Toshiba HWS-1402XWHT6-E, HWS-1402XWHM3-E, HWS-802XWHM3-E, HWS-802XWHT6-E, HWS-1402XWHT9-E INSTALLATION MANUAL

0 (0)

AIR TO WATER HEAT PUMP

Installation manual

Hydro Unit

Model name:

HWS-802XWHM3-E

HWS-802XWHT6-E

HWS-1402XWHM3-E

HWS-1402XWHT6-E

HWS-1402XWHT9-E

Installation manual

 

English

Hydro Unit (Air to Water Heat Pump)

2

 

 

 

Manuel d’installation

 

 

 

 

Unité hydroélectrique

44

Français

(Pompe à chaleur air/eau)

Installations-handbuch

 

 

 

 

Hydrogerät

86

Deutsch

(Luft-Wasser-Wärmepumpe)

Installationshandbok

 

 

 

 

Hydroenhet

128

Svenska

(Luft-till-vatten-värmepump)

Hydro Unit

Installation Manual

Please read this Installation Manual carefully before installing the Air to Water Heat Pump.

This Manual describes the installation method of the hydro unit.

For installation of the outdoor unit, follow the Installation Manual attached to the outdoor unit.

ADOPTION OF NEW REFRIGERANT

This Air to Water Heat Pump is a new type which adopts a new refrigerant HFC (R410A) instead of the conventional refrigerant R22 in order to prevent destruction of the ozone layer.

Contents

 

1

GENERAL INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. 3

2

ACCESSORY PARTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4

3

PREPARATIONS FOR INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4

4

PRECAUTIONS FOR SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5

5

EXAMPLE OF HYDRO UNIT INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

7

6

MAIN COMPONENTS OF HYDRO UNIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9

7

HYDRO UNIT INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

11

8

START UP AND CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

31

9

TEST RUN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

38

10 MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

39

11 SENSOR TEMPERATURE MONITORING FUNCTION . . . . . . . . . . . . . . . . . . . . . . .

39

12 TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

40

1-EN

– 2 –

Hydro Unit

Installation Manual

1 GENERAL INFORMATION

Hydro Unit Description

Hydro Unit

 

Model Description

 

 

HWS-802XWHM3-E

8 kW Hydro Unit (3 kW 230 V ~ back up heater)

 

 

HWS-802XWHT6-E

8 kW Hydro Unit (6 kW 400 V 3N ~ back up heater)

 

 

 

HWS-1402XWHM3-E

11

& 14 kW Hydro Unit (3 kW 230 V ~ back up heater)

 

 

 

HWS-1402XWHT6-E

11

& 14 kW Hydro Unit (6 kW 400 V 3N ~ back up heater)

 

 

 

HWS-1402XWHT9-E

11

& 14 kW Hydro Unit (9 kW 400 V 3N ~ back up heater)

 

 

 

General Specifications

 

Outdoor unit

 

HWS-802H-E

HWS-1102H-E

HWS-1402H-E

Type

 

 

 

 

Inverter

 

 

 

 

 

 

 

 

Function

 

 

 

 

Heating & Cooling

 

 

 

 

 

 

 

 

 

 

Capacity

(kW)

8.0

11.2

14.0

 

 

 

 

 

 

 

Heating

 

Input

(kW)

1.96

2.40

3.15

 

 

 

 

 

 

 

 

 

COP

 

4.08

4.66

4.45

 

 

 

 

 

 

 

 

 

Capacity

(kW)

6.0

10.0

11.0

 

 

 

 

 

 

 

Cooling

 

Input

(kW)

2.13

3.52

4.08

 

 

 

 

 

 

 

 

 

EER

 

2.82

2.84

2.69

 

 

 

 

 

 

Power supply

 

 

230 V ~

 

 

 

 

 

 

 

 

Refrigerant

 

 

 

 

R410A

 

 

 

 

 

 

 

 

Dimension

 

HxWxD

(mm)

890 x 900 x 320

1,340 x 900 x 320

 

 

 

 

 

 

 

Hydro Unit

 

HWS-

HWS-

 

HWS-

 

 

HWS-

HWS-

 

 

802XWHM3-E

802XWHT6-E

1402XWHM3-E

1402XWHT6-E

1402XWHT9-E

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Back up heater capacity

 

3 kW

6 kW

 

3 kW

 

 

6 kW

9 kW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

for backup heater

230 V ~

400 V 3N ~

230 V ~

 

400 V 3N ~

400 V 3N ~

 

 

Power supply

 

 

 

 

 

 

 

 

 

 

 

 

 

for hot water cylinder

 

 

 

 

230 V ~

 

 

 

 

 

 

heater(option)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Leaving water

Heating

(°C)

 

 

 

 

20 to 55

 

 

 

 

 

temperature

Cooling

(°C)

 

 

 

 

10 to 25

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

For use with

 

 

HWS-802H-E

 

HWS-1102H-E/HWS-1402H-E

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Dimension

HxWxD

(mm)

 

 

 

 

925 x 525 x 355

 

 

 

 

 

 

 

 

 

 

 

 

 

EN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Hot water cylinder (option)

HWS-1501CSHM3-E

 

HWS-2101CSHM3-E

 

HWS-3001CSHM3-E

 

 

HWS-1501CSHM3-UK

 

HWS-2101CSHM3-UK

HWS-3001CSHM3-UK

 

 

 

 

 

 

 

Water volume

 

litres

150

 

 

 

210

 

 

 

300

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Max water temperature

(°C)

 

 

 

 

75

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Electric heater

 

(kW)

 

 

 

 

2.75 (230 V ~)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Height

 

(mm)

1,090

 

 

 

1,474

 

 

 

2,040

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Diameter

 

(mm)

 

 

 

 

550

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Material

 

 

 

 

 

 

Stainless steel

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

– 3 –

2-EN

Hydro Unit Installation Manual

2

ACCESSORY PARTS

 

 

No

Parts name

Quantity

 

No

Parts name

Quantity

 

 

 

 

 

 

 

1

Installation manual (this document)

1

 

3

Insulator for cooling

1

 

 

 

 

 

 

 

2

Owner’s manual

1

 

 

 

 

 

 

 

 

 

 

 

3 PREPARATIONS FOR INSTALLATION

Parts required to connect this product (Common items)

Category

Part

Specification

Quantity

 

 

 

 

 

Strainer (water filter)

1 1/4" 30 to 40 meshes

1

 

 

 

 

Water piping

Drain cock

(for water charge)

1

 

 

 

 

Isolating ball valves

1 1/4"

2

 

for service 1 1/4"

 

 

 

 

Earth leakage breaker for main power

30 mA

1

 

supply

 

 

 

Electrical system

Earth leakage breaker for backup heater

30 mA

1

 

 

 

 

(Option)

30 mA

1

 

Earth leakage breaker for hot water cylinder

 

heater

 

 

Options required for each function

Purpose

In the Hydro Unit

 

Purchased part

 

 

 

 

 

 

Part name

Model name

Part name

Prescribed specification

 

 

 

 

 

 

 

Heating

 

Radiator(s), Fan coil(s),

 

 

Under floor heating

 

 

 

 

 

 

Heating &Cooling

 

Fan coil(s)

 

(all rooms)

 

 

 

 

 

 

 

Heating & Cooling

 

Motorized 2-way valve (for

Refer to “Control parts

(partly heating only)

 

cooling)

specifications” on page 23.

 

 

 

 

Hot water cylinder

 

 

 

 

 

 

 

 

 

 

 

150 L

HWS-1501CSHM3-E

 

 

 

 

 

 

 

 

 

HWS-1501CSHM3-UK

Motorized 3-way valve

Refer to “Control parts

 

 

 

Hot water supply

 

 

 

 

 

HWS-2101CSHM3-E

 

210 L

Earth leakage breaker

specifications” on page 23.

 

 

 

 

 

HWS-2101CSHM3-UK

 

 

 

 

 

 

 

 

 

 

 

 

 

300 L

HWS-3001CSHM3-E

 

 

 

 

 

 

 

 

 

HWS-3001CSHM3-UK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Motorized mixing valve

Refer to “Control parts

 

 

 

 

specifications” on page 23.

2-zone control

 

 

 

Circulator pump

Other power supply

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Buffer tank

 

 

 

 

 

 

 

Interlocking with

Output control

 

 

Other power supply

TBC-PCIN3E

Boiler

Signal 12 V input function is

boiler

board kit (1)

 

 

required for boiler.

 

 

 

 

 

 

 

 

 

 

 

Interlocking with

Output control

 

 

Other power supply.

TBC-PCIN3E

Electric heater

Signal 230 V input function

booster heater

board kit (1)

is required for booster

 

 

 

 

 

 

 

heater

 

 

 

 

 

 

3-EN

– 4 –

Hydro Unit Installation Manual

Optional Parts

No.

Part name

Model name

Application

Remarks

 

 

 

 

 

 

External output

 

Boiler-linked output, Alarm output

Up to two boards

1

TCB-PCIN3E

 

Defrost signal output, compressor operation

board

(according to applications)

 

 

 

 

 

signal output

 

2

External input

TCB-PCMO3E

Cooling/heating thermostat input

Up to two boards

 

board

Forced-stop signal input

(according to applications)

 

 

 

 

 

 

 

 

 

 

 

Use specified products for the outdoor unit, Hydro Unit, and hot water cylinder. Do not use commercially available products.

Use parts that conform to prescribed specifications for parts to be connected to the Hydro Unit. If unspecified products or parts are used, a malfunction, failure or fire may be caused.

4 PRECAUTIONS FOR SAFETY

General Safety Precautions

Ensure that all Local, National and International regulations are satisfied.

Read the “PRECAUTIONS FOR SAFETY” carefully before installation.

The precautions described below include the important items regarding safety – Observe them without fail.

After the installation work has been completed, perform a trial operation to check for any problems. Follow the Owner’s Manual to explain how to use and maintain the unit to the customer.

Turn off the main power supply switch (or breaker) before unit maintenance.

Ask the customer to keep the Installation Manual along with the Owner’s Manual.

Refrigerant Precautions

If a refrigerant leak is suspected contact the dealer who supplied the system, in the case of a recharge of refrigerant ask service personnel for details of the leak and confirmation of the repairs completed.

The refrigerant used in the system is harmless.

Generally the refrigerant does not leak, however, if the refrigerant should leak into a room and a heater or stove burner in the room is lit, toxic gas may be generated.

Do not install the system in a location subject to a risk of exposure to a combustible gas. If a combustible gas leaks and stays around the unit a fire may occur.

Install the refrigerant pipe securely during installation and before operation.

If the compressor is operated with no pipe work connected and valves open the compressor will suck air which

would result in over pressurization of the system which may result in bursting or injury.

 

Observe the same precautions for refrigerant recovery work (pump back procedure to outdoor unit) and do not

 

disconnect pipe work until refrigerant is recovered and valves closed.

EN

– 5 –

4-EN

Hydro Unit

Installation Manual

WARNING

Installation Precautions

Ask an authorized dealer or qualified installation professional to install/maintain the Air to Water Heat Pump System. Inappropriate installation may result in water leaks, electric shock or fire.

Electrical work must be performed by a qualified electrician in accordance with the installation manual. An inappropriate power supply capacity or installation may result in fire.

When completing any electrical works to the system ensure that all Local, National and International regulations are satisfied.

Inappropriate grounding may result in electric shock.

Use the specified electrical cables, fixing securely at all terminations.

Earth wire connections.

Install an earth leakage breaker without fail. Incomplete grounding can cause electric shock.

Do not ground wires to gas pipes, water pipes, lightning rods or telephone cable ground wires.

This unit must be connected to the main power supply using a circuit breaker or switch with a contact separation of at least 3 mm.

Be sure to turn off all main power supply switches or the circuit breaker before starting any electrical work. Ensure all power switches are off, failure to do so can cause electric shock.

Use an exclusive power circuit for the Air to Water Heat Pump system using the rated voltage.

Ensure correct connection of interconnecting wire between Outdoor Unit and Hydro Unit. Incorrect connection of the interconnecting cable may result in the damage of electrical parts.

Ensure refrigeration system remains sealed to external gases and air.

Should air or other gases contaminate the refrigeration circuit, high system pressures could result in burst pipes and injuries.

Do not modify or bypass any of safety guards or switches in this system.

After unpacking the outdoor unit, examine the unit carefully for any possible damage.

Do not install in any place that might increase the vibration of the unit.

To avoid personal injury (with sharp edges), be careful when handling parts.

Perform installation work properly in accordance with the installation manual. Inappropriate installation may result in water leaks, electric shock or fire.

Tighten all flare nuts with a torque wrench in the specified manner.

Excessive tightening of the flare nut may result in cracking of the pipe work or flare nut which may result in a refrigerant leakage.

Wear heavy duty gloves during installation work to avoid injury.

Install the outdoor unit securely in a location where the base can sustain the weight adequately.

In enclosed areas, if the refrigerant leaks during installation vacate and ventilate immediately.

After installation is complete ensure and confirm that refrigerant does not leak.

If refrigerant leaks into a room and flows near a fire source noxious gas may be generated.

Do not block any drain hoses. Hoses may come off and electric shocks may occur.

Do not hit the manometer, because it is made of glass. It is breakable.

Notes on System Design

The input water temperature to the Hydro Unit must be 55°C or less. Especially, be careful when there is an external heating source such as a boiler.

When hot water over 55°C returns, it may result in a failure of the unit or water leakage.

The flow rate of the circulating water must meet the following range. 11 and 14 kW 18 L/minute or more

8 kW 13 L/minute or more

If the flow rate becomes less than the minimum, the protective device is activated to stop operation. Ensure the flow rate with a bypass valve, etc. when you use a flow rate valve for the Hydro Unit.

Do not drive water by power other than the pump built in the Hydro Unit.

The backup heater operates supplementarily to exert a prescribed capacity when the heat pump cannot exert its capacity at a low outside temperature.

Install the Hydro Unit and water pipes in a place in which they do not freeze.

Make the water circuit closed. Never use it as an open circuit.

Circulating water must be 20 liters or more. If total water amount is not enough, the unit may not function fully due to protective operation.

5-EN

– 6 –

Hydro Unit

Installation Manual

5 EXAMPLE OF HYDRO UNIT INSTALLATION

Example of Installation for Cooling and Heating

When both cooling and heating are used, install a 2-way valve (for cooling) to the pipe to the room for heating only.

Fig. 5-01

 

Fan Coil Units

Isolating

(Cooling or Heating)

Ball

 

 

Valves

 

 

Strainer (40 mesh / 0.4 mm)

Diverting 3-Way

 

Valve for

 

Drain Cock for water

Sanitary Hot

Charge and Drain

Water Tank

M

 

Radiators (Heating Only)

 

 

[2-Way Valve Control]

 

M

2-Way

 

Valve

 

Use it when

 

do not

 

operate

TTW

cooling.

 

 

Indirect Sanitary

 

 

Hot Water Tank

2-Way

Use it when do not

M

Valve

operate cooling.

Alternative to Radiators

Under-floor Heating (Heating Only) [2-Way Valve Control]

EN

– 7 –

6-EN

Hydro Unit

Installation Manual

Example of 2-Zone Temperature Control and Hot Water Supply System

The following shows an example of the 2-zone temperature control.

A buffer tank and a water pump are required for the 2-zone temperature control.

Fig. 5-02

Isolating Valves (Service)

Strainer (40 mesh / 0.4 mm)

Drain Cock for water

Charge and Drain

TTW

Hi-Pressure

Temperature

By-Pass

Regulating

Valve

Valve

 

(Mechanical)

TRV

Temp. Regulating Valve (Mechanical)

TRV

 

Zone 1

Diverting

Fan Coil Unit (Heating

3-Way

or Cooling)

Valve for

 

Sanitary

 

Hot

 

Water

 

Tank

 

M

Motorized 2-Way Valve is required if fan coil

Munits are in cooling operation.

Indirect Sanitary Hot

Water Tank

Mixing 3-Way

MValve for Under Floor Heating

External Pump for

Under Floor Heating

TFI

Direct Buffer tank for Under Floor Heating

Zone 2

Under-floor Heating

(2-Way Valve Control)

7-EN

– 8 –

Hydro Unit

Installation Manual

6 MAIN COMPONENTS OF HYDRO UNIT

Exploded view and description for Hydro Unit

Fig. 6-01

1

2

3

4

5

6

7

8

9

10

11

1 : Expansion vessel

2 : Hi pressure switch (4.15 MPa)

3 : Temperature sensor (for Heat pump outlet -TWO) 4 : Pressure sensor

5 : Heat exchanger

6 : Flow switch (13.0 L/min 17.5 L/min)

7 : Temperature sensor (for refrigerant -TC)

8 : Temperature sensor (for water inlet -TWI)

9 : Drain nipple

10 : Water inlet connection

11 : Refrigerant liquid connection

12 : Air relief valve

13 : Pressure relief valve (0.3 MPa (3 bar))

14 : Thermal protector (auto)

15 : Temperature sensor (for water outlet THO)

16 : Thermal protector (Single operation)

17 : Water pump

18 : Backup heater (3 kW, 3 kW x 2, 3 kW x 3) 19 : Manometer

20 : Water outlet connection

21 : Refrigerant gas connection

12

13

14

15

16

17

18

19

20

21

EN

– 9 –

8-EN

Hydro Unit

Installation Manual

E-Box layout

Fig. 6-02

P.C. board

MCC-1511

 

Trans

 

former

Relay P.C. board

MG-SW (RY04)

MCC-1217

Relay

(Option)

(RY03)

 

MG-SW (RY05)

Relay

MG-SW (RY02)

Relay

 

(RY06)

(RY01)

 

Relay P.C. board

 

 

MCC-1217

 

 

(Option)

Fuse

 

 

 

Relay P.C. board

Relay P.C. board

MCC-1431

 

MCC-1214

 

(Option)

9-EN

– 10 –

Hydro Unit

Installation Manual

7 HYDRO UNIT INSTALLATION

WARNING

To protect yourself from injury, always use PPE (Personal Protective Equipment), that is, wear gloves.

Install the Hydro Unit by at least two persons.

Install the Hydro Unit in a place strong enough to withstand the following weights: Hydro Unit weight with no water 60 kg (802) 65 kg (1402)

Hydro Unit weight with full water 80 kg (802) 85 kg (1402)

CAUTION

• The operating temperature range is 5 to 32°C (Heating) and 18 to 30°C (Cooling). Do not install the unit in a place where water freezes.

• Do not install the Hydro Unit in a place where combustible gas may leak.

• Do not install the Hydro Unit in a place exposed to rain or water.

• Do not install the Hydro Unit near equipment which generates heat.

• Do not install the Hydro Unit to a movable object.

• Do not install the Hydro Unit in a place exposed to vibration.

Handling, Unpacking, and Checking the Hydro Unit

• The unit should be checked when it is delivered, and any damage reported immediately to the courier claims the department.

Positioning

Refrigeration pipe

The length and height of the refrigeration pipe must be within the following values.

As long as the Hydro Unit is installed within these ranges, no additional refrigerant is required.

Fig. 7-01

Outdoor unit

L

H

EN

H: Max. ±30 m (above or below)

L:Max. 30 m

Min. HWS-802H-E : 5 m HWS-1102H-E : 3 m HWS-1402H-E : 3 m

– 11 –

10-EN

Hydro Unit

Installation Manual

Water pipe

Design the water pipe length within the QH characteristics of the pump (Refe to “Fig. 7-16” and “Fig. 7-17” on page 19). The height of the pipe must be 7 m or less.

Fig. 7-02

H < 7 m

Service space

Secure a service space for the Hydro Unit.

• Do not install the Hydro Unit in a place where heat stagnates.

Fig. 7-03

 

200 mm

 

100 mm

350 mm

 

500 mm

 

500 mm

Mounting

Install M10 bolts at the positions shown below and secure them with nuts.

Fig. 7-04

380 mm

 

 

 

M10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

960 mm

11-EN

 

 

 

– 12 –

 

 

 

Hydro Unit

Installation Manual

The Hydro Unit can be installed directly without using the fixing angles.

However, the back side of the Hydro Unit can be highly heated, therefore, the installing surface must be heatresistant.

Fig. 7-05

Fig. 7-06

Fig. 7-07

380

M10

860

M10

Remove the M5a screws to detach the fixing angles.

Install the Hydro Unit so that its tilting angle falls within the range below.

Fig. 7-08

Fig. 7-09

± 1°

Secure the Hydro Unit with plain washers and nuts.

± 1°

EN

– 13 –

12-EN

Hydro Unit

Installation Manual

Refrigerant Piping

WARNING

THIS SYSTEM ADOPTS HFC REFRIGERANT (R410A) WHICH DOES NOT DESTROY THE OZONE LAYER.

The characteristics of R410A refrigerant are: ease to absorb water, oxidizing membrane or oil, and its pressure is approximately 1.6 times higher that of R22. Accompanied with the new refrigerant the oil has also been changed. Therefore during installation work prevention of the invasion of water, dust, former refrigerant or oil is of a paramount importance.

To prevent the charging of incorrect refrigerants into the system the service valve connection ports have also increased in size.

The use of R410A tools is required for correct installation of the system.

The use of the correct pipe sizes and wall thicknesses of copper pipe work is required for the correct installation of the system.

CAUTION

Ensure all refrigerant pipes are protected from the invasion of dust and water.

Ensure all pipe work connections are tightened to the required torque settings detailed in this section.

Perform an air tight using Oxygen Free Nitrogen (OFN) only.

Evacuate the air in the pipe work using a vacuum pump.

Check for refrigerant gas leaks at all connections throughout the pipe work.

NOTE

The Air to Water Heat Pump system uses R410A refrigerant. It is important that copper pipes used for refrigerant piping have the following wall thickness:

0.8 mm for Ø6.4 mm, Ø9.5 mm and Ø12.7 mm

1.0 mm for Ø15.9 mm

Refrigerant pipe sizes

Hydro Unit Model

Gas Side (mm)

Liquid Side (mm)

 

 

 

8 kW Hydro Unit

Ø 15.88

Ø 9.52

 

 

 

11 & 14 kW Hydro Unit

Ø 15.88

Ø 9.52

 

 

 

Flaring

Cut the refrigerant pipes to the correct length using a pipe cutter. Remove any burrs that may be on the pipes as these may cause refrigerant leaks or component failure in the refrigeration cycle.

Place the correct size flare nuts onto the pipes (use the flare nuts supplied with the Hydro Unit or use flare nuts designed specifically for R410A refrigerant) and then flare the pipes using the correct flaring tool.

13-EN

– 14 –

Hydro Unit

Installation Manual

Tightening

• Connect the refrigerant pipes, from the outdoor unit, to the Hydro Unit as shown below.

Fig. 7-10

Gas line Ø 15.88

Liquid line Ø 9.52

• Align the flare connection on each pipe with the corresponding outlet connection on the Hydro Unit. Tighten the flare nuts, using fingers, to secure the pipes in place.

• Tighten the flare nuts, using a torque wrench, to the tightening torques shown below:

Outer Ø of Copper Pipe (mm)

Tightening Torque (N/m)

 

 

9.5

33 to 42

 

 

15.9

63 to 77

 

 

• To prevent damage, to the refrigerant pipes, use two spanners to tighten the flare nut connections to the required torque.

Water Pipe

WARNING

Install water pipes according to the regulations of respective countries.

Install water pipes in a freeze-free place.

Make sure that water pipes have sufficient pressure resistance. The setting value of the pressure relief valve is 0.3 MPa.

CAUTION

Do not use zinc plated water pipes. When steel pipes are used, insulate both ends of the pipes.

The water to be used must meet the water quality standard specified in EN directive 98/83 EC.

EN

– 15 –

14-EN

Hydro Unit

Installation Manual

Water circuit

Install a strainer with 30 to 40 meshes (procured locally) at the water inlet of the Hydro Unit.

Install drain cocks (procured locally) for water charge and discharge at the lower part of the Hydro Unit.

Make the piping route a closed circuit. (An open water circuit may cause a failure.)

Fig. 7-11

Attention

To avoid water leak, exchange the seal tapes to new one.

Attention

Water (used at test in factory before shipping) may be found in the caps.

Hot water outlet connection 1 1/4"

Water inlet connection 1 1/4"

Fig. 7-12

Inlet

Isolating Ball Valve

Strainer (30 to 40 meshes)

Drain cock for water charge and discharge

Local arrangement

15-EN

– 16 –

Hydro Unit

Installation Manual

Piping to hot water tank (option)

Water supplied to the hot water cylinder is branched by a motorized 3-way valve (procured locally). For the specifications of the motorized 3-way valve, refer to “Control parts specifications” on page 23. Connect the hot water cylinder to port A (open when energized) of the valve.

Fig. 7-13

to hydro unit

room heating or cooling

 

AB to hot water cylinder

 

 

 

 

 

 

 

 

 

B

 

 

 

A

Open when de-energized

 

 

 

Open when energized

Piping to 2-zone operation

To perform 2-zone temperature control, circulate water by another pump (procured locally) through a motorized mixing valve (procured locally) and a buffer tank (procured locally).

For the specifications of the motorized mixing valve, Refer to “Control parts specifications” on page 23.

Fig. 7-14

Motorized mixing valve

 

A

 

 

 

 

 

(Procured locally)

 

 

 

 

 

 

 

Open when

 

 

 

 

 

 

 

 

 

 

 

Water pump

 

 

 

 

 

energized

 

 

 

 

 

 

 

 

 

 

 

 

to hydro unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Procured locally)

 

 

AB

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Zone 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B

 

 

 

 

 

 

 

 

 

 

Open when

 

 

 

 

 

 

 

 

 

 

de-energized

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Buffer tank

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Procured locally)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Checking water volume and initial pressure of expansion vessel

The expansion vessel of the Hydro Unit has a capacity of 12 liters. The initial pressure of the expansion vessel is 0.1 MPa (1 bar). The pressure of the safety valve is 0.3 MPa (3 bar).

Verify whether the capacity of the expansion vessel is sufficient using the following expression. If the volume is insufficient, add the capacity locally.

EN

– 17 –

16-EN

Hydro Unit

Installation Manual

Expression for expansion vessel selection

V:Necessary total tank capacity ()

: Water expansion coefficient at average hot water temperature Vs: Total water amount in the system

P1: System pressure at tank setting position (MPaabs.)

(Pipe inner pressure during pump operation before heating device operates = water supply pressure) P2: Maximum pressure used during operation at tank setting position (MPaabs.)

(= safety valve setting pressure)

*The absolute pressure value (abs.) is obtained by adding the atmospheric pressure (0.1 MPa (1 bar)) to the gauge pressure.

Tank selection method

 

 

 

 

 

 

 

 

 

 

 

Water temperature and expansion coefficient

 

 

Hot water temperature (°C)

 

Expansion rate

 

Hot water temperature (°C)

Expansion rate

0

0.0002

 

 

50

 

 

 

0.0121

4

0.0000

 

 

55

 

 

 

0.0145

5

0.0000

 

 

60

 

 

 

0.0171

10

0.0003

 

 

65

 

 

 

0.0198

15

0.0008

 

 

70

 

 

 

0.0229

20

0.0017

 

 

75

 

 

 

0.0258

25

0.0029

 

 

80

 

 

 

0.0292

30

0.0043

 

 

85

 

 

 

0.0324

35

0.0050

 

 

90

 

 

 

0.0961

40

0.0078

 

 

95

 

 

 

0.0967

45

0.0100

 

 

 

 

 

 

 

Fig. 7-15

 

 

 

 

 

 

 

 

 

 

 

18

 

 

 

 

 

 

 

 

)

16

 

 

 

 

 

 

 

 

volume(

14

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12

 

 

 

 

 

 

 

 

vessel

10

 

 

 

 

 

 

 

 

8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Expansion

6

 

 

 

 

 

 

 

 

4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

 

0

 

 

 

200

250

300

 

 

 

0

50

100

150

 

 

 

 

 

Water volume (

)

 

 

 

*Hot water temperature 55ºC

Install an external expansion vessel when the capacity of the expansion vessel is insufficient.

17-EN

– 18 –

Hydro Unit

Installation Manual

Pump operation/configuration

Fig. 7-16

Hydraulic heat exchanger (14 kW) QH characteristics

Minimum flow rate

 

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8

 

 

 

 

 

 

 

 

 

 

 

 

 

(m)

7

 

 

 

 

 

 

 

 

 

 

 

 

 

6

 

 

 

 

 

 

 

 

 

 

 

 

 

head

 

 

 

 

 

 

 

 

 

 

 

 

 

5

 

 

 

 

 

 

 

 

 

 

 

 

 

Pump

4

 

 

 

 

 

 

 

 

 

 

SW3

 

3

Out of Operation

 

 

 

 

SW2

 

 

 

 

 

 

 

 

 

 

 

 

2

Range

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SW1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

5

10

15

20

25

30

35

40

45

50

55

60

65

Flow rate ( /min)

Fig. 7-17

Hydraulic heat exchanger (8 kW) QH characteristics

Minimum flow rate

 

8

 

 

 

 

 

7

 

 

 

 

 

6

 

 

 

 

(m)

5

 

 

 

 

head

4

 

 

 

 

Pump

3

 

 

 

SW 3

 

 

 

 

 

2

 

 

 

 

 

 

SW 2

 

 

 

Out of

 

 

 

1

Operation

 

 

 

 

 

Range

SW 1

 

 

 

 

 

 

 

 

0

 

 

 

 

 

10

15

20

25

30

Flow rate ( /min)

EN

– 19 –

18-EN

Hydro Unit

Installation Manual

Water charging

Charge water until the pressure gauge shows 0.2 MPa (2 bar).

Hydraulic pressure may drop when the trial run begins. In that case, add water.

Air may enter if the charged hydraulic pressure is low.

Loosen the purge valve cap by two turns to release air.

Fig. 7-18

Loosen 2 turns for

 

proper venting

Loosen the air vent screw of the pump, pull out air in the pump, and tighten again. Loosen the cap of the pressure relief valve to release air.

Water may come out of the pressure relief valve.

Release the air completely from the water circuit. Failure to do so may disable correct operation.

Water quality

The water used must satisfy EN directive 98/83 EC.

Piping insulation

It is recommended that insulation treatment be applied to all pipes. To perform optional cooling operation, apply insulation treatment of 20 t or more to all pipes.

19-EN

– 20 –

Hydro Unit

Installation Manual

Electrical Installation

WARNING

Ensure electrical circuits are isolated before commencing the electrical installation.

The electrical installation must be completed by a qualified electrician.

The electrical installation must comply to all Local, National and International electrical installation regulations.

This product must be earthed in accordance with Local, National and International electrical installation regulations.

CAUTION

The Hydro Unit must be connected to a dedicated power supply for the back up heater circuit.

The electrical supply must be protected by a suitably sized over current protection device (fuse, MCB etc) and an earth leakage protection device.

The Hydro Unit must be connected to the mains power supply using a isolating switch which disconnects all poles and has a contact separation of at least 3 mm.

The cord clamps, attached to the Hydro Unit, must be used to secure the electrical cables.

Wrong connection of electrical cables may result in electrical component failure or fire.

Ensure the electrical cables are sized in accordance with the installation instructions.

Power line

Fig. 7-19

Backup heater

230 V ~ (3 kW type)

Input power 230 V ~ 50 Hz

Leakage breaker 30 mA

L N

TB02

 

 

1

1

TB01

 

 

2

2

 

 

 

Input power

Leakage

3

3

 

230 V ~

breaker

L

 

 

50 Hz

30 mA

N

 

 

 

 

 

 

Backup heater

400 V 3N ~ (6.9 kW type)

Input power 400 V 3N ~ 50 Hz

Leakage breaker 30 mA

L1 L2 L3 N

TB02

TB03

1

 

2

 

 

 

 

 

Leakage

 

L

breaker

 

N

30 mA

 

 

Hot water cylinder

1

2

Input power for cylinder heater 230 V ~ 50 Hz

EN

Outdoor unit

Hydro unit

– 21 –

20-EN

Toshiba HWS-1402XWHT6-E, HWS-1402XWHM3-E, HWS-802XWHM3-E, HWS-802XWHT6-E, HWS-1402XWHT9-E INSTALLATION MANUAL

Hydro Unit

Installation Manual

Control line

Fig. 7-20

Pump (local)

Max 12 m

230 V 1 A

0.75 mm² or more

2Way-Valve for Max 12 m cooling stop

230 V 100 mA

0.75 mm² or more

Booster heater

(local) Max 12 m 230 V 1 A

0.75 mm² or more

3Way-Valve for hot water cylinder

Alert output (local)

Mixing-Valve

Mixing-Valve type

type 2 for 2

1 for 2 zone control

zone control

 

 

Max 12 m

 

230 V 100 mA

 

0.75 mm² or more

1

2

3

4

CW

N

CCW

Max 5 m shield wire

 

TB04

 

 

 

0.75 mm² or more

 

 

 

1

2

3

4

 

Temp sensor in hot water cylinder

 

 

 

TB04

 

 

A

A

1

 

 

 

 

 

 

 

B

B

2

TB05

 

 

 

 

TB06

 

 

4

 

 

 

 

D

wire 0.75 mm² or

3

 

 

 

 

 

 

 

C

Max 5 m shield

 

 

 

 

 

 

 

 

 

5

 

 

 

 

 

 

 

 

more

 

 

 

 

 

 

 

Temp sensor

6

 

 

 

 

 

 

 

for 2 zone

7

 

 

 

 

 

 

 

control

 

 

 

 

 

 

 

 

 

8

CN208

 

 

CN209

 

 

 

9

OPTION

 

OPTION

 

 

 

 

PJ20

 

 

PJ20

 

 

 

1

2

3

4

1

2

3

 

4

Max 12 m

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

non voltage

 

 

 

 

 

 

 

 

 

0.75 mm² or more

Boiler operation

 

Defrost output

Compressor

(local)

 

 

 

 

(local)

operation output

 

 

 

 

 

 

 

 

 

(local)

Fig. 7-21

TB03

TB01

51

52

53

54

55

56

57

58

59

 

41

42

43

44

 

 

 

 

 

 

 

WPM

2WV

 

BH

 

3WV

 

 

 

MIXV

 

 

 

 

 

 

 

 

 

 

TB 05

 

 

 

 

 

 

 

 

TB 04

 

 

 

 

 

TB02

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

2

3

 

 

 

L1

L2

L3

N

L1

L2

L3

N

6A 6B 6C 6D

Don't apply

11

12 13

31 32

L N

L

N

220-240V

TTW

TF1

or

 

 

HOT WATER CYLINDER

 

 

TB 06

breakdown

 

TB 01

 

TB 03

 

TB 02

will occur.

 

 

 

 

to Outdoor unit

Hot

Input

Input

Input

 

 

water

power

power

power

 

 

cylinder

230 V ~

230 V ~

400 V 3N ~

 

 

 

50 Hz

50 Hz

50 Hz

Sensor

Outdoor unit

Hot water

Backup heater

connection

connection

cylinder power

power supply

 

 

 

supply

 

 

 

21-EN

– 22 –

Hydro Unit Installation Manual

Electrical supply/cable specifications

Wiring specifications

Description

 

POWER SUPPLY

Maximum

Installation fuse

Power wire

 

Connection

 

 

 

 

 

current

rating

 

 

destination

 

 

Outdoor unit

14 kW

230 V ~ 50 Hz

22.8 A

25 A

2.5 mm² or more

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

11 kW

230 V ~ 50 Hz

22.8 A

25 A

2.5 mm² or more

 

 

 

,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

power

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8 kW

230 V ~ 50 Hz

20.8 A

25 A

2.5 mm² or more

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor-Hydro

 

 

 

1.5 mm² or more

 

 

 

,

 

 

,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Hydro inlet heater

3 kW

230 V ~ 50 Hz

13 A

16 A

1.5 mm² or more

 

 

 

,

 

 

(TB02)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6 kW

400 V 3N ~ 50 Hz

13

A (13 A x 2P)

16 A

1.5 mm² or more

 

 

,

 

 

,

 

 

 

,

 

 

 

 

 

power

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9 kW

400 V 3N ~ 50 Hz

13 A (13 A x 3P)

16 A

1.5 mm² or more

 

 

 

 

(TB02)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Hydro cylinder heater power

230 V ~ 50 Hz

12

A

16 A

1.5 mm² or more

 

 

,

 

 

(TB03)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Hydro - cylinder

 

12

A

1.5 mm² or more

 

 

,

 

 

(TB03)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Wiring specifications (control line)

Description

Line spec

Maximum

Maximum length

 

Connection

current

 

destination

 

 

 

 

3-way valve control

2 line or 3 line

100 mA

12 m

0.75 mm² or more

 

 

,

 

,

 

 

 

 

 

(TB05)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

,

 

,

 

 

 

 

 

 

 

 

 

 

 

Mixing valve control

3 line

100 mA

12 m

0.75 mm² or more

 

or

,

 

,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(TB04)

 

 

 

2-zone thermo sensor

2 line

100 mA

5 m

0.75 mm² or more

 

 

,

 

(TB06)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cylinder thermo sensor

2+GND(shield

100 mA

5 m

0.75 mm² or more

 

 

,

 

(TB06)

 

 

 

wire)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Second remote controller

2 line

50 mA

50 m

0.75 mm² or more

 

 

,

 

(TB07)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Control parts specifications

 

Power

Maximum current

Type

 

 

 

 

Motorized 3-way valve

 

 

Spring return type

AC 230 V

100 mA

Note: 3-wire SPST and SPDT type can be used by changing

(for hot water)

 

 

DIP switch 13-1.

 

 

 

 

 

 

 

Motorized 2-way valve

AC 230 V

100 mA

spring return type (normally open )

(for cooling)

 

 

 

Motorized mixing valve

 

 

60 sec 90º. SPDT type

AC 230 V

100 mA

Note: SPST and 20 to 240 sec type can be used by changing

type 1 (for 2-zone)

 

 

the function code.

 

 

 

 

 

 

 

Output line specifications

Description

Output

Maximum

Max

Maximum

 

 

EN

current

voltage

length

 

 

 

 

 

 

External pump No.1

AC230V

1 A

12 m

 

 

 

 

 

 

 

 

 

 

External boost heater

AC230V

1 A

12 m

Output as required when outdoor air

 

 

temperature is -20°C or less

 

 

 

 

 

 

 

 

Boiler control

Non-voltage

0.5 A

AC230 V

12 m

Output as required when outdoor air

 

 

contacts

1 A

DC24 V

12 m

temperature is -10°C or less

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ALARM Output

Non-voltage

0.5 A

AC230 V

12 m

 

 

 

contacts

1 A

DC24 V

12 m

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor operation

Non-voltage

0.5 A

AC230 V

12 m

 

 

 

output

contacts

1 A

DC24 V

12 m

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

– 23 –

22-EN

Hydro Unit

Installation Manual

Description

Output

Maximum

Max

Maximum

 

current

voltage

length

 

 

 

 

 

 

 

 

 

 

Defrost Output

Non-voltage

0.5 A

AC230 V

12 m

 

contacts

1 A

DC24 V

12 m

 

 

 

 

 

 

 

 

 

 

 

 

Input line specifications

Description

Input

Maximum length

 

 

 

Emergency stop control

Non-voltage

12 m

 

 

 

Cylinder thermostat input

Non-voltage

12 m

 

 

 

Cooling thermostat input

Non-voltage

12 m

 

 

 

Heating thermostat input

Non-voltage

12 m

 

 

 

CAUTION

Earthing arrangements

The Hydro Unit and related equipment must be earthed in accordance with your local and national electrical regulations. It is essential that the equipment is earthed to prevent the electric shock and damage to the equipment.

Electrical connection to hydro unit

Remove the front cover and the electrical box cover from the Hydro Unit.

The Hydro Unit power cable must be sized in accordance with refer to “Electrical supply/cable specifications”.

Connect the Hydro Unit power cable to Terminal 02 as shown below.

Single Phase Units: Live conductor – Terminal L1

Neutral conductor – Terminal L2

Earth conductor – Earth terminal

Three Phase Units: Phase 1 conductor – Terminal L1

Phase 2 conductor – Terminal L2

Phase 3 conductor – Terminal L3

Neutral conductor – Terminal N

Earth conductor – Earth Terminal

Ensure the Hydro Unit power cable is secured using the cable clamp fitted in the electrical box.

Ensure the Hydro Unit power cable connection terminals are tight.

Outdoor unit to hydro unit electrical connection

Fig. 7-22

 

(Hydro/outdoor

 

(Main circuit)

 

connecting wires)

 

Input power

L

1

1

Hydro Unit: Terminal 01

230 V~,

N

2

2

 

50 Hz

 

3

3

Remote controller

 

 

 

Outdoor unit

 

Hydro unit

Earth

 

 

Earth

 

Leakage

 

 

Earth

 

breaker

 

 

 

 

Ensure electrical circuits are isolated before commencing work.

The Outdoor Unit to Hydro Unit interconnecting cable must be sized in accordance with refer to “Electrical supply/ cable specifications”.

Connect the Outdoor Unit to Hydro Unit interconnecting cable as shown in the diagram above.

23-EN

– 24 –

Hydro Unit

Installation Manual

Ensure the Outdoor Unit to Hydro Unit interconnecting cable is secured using the cable clamp fitted in the electrical box.

Ensure the Outdoor Unit to Hydro Unit interconnecting cable connection terminals are tight.

Electrical connection for external booster heater

CAUTION

The maximum current available from the booster heater output is 1 A. Do not connect the booster pump directly to Terminal Block 05 on the Hydro Unit. A separate contactor, supplied locally, must be used to supply the booster heater.

The booster heater can be installed only for room heating and cannot be used for hot water supply.

Install the booster heater downstream of the 3-way valve on the indoor unit side.

The booster heater is an external heater, supplied locally, used to assist the Hydro Unit during low ambient conditions.

The AC230 V 1 A output from the Hydro Unit must only be used to energize an external contactor. (Supplied locally)

The output from the Hydro Unit is only enabled when the outdoor air temperature is less than -20°C.

Ensure the external booster heater is installed and set up in accordance with all Local, National and International regulations.

Connect the external booster heater to the Hydro Unit in accordance with the diagram shown below.

Connect the coil, of the field supplied contactor, to terminals 5 & 6 on Terminal Block 05. The contactor will energize in the event of low ambient conditions.

A separate dedicated electrical supply must be used for the external booster heater. This must be connected through the contacts on the field supplied contactor.

Fig. 7-23

Booster Heater

1

2

3

4

5

6

7

8

Terminal Block 05

9

Electrical connection for external additional pumps

The Hydro Unit has the facility to connect an additional circulating pump, if required, into the heating or cooling system.

There is an output available from the Hydro Unit. AC230 V 1 A (maximum) is available from each output. The output for each additional pump is synchronized with the operation of the main circulating pump inside the Hydro Unit.

• Connect the additional pumps as shown in the diagram below.

EN

Connect external pump 1 to terminals 1 & 2 on Terminal Block 05.

Install external pumps so that their motive power does not affect the internal pump.

Fig. 7-24

Pump

01

1

2

3

4

5

6

7

8

9

Terminal Block 05

 

– 25 –

24-EN

Hydro Unit

Installation Manual

3-way valve (diverter) connection

Required Valve Specification:

Electrical Specification: 230 V; 50 Hz; <100 mA

Valve Diameters: Port A, Port B: Ø 1 1/4"

Return Mechanism: 3 types of 3-way valve (diverter) can be used.

Set the 3-way valve in use with the DIP switch SW13-1 on the Hydro Unit board.

 

 

SW13-1

 

 

 

Type 1

2-wire spring return

OFF

 

 

 

Type 2

3-wire SPST

OFF

 

 

 

Type 3

3-wire SPDT

ON

 

 

 

NOTE

Continuous operation of the valve motor at the fully open position is not recommended.

The 3-way diverter valve is used to select either domestic hot water or space heating.

Connect the 3-way diverter valve to terminals 7, 8 and 9 on Terminal Block 05.

Connect the 3-way diverter valve in accordance with the diagram below:-

Fig. 7-25

Type 1: SPRING RETURN

port “A” to Hot water cylinder

port “AB” to Hydro unit

Hydro Unit

TB 05

7

8

port “A” open

9

Fig. 7-26

Type 2: SPST

 

port “A” to Hot water

 

 

 

 

 

cylinder

 

Hydro Unit

 

 

 

 

 

port “A”

TB 05

port “AB” to

close

 

 

 

 

7

 

 

Hydro unit

open

 

 

 

 

 

 

 

 

 

 

8

 

 

 

 

 

 

 

 

9

port “B” to Room heating or cooling

Fig. 7-27

Type 3: SPDT

port “A” to Hot water cylinder

port “A” close

port “AB” to

Hydro unit

open

Hydro Unit

TB 05

7

8

9

port “B” to Room heating or cooling

port “B” to Room heating or cooling

25-EN

– 26 –

Loading...
+ 60 hidden pages