 3 1 2 3
1 2 3 1 2 3
4 5 6
1 2 3 4 5 6 1 2 3 4 5 6
1 2 3 4 5 6 1 2 3 4 5 6
CN050 (WHI)
CN041
(BLU)
CN040
(BLU)
CN01 (WHI)
CN02 (BLU)
Network adaptor (Option)
1 2
1 2 3 4 5
1 2 1 2
3 3
2
1 1
CN03
(RED)
MCC-1401
2 2
1 1
RY004
1
2
3
1 2
1 2
RY002
RY006
RY007
RY005
1 2
BA
YX
S(N)R(L)
U
2
1 2
Remote controller
CN1
(WHI)
Power supply
Single phase 220-240V 50Hz 220V 60Hz
Indoor unit
Earth screw
Outdoor unit
BLU
BLU
BLK
BLK
U
1
U2U
1
Flow selector
unit earth
screw
Power supply
circuit
CN01 (WHI)
CN02 (YEL)
Sub P.C. board
MCC-1520
Symbol
FM RC TR LM TA
TC1,TC2,TCJ
RY001 RY002 RY004
RY005~007
FS DM
PMV
Parts name
Fan motor Running capacitor Transformer Louver motor Indoor temp sensor Temp sensor Louver control relay Drain control relay Heater control relay Fan motor control relay Float switch Drain pump motor Pulse Motor Valve
LM (GRN) CN033
LM
1 2 3 1 2 3
FS
(RED)
CN030
PMV
(BLU)
CN082
FS
1 2 3 1 2 3
1 2 3 1 2 3
4 5 6 4 5 6
6 4 3 6 4 3
1 2 5 1 2 5
RY001
TR
Fuse
T5.0A
250V~
1
2
3
1
2
3
CN039
(YEL)
1
2
3
1
2
3
1 2 1 2
PMV
121
2
343
4
565
6
77
9
FM
YEL
BLU
ORN
BLK
HML UL
RC
RED
1. indicates the terminal block, letter at inside indicates the terminal number.
2. A dotted line and broken line indicate the wiring at site.
3. indicates the control P.C. board.
Closed end connector
Color
indication
RED : RED WHI : WHITE YEL : YELLOW BLU : BLUE BLK : BLACK GRY : GRAY PNK : PINK ORN : ORANGE BRW : BROWN GRN : GREEN
Line Filter
P301
(BLK)
15
2-1-3. 1-way Air Discharge Cassette Type (Compact type)
Model: MMU-AP0071YH, AP0091YH, AP0121YH
CN104
(YEL)
CN102
(RED)
CN101
(BLK)
5 4 3 2 1 5 4 3 2 1
9 8 7 6 9 8 7 6
FAN CN083
(WHI)
DP
(BLU)
CN068
DM
CN304
(GRY)
Heater
CN301
(BLK)
CN066
(WHI)
WHI
RED
BLU
BLU
BLU
CN067
(BLK)
Indoor control P.C. board
121
2
TA
TCJ
121
2 1
2
CN100 (BRW)
121
2
33
CN080 (GRN)
PNL
EXCT
1 2
CN073
(RED)
1 2
Filter
CN070
(WHI)
CN081
(BLK)
CN060
(WHI)
Option
CN032
(WHI)
CN075
(WHI)
CN074
(WHI)
TR
1 2
1 2 3 4 5
1 2
3
TC1
1 2 3 4 5 6
CN061
(YEL)
Fan drive
1 2 3 4 5 61 2 3 4 5 6
1 2 3
1 2 3 1 3
1 2 1 2
1 2 3 1 2 3
1 2 3 1 2 3
1 2 3 1 2 3
4 5 6
CN050
(WHI)
CN041
(BLU)
CN040
(BLU)
1 2 1 2
CN044 (BRW)
CN01 (WHI)
CN02 (BLU)
Network adaptor (Option)
1 2
1 2 3 4 5
1 2
1 2 1 1 2 2
2 123
3 1
CN03 (RED)
MCC-1401
RY004
1
2
3
1 2
RY002
RY006
RY007
RY005
1 2
BA
YX
S(N)R(L)
U
2
1 2
Remote controller
CN1
(WHI)
Power supply
Single phase 220-240V 50Hz 220V 60Hz
Indoor unit
Earth screw
Outdoor
unit
BLU
BLU
RED
WHI
BLK
BLK
U
1
U2U
1
Power supply
circuit
Network adaptor P.C. board
Symbol
FM RC TR LM TA
TC1,TCJ
RY001 RY002 RY004
RY005~007
FS DM
PMV
Parts name
Fan motor Running capacitor Power transformer Louver motor Indoor temp sensor Temp sensor Flap motor control relay Drain pump control relay Heater control relay Fan motor control relay Float switch Drain pump motor Pulse Motor Valve
LM (GRN) CN033
LM
1 2 3 1 2 3
FS
(RED)
CN030
PMV
(BLU)
CN082
FS
1 2 3 1 2 3
1 2 3 1 2 3
4 5 6 4 5 6
6 4 3 6 4 3
1 2 5 1 2 5
RY001
AI-NET central control terminal
TR
Fuse
T5.0A
1
2
3
1
2
3
CN309
(YEL)
AC IN
1
2
3
1
2
3
2 1 2 1
2 1 2 1
PMV
121
2
343
4
565
6
FM
YEL
BLU
ORN
BLK
RED
HML UL
RC
1. indicates the terminal block, letter at inside indicates the terminal number.
2. A dotted line and broken line indicate the wiring at site.
3. indicates the control P.C. board.
Closed end connector
1 2 3 4 5 6 1 2 3 4 5 6
1 2 3 4 5 6 1 2 3 4 5 6
CN01 (WHI)
CN02 (YEL)
Sub P.C. board
MCC-1520
Color
indication
RED : RED WHI : WHITE YEL : YELLOW BLU : BLUE BLK : BLACK GRY : GRAY PNK : PINK ORN : ORANGE BRW : BROWN GRN : GREEN
Line Filter
Flow selector
unit earth
screw
16
Model: MMU-AP0151SH, AP0181SH, AP0241SH
FM RC TR LM TA TC1,TC2,TCJ RY001 RY002 RY005~007 FS DM PMV
Fan motor Running capacitor Transformer Lover motor Indoor temp sensor Temp sensor Louver control relay Drain control relay Fan motor control relay Float switch Drain pump motor Pulse motor valve
Symbol
Parts name
Color
indication
RED : RED WHI : WHITE YEL : YELLOW BLU : BLUE BLK : BLACK GRY : GRAY PNK : PINK ORN : ORANGE BRW : BROWN GRN : GREEN
1. Indicates the terminal bolock, letter. Letter at inside indicates the terminal number.
2. A dotted line and broken line indicate the wiring at side.
3. indicate the control p.c. board.
5 3 1779
9 5 3 1
RY007
P301
RY004
(GRY) CN304
(YEL) CN309
(BLK)
BLK
CN067
FUSE
T5.0A 250V~
RY006
RY005
H
RED BLK ORN BLU YEL
M LUL
313
1
313
1
3
1
RC
FM
1 2 313
CN104
(YEL)
TA
212
1
CN102
(RED)
TCJ
212
1
CN101
(BLK)
CN100
(BRW)
1
3
CN080
(GRN)
TC2
PNL
EXCT
2
1
CN073
(RED)
2
2
1
FILTER
CN070
(WHI)
CN081
(BLK)
2
1
2
1
2
1
112
2
112
2
112
2
112
X Y
2
3
2
1 1
3
1
1 233 1 2 3 4 5
1 2 3 4 5 6 1 2 1 23 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6
2
1
4
3
5
2
1
TC1
CN066 (WHI)
AC IN
CN044 (BRW)
CN040
(BLU)
Outdoor unit Remote Controller
Power supply single phase
220-240V 50Hz
220V 60Hz
Indoor unit
earth screw
Closed-end
connector
Line Filter
CN01(WHI)
CN03(RED)
CN02 (BLU)
CN041
(BLU)
CN050 (WHI)
CN061
(YEL)
CN032
(WHI)
FAN
DRIVE
OPTION
CN060
(WHI)
EMG
BLU
BLU
BLK
BLK
RC
TR
U1
U1 U2
U2 A B
Network Adapter
(Option)
Control P.C. board
for Indoor unit
MCC-1403
MCC-1401
112
2
CN1
113
3
CN074
(WHI)
CN075
(WHI)
Power supply
circuit
TR
1
133
CN068
(BLU)
FAN
CN083
(WHI)
RY002
DM
DM
113
3
CN033 (GRN)
RY001
LM
CN082
(BLU)
PMV
LM
113
3
CN030
(RED)
FS
FS
112
2
1 2 3 4 5 6
1 2 3 4 5 6
1 234 56
1 234 56
PMV
313
2
1
6
5
4
6
5
4
R(L) S(N)
1 2 3 4 5 6 1 2 3 4 5 6
1 2 3 4 5 6 1 2 3 4 5 6
CN01 (WHI)
CN02 (YEL)
Sub P .C . board
MCC-1520
Flow selector
unit earth
screw
17
2-1-4. Concealed Duct Standard Type
Model: MMD-AP0071BH, AP0091BH, AP0121BH, AP0151BH, AP0181BH, AP0241BH
MMD-AP0271BH, AP0301BH, AP0361BH, AP0481BH, AP0561BH
CN104
(YEL)
CN102
(RED)
CN101
(BLK)
1 2 3 4 5
1 2 3 4 5 6 1 2 3 4 5 6
6 4 3 1 2 5 6 4 3 1 2 5
3 1 321
CN34 (RED)
FS
CN33 (WHI)
CN82 (BLU)
DC20V
CN68 (BLU)
CN304
(GRY)
CN66 (WHI)
CN44 (BRW)
CN67 (BLK)
Reactor
PMV
Indoor control P.C. board
121
2
TA
121
2
TCJ
121
2
TC2
CN100
(BRN)
121
2
33
CN80
(GRN)
PNL
EXCT
1 2
CN73
(RED)
1 2
(Signal output)(Fan drive)
CN70 (WHI)
CN20
(BLU)
1 2
3
TC1
1 2 3 4 5
CN81 (BLK)
CN60 (WHI)
CN32
(WHI)
CN61 (YEL)
CN50 (WHI)
Adaputor for wired
remote controller
CN309
(YEL)
CN41 (BLU)
CN40 (BLU)
T10
1 2 3 4 5
1 21 2 3 4 5 61 2 3 4 51 2 31 2 3
1 2 3
1 2 3 1 2
1 2 1 2 3
1 3 1 2 2
4 5 6
1 2 1 2
RY302
1
2
3
1
2
3
1
2
3
1
2
3
1
2
1 2
1 2
3
~
+
~
Fuse
T6.3A
250V~
Fuse
T3.15A
250V~
DC15V DC12V DC7V
P301
BLK
RED
WHI
WHI
WHI
RED
Wired remote
controller
1 2
BA
S(N)R(L)
U
2
1 2
CN1
(WHI)
CN001 (WHI)
Indoor unit power supply
Single phase 220-240V 50Hz 220V 60Hz
Indoor unit
Earth screw
WHI
Outdoor unit
BLK WHI BLK
BLK
BLU
BLU
BLK
BLK
TR
WHI
U
1
U2U
1
DM
Power supply circuit
Motor drive
circuit
CN01 (WHI)
CN02 (BLU)
CN03 (RED)
Network adaptor (Option)
1 2 1 2
1 2 1 2
X Y
3 3 2 2 1 1
Network adaptor P.C. board
Symbol
FM TA
TC1,TC2,TCJ
DM FS
RY302
PMV
Parts name
Fan motor Indoor temp sensor Indoor temp sensor Drain pump motor Float switch Drain pump control relay Pulse Motor Valve
Color identification
1. indicates the terminal block, letter at inside indicates the terminal number.
2. A dotted line and broken line indicate the wiring at site.
3. indicates the control P.C. board.
RED : RED WHI : WHITE YEL : YELLOW BLU : BLUE BRW : BROWN
BLK : BLACK GRY : GRAY PNK : PINK ORN : ORANGE GRN : GREEN
Closed end connector
CN333
(WHI)
CN334
(WHI)
11223445
5
1 3 5
1 3
1 2 3
1 2 3
5
11
545
4
FM
Flow selector
unit earth
screw
18
2-1-5. Concealed Duct High Static Pressure Type
Model: MMD-AP0181H, AP0241H, AP0271H, AP0361H, AP0481H
TC1
TC2
CN080 (GRN)
CN101
(BLK)
CN073 (RED)
CN070
(WHI)
4 2
5 4 3 2 1
9 8 7 6
9 8 7 6
FAN CN083
(WHI)
DP
(BLU)
CN068
DP
CN304
(GRY)
CN066
(WHI)
CN067
(BLK)
(BLK)
PNL
EXCT
1 2
1 2
Filter
CN082
(BLU)
CN060
(WHI)
Option
CN032
(WHI)
CN075
(WHI)
CN074
(WHI)
TR
T10
1 2
6 5 4 3 2 1
6 5 4 3 2 1
5 2 1 3 4 6
5 2 1 3 4 6
CN081
(BLK)
1 2 3 4 5
3
1 2 3 4 5 6
CN061
(YEL)
Fan drive
1 2 3 4 5 61 2 3 4 5 6
1 2 3
1 2 3 1 3
1 21 2 1 2
1 2 3 1 2 3
1 2 3 1 2 3
4 5 6
CN050
(WHI)
CN041
(BLU)
CN040
(BLU)
CN044
(BRW)
1 2
1 2 3 4 5
RY004
P301
1
2
3
1 2
RY002
RY006
RY007
RY005
1 2
BA
S(N)R(L)
U
2
1 2
Remote controller
CN1
(WHI)
Power supply
Single phase 220-240V 50Hz 220V 60Hz
Indoor unit
Earth screw
Outdoor unit
U
1
U2U
1
Power supply
circuit
Symbol
FM RC
TR TA
TC1,TC2,TCJ
RY005~007
RY001 RY002
PMV
F
43F1
DM
FS
Parts name
Fan motor Running capacitor Transformer Indoor temp sensor Temp sensor Fan motor control relay Flap motor control relay Drain control relay Pulse Motor Valve Fuse Fan motor control relay Drain pump motor Float switch
Sold
separately
LM
(GRN)
CN033
1 2 3 1 2 3
CN100
(BRN)
1 2 3 1 2 3
1 2 3 1 2 3
1 2 1 2
TCJ
CN102
(RED)
1 2 1 2
TA
CN104
(YEL)
FS
CN030
(RED)
1 2 1 2
RY001
TR
OC
EMG
RC
Fuse
T5.0A
T10A,250V~
1
2
3
1
2
3
CN309
(YEL)
1
2
3
1
2
3
REDWHI
HML UL
1. indicates the terminal block, letter at inside indicates the terminal number.
2. A dotted line and broken line indicate the wiring at site.
3. indicates the control P.C. board.
4. When attaching a drain pump, exchange CN030 connector with a connector of the float switch.
5. A part is connected to the terminal block. When exchanging to the outside static pressure necessary at the local site, check the terminal No. and lead color of the fan motor in the below diagram, and then exchange the lead wire indicated by the arrow mark ( ),
6. Pay attention to change static pressure because the outside static pressure of H tap in 50 or 60Hz.
PMV
(Option)
CN01 (WHI)
CN02 (BLU)
WHI
WHI
RED
GRY
WHI
RED
BLU
ORN
BLK
BRN
GRY
YEL
RED
REDRED F
RED WHI
43F1
6
4
CN03 (RED)
MCC-1401
Network adaptor (Option)
1 2 1 2
1 2 1 2
X Y
3 3
2
1 1
43F1
Spark
killer
87
43F1
5
3
1 2 3 4 1 2 3 4
F1F2F3F
4
RC
FM
WHI
BLK
BLU ORN
BRN
GRY RED
49F
Indoor control P.C. board
Closed end connector
Closed end connector
Wired for MMD-AP0481 only (BRN Wire)
Motor over heating protection switch
Color
indication
RED : RED WHI : WHITE YEL : YELLOW BLU : BLUE BLK : BLACK GRY : GRAY PNK : PINK ORN : ORANGE BRW : BROWN GRN : GREEN
1 2 3 4 5 6 1 2 3 4 5 6
1 2 3 4 5 6 1 2 3 4 5 6
CN01 (WHI)
CN02 (YEL)
Sub P.C. board
MCC-1520
Flow selector
unit earth
screw
19
Model: MMD-AP0721H, AP0961H
FM RC TR TA TC1,TC2,TC3 RY005~007 RY001 RY002 PMV F1~3 43F1,43F2 DM FS
Fan motor Running capacitor Transformer Indoor temp sensor Temp sensor Fan motor control relay Louver control relay Drain control relay Pulse motor valve Fuse for fan motor Fan motor control relay Drain pump motor Float switch
Sold separately
Symbol
Parts name
1. Indicates the terminal bolock, letter. Letter at inside indicates the terminal number.
2. A dotted line and broken line indicate the wiring at side.
3. indicate the control p.c. board.
4. When installing the drain pump connector the froat switch connector to CN030 connector.
5. Position is connected to terminal block when change to static pressure. Exchange the lead wire of arrow position after check the terminal number as figure and lead wire's color of fan motor.
6. When midifiy the high tap, to care the static pressure are differ by 50Hz or 60Hz.
CN080 (GRN)
PNL
EXCT
2 3
1
2
2
3
3
4
4
5
5
6
1
1
2
2 2
3 3 3
4
4 4
5
5 56
6 6
1
1 1
CN073
(RED)
2
1
FILTER
CN070
(WHI)
CN081
(BLK)
CN082
(BLU)
2
1
112 3
3
CN100
(BRW)
112
2
CN101
(BLK)
CN030
(RED)
TC1
TC2
112
2
CN102
(RED)
TCJ
112
2
CN104
(YEL)
TA
PMV
113
3
FS
5 3 1779
9 5 3 1
RY007
P301 (BLK)
RED
RED
Spark Killer
WHI
WHI
RED
YEL
BLK WHI
GRY RED
BLU
ORN
RY004
(GRY) CN304
(YEL) CN309
FUSE
T5.0A 250V~
RY006
RY005
H
M LUL
313
1
313
1
3
1
6
8
7
2
1
112
21 2
112
2
112
X Y
2
3
2
1 1
3
1
1 233 1 2 3 4 5
1 2 3 4 5 6 1 2 1 23 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6
CN066
(WHI)
CN067
(BLK)
AC IN RED
WHI
CN044 (BRW)
EMG
Remote Controller
Power supply single phase
220-240V 50Hz
220V 60Hz
Indoor unit earth screw
Closed-end
connector
Closed-end
connector
Line Filter
WHI RED
RED
WHI
RED
WHI
WHI
CN01(WHI)
CN03(RED)
CN02 (BLU)
CN040 (BLU)
CN041
(BLU)
CN050
(WHI)
CN061
(YEL)
CN032
(WHI)
FAN
DRIVE
OPTION
CN060
(WHI)
BLU
BLU
BLK
BLK
RCCO
TR
U1 U2 A B
Network Adapter
(Option)
Control P.C. board
for Indoor unit
MCC-1403
MCC-1401
112
2
CN1
113
3
CN074
(WHI)
CN075
(WHI)
Power supply
circuit
TR
DP
CN068
(BLU)
LM
CN033
(GRN)
FAN
CN083
(WHI)
RY002
1 3
RY001
R(L) S(N)
1
133
DM
(Option)
43F243F1
49F
F1
T10.0A, 250V~
T10.0A, 250V~
T10.0A, 250V~
RED
F2
RED
F3
RED
7
8
5
3
43F1
7
8
5
3
43F2
FAN3
4P
(RED)
RC
ORW
RED
RED
ORW
ORW
YEL
YEL
WHI
RED
GRY
WHI
RED
GRY
BLU
ORN
1 2 3 4 1 2 3 4
FM3
F1 F2 F3 F4
6
4
43F2
FAN2
4P
(BLU)
RC
YEL
WHI
RED
GRY
WHI
RED
GRY
BLU
ORN
1 2 3 4 1 2 3 4
FM2
F1 F2 F3 F4
6
4
43F1
FAN1
4P
(WHI)
RC
YEL
WHI
RED
GRY
WHI
RED
GRY
BLU
ORN
1 2 3 4 1 2 3 4
FM1
F1 F2 F3 F4
5
Motor over heating protection switch
Fan motor inside
wiring diagram
Color
indication
RED : RED WHI : WHITE YEL : YELLOW BLU : BLUE BLK : BLACK GRY : GRAY PNK : PINK ORN : ORANGE BRW : BROWN GRN : GREEN
A
U1 U2
Outdoor unit
F1 F2 F3
Terminal
No.
YEL BLU ORN
Fan motor
wiring
69(7) 137(14) 196(20)
Static pressure
Pa (mmAg)
Setting from factory
Note
1 2 3 4 5
6
1 2 3 4 5
6
1 2 3 4 5
6
1 2 3 4 5
6
CN01 (YEL)
CN02 (YEL)
Sub P.C. board
MCC-1520
S.K
S.K
20
2-1-6. Under Ceiling Type
Model: MMC-AP0151H, AP0181H, AP0241H, AP0271H, AP0361H, AP0481H
CN104
(YEL)
CN102 (RED)
CN101
(BLK)
1 2 3 4 5 1 2 3 4 5
1 2 3 4 5 1
1 1
2
2 2
3
3 3
4
4 4
5
5 5
6 6
6 6
1 2 3 4 5 1 2 3 4 5
1 3 123
CN34 (RED)
FS
CN33 (WHI)
CN82 (BLU)
5 4 1 5 4 3 2 1
CN334 (WHI)
DC20V
CN333
(WHI)
CN68 (BLU)
CN304
(GRY)
CN66 (WHI)
CN67 (BLK)
Indoor control P.C. board
121
2
TA
121
2
TCJ
121
2
TC2
CN80
(GRN)
PNL
EXCT
1 2
CN73
(RED)
1 2
FILTER
Option GRLFandrive
CN70
(WHI) CN20 (BLU)
1 2
3
1 2 3 4 5 1 2 3 4 5
LM
1 2 3 4 5
CN60 (WHI)
CN32 (WHI)
CN61 (YEL)
CN50 (WHI)
Adpter for wireless
remote controller
CN309
(YEL)
CN41 (BLU)
T10
1 21 2 3 4 5 6
CN81 (BLK)
1 2 3 4 51 2 3 4 51 2 31 2 3
1 2 3
CN40 (BLU)
4 5 6
1 2 1 2
RY302
1
2
3
1
2
3
1
2
3
1
2
3
1
2
121
2
121
33
1 2
3
RY303
~
+
~
Fuse
T6.3A 250V~
Fuse
T3.15A
DC15V DC12V DC7V
P301
BLK
RED
WHI
Closed end
terminal
RED
WHI
Wired remote
controller
Outdoor unit
1 2
BA
U2U
1
U2U
1
1 2
CN1
(WHI)
CN001 (WHI)
Indoor unit
Earth screw
WHI BLK BLKWHI
BLK
TR
BLU
WHI
BLU
BLK
BLK
DM
FM
Power supply circuit
Motor drive
circuit
CN01 (WHI)
CN02
(BLU)
CN03 (RED)
Network adaptor (Option)
1 2 1 2
1 2 1 2
X Y
3 3 2 2 1 1
Network adaptor P.C. board
Color identification
1. indicates the terminal block, letter at inside indicates the terminal number.
2. A dotted line and broken line indicate the wiring at site.
3. indicates the control P.C. board.
RED : RED WHI : WHITE YEL : YELLOW BLU : BLUE BRW : BROWN
BLK : BLACK GRY : GRAY PNK : PINK ORN : ORANGE GRN : GREEN
S(N)R(L)
Power supply
single phase 200-240V 50Hz 200V 60Hz
Symbol
FM
TA
TC,TC2,TCJ
LM
RY302
DM
FS
Parts name
Fan motor Indoor temp sensor Temp sensor Louver motor Drain control relay Drain pump motor Float switch
Sold separately
PMV
Flow selector
unit earth
screw
CN100 (BRW)
121
2
33
TC1
21
2-1-7. High Wall T ype
Model: MMK-AP0071H, AP0091H, AP0121H, AP0151H, AP0181H, AP0241H
FM TA TC1,TC2,TCJ PMV LM RY303
Fan motor Indoor temp sensor Temp sensor Pulse motor valve Lover motor Louver control relay
Symbol
Parts name
Color
indication
RED : RED WHI : WHITE YEL : YELLOW BLU : BLUE BLK : BLACK GRY : GRAY PNK : PINK ORN : ORANGE BRW : BROWN GRN : GREEN
1. Indicates the terminal bolock. Letter at inside indicates the terminal number.
2. A dotted line and broken line indicate the wiring at side.
3. indicate the control p.c. board.
CN080
(GRN)
EXCT
2 3
1
CN68 (BLU)
3
1
CN304
(GRY)
313
1
CN67 (BLK)
CN66 (WHI)
3
1
2
1
3
1
CN103
(GRN)
2
1
CN73 (RED)
2
1
CN70 (WHI)
2
1
112 31 2 3 4 5
3
CN100 (BRW)
CN101
(BLK)
CN34 (RED)
CN33 (WHI)
1 2 3 4 5
CN20 (BLU)
1 2 3 4 5
CN81 (BLK)
1 2 3 4 5 6
CN60 (WHI)
1 2 3 4 5
6
CN61 (YEL)
1 2 31 3
1 3
1 21 2
1 231 3
4 5
CN50
(WHI)
CN41
(BLU)
CN40 (BLU)
GRY
BLU
BLU
BLK
BLK
BLK
WHI
GRY
CN309
(YEL)
Option
1 2
CN32 (WHI)
Fandrive
CN82 (BLU)
Motor drive
circuit
CN333
(WHI)
CN334
(WHI)
TC1
TC2
CN102
(RED)
TCJ
21212121212
1
CN104
(YEL)
TA
113
3
1 2 3 4 5 6
1
1
1 2 3 4 5 6
1 234 56
1 234 56
223445
5
1 3 5
1 3
1 2 3
1 2 3
5
PMV
11
545
4
LM
P301
BLK
RY302
FUSE
T6.3A 250V~
RY303
112
2
112
2
3
2
1 1
3
CN01(WHI)
CN03(RED)
CN02 (BLU)
TR
112
2
Network Adapter
(Option)
MCC-1401
U1 U2
U1 U2
A B X Y
CN1
(WHI)
WHI BLK
Wired remote
controller
Outdoor
unit
112
2
CN001
(WHI)
WHI BLK
Adapter for
wireless remote
controller
Power supply single phase
220-240V 50Hz
220V 60Hz Indoor unit
Earth screw
Closed-end
connector
RED
WHI
R(L) S(N)
FM
FUSE
T3.15A 250V~
Power supply circuit
DC20V DC15V DC12V DC7V
Control P.C. board
for Indoor unit
MCC-1402
Flow selector
unit earth
screw
RED
WHI
22
2-1-8. Floor Standing Cabinet Type
Model: MML-AP0071H, AP0091H, AP0121H, AP0151H, AP0181H, AP0241H
FM RC TR TA TC1,TC2,TCJ RY001 RY002 RY004 RY005~007 PMV
Fan motor Running capacitor Transformer Indoor temp sensor Temp sensor Louver control relay Drain control relay Heater control relay Fan motor control relay Pulse motor valve
Symbol
Parts name
Color
indication
RED : RED WHI : WHITE YEL : YELLOW BLU : BLUE BLK : BLACK GRY : GRAY PNK : PINK ORN : ORANGE BRW : BROWN GRN : GREEN
1. Indicates the terminal bolock. Letter at inside indicates the terminal number.
2. A dotted line and broken line indicate the wiring at side.
3. indicate the control p.c. board.
5 3 1779
9 5 3 1
RY007
P301
(BLK)
RY004
(GRY) CN304
(YEL) CN309
FUSE
T5.0A 250V~
RY006
RY005
H
RED BLK ORN BLU YEL
M LUL
313
1
313
1
313
1
RC
FM
CN104
(YEL)
TA
212
1
CN102
(RED)
TCJ
212
1
CN101
(BLK)
CN100
(BRN)
1
3
CN080 (GRN)
TC2
PNL
EXCT
2
1
CN073
(RED)
2
2
1
3
2
4 5
1
FILTER
CN070
(WHI)
CN081
(BLK)
2
1
212
1
112
2
112
2
112
X Y
2
3
2
1 1
3
1
1 233 1 2 3 4 5
1 2 3 4 5 6 1 2 1 23 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6
1 2 3 4 5 6 1 2 3 4 5 6
1 2 3 4 5 6 1 2 3 4 5 6
2
1
TC1
212
1
CN066
(WHI)
CN067
(BLK)
AC IN RED
WHI
CN040
(BLU)
Outdoor unit Remote Controller
Power supply single phase
220-240V 50Hz
220V 60Hz
Indoor unit earth screw
Closed-end
connector
Line Filter
RED
WHI
CN01(WHI)
CN03(RED)
CN02 (BLU)
CN041
(BLU)
CN050
(WHI)
CN061
(YEL)
T10
CN032
(WHI)
FAN
DRIVE
OPTION
CN060
(WHI)
BLU
BLU
BLK
BLK
RC
TR
U1
U1 U2
U2 A B
Network Adapter
(Option)
Control P.C. board
for Indoor unit
MCC-1403
MCC-1401
112
2
CN1
113
3
CN074
(WHI)
CN075
(WHI)
Power supply
circuit
TR
1
3
CN068
(BLU)
FAN
CN083
(WHI)
RY002
DP
1 3
CN033
(GRN)
RY001
LM
CN082 (BLU)
PMV
112 3
3
CN030
(RED)
FS
1 2 3 4 5 6
1 2 3 4 5 6
1 234 56
1 234 56
PMV
323
2
6
5
4
6
5
4
R(L) S(N)
CN01
(WHI)
CN02 (YEL)
Sub P.C. board
MCC-1520
Flow selector
unit earth
screw
23
2-1-9. Floor Standing Concealed Type
Model: MML-AP0071BH, AP0091BH, AP0121BH, AP0151BH, AP0181BH, AP0241BH
GRN
1. Indicates the terminal bolock. Letter at inside indicates the terminal number.
2. A dotted line and broken line indicate the wiring at side.
3. indicate the control p.c. board.
5 3 1779
9 5 3 1
RY007 R301 (BLK)
RY004
(GRY) CN304
(YEL) CN309
(BLK) CN067
FUSE
T5.0A 250V~
RY006
RY005
H
RED BLK ORN BLU YEL
M LUL
313
1
313
1
3
1
RC
WHI
131
3
CN104
(YEL)
TA
212
1
CN102
(RED)
TCJ
212
1
CN101
(BLK)
CN100 (BRW)
1
3
CN080
(GRN)
TC2
PNL
EXCT
2
1
CN073
(RED)
2
2
1
FILTER
CN070
(WHI)
CN081
(BLK)
2
1
2
1
112
2
112
2
112
2
2 2
3
2
1 1
1 1
3
1
1 233 1 2 3 4 5
1 2 3 4 5 6 1 2 1 23 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6
1 2 3 4 5 6 1 2 3 4 5 6
1 2 3 4 5 6 1 2 3 4 5 6
2
1
4
3
5
2
2
1
TC1
AC IN
CN044 (BRW)
2
1
CN066 (WHI)
CN040
(BLU)
Outdoor unit
Remote Controller
Power supply
single phase
220-240V 50Hz
220V 60Hz
Indoor unit earth screw
Closed-end
connector
CN01(WHI)
CN03(RED)
CN02 (BLU)
CN03
(RED)
CN041 (BLU)
CN050
(WHI)
CN061
(YEL)
CN032
(WHI)
FAN
DRIVE
OPTION
CN060
(WHI)
EMG
TR
RED
RED
WHI
WHI
U1 U2
U1 U2
A B X Y
Network
adapter (Option)
Control P.C. board
for undoor unit
MCC-1403
MCC-1401
For AP0071BH,AP0091BH,AP0121BH
112
2
CN1
113
3
CN074
(WHI)
CN075
(WHI)
Power supply
circuit
TR
1
133
CN068
(BLU)
FAN
CN083
(WHI)
RY002
113
3
112 3
3
CN033 (GRN)
RY001
CN082
(BLU)
CN030 (RED)
PMV
1 2 3 4 5 6
1 2 3 4 5 6
1 234 56
1 234 56
PMV
RED
424
2
3
6
5
3
6
5
R(L) S(N)
FM
GRN
5 3 1779
9 5 3 1
RED BLK ORN BLU YEL
FAN
CN083
(WHI)
RED
WHI
2
3
1
2
3
1
6
5
4
6
5
4
RC
FM
FM RC TR TA TC1,TC2,TCJ RY001 RY002 RY004 RY005~007 PMV
Fan motor Running capacitor Transformer Indoor temp sensor Temp sensor Louver control relay Drain control relay Heater control reley Fan motor control relay Pulse motor valve
Symbol
Parts name
Color
indication
RED : RED WHI : WHITE YEL : YELLOW BLU : BLUE BLK : BLACK GRY : GRAY PNK : PINK ORN : ORANGE BRW : BROWN GRN : GREEN
CN01 (WHI)
CN02 (YEL)
Sub P .C. board
MCC-1520
Flow selector
unit earth
screw
24
2-1-10. Floor Standing Type
Model: MMF-AP0151H, AP0181H, AP0241H, AP0271H, AP0361H, AP0481H, AP0561H
FM RC TR LM TA TC1,TC2,TCJ RY001 RY002 RY005~007 PMV
Fan motor Running capacitor Transformer Lover motor Indoor temp sensor Temp sensor Louver control relay Drain control relay Fan motor control relay Pulse motor valve
Symbol
Parts name
Color
indication
RED : RED WHI : WHITE YEL : YELLOW BLU : BLUE BLK : BLACK GRY : GRAY PNK : PINK ORN : ORANGE BRW : BROWN GRN : GREEN
1. Indicates the terminal bolock, letter. Letter at inside indicates the terminal number.
2. A dotted line and broken line indicate the wiring at side.
3. indicate the control p.c. board.
5 3 1779
9 5 3 1
RY007 P301 (BLK)
RY004
(GRY) CN304
(YEL) CN309
(BLK) CN067
FUSE
T5.0A 250V~
RY006
RY005
H
RED BLK ORN BLU YEL
M LUL
313
1
313
1
3
1
RC
BRW
FM
131
3
CN104
(YEL)
TA
212
1
CN102
(RED)
TCJ
212
1
CN101
(BLK)
CN100 (BRW)
1
3
CN080
(GRN)
TC2
PNL
EXCT
2
1
CN073
(RED)
2
2
1
FILTER
CN070
(WHI)
CN081
(BLK)
2
1
2
1
2
1
112
2
112
2
112
2
112
X Y
2
3
2
1 1
3
1
1 233 1 2 3 4 5
1 2 3 4 5 6 1 2 1 23 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6
2
1
4
3
5
2
1
TC1
CN066 (WHI)
AC IN
CN044 (BRW)
CN040 (BLU)
Outdoor unit Remote Controller
Power supply
single phase
220-240V 50Hz
220V 60Hz
Indoor unit earth screw
Closed-end
connector
Line Filter
CN01(WHI)
CN03(RED)
CN02 (BLU)
CN041
(BLU)
CN050
(WHI)
CN061
(YEL)
CN032 (WHI)
FAN
DRIVE
OPTION
CN060 (WHI)
EMG
BLU
BLU
RED
WHI
BLK
BLK
RC
TR
U1
U1 U2
U2 A B
Network Adapter
(Option)
Control P.C. board
for Indoor unit
MCC-1403
MCC-1401
112
2
CN1
113
3
CN074 (WHI)
CN075 (WHI)
Power supply
circuit
TR
1
3
CN068 (BLU)
FAN CN083 (WHI)
RY002
DP
113
3
CN033
(GRN)
RY001
LM
CN082
(BLU)
PMV
LM
112 3
3
CN030 (RED)
FS
221
1
1 2 3 4 5 6
1 2 3 4 5 6
1 234 56
1 234 56
PMV
R(L) S(N)
313
1
6
5
4
6
5
4
787
1 2 3 4 5 6 1 2 3 4 5 6
1 2 3 4 5 6 1 2 3 4 5 6
CN01 (WHI)
CN02 (YEL)
Sub P.C. board
MCC-1520
Flow selector
unit earth
screw
25
112
2
11223
3
CN311(BLU)
CN03 (WHI)
CN300
(WHI)
CN301
(WHI)
Except 5HP, 6HP
CN500 (WHI)
CN01 (BLU)
BLU
BLU
WHI
WHI
7
5
3
1
7
5
3
1
SV41
BLU
BLU
CN312(WHI)
313
1
SV2
BLU
BLU
CN324(RED)
313
1
SV3A
BLU
BLU
CN313(YEL)
313
1
SV3B
BLU
BLU
CN314(BLK)
313
1
SV3C
BLU
BLU
BRW
BRW
CN316(WHI)
Heater 1
131
3
CN315(BLU)
T Heater 2
131
3
CN310(WHI)
4 3 212
1
SV51
BLU BLU
SV42
BLU
BLU
RY503
CR503
RY502
CR502
RY506
CR506
RY507
CR507
RY508
CR508
RY509
CR509
RY516
CR516
RY517
L3
L1
CR517
RY504
CR504
U1 U2 U3U4 U5 U6
U1 U2 U5 U6
112
2
6 5 4 3 2 1 6 5 4 3 2 1
RED
BRN
BLU
ORN
YEL
WHI
PMV1
4 3 2 4 3 2 1
RED
BLK
WHI
6 5 4 3 2 1 6 5 4 3 2 1
RED
BRN
BLU
ORN
YEL
WHI
PMV2
Pressure
Sensor
PS
CN501 (RED)
4 3 1 4 3 2 1
RED
BLK
WHI
Pressure
Sensor
PD
CN508 (RED)
4 3 2 1 4 3 2 1
Option
Board
CN509
(BLK)
4 3 2 1 4 3 2 1
Option
Board
CN510
(WHI)
4 3 2 1 4 3 2 1
Option Board
CN512
(BLU)
CN306
(WHI)
63H1
4 3 2 1 4 3 2 1
1 3 1 3
Option Board
CN513
(BLU)
4 3 2 145
5 3 2 1
Option Board
CN308 (BLU)
63H2
1 3 1 3
BLU(BLK)
BLU(BLK)
CN502 (WHI)
313
1
TD1 (YEL)
TD2 (RED)
TS1 (GRY)
BLU(BLK)
BLU(BLK) BLK
BLK
313
1
CN504
(WHI)
CN503
(PNK)
TK1 (BLK)
BLU(BLK)
BLU(BLK)
313
1
CN514
(BLK)
TK2 (BLU)
BLU(BLK)
BLU(BLK)
313
1
CN515
(GRN)
TK3 (BLU)
BLU(BLK)
BLU(BLK)
313
1
CN516
(RED)
TK4 (GRN)
BLU(BLK)
BLU(BLK)
313
1
CN523
(YEL)
BLU
BLU
313
1
CN100
(BLK)
313
4 4
1
CN511
(GRN)
212
1
TE1 (BLK)
BLK BLK
CN505
(GRN)
212
1
TO (BLK)
BLK BLK
CN507
(YEL)
212
1
TL (WHI)
BLK BLK
CN521
(WHI)
212
2 2
1
Option board
313
4 4
1
CN600(WHI)
T6.3A FUSE
CN325
(YEL)
CN400
(WHI)
CN305(RED)
ORN
BLK BLK
ORN
CN307(WHI)
RY521RY511
CN401
WHI
RED
PNK
RED
BLU
WHI
BLK
CN402
2 2
5 5
5 3 1 3 2 17
7 5
4 4
333221
3 1 3 1
4 3 2 1
2 1
1 1
T6.3A FUSE
T6.3A FUSE
RED
WHI
BLK
GRY
CN317
(BLU)
CN323
(WHI)
4 4
33221
1
PNK
PNK
PNK
PNK
L1L2L3
N
ORN
RED
BLU
ORN
BLK(PNK)
BLK(PNK)
Comp1
Comp2
1 2 1 2
4WV1
SV3ESV
3D
RY518
CN321 (RED)
BRN
1 2 1 2
Accumulator
heater
RY510
CR521CR511
CR 510CR518
ON
SW30
SW01
SW06
4
31ON2
SW14
431ON2
SW13
1
ON SW08
4
31ON2
SW12
431ON2
SW11
431ON2
SW07
431ON2
SW06
431ON2
SW10
431ON2
SW09
SW05SW04
SW32
SW02 SW03
D603D602D601D600 D604
SW31
SW30
CN800
CN802
Flash
6
5
4
3
2
1
6
5
4
9
8
7
3
2
1
(Srvice)
3 1
3 1
3 1
3 1
3 2 1
3 2
5 4
5 4 1
3 2 1
3 2
5 4
5 4 1
3
1
CN18 (RED)
CN17 (BLK)
CN06 (WHI)
CN26 (BLU)
CN11 CN10 CN09
CN25 (WHI)
W V U
BLK
PNK
RED
BLU
WHI
BLK
PNK
RED
BLU
WHI
BLK
BLU
YEL
WHI RED YEL BLU
CN22 CN23
CM2
CN03 CN02 CN01
CN15 CN13
CN07 WHI
CN08 WHI
T S R
BLK WHI RED
Reactor
3 1
3 1
3 1
3 1
3 4 5
3 4
1 2
1 2 5
3 4 5
3 4
1 2
1 2
331
1
53 41 2 5
3 2 1
3 2
5 4
5 4 1
2 2 3 3
1 1
CN18 (RED)
CN17 (BLK)
CN06 (WHI)
CN26 (BLU)
CN500
(WHI)
CN503
(WHI)
CN504 CN505(RED)
CN506(BLK)
CN502
(BLU)
GRY
BLU YEL
RED
CN501 (RED)
CN11 CN10 CN09
CN25 (WHI)
YEL
BLU
W V U
CN21
CN01
CN02
CN03
RED
WHI
BLK
GRY
CN04
CN23(BLU)CN22(WHI)
CN17
CN18
CN19
CN20
BLK WHI RED YEL BLU
CN22 CN23
CM1
CN03 CN02 CN01
CN15
BLK
BLU
YEL
YEL
BLK
BLU
BLK
CN13
CN20 WHI
CN21 WHI
T S R
BLK WHI RED
Reactor
+–+–
1 3 1 3
1 3 1 3
1
3
5
2
4
6
2
4
6
A1 A2
Mg-SW OCR
RED
RED
RED RED RED WHI BLK
BLK
BLK
GRY GRY GRY
PTC Themistor
5 4 3 2 1
5 4 3 2 1
313
1
5
3
1
5
3
1
313
1
5 4 3 2 1
5 4 3 2 1
CN01 (WHI)
RED
WHI
BLK
WVU
FM
+
+–
YEL
PNK
PNK
RED
RED
BLU
BLU
WHI
BLK
WHI
BLK
BLU
Indoor
unit
Outdoor
unit
Central remote
controller
Transformer
RED
WHI
BLK GRY
L1
L2
L3
N
Power Supply
3phase
380-415V 50Hz
380 60Hz
RED : RED WHI : WHITE YEL : YELLOW BLU : BLUE BLK : BLACK GRY : GRAY PNK : PINK ORN : ORANGE BRN : BRWN VLT : VIOLET
1. The two-dot chain line indicates wiring at the local site, and the dashed line indicates accessories sold separately and service cables, respectively.
2. , , and indicate the terminal blocks and the numerals indicate the terminal numbers.
3. indicates P.C. board. * Be sure to fix the electric parts cover surely with two screws.
(Otherwise water enters into the box resulting in a trouble.)
CM1, CM2 PMV1, PMV2 SV2, SV41, SV42, SV51, SV3A, SV3B, SV3C, SV3D, SV3E 4WV1 COMP1, COMP2 TS1 TD1, TD2 TE1 TO TK1, TK2, TK3, TK4 TL HEATER1, HEATER2, ACCU MEATER FM PS PD 63H1, 63H2 MG-SW OCR
Compressor Pulse motor valve 2-way valve coil 4-way valve coil Compressor case thermo. Pipe temp. sensor (Inlet) Pipe temp. sensor (Outlet) Heat exchange temp. sensor Air temp. sensor Oil temp. sensor Liquid temp. sensor Case heater, 230V, 26W Fan motor (DC) Low pressure sensor High pressure sensor High pressure switch Magnet switch Overcurrent relay
Noise filter P.C. board MCC-1366
Fan IPDU MCC-896
Interface
control
P.C. board
(I/F)
MCC-1429
Power supply
terminal
Comp. IPDU
No.1
MCC-1502
MG-
SW
OCR
Comp. IPDU
No.2
MCC-1502
Power supply
for fan
MCC-1439
U1U2U3U4U5U
6
L1L2L3N
Connecting terminal
Interface Control P.C. Board
MCC-1429
IPDU Board (2)
MCC-1502
Noise filter
P.C. board MCC-1366
IPDU P.C. Board (1)
MCC-1502
FAN IPDU
P.C. Board
MCC-896, 897
Power supply
P.C. board for FAN
MCC-1439
Color
indication
Symbol
Parts name
Parts layout
Earth screw
U3 U4
U1 U2
BLK WHI BLU
BLU
RED PNK
YEL
2-2. Outdoor Unit
Model: MMY-MAP1401H, MAP1601H, MAP2241H, MAP2801H, MAP3351H
26
3. PARTS RATING
3-1. Indoor Unit
4-way Air Discharge Cassette Type
Model MMU-AP 0091H 0121H 0151H 0181H 0241H 0271H 0301H
Fan motor SWF-230-60-1 Drain pump motor ADP-1409 Float switch FS-0218-102 TA sensor Lead wire length : 155mm TC1 sensor Ø4 size lead wire length : 1200mm Vinyl tube (Blue) TC2 sensor Ø6 size lead wire length : 1200mm Vinyl tube (Black) TCJ sensor Ø6 size lead wire length : 1200mm Vinyl tube (Red) Pulse motor EDM-MD12TF-3 Pulse motor valve EDM-B25YGTF EDM-B40YGTF Louver motor (panel) MP24GA
Model MMU-AP 0361H 0481H 0561H
Fan motor SWF-200-90-1 Drain pump motor ADP-1409 Float switch FS-0218-102 TA sensor Lead wire length : 155mm TC1 sensor Ø4 size lead wire length : 1200mm Vinyl tube (Blue) TC2 sensor Ø6 size lead wire length : 1200mm Vinyl tube (Black) TCJ sensor Ø6 size lead wire length : 1200mm Vinyl tube (Red) Pulse motor EDM-MD12TF-3 Pulse motor valve EDM-B60YGTF-1 Louver motor (panel) MP24GA
2-way Air Discharge Cassette Type
Model MMU-AP 0071WH 0091WH 0121WH 0151WH 0181WH
Fan motor AF-230-53-4G AF-230-39-4B Running condenser for fan motor AC 400V, 1µF AC 450V, 2µF Running capacitor for fan motor AC 400V, 1.0µ F AC 450V, 2.0µ F Drain pump motor PJD-05230TF-1 Float switch FS-0208-608 Control P.C. board transformer TT-13 Pulse motor EDM-MD12TF-3 Pulse motor valve EDM-B25YGTF EDM-B40YGTF TA sensor Lead wire length : 268mm TC1 sensor Ø4 size lead wire length : 1200mm Vinyl tube (Blue) TC2 sensor Ø6 size lead wire length : 1200mm Vinyl tube (Black) TCJ sensor Ø6 size lead wire length : 1200mm Vinyl tube (Red)
Model MMU-AP 0241WH 0271WH 0301WH 0481WH
Fan motor AF-200-53-4F AF-200-92-4B Running condenser for fan motor AC 450V, 2.5µF AC 450V, 3µF A C 450V, 5µF Running capacitor for fan motor AC 450V, 2.5µF AC 450V, 3.5µF AC 500V, 5µF Drain pump motor PJD-05230TF-1 Float switch FS-0208-608 Control P.C. board transformer TT-13 Pulse motor EDM-MD12TF-3 Pulse motor valve EDM-B40YGTF EDM-B60YGTF-1 TA sensor Lead wire length : 268mm TC1 sensor Ø4 size lead wire length : 1200mm Vinyl tube (Blue) TC2 sensor Ø6 size lead wire length : 1200mm Vinyl tube (Black) TCJ sensor Ø6 size lead wire length : 1200mm Vinyl tube (Red)
Tentative
27
1-way Air Discharge Cassette (Compact type) Type
Model MMU-AP 0071YH 0091YH 0121YH
Fan motor AF-200-22-4N-1 Running capacitor for fan motor AC 400V, 1µF Drain pump motor PJD-05230TF-1 Float switch FS-0208-602 Control P.C. board transformer TT-13 Pulse motor EDM-MD12TF-3 Pulse motor valve EDM-B25YGTF TA sensor Lead wire length : 818mm TC1 sensor Ø4 size lead wire length : 1200mm Vinyl tube (Blue) TCJ sensor Ø6 size lead wire length : 1200mm Vinyl tube (Red)
Model MMU-AP 0151SH 0181SH 0241SH
Fan motor AF-200-34-4D Running capacitor for fan motor AC 450V, 1.5µF AC 500V, 2.5µ F Drain pump motor PJD-05230TF-2 Float switch FS-0208-603 Control P.C. board transformer TT-13 Pulse motor EDM-MD12TF-3 Pulse motor valve EDM-B40YGTF TA sensor Lead wire length : 155mm Vinyl tube TC1 sensor Ø4 size lead wire length : 1200mm Vinyl tube (Blue) TC2 sensor Ø6 size lead wire length : 1200mm Vinyl tube (Black) TCJ sensor Ø6 size lead wire length : 1200mm Vinyl tube (Red)
Concealed Duct Standard Type
Model MMD-AP 0071BH 0091BH 0121BH 0151BH 0181BH
Fan motor ICF-280-120-2 Drain pump motor ADP-1409 Float switch FS-0218-102 Pulse motor EDM-MD12TF-3 Pulse motor valve EDM-B25YGTF EDM-B40YGTF TA sensor Lead wire length : 618mm TC1 sensor Ø4 size lead wire length : 1200mm Vinyl tube (Blue) TC2 sensor Ø6 size lead wire length : 1200mm Vinyl tube (Black) TCJ sensor Ø6 size lead wire length : 1200mm Vinyl tube (Red)
Model MMD-AP 0241BH 0271BH 0301BH 0361BH 0481BH 0561BH
Fan motor ICF-280-120-1 ICF-280-120-2 Drain pump motor ADP-1409 Float switch FS-0218-102 Pulse motor EDM-MD12TF-3 Pulse motor valve EDM-B40YGTF EDM-B60YGTF-1 TA sensor Lead wire length : 618mm TC1 sensor Ø4 size lead wire length : 1200mm Vinyl tube (Blue) TC2 sensor Ø6 size lead wire length : 1200mm Vinyl tube (Black) TCJ sensor Ø6 size lead wire length : 1200mm Vinyl tube (Red)
Tentative
28
Tentative
Concealed Duct High Static Pressure Type
Model MMD-AP 0181H 0241H 0271H 0361H 0481H
Fan motor STF-200-160-4B STF-200-160-4A STF-200-260-4C STF-200-260-4B Running condenser for fan motor AC 500V, 4µF AC 400V, 8µF AC 450V, 6µF AC 400V, 8µF Drain pump motor ADP-1409 Float switch FS-0218-102-6 Pulse motor EDM-MD12TF-3 Pulse motor valve EDM-B40YGTF EDM-B60YGTF-1 TA sensor Lead wire length : 1200mm TC1 sensor Ø4 size lead wire length : 1200mm Vinyl tube (Blue) TC2 sensor Ø6 size lead wire length : 1200mm Vinyl tube (Black) TCJ sensor Ø6 size lead wire length : 1200mm Vinyl tube (Red)
Model MMD-AP 0721H 0961H
Fan motor STF-200-370-4A Running condenser for fan motor AC 450V, 12µF Drain pump motor ADP-1409 Float switch FS-0218-102-6 Pulse motor EDM-MD12TF-3 Pulse motor valve EDM-BAOYGTF-1 TA sensor Lead wire length : 818mm TC1 sensor Ø4 size lead wire length : 2000mm Vinyl tube (Blue) TC2 sensor Ø6 size lead wire length : 2000mm Vinyl tube (Black) TCJ sensor Ø6 size lead wire length : 2000mm Vinyl tube (Red)
Under Ceiling Type
Model MMC-AP 0151H 0181H 0241H 0271H 0361H 0481H
Fan motor SWF-280-60-1 SWF-280-60-2 SWF-280-120-2 Driving motor for horizontal grille MP24GA1 Pulse motor EDM-MD12TF-3 Pulse motor valve EDM-B40YGTF EDM-B60YGTF-1 TA sensor Lead wire length : 155mm Vinyl tube TC1 sensor Ø4 size lead wire length : 1200mm Vinyl tube (Blue) TC2 sensor Ø6 size lead wire length : 1200mm Vinyl tube (Black) TCJ sensor Ø6 size lead wire length : 1200mm Vinyl tube (Red)
High Wall Type
Model MMK-AP 0071H 0091H 0121H 0151H 0181H 0241H
Fan motor ICF-280-120-3 Driving motor for horizontal grille MT8-3-6 Pulse motor EDM-MD12TF-3 Pulse motor valve EDM-B25YGTF EDM-B40YGTF TA sensor Lead wire length : 818mm Vinyl tube TC1 sensor Ø4 size lead wire length : 1200mm Vinyl tube (Blue) TC2 sensor Ø6 size lead wire length : 1200mm Vinyl tube (Black) TCJ sensor Ø6 size lead wire length : 1200mm Vinyl tube (Red)
29
Tentative
Floor Standing Cabinet Type
Model MML-AP 0071H 0091H 0121H 0151H 0181H 0241H
Fan motor AF-200-19-4F AF-200-45-4F AF200-70-4K Running condenser for fan motor AC450V, 1.2µF AC400V, 1.8µF AC450V, 2µF Transformer TT13 Pulse motor EDM-MD12TF-3 Pulse motor valve EDM-B25YGTF EDM-B40YGTF TA sensor Lead wire length : 818mm Vinyl tube TC1 sensor Ø4 size lead wire length : 1200mm Vinyl tube (Blue) TC2 sensor Ø6 size lead wire length : 1200mm Vinyl tube (Black) TCJ sensor Ø6 size lead wire length : 1200mm Vinyl tube (Red)
Floor Standing Concealed Type
Model MML-AP 0071BH 0091BH 0121BH 0151BH 0181BH 0241BH
Fan motor AF-200-19-4G AF-200-70-4K Running condenser for fan motor AC450V, 1.5µF AC450V, 1µF AC450V, 2µF Transformer TT-13 Pulse motor EDM-MD12TF-3 Pulse motor valve EDM-B25YGTF EDM-B40YGTF TA sensor Lead wire length : 818mm Vinyl tube
TC1 sensor
Ø4 size lead wire length : 2000mm Vinyl tube (Blue) TC2 sensor Ø6 size lead wire length : 2000mm Vinyl tube (Black) TCJ sensor Ø6 size lead wire length : 2000mm Vinyl tube (Red)
Floor Standing Type
Model MMF-AP 0151H 0181H 0241H 0271H 0361H 0481H 0561H
Fan motor AF-200-37R AF-200-63T
AF-200-110M -1
AF-200-160H-1 Running condenser for fan motor AC500V, 3µF AC500V, 3.5µF AC500V, 4µF Transformer TT-13 Pulse motor EDM-MD12TF-3 Pulse motor valve EDM-B40YGTF EDM-B60YGTF-1 Driving motor for vertical flap MT8-3-9 TA sensor Lead wire length : 1200mm Vinyl tube
TC1 sensor
Ø4 size lead wire length : 1200mm Vinyl tube (Blue) TC2 sensor Ø6 size lead wire length : 2000mm Vinyl tube (Black) TCJ sensor Ø6 size lead wire length : 1200mm Vinyl tube (Red)
30
Tentative
3-2. Outdoor Unit
Cooling Only Model
Model MMY- MAP0501∗T8 MAP0601∗T8 MAP0801∗T8 MAP1001∗T8 MAP1201∗T8
Compressor DA 351A3FB-23M Output: : 3.0kW × 2 DA421A3FB-23M Output: : 3.75kW × 2
4-way valve coil (Heat pump only) VHV-01AJ502C1
AC220-240V 50/60Hz
LB64046 AC220-240V 50/60Hz
Pulse motor valve coil VPV-MOAJ524C0 HAM-MD12TF-3 DC12V
AC220–240V 50/60Hz SV2, SV3D, SV42
2-way valve coil VPV-122DQ1
SV3A, SV3B, SV3C, SV3E, SV41, SV5
VPV-303DQ1 SV2, SV3C, SV3D, SV3E
SV3A, SV41, SV42, SV5
2-way valve
VPV-603DQ2
SV3B High-pressure SW ACB-JB215 OFF : 3.73MPa, ON : 2.9MPa Pressure sensor
(For high pressure)
150XA4-H3 0.5 to 3.5V / 0 to 0.9 8MPa
Pressure sensor (For low pressure)
150XA4-L1 0.5 to 4.3V / 0 to 3.73MPa
Fan motor MF-230-600-2 DC280V, 600W Case heater AC240V, 26W × 3 Compressor case the rmo US-622KXTM Q O - SS OFF : 125°C, ON : 90°C × 2
Heat Pump Model
Model MMY-
MAP0501HT7 MAP0601HT7 MAP0801HT7 MAP1001HT7 MAP1201HT7
Compressor DA 351A3FB-22M Output: : 3.0kW × 2 DA421A3FB-22M Output: : 3.7kW × 2 4-way valve coil VHV AC200V 50/ 60Hz LB64 AC200V 50/60Hz Pulse motor valve coil HAM-MD12TF-3 DC12V 2-way valve coil VPV AC200V 50/60Hz SV2, SV3D, SV42, SV3A, SV3B, SV3C, SV3E, SV41, SV5
VPV-122DQ1 SV2, SV3C, SV3D, SV3E VPV-303DQ1 SV3A, SV41, SV42, SV52-way valve
VPV-122DQ1 SV3B High-pressure SW SCB-JB215 OFF : 3.73MPa, ON : 2.9MPa Pressure sensor
(For high pressure)
150XA4-H3 0.5 to 3.5V / 0 to 0.9 8MPa
Pressure sensor (For low pressure)
150XA4-L1 0.5 to 4.3V / 0 to 3.73MPa
Fan motor MF-230-600-2 DC280V, 600W Case heater AC200V, 26W × 3 Compressor case the rmo US-622KXTM Q O - SS OFF : 125°C, ON : 90°C × 2