Toshiba RAS-13YA-E, RAS-13YK-E, RAS-13YA-ES, RAS-13YK-ES SERVICE MANUAL

0 (0)

FILE NO. DAS-SM-00-002

SUPPLEMENT

SERVICE MANUAL

AIR-CONDITIONER

SPLIT WALL TYPE

RAS-13YKX / RAS-13YAX RAS-13YK-E / RAS-13YA-E RAS-13YK-ES / RAS-13YA-ES RAS-13YK-HX / RAS-13YA-HX RAS-13YKX-T / RAS-13YAX-T RAS-13YKX-T2 / RAS-13YAX-T2

 

CONTENTS

 

1.

SPECIFICATIONS .....................................................................................

3

2.

CONSTRUCTION VIEWS ........................................................................

7

3.

WIRING DIAGRAM ..................................................................................

9

4.

SPECIFICATIONS OF ELECTRICAL PARTS .....................................

10

5.

REFRIGERANT CYCLE DIAGRAM .....................................................

12

6.

CONTROL BLOCK DIAGRAM .............................................................

13

7.

OPERATION DESCRIPTIONS................................................................

14

8.

INSTALLATION PROCEDURE ..............................................................

19

9.

TROUBLESHOOTING CHART ..............................................................

32

10.

PART REPLACEMENT ..........................................................................

47

11.

EXPLODED VIEWS AND PARTS LIST ..............................................

51

– 2 –

1. SPECIFICATIONS

RAS-13YK-E/13YA-E, RAS-13YK-ES/13YK-ES

 

 

 

 

MODEL

RAS-13YK-E/13YA-E

 

RAS-13YK-ES/13YA-ES

ITEM

 

 

 

 

 

 

Cooling

Capacity

 

 

 

 

kW *1

 

220V–240V

 

 

 

 

 

3,70–3,75

 

 

 

 

 

Phase

 

Single

Power source

 

 

 

 

V

 

220–240

 

 

 

 

 

Hz

 

50

Power consumption

 

 

 

 

kW

 

1,25–1,29

Power factor

 

 

 

%

 

98–95

Running current

 

 

 

 

V

 

220V–240V

Indoor/Outdoor

 

 

 

A

0,15/5,66–0,15/5,53

 

 

 

 

Starting current

 

 

 

 

A

 

24

Moisture removal

 

 

 

 

lit/h

 

2,0

Noise

Indoor (H/M/L)

 

 

 

dB (A)

 

44 / 39 / 34

(SPL at 1 meter)

Outdoor (220–240V)

 

dB (A)

47–48

 

47–48

Refrigerant

Name of refrigerant

 

 

R-22

 

R-410A

Rated volume

 

 

 

kg

0,90

 

0,82

 

 

 

 

 

Refrigerant control

 

 

 

 

 

 

Capillary tube

 

Gas side size

 

 

 

mm

12,7

 

9,52

 

Connection type

 

 

 

 

Flare connection

 

Liquid side size

 

 

 

mm

 

6,35

Interconnection pipe

Connection type

 

 

 

 

Flare connection

Maximum length (of one way)

 

m *2

 

15

 

 

 

 

Maximum height difference

 

 

 

 

 

 

Indoor unit

 

 

 

 

 

6

 

 

m

 

 

Outdoor unit

 

 

 

 

 

 

 

 

 

 

Condensate drain pipe

Outer diameter

 

 

 

mm

 

16

INDOOR UNIT

 

 

 

 

 

RAS-13YK-E

 

RAS-13YK-ES

 

Height

 

 

 

mm

 

265

Dimensions

Width

 

 

 

mm

 

790

 

Depth

 

 

 

mm

 

189

Net weight

 

 

 

 

kg

 

8

Evaporator type

 

 

 

 

 

 

Finned tube

Indoor fan type

 

 

 

 

 

 

Cross flow fan

 

High fan

 

 

 

m³/h

 

650

Air flow rate

Medium fan

 

 

 

m³/h

 

560

 

Low fan

 

 

 

m³/h

 

510

Fan motor output

 

 

 

 

W

 

20

Air filter

 

 

 

 

 

Polypropylene net filter (Washable)

OUTDOOR UNIT

 

 

 

 

 

RAS-13YA-E

 

RAS-13YA-ES

 

Height

 

 

 

mm

 

538

Dimensions

Width

 

 

 

mm

 

780

 

Depth

 

 

 

mm

 

300

Net weight

 

 

 

 

kg

37

 

39

Condenser type

 

 

 

 

 

 

Finned tube

Outdoor fan type

 

 

 

 

 

 

Propeller

Air flow rate (220–240V)

 

 

 

 

m³/h

 

1700–1900

Fan motor output

 

 

 

 

W

27 (UE6-31C5P)

Compressor

Model

 

 

 

 

2KS224D5CD02

 

PA150X2T-4FM

Output

 

 

 

W

 

1100

 

 

 

 

 

Safety device

 

 

 

 

 

Fuse, Overload relay

Auto louver

 

 

 

 

 

 

Yes

Usable outdoor temperature range

 

 

 

°C

 

21–43

Specifications are subject to change without notice.

– 3 –

RAS-13YKX/13YAX, RAS-13YK-HX/11-3YA-HX

 

 

 

 

 

 

MODEL

RAS-13YKX/13YAX

 

RAS-13YK-HX/13YA-HX

ITEM

 

 

 

 

 

 

 

Cooling

 

Capacity

 

 

 

 

 

 

kW *1

220V–240V

 

 

 

 

 

 

 

3,70–3,75

 

3,55–3,55

 

 

 

 

 

 

 

Phase

Single

 

Power source

 

 

 

 

 

 

V

220–240

 

 

 

 

 

 

 

 

Hz

50

 

Power consumption

 

 

 

 

 

 

kW

1,25–1,29

 

1,04–1,08

Power factor

 

 

 

 

 

%

98–95

 

98–95

Running current

 

 

 

 

 

 

V

220V–240V

 

Indoor/Outdoor

 

 

 

 

 

A

0,15/5,66–0,15/5,53

 

0,15/4,68–0,15/4,61

 

 

 

 

 

 

 

Starting current

 

 

 

 

 

 

A

24

 

22

Moisture removal

 

 

 

 

 

 

lit/h

2,0

 

Noise

Indoor (H/M/L)

 

 

 

 

 

dB (A)

44 / 39 / 34

 

44 / 39 / 34

(SPL at 1 meter)

Outdoor (220–240V)

 

dB (A)

47–48

 

49–50

Refrigerant

Name of refrigerant

 

 

R-22

 

Rated volume

 

 

 

 

 

kg

0,80

 

0,75

 

 

 

 

 

 

 

Refrigerant control

 

 

 

 

 

 

 

Capillary tube

 

Gas side size

 

 

 

 

 

mm

12,7

 

 

Connection type

 

 

Flare connection

 

Liquid side size

 

 

 

 

 

mm

6,35

 

Interconnection pipe

Connection type

 

 

Flare connection

Maximum length (of one way)

 

m *2

15

 

 

 

 

 

Maximum height difference

 

 

 

 

 

 

Indoor unit

 

 

 

 

 

 

6

 

 

 

 

m

 

 

Outdoor unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Condensate drain pipe

Outer diameter

 

 

 

 

 

mm

16

 

INDOOR UNIT

 

 

 

 

 

 

 

RAS-13YKX

 

RAS-13YK-HX

 

Height

 

 

 

 

 

mm

265

 

Dimensions

Width

 

 

 

 

 

mm

790

 

 

Depth

 

 

 

 

 

mm

189

 

Net weight

 

 

 

 

 

 

kg

8

 

Evaporator type

 

 

 

 

 

 

 

Finned tube

 

Indoor fan type

 

 

 

 

 

 

 

Cross flow fan

 

High fan

 

 

 

 

 

m³/h

650

 

Air flow rate

Medium fan

 

 

 

 

 

m³/h

560

 

 

Low fan

 

 

 

 

 

m³/h

510

 

Fan motor output

 

 

 

 

 

 

W

20

 

Air filter

 

 

 

 

 

 

 

Polypropylene net filter (Washable)

OUTDOOR UNIT

 

 

 

 

 

 

 

RAS-13YAX

 

RAS-13YA-HX

 

Height

 

 

 

 

 

mm

538

 

Dimensions

Width

 

 

 

 

 

mm

780

 

 

Depth

 

 

 

 

 

mm

300

 

Net weight

 

 

 

 

 

 

kg

37

 

40

Condenser type

 

 

 

 

 

 

 

Finned tube

 

Outdoor fan type

 

 

 

 

 

 

 

Propeller

 

Air flow rate (220–240V)

 

 

 

 

 

 

m³/h

1700–1900

 

1730–1930

Fan motor output

 

 

 

 

 

 

W

27 (UE6-31C5P) or 30 (HF-240-30A)

 

28 (HF-230-28P)

Compressor

Model

 

 

 

 

 

 

PH160T2-4L2

 

PH142T2-4K7

Output

 

 

 

 

 

W

1100

 

 

 

 

 

 

 

 

Safety device

 

 

 

 

 

 

 

Fuse, Overload relay

Auto louver

 

 

 

 

 

 

 

Yes

 

Usable outdoor temperature range

 

 

 

 

 

°C

21–43

 

Specifications are subject to change without notice.

– 4 –

RAS-13YKX-T / 13YAX-T, RAS-13YKX-T2/13YAX-T2

 

 

 

 

 

MODEL

RAS-13YKX-T/13YAX-T

 

RAS-13YKX-T2/13YAX-T2

ITEM

 

 

 

 

 

 

Cooling

Capacity

 

 

 

 

 

kW *1

220V

 

 

 

 

 

3,60

 

 

 

 

 

 

Phase

Single

Power source

 

 

 

 

 

V

220

 

 

 

 

 

 

Hz

50

Power consumption

 

 

 

 

 

kW

1,16

 

1,04

Power factor

 

 

 

 

%

98

Running current

 

 

 

 

 

V

220V

Indoor/Outdoor

 

 

 

A

0,15/5,24

 

0,15/4,68

 

 

 

 

 

Starting current

 

 

 

 

 

A

22

Moisture removal

 

 

 

 

 

lit/h

2,0

Noise

Indoor (H/M/L)

 

 

 

dB (A)

44 / 39 / 34

(SPL at 1 meter)

Outdoor (220V)

 

 

 

dB (A)

47

 

49

Refrigerant

Name of refrigerant

 

 

R-22

 

 

 

 

 

 

 

 

 

Rated volume

 

 

 

kg

0,72

 

0.83

 

 

 

 

 

Refrigerant control

 

 

 

 

 

 

Capillary tube

 

Gas side size

 

 

 

mm

12,7

 

Connection type

 

 

 

 

Flare connection

 

 

 

 

 

 

 

 

 

Liquid side size

 

 

 

mm

6,35

Interconnection pipe

Connection type

 

 

 

 

Flare connection

Maximum length (of one way)

 

m *2

15

 

 

 

Maximum height difference

 

 

 

 

 

 

Indoor unit

 

 

 

 

 

 

6

 

 

 

m

 

 

 

 

 

 

 

 

 

Outdoor unit

 

 

 

 

 

 

 

 

 

 

 

 

 

Condensate drain pipe

Outer diameter

 

 

 

mm

16

INDOOR UNIT

 

 

 

 

 

 

RAS-13YKX-T

 

RAS-13YKX-T

 

Height

 

 

 

mm

265

Dimensions

Width

 

 

 

mm

790

 

Depth

 

 

 

mm

189

Net weight

 

 

 

 

 

kg

 

8

Evaporator type

 

 

 

 

 

 

Finned tube

Indoor fan type

 

 

 

 

 

 

Cross flow fan

 

High fan

 

 

 

m³/h

650

Air flow rate

Medium fan

 

 

 

m³/h

560

 

Low fan

 

 

 

m³/h

510

Fan motor output

 

 

 

 

 

W

20

Air filter

 

 

 

 

 

 

Polypropylene net filter (Washable)

OUTDOOR UNIT

 

 

 

 

 

 

RAS-13YAX-T

 

RAS-13YAX-T

 

Height

 

 

 

mm

538

Dimensions

Width

 

 

 

mm

780

 

Depth

 

 

 

mm

300

Net weight

 

 

 

 

 

kg

38

 

41

Condenser type

 

 

 

 

 

 

Finned tube

Outdoor fan type

 

 

 

 

 

 

Propeller

Air flow rate (220V)

 

 

 

 

 

m³/h

1700

 

1830

Fan motor output

 

 

 

 

 

W

27 (UE6-31C5P) or 30 (HF-240-30A)

 

28 (AF-230-28P) or 42 (HF-240-42A)

Compressor

Model

 

 

 

 

RM5515FNE96

Output

 

 

 

W

1100

 

 

 

 

Safety device

 

 

 

 

 

 

Fuse, Overload relay

Auto louver

 

 

 

 

 

 

Yes

Usable outdoor temperature range

 

 

 

°C

21–43

Specifications are subject to change without notice.

– 5 –

Note : *1

• Capacity is based on the following temperature conditions.

CONDITION

COOLING

TEMPERATURE

 

(DB)

27 °C

Indoor unit inlet air temperature

 

(WB)

19 °C

(DB)

35 °C

Outdoor unit inlet air temperature

 

(WB)

24 °C

Notes : *2 CHARGELESS

No additional refrigerant required.

This air conditioner accepts a connection piping length of up to 15m and a head of up to 6m.

There is no need to add the refrigerant as long as the total length of the connection piping is up to 15m.

– 6 –

2. CONSTRUCTION VIEWS

2-1. Indoor Unit

Air inlet

Air filter

Heat exchanger

 

790

189

265

1800

Air outlet

790

232

326

232

Hanger

 

50

47

10

 

Knock out system

13YK-E, 13YK-ES : Without power cord

13YKX, 13YKX-T, 13YKX-T2 : With power cord

13YK-HX :

With power cord & plug

Front panel

Back body

50

Drain hose (0,54m)

321

 

Hanger

 

 

Connecting pipe (0,39m)

Connecting pipe (0,49m)

Flare Ø12,7

 

(Flare Ø6,35)

(Flare Ø9,52 for 13YK-ES only)

 

 

 

 

65,5

 

659

65,5

Hanger

 

 

 

 

 

450

 

 

 

 

 

 

 

For stud bolt

 

 

Hanger

 

326

 

 

 

 

 

(Ø8~Ø10)

 

 

 

 

 

66 or more

 

 

 

 

 

 

 

 

 

 

 

 

 

Minimum

 

For stud bolt

 

46

20

2,5

 

distance

20

(Ø6)

 

 

to ceiling

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Minimum

265

178,5

17

Minimum

 

 

20

distance

distance

 

 

to wall

 

 

 

to wall

 

 

 

 

 

 

 

120 or more

 

 

120 or more

 

40,5

3,5

 

 

 

37

40,5

 

 

Hanger

Hanger

 

 

 

 

 

 

 

 

 

 

 

Center line

Installation

 

 

 

 

 

 

plate outline

 

 

 

 

 

 

 

60,5

 

 

 

 

 

 

 

 

 

76

319

269

126

 

 

 

 

 

 

790

 

 

10

47

Knock out system

– 7 –

2-2. Outdoor Unit

A Detail Drawing

 

 

600

 

50

R10

 

36

 

 

325 301

 

23

 

Ø6 hole

Ø11x14 hole

A

 

 

120

 

 

Gas side (Flare Ø12,7)

 

 

(Flare Ø9,52 for 13YA-ES)

325

52,5

Liquid side (Flare Ø6,35)

 

 

 

Ø25Drain outlet

8-Ø6 hole (for fixing outdoor unit)

 

 

 

 

6-Ø11x14 hole (for Ø8-Ø10 anchor bolt)

Handle

Fan guard

 

 

 

 

ø420

 

 

 

 

538

 

27

 

 

 

 

 

 

 

 

100

130

300

600

90

(8,5)

 

780

 

59

 

Electric parts cover

 

Z

54 61

 

 

Service

 

port

325 (pitch)

(8,5)

342

 

Z View

Installation dimension

100 or more

600

Air inlet 600 or more

 

325

 

100 or more

600 or more 4xØ11x14 Long holes (for Ø8-Ø10 anchor bolt)

Air outlet

 

– 8 –

Toshiba RAS-13YA-E, RAS-13YK-E, RAS-13YA-ES, RAS-13YK-ES SERVICE MANUAL

3. WIRING DIAGRAM

Datail A

RAS-13YK-HX

RAS-13YA-HX

L

N

Power cord with plug

RAS-13YK-E

RAS-13YA-E

RAS-13YK-ES

RAS-13YA-ES

A

POWER L

TERMINAL N

 

BLOCK

RAS-13YKX

RAS-13YAX

RAS-13YKX-T

RAS-13YAX-T

RAS-13YKX-T2

RAS-13YAX-T2

Datail C

FAN MOTOR

RAS-13YA-ES only

C

 

 

 

 

 

 

 

 

 

LOUVER MOTOR

 

 

 

 

 

 

 

 

 

 

Datail B

 

B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RAS-13YKX, 13YKX-T

 

RAS-13YK-E

 

 

 

 

 

 

 

 

 

INFRARED RAYS RECEIVE

 

 

 

 

 

 

 

 

 

 

 

AND INDICATION PARTS

RAS-13YKX-T2, 13YK-HX

 

RAS-13YK-ES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

2

3

4

5 6

7

8 9

CN25

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

2

3

4

5 6

7

8 9

 

THERMAL

 

 

 

 

THERMAL

 

 

 

 

 

 

 

 

 

BLU BLU BLU BLU BLU BLU PNK BLK WHI

 

77˚C x 1

 

 

 

 

77˚C x 2

 

 

 

 

 

 

 

 

 

 

FUSE

 

 

 

 

 

FUSE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ORN

ORN

 

 

ORN

ORN

 

 

 

 

 

BLU

PNK YEL ORN RED BRW

 

 

 

 

 

 

 

 

 

 

 

 

 

CN04

1 2

 

 

 

 

 

 

 

6

5 4

3

2 1

 

 

 

 

 

 

 

 

 

 

 

 

 

1 2

 

 

 

 

CN07 6

5 4

3

2 1

1

2

3

4

5 6

7

8 9

CN13

BLK

P04

SG01

R22

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GRN&YEL

DSA

VARISTOR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VARISTOR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F01

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BRW

 

 

6,3A

 

 

 

 

C01

 

 

 

 

R01

 

DB01

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C02

 

 

 

 

 

 

 

 

250V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BLU

 

3

3

R21 C15

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

POWER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SUPPLY

 

 

 

 

 

L01

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RY02

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DC 12V

 

CIRCUIT

 

 

 

 

RY01

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BLK 4

4

 

 

 

 

 

CR03

 

IC 03

 

DC 5V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WHI

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C58

 

 

 

 

 

 

MCC-798

 

 

 

 

 

 

1

2

3

CN11

 

5

 

 

3

 

1

CN10

1

2

CN03

 

1

2

CN01

 

 

 

 

 

 

1

2

3

 

BLK

5

 

 

3

 

1

 

 

 

1

2

 

 

 

1

2

 

 

 

 

 

 

 

YEL BLK BRW

 

 

 

 

PNK WHI

 

 

BLK BLK

 

 

BLK BLK

 

 

 

 

 

 

 

 

 

 

 

1

2

3

 

4

5

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

2

3

 

4

5

6

 

 

 

 

 

 

 

 

 

 

 

 

TERMINALBLK

WHI

GRN&YEL

AC FAN MOTOR

 

INDOOR

 

 

 

 

 

BLOCK

1

 

2

 

 

 

 

 

INDOOR

 

OUTDOOR

 

 

OUTDOOR

 

 

 

 

 

 

TERMINAL

 

 

 

 

 

BLOCK

1

 

2

 

 

 

 

 

 

BLK

 

 

GRN & YEL

 

OVER LOAD

 

 

 

CHASSIS

 

RELAY

BLK BLK

RED RED

 

 

 

 

 

 

 

FAN

 

CAPACITOR

CAPACITOR

COMPRESSOR

MOTOR

 

 

 

 

 

RED

 

 

 

 

 

 

 

 

 

 

WHI

 

 

PNK

 

 

 

 

 

WHI

 

 

 

 

THERMO HEAT SENSOR EXCHANGER

(TA) SENSOR (TC)

COLOR IDENTIFICATION

BRW : BROWN RED : RED WHI : WHITE YEL : YELLOW BLU : BLUE BLK : BLACK GRY : GRAY PNK : PINK ORN : ORANGE

GRN&YEL : GREEN & YELLOW

– 9 –

4. SPECIFICATIONS OF ELECTRICAL PARTS

4-1. Indoor Unit

RAS-13YKX, RAS-13YK-E, RAS-13YKX-T

RAS-13YKX-T2, RAS-13YK-HX, RAS-13YK-ES

No.

PARTS NAME

TYPE

SPECIFICATIONS

 

 

 

 

 

 

 

 

 

 

Output (Rated) 20W, 6poles, 1phase, 220–240V, 50Hz

 

Fan motor (for indoor)

 

 

 

 

1

MMF-240-20-4A

Winding resistance (W)

Red-Black

White-Black

 

 

 

(at 20°C)

220,8

324,3

 

 

 

 

 

 

 

 

 

 

2

Thermo. sensor (TA-sensor)

(Microprocessor)

10kW at 25°C

 

 

 

 

 

 

 

 

3

Switching transformer

SWT-47

 

 

 

 

 

 

 

 

 

4

Microcomputer

TMP87CK40AN

 

 

 

 

 

 

 

 

 

5

Power relay, Common relay

DI1U

Coil : DC 12V 75mA, Rated AC 250V 20A

 

(RY01, RY02)

 

 

 

 

 

 

 

 

 

 

 

 

6

Heat exchanger sensor (TC-sensor)

(Microprocessor)

10kW at 25°C

 

 

 

 

 

 

 

 

7

Line filter (L0)

SS11V-06180

18mH, AC 0,6A

 

 

 

 

 

 

 

 

8

Diode (DB01)

D3SBA60

4A, 600V

 

 

 

 

 

 

 

 

9

Capacitor (C02)

ECEC2GA470BL

47mF, 400V

 

 

 

 

 

 

 

 

10

Fuse (F01)

TSCR

T6, 3A, 250V

 

 

 

 

 

 

 

 

11

Varistor (R21, R109)

15G561K

560V

 

 

 

 

 

 

 

 

12

Resistor (R01)

 

5,6W, 2W

 

 

 

 

 

 

13

Louver motor

MP35EA12

Output (Rated) 2W, 10poles, 1phase DC 12V

 

 

 

 

 

 

4-2. Outdoor Unit

RAS-13YAX, RAS-13YA-E, RAS-13YAX-T

RAS-13YAX-T2, RAS-13YA-HX, RAS-13YA-ES

No.

PARTS NAME

TYPE

SPECIFICATIONS

 

 

 

 

 

 

 

 

 

 

 

 

Output (Rated) 1100W, 2poles, 1phase, 220–240V, 50Hz

 

 

RAS-13YA-E

2KS224D5CD02

 

 

 

 

 

Winding resistance (W)

C-R

C-S

 

 

 

 

 

 

 

 

 

 

(at 20°C)

2,21

2,92

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output (Rated) 1100W, 2poles, 1phase, 220–240V, 50Hz

 

 

RAS-13YAX

PH160T2-4L2

 

 

 

 

 

Winding resistance (W)

C-R

C-S

 

 

 

 

 

 

 

 

 

 

(at 20°C)

2,43

3,78

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output (Rated) 1100W, 2poles, 1phase, 220–240V, 50Hz

 

 

RAS-13YAX-T

 

 

 

 

1

Compressor

RM5515FNE96

Winding resistance (W)

C-R

C-S

RAS-13YAX-T2

 

 

 

 

 

 

 

 

(at 20°C)

2,16

3,90

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output (Rated) 1100W, 2poles, 1phase, 220–240V, 50Hz

 

 

RAS-13YA-HX

PH142T2-4K7

 

 

 

 

 

Winding resistance (W)

C-R

C-S

 

 

 

 

 

 

 

 

 

 

(at 20°C)

2,43

3,78

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output (Rated) 1100W, 2poles, 1phase, 220–240V, 50Hz

 

 

RAS-13YA-ES

PA150X2T-4FM

 

 

 

 

 

Winding resistance (W)

C-R

C-S

 

 

 

 

 

 

 

 

 

 

(at 20°C)

2,49

3,95

 

 

 

 

 

 

 

 

 

 

 

 

– 10 –

No.

PARTS NAME

TYPE

SPECIFICATIONS

 

 

 

 

 

 

 

 

 

 

 

 

Output (Rated) 27W, 6poles, 1phase, 220–240V, 50/60Hz

 

 

RAS-13YA-E

 

 

 

 

 

 

UE6-31C5P

Winding resistance (W)

Red-Black

White-Black

 

 

RAS-13YA-ES

 

 

 

 

 

 

 

 

(at 20°C)

210

435

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output (Rated) 27W, 6poles, 1phase, 220–240V, 50/60Hz

 

 

 

 

 

 

 

 

 

 

UE6-31C5P

Winding resistance (W)

Red-Black

White-Black

 

 

RAS-13YAX

 

(at 20°C)

210

435

 

 

 

 

 

 

 

 

 

 

 

 

RAS-13YAX-T

 

Output (Rated) 30W, 6poles, 1phase, 220–240V, 50/60Hz

 

 

 

 

 

Fan motor

 

HF-240-30A

 

 

 

2

 

Winding resistance (W)

Red-Black

White-Black

(for outdoor)

 

(For altinate use)

 

 

 

 

 

 

(at 20°C)

245

388

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output (Rated) 28W, 6poles, 1phase, 220–240V, 50/60Hz

 

 

 

 

 

 

 

 

 

 

AF-230-28P

Winding resistance (W)

Red-Black

White-Black

 

 

 

 

 

 

 

 

RAS-13YA-HX

 

(at 20°C)

162,1

233,5

 

 

 

 

 

 

RAS-13YAX-T2

 

Output (Rated) 42W, 6poles, 1phase, 220–240V, 50/60Hz

 

 

 

HF-240-42A

 

 

 

 

 

 

Winding resistance (W)

Red-Black

White-Black

 

 

 

(For altinate use)

 

 

 

 

 

 

 

 

(at 20°C)

176,

291

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RAS-13YA-E

SK-50FMP1,5U2

AC 500V, 1,5mF

 

 

 

 

RAS-13YA-ES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Running capacitor

RAS-13YAX

DS501155BPQA

AC 500V, 1,5mF

 

 

3

RAS-13YAX-T

 

 

 

 

 

 

(for fan motor)

 

 

 

 

 

 

RAS-13YAX-T2

DS451205BPQA

AC 450V, 2,0mF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RAS-13YA-HX

SK-45FMP02U2

AC 450V, 35mF

 

 

 

 

 

 

 

 

 

 

 

RAS-13YAX

SH-D CAP

AC 400V, 35mF

 

 

 

 

 

 

 

 

 

 

Running capacitor

RAS-13YA-E

SK-40CMP35U1

AC 400V, 25mF

 

 

4

RAS-13YA-ES

 

 

 

 

 

 

 

(for compressor)

 

 

 

 

 

 

RAS-13YA-HX

 

 

 

 

 

 

 

 

 

 

 

 

RAS-13YAX-T

SH-D CAP

AC 440V, 25mF

 

 

 

 

RAS-13YAX-T2

 

 

 

 

 

 

 

 

 

 

 

 

 

RAS-13YAX

 

 

 

 

 

 

RAS-13YA-E

 

 

 

 

 

 

RAS-13YAX-T

LAAO00A

U/T 9,0A (80°C), OPEN 135 ± 5°C, CLOSE 75 ± 11°C

5

Overload relay

RAS-13YAX-T2

 

 

 

 

 

 

RAS-13YA-HX

 

 

 

 

 

 

 

 

 

 

 

 

 

RAS-13YA-ES

Internal Overload Use

 

 

 

 

 

 

 

 

 

– 11 –

5. REFRIGERANT CYCLE DIAGRAM

Connecting pipe 0,39m Ø12,7

(for RAS-13YK-ES Ø9,52)

Indoor unit

T

Evaporator

 

Cross flow fan

 

Connecting pipe 0,49m Ø6,35

 

 

Optional piping kits

 

 

O.D.:12,7mm

P

RB-P31BFH1 (3m)

 

O.D.:6,35mm

RB-P51BFH1 (5m)

 

(for RAS-13YK-ES/

 

 

 

RB-P71BFH1 (7m)

 

 

13YA-ES 9,25mm)

 

 

 

Packed valve

 

Packed valve

 

 

 

 

 

Ø12,7 (for RAS-13YA-ES Ø9,52)

(Ø6,35)

 

Accumulator

 

Capillary tube

 

 

 

B

 

Compressor

A

 

Dryer

 

 

 

 

 

Condenser

 

 

 

 

Propeller fan

Refrigerant

C

Outdoor unit

Mark ( ) means check points of Gas Leak

MODEL

A Compressor

B Capillary tube

C Refrigerant

RAS-13YK-E

2KS224D5CD02

Ø1,7 x 1,100 l

R22 (0,90 kg)

 

 

 

 

 

RAS-13YKX

PH160T2-4L2

Ø1,7 x

900 l

R22 (0,80 kg)

 

 

 

RAS-13YKX-T

RM5515FNE96

R22 (0,72 kg)

 

 

RAS-13YKX-T2

Ø1,7 x

800 l

R22 (0,83 kg)

 

RAS-13YK-HX

PH142T2-4K7

R22 (0,75 kg)

 

 

RAS-13YK-ES

PA150X2T-4FM

Ø1,5 x

900 l

R410A (0,82 kg)

 

 

 

 

 

• For R-22

 

 

Standard

Surface temp. of heat

Fan speed

Ambient temp.

 

50Hz

pressure P

exchanger interchanging

conditions DB/WB (°C)

 

(indoor)

 

 

(kg/cm²G)

pipe T (°C)

Indoor

Outdoor

 

 

 

 

 

 

 

 

 

 

 

Standard

5,0

13,0

High

27/19

35/24

 

 

 

 

 

 

 

Cooling

High temperature

6,5

18,0

High

32/23

43/26

 

Low temperature

4,0

2,0

Low

21/15

21/15

 

 

 

 

 

 

 

• For R-410A (RAS-13YK-ES/13YA-ES)

 

 

Standard

Surface temp. of heat

Fan speed

Ambient temp.

 

50Hz

pressure P

exchanger interchanging

conditions DB/WB (°C)

 

(indoor)

 

 

(kg/cm²G)

pipe T (°C)

Indoor

Outdoor

 

 

 

 

 

 

 

 

 

 

 

Standard

0,9

10,0

High

27/19

35/24

Cooling

High temperature

1,1

16,0

High

32/23

43/26

 

 

 

 

 

 

 

 

Low temperature

0,6

2,0

Low

21/15

21/15

 

 

 

 

 

 

 

Note : Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor.)

– 12 –

– 13 –

 

Indoor Unit Control Panel

C. P. U

 

 

Functions

Heat Exchanger Sensor

 

 

 

 

 

• Louver Control

 

 

 

Thermo. Sensor

 

 

 

 

 

 

 

Infrared Rays Signal Receiver

Infrared

Rays

Remote Control

Operation (START/STOP)

Operation Mode Selection

AUTO, COOL, DRY, FAN ONLY

Thermo. Setting

Fan Speed Selection

ON TIMER Setting

OFF TIMER Setting

Louver AUTO Swing

Louver Direction Setting

ECONO.

AC 220-240V 50Hz

AC 220V 50Hz (RAS-13YKX-T, 13YKX-T2 only)

Initializing Circuit

Clock Frequency

Oscillator Circuit

Power Supply

Circuit

Noise Filter

3-minute Delay at Restart for Compressor

Motor Revolution Control

Processing

(Temperature Processing)

Timer

Compressor, Outdoor Fan

Louver

ON/OFF Signal

ON/OFF Signal

Relay Driver

Louver Driver

Relay

 

RY01

 

Relay

 

RY02

 

Compressor

 

Outdoor Fan Motor

 

 

 

Operation

Display

Timer

Display

ECONO.

Sign Display

FAN-ONLY

Sign Display

Indoor

Fan Motor

Louver

Motor

DIAGRAM BLOCK CONTROL .6

7. OPERATION DESCRIPTIONS

7-1. FAN ONLY Operation

(The Remote Control MODE Button is Set to the FAN ONLY Operation)

Once the setting is made, the operation mode is memorized in the microcomputer so that the same operation can be effected thereafter simply by pushing [START/STOP] button.

(MODE of the remote control : FAN ONLY)

(1)During this mode, the relay RY01 is always turned off so that only the indoor fan is operated. RY02 is always turnd on. FAN-ONLY display is lit.

1)When the FAN is set to AUTO, the indoor fan motor operates as shown in Fig 7-1-1.

2)When the FAN is set to LOW, MED. or HIGH, the indoor fan motor operates with a constant in volume as listed in Table 7-1-1.

Set temp.)

28

 

 

HIGH

temp.

27

MED

 

 

 

(Room

26

LOW(+)

25

 

 

 

 

 

Set

 

24

LOW

 

 

temp.

 

LOW

 

 

 

 

Fig. 7-1-1 Auto setting of air volume

Table 7-1-1 Manual setting of FAN SPEED

Indication of

HIGH Air volume

FAN SPEED

(m3/hr)

 

 

LOW

510

 

 

MED

560

 

 

HIGH

650

 

 

7-2. COOL Operation

(MODE of the remote control : COOL)

(1)Compressor, outdoor fan and operation display are controlled as shown in Fig. 7-2-1.

temp.)

 

ON

 

 

 

 

 

Set–

+1

 

 

 

 

 

 

 

 

 

 

temp.

 

OFF

ON

ON

 

 

 

(Room

 

 

 

 

 

 

 

Set

 

0

 

 

 

 

 

 

 

temp.

 

Compressor Outdoor fan (RY01)

Common relay (RY02)

OPERATION display

 

 

 

 

 

 

 

 

 

Fig. 7-2-1

(2)Relays RY01 and RY02 are turned on to energize the outdoor unit, and a cool operation is carried out.

1)When the FAN is set to AUTO, the indoor fan motor operates as shown in Fig 7-2-2.

2)When the FAN is set to LOW, MED, or HIGH, the indoor fan motor operates with a constant in volume as listed in Table 7-1-1.

 

 

 

 

FAN

 

temp.)

 

 

 

 

 

 

AUTO

Manual

 

 

 

 

Set–

+4

 

HIGH

 

 

MED

 

 

 

 

 

 

temp.

+3

 

LOW(+)

to the set

 

 

 

 

 

According

(Room

+2

 

 

position

 

 

LOW

+1

 

 

 

 

 

 

 

 

 

 

 

Set

 

0

 

LOW

 

 

 

(continuous)

 

 

 

temp.

 

 

 

 

 

RY01

 

 

 

 

 

 

 

 

OFF

 

Fig. 7-2-2

(3)Once the setting is made, the operation mode is memorized in the microcomputer so that the same operation can be effected thereafter simply by pushing the START/STOP button.

– 14 –

7-2-1. Louver Control

(1) Vertical air flow louvers

Positions of vertical air flow louvers are automatically controlled according to the operation status (COOL, AUTO, DRY, FAN ONLY).

Besides, positions of vertical air flow louvers can be arbitrarily set by pushing the [SET] button.

The louver position which has been set by the [SET] button is stored in microcomputer, and the louver is automatically set at the stored position in the next operation.

(2) Swing

If the [AUTO] button is pushed during running operation, vertical air flow louvers start swinging. When the [AUTO] button is pushed again, swinging stops.

7-3. DRY Operation

(MODE of the remote control : DRY)

(1)Compressor, outdoor fan and operation display are controlled as shown in Fig. 7-3-1.

temp.)

+3

ON:6min.

OFF:4min.

 

 

temp.– Set

ON:5min.

OFF:5min.

 

 

+2

ON

ON

(Room

 

 

+1

OFF

 

 

 

 

 

 

 

 

Set

 

0

 

 

 

 

temp.

 

Compressor fanOutdoor (RY01)

relayCommon (RY02)

OPERATION display

 

 

 

 

 

 

 

 

 

 

 

 

Fig. 7-3-1

The microprocessor turns the compressor on and off at regular intervals (4 to 6 minutes on and/or off).

During the compressor off, the indoor fan will operate in the super low position.

The indoor fan will operate in the AUTO position.

(2)The pattern of operation depending on the relation between room temperature and set temperature is shown below:

Room temp.

Set temp.+1

Set temp.

Compressor

ON

ON

 

ON

 

ON

 

 

 

 

 

 

 

Outdoor fan

 

OFF

 

OFF

OFF

 

 

 

Indoor fan

 

 

 

 

 

 

L.

*S.L.

L.

S.L.

L.

S.L.

L.

 

*Super Low

 

 

 

 

 

Fig. 7-3-2

– 15 –

7-4. AUTO Operation

(MODE of the remote control : AUTO)

(1)One of the 2 modes, Cooling or Dry is selected according to room temperature at which operation is to start, as shown in Fig. 7-4-1. The Fan mode will continue until room temperature reaches a level at which another mode is selected.

7-4-1. Temporary Auto

When the TEMPORARY button is pushed (1 sec), the set temperature is fixed at 24°C and controlled in accordance with the chart shown in Fig. 7-4-1.

(Room temp. – Set temp.)

 

Powerful

(The same cooling mode as the room temperature control is set at set temp. –1˚C)

 

Cooling mode

The Louver moved downward. (DIRECT AUTO COOL)

+4

 

 

Cooling mode

(The same cooling mode as the room temperature control is set at set temp. –1˚C)

 

+1

 

 

Dry mode

(The same dry operation as the room temperature control is set at set temp. –1˚C)

 

 

 

 

Fig. 7-4-1

7-5. ECONO. Mode

When the ECONO. button is pushed, during COOL and AUTO operation, the OPERATION display is turned off and the ECONO. display is lit and the indoor unit operates quietly and mildly with controlling airflow.

7-5-1. Cooling

(1)In the ECONO. mode, the set temp. by the remote control is changed automatically as shown in Fig. 7-5-1.

(2)Fan speed → LOW

(˚C)

 

 

 

 

 

 

Set temp.

 

 

 

 

is changed

 

+2

 

 

 

 

 

 

Set temp.

 

 

 

 

is changed

 

 

+1

 

 

 

 

Set temp.

0H

1H

2H

TIME

ECONO. button is pushed

Fig. 7-5-1

7-6. Low-Temperature Limit Control

(Cooling Operation)

The microprocessor detects the indoor heat exchanger temperature so as to prevent freezing up the indoor heat exchanger.

Control is performed as shown in Fig. 7-6-1.

Heat exchanger

 

temperature

Compressor Outdoor fan

 

(˚C)

ON

7

Less than 5˚C continues

 

5

for 5 minutes

OFF

Fig. 7-6-1

– 16 –

7-7. Auto Restart Function

This unit is equipped with an Automatic restarting function which allows the unit to restart and resume the set operating conditions in the event of a supply power shutdown without the use of the hand control.

The operation will resume without warning three minutes after the power is restored.

INFORMATION

The AUTO RESTART FUNCTION is set not to work on shipment from the factory, and so it is necessary to set it to function as required.

• When the system is stand-by (not running)

7-7-1. How to Set the Auto Restart

To set the Auto Restart function, proceed as follows:

Access the TEMPORARY button located in the lower right hand corner beneath the hinged front panel of the indoor unit.

The power supply to the unit must be on - the function will not be set if the power is off.

To enable the Auto Restart function, push the TEMPORARY button continuously for three seconds.

The unit will acknowledge the setting and beep three times. The system will now restart automatically.

The above Auto Restart settings can be carried out:

OPERATION

 

 

 

MOTION

 

 

 

 

 

 

Push the TEMPORARY button

 

Stand-by

 

 

continuously more than three

 

 

 

seconds.

 

The system starts to operate.

The green light will be lit.

 

 

 

 

 

 

about three seconds after

0

3S

The unit beeps three times.

The orange light will be lit.

 

 

 

 

 

 

 

 

 

TEMPORARY

 

The system is operating.

The orange light is lighting.

 

 

 

 

 

 

 

If the system is not required to run at this time, push the TEMPORARY

 

 

 

 

 

 

button once more or use the remote control and the unit will stop.

 

 

 

 

 

 

• When the system is operating

 

 

 

 

 

 

 

 

 

 

OPERATION

 

 

 

MOTION

 

 

 

 

 

 

Push the TEMPORARY button

 

Operating

 

The green light is lit.

continuously more than three

 

 

 

seconds.

 

The system stops to operate.

The green light is turned off.

 

 

 

about three seconds after

0

3S

The unit beeps three times.

 

 

 

 

 

The system stops.

TEMPORARY

If the system is not required to stop at this time, use the remote control and to restart.

During subsequent operation, the orange light goes on.

The Auto Restart function will not accept an instruction if timer operation with the remote control is selected.

During louver swing (AUTO) operation, after restarting by the Auto Restart function, the louver swing stops.

17 –

7-7-2. How to Cancel the Auto Restart

To cancel the Auto Restart function, proceed as follows:

Repeat the setting procedure: the unit will acknowledge the instruction and beep three times.

The system will now be required to manually restart with the remote control after the main supply is turned off.

Cancellation is carried out:

• When the system is stand-by (not running)

OPERATION

 

 

MOTION

 

 

 

 

 

Push the TEMPORARY button

Stand-by

 

 

continuously more than three

 

 

seconds.

The system starts to operate.

The orange light will be lit.

 

 

 

 

about three seconds after

0

The unit beeps three times.

The green light will be lit.

 

3S

 

 

 

 

 

 

 

 

TEMPORARY

The system is operating.

 

 

 

If the system is not required to run at this time, push the TEMPORARY

 

 

 

 

button once more or use the remote control and Stop the unit.

 

 

 

 

 

• When the system is operating

 

 

 

 

 

 

 

 

OPERATION

 

 

MOTION

 

 

 

 

 

Push the TEMPORARY button

Operating

 

The orange light is lit.

continuously more than three

 

 

seconds.

The system stops to operate.

The orange light is turned off.

 

 

 

 

about three seconds after

0

The unit beeps three times.

 

 

3S

 

 

 

 

 

 

TEMPORARY

The system stops.

 

 

 

 

 

 

If the system is not required to stop at this time, use the remote control

 

 

 

 

and to restart.

 

 

 

 

 

 

During subsequent operation, the green light goes on.

7-7-3. In Case of Power Failure during the Timer Operation

(1)If ON-TIMER operation is reserved with setting of Auto Restart operation, it is cancelled with power failure. (The OPERATION lamp on the main unit goes on and off to inform of power failure.) In that case, try to reserve ON-TIMER operation once again.

(2)If OFF-TIMER operation is reserved without setting of Auto Restart operation, the reservation is cancelled with power failure. (The OPERATION lamp on the main unit goes on and off to inform of power failure.) In that case, try to reserve OFF-TIMER operation. When Auto Restart operation is set, OFF-TIMER reservation is also cancelled with power failure.

– 18 –